Finals Module 1 2 Avt 4232
Finals Module 1 2 Avt 4232
Finals Module 1 2 Avt 4232
Me c hanic al
Harnessing
AV T 4232- FINALS
W i r e & Cables
Wire
- formed from a sing le solid conductor or stranded conductors,
contained within the insulation and protective sheath materials.
W i r e & Cables
Cables
1. Two or more separately insulated conductors in the same jacket.
2. Two or more separately insulated conductors are twisted together
(twisted pair).
3. One or more insulated conductors are covered with a metallic braided
shield (shielded cable).
4. A single insulated center conductor with a metallic braided outer
conductor (radio frequency cable).
W i r e & Cables
Cables
W i r e & Cables
Cables
Wire and cable installations cannot be considered (or treated) as 'fit and
forget '. System reliability will be seriously affected by wiring that has not
been correctly installed or maintained.
The following general precautions are recommended when stripping any type
of wire:
1.W hen using any type of wire stripper, hold the wire so that it is
perpendicular to the cutting blades.
Stripping W i r e and Cables
2. Adjust automatic stripping tools carefully; follow the manufacturer’s
instructions to avoid nicking, cutting, or otherwise damaging strands. This is
especially important for aluminum wires and for copper wires smaller than
No.10. Examine stripped wires for damage. Cut off and strip, if the length is
sufficient, or reject and replace any wires with more than the allowable
number of nicked or broken strands listed in the manufacturer’s instructions.
4.Make sure all insulation is removed from the stripped area. Some types of
wire are supplied with a transparent layer of insulation between the
conductor and the primary insulation. If this is present, remove it.
Stripping W i r e and Cables
5.When using hand wire strippers to remove lengths of insulation longer than
3/4 inch, it is easier to accomplish in two or more operations.
This tool is commonly used to strip most types of wire. The following general
procedures describe the steps for stripping wire with a hand stripper.
1.Insert wire into the exact center of the correct cutting slot for wire size
to be stripped. Each slot is marked with wire size.
2.Close handles together as far as they will go.
3. Release handles allow wire holder to return to the open position.
4. Remove stripped wire.
Stripping W i r e and Cables
Crimps and splices
Individual wires and cables can be terminated or connected using crimps
and splices.
Care must be taken when stripping shielded cables; both the inner
conductor and outer screen must be exposed in order to make the
connection.
The outer shield is formed into pigtails and terminated with a crimp, or
ring tongue terminal, see FIG. 3(a).
Crimps and splices
Alternatively, individual wires can be joined with an in-line splice, e.g. if a
system is being modified with additional wiring, see FIG. 3(b). Crimps and
splices are formed over the exposed conductor and insulating material.
The entire crimp or splice termination is then protected mechanically with
a hard plastic case.
Electro-
Me c hanic al
Harnessing
AV T 4232- FINALS 2
E l e c t r i c al Bonds and Grounds
Grounding is the process of electrically connecting conductive objects to
either a conductive structure or some other conductive return path for the
purpose of safely completing either a normal or fault circuit.
Grounding. One of the more important factors in the design and
maintenance of aircraft electrical systems is proper bonding and
grounding. Inadequate bonding or grounding can lead to unreliable
operation of systems, such as EMI, electrostatic discharge damage to
sensitive electronics, personnel shock hazard, or damage from a lightning
strike.
E l e c t r i c al Bonds and Grounds
Types of grounding
– AC returns
– DC returns
– Others
Factors to consider when grounding
M ixing return currents.
If wires carrying return currents from different types of sources, such as
signals or DC and AC generators, are connected to the same ground point
or have a common connection in the return paths, an interaction of the
currents will occur. This interaction may not be a problem, or it could be a
major non-repeatable anomaly.
E l e c t r i c al Bonds and Grounds
To minimize the interaction between various return currents, different
types of grounds should be identified and used. As a minimum, the design
should use three ground types: (1) AC returns, (2) DC returns, and (3) all
others.
Purpose. The proper identification of EWIS components with their circuits and
voltages is necessary to provide safety of operation, safety to maintenance
personnel, and ease of maintenance.
EWIS IDENTIFICATION
Only wires complying with the standards of the aeronautical authorities and
the aircraft manufacturer may be installed in aircraft. To ensure that this
demand is met, the manufacturers of the wires label their wires with
corresponding part numbers. These part numbers follow the rules for
identification by the standards organization or the aircraft manufacturer.
The numbers are printed in light or dark green. Exceptions are red, black, or
dark green wires: they are labeled with white numbers.
The aircraft manufacturers furthermore label the wires with a number− and/or
letter code which describes the function of the wire in the aircraft. This is
usually a black imprint.
EWIS IDENTIFICATION
EWIS IDENTIFICATION
Common manufacturer marking process. Each wire and cable should be marked
with a part number. It is common practice for wire manufacturers to follow the
wire material part number with the five-digit/letter C.A.G.E. code identifying
the wire manufacturer. Using this code, existing installed wire that needs
replacement can be identified as to its performance capabilities. This helps to
prevent the inadvertent use of lower performance and unsuitable replacement
wire.
NOTE: Special care should be taken when hot stamping wire. Service history
has shown problems associated with hot stamping due to insulation damage
caused during the process.
EWIS IDENTIFICATION
The method of identification should not impair the characteristics of the EWIS.
AIRBUS
EWIS IDENTIFICATION
- Markings should be legible in size, type, and color at 15-inch maximum
intervals along the wire (directly on wire or indirect [sleeve/tag])
Connectors consist of a receptacle and plug. They are required for a simple and
the safe disconnect of electrical connections during maintenance.
Connectors have pins and sockets which can both (depending on the type of
plug) be housed either in the socket or in the plug.
There is a general rule for determining the socket side: sockets shall always be
installed on the live part of the connector because the sockets are scoop−proof
and so unwanted short circuits can be prevented. A distinction is made
between circular and rectangular connectors. Rectangular connectors are
preferably used in equipment racks and panels; circular plug connections can
be used in areas with increased environmental influences.
WHY USE CONNECTORS?
For ease of assembly and maintenance, connectors using crimped contacts
are generally chosen for all applications except those requiring a hermetic
seal.
A replacement connector of the same basic type and design as the
connector it replaces should be used.
With a crimp type connector for any electrical connection, the proper
insertion, or extraction tool should be used to install or remove wires from
such a connector. Refer to manufacturer or aircraft instruction manual.
After the connector is disconnected, inspect it for loose soldered
connections to prevent unintentional grounding
CONNECTORS
INSTRUCTIONS FOR CONTINUED AIRWORTHINESS
14 CFR 25.1729 requires applicants to submit Instructions for Continued
Airworthiness, otherwise known as the maintenance requirements, for the
proposed EWIS installation as part of the compliance data package.
Historically, EWIS has been thought of as “fit and forget” and typically has not
been properly addressed in the ICA data package submitted to the FAA for
approval.
EZAP was used to develop ICA to prevent the possibility of smoke and fire by
– M inimizing accumulation of combustibles on and around EW IS
– Detecting EW IS degradations
INSTRUCTIONS FOR CONTINUED AIRWORTHINESS
3 EWIS Inspection Types
1. A. General Visual Inspection (GVI)
A visual examination of an interior or exterior area, installation, or assembly to
detect obvious damage, failure, or irregularity. This level of inspection is made
from within touching distance unless otherwise specified.
For General Visual Inspection, a mirror may be necessary to enhance visual
access to all exposed surfaces in the inspection area. This level of inspection is
made under normally available lighting conditions such as daylight, hangar
lighting, flashlight, or droplight and may require the removal or opening of
access panels or doors. Stands, ladders, or platforms may be required to gain
proximity to the area being checked.
INSTRUCTIONS FOR CONTINUED AIRWORTHINESS
1. B. Stand-Alone GVI
A general visual inspection is not performed as part of a zonal inspection. Even
in cases where the interval coincides with the zonal inspection, the stand-alone
GVI remains an independent step on the work card.