Electropneumatic positioners

SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF

Overview

SIPART PS2 electropneumatic positioner

Benefits
SIPART PS2 positioners are characterized by significant advantages:
Simple installation and automatic commissioning (self-adjustment of zero and span)
Simple operation with
- Local operation and configuration of the device using three
input keys and a user-friendly two-line LCD
- Programming through SIMATIC PDM;
very high-quality control thanks to an online adaptation procedure
Negligible air consumption in stationary operation
"Tight shut-off" function (ensures maximum positioning pressure on the valve seat)
Numerous functions can be activated by simple configuring
(e.g. characteristics and limits)
Extensive diagnosis functions for valve and actuator
Only one device version for linear and part-turn actuators
Few moving parts, hence Insensitive to vibrations
External non-contacting position sensor as option for extreme
ambient conditions

Application
The SIPART PS2 positioner is used, for example, in the following
branches:
Chemical industry
Power stations
Paper and glass
Food and pharmaceuticals
Offshore plants

SIPART PS2 EEx d electropneumatic positioner in flameproof casing

The SIPART PS2 positioner is available:


For single-action actuators: in plastic, stainless steel or aluminium casings
For double-action actuators: in plastic casings and stainless
steel casings
For non-hazardous applications
For hazardous applications in the designs
- as intrinsically-safe device (EEx ia/ib) or
- in flameproof casing (EEx d) or
- in Ex n design (non sparking)
and in the versions:
With 0/4 ... 20 mA control communication through HART signal (as option)
With PROFIBUS PA communications interface (EEx ia)
With Foundation Fieldbus (FF) communications interface.
Explosion-proof versions
The basic version of the device is available in an intrinsicallysafe design with degree of protection EEx ia/ib or in a non-intrinsically-safe design for zone 2 (see Technical data for intrinsically-safe versions).

SIPART PS2 or SIPART PS2 in stainless steel casing

The SIPART PS2 electropneumatic positioner is used to control


the final control element of pneumatic linear or part-turn actuators. The electropneumatic positioner moves the actuator to a
valve position corresponding to the setpoint. Additional function
inputs can be used to block the valve or to set a safety position.
A binary input is present as standard in the basic device for this
purpose.

A non-intrinsically-safe application is permissible in zone 1 for


the SIPART PS2 EEx d flameproof version (see Technical data).
It is then permissible to use all option modules (except external
actuator travel detection systems and NCS).
Stainless steel casing for extreme ambient conditions
The SIPART PS2 is available in a stainless steel casing for use in
particularly aggressive environments (e.g. offshore operation,
chlorine plants etc.). The device functions are the same as with
the basic device.

Siemens FI 01 2005

6/3

Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF

Design
The SIPART PS2 positioner is a digital field device with a highlyintegrated microcontroller.
The positioner consists of the following components:
Casing and cover
PCB with corresponding electronics with or without communication through HART
or with electronics for communication in accordance with
- PROFIBUS PA specification, IEC 61158-2; bus-supplied
device, or
- Foundation Fieldbus (FF) specification, IEC 61158-2,
bus-supplied device
Actuator travel detection system
Terminal housing with screw terminals
Pneumatic valve manifold with piezoelectric valve precontrol.

The use of linear potentiometers is recommendable for very


small actuators with a short valve travel since, on the one hand,
the space required by the linear potentiometer is very small and,
on the other, the transmission characteristic is optimum for a
small travel.

The valve manifold is located in the housing, the pneumatic connections for the inlet air and the positioning pressure on the righthand side. A pressure gauge block and/or a safety solenoid
valve can be connected there as options. The circuit board container in the casing provides slots for separately ordered boards
with the following functions:
I y module
Position feedback as a two-wire signal 4 to 20 mA.

Separate connection of actuator travel detection system and controller


unit

Non-contacting position sensor (NCS)

Alarm module (3 outputs, 1 input)


Signaling of two limits of the travel or angle by binary signals.
The two limits can be set independently as maximum or minimum values.
Output of an alarm if the setpoint position of the final control
element is not reached in automatic mode or if a device fault
occurs.
Second binary input for alarm signals of for triggering safety
reactions or for blocking/signaling function or safety position.
All signals in the ly and alarm modules as well as the SIA module
are electrically isolated from one another and from the basic unit.
The outputs indicate self-signaling faults.
Limit signaling through slot-type initiators (SIA module)
Two limits can be signaled redundantly as NAMUR signals
(DIN19234) by slot-type initiators using an easy-to-fit module.
The module additionally contains an alarm output (see Alarm
module).
Stainless steel casing for extreme ambient conditions
The SIPART PS2 is available in a stainless steel casing for use in
particularly aggressive environments (e.g. offshore operation,
chlorine plants etc.). The device functions are the same as with
the basic device.
Separate mounting of actuator travel detection system and
controller unit
The actuator travel detection system and controller unit can be
connected separately for all casing versions of the SIPART PS2
(except flame-proof design). Measurement of the travel or angle
is carried out directly on the actuator. The controller unit can then
be fitted a certain distance away, e.g. on a mounting pipe or similar, and is connected to the travel detection system by an electric cable and to the actuator by one or two pneumatic lines.
Such a split design is frequently advantageous if the ambient
conditions at the fitting exceed the specified values for the positioner.
The following can be used for measuring the travel or angle:
NCS sensor
External position detection system C73451-A430-D87
A commercially available potentiometer (10 k resistance)

6/4

Siemens FI 01 2005

Non-contacting position sensor (NCS) for part-turn actuators (left) and for
linear actuators (right)

The actuator travel detection unit can also consist of a non-contacting position sensor instead of a potentiometer. All coupling
elements are omitted such as coupling wheel and driver pin with
part-turn actuators or lever and pick-up bracket with linear actuators.
This results in:
Even greater resistance to vibration and shock
No wear of sensor
Problem-free mounting on very small actuators
Negligible hysteresis with very small travels.
The sensor does not require an additional power supply, i.e.
SIPART PS2 can be operated in a 2-wire system. The NCS (Non
Contacting Position Sensor) consists of a potted sensor housing
which must be mounted permanently and a magnet which is
mounted on the spindle or lever shaft of linear actuators or on the
shaft butt of part-turn actuators.
The installation of a special EMC filter module in the positioner
(controller unit) is necessary in order to provide and guarantee a
connection level with EMC according to EN61326/A1 and
NAMUR NE21 when using external sensors (see Ordering data
for "EMC filter module").

Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF

Function
The SIPART PS2 electropneumatic positioner works in a completely different way to normal positioners.
Mode of operation
Comparison of the setpoint and the actual value takes place
electronically in a microcontroller. If the microcontroller detects a
deviation, it uses a 5-way switch procedure to control the piezoelectric valves, which in turn regulate the flow of air into the actuating chambers.
The microprocessor then outputs an electric control command to
the piezoelectric valve in accordance with the magnitude and direction of the deviation (deviation between setpoint w and control output x). The piezoelectric valve converts the command into
a pneumatic positional increment.
The positioner outputs a continuous signal in the area where
there is a large control deviation (high-speed zone); in areas of
moderate control deviation (slow-speed zone) it outputs a sequence of pulses. No positioning signals are output in the case
of a small control deviation (adaptive or variable dead zone).
The SIPART PS2 positioner is fitted to the linear or part-turn actuator using an appropriate mounting assembly.
The linear or rotary motion of the actuator is detected by the
mounting assembly and transferred through a rigid connection
to a potentiometer made of a wear-resistant plastic conductive
material.
The angular error of the pick-up in cases where the assembly is
mounted on a linear actuator is corrected automatically.
When connected in a 2-wire system, the SIPART PS2 draws its
power exclusively from the 4 to 20 mA setpoint signal. The electric power is connected through the 2-wire bus signal also with
PROFIBUS operation (SIPART PS2 PA). The same applies for the
Foundation Fieldbus version.
Pneumatic valve manifold with piezoelectric valve precontrol
The piezoelectric valve can release very short control pulses.
A high positioning accuracy can then be achieved. The pilot
element is a piezoelectric bending converter which switches the
pneumatic main control unit. The valve manifold is characterized
by an extremely long service life.
Local operation
Local operation is performed with the built-in LCD and the three
input keys. Switching between the operating levels Automatic,
Manual and Configuring is possible with the press of a button.
In Manual mode the drive can move over the entire range.
Operation and monitoring with the
SIMATIC PDM communications program
The SIMATIC PDM communications software permits easy remote operation and monitoring using a PC or laptop. The positioner can also be configured using this program. Parameters
which provide important information for maintenance and fault
diagnosis of the complete unit can additionally be determined
using process data and comparison data.
The SIMATIC PDM program is available for communication
through the HART interface and also for the PROFIBUS PA coupling.

Automatic commissioning
With a simple configuration menu the SIPART PS2 can be quickly
adapted to the fitting and adjusted by means of an automatic
startup function.
During initialization, the microcontroller determines the zero
point, full-scale value, the direction of action and the positioning
speed of the actuator. From this data it establishes the minimum
pulse time and the dead zone, thus optimizing the control.
Low air consumption
A hallmark of the SIPART PS2 is its own extremely low consumption of air. Normal air losses on conventional positioners are very
costly. Thanks to the use of modern piezoelectric technology, the
SIPART PS2 consumes air only when it is needed, which means
that it pays for itself within a very short time
Extensive diagnosis functions
The SIPART PS2 (6DR5...) has various monitoring functions with
which changes on the actuator and valve can be detected and
signaled if applicable when a selectable limit has been exceeded. This information may be important for diagnosis of the
actuator or valve. The measured values to be determined and
monitored, some of whose limits can be adjusted, include:
Travel integral
Number of changes in direction
Alarm counter
Self-adjusting dead zone
Valve limit position (e.g. wear of valve seat)
Operating hours (also according to temperature and positioning ranges) as well as min./max. temperature
Operating cycles of piezoelectric valves
Valve positioning time
Actuator leakages
Configuring
The following settings, for example, can be configured in configuring mode as required with the SIPART PS2 positioner:
Input current range 0 to 20 mA or 4 to 20 mA
Rising or falling characteristic at the setpoint input
Positioning speed limit (setpoint ramp)
Split-range operation; adjustable start-of-scale and full-scale
values
Response threshold (dead zone); self-adjusting or fixed
Direction of action; rising or falling output pressure with rising
setpoint
Limits (start-of-scale and full-scale values) of positioning
range
Limits (alarms) of the final control element position; minimum
and maximum values
Automatic "tight shut-off" (with adjustable response threshold)
The travel can be corrected in accordance with the valve characteristic.
Function of binary inputs
Function of alarm output etc.
Configuring the SIPART PS2 variants is identical in the main
points.

When operating the SIPART PS2 through the HART interface,


the connection is made directly to the 2-wire cable to the
SIPART PS2 positioner through a HART modem that can be connected to the PC COM interface. The signals needed for communication in conformity with the HART protocol are superimposed on the current signal in accordance with the Frequency
Shift Keying (FSK) method.

Siemens FI 01 2005

6/5

Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF
1

HART

2
BE1

3V
_

I W+

Inlet air
pZ
Exhaust

+24 V

p1

+5 V
W

I Wy

A
+U

p1
p2

Microcontroller

p2

Exhaust

W
x

x
U
6

I
5

BE2

A1

A2

I
9

8
p2
A1

1
2
3
4
5
6

A2

Motherboard with microcontroller and input circuit


Control panel with LCD and pushbuttons
Piezoelectric valve unit, always present
Valve unit, present as accessory in double-action positioner
Iy module for SIPART PS2 controller
Alarm module for 3 alarm outputs and one binay input

SIPART PS2, electropneumatic positioner, function diagram

6/6

Siemens FI 01 2005

p1

Travel

7 SIA module (slot initiator alarm module)


8 Spring loaded pneumatic actuator (single-action)
9 Springless pneumatic actuator (double-action)
Note:
Alarm module (6) and SIA module (7) can only be inserted
as alternatives.

p1

Travel

Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF

Technical specifications

Vibration resistance

SIPART PS2 (all versions)


General data
Travel range (linear actuators)

3 ... 130 mm (0.12 ... 5.12 inch)


(angle of feedback shaft 16 ... 90)

Angle of rotation (part-turn actuators)

30 ... 100

Installation
On linear actuators

On part-turn actuators

Using attachment set


6DR4004-8V and where necessary with an additional lever arm
6DR4004-8L on actuators
according to IEC 534-6 (NAMUR)
with ribs, bars or flat face
Using attachment set
6DR4004-8D on actuators with
mounting plane according to
VDI/VDE 3845 and DIN 3337:
The required mounting console
has to be provided on the actuator side; shaft with groove and
female thread M6

Controller
Five-point switch
Dead zone
- dEbA = Auto
- dEbA = 0.1 ... 10%

Self-adjusting
Self-adjusting or can be set as
fixed value
Self-adjusting or can be set as
fixed value

A/D converter
Scan time
Resolution
Transmission error
Temperature effect

10 ms
0.05%
0.2%
0.1%/10 K ( 0.1%/18 F)

Cycle time
20 mA/HART device
PA device
FF device

20 ms
60 ms
60 ms (min. loop time)

Binary input BE1 (terminals 9/10;


electrically connected to the basic
device)

Suitable only for floating contact;


max. contact load < 5 mA with
3V

Degree of protection

IP65 to EN 60 529/NEMA 4x

Mounting position

Any; pneumatic connections and


exhaust opening not facing up in
wet environment

CE marking

Conformity as regards EMC


Directive 89/336 EC in accordance with the following standards

EMC requirements

EN 61326/A1 Appendix A.1 and


NAMUR NE21 August 98

Material
Housing
- 6DR5..0-... (plastic)
- 6DR5..1-... (metal)
- 6DR5..2-... (stainless steel)
- 6DR5..5-... (metal, pressureproof)
Pressure gauge block

Glass-fiber-reinforced Macrolon
GK AISi12
Austenitic stainless steel mat.
No. 1.4581
GK AISi12
Aluminium AIMgSi, coated

Harmonic oscillations
(sine-wave) according to
DIN EN 60062-2-6/05.96

3.5 mm (0.14 inch), 2 ... 27 Hz


3 cycles/axis

Bumping (half-sine)
to DIN EN 60068-2-29/03.95

150 m/s (492 ft/s), 6 ms,


1000 shocks/axis

Noise (digitally controlled)


to DIN EN 60068-2-64/08.95

10 ... 200 Hz; 1 (m/s)/Hz


(3.28 (ft/s)/Hz)

98.1 m/s (321.84 ft/s),


27 ... 300 Hz, 3 cycles/axis

200 ... 500 Hz; 0.3 (m/s)/Hz


(0.98 (ft/s)/Hz)
4 hours/axis
Recommended continuous duty
range of the complete fitting

30 m/s ( 98.4 ft/s) without resonance sharpness

Weight, basic device


Plastic casing
Metal casing, aluminium
Metal casing, stainless steel
Metal casing EEx d version

Approx. 0.9 kg (0.90 kg)


Approx. 1.3 kg (1.30 kg)
Approx. 3.9 kg (3.90 kg)
Approx. 5.2 kg (11.46 lb)

Dimensions

See Dimension drawing

Climate class to DIN EN 60721-3-4 To IEC 721


Storage 1)

1K5, but -40 ... +80 C


(1K5, but -40 ... +176 F)

Transport 1)

2K4, but -40 ... +80 C


(2K4, but -40 ... +176 F)

Operation 2)

4K3, but -30 ... +80 C


(4K3, but -22 ... +176 F)

Certificate and approvals


Classification according to pressure For gases of fluid group 1, comequipment
plies with requirements of
directive (DRGL 97/23/EC)
article 3, paragraph 3 (sound
engineering practice SEP)
Pneumatic data
Power supply (inlet air)
Pressure

1.4 ... 7 bar (20.3 ... 101.5 psi):


Sufficiently greater than max.
drive pressure (actuating pressure)

Air quality to ISO 8573-1


Solid particle size and density

Class 2

Pressure dew point

Class 2 (min. 20 K (36 F) below


ambient temperature)

Oil content

Class 2

Unthrottled flow
Inlet air valve 3)
- 2 bar (29 psi)
- 4 bar (58 psi)
- 6 bar (87 psi)

4.1 Nm/h (18.1 USgpm)


7.1 Nm/h (31.3 USgpm)
9.8 Nm/h (43.1 USgpm)

Outlet air valve 3)


- 2 bar (29 psi)
- 4 bar (58 psi)
- 6 bar (87 psi)

8.2 Nm/h (36.1 USgpm)


13.7 Nm/h (60.3 USgpm)
19.2 Nm/h (84.5 USgpm)

Valve leakage

< 610-4 Nm/h (0.0026 USgpm)

Throttle ratio

Adjustable up to : 1

Power consumption in the controlled state

< 3.610-2 Nm/h (0.158 USgpm)

Types of actuators
In plastic casing
In aluminium casing
In flameproof casing
In stainless steel casing

Single-action and double-action


Single-action
Single-action and double-action
Single-action and double-action

1) During commissioning at 0 C ( 32 F) make sure that the valves are


flushed long enough with the dry medium.
2) At -10 C the display refresh rate of the LCD is limited. Only T4 is permissible when using Iy module.
3) With EEx d version (6DR5..5-...) the values are reduced by approx. 20%

Siemens FI 01 2005

6/7

Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF

Technical specifications
SIPART PS2

Basic device
without Ex protection

Basic device
with EEx-d protection
(flameproof casing)

Basic device
Basic device
with EEx ia/ib protection with EEx n protection

Explosion protection to
EN 50014, EN 50020 and EN 50021

Without

EEx d
II 2 G EEx d II C T6

EEx ia/ib
II 2 G EEx ia/ib II C T6

EEx n
II 3 G EEx nA L [L] II C T6

Zone 1

Zone 2

Mounting location

Zone 1

-30 ... +80 C


Permissible ambient temperature for
(-22 ... +176 F)
operation
(for basic devices with EEX ia/ib and
EEx n protection the following applies:
At -10 C (+14 F) the display refresh
rate of the LCD is limited. Only T4 is
permissible when using Iy module.)

T4: -30 ... +80 C (-22 ... +176 F)


T5: -30 ... +65 C (-22 ... +149 F)
T6: -30 ... +50 C (-22 ... +122 F)

Electrical data
Input
2-wire connection (terminals 6/8)
Rated signal range

4 ... 20 mA

4 ... 20 mA

4 ... 20 mA

4 ... 20 mA

Current to maintain the power supply

3.6 mA

3.6 mA

3.6 mA

3.6 mA

- Typical

6.36 V (corresponds to
318 )

6.36 V (corresponds to
318 )

7.8 V (corresponds to
390 )

7.8 V (corresponds to
390 )

- Max.

6.48 V (corresponds to
324 )

6.48 V (corresponds to
324 )

8.3 V (corresponds to
415 )

8.3 V (corresponds to
415 )

- Typical

7.9 V (corresponds to
395 )

- Max.

8.4 V (corresponds to
420 )

- Typical

6.6 V (corresponds to
330 )

6.6 V (corresponds to
330 )

- Max.

6.72 V (corresponds to
336 )

6.72 V (corresponds to
336 )

- Typical

8.4 V (corresponds to
420 )

8.4 V (corresponds to
420 )

8.4 V (corresponds to
420 )

- Max.

8.8 V (corresponds to
440 )

8.8 V (corresponds to
440 )

8.8 V (corresponds to
440 )

Required load voltage


UB (corresponds to at 20 mA)
Without HART (6DR50..)

Without HART (6DR53..)

With HART (6DR51..)

With HART (6DR52..)

Static destruction limit

40 mA

Internal capacitance Ci
Without HART

22 nF

With HART

7 nF

0.12 mH

Internal inductance Li
Without HART
With HART

0.24 mH

For connection to power circuits with

intrinsically safe
Uo 30 V DC
Ik 100 mA
P1W

Ui 30 V DC
Ii 100 mA

6/8

Siemens FI 01 2005

Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF
SIPART PS2

Basic device
without Ex protection

Basic device
with EEx-d protection
(flameproof casing)

Basic device
Basic device
with EEx ia/ib protection with EEx n protection

18 ... 35 V DC

18 ... 30 V DC

3-/4-wire device (terminals 2/4


and 6/8) (6DR52.. and 6DR53..)
Power supply UH

18 ... 35 V DC

Current consumption IH

(UH - 7.5 V)/2.4 kW [mA] (UH - 7.5 V)/2.4 kW [mA] (UH - 7.5 V)/2.4 kW [mA] (UH - 7.5 V)/2.4 kW [mA]

18 ... 30 V DC

Internal capacitance Ci

Internal inductance Li

For connection to power circuits with

22 nF

0.12 mH

intrinsically safe
Uo 30 V DC
Ik 100 mA
P1W

Ui 30 V DC
Ii 100 mA

Current input IW
Rated signal range

4 ... 20 mA

4 ... 20 mA

4 ... 20 mA

4 ... 20 mA

Load voltage at 20 mA

0.2 V (corresponds to
10 )

0.2 V (corresponds to
10 )

1 V (corresponds to
50 )

1 V (corresponds to
50 )

Internal capacitance Ci

22 nF

Internal inductance (Li)

0.12 mH

For connection to power circuits with

intrinsically safe
Uo 30 V DC
Ik 100 mA
P1W

Ui 30 V DC
Ii 100 mA

Electrical isolation

between UH and IW

between UH and IW

between UH and IW
(2 intrinsically safe circuits)

between UH and IW

Test voltage

840 V DC (1 s) or 700 V DC (50 Hz, 1 s)

Connections
Electric

Screw terminals 2.5


AWG28-12
Cable gland M20 or
NPT

Screw terminals 2.5


AWG28-12
EEx d certified cable
gland M20x1.5, NPT
or M25x1.5

Pneumatic

Female thread G1/4 DIN 45141 or 18 NPT

Screw terminals 2.5


AWG28-12
Cable gland M20 or
NPT

Screw terminals 2.5


AWG28-12
Cable gland M20 or
NPT

External position sensor (potentiometer or NCS; as option)


Uo

<5V

<5V

Io

< 75 mA

< 75 mA

Is

<160 mA

<160 mA

Po

<120 mW

<120 mW

Maximum permissible external capaci-


tance Co

< 1 F

< 1 F

Maximum permissible external inductance Lo

< 1 mH

< 1 mH

Siemens FI 01 2005

6/9

Electropneumatic positioners
SIPART PS2
SIPART PS2 PA

Technical specifications
SIPART PS2 PA

Basic device
without Ex protection

Basic device
with EEx-d protection
(flameproof casing)

Basic device
Basic device
with EEx ia/ib protection with EEx n protection

Explosion protection to
Without
EN 50.014, EN 50.020 and EN 50.021

EEx d
EEx ia/ib
II 2 G EEx d II C T4/T5/T6 II 2 G EEx ia/ib II C T6

EEx n
II 3 G EEx nA L [L] II C T6

Mounting location

Zone 1 or zone 2

Zone 2

-30 ... +80 C


Permissible ambient temperature for
(-22 ... +176 F)
operation
(for basic devices with Ex protection
the following applies: At -10 C
(+14 F) the display refresh rate of the
LCD is limited. Only T4 is permissible
when using Iy module.)

Zone 1

T4: -30 ... +80 C (-22 ... +176 F)


T5: -30 ... +65 C (-22 ... +149 F)
T6: -30 ... +50 C (-22 ... +122 F)

Electrical data
Input
Power supply (terminals 6/7)

Bus-supplied

Bus voltage

9 ... 32 V

Bus connection with FISCO supply


unit,
ia or ib group IIC or IIB

9 ... 32 V

9 ... 24 V

9 ... 32 V

17.5 V

- Max. supply voltage Uo

- Max. short-circuit current Io

- Max. power Po

Bus connection with barrier,


ia or ib group IIC or IIB

380 mA

5.32 W

- Max. supply voltage (Uo)

24 V

- Max. short-circuit current (Io)

250 mA

- Max. power Po

1.2 W

Current consumption

10.5 mA 10%

10.5 mA 10%

10.5 mA 10%

10.5 mA 10%

Fault current

0 mA

0 mA

0 mA

0 mA

Effective internal inductance

Li 8 mH

Effective internal capacitance

Negligible

Connection

Certified intrinsically safe


circuit

Safety shutdown can be activated with


coding bridge (terminals 81/82; electrically isolated from the basic device)
Input resistance

> 20 k

> 20 k

> 20 k

> 20 k

Signal status "0" (shutdown active)

0 ... 4.5 V or unused

0 ... 4.5 V or unused

0 ... 4.5 V or unused

0 ... 4.5 V or unused

Signal status "1" (shutdown not active)

13 ... 30 V

13 ... 30 V

13 ... 30 V

13 ... 30 V

Effective Internal capacitance Ci

Negligible

Effective internal inductance Li

Negligible

For connection to power supply with

Intrinsically safe

- Max. supply voltage Ui

< 30 V

< 30 V

- Max. short-circuit current Ii

<100 mA

<100 mA

- Maximum power Pi

<1W

Electrical isolation

Between basic device


and the input for safety
shutdown, as well as the
outputs of the option
modules

Between basic device


and the input for safety
shutdown, as well as the
outputs of the option
modules

The basic device and the


input to the safety shutdown, as well as the outputs of the option
modules, are individual,
intrinsically-safe circuits

Between basic device


and the input for safety
shutdown, as well as the
outputs of the option
modules

Test voltage

840 V DC, 1 s

840 V DC, 1 s

840 V DC, 1 s

840 V DC, 1 s

6/10

Siemens FI 01 2005

Electropneumatic positioners
SIPART PS2
SIPART PS2 PA
SIPART PS2 PA

Basic device
without Ex protection

Basic device
with EEx-d protection
(flameproof casing)

Basic device
Basic device
with EEx ia/ib protection with EEx n protection

Communication

Layers 1 and +2 according to PROFIBUS PA, transmission technique according to IEC 1158-2;
slave function; layer 7 (protocol layer) according to PROFIBUS DP,
EN 50170 standard with the extended PROFIBUS functions
(all data acyclic, manipulated variable, feedbacks and status also cyclic)

C2 connections

Four connections to master class 2 are supported,


automatic connection setup 60 s after break in communication;

Device profile

PROFIBUS PA profile B, version 3.0, more than 150 objects

Response time to master message

Typical 10 ms

Device address

126 (when delivered)

PC parameterizing software

SIMATIC PDM, for Windows 95 or Windows NT;


supports all device objects. The software is not included in the scope of delivery

Connections
Electric

Screw terminals 2.5


AWG28-12
Cable gland M20 or
1/2 NPT

Screw terminals 2.5


AWG28-12
EEx d certified cable
gland M20x1.5, 1/2 NPT
or M25x1.5

Screw terminals 2.5


AWG28-12
Cable gland M20 or
1/2 NPT

Screw terminals 2.5


AWG28-12
Cable gland M20 or
1/2 NPT

Pneumatic

Female thread G
DIN 45141 ( -18 NPT)

Female thread G
DIN 45141 ( -18 NPT)

Female thread G
DIN 45141 ( -18 NPT)

Female thread G
DIN 45141 ( -18 NPT)

Uo

<5V

<5V

Io

<75 mA

<75 mA

Is

<160 mA

<160 mA

Po

<120 mW

<120 mW

Maximum permissible external capacitance Co

< 1 F

< 1 F

Maximum permissible external inductance Lo

< 1 mH

< 1 mH

External position sensor


(potentiometer or NCS; as option)

Siemens FI 01 2005

6/11

Electropneumatic positioners
SIPART PS2
SIPART PS2 FF

Technical specifications
SIPART PS2 FF

Basic device
without Ex protection

Basic device
with EEx d protection,
flameproof casing
(available soon)

Basic device
with EEx ia/ib protection

Explosion protection to
EN 50014, EN 50020 and EN 50021

Without

EEx d
II 2 G EEx d II C T4/T5/T6

EEx ia/ib
II 2 G EEx ia/ib II C T6

Zone 1 or zone 2

Zone 1

Mounting location
Permissible ambient temperature for operation -30 ... +80 C (-22 ... +176 F)
(for basic devices with Ex protection the following applies: At -10 C (+14 F) the display refresh rate of the LCD is limited. Only
T4 is permissible when using Iy module.)

T4: -30 ... +80 C (-22 ... +176 F)


T5: -30 ... +65 C (-22 ... +149 F)
T6: -30 ... +50 C (-22 ... +122 F)

Electrical data
Input
Power supply (terminals 6/7)

Bus-supplied

Bus-supplied

Bus-supplied

Bus voltage

9 ... 32 V

9 ... 32 V

9 ... 24 V

Bus connection with FISCO supply unit, ia or


ib group IIC or IIB
- Max. supply voltage Uo

17.5 V

- Max. short-circuit current Io

380 mA

- Max. power Po

5.32 W

Bus connection with barrier,


ia or ib group IIC or IIB

- Max. supply voltage Uo

24 V

- Max. short-circuit current Io

250 mA

- Max. power Po

1.2 W

Electrical data
Current consumption

10.5 mA 10%

10.5 mA 10%

10.5 mA 10%

Fault current

0 mA

0 mA

0 mA

Effective internal inductance

Li 8 mH

Effective internal capacitance

Negligible

Connection

Certified intrinsically safe circuit

Input resistance

> 20 k

> 20 k

> 20 k

Signal status "0" (shutdown active)

0 ... 4.5 V or unused

0 ... 4.5 V or unused

0 ... 4.5 V or unused

Signal status "1" (shutdown not active)

13 ... 30 V

13 ... 30 V

13 ... 30 V

Effective Internal capacitance Ci

Negligible

Safety shutdown can be activated with coding bridge (terminals 81/82; electrically isolated from the basic device)

Effective internal inductance Li

Negligible

For connection to power supply with

Intrinsically safe

- Max. supply voltage Ui

< 30 V

- Maximum short-circuit current Ii

<100 mA

- Maximum power Pi

<1W

Electrical isolation

Between basic device and the


input for safety shutdown, as
well as the outputs of the option
modules

Between basic device and the


input for safety shutdown, as
well as the outputs of the option
modules

The basic device and the input


to the safety shutdown, as well
as the outputs of the option
modules, are individual, intrinsically-safe circuits

Test voltage

840 V DC, 1 s

840 V DC, 1 s

840 V DC, 1 s

6/12

Siemens FI 01 2005

Electropneumatic positioners
SIPART PS2
SIPART PS2 FF
SIPART PS2 FF

Basic device
without Ex protection

Basic device
with EEx d protection,
flameproof casing
(available soon)

Basic device
with EEx ia/ib protection

Communication
Communications group and class

According to technical specification of the Fieldbus Foundation for H1 communication

Function blocks

Group 3, Class 31PS (publisher, subscriber)


1 resource block (RB2)
1 analog output function block (AO)
1 PID function block (PID)
1 transducer block (standard advanced positioner valve)

Execution times of the blocks

AO: 50 ms
PID: 80 ms

Physical layer profile

123, 511

FF registration

Tested with ITK 4.51 or higher

Connections
Electric

Screw terminals 2.5 AWG28-12


Cable gland M20 or NPT

Screw terminals 2.5 AWG28-12


EEx d certified cable gland
M20x1.5, NPT or M25x1.5

Pneumatic

Female thread G1/4 DIN 45 141 ( -18 NPT)

Screw terminals 2.5 AWG28-12


Cable gland M20 or NPT

External position sensor


(potentiometer or NCS; as option)
Uo

<5V

Io

<75 mA

Is

<160 mA

Po

<120 mW

Maximum permissible external capacitance Co

< 1 F

Maximum permissible external inductance Lo

< 1 mH

Siemens FI 01 2005

6/13

Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF

Technical specifications
Option modules

Without Ex protection

With Ex protection

Ex protection to EN 50 014 and EN 50 020

II 2G EEx ia/ib II C T4/T5/T6

II 3G EEx nA L [L] II C T6

Mounting location

Zone 1

Zone 2

Permissible ambient temperature for opera- -30 ... +80 C (-22 ... +176 F)
tion
(For devices with Ex protection: Only in conjunction with the basic device 6DR5... -.E....
Only T4 is permissible when using Iy module)

T4: -30 ... +80 C (T4: -22 ... +176 F)


T5: -30 ... +65 C (-22 ... +149 F)
T6: -30 ... +50 C (-22 ... +122 F)

Electrical data
Alarm module

6DR4004-8A (without Ex protec- 6DR4004-6A (with Ex protection) 6DR4004-6A (with Ex protection)


tion)

Binary alarm outputs A1, A2 and alarm output


Signal status High (not responded)
Signal status Low* (responded)
(* Low is also the status when the basic
device is faulty or has not electric power supply)

Active, R = 1 k, +3/-1%*
Disabled, IR < 60 A

2.1 mA
1.2 mA

(* When used in the flameproof (Switching threshold with supcasing the current consumption ply to DIN 19234: UH = 8.2 V,
is limited to 10 mA per output.) Ri = 1k)

2.1 mA
1.2 mA
(Switching threshold with supply to DIN 19234: UH = 8.2 V,
Ri = 1k)

Internal capacitance Ci

5.2 nF

Internal inductance Li

Negligible

Power supply UH

35 V

Connection to power circuits with

intrinsically safe switching


amplifier DIN 19234
Uo 15.5 V DC
Ik 25 mA, P 64 mW

Ui 15.5 V DC

Electrically connected to the basic device


- Signal status 0
- Signal status 1
- Contact load

Floating contact, open


Floating contact, closed
3 V, 5 A

Floating contact, open


Floating contact, closed
3 V, 5 A

Floating contact, open


Floating contact, closed
3 V, 5 A

Electrically isolated from the basic device


- Signal status 0
- Signal status 1
- Natural resistance

4.5 V or open
13 V
25 k

4.5 V or open
13 V
25 k

4.5 V or open
13 V
25 k

Binary input BE2

Static destruction limit

35 V

Internal inductance and capacitance

Negligible

Connection to power circuits

Intrinsically safe Ui 25.2 V

Ui 25.2 V DC

Electrical isolation

The 3 outputs, the input BE2 and the basic device are electrically isolated from each other

Test voltage

840 V DC, 1 s

SIA module (not for EEx d version)

6DR4004-8G (without Ex protec- 6DR4004-6G (with Ex protection)


tion)

6DR4004-6G (with Ex protection)

Limit transmitter with slot-type initiators and


alarm output

2-wire connection

2-wire connection

2-wire connection

Ex protection

Without

II 2 G EEx ia/ib IIC T6

II 2 G EEx nA L [L] IIC T6

Connection

2-wire system to DIN 19234


2-wire system to DIN 19234
2-wire system to DIN 19234
(NAMUR), for switching amplifier (NAMUR), for switching amplifier (NAMUR), for switching amplifier
to be connected on load side
to be connected on load side
to be connected on load side

2 slot-type initiators

Type SJ2-SN

Type SJ2-SN

Type SJ2-SN

Function

NC (normally closed)

NC (normally closed)

NC (normally closed)

Connection to power circuits with

nominal voltage 8 V
Current consumption:
3 mA (limit value not
responded)
1 mA (limit value
responded)

Intrinsically safe switching


amplifier DIN 19 234
Ui 15.5 V DC
Ii 25 mA, Pi 64 mW

Ui 15.5 V DC
Pi 64 mW

Internal capacitance

41 nF

Internal inductance

100 mH

Electrical isolation

The 3 outputs are electrically


isolated from the basic device

The 3 outputs are electrically


isolated from the basic device

The 3 outputs are electrically


isolated from the basic device

Test voltage

840 V DC, 1 s

840 V DC, 1 s

840 V DC, 1 s

Alarm output

See Alarm module

See Alarm module

See Alarm module

6/14

Siemens FI 01 2005

840 V DC, 1 s

840 V DC, 1 s

Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF
Accessory modules

Without Ex protection

With Ex protection

Explosion protection to EN 50014 and


EN 50020

II 2G EEx ia/ib II C T4/T5/T6

II 3G EEx nA L [L] II C T6

Mounting location

Zone 1

Zone 2

Electrical data

Permissible ambient temperature for oper- -30 ... +80 C (-22 ... +176 F)
ation
(For devices with Ex protection: Only in
conjunction with the basic device
6DR5... -.E.... Only T4 is permissible when
using Iy module. )

T4: -30 ... +80 C (-22 ... +176 F)


T5: -30 ... +65 C (-22 ... +149 F)
T6: -30 ... +50 C (-22 ... +122 F)

Iy module

6DR4004-8J (without Ex protection)

6DR4004-6J (with Ex protection)

6DR4004-6J (with Ex protection)

DC output for position feedback

2-wire connection

2-wire connection

2-wire connection

Nominal signal range i

4 ... 20 mA, short-circuit-proof

4 ... 20 mA, short-circuit-proof

4 ... 20 mA, short-circuit-proof

Total operating range

3.6 ... 20.5 mA

3.6 ... 20.5 mA

3.6 ... 20.5 mA

Power supply UH

+12 ... +35 V

+12 ... +30 V

+12 ... +30 V

External load RB [kW]

(UH [V] - 12 V) /i [mA]

(UH [V] - 12 V) /i [mA]

(UH [V] - 12 V) /i [mA]

Transmission error

0.3%

0.3%

0.3%

Temperature effect

0.1%/10 K ( 0.1%/18 F)

0.1%/10 K ( 0.1%/18 F)

0.1%/10 K ( 0.1%/18 F)

Resolution

0.1%

0.1%

0.1%

Residual ripple

1%

1%

1%

Internal capacitance Ci

11 nF

Internal inductance Li

Negligible

Intrinsically safe: Ui 30 V DC
Ii 100 mA; Pi 1 W (only T4)

Ui 30 V DC
Ii 100 mA; Pi 1 W (only T4)

For connection to power circuits with


Electrical isolation

Electrically isolated from the


basic device

Electrically isolated from the


basic device

Electrically isolated from the


basic device

Test voltage

840 V DC, 1 s

840 V DC, 1 s

840 V DC, 1 s

NCS sensor
(not for EEx d version)
Position range
Linear actuator

3 ... 130 mm (0.12 ... 5.12 inch), 3 ... 130 mm (0.12 ... 5.12 inch), 3 ... 130 mm (0.12 ... 5.12 inch),
to 200 mm (7.87 inch) on request to 200 mm (7.87 inch) on request to 200 mm (7.87 inch) on request

Part-turn actuator

30 ... 100

Linearity (after correction by SIPART PS2)


Linear actuator
1%
Part-turn actuator
1%

30 ... 100

30 ... 100

1%
1%

1%
1%

Hysteresis

0.2%

0.2%

0.2%

Continuous working temperature

-40 ... +85 C (-40 ... +185 F),


extended temperature range on
request

-40 ... +85 C (-40 ... +185 F),


extended temperature range on
request

-40 ... +85 C (-40 ... +185 F),


extended temperature range on
request

Degree of protection of casing

IP68/NEMA 4x

IP68/NEMA 4x

IP68/NEMA 4x

Siemens FI 01 2005

6/15

Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF

Dimensional drawings
29.5 29.5
(1.16) (1.16)
72 (2.83)

95 (3.74)
99 (3.89)1)

50 x 4 (1.97 x 0.16) x M6

182 (7.17)

29.5
(1.16)
59 (2.32)

50 x 4 (1.97 x 0.16) x M6

95 (3.74)

All air
11.2 (0.44)
connections
G 1/4 or 1/4 NPT

182 (7.17)

96.6 (3.80)
97 (3.82)1)

All air
connections
11.2 (0.44)
G 1/4 or 1/4 NPT

M20 x 1.5
1) For stainless steel version only

Plastic and stainless steel casing (top), aluminium casing (center), plastic and metal casing (bottom), dimensions in mm (inch)

0  GHHS [

 

00 RU
137 [

 

Flameproof casing left, dimensions in mm (inch)

 

 
 

 
  h9

Siemens FI 01 2005





 
 




 

 &RQQHFWLRQ<RQO\IRUGRXEOHDFWLRQYHUVLRQ
 

6/16


 
 





 

0  GHHS [

(
 

 

 
 

 

 

 

 

<

 

DOODLUFRQQHFWLRQV
*RU137

 
0  GHHS [

 

Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF
Electric connection of 2-, 3- and 4-wire device (6DR52.. and
6DR53..)

Mounting level of positioner

Devices of types 6DR52.. and 6DR53.. can be operated in a 2-,


3- and 4-wire system.

25 (0,98)

M6

4 +0,1 (0.16+0.04)
12
(0.47)

4
(0,16)

>4 mm
(0.16)

Mounting plate

+
I

*) R 250 W if req.

I H+

i y = 4 to
20 mA

Part-turn actuator
IW

35 (1.38)

2
3
4
5
6
7
8

HART
modem

PC/Laptop

SIPART PS2 electropneumatic positioner, example of connection for communication through HART for 6DR52..

6,

*) Only required with current sources not conforming to HART

Two-wire system
F05-Lkr.-

50 (1.97)
+

Mounting onto part-turn actuators; mounting plate (scope of delivery of


actuator manufacturer), extract from VDI/VDE 3845, dimensions in mm
(inch)

4 ... 20 mA

Schematics
_

Electric connection of 2-wire devices (6DR50.. and 6DR51..)


Devices of types 6DR50.. and 6DR51.. are operated in a 2-wire
system.

Two-wire system
J

4 ... 20 mA

+
_

2
3
4
5

6
7
8
9
BE1
10

Three-/Four-wire system

6
7
8
9
BE1
10

+
18 ... 30 V

_
*)

SIPART PS2 electropneumatic positioner, input circuit for 6DR50.. and


6DR51..

Electric connection of PROFIBUS PA device (6DR55..) and


Foundation Fieldbus devices (6DR56..)

+
0/4 ...
20 mA _

2
3
4
5
6
7
8
9
BE1
10

*) Jumper between 5 and 7 only for three-wire system


+

30 V

+
PROFIBUS-PA and
FOUNDATION fieldbus connection

24 V

81
82

*)

SIPART PS2 electropneumatic positioner, input circuits for 6DR52..

6
7
9
10

+3 V
BE1

*) Input for safety shutdown (activated using coding jumper)

SIPART PS2 PA and SIPART PS2 FF electropneumatic positioner, input


circuit for 6DR55.. and 6DR56..

Siemens FI 01 2005

6/17

Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF
Selection and Ordering Data

Order No.

Selection and Ordering Data

Order No.

SIPART PS2, PS2 PA und PS2 FF


electropneumatic positioner

6 DR 5 777 - 0 7777 - 77A7

SIPART PS2, PS2 PA und PS2 FF


electropneumatic positioner

6 DR 5 777 - 0 7777 - 77A7

Design
Two-wire
without HART (4 to 20 mA)
}
with HART, without explosion protec-}
tion (except EEx d)
Two-wire, three-wire, four-wire
with HART, with explosion protection}
without HART, without explosion pro-}
tection
PROFIBUS PA connection
Foundation Fieldbus connection
For actuator
single-action
double-action

}
}

Housing
Plastic
}
Aluminium; only single-action
}
Stainless steel; not for EEx d version: }
not FM/CSA
Aluminium; EEx d casing (flameproof)1)

Explosion protection
Without
}
With explosion protection EEx ia/ib or
EEx d (CENELEC/FM/CSA)1)
With explosion protection EEx n
(CENELEC)
Connection thread
electric/pneumatic
M20 x 1,5 / G1/4
1/2 NPT / 1/4 NPT
M20 x 1,5 / 1/4 NPT
1/2 NPT / G1/4
M25 x 1,5 / G1/4 (EEx d version
only)1)
With PROFIBUS plug M12 / G1/4
With PROFIBUS plug M12 / N1/4
VDI/VDE 3847

Option modules
built-in, incl. 2nd cable gland
Without

Siemens FI 01 2005

0
1

Instruction manual
German/English
French/Spanish/Italian

2
3

Attached gauge block assembly


Without

A
B

5
6
1
2

} Available ex stock
1

) without cable gland

0
1
2

Selection and Ordering Data

Order No.

Accessories
NCS sensor
for non-contacting detection of position
(not with EEx d version), cable length 6 m
(19.68 ft)

6 D R 4 00 0 4 - 7 N N 7 0

N
E

Without explosion protection

With explosion protection

for part-turn actuators

for linear actuators up to 14 mm (0.55 inch)

for linear actuators >14 mm (0.55 inch), up


to 130 mm (5.12 inch) with standard mounting kit
An EMC filter module for the controller unit
is also required.
(separate ordering data see next page)

G
N
M
P
Q
R
S
V

Limit monitor
built-in, incl. 2nd cable gland
Without

6/18

Customer-specific design
Without

Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF

Selection and Ordering Data

Order No.

Accessories
Alarm module for 3 alarm outputs and 1 binary input (functionality: 2 limit monitors, 1 fault
alarm, 1 binary input)
- Without explosion protection }
- With explosion protection
}
- CENELEC 1)
SIA module (slot-type initiator
alarm module, not for 6DR4 version and not for EEx d version)
- Without
- With
Iy module for position feedback
signal (4 to 20 mA)
- Without explosion protection }
- With explosion protection
}
- CENELEC
HART module (only for 6DR400
version)
- Without explosion protection }
- With explosion protection
}
- CENELEC
HART modem for connecting to }
PC or laptop for 6DR40... and
6DR5...
Mounting kit for NAMUR partturn actuators
(VDI/VDE 3845, without mounting }
plate)
The following mounting plates
can be used with the NAMUR
part-turn actuator mounting kit
6DR4004-8D.
Size W x L x H (H = height of shaft
butt)
30 x 80 x 20 mm
}
30 x 80 x 30 mm
}
30 x 130 x 30 mm
}
30 x 130 x 30 mm
}
Mounting kit for other part-turn
actuators
The following mounting plates
can be used together with the
NAMUR part-turn actuator mounting kit 6DR4004-8D.
SPX (DEZURIK) Power Rac,
}
sizes R1, R1A, R2 and R2A
Masoneilan Camflex II
}
Fisher 1051/1052/1061, sizes }
30, 40, 60 to 70
Fisher 1051/1052, size 1033
}
Mounting kit for NAMUR linear
actuators
NAMUR linear actuator
}
mounting kit with short lever
arm (2 to 35 mm)
Lever arm for travels from 35 mm }
to 130 cm (1.38 inch to
5.12 inch)
Reduced mounting kit for linear }
actuator (without fixing angle
and U-bracket), with short lever
with up to 35 mm travel
(1.38 inch)
Reduced mounting kit for linear }
actuator (without fixing angle
and U-bracket), with long lever
with >35 mm travel (1.38 inch)

6DR4004-8A
6DR4004-6A
6DR4004-7A

6DR4004-8G
6DR4004-6G

6DR4004-8J
6DR4004-6J
6DR4004-7J

6DR4004-8H
6DR4004-6H
6DR4004-7H
7MF4997-1DA

6DR4004-8D

TGX:16152-105
TGX:16152-147
TGX:16300-149
TGX:16300-151

TGX:16152-328
TGX:16152-350
TGX:16152-364
TGX:16152-348

6DR4004-8V
6DR4004-8L
6DR4004-8VK

6DR4004-8VL

Mounting kit for other linear


actuators
Retrofitting kit for Moore series }
72 and 750 valve positioners
Fisher type 657/667, size 30
}
to 80
SAMSON actuator type 3277 }
(yoke dimension (H5) =
101 mm 2) (integrated connection without tube)
Pipe mounting
Mounting bracket for pipe mount- }
ing of the SIPART PS2 position
(e.g. when using the NCS sensor)

TGX:16152-117
TGX:16152-110
6DR4004-8S

TGX:16152-117

Mounting kit to VDI/VDE 3847


SIPART PS2 mounting block for }
single-action actuators, incl.
mounting material
SIPART PS2 mounting block for }
double-action actuators, incl.
mounting material
Mounting block for actuator, for }
mounting on IEC 534-6 interface
(NAMUR yoke), incl. mounting
material and mounting kit
6DR4004-8VK
VDI/VDE 3847 adapter block for }
part-turn actuators (to NAMUR
3847)

6DR4004-8CE
6DR4004-8CD
6DR4004-8CA

On request

Additional actuator items can be


found at the following Internet
address:
www.siemens.com/sipartps2
Customer-specific actuators available on request.
Pressure gauge block including
pressure gauge
For single-action SIPART PS2
positioner (2 pressure gauges,
scaled in MPa and bar)
For double-action SIPART PS2
positioner (3 pressure gauges,
scaled in MPa and bar)
Connection block, for safety
solenoid valve with extended
mounting flange to NAMUR
For mounting to IEC 534-6

6
6DR4004-1M 3)
6DR4004-2M 3)

6DR4004-1B

For SAMSON actuator (integrated mounting) see above

6DR4004-1C 4)

Rating plate set Ex n (for


6DR400.-.E) for conversion to
Ex n mode approval (zone 2)

C73451-A430-D55

External position detection system (with explosion protection to


CENELEC) for separate mounting of position sensor and controller (for for EEx d version),
comprising SIPART PS2 plastic
casing with integral potentiometer
and sliding clutch (without electronics and valve block)
For the CE marking, the EMC filter
module is additionally required for
the controller unit.
(separate ordering item below)

C73451-A430-D78

EMC filter module for connection


of external position sensor
(10 k) (not for EEx d version)

C73451-A430-D23

} Available ex stock.
1) U.S. certification by FM institute
2) With a yoke dimension H5 = 95 mm, only the SIPART PS2 in a metal casing can be used.
3) 1MN or -2MN with NPT thread, scaled in MPa and psi.
4) Only together with 6DR4004-8S and 6DR4004-1M.

Siemens FI 01 2005

6/19

Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF
Documentation
Instruction Manual SIPART PS2
German/English
French/Italian/Spanish

A5E00074600
A5E00074601

Instruction Manual SIPART PS2


PROFIBUS PA
German/English
French/Italian/Spanish

A5E00120716
A5E00120717

Instruction Manual NCS Sensor


German/English/French/
Spanish/Italian

A5E00097485

Manual for SIPART PS2/


PS2 EEx d (6DR5xxx)
German
English

A5E00074630
A5E00074631

Manual for SIPART PS2


PROFIBUS PA
German
English

A5E00127924
A5E00127926

Instruction Manual SIPART PS2


EEx d
German/English

A5E00165376

Instruction Manual SIPART PS2


EEx d PA
German/English

A5E00165378

SITRANS I outgoing isolator


HART (see "SITRANS I supply
units and input isolators") with
24 V DC power supply
230 V AC power supply

7NG4130-1AA11
7NG4130-1BA11

Note
All the above mentioned manuals are included on CD-ROM or
can be downloaded from the Internet.
Following manuals are available in addition as downloads from
the Internet or are included on CD-ROM:
Instruction Manual SIPART PS2 FF, Electropneumatic Positioner (6DR56xx) with Foundation Fieldbus
- German/English: A5E00214570
Instruction Manual SIPART PS FF, Electropneumatic Positioner
(6DR56xx) with Foundation Fieldbus
- German: A5E00214568
- English: A5E00214569

6/20

Siemens FI 01 2005

Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF

Scope of delivery for positioner

More infomation

1 SIPART PS2 positioner as ordered


1 CD-ROM with the complete documentation for all versions
and accessories
1 each "SIPART PS2 Configuring Instructions - a concise overview" in German and English

Training

Scope of delivery for mounting kit 6DR4004-8V


(for linear actuators)
1 mounting bracket
2 mounting prisms
1 U-bracket
1 lever arm with adjustable pick-up roll
2 U-bolts
Various screws and lock washers

On request

Refer to Catalog ITC for details of training courses for these devices.
Special versions

Scope of delivery for mounting kit 6DR4004-8D


(for part-turn actuators)
1 coupling wheel
1 driver pin
8 scales
1 pointer
Various screws and lock washers
Note: The mounting consoles and the screws for mounting onto
the part-turn actuator are not included in the scope of delivery
and must be provided by the customer (see Technical data).

Siemens FI 01 2005

6/21

Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF

Mounting of SIPART PS2 on linear actuators

6/22

Siemens FI 01 2005

Mounting of SIPART PS2 on part-turn actuators

Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF

Mounting of SIPART PS2 EEx d on linear actuators

Mounting of SIPART PS2 EEx d on part-turn actuators

Siemens FI 01 2005

6/23