SIEMENS Catalouge
SIEMENS Catalouge
SIEMENS Catalouge
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF
Overview
Benefits
SIPART PS2 positioners are characterized by significant advantages:
Simple installation and automatic commissioning (self-adjustment of zero and span)
Simple operation with
- Local operation and configuration of the device using three
input keys and a user-friendly two-line LCD
- Programming through SIMATIC PDM;
very high-quality control thanks to an online adaptation procedure
Negligible air consumption in stationary operation
"Tight shut-off" function (ensures maximum positioning pressure on the valve seat)
Numerous functions can be activated by simple configuring
(e.g. characteristics and limits)
Extensive diagnosis functions for valve and actuator
Only one device version for linear and part-turn actuators
Few moving parts, hence Insensitive to vibrations
External non-contacting position sensor as option for extreme
ambient conditions
Application
The SIPART PS2 positioner is used, for example, in the following
branches:
Chemical industry
Power stations
Paper and glass
Food and pharmaceuticals
Offshore plants
Siemens FI 01 2005
6/3
Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF
Design
The SIPART PS2 positioner is a digital field device with a highlyintegrated microcontroller.
The positioner consists of the following components:
Casing and cover
PCB with corresponding electronics with or without communication through HART
or with electronics for communication in accordance with
- PROFIBUS PA specification, IEC 61158-2; bus-supplied
device, or
- Foundation Fieldbus (FF) specification, IEC 61158-2,
bus-supplied device
Actuator travel detection system
Terminal housing with screw terminals
Pneumatic valve manifold with piezoelectric valve precontrol.
The valve manifold is located in the housing, the pneumatic connections for the inlet air and the positioning pressure on the righthand side. A pressure gauge block and/or a safety solenoid
valve can be connected there as options. The circuit board container in the casing provides slots for separately ordered boards
with the following functions:
I y module
Position feedback as a two-wire signal 4 to 20 mA.
6/4
Siemens FI 01 2005
Non-contacting position sensor (NCS) for part-turn actuators (left) and for
linear actuators (right)
The actuator travel detection unit can also consist of a non-contacting position sensor instead of a potentiometer. All coupling
elements are omitted such as coupling wheel and driver pin with
part-turn actuators or lever and pick-up bracket with linear actuators.
This results in:
Even greater resistance to vibration and shock
No wear of sensor
Problem-free mounting on very small actuators
Negligible hysteresis with very small travels.
The sensor does not require an additional power supply, i.e.
SIPART PS2 can be operated in a 2-wire system. The NCS (Non
Contacting Position Sensor) consists of a potted sensor housing
which must be mounted permanently and a magnet which is
mounted on the spindle or lever shaft of linear actuators or on the
shaft butt of part-turn actuators.
The installation of a special EMC filter module in the positioner
(controller unit) is necessary in order to provide and guarantee a
connection level with EMC according to EN61326/A1 and
NAMUR NE21 when using external sensors (see Ordering data
for "EMC filter module").
Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF
Function
The SIPART PS2 electropneumatic positioner works in a completely different way to normal positioners.
Mode of operation
Comparison of the setpoint and the actual value takes place
electronically in a microcontroller. If the microcontroller detects a
deviation, it uses a 5-way switch procedure to control the piezoelectric valves, which in turn regulate the flow of air into the actuating chambers.
The microprocessor then outputs an electric control command to
the piezoelectric valve in accordance with the magnitude and direction of the deviation (deviation between setpoint w and control output x). The piezoelectric valve converts the command into
a pneumatic positional increment.
The positioner outputs a continuous signal in the area where
there is a large control deviation (high-speed zone); in areas of
moderate control deviation (slow-speed zone) it outputs a sequence of pulses. No positioning signals are output in the case
of a small control deviation (adaptive or variable dead zone).
The SIPART PS2 positioner is fitted to the linear or part-turn actuator using an appropriate mounting assembly.
The linear or rotary motion of the actuator is detected by the
mounting assembly and transferred through a rigid connection
to a potentiometer made of a wear-resistant plastic conductive
material.
The angular error of the pick-up in cases where the assembly is
mounted on a linear actuator is corrected automatically.
When connected in a 2-wire system, the SIPART PS2 draws its
power exclusively from the 4 to 20 mA setpoint signal. The electric power is connected through the 2-wire bus signal also with
PROFIBUS operation (SIPART PS2 PA). The same applies for the
Foundation Fieldbus version.
Pneumatic valve manifold with piezoelectric valve precontrol
The piezoelectric valve can release very short control pulses.
A high positioning accuracy can then be achieved. The pilot
element is a piezoelectric bending converter which switches the
pneumatic main control unit. The valve manifold is characterized
by an extremely long service life.
Local operation
Local operation is performed with the built-in LCD and the three
input keys. Switching between the operating levels Automatic,
Manual and Configuring is possible with the press of a button.
In Manual mode the drive can move over the entire range.
Operation and monitoring with the
SIMATIC PDM communications program
The SIMATIC PDM communications software permits easy remote operation and monitoring using a PC or laptop. The positioner can also be configured using this program. Parameters
which provide important information for maintenance and fault
diagnosis of the complete unit can additionally be determined
using process data and comparison data.
The SIMATIC PDM program is available for communication
through the HART interface and also for the PROFIBUS PA coupling.
Automatic commissioning
With a simple configuration menu the SIPART PS2 can be quickly
adapted to the fitting and adjusted by means of an automatic
startup function.
During initialization, the microcontroller determines the zero
point, full-scale value, the direction of action and the positioning
speed of the actuator. From this data it establishes the minimum
pulse time and the dead zone, thus optimizing the control.
Low air consumption
A hallmark of the SIPART PS2 is its own extremely low consumption of air. Normal air losses on conventional positioners are very
costly. Thanks to the use of modern piezoelectric technology, the
SIPART PS2 consumes air only when it is needed, which means
that it pays for itself within a very short time
Extensive diagnosis functions
The SIPART PS2 (6DR5...) has various monitoring functions with
which changes on the actuator and valve can be detected and
signaled if applicable when a selectable limit has been exceeded. This information may be important for diagnosis of the
actuator or valve. The measured values to be determined and
monitored, some of whose limits can be adjusted, include:
Travel integral
Number of changes in direction
Alarm counter
Self-adjusting dead zone
Valve limit position (e.g. wear of valve seat)
Operating hours (also according to temperature and positioning ranges) as well as min./max. temperature
Operating cycles of piezoelectric valves
Valve positioning time
Actuator leakages
Configuring
The following settings, for example, can be configured in configuring mode as required with the SIPART PS2 positioner:
Input current range 0 to 20 mA or 4 to 20 mA
Rising or falling characteristic at the setpoint input
Positioning speed limit (setpoint ramp)
Split-range operation; adjustable start-of-scale and full-scale
values
Response threshold (dead zone); self-adjusting or fixed
Direction of action; rising or falling output pressure with rising
setpoint
Limits (start-of-scale and full-scale values) of positioning
range
Limits (alarms) of the final control element position; minimum
and maximum values
Automatic "tight shut-off" (with adjustable response threshold)
The travel can be corrected in accordance with the valve characteristic.
Function of binary inputs
Function of alarm output etc.
Configuring the SIPART PS2 variants is identical in the main
points.
Siemens FI 01 2005
6/5
Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF
1
HART
2
BE1
3V
_
I W+
Inlet air
pZ
Exhaust
+24 V
p1
+5 V
W
I Wy
A
+U
p1
p2
Microcontroller
p2
Exhaust
W
x
x
U
6
I
5
BE2
A1
A2
I
9
8
p2
A1
1
2
3
4
5
6
A2
6/6
Siemens FI 01 2005
p1
Travel
p1
Travel
Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF
Technical specifications
Vibration resistance
30 ... 100
Installation
On linear actuators
On part-turn actuators
Controller
Five-point switch
Dead zone
- dEbA = Auto
- dEbA = 0.1 ... 10%
Self-adjusting
Self-adjusting or can be set as
fixed value
Self-adjusting or can be set as
fixed value
A/D converter
Scan time
Resolution
Transmission error
Temperature effect
10 ms
0.05%
0.2%
0.1%/10 K ( 0.1%/18 F)
Cycle time
20 mA/HART device
PA device
FF device
20 ms
60 ms
60 ms (min. loop time)
Degree of protection
IP65 to EN 60 529/NEMA 4x
Mounting position
CE marking
EMC requirements
Material
Housing
- 6DR5..0-... (plastic)
- 6DR5..1-... (metal)
- 6DR5..2-... (stainless steel)
- 6DR5..5-... (metal, pressureproof)
Pressure gauge block
Glass-fiber-reinforced Macrolon
GK AISi12
Austenitic stainless steel mat.
No. 1.4581
GK AISi12
Aluminium AIMgSi, coated
Harmonic oscillations
(sine-wave) according to
DIN EN 60062-2-6/05.96
Bumping (half-sine)
to DIN EN 60068-2-29/03.95
Dimensions
Transport 1)
Operation 2)
Class 2
Oil content
Class 2
Unthrottled flow
Inlet air valve 3)
- 2 bar (29 psi)
- 4 bar (58 psi)
- 6 bar (87 psi)
Valve leakage
Throttle ratio
Adjustable up to : 1
Types of actuators
In plastic casing
In aluminium casing
In flameproof casing
In stainless steel casing
Siemens FI 01 2005
6/7
Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF
Technical specifications
SIPART PS2
Basic device
without Ex protection
Basic device
with EEx-d protection
(flameproof casing)
Basic device
Basic device
with EEx ia/ib protection with EEx n protection
Explosion protection to
EN 50014, EN 50020 and EN 50021
Without
EEx d
II 2 G EEx d II C T6
EEx ia/ib
II 2 G EEx ia/ib II C T6
EEx n
II 3 G EEx nA L [L] II C T6
Zone 1
Zone 2
Mounting location
Zone 1
Electrical data
Input
2-wire connection (terminals 6/8)
Rated signal range
4 ... 20 mA
4 ... 20 mA
4 ... 20 mA
4 ... 20 mA
3.6 mA
3.6 mA
3.6 mA
3.6 mA
- Typical
6.36 V (corresponds to
318 )
6.36 V (corresponds to
318 )
7.8 V (corresponds to
390 )
7.8 V (corresponds to
390 )
- Max.
6.48 V (corresponds to
324 )
6.48 V (corresponds to
324 )
8.3 V (corresponds to
415 )
8.3 V (corresponds to
415 )
- Typical
7.9 V (corresponds to
395 )
- Max.
8.4 V (corresponds to
420 )
- Typical
6.6 V (corresponds to
330 )
6.6 V (corresponds to
330 )
- Max.
6.72 V (corresponds to
336 )
6.72 V (corresponds to
336 )
- Typical
8.4 V (corresponds to
420 )
8.4 V (corresponds to
420 )
8.4 V (corresponds to
420 )
- Max.
8.8 V (corresponds to
440 )
8.8 V (corresponds to
440 )
8.8 V (corresponds to
440 )
40 mA
Internal capacitance Ci
Without HART
22 nF
With HART
7 nF
0.12 mH
Internal inductance Li
Without HART
With HART
0.24 mH
intrinsically safe
Uo 30 V DC
Ik 100 mA
P1W
Ui 30 V DC
Ii 100 mA
6/8
Siemens FI 01 2005
Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF
SIPART PS2
Basic device
without Ex protection
Basic device
with EEx-d protection
(flameproof casing)
Basic device
Basic device
with EEx ia/ib protection with EEx n protection
18 ... 35 V DC
18 ... 30 V DC
18 ... 35 V DC
Current consumption IH
(UH - 7.5 V)/2.4 kW [mA] (UH - 7.5 V)/2.4 kW [mA] (UH - 7.5 V)/2.4 kW [mA] (UH - 7.5 V)/2.4 kW [mA]
18 ... 30 V DC
Internal capacitance Ci
Internal inductance Li
22 nF
0.12 mH
intrinsically safe
Uo 30 V DC
Ik 100 mA
P1W
Ui 30 V DC
Ii 100 mA
Current input IW
Rated signal range
4 ... 20 mA
4 ... 20 mA
4 ... 20 mA
4 ... 20 mA
Load voltage at 20 mA
0.2 V (corresponds to
10 )
0.2 V (corresponds to
10 )
1 V (corresponds to
50 )
1 V (corresponds to
50 )
Internal capacitance Ci
22 nF
0.12 mH
intrinsically safe
Uo 30 V DC
Ik 100 mA
P1W
Ui 30 V DC
Ii 100 mA
Electrical isolation
between UH and IW
between UH and IW
between UH and IW
(2 intrinsically safe circuits)
between UH and IW
Test voltage
Connections
Electric
Pneumatic
<5V
<5V
Io
< 75 mA
< 75 mA
Is
<160 mA
<160 mA
Po
<120 mW
<120 mW
< 1 F
< 1 F
< 1 mH
< 1 mH
Siemens FI 01 2005
6/9
Electropneumatic positioners
SIPART PS2
SIPART PS2 PA
Technical specifications
SIPART PS2 PA
Basic device
without Ex protection
Basic device
with EEx-d protection
(flameproof casing)
Basic device
Basic device
with EEx ia/ib protection with EEx n protection
Explosion protection to
Without
EN 50.014, EN 50.020 and EN 50.021
EEx d
EEx ia/ib
II 2 G EEx d II C T4/T5/T6 II 2 G EEx ia/ib II C T6
EEx n
II 3 G EEx nA L [L] II C T6
Mounting location
Zone 1 or zone 2
Zone 2
Zone 1
Electrical data
Input
Power supply (terminals 6/7)
Bus-supplied
Bus voltage
9 ... 32 V
9 ... 32 V
9 ... 24 V
9 ... 32 V
17.5 V
- Max. power Po
380 mA
5.32 W
24 V
250 mA
- Max. power Po
1.2 W
Current consumption
10.5 mA 10%
10.5 mA 10%
10.5 mA 10%
10.5 mA 10%
Fault current
0 mA
0 mA
0 mA
0 mA
Li 8 mH
Negligible
Connection
> 20 k
> 20 k
> 20 k
> 20 k
13 ... 30 V
13 ... 30 V
13 ... 30 V
13 ... 30 V
Negligible
Negligible
Intrinsically safe
< 30 V
< 30 V
<100 mA
<100 mA
- Maximum power Pi
<1W
Electrical isolation
Test voltage
840 V DC, 1 s
840 V DC, 1 s
840 V DC, 1 s
840 V DC, 1 s
6/10
Siemens FI 01 2005
Electropneumatic positioners
SIPART PS2
SIPART PS2 PA
SIPART PS2 PA
Basic device
without Ex protection
Basic device
with EEx-d protection
(flameproof casing)
Basic device
Basic device
with EEx ia/ib protection with EEx n protection
Communication
Layers 1 and +2 according to PROFIBUS PA, transmission technique according to IEC 1158-2;
slave function; layer 7 (protocol layer) according to PROFIBUS DP,
EN 50170 standard with the extended PROFIBUS functions
(all data acyclic, manipulated variable, feedbacks and status also cyclic)
C2 connections
Device profile
Typical 10 ms
Device address
PC parameterizing software
Connections
Electric
Pneumatic
Female thread G
DIN 45141 ( -18 NPT)
Female thread G
DIN 45141 ( -18 NPT)
Female thread G
DIN 45141 ( -18 NPT)
Female thread G
DIN 45141 ( -18 NPT)
Uo
<5V
<5V
Io
<75 mA
<75 mA
Is
<160 mA
<160 mA
Po
<120 mW
<120 mW
< 1 F
< 1 F
< 1 mH
< 1 mH
Siemens FI 01 2005
6/11
Electropneumatic positioners
SIPART PS2
SIPART PS2 FF
Technical specifications
SIPART PS2 FF
Basic device
without Ex protection
Basic device
with EEx d protection,
flameproof casing
(available soon)
Basic device
with EEx ia/ib protection
Explosion protection to
EN 50014, EN 50020 and EN 50021
Without
EEx d
II 2 G EEx d II C T4/T5/T6
EEx ia/ib
II 2 G EEx ia/ib II C T6
Zone 1 or zone 2
Zone 1
Mounting location
Permissible ambient temperature for operation -30 ... +80 C (-22 ... +176 F)
(for basic devices with Ex protection the following applies: At -10 C (+14 F) the display refresh rate of the LCD is limited. Only
T4 is permissible when using Iy module.)
Electrical data
Input
Power supply (terminals 6/7)
Bus-supplied
Bus-supplied
Bus-supplied
Bus voltage
9 ... 32 V
9 ... 32 V
9 ... 24 V
17.5 V
380 mA
- Max. power Po
5.32 W
24 V
250 mA
- Max. power Po
1.2 W
Electrical data
Current consumption
10.5 mA 10%
10.5 mA 10%
10.5 mA 10%
Fault current
0 mA
0 mA
0 mA
Li 8 mH
Negligible
Connection
Input resistance
> 20 k
> 20 k
> 20 k
13 ... 30 V
13 ... 30 V
13 ... 30 V
Negligible
Safety shutdown can be activated with coding bridge (terminals 81/82; electrically isolated from the basic device)
Negligible
Intrinsically safe
< 30 V
<100 mA
- Maximum power Pi
<1W
Electrical isolation
Test voltage
840 V DC, 1 s
840 V DC, 1 s
840 V DC, 1 s
6/12
Siemens FI 01 2005
Electropneumatic positioners
SIPART PS2
SIPART PS2 FF
SIPART PS2 FF
Basic device
without Ex protection
Basic device
with EEx d protection,
flameproof casing
(available soon)
Basic device
with EEx ia/ib protection
Communication
Communications group and class
Function blocks
AO: 50 ms
PID: 80 ms
123, 511
FF registration
Connections
Electric
Pneumatic
<5V
Io
<75 mA
Is
<160 mA
Po
<120 mW
< 1 F
< 1 mH
Siemens FI 01 2005
6/13
Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF
Technical specifications
Option modules
Without Ex protection
With Ex protection
II 3G EEx nA L [L] II C T6
Mounting location
Zone 1
Zone 2
Permissible ambient temperature for opera- -30 ... +80 C (-22 ... +176 F)
tion
(For devices with Ex protection: Only in conjunction with the basic device 6DR5... -.E....
Only T4 is permissible when using Iy module)
Electrical data
Alarm module
Active, R = 1 k, +3/-1%*
Disabled, IR < 60 A
2.1 mA
1.2 mA
(* When used in the flameproof (Switching threshold with supcasing the current consumption ply to DIN 19234: UH = 8.2 V,
is limited to 10 mA per output.) Ri = 1k)
2.1 mA
1.2 mA
(Switching threshold with supply to DIN 19234: UH = 8.2 V,
Ri = 1k)
Internal capacitance Ci
5.2 nF
Internal inductance Li
Negligible
Power supply UH
35 V
Ui 15.5 V DC
4.5 V or open
13 V
25 k
4.5 V or open
13 V
25 k
4.5 V or open
13 V
25 k
35 V
Negligible
Ui 25.2 V DC
Electrical isolation
The 3 outputs, the input BE2 and the basic device are electrically isolated from each other
Test voltage
840 V DC, 1 s
2-wire connection
2-wire connection
2-wire connection
Ex protection
Without
Connection
2 slot-type initiators
Type SJ2-SN
Type SJ2-SN
Type SJ2-SN
Function
NC (normally closed)
NC (normally closed)
NC (normally closed)
nominal voltage 8 V
Current consumption:
3 mA (limit value not
responded)
1 mA (limit value
responded)
Ui 15.5 V DC
Pi 64 mW
Internal capacitance
41 nF
Internal inductance
100 mH
Electrical isolation
Test voltage
840 V DC, 1 s
840 V DC, 1 s
840 V DC, 1 s
Alarm output
6/14
Siemens FI 01 2005
840 V DC, 1 s
840 V DC, 1 s
Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF
Accessory modules
Without Ex protection
With Ex protection
II 3G EEx nA L [L] II C T6
Mounting location
Zone 1
Zone 2
Electrical data
Permissible ambient temperature for oper- -30 ... +80 C (-22 ... +176 F)
ation
(For devices with Ex protection: Only in
conjunction with the basic device
6DR5... -.E.... Only T4 is permissible when
using Iy module. )
Iy module
2-wire connection
2-wire connection
2-wire connection
Power supply UH
Transmission error
0.3%
0.3%
0.3%
Temperature effect
0.1%/10 K ( 0.1%/18 F)
0.1%/10 K ( 0.1%/18 F)
0.1%/10 K ( 0.1%/18 F)
Resolution
0.1%
0.1%
0.1%
Residual ripple
1%
1%
1%
Internal capacitance Ci
11 nF
Internal inductance Li
Negligible
Intrinsically safe: Ui 30 V DC
Ii 100 mA; Pi 1 W (only T4)
Ui 30 V DC
Ii 100 mA; Pi 1 W (only T4)
Test voltage
840 V DC, 1 s
840 V DC, 1 s
840 V DC, 1 s
NCS sensor
(not for EEx d version)
Position range
Linear actuator
3 ... 130 mm (0.12 ... 5.12 inch), 3 ... 130 mm (0.12 ... 5.12 inch), 3 ... 130 mm (0.12 ... 5.12 inch),
to 200 mm (7.87 inch) on request to 200 mm (7.87 inch) on request to 200 mm (7.87 inch) on request
Part-turn actuator
30 ... 100
30 ... 100
30 ... 100
1%
1%
1%
1%
Hysteresis
0.2%
0.2%
0.2%
IP68/NEMA 4x
IP68/NEMA 4x
IP68/NEMA 4x
Siemens FI 01 2005
6/15
Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF
Dimensional drawings
29.5 29.5
(1.16) (1.16)
72 (2.83)
95 (3.74)
99 (3.89)1)
50 x 4 (1.97 x 0.16) x M6
182 (7.17)
29.5
(1.16)
59 (2.32)
50 x 4 (1.97 x 0.16) x M6
95 (3.74)
All air
11.2 (0.44)
connections
G 1/4 or 1/4 NPT
182 (7.17)
96.6 (3.80)
97 (3.82)1)
All air
connections
11.2 (0.44)
G 1/4 or 1/4 NPT
M20 x 1.5
1) For stainless steel version only
Plastic and stainless steel casing (top), aluminium casing (center), plastic and metal casing (bottom), dimensions in mm (inch)
00 RU
137[
h9
Siemens FI 01 2005
&RQQHFWLRQ<RQO\IRUGRXEOHDFWLRQYHUVLRQ
6/16
(
<
DOODLUFRQQHFWLRQV
*RU137
0GHHS[
Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF
Electric connection of 2-, 3- and 4-wire device (6DR52.. and
6DR53..)
25 (0,98)
M6
4 +0,1 (0.16+0.04)
12
(0.47)
4
(0,16)
>4 mm
(0.16)
Mounting plate
+
I
*) R 250 W if req.
I H+
i y = 4 to
20 mA
Part-turn actuator
IW
35 (1.38)
2
3
4
5
6
7
8
HART
modem
PC/Laptop
SIPART PS2 electropneumatic positioner, example of connection for communication through HART for 6DR52..
6,
Two-wire system
F05-Lkr.-
50 (1.97)
+
4 ... 20 mA
Schematics
_
Two-wire system
J
4 ... 20 mA
+
_
2
3
4
5
6
7
8
9
BE1
10
Three-/Four-wire system
6
7
8
9
BE1
10
+
18 ... 30 V
_
*)
+
0/4 ...
20 mA _
2
3
4
5
6
7
8
9
BE1
10
30 V
+
PROFIBUS-PA and
FOUNDATION fieldbus connection
24 V
81
82
*)
6
7
9
10
+3 V
BE1
Siemens FI 01 2005
6/17
Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF
Selection and Ordering Data
Order No.
Order No.
Design
Two-wire
without HART (4 to 20 mA)
}
with HART, without explosion protec-}
tion (except EEx d)
Two-wire, three-wire, four-wire
with HART, with explosion protection}
without HART, without explosion pro-}
tection
PROFIBUS PA connection
Foundation Fieldbus connection
For actuator
single-action
double-action
}
}
Housing
Plastic
}
Aluminium; only single-action
}
Stainless steel; not for EEx d version: }
not FM/CSA
Aluminium; EEx d casing (flameproof)1)
Explosion protection
Without
}
With explosion protection EEx ia/ib or
EEx d (CENELEC/FM/CSA)1)
With explosion protection EEx n
(CENELEC)
Connection thread
electric/pneumatic
M20 x 1,5 / G1/4
1/2 NPT / 1/4 NPT
M20 x 1,5 / 1/4 NPT
1/2 NPT / G1/4
M25 x 1,5 / G1/4 (EEx d version
only)1)
With PROFIBUS plug M12 / G1/4
With PROFIBUS plug M12 / N1/4
VDI/VDE 3847
Option modules
built-in, incl. 2nd cable gland
Without
Siemens FI 01 2005
0
1
Instruction manual
German/English
French/Spanish/Italian
2
3
A
B
5
6
1
2
} Available ex stock
1
0
1
2
Order No.
Accessories
NCS sensor
for non-contacting detection of position
(not with EEx d version), cable length 6 m
(19.68 ft)
6 D R 4 00 0 4 - 7 N N 7 0
N
E
G
N
M
P
Q
R
S
V
Limit monitor
built-in, incl. 2nd cable gland
Without
6/18
Customer-specific design
Without
Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF
Order No.
Accessories
Alarm module for 3 alarm outputs and 1 binary input (functionality: 2 limit monitors, 1 fault
alarm, 1 binary input)
- Without explosion protection }
- With explosion protection
}
- CENELEC 1)
SIA module (slot-type initiator
alarm module, not for 6DR4 version and not for EEx d version)
- Without
- With
Iy module for position feedback
signal (4 to 20 mA)
- Without explosion protection }
- With explosion protection
}
- CENELEC
HART module (only for 6DR400
version)
- Without explosion protection }
- With explosion protection
}
- CENELEC
HART modem for connecting to }
PC or laptop for 6DR40... and
6DR5...
Mounting kit for NAMUR partturn actuators
(VDI/VDE 3845, without mounting }
plate)
The following mounting plates
can be used with the NAMUR
part-turn actuator mounting kit
6DR4004-8D.
Size W x L x H (H = height of shaft
butt)
30 x 80 x 20 mm
}
30 x 80 x 30 mm
}
30 x 130 x 30 mm
}
30 x 130 x 30 mm
}
Mounting kit for other part-turn
actuators
The following mounting plates
can be used together with the
NAMUR part-turn actuator mounting kit 6DR4004-8D.
SPX (DEZURIK) Power Rac,
}
sizes R1, R1A, R2 and R2A
Masoneilan Camflex II
}
Fisher 1051/1052/1061, sizes }
30, 40, 60 to 70
Fisher 1051/1052, size 1033
}
Mounting kit for NAMUR linear
actuators
NAMUR linear actuator
}
mounting kit with short lever
arm (2 to 35 mm)
Lever arm for travels from 35 mm }
to 130 cm (1.38 inch to
5.12 inch)
Reduced mounting kit for linear }
actuator (without fixing angle
and U-bracket), with short lever
with up to 35 mm travel
(1.38 inch)
Reduced mounting kit for linear }
actuator (without fixing angle
and U-bracket), with long lever
with >35 mm travel (1.38 inch)
6DR4004-8A
6DR4004-6A
6DR4004-7A
6DR4004-8G
6DR4004-6G
6DR4004-8J
6DR4004-6J
6DR4004-7J
6DR4004-8H
6DR4004-6H
6DR4004-7H
7MF4997-1DA
6DR4004-8D
TGX:16152-105
TGX:16152-147
TGX:16300-149
TGX:16300-151
TGX:16152-328
TGX:16152-350
TGX:16152-364
TGX:16152-348
6DR4004-8V
6DR4004-8L
6DR4004-8VK
6DR4004-8VL
TGX:16152-117
TGX:16152-110
6DR4004-8S
TGX:16152-117
6DR4004-8CE
6DR4004-8CD
6DR4004-8CA
On request
6
6DR4004-1M 3)
6DR4004-2M 3)
6DR4004-1B
6DR4004-1C 4)
C73451-A430-D55
C73451-A430-D78
C73451-A430-D23
} Available ex stock.
1) U.S. certification by FM institute
2) With a yoke dimension H5 = 95 mm, only the SIPART PS2 in a metal casing can be used.
3) 1MN or -2MN with NPT thread, scaled in MPa and psi.
4) Only together with 6DR4004-8S and 6DR4004-1M.
Siemens FI 01 2005
6/19
Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF
Documentation
Instruction Manual SIPART PS2
German/English
French/Italian/Spanish
A5E00074600
A5E00074601
A5E00120716
A5E00120717
A5E00097485
A5E00074630
A5E00074631
A5E00127924
A5E00127926
A5E00165376
A5E00165378
7NG4130-1AA11
7NG4130-1BA11
Note
All the above mentioned manuals are included on CD-ROM or
can be downloaded from the Internet.
Following manuals are available in addition as downloads from
the Internet or are included on CD-ROM:
Instruction Manual SIPART PS2 FF, Electropneumatic Positioner (6DR56xx) with Foundation Fieldbus
- German/English: A5E00214570
Instruction Manual SIPART PS FF, Electropneumatic Positioner
(6DR56xx) with Foundation Fieldbus
- German: A5E00214568
- English: A5E00214569
6/20
Siemens FI 01 2005
Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF
More infomation
Training
On request
Refer to Catalog ITC for details of training courses for these devices.
Special versions
Siemens FI 01 2005
6/21
Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF
6/22
Siemens FI 01 2005
Electropneumatic positioners
SIPART PS2
SIPART PS2, PS2 PA, PS2 FF,
PS2 EEx d, PS2 EEx d PA and PS2 EEx d FF
Siemens FI 01 2005
6/23