Sipart PS2 Siemens Positioner
Sipart PS2 Siemens Positioner
Sipart PS2 Siemens Positioner
Siemens AG 2015
Positioners
5/2
5/3
5/8
5/10
5/11
5/13
5/17
5/20
5/22
5/25
5/26
Product Overview
SIPART PS2
Technical description
Technical specifications
- all versions
- SIPART PS2 with and without HART
- SIPART PS2 with PROFIBUS PA/
with FOUNDATION Fieldbus
- Option modules
Selection and Ordering data
- SIPART PS2
- Accessories/Spare parts
Dimensional drawings
Schematics
Mounting kit
Software
Sec. 8 SIMATIC PDM, for parametrize
HART and PROFIBUS PA devices
Siemens AG 2015
Positioners
Product Overview
Overview
Application
Description
Positioners
Position control of pneumatic linear SIPART PS2
or part-turn actuators, also for
Universal device for positioning
intrinsically safe operation
pneumatic actuators
Connection: 4 to 20 mA
HART, PROFIBUS PA or
FOUNDATION Fieldbus
Local manual operation
Binary inputs and outputs
Diagnostic function
Blocking function
Automatic startup
5/3
SIMATIC PDM
5/3
SIMATIC PDM
5/2
Siemens AG 2015
Positioners
SIPART PS2
Technical description
Overview
Benefits
SIPART PS2 positioners offer decisive advantages:
Simple installation and automatic commissioning
(self-adjustment of zero and span)
Simple operation with
- Local operation (manual operation) and configuration of the
device using three buttons and a user-friendly two-line
display
- Parameterization via SIMATIC PDM
Very high-quality control thanks to an online adaptation
procedure
Negligible air consumption in stationary operation
"Tight closing" function (ensures maximum positioning
pressure on the valve seat)
"Fail in place" function: Current position is retained on electrical power failure (does not apply in conjunction with SIL)
Numerous functions can be activated by simple configuring
(e. g. characteristic curves and limits)
Extensive diagnostic functions for valve and actuator
Only one device version for linear and part-turn actuators
Few moving parts, hence insensitive to vibrations
External non contacting sensor as option for extreme ambient
conditions
"Intelligent solenoid valve": Partial Stroke Test and solenoid
valve function in one device
Partial Stroke Test e. g. for safety valves
Full Stroke Test, Multi Step Response Test, Valve Performance
Test for performance and maintenance evaluation of the valve
Can also be operated with purified natural gas,
carbon dioxide, nitrogen or noble gases
SIL (Safety Integrity Level) 2
Application
SIPART PS2 electropneumatic positioner in flameproof aluminum enclosure with manometers
5/3
Siemens AG 2015
Positioners
SIPART PS2
Technical description
Explosion-proof versions
Device with protection type "intrinsic safety" for use in Zone 1,
2, 21, 22 or Class I, II, III/Division 1/Groups A-G
Device with protection type "dust protection with enclosure" for
use in Zone 21, 22 or Class II, III/Division 1/Groups E-G
Device with protection type "non-sparking" for use in Zone 2 or
Class I, Division 2, Groups A-D
Device with protection type "flameproof enclosure" for use in
Zone 1 or Class I, Division 1, Groups A-D
Stainless steel enclosure for extreme ambient conditions
The SIPART PS2 is available in a stainless steel enclosure (with
no window in the cover) for use in particularly aggressive environments (e.g. offshore operation, chlorine plants etc.). The device functions are the same as for the basic version.
Design
The SIPART PS2 positioner is a digital field device with a highlyintegrated microcontroller.
Pneumatic connection
Electric cable
SIPART PS2
NCS for part-turn actuator (6DR4004-.N.10) mounted with mounting console (left) and NCS for linear actuator 14 mm (0.55 inch)
(6DR4004-.N.20) mounted with actuator-specific mounting solution
(right)
5/4
Siemens AG 2015
Positioners
SIPART PS2
Technical description
The positioner outputs a continuous signal in the area where
there is a large system deviation (fast step zone); in areas of
moderate system deviation (slow step zone) it outputs a sequence of pulses. No positioning signals are output in the case
of a small system deviation (adaptive or variable deadband).
The linear or rotary motion of the actuator is detected by the
mounting kit and transferred to a high-quality potentiometer over
a shaft and a non-floating gear transmission.
The angular error of the pick-up in cases where the assembly is
mounted on a linear actuator is corrected automatically.
When connected in a 2-wire system, the SIPART PS2 draws its
power exclusively from the 4 to 20 mA setpoint signal.
The electric power is also connected through the 2-wire bus signal with PROFIBUS operation (SIPART PS2 PA).
The same applies for the FOUNDATION Fieldbus version.
Pneumatic valve manifold with piezoelectric valve
precontrol
Function
The SIPART PS2 positioner works in a completely different way
to normal positioners.
Mode of operation
Comparison of the setpoint and the actual value takes place
electronically in a microcontroller. If the microcontroller detects a
deviation, it uses a 5-way switch procedure to control the piezoelectric valves, which regulates the flow of air into and from the
chambers of the pneumatic actuator or blows it in the opposite
direction.
The microcontroller then outputs an electric control command to
the piezoelectric valve in accordance with the size and direction
of the deviation (deviation between setpoint and actual values).
The piezoelectric valve converts the command into a pneumatic
positional increment.
5/5
Siemens AG 2015
Positioners
SIPART PS2
Technical description
The Full Stroke Test, Step Response Test, Multi Step Response
Test and Valve Performance Test provide detailed information
about the maintenance required of the valve. With the help of
HART communication, you receive comprehensive test results
and can identify the extent of the maintenance measures. In order to quantify the performance capability of valves, characteristic values such as step response times (T63, T86, user-selectable Txx), dead times, overshoot, hysteresis, errors of
measurement, non-linearity, etc., are determined.
5/6
Siemens AG 2015
Positioners
SIPART PS2
Technical description
Configuring
In configuring mode, the SIPART PS2 positioner can be configured to requirements and include the following settings:
Input current range 0 to 20 mA or 4 to 20 mA
Rising or falling characteristic curve at the setpoint input
Positioning speed limit (setpoint ramp)
Splitrange operation; adjustable start-of-scale and full-scale
values
Response threshold (deadband); self-adjusting or fixed
Direction of action; rising or falling output pressure with rising
setpoint
Limits (start-of-scale and full-scale values) of positioning
range
Limits (alarms) of the final control element position; minimum
and maximum values
Automatic "tight closing" (with adjustable response threshold)
The travel can be corrected in accordance with the valve characteristic curve.
Function of binary inputs
Function of alarm output etc.
5/7
Siemens AG 2015
Positioners
SIPART PS2
Technical specifications
Technical specifications
SIPART PS2 (all versions)
Rated conditions
Ambient conditions
Ambient temperature
Permitted ambient temperature for -30 ... +80 C (-22 ... +176 F)
operation2)3)
Standard
20 ml/min
Altitude
Fail in Place
10 ml/min
Restrictor ratio
Adjustable up to : 1
Auxiliary power consumption in the < 3,6 10-2 Nm/h (0.158 USgpm)
controlled state
Relative humidity
0 ... 100 %
Degree of protection1)
IP66 according to
IEC/EN 60529/NEMA 4X
Sound pressure
Mounting position
Design
Vibration resistance
Harmonic oscillations (sine-wave) 3.5 mm (0.14"), 2 ... 27 Hz,
according to
3 cycles/axis
EN 60068-2-6/10.2008
98.1 m/s (321.84 ft/s),
27 ... 300 Hz, 3 cycles/axis
Bumping (half-sine) according to
EN 60068-2-27/02.2010
Climatic class
According to EN 60721-3
Storage
Transport
Pressure4)
Class 2
Range of stroke (linear actuators) 3 ... 130 mm (0.12 ... 5.12 inch)
(angle of positioner shaft
16 ... 90)
Larger range of stroke on
request.
Angle of rotation range
(part-turn actuators)
30 ... 100
Mounting type
On linear actuators
On part-turn actuators
Material
Enclosure
- 6DR5..0 Makrolon
GD AISi12
- 6DR5..3 Aluminum
GD AISi12
GK AISi12
5/8
Mode of operation
Pneumatic data
Oil content
LAeq < 75 dB
LAmax < 80 dB
Siemens AG 2015
Positioners
SIPART PS2
Technical specifications
Dimensions
Explosion protection
II 2 G Ex d IIC T6/T4 Gb
Single-acting
II 2 G Ex ia IIC T6/T4 Gb
II 3 G Ex ic IIC T6/T4 Gc
II 2 D Ex ia IIIC T110C Db
Non-sparking "nA"
II 3 G Ex nA IIC T6/T4 Gc
Device versions
Gauge
- Gauge made of plastic
IP31
IP44
- Gauge made of
stainless steel 316
IP54
Non-sparking "NI"
NI / I / 2 / A-D
NI / 2 / AEx / Ex nA, Ex ic / IIC, Gc
Degree of protection
Vibration resistance
According to EN 837-1
Connections, electrical
Screw terminals
Cable gland
- Without explosion protection as
well as with Ex i
Ex d certified M20x1.5;
-14 NPT or M25x1.5
Connections, pneumatic
Female thread G or
-18 NPT
1)
2)
3)
With Order suffix (Order code) -Z M40 the following applies to SIPART PS2
device version with and without HART: -40 ... +80 C (-40 ... +176 F).
4)
The following applies to fail in place: 3 ... 7 bar (43.5 ... 101.5 psi).
5)
6)
Controller
Controller unit
Five-point switch
Self-adjusting
Deadband
- dEbA = Auto
Self-adjusting
- dEbA = 0.1 10 %
Analog-to-digital converter
Scan time
10 ms
Resolution
0,05 %
Transmission error
0,2 %
5/9
Siemens AG 2015
Positioners
SIPART PS2
Technical specifications
SIPART PS2 with and without HART
Basic device
without Ex protection
Electrical specifications
Current input IW
Rated signal range
Test voltage
Binary input BIN1 (terminals 9/10;
electrically connected to the basic
device)
2-wire connection (terminals 6/8)
6DR50.. and 6DR53.. without HART
6DR51.. and 6DR52.. with HART
Current to maintain the auxiliary power
supply
Required load voltage UB
(corresponds to at 20mA)
Without HART (6DR50..)
- Typical
- max.
Without HART (6DR53..)
- Typical
- max.
With HART (6DR51..)
- Typical
- max.
With HART (6DR52..)
- Typical
- max.
Static destruction limit
Effective internal capacitance Ci
Without HART
With HART
Effective internal inductance Li
Without HART
With HART
For connecting to circuits with the
following peak values
Basic device
with Ex d explosion
protection
0/4 ... 20 mA
840 V DC, 1 s
Suitable only for floating contact; max. contact load
< 5 A at 3 V
3.6 mA
6.36 V (= 318 )
6.48 V (= 324 )
6.36 V (= 318 )
6.48 V (= 324 )
7.8 V (= 390 )
8.3 V (= 415 )
7.8 V (= 390 )
8.3 V (= 415 )
7.9 V (= 395 )
8.4 V (= 420 )
6.6 V (= 330 )
6.72 V (= 336 )
6.6 V (= 330 )
6.72 V (= 336 )
40 mA
8.4 V (= 420 )
8.8 V (= 440 )
40 mA
8.4 V (= 420 )
8.8 V (= 440 )
-
8.4 V (= 420 )
8.8 V (= 440 )
-
11 nF
11 nF
"ic": 11 nF
"ic": 11 nF
207 H
310 H
Ui = 30 V
Ii = 100 mA
Pi = 1 W
"ic": 207 H
"ic": 310 H
"ic":
Ui = 30 V
Ii = 100 mA
"nA"/"t":
Un 30 V
In 100 mA
3-/4-wire connection
(terminals 2/4 and 6/8)
6DR52.. with HART,
explosion-protected
6DR53.. without HART,
not explosion-protected)
Load voltage at 20 mA
Power supply UH
Current consumption IH
Effective internal capacitance Ci
Effective internal inductance Li
For connecting to circuits with the following peak values
0.2 V (= 10 )
18 ... 35 V DC
0.2 V (= 10 )
1 V (= 50 )
18 ... 35 V DC
18 ... 30 V DC
(UH -7.5 V)/2.4 k [mA]
22 nF
0.12 mH
Ui = 30 V DC
Ii = 100 mA
Pi = 1 W
Electrical isolation
between UH and IW
between UH and IW
between UH and IW
(2 intrinsically safe circuits)
1 V (= 50 )
18 ... 30 V DC
"ic": 22 nF
"ic": 0,12 mH
"ic":
Ui = 30 V
Ii = 100 mA
"nA/"t":
Un 30 V
In 100 mA
between UH and IW
HART communication
HART version
PC parameterization software
5/10
7
SIMATIC PDM; supports all device objects. The software is not included in the scope of delivery.
Siemens AG 2015
Positioners
SIPART PS2
Technical specifications
SIPART PS2 with PROFIBUS PA/with FOUNDATION Fieldbus
Basic device
without Ex protection
Basic device
with Ex d explosion
protection
9 ... 32 V
9 ... 32 V
Electrical specifications
Power supply, bus circuit
Bus voltage
Bus-supplied
9 ... 24 V
9 ... 32 V
Ui = 17.5 V
Ii = 380 mA
Pi = 5.32 W
"ic":
Ui = 17.5 V
Ii = 570 mA
"nA"/"t": Un 32 V
Ui = 24 V
Ii = 250 mA
Pi = 1.2 W
"ic": Ui = 32 V
"nA"/"t": Un 32 V
Ci = negligible
Ci = negligible
Li = 8 H
"ic": Li = 8 H
11.5 mA 10 %
Current consumption
Additional error signal
0 mA
electrically isolated from bus circuit and binary input
13 ... 30 V
> 20 k
Ui = 30 V
Ii = 100 mA
Pi = 1 W
"nA":
Un 30 V
In 100 mA
"ic":
Ui = 30 V
Ii = 100 mA
negligibly small
negligibly small
Electrical isolation
For basic device without Ex protection and for basic device with Ex d
For basic device Ex "ia"
For basic device Ex "ic", "nA", "t"
Test voltage
Electrical isolation between basic device and the input for safety shutdown, as well as the outputs of the
option modules
The basic device and the input to the safety shutdown, as well as the outputs of the option modules,
are separate, intrinsically safe circuits.
Electrical isolation between basic device and the input for safety shutdown,
as well as the outputs of the option modules
840 V DC, 1 s
PROFIBUS PA communication
Communication
Layers 1 and +2 according to PROFIBUS PA, transmission technology according to IEC 61158-2;
slave function; layer 7 (protocol layer) according to PROFIBUS DP,
EN 50170 standard with the extended PROFIBUS functions
(all data acyclic, manipulated variable, feedbacks and status also cyclic)
C2 connections
Four connections to master class 2 are supported; automatic connection setup 60 s after break in communication
Device profile
Response time to master message
Device address
PC parameterization software
5/11
Siemens AG 2015
Positioners
SIPART PS2
Technical specifications
Basic device
without Ex protection
Basic device
with Ex d explosion
protection
FOUNDATION Fieldbus
communication
Communications group and class
Function blocks
FF registration
Device address
22 (when delivered)
5/12
Siemens AG 2015
Positioners
SIPART PS2
Technical specifications
Option modules
Alarm module
Without Ex protection/
with Ex protection Ex d
6DR4004-8A
6DR4004-6A
6DR4004-6A
Conductive, R = 1 k, +3/-1 % *)
2.1 mA
2.1 mA
- Low *) (activated)
Blocked, IR < 60 A
1.2 mA
1.2 mA
Power supply UH
Signal state
Ui = 15 V
Ii = 25 mA
Pi = 64 mW
"ic":
Ui = 15 V
Ii = 25 mA
"nA"/"t": Un 15 V
Ci = 5.2 nF
Ci = 5.2 nF
Li = negligibly small
Li = negligibly small
- Signal state 1
- Contact load
3 V, 5 A
- Signal state 0
13 V
- Signal state 1
25 k
- Natural resistance
Static destruction limit
35 V
Ui = 25.2 V
"ic": Ui = 25.2 V
"nA"/"t": Un 25.5 V
Ci = negligibly small
Ci = negligibly small
Li = negligibly small
Li = negligibly small
The 3 outputs, the input BE2 and the basic device are electrically isolated from each other
Electrical isolation
Test voltage
Position feedback module
840 V DC, 1 s
6DR4004-8J
6DR4004-6J
6DR4004-6J
2-wire connection
4 ... 20 mA, short-circuit proof
3.6 20.5 mA
+12 +35 V
+12 +30 V
+12 +30 V
0,3 %
Transmission error
0,1 %
Resolution
1%
Residual ripple
For connecting to circuits with the following peak values
Ui = 30 V
Ii = 100 mA
Pi = 1 W
"ic":
Ui = 30 V,
Ii = 100 mA
"nA"/"t":
Un 30 V, In 100 mA
Pn 1 W
Ci = 11 nF
Ci = 11 nF
Li = negligibly small
Li = negligibly small
Electrical isolation
Test voltage
Electrically isolated from the alarm option and safely isolated from the basic device
840 V DC, 1 s
5/13
Siemens AG 2015
Positioners
SIPART PS2
Technical specifications
SIA module
Limit transmitter with slot-type
initiators and alarm output
Without Ex protection
6DR4004-8G
6DR4004-6G
6DR4004-6G
2 slot-type initiators
Connection
2-wire system to EN 60947-5-6 (NAMUR), for switching amplifier to be connected on load side
> 2.1 mA
< 1.2 mA
Type SJ2-SN
2 slot-type initiators
Function
NC (normally closed)
"ic":
Ui = 15 V
Ii = 25 mA
"nA":
Un 15 V
Pn 64 mW
Ci = 41 nF
Ci = 41 nF
Li = 100 H
Li = 100 H
1 alarm output
Connection
R = 1.1 k
> 2.1 mA
> 2.1 mA
R = 10 k
< 1.2 mA
< 1.2 mA
Power supply UH
UH 35 V DC
I 20 mA
Ui = 15 V
Ii = 25 mA
Pi = 64 mW
"ic":
Ui = 15 V
Ii = 25 mA
"nA":
Un 15 V
Pn 64 mW
Ci = 5.2 nF
Ci = 5.2 nF
Li = negligibly small
Li = negligibly small
Electrical isolation
840 V DC, 1 s
Test voltage
5/14
Siemens AG 2015
Positioners
SIPART PS2
Technical specifications
Without Ex protection
6DR4004-8K
6DR4004-6K
6DR4004-6K
4A
Ui = 30 V
Ii = 100 mA
Pi = 750 mW
"ic":
Ui = 30 V
Ii = 100 mA
"t":
Un = 30 V
In = 100 mA
Ci = negligibly small
Ci = negligibly small
Li = negligibly small
Li = negligibly small
250 V/24 V
30 V DC
30 V DC
1 alarm output
Connection
R = 1.1 k
> 2.1 mA
> 2.1 mA
R = 10 k
< 1.2 mA
< 1.2 mA
Auxiliary power
UH 35 V DC
I 20 mA
Ui = 15 V
Ii = 25 mA
Pi = 64 mW
"ic":
Ui = 15 V
Ii = 25 mA
"t":
Un = 15 V
In = 25 mA
Ci = 5.2 nF
Ci = 5.2 nF
Li = negligibly small
Li = negligibly small
Electrical isolation
Test voltage
Rated conditions altitude
Max. 2 000 m NN
At altitudes over 2 000 m NN,
use a suitable power supply
Without Ex protection
EMC filter module type C73451-A430-D23 is required for NCS sensor or an external potentiometer. External
position sensor (potentiometer or NCS; as option) with the following peak values
10 k
-
Electrical isolation
Uo = 5 V
Io = 75 mA statisch
Io = 160 mA kurzfristig
Po = 120 mW
Uo = 5 V
Io = 75 mA
Po = 120 mW
Uo = 5 V
Io = 100 mA
Po = 33 mW
Co = 1 F
Lo = 1 mH
Uo = 5 V
Io = 75 mA
Po = 120 mW
Co = 1 F
Lo = 1 mH
5/15
Siemens AG 2015
Positioners
SIPART PS2
Technical specifications
Without Ex protection
NCS sensor
Position range
Linear actuator 6DR4004-.N.20
Part-turn actuator
30 ... 100
Linear actuator
1%
Part-turn actuator
0,2 %
Hysteresis
0,1 %/10 K ( 0.1 %/18 F) for -20 ... +90 C (-4 ... +194 F)
0,2 %/10 K ( 0.2 %/18 F) for -40 ... -20 C (-40 ... -4 F)
According to EN 60721-3
Storage
1K5, but -40 ... +90 C (1K5, but -40 ... +194 F)
Transport
2K4, but -40 ... +90 C (2K4, but -40 ... +194 F)
Vibration resistance
Bumping according to
IEC 60068-2-29
Degree of protection of enclosure
Ui = 5 V
Ii = 160 mA
Pi = 120 mW
Ui = 5 V
Ci = 180 nF
Ci = 180 nF
Li = 922 H
Li = 922 H
Non-sparking, "nA":
NI, Class I, Divison 2, ABCD
NI, Class I, Zone 2, AEx nA, IIC
FM
5/16
Siemens AG 2015
Positioners
SIPART PS2
Selection and Ordering data SIPART PS2
Selection and ordering data
Article No.
6 DR 5
Order code
Article No.
6 DR 5
Limit monitor
Installed, incl. 2nd cable gland
Without
Alarm module;
electronic (6DR4004-.A)
SIA module; slot-type initiators
(6DR4004-.G)
Mechanical limit switch module
(mechanical switching contacts
(6DR4004-.K))4)
Version
2-wire (4 to 20 mA)
Without HART
} 0
With HART, not explosion} 1
protected
2-, 3-, 4-wire (0/4 to 20 mA)
With HART, explosion-protected } 2
Without HART, not explosion
3
-protected
PROFIBUS PA connection
5
FOUNDATION Fieldbus connection
6
For actuator
Single-acting
Double-acting
Enclosure
Makrolon
Aluminum, narrow;
only single-acting
Stainless steel, without inspection
window
Aluminum
Explosion protection
Without
With protection type
Intrinsic safety
With protection type1)
Non-sparking
Dust protection via enclosure
With protection type2)
Intrinsic safety
Non-sparking
With protection type2)
Non-sparking
With protection type1)
Intrinsic safety
Non-sparking
Dust protection via enclosure
Connection thread
electrical/pneumatic
M20x1.5/G
-14 NPT / -18 NPT
M20x1.5/-18 NPT
-14 NPT / G
Plug M12 / G3)
Plug M12 / -18 NPT3)
}
}
1
2
0
11
3
}
}
N
E
0
1
2
5
3
G
K
G
N
M
P
R
S
2)
0
1
2
Brief instructions
German/English
French/Spanish/Italian
} Available ex stock
1)
Customer-specific design
Without
}
}
Option modules
Installed,
incl. 2nd cable gland
Without
}
Position feedback module for position feedback signal (4 ... 20 mA)
(6DR4004-.J)
EMC filter module for external position sensor in the SIPART PS2
enclosure (C73451-A430-D23),
NCS sensor 6DR4004-.N..0 and
external position sensing with nonSiemens potentiometer
Position feedback module and EMC
filter module for external position
sensor
Order code
A
B
0
1
2
3
4
9 R1A
9 R2A
9 R1B
9 R2B
9 R1C
9 R2C
9 R1D
9 R2D
5/17
Siemens AG 2015
Positioners
SIPART PS2
Selection and Ordering data SIPART PS2
Selection and ordering data
Article No.
6 DR 5
Further designs
Order code
A20
A40
C20
Fail in Place
Holding function in case of auxiliary
electrical power failure
F01
K18
K20
Marine approval
Germanischer Lloyd certificate
S10
S11
S12
S13
S14
Y15
Y16
Y17
Y25
Y30
} Available ex stock
5/18
Order code
Siemens AG 2015
Positioners
SIPART PS2
Selection and Ordering data SIPART PS2
Selection and ordering data
Article No.
6 DR 5
Order code
Article No.
6 DR 5
7 7 5 - 0 E 7 7 7 - 00 7 A 7 7 7 7
0
1
}
}
}
}
Option modules
Built-in
Without
}
Position feedback module for position feedback signal (4 ... 20 mA)
(6DR4004-8J)
EMC filter module for external
position sensor
Position feedback module and EMC
filter module for external position
sensor
Brief instructions
German/English
French/Spanish/Italian
2
3
5
6
7 7 5 - 0 E 7 7 7 - 00 7 A 7 7 7 7
0
1
2
3
4
1
2
G
N
M
P
Q
9 R1A
9 R2A
9 R1B
9 R2B
0
1
0
1
2
3
A
B
} Available ex stock
We can offer shorter delivery times for configurations designated with
the Quick Ship Symbol . For details see page 9/5 in the appendix.
Order code
9 R1C
9 R2C
9 R1D
9 R2D
Further designs
Add "-Z" to Article No. and specify
Order Code.
Order code
A20
C20
Fail in Place
Holding function in case of auxiliary
electrical power failure
F01
K18
Y15
Y16
Y17
Y25
} Available ex stock
Siemens FI 01 June 2015
5/19
Siemens AG 2015
Positioners
SIPART PS2
Selection and Ordering data Accessories/Spare parts
Article No.
Accessories
} 6DR4004-8J
} 6DR4004-6J
} 6DR4004-6A
} 6DR4004-8G
} 6DR4004-6G
} 6DR4004-2MN
} 6DR4004-1P
} 6DR4004-2P
} 6DR4004-1PN
Article No.
} 6DR4004-2PN
6 D R 4 00 0 4 - 7 N 7 7 0
} 6DR4004-1Q
2 gauges made of stainless steel 316
Block made of stainless steel 316, single-acting
G, scaled in MPa, bar, psi
} 6DR4004-8K
} 6DR4004-6K
} C73451-A430-D23
} Available ex stock
Accessories
} 6DR4004-2Q
3 gauges made of stainless steel 316
Block made of stainless steel 316, double-acting
G, scaled in MPa, bar, psi
} 6DR4004-1QN
2 gauges made of stainless steel 316
Block made of stainless steel 316, single-acting
-18 NPT, scaled in MPa, bar, psi
8
6
} 6DR4004-2QN
3 gauges made of stainless steel 316
Block made of stainless steel 316, double-acting
-18 NPT, scaled in MP, bar, psi
N
P
R
5/20
} 6DR4004-2M
3 gauges made of plastic, block made of
aluminum, double-acting G, scaled in MPa and
bar
} 6DR4004-1MN
NCS sensor
for non-contacting detection of position (not
for Ex d version)
} 6DR4004-1M
2 gauges made of plastic, block made of
aluminum, single-acting G, scaled in MPa and
bar
} C73451-A430-D78
External position detection system
(with explosion protection to ATEX/IECEx) for
separate mounting of position sensor and controller unit (not for Ex d version), comprising
SIPART PS2 Makrolon enclosure with integral
potentiometer and sliding clutch (without electronics and valve block)
The EMC filter module is additionally required for
the controller unit. (separate ordering item, see
above).
Article No.
Single-acting with G
} 6DR4004-1R
Double-acting with G
} 6DR4004-2R
} 6DR4004-1RN
} 6DR4004-2RN
} 6DR4004-8D
} TGX:16300-1556
TGX:16152-105
30 x 80 x 30 mm
TGX:16300-147
30 x 130 x 30 mm
TGX:16300-149
30 x 130 x 50 mm
TGX:16300-151
Siemens AG 2015
Positioners
SIPART PS2
Selection and Ordering data Accessories/Spare parts
Mounting kit for other part-turn actuators
Operating Instructions
SIPART PS2 HART German
A5E00074630
TGX:16152-328
A5E00074631
A5E00127924
TGX:16152-350
A5E00127926
TGX:16152-364
A5E00214568
TGX:16152-348
A5E00214569
Masoneilan Camflex II
Fisher 1051/1052, size 33
Mounting kit for NAMUR linear actuators
6DR4004-8V
A5E03436620
6DR4004-8L
A5E03436655
A5E03436664
A5E03436683
}
Reduced mounting kit (like 6DR4004-8V but
without fixing angle and U-bracket), with short
lever with up to 35 mm travel (1.38 inch)
6DR4004-8VK
6DR4004-8VL
}
Roll and disk made of stainless steel 316
for replacement of the Teflon roll and aluminum
disk in the 6DR4004-8, -8VK and -8VL mounting
kits for NAMUR linear actuators
6DR4004-3N
6DR4004-3M
A5E00097485
TGX:16152-117
TGX:16152-620
TGX:16152-110
6DR4004-8S
A5E00214567
7NG4124-0AA00
7NG4131-0AA00
7MF4997-1DB
Note:
6DR4004-5PA
6DR4004-5PL
6DR4004-1B
6DR4004-1C1)
Article No.
A5E00078030
A5E00524070
5/21
Siemens AG 2015
Positioners
SIPART PS2
Dimensional drawings
Dimensional drawings
Makrolon enclosure 6DR5..0
Stainless steel enclosure 6DR5..2
60
(2.36)
Y2
23
(0.91)
11,2
(0.44)
58
(2.28)
186.5 *)
(7.34) *)
182
(7.17)
12
(0.47)
6.5
(0.26)
Y1
14
(0.55)
59
(2.32)
29.5
(1.16)
29.5
(1.16)
29
(1.14)
84
(3.31)
27.5
(1.08)
7
(0.28)
34.5
(1.36)
Y1
9 (0.35)
2
(0.08)
65
(2.56)
50 (1.97), 4 x M6
58
(2.28)
11.2
(0.44)
PZ
185
(7.28)
*)
96.6 (3.80)3)
72 (2.84) 2)
95 (3.74)1)
37
(1.46)
29.5
(1.16)
29.5
(1.16)
9 (0.35) deep
M8, 9 (0.35) deep
PZ
29
(1.14)
33
(1.30)
48
(1.89)
Y1
7
(0.28)
Y1
2
(0.08)
65
(2.56)
50 (1.97), 4 x M6
M20 x 1.5
G"
88.5 90.5 *)
(3.48) (3.56) *)
5/22
Siemens AG 2015
Positioners
SIPART PS2
Dimensional drawings
60 (2.36)
1 (0.04)
Y2
11.2 (0.44)
23
(0.91)
14.5 (0.57)
58 (2.28)
186.5 (7.34)
29.5
29.5
(1.16) (1.16)
73.05 (2.88)
Pz
7
(0.28)
98.6 (3.88)
37
(1.46)
Y1
30.05
(1.18)
39 (1.53)
7 (0.28)
33
(1.30)
48.6 (1.91)
2 (0.08)
65 (2.56)
188.5 (7.42)*)
103 (4.05)
*)
88.1 (3.47)
90.1 (3.55) *)
15.5 (0.61)
14.5 (0.57)
5/23
Siemens AG 2015
Positioners
SIPART PS2
Dimensional drawings
M20, M25 or
NPT (2x)
14.3
(0.56)
25.7
(1.00)
87.2
(3.43)
136.5
(5.37)
82.5
(3.25)
158.5
(6.24)
3.5
(0.14)
1)
8 (0.31) h9
235.3
(9.26)
M6
4+0.1 (0.16+0.04)
Mounting
plate
>4
(0.16)
25 (0.98)
a = 4 (0.16)
b = 12 (0.47)
Part-turn actuator
6.5 (0.26)
35 (1.38)
F05-Lkr.50 (1.97)
5/24
33.5
(1.32)
10.25
(0.40)
34
25
(1.34) (0.98)
7.75
(0.31)
43
(1.69)
65
(2.56)
4.5
19.25 (0.18)
(0.76)
1)
7.5
(0.30)
233.3
(9.19)
128.5
(5.06)
M6,
8 (0.31) deep (2x)
0
5 7)
(1.9
60
(2.36)
M6,
11 (0.43) deep (4x)
12
(0.47)
33.5
(1.32)
23
(0.91)
7
(0.28)
M8,
14 (0.55) deep (4x)
5 (0
. 2)
Siemens AG 2015
Positioners
SIPART PS2
Schematics
Schematics
Two-wire system
+
4 ... 20 mA
J
6
7
8
9
BE1
10
4 ... 20 mA
Two-wire system
J
6
7
8
9 BE1
10
Three-/Four-wire system
18 ... 30 V
1)
30 V
81
82
24 V
0/4 ... 20 mA
6
7
9
10
1)
2
3
4
5
1)
J
PROFIBUS PA and
FOUNDATION
Fieldbus connection
2
3
4
5
6
7
8
9 BE1
10
BE1
R 250 if req. 1)
lH+
ly = 4 ... 20 mA
lW-
HART
modem
2
3
4
5
6
7
8
PC/Laptop
SIPART PS2 electropneumatic positioner, example of connection for communication through HART for 6DR52..
5/25
Siemens AG 2015
Positioners
SIPART PS2
Mounting kit
Mounting kit for NAMUR linear actuators
1 mounting bracket
2 mounting prisms
1 U-bracket
1 lever arm with adjustable pick-up roll
2 U-bolts
Various screws and lock washers
5/26
Siemens AG 2015
Positioners
SIPART PS2
Mounting kit
Mounting kit for NAMUR part-turn actuators
1 coupling wheel
1 driver pin
8 scales
1 pointer
Various screws and lock washers
Caution: The mounting consoles and the screws for mounting onto the part-turn actuator are not included in the scope of delivery
and must be provided by the customer (see "Technical specifications")
More information
Special versions
On request
5/27
Siemens AG 2015
Positioners
Notes
5/28