HTLT Tender
HTLT Tender
HTLT Tender
C and accordingly
necessary derating has to be done if the ACB
s
rating are specified at
lower ambient temperature.
The release unit shall also have onscreen display of following
measurements:
Current: Phase, Line, Average, Max, % loading
Voltage: Phase, Line, Average
The make & model of ACBs for outgoing feeders shall be as under:
L&T U-power series with UN-RS 2.5GC / Siemens 3WL series with 45 B
/ Schneider Masterpact NW series with 6.0A/ ABB SACE with PR123 P
/ GE M-Pact with MPro 50
All ACBs shall be provided with removable arc chutes and the
mechanical spring charging mechanism, stored energy type, with
indicators to show Open, Closed, Service & Test positions. The
MILKFED PUNJAB VI - 35 Bidder
-42-
circuit breaker shall be provided with emergency tripping device. This
device shall be available on the front of the panel.
The control supply shall be 240 V AC. 6 NO + 6 NC auxiliary contacts
shall be provided.
The interlocks shall be as under:
It shall not be possible to plug in a closed circuit breaker or to draw
out a circuit breaker in closed position. It shall not be possible to
operate a circuit breaker unless it is in fully plugged-in, test or fully
isolated position. In test position, the breaker shall be tested without
energizing the power circuit. The ACB feeder cubical door cannot be
opened when ACB is ON. However, it shall be possible to defeat this
interlock for inspection purpose. Whenever specified, interlock to
prevent paralleling shall be provided. Closing and trip coils shall work
under the following voltage variation conditions:
Closing coils - 85 % to 110 % of rated voltage
Trip coils - 50 % to 110 % of rated voltage
All ACBs used as incomers shall be provided with under voltage coil
and with shunt trip, while ACBs used as outgoing feeders shall have
shunt trip coil only.
Current rating, short circuit current, protection relays etc. shall be as
specified in feeder details.
The circuit breaker position shall be indicated electrically. The
following indicating colors shall be used:
BREAKER CLOSE - RED
BREAKER OPEN - GREEN
BREAKER AUTO TRIP - AMBER
6.6.8.2 Interlocking among Incoming Feeders:
Electrical and Mechanical Interlocking shall be provided between 2
Nos. Incomer feeder from 1000 KVA Transformer & 1 No Incomer
feeder from DG Set (Future).
MILKFED PUNJAB VI - 36 Bidder
-43-
It should be possible to switch ON either or bot h incoming feeders
from the transformers or incoming feeders from the DG Set at any
given point of time.
All incoming feeders from transformers and DG set shall be
provided with 240 V Under Voltage coil & shunt trip coils while all
outgoing feeders shall be provided with 240 V, AC shunt trip coil
only.
The panels shall be designed for proper protection system & 50 kA
fault level.
NOTE: All ACBs shall be arranged in such a manner they can be
easily serviced when drawn out as per layout drawing which
shall be approved by purchaser. Suitable wheel mounted
jackable type service trolley to be provided for
maintenance of ACBs provided in double tier.
6.6.8.3 Moulded Case Circuit Breakers (MCCBs):
MCCBs shall always be provided with separate rotary operating handle
mechanism with door interlocking. The MCCB
s
shall be of four-pole
construction arranged for simultaneous manual closing or opening of
all the poles of the MCCB and automatic instantaneous tripping on
short circuits. All MCCBSs shall be microprocessor type with in-built
earth fault feature.
Closing mechanism shall be quick make, quick break and trip-free
type. Operating handle shall give a clear ON, OFF and Trip
indications. The MCCBs should preferably have an anti - reclosing
feature.
MCCBs shall be provided with microprocessor based tripping
device with earth fault protection as integral feature of the MCCB.
The MCCBs shall be rated for continuous maximum duty as specified.
The rating of the MCCBs shall be as per the feeder details.
Minimum rated breaking capacities shall be as under:
The MCCBs should have a Service short circuit breaking capacity (Ics)
as well as Ultimate breaking capacities (Icu) as 50 KA at 415 Volts 50
Hz AC.
MILKFED PUNJAB VI - 37 Bidder
-44-
The control voltage of MCCB shall be 240 V AC.
6.6.8.3.1 Protection Releases of MCCB:
Adjustable Overload protection adjustable from 40% to 100% of In.
Adjustable short circuit protection 6 to 9 times Ir upto 400 A
MCCB & 3 to 6 times Ir for above 400 A MCCB.
Adjustable Ground Fault protection with pick up settings from
20% to 50% of In and delay settings from 100 m. secs or 200 m.
secs.
In-built thermal memory.
True RMS sensing.
Accessories:
Internal Accessories - The MCCB should have user friendly clip-
fit type accessories site fittable.
Internal accessories like Shunt / Trip alarm contacts / auxiliary
contacts etc. shall be provided wherever required.
Internal accessories should have double insulation & No side
bias.
Make & Model of MCCB shall be : L&T DSine/Siemens 3 VL/ Merlin
Gerin Compact Series/ABB equivalent.
6.6.8.4 Switch Disconnector Fuse Units:
The load break switches if provided shall be suitable for continuous
maximum rating, air break type and shall have manual quick make /
break mechanism. These shall have positive isolation with positive
indication of contact separation. They shall have high short circuit
making and withstanding capacities. Breaking capacity shall
correspond to AC 23A utilization category. Switch handle shall be
provided with door interlocking arrangement. Also, defeat
arrangement shall be provided to open the door in switch Close
position for testing purpose. Live terminals of the switch shall be
shrouded. Fuses shall be HRC cartridge link type. One set of fuse
pullers to cover entire range of fuses used in the panel also shall be
provided.
6.6.8.5 Current Transformers (CT
s
):
Current transformers shall be cast resin type. Primary and secondary
terminals shall be marked indelibly. CTs shall preferably be mounted
MILKFED PUNJAB VI - 38 Bidder
-45-
on stationery parts. The short time withstand rating of CTs shall be
equal to that of the associated switchgear for one second.
The protection CTs shall be of minimum rating 15 VA, accuracy class
5P and an accuracy limit factor of greater than 10.0. The instrument
CTs shall be of minimum 10 VA, accuracy class 1.0 and an accuracy
limit factor less than 5.0.
Separate CT
s
to be provided for protection and metering purposes.
6.6.8.6 Protective Relays:
In case of any protective relays being specified in addition to the built-
in relays provided with ACBs & MCCBs, the same shall be mounted on
front door of the compartment and accessible for setting and resetting
from the front. Hand-reset flag indicators visible from the front shall be
provided.
All such protective relays, wherever used, shall be back connected,
draw out type suitable for flush mounting and fitted with dust tight
covers. Alternatively, plug-in type relays shall also be acceptable. The
relay cases shall have provision for installation of test plug at the front
for testing and calibration using an external power supply without
disconnecting permanent wiring. It should be possible to short the CTs
through the test plugs.
Auxiliary relays/ contactors shall generally be used for interlocking
and multiplying contacts. Auxiliary contacts shall be capable of
carrying the maximum estimated current. In any case their rating
must not be less than 5 A for 240 V, AC at a power factor between 0.3
to 0.1 and 1.5 A for 100 V, DC (inductive load).
Lower voltage contactors with a series resistance will not be acceptable
for 220 V DC control supply.
6.6.8.7 Measuring Instruments:
These shall be of square pattern having approx dimensions 144 mm x
144 mm for analogue type and 96 mm x 96 mm for digital type, flush
mounting type with range as per corresponding feeder. All AC meters
shall generally be of Digital type for displaying three phases
reading. Suitable selector switch shall be provided if the digital meter
does not have provision for simultaneous display of three phase
readings.
MILKFED PUNJAB VI - 39 Bidder
-46-
Ammeters shall always be CT operated. Necessary auxiliary
instruments like CTs etc. are also included in the scope of supply.
Voltmeter shall be suitable for direct line connection. Voltmeters shall
be connected through fuses only.
The voltmeters and ammeters shall have 3 digit displays whereas the
power factor meter shall have 4 digit displays.
Intelligent Panel Meter (Load Manager) shall be provided with each of
transformers and DG sets incoming feeders of the PCC for the local
measurement & digital display of Multifunctional Electrical
Parameters such as voltage, current, active power, reactive power,
frequency, power factor, active energy, reactive energy, etc. on all three
phases.
6.6.8.8 Indicating Lamps:
Indicating lamps shall be of LED (cluster of high intensity light
emitting diodes) type, suitable for 240 V AC supply. These shall be
provided with translucent covers of red, green and amber colours as
required. These lamps shall be of minimum 22.5 mm dia. Indication
lamps to be provided for all feeders.
6.6.8.9 Push Buttons:
Push buttons shall be of momentary contact type, rated to carry 10 A,
240 V AC with 2 NO + 2 NC contacts. These should be of size 22.5 mm
dia and conform to IP 65 protection to prevent any dust and water
ingress.
Colour codes shall be as under:
Start, Close : Green
Stop, Open / Emergency : Red
6.6.8.10 Contactors:
All contactors shall be suitable for AC3 duty unless specified
otherwise. Contactor coil shall be suitable for 240 Volts, 50 Hz. All
contactors shall be supplied with minimum 2 NO + 2 NC auxiliary
contacts. Minimum contactor rating for power shall be 16 Amp.
MILKFED PUNJAB VI - 40 Bidder
-47-
6.6.7 ANNUNCIATION PANEL:
The alarm and annunciation system, suitable to operate on 110 V DC
supply, shall be incorporated in the LT PCC Panel to comprehensively
indicate the following faults in the system complete with internal
wiring and terminals duly identified for various inputs:
For each transformer feeder panel:
1 For high oil temperature 1 No
2 For Buchholz relay 1 No
3 For high winding temperature 1 No
4 For low oil level 1 No
5 For restricted earth fault relay 1 No
For 11 KV VCB Panel:
1 Over current trip 1 No
2 Short circuit trip 1 No
3 Earth fault trip 1 No
4 Control circuit healthy 1 No
Other annunciation
1 Power Failure 1 No
2 Annunciation for restoration of power from TNEB 1 No
The annunciation panel shall have the following:
Hooter for audible alarm suitable for operation on 110 V, DC
Auxiliary relay for hooter cancellation
Push button for hooter cancellation
Auxiliary relay for audible alarm for restoration of power supply
Battery & Battery Charger Panel for producing 110 V DC with 100
AH SMF batteries.
The scope of work also includes providing and laying required
armoured copper control cables (min. 2.5 mm
2
conductor size) for
entire field cabling up to the output terminals of various relays etc.
as required for carrying annunciation panel signals.
Rating/ details of PCC Feeders:
Sr. Name of Feeder Rating of Feeder Qty
Incoming Feeders:
1 Incomer from Transformer 4P, 1600 A, MDO ACB 2
2 Incomer from DG Set
(Future)
4P, 1600 A, MDO ACB 1
MILKFED PUNJAB VI - 41 Bidder
-48-
Outgoing Feeders:
3 Refrigeration Plant MCC 4P, 1000 A, MDO ACB 1
4 Processing Section MCC 4P, 800 A, MDO ACB 1
5 Existing PCC Panel 4P, 1250 A, MDO ACB 1
6 APFC Panel (400 KVAR) 4P, 630 A, MCCB 1
7 Boiler Panel 4P, 200 A, MCCB 1
8 ETP 4P, 200 A, MCCB 1
9 Welding Feeder with
Industrial Plug & Socket
4P, 63 A, MCCB 1
10 Guest House 4P, 125 A MCCB 1
11 Street Light 4P, 63 A MCB 1
12 Spare -1 4P, 1250 A, MDO ACB 1
13 Spare -2 4P, 800 A, MDO ACB 1
14 Spare -3 4P, 630 A, MCCB 1
15 Spare -4 4P, 63 A, MCB 1
The rating of main bus bars of LT Power Control Centre shall be
TPN, 1600 A, 50 kA breaking capacity.
Single Line Diagram & GA Drawing must be prepared and submitted
for approval to MILKFED PUNJAB before starting fabrication of
PCC & APFC Panels.
6. 7 APFC PANEL WITH AUTOMATIC PF CORRECTION RELAY:
6.7.1 POWER FACTOR IMPROVEMENT PANEL WITH APFCR RELAY :
Power Factor Correction Panel with Microprocessor based Automatic
Power Factor Controlling Relay and bank of capacitors as given in the
data sheet shall be provided for PCC to continuously measure and
monitor the power factor of the electrical system by sensing the total load
from the incomer and switch ON / OFF bank of power capacitors to bring
the power factor of the system to a preset value. The APFCR shall have a
digital power factor meter with 4 digit LCD/ LED display.
Panel to be fabricated with 14 SWG thick cold rolled sheet steel structure,
indoor type, floor mounted, weather and vermin proof. Panel shall be
powder coated with 2 coats of Siemens Grey-RAL 7032 paint shade.
Panel should be suitable for 415 volt, 50 Hz, 3 phase supply.
MILKFED PUNJAB VI - 42 Bidder
-49-
It would consist of
An automatic power factor correction relay, microprocessor based,
with arrangement for sensing the power factor of the inductive load
(minimum 16 channels/outputs considering future) and giving
signal to the feeders of power capacitors as per the setting of P.F.
and electronic circuit to ensure that once a capacitor gets cut off, it
is not put on at least for a minute. The relay should automatically
manage capacitor banks according to the reactive power required to
correct the power factor of the load to the power factor set on the
relay. The capacitors must be turned on and off to correct the
power factor of the load to the power factor set on the relay. The
relay should have automatic and manual mode of operation with an
LED to indicate the operating mode. The auto/manual function
makes it possible to turn the capacitor banks on and off
manually regardless of the line value measured.
For each of capacitor feeder one set of suitable rating MCCB,
contactor, pair of ON/OFF push button and indication lamp shall
be provided. MCCBs for power capacitors shall be provided with
thermo magnetic release only.
Flush mounted, 96 mm x 96 mm square, digital Power Factor meter
having 4 digits LCD or LED display.
Selector switch and CT operated digital Ammeter of size 96 mm x
96 mm.
Selector switch and digital Voltmeter of size 96 mm x 96 mm.
Auto-manual switch and connected circuit to ensure that in
manual mode each capacitor can be put ON/OFF manually also.
Incoming feeder of APFC Panel:
4 Pole, 415 V, 50 Hz, MCCB of 630 A rating with built-in
microprocessor based programmable protection.
Suitable 3 phase and neutral bus bars.
Panel shall have sufficient spare cubicles (space only- for future
provision of capacitors & switch gear and shall be decided at the
time of drawing approval of APFCR panel)
Wiring for all above accessories/functions should be complete and
ready for use. The details of each capacitor bank rating, no. of
capacitor banks for power factor improvement shall be as per details
given in the data sheet and schedule of quantities.
MILKFED PUNJAB VI - 43 Bidder
-50-
All power cabling between PCC and capacitor banks panel and cabling
of each capacitor are included in the scope of work of this package.
Power improvement capacitor banks shall be housed in the APFC
Panel itself and provided with adequate louvers with ventilation fans,
prewired through MCB switch for adequate ventilation.
6.7.2 POWER CAPACITORS BANKS:
The power capacitor banks shall be used to improve the power factor
of an electrical system and shall be housed in the APFC panel itself
and provided with adequate louvers for proper ventilation.
6.7.3 Design Requirements:
Each basic unit is to be built up with a number of elements. These
elements shall be of two layer dielectric design (non-self healing) using
heavy Polypropylene Film, Aluminium Foil and Capacitor Tissue Paper
as required; to ensure that total dielectric thickness is more than 14
micron. Capacitor element must be completely sealed with epoxy
resins to provide maximum humidity protection and highest
insulation. The capacitor elements are to be given adequate outside
insulation and should be put in all welded surface treated MS
containers. The outer surface shall be provided with a coat of
protective primer followed by two coats of synthetic enamel paint of
approved shade. These capacitors shall be impregnated with special
grade of capacitor oil under high vacuum. The metal case shall be
equipped with porcelain bushings to permit connection between power
lines and active capacitors. The unit shall have built-in internal
individual fuses.
All capacitors shall be of APP type.
Externally each capacitor unit shall have two separate earthing points,
name plate confirming to the requirements of IS-2834 (amended up to
date), discharge resistances etc. Each capacitor should be suitable for
operation on 440 V, 3 Phase, 50 Hz AC power supply.
TECHNICAL REQUIREMENTS:
Total bank capacity for each panel: 400 KVAR
No. of basic units X basic unit:
MILKFED PUNJAB VI - 44 Bidder
-51-
6 X 50 kVAR +3 No X 25 kVAR + 2 No X 10 kVAR +1 X 5 kVAR
Voltage rating : 440 V, 3 Phase, 50 Hz AC
6.8 LT POWER & CONTROL CABLES:
6.8.1 LT Power Cables:
Power cables for use on 415 V system shall be of 1100 V grade,
aluminium conductor, XLPE insulated, PVC sheathed, armoured and
overall PVC sheathed, strictly as per IS: 7098 (Part I)/88 for cables of
size 35 mm
2
and above. Power cables of size less than 35 mm
2
shall be
PVC insulated, PVC sheathed, armoured and overall PVC sheathed as
per IS: 1554 (Part I)/88. Unarmoured cable to be used only if
specifically mentioned in schedule of quantities.
6.8.1.1 Schedule of LT XLPE Power Cables:
Sr From To Cable
Size
(mm
2
)
No. of
Runs
Route
Length
(M)
Approx.
Qty (M)
Mode of Cable
Laying
1 1000 KVA
Transformer &
750 KVA
Transformer
New PCC
Panel
3.5 C x
300
4 50 200
Partly
Underground/
Partly Trench
2 New PCC Panel Existing
PCC
Panel
3 50 150 Partly
Underground/
Partly Trench
3 New PCC Panel APFC
Panel
2 15 30 Trench
TOTAL (M) 380
6.8.2 LT Control Cables:
Control cables for use on 415 V system shall be of 1100 V grade,
copper conductor, PVC insulated, PVC sheathed armoured and overall
PVC sheathed, strictly as per IS: 1554 (Part I) 1976. Unarmoured
cables to be used only if specifically mentioned in schedule of
quantities.
MILKFED PUNJAB VI - 45 Bidder
-52-
The size of various cables shall be worked out by the contractor and
details and indicated in single line diagram to be submitted with their
bids. The minimum conductor diameter shall be 2.5 mm
2
.
Copper armoured control cables lot shall comprise of supply & laying
of suitable size & quantity of cables required between HT Breaker
Panel, Transformer, RTCC/OLTC Panel, Annunciation Panel, PCC
Panel, APFC Relay, Battery Charger etc.
6.8.2.1 Schedule of Copper Control Cables:
Scope of copper control cables shall include (but not limited to) the following.
These shall have the adequate no. of cores required functionally plus 20%
spare cores.
1. Control cable required between Transformer and the RTCC Panel
2. Control cable required between Transformer and HT VCB Panel
3. Control cable required between VCB panel and Annunciation panel.
4. Control cable required between PCC and APFC panel for PF control
5. Control cable required for power supply from PCC to HT panel for
controls, indications, HT panel lighting.
6. Any other control cable required functionally as per the contract but not
mentioned above.
Note:
Cables shall be laid underground or in the masonry trenches or on
suitable size cable trays as per approved layout drawings. Supply and
installation of HT/ LT Power cables and control cables includes supply
& fixing of suitable size lugs and glands for cable terminations on both
ends, as required under the battery limits & contractual obligations.
No separate payment shall be made for supply/fixing of the lugs &
glands.
6.9 EARTHING SYSTEM & LIGHTNING ARRESTOR:
The intent of this specification is to define the requirement for the
supply, installation, testing and commissioning of the earthing system
and lightning arrestor.
6.9.1 Earthing Network: The scope of earthing includes complete earthing
system for the four pole structure, HT VCB Panels, transformers, PCC,
MILKFED PUNJAB VI - 46 Bidder
-53-
APFC panels, RTCC Panel, DG set, cable glands etc complete with
suitable earth pits and earth strips as per IS 3043.
6.9.1.1 The entire earthing installation shall be done in accordance with the
earthing drawings, specifications and standard drawings of reference.
The entire earthing system shall fully comply with the Indian
Electricity Act and Rules framed there under. The contractors shall
carry out any changes desired by the Electrical Inspector or the Owner
in order to make the installation conform to the Indian Electricity
Rules at no extra cost. Any changes in the method, routing, size of
conductors etc. shall be subject to approval of the owner / engineer-in-
charge before execution.
6.9.1.2 Excavating and refilling of earth necessary for laying underground earth
bus loops shall be the responsibility of the contractor.
6.9.1.3 The resistance between the earthing system and the general mass of
earth shall be as per IS code of practice. The earth loop impedance to
any point in the electrical system shall not be in excess of 1.0 in
order to ensure satisfactory operation of the protective devices.
6.9.1.4 The main earth loop shall be laid at the depth of 500 mm below ground
level. Wherever cable trenches are available, the earth lead shall be
laid in the trenches and shall be firmly cleated to the walls when
running in concrete lined trenches. The earthing strip shall be
protected against mechanical damage.
6.9.1.5 Joints and tapping in the main earth loop shall be made in such a way
that reliable and good electrical connections are permanently ensured.
All joints below ground shall be welded and suitably protected. Joints
above ground shall be made by means of connectors/lugs as far as
possible. The connectors shall be used for tapping earth leads from the
main earth loop wherever it is installed above ground. Where
aluminium risers are to be connected to the underground GI earth
bus, the aluminium riser shall be taken to the nearest earth pit and
terminated through a bolted joint. If this is not practicable then GI
riser shall be brought above ground and a bolted joint shall be made
between this GI riser and the aluminium riser.
6.9.1.6 Conduits in which cables have been installed shall be effectively
bonded and earthed. Cables armouring shall be earthed at both ends.
MILKFED PUNJAB VI - 47 Bidder
-54-
6.9.2 Earth Pits & Electrodes:
6.9.2.1 Earth pits and the plate electrodes (of 600 mm x 600 mm x 6.3 mm
thick GI plate) of earth pits shall be installed for body earthing of
substation electrical equipment in accordance with the standard
drawings of reference and latest amendment of IS: 3043- 1987.
However, the earth pits for neutral earthing of transformers and DG
Sets shall have copper plate electrode of 600 mm x 600 mm x 3.15
mm. The earth pit shall be complete with GI pipe and funnel for
watering, necessary quantity of salt & charcoal and a masonry
chamber with hinged CI cover. Their location shall be marked to
enable accurate location by permanent markers.
6.9.2.2 All earth electrodes shall preferably be driven to a sufficient depth to
reach permanent moist soil. Electrodes shall preferably be situated in
a soil which has a fine texture and which is packed by watering and
ramming as tightly as possible. Wherever practicable the soil shall be
dug up, all lumps broken and stones removed from the immediate
vicinity of the electrodes.
6.9.2.3 All earth electrodes shall be tested for earth resistance by means of
standard earth test meter. The tests shall take place in dry months
preferably after a protected dry spell. If necessary a number of
electrodes shall be connected in parallel to reduce the earth resistance.
In such a case, the distance between the electrodes shall preferably be
not less than twice the length of the electrode.
6.9.2.4 The electrodes shall have a clean surface not covered by paint,
enamel, grease or materials of poor conductivity.
6.9.2.5 The exact location and number of earth electrodes required at each
location shall be determined in the field in consultation with the
owner/engineer-in-charge or his authorized representative, depending
upon the soil data and resistivity to meet the ohmic values as per
statutory requirement.
6.9.2.6 The distance of Earth Pit centre from the nearest building shall not be
less than 3 meter. Also, the earth pit to earth pit distance shall not be
less than 3 meter.
6.9.2.7 Test disconnect facility shall be provided for the earth pits to check
their earth resistance periodically.
MILKFED PUNJAB VI - 48 Bidder
-55-
6.9.3 Connection:
6.9.3.1 All electrical equipment under the scope of this tender is to be doubly
earthed by connecting two earth conductors from the frame of the
equipment to a main earthing ring. The earthing ring will be connected
via links to several earth electrodes. The cable armouring will be
earthed through the strips cable glands.
6.9.3.2 In hazardous areas, all major process equipment shall be connected to
the earthing ring by means of anti-loosening connections and all
pipelines will be bonded and earthed on entering the battery limit of
the process area.
6.9.3.3 The following shall be earthed:
Transformers
Neutral earthing,
Body earthing of
HT VCB switch
Shall have two earth pits per transformer with
600 X 600 X 3.15 mm Copper plate
Electrode for neutral earthing. These shall be
independent of all other earth pits
Body earthing of
Transformers,
APFC Panels, 4
pole structure
Shall have earth pits with 600 X 600 X 6.30
mm GI plate electrode. These earth pits shall
be connected in ring mains and shall be
independent of neutral earthing and lightning
arrestor earthing.
Lightning
arrestor of 4 pole
structure
Shall have earth pits with 600 X 600 X 6.30
mm GI plate electrode. These shall be
independent of all earth pits meant for body
earthing & neutral earthing of electrical
equipment in the substation.
All fences/
enclosures
housing
electrical Equip
Shall have earth pits with 600 X 600 X 6.30
mm GI plate electrode. These shall be
independent of all earth pits meant for earthing
of four pole structure and neutral earthing of
DG sets and transformers
Number of earth pits and conductor size for connection to various
equipment shall be as per the requirement / approval of the
purchaser/owner and meet the requirement of local electrical
inspectorate.
MILKFED PUNJAB VI - 49 Bidder
-56-
6.9.3.4 System shall be earthed by two distinct conductors directly connected to
independent earth electrodes, which in turn shall be connected to the
earth loop.
The earth connection shall be properly made. A small flexible
aluminium loop to bridge the top cover of the transformer and the tank
shall be provided to avoid earth fault current passing through fastening
bolts when there is a lightening surge, high voltage surge or failure of
bushings.
6.9.3.5 All paint, scale & enamel shall be removed from the contact surface
before the earthing connections are made.
6.9.3.6 Earth connections at the equipment terminals shall be made in a
mutually agreed manner. Anchor bolts or fixing bolts shall not be used
for earthing.
6.9.3.7 All hardware used for earthing installation shall be hot dipped
galvanized or zinc passivated. Spring washers shall be used for all
earthing connections of equipment having parts of vibrations.
6.9.4 Testing:
Earthing systems/connections shall be tested as follows :
i) Resistance of individual electrodes shall be measured after
disconnecting it from the grid.
ii) Earthing resistance of the grid shall be measured after connecting all
the electrodes to the grid and generally the test value shall conform
to IS Code of practice unless otherwise specified.
iii) The resistance to earth shall be measured at the following:
a. At each electrical system (earth or system neutral earth)
b. At one point on each earthing system used to earth electrical
equipment enclosures.
c. At one point on each earthing system used to earth wiring
system enclosures such as metal conduits and cable sheaths
or armour.
d. At one point on each fence enclosing electrical equipment.
Measurement shall be made before connection is made between the
ground and the object to be grounded.
MILKFED PUNJAB VI - 50 Bidder
-57-
6.10 RUBBER MATS:
Neoprene rubber mats of thickness 12 mm minimum suitable for the
applicable HT/LT voltage grade and conforming to the IS: 5424
specifications shall be supplied for HT Panels, Battery charger, LT
Power Control Centre, APFC Panel, RTCC Panel etc.
6.11 SAFETY ACCESSORIES & MISCELLANEOUS ITEMS:
The supply and installation, wherever applicable, of following sub-
station safety accessories and miscellaneous items is included under
the scope of work of this contract:
Fire extinguishers as per details given below shall be provided by
the contractor :
a) Foam type 2 nos. for Transformers (capacity 2 L each)
b) CO2 type 2 nos. for LT Panel (capacity 4.5 kg each)
c) CO2 type 1 no. for HT Panel (capacity 4.5 kg each)
d) Fire Buckets (5 No) mounted on MS Stand (1 No) 1 Set for
Transformer Yard
Hand Gloves suitable for the applicable HT voltage grade 2 pairs
VCB breaker operating tools and tackles 2 Sets
Danger Boards, Shock Treatment Chart, Artificial Resuscitation
Unit, First-aid box etc. which are required as per statutory
regulations 1 Lot
6.12 CABLE TRAYS:
(Not applicable to this job)
6.13 MS STRUCTURAL STEEL FOR INSTALLATION OF PANELS:
MS channels of suitable cross section shall be provided by the
substation contractor across the masonry trench in substation building
for supporting VCB panels, battery charger, RTCC Panel, LT power
control centre and APFC panels. Also, 50X50X6 mm MS nosing angles
for cable/panel trenches shall be supplied & fixed by the contractor.
Chequered plate covers minimum 6 mm thickness shall also be
provided over the open portion of the masonry trench in substation &
PCC Room. All MS structures/supports and chequered plates (both
MILKFED PUNJAB VI - 51 Bidder
-58-
sides) shall be painted with 2 coats of red oxide primer followed by 2
coats of paint of shade Siemens Grey - RAL 7032.
6.14 LIST OF APPROVED MAKES OF EQUIPMENT & ACCESSORIES:
MAKES OF ELECTRICAL ITEMS
NAME OF ITEMS APPROVED MAKES
HT VCB Panel SIEMENS/ ABB / AREVA T&D/
ALSTOM/KIRLOSKAR/ L&T/ GE
Distribution Transformer (Oil
Filled Type)
SIEMENS / BHARAT BIJLEE / AREVA
T&D/ VOLTAMP / KIRLOSKAR
Dry Type Distribution
Transformer
SIEMENS / BHARAT BIJLEE / AREVA
T&D / VOLTAMP / KIRLOSKAR/ GE
Air Circuit Breaker L&T U-power series with UN-RS 3 /
Siemens 3WL series with 76 B /
Schneider Masterpact NW series with
6.0P/ ABB SACE with PR123 P / GE M-
Pact with MPro 50
MCCB L&T D SINE / LEGRAND / SIEMENS 3
VL / MERLIN GERIN Compact series/
ABB Tmax/ GE Record Range / HAGER
Protection Relays L&T / SIEMENS / ABB / AREVA T&D/
ASHIDA
Contactors L&T / SIEMENS / ABB / SCHNIEDER/
GE
Timers Electronic L&T / SIEMENS / GE/ ABB/
SCHNIEDER
Switch Dis-connector Fuse
Units
L&T / SIEMENS / ABB
/SCHNIEDER/GE
MCB SIEMENS / HAGER / MERLIN GERIN /
LEGRAND/ABB/ L&T/ GE/
SCHNIEDER
MILKFED PUNJAB VI - 52 Bidder
-59-
Indicating Lamps L&T / SIEMENS / SCHNEIDER /
VAISHNO / TEKNIC / PRECIFINE/ ABB
Push Buttons ESBEE / SIEMENS / ABB / VAISHNO /
TEKNIC/ L&T
Load Manager SIEMENS/ ABB/ L&T / SCHNEIDER/
CONZERV/ ALLEN BRADLEY
(ROCKWELL)
Digital Ammeter & Voltmeter CONZERV / L&T / HPL SOCOMEC
Analog Ammeter & Voltmeter RISHABH / IMP / AE/ L&T
Digital Energy Meter CONZERV / L&T / HPL SOCOMEC / AE
PVC Conduit & accessories PRECISION / POLYCAB / CLIPSAL
Power Factor Meter RISHABH / IMP / MECO / AE/ L&T
Current Transformer KAPPA / AE / IMP /GILBERT/
MAXWELL/ ASHMORE
HT XLPE Power Cables GLOSTER/ CCI / RPG ASIAN /
FINOLEX / NICCO
LT XLPE Power Cables GLOSTER/ CCI / RPG ASIAN /
FINOLEX /LAPP KABEL / NICCO
LT Copper Control Cables LAPP KABEL / CONCAB / CCI / RPG
ASIAN / FINOLEX / RR KABELS
(UNILAY) / GLOSTER / POLYCAB
Signal & Instrument cable LAPP KABEL / CONCAB / POLYCAB/
FINOLEX/LAPP KABEL/DIGILINK
Power Capacitors SIEMENS/ EPCOS / MEHER / L&T/
ABB/ SCHNIEDER / GE
APFC Relay SIEMENS / EPCOS / L&T/ ABB/
SCHNEIDER/ GE
MILKFED PUNJAB VI - 53 Bidder
-60-
Cable Tray INDIANA / MEK / SUNRISE / SUPER /
PILCO
Isolating Switches SIEMENS / L&T / SCHNEIDER
HRC fuses L&T / SIEMENS / GE/ ABB
Terminal Blocks WAGO / LAPP INDIA / CONNECT
WELL/ ELMEX
Potential Transformers KAPPA / IMP / AE / ASHMORE/
GILBERT/ MAXWELL
Rotary Selector Switch KAYCEE / SALZER - L&T / SIEMENS /
ABB
Cable Glands COMET / EX-PROTECTA / DOWELS /
LAPP KABEL
Cable Lugs DOWELS / COMET / LAPP KABEL
Mechanical Interlock L&T / SCHNEIDER / ABB/ GE
XLPE cable jointing /
terminating kit
RAYCHEM / M-SEAL
Programmable Protection
Relay
MINILEC/ ABB/ L&T/ SIEMENS/
SCHNIEDER/ GE
LT Sandwich Bus duct L&T/ GE/ C&S/ SIEMENS/ ABB/
SCHNIEDER
Steel Structure SAIL/ESSAR/TISCO/ JINDAL
7.0 BATTERY LIMIT:
This specifies in brief the scope of the contractor and Owner/ Purchaser
by specifying the limits at which contractors scope Starts and Ends.
PURCHASERS SCOPE CONTRACTORS SCOPE
Electric Sub-station
Civil Works:
Providing all necessary
foundation bolts, foundation
plates and templates. All civil
buildings for the indoor type
MILKFED PUNJAB VI - 54 Bidder
-61-
equipment and RCC
foundations/platforms for
installation of transformers.
RCC Hume pipes for crossing
roads. Civil works related to
laying of underground cables,
such as digging of trenches,
providing sand and bricks
etc., and for fixing cable route
markers
Fencing with related civil works
for Transformer Yard.
Civil works related to earth
pits such as digging/ re-filling
of earth, making watering
chambers etc.
Civil works related to
installation of Four Pole
structure
Supply and grouting of
additional MS angles/
channels supports/ brackets
for installation of equipment,
cable trays and laying cables
in trenches inside the
building. Supply and
installation of MS nosing
angles & chequered plate
covers for cable/panel
trenches in substation yard &
PCC Room building. RCC
cable trenches in transformer
yard and sub- station building
for laying HT/LT cables
Clearing of site, de-watering, if
water logging is encountered
during digging for cable laying
/earth pits/ Four pole
structure erection etc.
MILKFED PUNJAB VI - 55 Bidder
-62-
Electrical Works:
Illumination in sub-station
building and transformer area
Scope starts from outgoing
side of the State Electricity
Boards out door H. T.
Swi t ch out si de t he Pl ant
bui l di ng. HT Meter and
ends at PCC. However,
supply and laying of power
cables from new PCC to new
APFC Panel and from new
PCC to the existing PCC,
including termination at both
ends, are within scope of
contractor.
Supply and installation of
earth continuity strip/
conductor as per statutory
requirement.
8.0 TECHNICAL DATA AS PROVIDED BY THE CONTRACTOR:
The information on technical data to be provided by the supplier are
as following:
Transformers Critical Technical Data
1. No load losses at rated voltage & frequency :
2. Full load losses at rated current at 75 Deg. C. :
3. Impedance at rated current & frequency at 75 Deg. C. :
4. Efficiency at full load 0.8 P.F. lagging at 75 Deg. C. :
5. Approximate quantity of oil required for first filling :
6. Max. rise in winding temperature (above ambient temp.):
7. Max. rise in oil temperature (above ambient temp.) :
8. Duration and percentage overloading :
MILKFED PUNJAB VI 56 Bidder
-63-
9. Losses of transformer at 0.8 pf
100% load of transformer rated
capacity :
75% load of transformer rated
capacity :
50% load of transformer rated
capacity
& 25% load of transformer rated
capacity :
PCC Critical Technical Data
1. Fault Level :
2. Class of Protection :
9.0 APPLICABLE BIS CODES &
STANDARDS:
The switchgear and the mounted equipment shall conform to the latest
revision of the following Indian Standards:
IS: 12729 General requirements for switchgear and control gear for
voltages exceeding 1000 V
IS: 13118 General requirements for circuit breakers for voltages
exceeding 1000 V
IS: 3427 Metal enclosed switchgear and control gear for voltages above
1000V but not exceeding 11000 V
IS: 5082 Material data for Aluminium bus bars
IS: 9920 Switches and switch isolators for voltages above 1000 V
IS: 9921 AC disconnectors (isolators) and earthing switches for
voltage above 1000 V
IS: 9046 AC contactors of voltage above 1000 V upto & including
11000V
IS: 13703 Low voltage fuses
IS: 2705 Current transformers
IS: 3156 Voltage transformer
IS: 3231 Electrical relays for power system protection
MILKFED PUNJAB VI - 57 Bidder
-64-
IS: 6875 Control switches and push buttons
IS: 694 PVC insulated cables for working voltages up to and
including 1100V
IS: 11353 Guide for uniform system of marking and identification of
conductors and apparatus terminals
IS: 5578 Guide for marking of insulated conductors
IS: 3618 Phosphate treatment of iron and steel for protection against
corrosion
IS: 6005 Code of practice for phosphating of iron and steel
IS: 772 Part-I AC Electricity Meters: Part I general requirements
and tests
IS: 1248 Direct acting electrical indicating instruments
IS: 3618 LV Switchgear and control gear
IS: 5 Colors for ready mixed (Part-I to Part-5)
MILKFED PUNJAB VI - 58 Bidder
-65-
10. Item wise Price Schedule for Part A (Design, Fabrication & Supply)
and Part B (Installation, Testing and Commissioning)
Sr
Item Description
Qty Unit Part-A Part-B
Unit Rate
(Rs.)
Total
Price (Rs.)
Unit Rate
(Rs.)
Total
Price (Rs.)
1 11 KV, HT Breaker
Panel with 1 No. 11
KV VCB, 630 A with
steel sheet enclosure
indoor type including
protection relays and
measuring
instruments as per
specs
3
No
2 11 kV, XLPE, Al Arm
HT Cable of size 3C X
240 mm
2
including
suitable lugs, glands
& terminations at
both ends. HT cable
shall be laid
underground as per
specs.
300 M
3 Distribution
Transformer, 1000
KVA, 11 kV/ 433 V
with OLTC & RTCC
Panel as per specs
1 No
4 1.1 kV gr. Aluminium
Armoured, LT XLPE
Cable, 3.5 C X 300
mm
2
with suitable
termination lugs &
glands on both ends
380 M
5 LT Power Control
Centre with
Annunciation Panel
as per specs
1 No.
MILKFED PUNJAB VI - 59 Bidder
6 Battery & Battery
Charger Panel, 110 V
DC with 100 AH SMF
batteries as per specs
1 No.
7 APFC Panel, each
with Capacitors
banks & feeders for
6X50 KVAR, 3X25
KVAR, 2 X 10 KVAR &
1X 5 KVAR with APFC
Relay (Total 400
KVAR)
1 No
8 1.1 kV grade,
armoured copper
control cables of
different sizes
1 Lot
9 Copper Plate Earth
Pits complete with
masonry chambers
and CI hinged covers
4 No
10 GI Plate Earth Pits
complete with
masonry chambers
and CI hinged covers
6 No
11 Copper Earthing Strip
(50 X 6 mm)
100 M
12 GI Earthing Strip
(50 X 6 mm)
200 M
13 Electrical grade
Neoprene rubber mats
suitable for applicable
HT & LT Voltage as
detailed in specs
1 Lot
14 Safety Accessories,
fire extinguishers, fire
buckets, hand gloves
& other
miscellaneous items
as detailed in specs
1 Lot
15 MS Structural
supports and
chequered plates etc
1000 Kg
MILKFED PUNJAB VI - 60 Bidder
duly painted as
detailed in specs.
16 Disconnection of LT
cables between
existing 750 KVA
Transformer and
existing PCC Panel
- Job
17 Testing &
commissioning of all
items/ equipment of
sub-station including
all statutory
approvals.
- Job
Total (in Rs.)
Rupees in word:
NOTE:
For the quantities of HT/LT power & control cables, earthing strips and pits etc.
bidders are requested to submit the tentative schematic diagram showing the
location of various electrical equipment, cable routes, nos. of earth pits and
sizes of various cables and earth strips. However, execution shall be as per the
statutory requirement and the drawings approved by MILKFED PUNJAB/ office
of electrical inspectorate of the area where the project is being executed.
Required quantities for supply & installation of HT/ LT power cables, earthing
etc must be assessed as per site conditions by the bidder and supplied as per
actual site requirement only. Payment will be made as per unit rates on total
quantities supplied & installed/consumed at site.
MILKFED PUNJAB VI - 61 Bidder
-66-
SCALE= SINGLE LINE DIAGRAM FOR NEW PROPOSED ELECTRICAL
EXPENSION OF CHANDIGARH MILK PLANT 11kv Supply FromChd
Electricity Board
PT
600 KVA DG SET C.T
11 KV VCB PROPOSED NEW DG SET
630 A (No.1) 1000
ACB 1000A
11 kv VCB 11 kv VCB
630 A (NO.2) 630 A (No.3)
TRF. NO. 1 TRF. NO. 2
750 KVA, 11KV/415V 1000 KVA,
11KV/415V
LT BKR NO. 1 LT BKR NO.2
(ACB) 1600 A, 4P (ACB) 1600
A, 4P
ACB, 1000 A LT BKR. NO.3
ACB 1600A
(600 KVA DG) 1000 A (ACB)
BUS COUPLER
ACB 1000A
ACB 1000A
Ice cream Milk Recp. Boiler APS ETP Lighting Spare
Ref. Section
Section SectionSection DB
OLD PCC NEW PROPOSD PCC
-67-
LAYOUT OF NEW PROPOSED ELECTRICAL SUB STATION
DRAWING NO. - 2
Boiler side
20 ft 15 ft 25 ft
1000 KVA Exiting MCC
Transformer 11KV VCB
35 ft
Ref.
Boiler MCC
SPARE
New MCC
60 FT
SUB STATION FRONT AUDI SIDE
750 KVA
Transformer
600
KVA
DG
SET
1 2 3
-68-
LAYOUT OF OLD EXISTING ELECTRICAL SUB STATION
DRAWING NO. - 3
Boiler side
20 ft 15 ft 25 ft
Spare Space for Exiting MCC
Proposed 1000 KVA 11KV VCB
Transformer Metering Unit 35
ft
Ref.
Boiler MCC
Spare
60 FT
SUB STATION FRONT AUDI SIDE
300 KVA
DG SET
ROOM
750 KVA
TRANSFORMER
350 KVA
DG SET
600
KVA
DG
SET