A Complete Narrow-Band Power Line Communication Node For AMR
A Complete Narrow-Band Power Line Communication Node For AMR
A Complete Narrow-Band Power Line Communication Node For AMR
Lotito
STMicroelectronics S.r.l.
Via Olivetti, 2
20041 Agrate B. (MI) - Italy
R. Fiorelli
DORA S.p.A.
Via Lavoratori Vittime del
Col Du Mont, 24
11100 Aosta (AO) Italy
D. Arrigo
STMicroelectronics S.r.l.
Via Olivetti, 2
20041 Agrate B. (MI) - Italy
R. Cappelletti
STMicroelectronics S.r.l.
Via Tolomeo, 1
20010 Cornaredo (MI) - Italy
Abstract- In this paper it is reported the description of a
demonstrator implementing a low data rate Power Line
Communication node, developed for Automated Meter Reading
applications. This study is focused on investigating those aspects
of the communication node design impacting most on the
requirements for compliance with communication on the
electrical network environment. Design choices, compliance tests,
thermal analysis and experimental results are described in this
paper.
Index Terms- Power line communication, automated meter
reading, analog front-end, power amplifier, line coupling, thermal
impedance.
I. INTRODUCTION
When designing a Power Line Communication (PLC) node,
attention is required to make this node capable to operate in a
complex and challenging environment like the power line. One
of the most restrictive requirements is the compliance with the
European EN50065 standard for signaling on low voltage
electrical networks [1].
The requirements set by this standard are not only related to
conducted emissions, according to EN50065-1, but also to
impedance magnitude limits fixed by EN50065-7 and to
immunity against conducted interferences as required by
EN50065-2-1.
The specific structure of the coupling interface is a weak
point of the application against high voltage disturbances that
can come from the external environment. The immunity
requirements to be addressed are the ones listed in the
EN50065-2-1 document, which refers to EN61000-4 for the
tests to be applied [2].
Analysis of the thermal behavior with respect to the required
output power is fundamental for a PLC node design. Such
analysis has to take into account the operating conditions of a
typical Automated Meter Reading (AMR) application, which is
the target application for the described PLC solution. A thermal
study, oriented to EN50065-1 compliance, is presented in this
paper.
II. DESCRIPTION OF THE COMMUNICATION NODE
DEMONSTRATOR
The PLC communication node described in this paper has
been designed to operate within the so called A-band, from 9 to
95 kHz, dedicated to AMR. The architecture of the PLC node
demonstrator is reported in the block diagram of Fig. 1, which
shows the various sections of the module. The demonstrator
hosts the new ST7540 FSK power line transceiver, supplied by
a Switching Mode Power Supply (SMPS) in flyback
configuration, and controlled by an external host. The external
circuitry for the PLC transceiver is composed of a 16 MHz
crystal resonator driven by the internal oscillator, a passive R-C
network for the transmission active filter based on the internal
A complete Narrow-Band Power Line
Communication node for AMR
Fig. 1. Block diagram of the PLC node demonstrator
1-4244-1090-8/07/$25.00 2007 IEEE. 161
Power Amplifier (PA), and the line coupling interface
including passive filters and protections against high energy
disturbances from the line.
A photograph of the PLC demonstrator is shown in Fig. 2.
The three main sections are highlighted: the SMPS section, the
transceiver IC section and the line coupling interface.
Description of the transmission active filter, the coupling
interface and the SMPS is included below.
A. Transmission Active Filter
The integrated PA of the transceiver, whose input and output
lines are externally available, has been configured to
implement an active filter whose schematic is reported in Fig.
3. It is a 3-pole active filter, made up of the R3-C2 low-pass
stage and of a 2-pole Sallen-Key cell. Capacitor C1 for dc
decoupling and R1-R2 resistor partitioning are included to set
the optimum bias for the PA input.
A Chebyshev type low-pass filter has been chosen to have
high rejection on 2
nd
harmonic of the transmitted signal, well
higher than the rejection obtainable with a passive filtering.
The filter has been dimensioned to have a dc gain of 9 dB, to
get the correct output bias (depending on the input bias
multiplied by the dc gain) and to exploit the output voltage
dynamic range. Both factors contribute to obtain high linearity.
Measured frequency response is shown in Fig. 4. The filter,
designed for the 72 kHz channel, has a corner frequency at 87
kHz, a maximum ripple of 1 dB and a 2
nd
harmonic rejection of
about 9 dB at 144 kHz.
B. Line Coupling Interface
Interfacing to the power line requires a passive circuit to
obtain selective coupling for the signal in transmission and
reception. This requires both an adequate frequency response,
to ensure good performance on the communication channel,
and correct impedance at the line connection, to comply with
EN50065-7 requirements on the impedance seen from the line.
It has been chosen the coupling topology shown in Fig. 5.
The 50 Hz mains voltage is filtered by the L-C high-pass filter
made up of C8, L1 and the magnetizing inductance of the
transformer T1 (about 1 mH). The transmitted signal coupling
includes capacitor C7 for dc decoupling, L1-C8 series
resonance for band-pass filtering and transformer T1 for high
voltage isolation. The receiving filter is made up of series
resistor R8, L2-C9 parallel resonant circuit for band-pass
response and capacitor C10 for dc decoupling at the receivers
input.
This line coupling topology includes a protection structure
capable to clamp high energy disturbances coming from the
mains as either differential or common mode interferences. The
protection structure is made up of D1 and D2, aimed at
clamping fast common mode disturbances, and D3, for
absorbing high energy differential disturbances. T1 also
introduces suppression of common mode disturbances.
C. Switching Mode Power Supply
The small size and good efficiency ( = 70% at full load)
power supply included in the PLC node demonstrator has been
designed for compatibility with the PLC communication. A
SMPS is required to supply a power amplifier having 35%
Fig. 2. Photograph of the PLC node demonstrator with its different sections
Fig. 3. Schematic of the active Tx filter based on the integrated PA
-20
-15
-10
-5
0
5
10
15
1.0E+04 1.0E+05 1.0E+06
Frequency (Hz)
G
a
i
n
M
o
d
u
l
u
s
(
d
B
)
-200
-150
-100
-50
0
50
100
150
200
P
h
a
s
e
(
d
e
g
r
e
e
s
)
Fig. 4. Typical frequency response of the active filter
Fig. 5. Schematic of the line coupling circuit
+12V
D1
1N4148
D2
ESDA14V2L
P
L1
47 uH
C8
100nF X2
C7
10uF
T1
D3
TRANSIL 12V
N
PA_OUT
R8
750
L2
220 uH
C9
22 nF
C10
10 nF
Rx_IN
C4
PA_OUT
C2
390 pF
Tx_OUT
C5
22 pF
R3
3k9
R1
25k
C1
100 nF
R4
4k7
R5
12k
PA
PA_IN-
C3
150 pF
PA_IN+
150 pF
R6
1k
R2
15k
+5V
R7
1k8
C6
15 pF
162
efficiency and driving the power line, which typically shows
very low impedance. The SMPS output voltage of 12 V dc sets
the dynamic range of the PA output signal to 7.5 V peak-to-
peak, within which the PA output stage will show a linear
behavior.
The input filter of Fig. 6 has been introduced at the mains
connection of the SMPS. One purpose of the filter is to reject
disturbances generated at switching frequency by the power
supply. Common mode conducted emissions are filtered by
common mode choke L4, while differential mode conducted
emissions are reduced by the leakage inductance of L4 and the
X2 safety capacitor C11.
This specific input filter implementation is also aimed at
ensuring that the SMPS shows input impedance being as high
as possible at the communication frequency, for compatibility
with the PLC transceiver. In particular, inductor L3 and resistor
R9 prevent the transceiver from being loaded by the low
impedance of C11.
R9 is also designed in order to damp the resonant circuit
composed of L3, C11 and the transceivers line coupling
circuit. R9 value is chosen as a compromise between SMPS
efficiency and robustness against high voltage disturbances
from the line.
III. PLC TRANSCEIVER ARCHITECTURE
The module is built around the new ST7540 FSK
transceiver, realized in Multipower BCD 0.6 m technology to
allow the integration of digital, analog and power circuitry in
the same chip [3]. It operates from a single 12V power supply.
The internal block diagram of the IC is shown in Fig. 1. The
SPI host interface allows setting the operating parameters of
the device through access to the internal Control Register.
Eight different communication channels are available; six of
them (60, 66, 72, 76, 82.05, 86 kHz) are within the A-band. For
our tests, the IC has been programmed to communicate at 72
kHz channel frequency, 4800 baud and deviation 1, as the
parameters for the binary FSK modulation.
A. Analog Front-End and Power Amplifier
The transmitted signal is generated by a Digital Direct
Synthesis (DDS) circuit at channel frequency plus or minus the
frequency deviation set by the programmed baud rate. The
digital signal is converted to analog by an 8-bit DAC and
properly filtered. The filtered signal is then regulated by an
Automatic Level Control (ALC) block, driven by the voltage
and current automated controls. The IC integrates a class AB
linear Power Amplifier able to provide an output signal for the
ST7540 transceiver up to 130 dBV rms. The behaviour of the
ALC block is illustrated by Fig. 7. An external resistor
partitioning fixes the desired PA output voltage level, kept
constant by the ALC until the load impedance goes under a
Z
LIMIT
value corresponding to the current limit, set by another
external resistor. If the current limit is reached, the PA output
voltage level is reduced step by step until the output current is
again under the threshold value.
IV. NORMATIVE REQUIREMENTS AND TESTS
A. Spectrum of the Transmitted Signal
The EN50065-1 document sets the limits for transmission
level and spurious conducted disturbances of equipments
communicating within the A-band. Those limits refer to the
signal measured on the 50 measure port of the artificial mains
network defined by CISPR 16-1 document [4]. Different limits
on the transmission level are set for narrow-band and wide-
band signals. If the signal bandwidth at -20 dB is equal to or
greater than 5 kHz, the signal is considered as wide-band and
the limit is defined as 134 dBV rms over the whole signal
bandwidth and 120 dBV rms when measuring with a peak
detector having a bandwidth of 200 Hz. In the case of an FSK
modulation, the main constraint is the spectral density limited
at 120 dBV rms, because the FSK spectrum is characterized
by two narrow peaks corresponding to 0 and 1 symbols.
B. Immunity Requirements
The most disturbing interferences for a PLC node are surges
and fast transients from the line. For this kind of disturbances,
the EN50065-2-1 document requires to perform the immunity
tests described in Table I. The criterion for compliance is that a
temporary degradation or loss of function, with automatic
recovery, may occur, while no change in operating state is
allowed.
C. Input Impedance
EN50065-7 document sets the impedance constraints for
equipment operating in the A-band. The purpose is to avoid
introducing attenuation on signals from other devices on the
line. Impedance limit masks are shown in Fig. 10 and Fig. 11.
Fig. 6. Schematic of the input filter for the SMPS
I zone
V zone
O
u
t
p
u
t
S
i
g
n
a
l
L
e
v
e
l
(
V
r
m
s
)
Current
Control
Zone
Voltage
Control
Zone
Line impedance modulus (ohm)
ZLIMIT
I zone
V zone
O
u
t
p
u
t
S
i
g
n
a
l
L
e
v
e
l
(
V
r
m
s
)
Current
Control
Zone
Voltage
Control
Zone
Line impedance modulus (ohm)
ZLIMIT
Fig. 7. Output voltage level vs. line load
TABLE I
IMMUNITY TESTS
TEST
TYPE
TEST
SPECIFICATIONS
BASIC
STANDARD
Surges
Trise =1.2 us, Thold =50 us
1 kV common mode (peak)
0.5 kV differential (peak)
EN61000-4-5
Fast transients
Trise =5 us, Thold =50 ns
1 kV (peak)
5 kHz frequency
EN61000-4-4
N
C11
33 nF X2
To the
bridge rectifier
L4
R9
10 / 6 W
L3
1 mH
P
2x10 mH
163
D. Compliance Measurements
First of all, the compliance with the limits on the output
spectrum has been verified. For this purpose, wide-band case
has been addressed, transmitting at 4800 bps to have a signal
bandwidth greater than 5 kHz. Fig. 8 shows the measured
spectrum, which shows a signal bandwidth of about 10 kHz.
The PA output level chosen to achieve compliance with the
EN50065-1 document is 128 dBV rms; this equals to 122
dBV rms measured at CISPR 16-1 artificial mains network
over the whole signal bandwidth, or 116 dBV rms when
measuring the two narrow peaks of the FSK spectrum as in Fig.
8. Setting the output level at 128 dBV rms, i.e. 7 V peak-to-
peak, allows keeping the signal inside the PA output dynamic
range, thus ensuring the linearity needed to respect the
disturbance mask. This is proven by the measured output
spectrum shown in Fig. 9, in which the EN50065-1 conducted
disturbance limit mask is drawn for comparison.
Once the performance of the circuit in terms of spectral
purity has proved to be satisfying, the next check regarded the
impedance offered to the line by the PLC node. Results shown
in Fig. 10 and Fig. 11 demonstrate the compliance with the
EN50065-7 document requirements.
The immunity against the possible interferences from the
power line, as listed in the EN50065-2-1 document, has also
been tested (see Table I). These tests have made possible to
guarantee the capability of the PLC node to operate in a very
noisy and disturbing environment like the power line
communication scenario.
V. THERMAL ANALYSIS
The power dissipation of the power amplifier stage, driving
the power line, is the main cause for the overheating of the
PLC transceiver. According to the desired output level (V
OUT
)
and the line impedance (Z
L
), the PA will have to dissipate a
power equal to:
= 1
1
2
L
rms OUT
D
Z
V
P
. (1)
Assuming V
OUT rms
= 128 dBV, = 35% and a typical load
impedance of 4, the resulting power to be dissipated would
be 2.9 W. Since the ST7540 is hosted in a HTSSOP28 package
with exposed pad, exhibiting an asymptotic junction-to-case
thermal impedance of 35 C/W, the junction temperature T
J
would reach 131 C (assuming an ambient temperature T
A
= 30
C) if the transmission was long enough to reach the thermal
asymptote. Even though permanent damages to the chip would
occur for junction temperature exceeding 170 C, during
normal operating conditions it is however recommended not to
surpass 125 C to ensure a proper functionality of the chip and
to avoid affecting its reliability over time.
On the basis of the considerations above, a thermal analysis
of the actual behavior of a PLC node is required to guarantee
that this condition can be respected.
Since the transmission is typically limited in time, a proper
thermal analysis should take into account two aspects:
the dynamic behavior of the thermal impedance;
the characteristics of the transmission itself.
Fig. 8. Measured spectrum of the FSK modulated signal at CISPR 16-1
artificial mains network
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
75.0
80.0
85.0
90.0
95.0
100.0
105.0
110.0
115.0
120.0
125.0
1.0E+04 1.0E+05 1.0E+06 1.0E+07 1.0E+08
Frequency (Hz)
O
u
t
p
u
t
L
e
v
e
l
(
d
B
u
V
)
Fig. 9. Output spectrum of the PLC node transmitting at 72 kHz, 4800 baud,
deviation 1 measured at CISPR 16-1 artificial mains network, compared with
EN50065-1 disturbance limit mask
1
10
100
1000
1.0E+04 1.0E+05 1.0E+06
Frequency (Hz)
I
m
p
e
d
a
n
c
e
M
o
d
u
l
u
s
(
O
h
m
)
Fig. 10. Input impedance of the PLC node in Reception mode
compared with EN50065-7 minimum impedance limit mask
1
10
100
1000
1.0E+04 1.0E+05 1.0E+06
Frequency (Hz)
I
m
p
e
d
a
n
c
e
M
o
d
u
l
u
s
(
O
h
m
)
Fig. 11. Input impedance of the PLC node in Transmission mode
compared with EN50065-7 minimum impedance limit mask
B 10 kHz
20 dB
EN50065-7
EN50065-7
EN50065-1
164
A. Thermal Impedance
The junction temperature T
J
can be expressed as follows:
) , ( ) , ( d t P T d t T
TX JA D A TX J
+ = , (2)
where
JA
is the junction-to-ambient thermal impedance,
which is related to the length of the transmission (t
TX
) and to
the duty cycle d = t
PKT
/ (t
PKT
+ t
IDLE
), assuming a packet-
fragmented transmission as illustrated by Fig. 12.
The thermal impedance
JA
has been estimated by simulating
a 6-cells equivalent model, as shown in Fig. 13. In this model,
each cell represents one of the time constants involved in the
thermal transient.
B. Characteristics of a typical AMR transmission
A typical application of a deployed AMR system is taken
into account. AMR networks consist of a master node
(concentrator) polling several slave nodes (meters) to collect
data about readings. These two classes of nodes (concentrator
and meters) are affected by different thermal behavior due to
the different operating conditions of the transmission, as
described below. The two typical transmission types have been
characterized in terms of the resulting thermal impedance and
maximum allowed power dissipation.
a) Meters
Meters are requested by the concentrator to send data about
consumption few times per day. The data are fragmented in
108-bytes packets; taking into account possible repetitions due
to bad reception, the traffic amount can be assumed to be 4
packets long in average, with a duty cycle lower than 50%. As
the bit rate is 4800 bps, the resulting packet time is t
PKT
= 180
ms and the total transmission time is t
TX
= 4* t
PKT
/ d 1.4 s.
The above mentioned operating conditions will cause a PLC
transceiver in a meter node to get, according to simulation,
junction-to-ambient thermal impedance equal to:
JA
(1.4 s, 50%) = 14 C/W. (3)
In order to avoid an overheating of the junction and remain
below the safe value of 125 C in an environment with a T
A
=
30 C, the dissipated power P
D
should not exceed:
P
D
= (125 C 30 C) / 14 C/W = 6.8 W. (4)
Experimental measurements have been performed to verify
if this limit about power dissipation can be respected. Results
are reported at paragraph V.C.
b) Concentrator
When polling data from meters, the concentrator usually
sends short packets (tens of bytes) to the target node and waits
for data. But from time to time the concentrator performs a
firmware update requiring the transmission of hundreds of
maximum-length packets with a short inter-packet interval,
thus leading to high duty cycle. This is the worst-case
transmission from the point of view of the thermal transient.
We can assume a duty cycle of 90% and transmission duration
(t
TX
) of almost 80 s (at 4800 bps).
The PLC transceiver in the concentrator will get, according
to simulation, junction-to-ambient thermal impedance equal to:
JA
(80 s, 90%) = 34 C/W. (5)
To keep the device operating in the safe temperature area
with ambient temperature T
A
= 30 C, the dissipated power P
D
should not exceed:
P
D
= (125 C 30 C) / 34C/W = 2.8 W. (6)
Such dissipating power corresponds, according to Equation
1, to an output level V
OUT rms
= 128 dBV over a line load |Z
L
|
=
4.2 . Since the worst-case load at the concentrator should be
greater than this value, it can be assumed that power
dissipation will not be a limit for the maximum transmitting
level of a concentrator node.
Table II summarizes the parameters characterizing the two
typical AMR cases.
TABLE II
SUMMARY OF AMR TYPICAL OPERATING CONDITIONS
Node Type tTX d JA PD max
Meter 1.4 s 50% 14 C/W 6.8W
Concentrator 80 s 90% 34 C/W 2.8W
C. Experimental Results
Tests have been performed to record the thermal heating of
the PLC transceiver in five different conditions of power
dissipation. The communication node was configured to
emulate the typical traffic of a meter node, i.e. sending a
message at 4800 bps, fragmented in four 108 bytes-long
packets with a duty cycle of 50%. Five different levels of
power dissipation were tested, changing the load impedance
(Z
L
) connected to the power amplifier of the device. For each
Z
L
value, the voltage output level (V
OUT rms
) and power
dissipation (P
D
) were measured and listed in Table III. The
case temperature (T
C
) reached by the device during operation
was captured by means of an infrared camera and plotted in
Fig. 12. Packet-fragmented transmission
Fig. 13 Equivalent model of the thermal impedance of the HTSSOP28
package with exposed pad
C1
5e-4
R2
1
C2
6e-3
R3
8
C3
17e-3
R4
11
C4
0.09
R5
9.5
C5
0.8
R6
6
C6
15
T
A
P
D
R1
0.4
R C/W
C W*s/C
tPKT
tTX
Transmission
in progress Idle
state
tIDLE
165
Fig. 14. The maximum value (T
C max
)
for each condition is
reported in Table III.
TABLE III
MEASURED POWER DISSIPATION AND CASE-TO-AMBIENT IMPEDANCE (
CA
)
OF A METER NODE UNDER DIFFERENT IMPEDANCE LOAD CONDITIONS
|Z
L
|
[]
V
OUT rms
[dBV]
T
C max
[C]
P
D
[W]
CA
[C/W]
1 122 110 C 6.1 14
1.5 126 90 C 4.8 13
5 128 60 C 2.2 14
7 128 50 C 1.6 13
12 128 45 C 1.0 14
Table III also shows the equivalent case-to-ambient thermal
impedance
CA
calculated as follows:
CA
= (T
C max
30 C) / P
D
.
(7)
The calculated
CA
can be compared with the expected
junction-to-ambient thermal impedance
JA
(1.4s, 50%) = 14
C/W, as described in previous section. Negligible difference is
expected between junction-to-ambient and case-to-ambient
thermal impedance. Data listed in Table III, in fact, show a
good agreement between simulated
JA
and measured
CA
values.
It can be noticed that in the two heaviest load conditions, i.e.
|Z
L
| = 1.5 and 1 , the PLC transceiver was not able to
maintain the output level at 128 dBV rms because of current
limitation. These cases represent extreme line load conditions,
possibly related to a short circuit on the line. Nevertheless,
even in such extreme conditions, the device showed a good
thermal behavior, maintaining the junction temperature below
the safe operating limit.
Fig. 15 shows the infrared image captured at the end of the
transmission in the case characterized by |Z
L
| = 1 and P
D
=
6.1 W. The maximum temperature value reached by the PLC
transceiver was T
C
= 110 C; the overheating was located on
the line driver inside the chip.
As expected, the meter node can dissipate up to about 6 W
without undergoing junction overheating.
VI. CONCLUSIONS
An in-depth analysis of the electrical requirements for an
AMR application has been presented in this paper. These
requirements impact mostly on the characteristics of the PLC
node that have been described in detail: filtering of the
transmitted signal, coupling of the signal to the power line,
adequate protection against high energy disturbances, and
coexistence between power supply and communication
circuitry in terms of noise and impedance. All these aspects
have been taken into account in designing the PLC node
demonstrator.
On the basis of the considerations reported in this document,
it is possible to assert that the adoption of the design criteria
described above will allow the development of a low data rate
PLC node suitable for AMR applications.
An analysis of the thermal stress of the nodes of an AMR
network compliant to Standard EN50065 has been performed.
This study has given evidence that a PLC node with the
characteristics described in this paper is not subject to critical
overheating. In fact, both the typical conditions of the AMR
communication and the choice of appropriate thermal
impedance for the PLC transceiver allow the device to operate
in safe conditions even when transmitting over low impedance
offered by the power line.
The same method for evaluating the thermal stress may be
applied to any PLC implementation, adapting the
considerations presented in this paper to the actual conditions
of that particular case.
REFERENCES
[1] CENELEC, European Standard EN50065: Signalling on low-voltage
electrical installations in the frequency range 3 kHz to 148.5 kHz, 2001.
[2] CENELEC, European Standard EN61000: Electromagnetic
compatibility (EMC) Part 4: Testing and measurement techniques,
1995.
[3] STMicroelectronics, ST7540 FSK Power Line Transceiver, 2006.
[4] IEC, International Standard CISPR 16: Specification for radio
disturbance and immunity measuring apparatus and methods Part 1:
Radio disturbance and immunity measuring apparatus, 1993.
30
40
50
60
70
80
90
100
110
120
0 1 2 3 4 5 6
Time (s)
C
a
s
e
T
e
m
p
e
r
a
t
u
r
e
(
C
)
load=0.5, Pd=6.1W
load=1.5, Pd=4.8W
load=5, Pd=2.2W
load=7, Pd=1.6W
load=12, Pd=1W
Fig. 14 Transient of the case temperature TC of the PLC transceiver
during transmission with different power dissipation conditions
Fig. 15. Infrared photo showing the maximum case temperature (TC = 110 C)
reached by the PLC transceiver during transmission with ZL = 1 and
PD = 6.1 W. The heating is located on the PA.
Power
Amplifier
PLC
Transceiver
25 C 150 C
166