Troubleshooting and Service Information For Voltmaster Generators
Troubleshooting and Service Information For Voltmaster Generators
Troubleshooting and Service Information For Voltmaster Generators
SUGGESTED REPAIR PROCEDURES FOR A,LA,LV,LR, AB, AR, AE, G,V AND VX SERIES GENERATORS
1. Check engine speed (3690 RPM no load) and frequency 61.5 hertz no load. Important on models A25/40, 3720 RPM and 62 hertz no load. 2. Open end cover with receptacles exposed. See figure 1. Check lead wires 1,2,3 & 4 according to the resistance chart as follows: Lead wires 1 (black) to lead 2 (white) Lead wires 3 (white) to lead 4 (black) Orange to orange (exciter) Disconnect the red wires to the capacitor before checking the resistance in the wires. Important On some models, lead wire 2(white) and 3 (white) are connected together. See figure 2. To test the stator lead wires and leads 1,2,3 and 4 must not be connected together. See figure 3.When checking lead wires, leads 2 and 3 are connected together (except A25/30) at the factory. You must disconnect these leads when testing resistance of the various coils or you will get incorrect readings.
Figure 1
Figure 2
Figure 3
Figure 4
In addition to checking each coil, test each coil to the ground terminal on the aluminum end bracket to see if any winding has gone to ground. If any lead wire indicates positive continuity to the ground, replace the stator. 3. Check the capacitor for the proper micro farand reading with a capacitor tester. If a capacitor tester is not available, use an ohmmeter set at 10k and touch both terminals at the same time. See figure 4. The meter should bounce up with a reading and immediately drop off. If the meter does not indicate anything or remains holding a reading, the capacitor is defective and must be replaced.
3 4. For a unit that has been out of service for a period of time, flashing the field is recommended. See attached instructions. 5. If the first four steps show no failures, remove the stator from the generators. With the stator removed, the diodes must be checked. To test each diode without disconnecting it from the circuit, use a 12-volt battery and a 45-watt light bulb (automotive type) as shown in illustration 950204. The light should turn on in one direction, as shown. If you cannot test the diodes as previously indicated, you must disconnect the copper wires from one end of the diode. You must also disconnect the varister (surge suppressor) from the diode. With the wire removed use an ohmmeter set to 10K and touch both terminals of the diode. Diodes pass current in one direction only. If you do not get a reading, reverse the terminals of the meter. If you do not get any readings or if you get readings in both directions, the diode is defective. Be sure to check both diodes. If you have only one defective diode, it is strongly recommended to replace both diodes. If the positions of the diodes are reversed, you will block the current flow and get no output form the generator. Pay careful attention to the marking to the current direction of each diode. 6. To check the winding on the rotor you must remove one end the diodes and varister. With an ohmmeter check the readings for each coil. The rotor coils are identical. See chart for the various ohm readings. Prior to testing resistance in each coil, be sure to zero out your ohm meter. All readings must be within 20% or less of the published ohms and be consistent (either at slightly higher or slightly lower, not some higher and some lower).
TROUBLE SHOOTING FOR A, AB, AE, AR, LA, LE, LR, LV, G, V AND VX SERIES
PROBLEM
No Voltage
CAUSES
1. 2. 3. 4.
REMEDIES
Check RPM of engine 3600 RPM Check and replace Check winding resistance Flash capacitor (See Instructions) Check and replace. Consult factory for proper engine HP Correct pulley sizes-consult factory
Low speed 1. Faulty capacitor 2. Faulty windings 3. Out of Service 4. many months 5. Faulty Circuit 5. Breaker (AB/AE/AR series only) 6. Not enough eng. HP 6. (AB/AE/AR series only) 7. Improper pulley ratios7. High no load Voltage 1. Speed too high 2. Capacitor with high capacity Low no load Voltage 1. Speed to low 2. Faulty diodes 3. Winding breakdown 4. Capacitor with low capacity Voltage on 120 volt Side is 60-90 volts Circuit breaker trips
1. Check and adjust to 3600 RPM 2. Check and replace 1. 2. 3. 4. Check and adjust to 3600 RPM Check & replace diodes Check winding resistance Check and replace
1. Overload on circuit 1. Reduce electric load 2. Shorted electric load 2. Repair short in device 3. Defective breaker 3. Replace breaker Low loaded speed Load too heavy Diodes shorted Engine governor 1. 2. 3. 4. Check & adjust engine RPM Check & reduce load Check & replace Adjust or repair governor
Proper no load Voltage1. But Low loaded 2. Voltage 3. 4. Proper no load but High loaded voltage Unstable voltage
1. Excessive RPM
1. Check connections at receptacles and circuit breakers 2. Check engine RPM 3. Tighten rotor screw 1. Replace 2. Check & repair 3. Replace 1. Replace 2. Replace extension cord 1. Replace rotor or stator
Noisy Generator
1. Broken bearing 2. Poor coupling 3. Broken fan 1. Receptacle too sensitive 2. Extension Cord 1. Cracked windings
**Note for all 50 hertz generators the engine RPM should be 3000.
TROUBLE SHOOTING EASY IDLERS ON LM, LEI, LVI, LR AND LRI UNITS
With the generator set operating at normal speed (3600 RPM) and no load on the generator, turn on the idler switch on the control box. If the engine does not slow down: A. Disconnect the two wires that are connected to the solenoid with the idler switch turned on. The voltage should be 12V DC to 18V DC. B. If there is voltage (12V DC to 18V DC) check the two .25 inch tabs on the solenoid to assure good contact. C. Turn engine off, apply a 12Volt DC load to the solenoid to see if solenoid will pull plunger level into the solenoid housing. If the solenoid pulls into the housing, the black adjuster bracket holding the solenoid to the engine needs to be readjusted by loosening the two allen screws and pushing the solenoid away from the engine. D. Adjust the solenoid so that the frequency on the generator is at least 45 hertz under no load condition (at least 90 volts on 120 volt line). E. If the solenoid will not react to any 12-volt DC load, replace the solenoid. F. If there is no voltage to the solenoid, first check if the AC circuits are producing 120V and 240 V, then open up from the panel of the control box. Carefully start the engine. CAUTION! There are live 120 volt and 240 volt wires inside control panel. At both switch connections check wires to read 12 volts DC to 18 volts DC. If there is voltage to the switch but not running through the switch, replace the switch. If there is no voltage to the switch, replace idler module. IMPORTANT! Note wiring diagrams indicating that lead wires T1 and T4 from generator go through sensing torridol coil in opposite directions on the idler module. G. Some models feature a delay on the idler. This delay maintains normal operating speed (3600RPM) for 10-15 seconds after all loads have been removed before slowing down the engine speed.
CAUSE
REMEDIES
1. Interrupted fuse 1. Replace fuse 2. Insufficient residual voltage 2. Increase speed by 15% 3. No residual voltage 3. For an instant apply on the + and terminals of the electronic regulator a 12-volt battery voltage with a 30W resistor in series respecting the polarities 4. Bad capacitor 4. Replace capacitor
Low voltage at no load1. Voltage potentiometer out of setting 2. Intervention of protection 3. Winding failure.
1. Voltage potentiometer out of setting 2. Failed regulator 3. Engine RPM too high 1. Voltage potentiometer out of setting 2. Intervention by protection
1. Reset voltage 2. Replace regulator 3. Adjust RPM 1. Reset voltage potentiometer. 2. Current too high, power factor lower than 0.8; speed lower than 4% of rated speed 3. Replace regulator 4. Check diodes, disconnect cables. 5. Adjust RPM 1. Reset voltage potentiometer 2. Replace regulator 3. Replace capacitor 1. Check uniformity of rotation 2. Regulate stability of regulator by acting on "STABILITY" potentiometer with light bulb plugged into 120 volt receptacle
3. Failed regulator. 4. Rotating bridge failure 5. Engine RPM too low Higher than rated Voltage at load 1. Voltage potentiometer out of setting 2. Failed regulator 3. Capacitor value too high 1. Speed variation in engine 2. Regulator out of setting
Unstable voltage
10
LV105 .161 LR105, AR100 .109 M50/60* .4 Choke/transformer For M50/60 LV150 LR150, PTO15/12 .512 .075 .075
15.7 1.05 1.05 6.27 2.85 1.47 2.6 2.2 1.3 .75 .22 .22
9.4 5.23 5.23 2.83 3.55 4.02 3.51 4.03 5.0 ----1.7 1.7
----2-35MF 2-35MF 31.5MF 41MF 41MF 41MF 63MF 3-31.5 90MF 2-45MF,1-40MF 2-45MF,1-40MF
A25-5 (50 HZ) 1.23 A50-5 (50HZ) .81 A60-5 (50HZ) .52 LV80E-5 (50HZ).318 LV105E-5(50HZ).211 AE100/LE105E LE80E PTO30/25 AR250 .31 1.1 .06 .06
* Positive cable on meter MUST be connected to green lead as there is a diode across these two leads. Readings 15-20% different than those listed above indicate a defective winding.
11
Model EC8-3,EC7-1 EC13-3.EC11-1 EC15-3,EC12.5-1 EC29-3, EC24-1 EC40-3, EC30-1 PT040-1,PT055-3 EC50-3, EC40-1 PT0501, PT055-3 EC65-3, EC50-1 PT065-1,PT070-3 EC80-3, EC67-1 PT075-1,PT090-3 EC100-3,EC83-1 EC120-3,EC100-1 PT0110-3 EC145-3,EC120-1 EC176-3,EC145-1 EC215-3,EC180-1 EC240-3, EC200-1 EC325-3, EC270-1
0.061
0.993
2.473
11.35
0.47
SR7
0.035
0.79
3.171
11.35
0.47
SR7
0.03 0.02
0.965 0.838
2.477 2.951
15.28 15.28
0.41 0.41
SR7 SR7
12
DIODE DIRECTION
While looking at the rotor in this position, the numbers and letters on all diodes are readable as shown above. The numbers and letters may be different but all face the same direction in this position. 2. With the stator removed, unsolder one diode and loosen the wires from the copper windings and the varister. Note the direction of the wording on the original diode. Replace with a new varister and diode into the diode holder. Twist the leads from the varister and copper winding around the leads from the diode. Put welding flux on both ends to be soldered. Get the soldering iron very hot, put solder on the tip of the solder iron (strongly suggested to hold a pliers between the diode and connections being soldered to absorb the heat). Do not keep solder gun on new diode leads for more than a few seconds or damage to the diode may occur.
13
ENGLISH FASTENER TORQUE RECOMMENDATIONS FOR STANDARD APPLICATIONS TIGHTENING TORQUE Nm (in.lb.) + or 20%
Size 8-32 10-24 10-32 _-20 _-28 5/16-18 5/16-24 3/8-16 3/8-24 Grade 2 2.3 (20) 3.6 (32) 3.6 (32) 7.9 (70) 9.6 (85) 17.0 (150) 18.7 (165) 29.4 (260) 33.9 (300) Grade 5 2.8 (25) 4.5 (40) 4.5 (40) 13.0 (115) 15.8 (140) 28.3 (250) 30.5 (270) --------------------Grade 8 ------------------------------18.7 (165) 22.6 (200) 39.6 (350) ------------------------------Grade 2 or 5 into Aluminum 2.3 (20) 3.6 (32) ----------7.9 (70) ----------17.0 (150) -------------------------------
GENERAL TORQUE VALUES Metric Fastener Torque Recommendations for Standard Applications Tightening Torque: Nm (in.lb.) + or 10% Size M4 M5 M6 M8 4.8 5.8 8.8 10.9 12.9 Non-critical fasteners into Aluminum
Tightening Torque: Nm (ft.lb.) + or 10% Size M10 M12 M14 4.8 5.8 8.8 10.9 12.9 Non-critical fasteners into Aluminum
Torque Conversions Nm = in.lb. x 0.113 Nm = ft.lb. x 1.356 In.lb. = Nm x 8.85 Ft.lb. = Nm x 0.737
14
CAPACITOR TESTING
1. The generator should NOT be running. Disconnect the two exciter lead wires to the capacitor. With a capacitor tester connect to the capacitor and read the MFD indicated which should be exactly what is marked MF or UF on the capacitor. There are no polarity concerns when testing a capacitor. 2. If no capacitor tester is available, using multi-meter set in the resistance (Ohms) position at 1K or 10K, connect the lead wires as noted in the drawings below. A good capacitor should make the meter have a momentary reading and then drop off to zero. A defective capacitor will either cause the meter to hold a reading or have no reading at all. You can only do this test a couple of times as you will be discharging the capacitor. Replace defective capacitors with like size MFD 450 volt capacitors.
15
FIGURE 950204
DIODE TEST WITHOUT REMOVING THE DIODE FROM THE ROTOR Connect a 12 volt DC battery and a 45 watt (automobile type) bulb as shown below. The light will turn on in one direction only as shown.