Voltage and Frequency Relay 7RW80x - Catalog - SIP-2011 - en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 23

11 Generator Protection / 7RW80

SIPROTEC Compact 7RW80


Voltage and Frequency Relay
Function overview

Protection functions
• Under-/overvoltage protection (27/59)
• Displacement voltage (64/59N)
• Under-/overfrequency protection (81U/O)
• Load restoration
• Overexcitation protection (24)
• Jump of voltage vector
• Phase-sequence monitoring (47)
• Synch-check (25)
• Rate-of-frequency change (81R)
• Rate-of-voltage change
• Lockout (86)
LSP2874.tif

Control functions/programmable logic


• Commands for the control of CB, discon-
nect switches (isolators/isolating switches)
Fig. 1
• Control through keyboard, binary
SIPROTEC Compact 7RW80 inputs, DIGSI 4 or SCADA system
voltage and frequency relay • User-defined PLC logic with CFC
(e.g. interlocking)
Monitoring functions
The communication module is independ- • Operational measured values V, f
Description • Minimum and maximum values
ent from the protection. It can easily be
The SIPROTEC Compact 7RW80 is a nu- exchanged or upgraded to future commu- • Trip circuit supervision (74TC)
merical, multifunction relay for connec- nication protocols. • Fuse failure monitor
tion to voltage transformers. It can be used • 8 oscillographic fault records
Highlights
in distribution systems, on transformers Communication interfaces
and for electrical machines. If the Removable terminals provide the ideal so-
• System/service interface
SIPROTEC Compact 7RW80 detects any lution for fast and secure replacement of
– IEC 61850
deviation from the permitted voltage, fre- relays. Binary input thresholds are software
– IEC 60870-5-103
quency or overexcitation values, it will re- settings. There is thus no need to ever open
the relay to adapt the hardware configura- – PROFIBUS-DP
spond according to the values set. The – DNP 3.0
relay can also be applied for the purposes tion to a specific application.
– MODBUS RTU
of system decoupling and for load shed- The relay provides 9 programmable func- • Ethernet interface for DIGSI 4
ding if ever there is a risk of a system tion keys that can be used to replace push- • USB front interface for DIGSI 4
collapse as a result of inadmissibly large buttons, select switches and control switches.
frequency drops. An integrated load resto- Hardware
ration function allows the re-establishment The battery for event and fault recording • 3 voltage transformers
of the power system after recovery of the memory can be exchanged from the front • 3/7 binary inputs (thresholds
system frequency. of the relay. configurable using software)
The 7RW80 features “flexible protection The relay is available with IEC 61850 for • 5/8 binary outputs (2 changeover/
functions”. 20 additional protection func- incredible cost savings in applications (e.g. Form C contacts)
tions can be created by the user. For exam- transfer schemes with synch-check, bus • 1 live-status contact
ple, a rate-of-frequency change or a rate- interlocking and load shedding schemes). • Pluggable terminals
of-voltage change function can be created. This compact relay provides protection,
The relay provides circuit-breaker control, control, metering and PLC logic functional-
additional primary switching devices ity. Secure and easy to use one page matrix
(grounding switches, transfer switches and IO programming is now a standard feature.
isolating switches) can also be controlled The housing creates a sealed dust proof
from the relay. Automation or PLC logic environment for the relay internal elec-
functionality is also implemented in the tronics. Heat build up is dissipated through
relay. The integrated programmable logic the surface area of the steel enclosure. No
(CFC) allows the user to add own func- dusty or corrosive air can be circulated
tions, e.g. for the automation of switch- over the electronic components. The relay
gear (including: interlocking, transfer and thus will maintain its tested insulation
load shedding schemes). The user is also characteristic standards as per IEC, IEEE,
allowed to generate user-defined messages. even if deployed in harsh environment.

Siemens SIP February 2011 1


11 Generator Protection / 7RW80

Application

V, f
V/f dV/dt df/dt
Energy meter: 24
by counting pulses

SIP-0001.en.ai
64

Fig. 2 Function diagram

The SIPROTEC Compact 7RW80 unit is a Programmable logic Metering values


numerical protection relay that can per- The integrated logic characteristics (CFC) Extensive measured values (e.g. V), and
form control and monitoring functions allow the user to add own functions for limit values (e.g. for voltage, frequency)
and therefore provide the user with a cost- automation of switchgear (e.g. interlock- provide improved system management.
effective platform for power system man- ing) or switching sequence. The user can
agement, that ensures reliable supply of also generate user-defined messages. This Reporting
electrical power to the customers. The er- functionality can form the base to create
gonomic design makes control easy from The storage of event logs, trip logs, fault
extremely flexible transfer schemes. records and statistics documents are stored
the relay front panel. A large, easy-to-read
display was a key design factor. in the relay to provide the user or operator
Line protection with all the key data required to operate
Control For the enhancement of the feeder protec- modern substations.
tion the 7RW80 provides several stages for
The integrated control function permits voltage and frequency protection. Switchgear cubicles for
control of disconnect devices, grounding high/medium voltage
switches or circuit-breakers through the Generator and transformer protection
integrated operator panel, binary inputs, All units are designed specifically to meet
Through implemented voltage, frequency the requirements of high/medium-voltage
DIGSI 4 or the control or SCADA/automa- and overexcitation protection the 7RW80
tion system (e.g. SICAM, SIMATIC or other applications.
can be used for generators and transform-
vendors automation system). A full range of ers in case of defective voltage or frequency In general, no separate measuring instru-
command processing functions is provided. control, full load rejection or operation in ments (e.g., for voltage, frequency, …) or
islanding generation systems. additional control components are neces-
sary.
System decoupling and load shedding
Typically the relay provides all required
For system decoupling and load shedding
measurements, thus negating the use of
the 7RW80 provides voltage, frequency,
additional metering devices like volt or
rate-of-frequency-change and rate-of-
frequency meters. No additional control
voltage-change protection.
switches are required either. The relay pro-
Load restoration vides 9 function keys that can be config-
For power system recovery frequency pro- ured to replace pushbuttons and select
tection and load restoration are available in switches.
7RW80.

1) Not available if function package 'Q' (synch-check, ANSI 25) is selected.

2 February 2011 Siemens SIP


11 Generator Protection / 7RW80

Application

ANSI No. IEC-Norm Protection functions

27, 59 V<, V> Undervoltage/overvoltage protection

1) VE, V0> Displacement voltage, zero-sequence voltage


59N/64

81O/U f>, f< Overfrequency/underfrequency protection

Load restoration

24 V/f Overexcitation protection

Δ ϕ> Jump of voltage vector

47 V2>, phase-sequence Unbalance-voltage protection and/or phase-sequence monitoring

25 Synch-check

81R df/dt Rate-of-frequency-change protection

dV/dt Rate-of-voltage-change protection

1) Not available if function package 'C' or 'E' (synch-check, ANSI 25) is selected.

Siemens SIP February 2011 3


11 Generator Protection / 7RW80

Construction and hardware

Connection techniques and


housing with many advantages

LSP2885.tif
The relay housing is 1/6 of a 19" rack. Illuminated 6-line display
The housing is thus identical in size to the
7RW600 relays that makes replacement Navigation keys
very easy. The height is 244 mm (9.61").
Pluggable terminals allow for pre-wiring Numerical keypad/9 function keys
and simplify the exchange of devices. 8 programmable LEDs
All binary inputs are independent and the
pick-up thresholds are settable using soft-
ware settings (3 stages). Up to 9 function
keys can be programmed for predefined
menu entries, switching sequences, etc. Control keys
The assigned function of the function keys Standard battery exchangeable from the front
can be shown in the display of the relay.
USB front port

Protection functions LSP2876.tif

Undervoltage protection (ANSI 27)


The two-element undervoltage protection
provides protection against dangerous
voltage drops (especially for electric ma-
chines). Applications include the isolation
LSP2878.tif
of generators or motors from the network
to avoid undesired operating conditions
and a possible loss of stability. Proper op-
erating conditions of electrical machines
Voltage terminal
are best evaluated with the positive- block
sequence quantities. The protection func-
tion is active over a wide frequency range
of 25 to 70 Hz.
The function can operate either with Fig. 3 7RW80 front view, rear view, terminals
phase-to-phase, phase-to-ground or posi-
tive phase-sequence voltage. Three-phase
and single-phase connections are possible. Frequency protection (ANSI 81O/U) Load restoration
In addition a user definable curve with up Frequency protection can be used for over- The load restoration function provides an
to 20 value pairs is available. frequency and underfrequency protection. automatic reconnection of power system
Overvoltage protection (ANSI 59) Electric machines and parts of the system parts when the system frequency has re-
are protected from unwanted frequency covered after load shedding.
The two-element overvoltage protection deviations. Unwanted frequency changes
detects unwanted network and machine Four load restoration stages are available.
in the network can be detected and the
overvoltage conditions. The function can They can be switched on and off separately.
load can be removed at a specified fre-
operate either with phase-to-phase, quency setting. If the frequency conditions allow the as-
phase-to-ground, positive phase-sequence sumption of sufficient generation re-
or negative phase-sequence voltage. Frequency protection can be used over
sources, the load restoration function will
Three-phase and single-phase connections a wide frequency range of 25 to 70 Hz.
consecutively reconnect small load parts at
are possible. There are four elements (individually set as
specified time intervals.
overfrequency, underfrequency or OFF)
In addition, a user definable curve with up and each element can be delayed sepa-
to 20 value pairs is available. rately. Blocking of the frequency protec-
tion can be performed by activating a
binary input or by using an undervoltage
element.

4 February 2011 Siemens SIP


11 Generator Protection / 7RW80

Protection functions (cont'd)

Overexcitation protection (ANSI 24)


The overexcitation protection serves for
detection of an unpermissible high induc-
tion (proportional to V/f) in generators or
transformers, which leads to thermal over-
loading. This may occur when starting up,
shutting down under full load, with weak
systems or under isolated operation. The
inverse characteristic can be set via eight
points derived from the manufacturer
data. dV/dt
SIP-0002.en.ai
In addition, a definite-time alarm stage and
an instantaneous stage can be used. For cal-
Fig. 4 Flexible protection functions
culation of the V/f ratio, frequency and also
the highest of the three line-to-line voltages
are used. The frequency range that can be
monitored comprises 25 to 70 Hz.
Protection functions/stages available are Trip circuit supervision (ANSI 74TC)
Jump of voltage vector based on the available measured analog One or two binary inputs can be used for
quantities: monitoring the circuit-breaker trip coil
Monitoring the phase angle in the voltage
is a criterion for identifying an interrupted Function ANSI No. including its incoming cables. An alarm
infeed. If the incoming line should fail, the signal is generated whenever the circuit is
V<, V>, VE> 27, 59, 64
abrupt current discontinuity leads to a interrupted. The circuit-breaker trip coil is
3V0>, V1><, V2>< 59N, 47 monitored in the open and closed position.
phase angle jump in the voltage. This is
measured by means of a delta process. The f>< 81O, 81U Interlocking features can be implemented
command for opening the generator or to ensure that the beaker can only be closed
df/dt>< 81R if the trip coil is functional.
coupler circuit-breaker will be issued if the
set threshold is exceeded. dV/dt><
Customized functions

Flexible protection functions For example, the following can be imple- Additional functions, which are not time
mented: critical, can be implemented using the CFC
The 7RW80 enables the user to easily add measured values.
up to 20 additional protective functions. • Rate-of-frequency-change protection
Parameter definitions are used to link (ANSI 81R)
• Rate-of-voltage-change protection Control and automatic functions
standard protection logic with any chosen
characteristic quantity (measured or calcu- Control
lated quantity) (Fig. 4). The standard logic Synch-check (ANSI 25)
consists of the usual protection elements When closing a circuit-breaker, the units In addition to the protection functions,
such as the pickup set point, the set delay can check whether two separate networks the SIPROTEC 4 and SIPROTEC Compact
time, the TRIP command, a block func- are synchronized. Voltage, frequency and units also support all control and monitor-
tion, etc. The mode of operation for phase-angle-differences are checked to de- ing functions that are required for operat-
voltage quantities can be three-phase or termine whether synchronous conditions ing medium-voltage or high-voltage
single-phase. Almost all quantities can be exist. substations.
operated with ascending or descending The main application is reliable control of
pickup stages (e.g. under and overvoltage). Lockout (ANSI 86) switching and other processes.
All stages operate with protection priority. All binary output statuses can be memo- The status of primary equipment or auxil-
rized. The LED reset key is used to reset iary devices can be obtained from auxiliary
the lockout state. The lockout state is also contacts and communicated to the 7RW80
stored in the event of supply voltage fail- via binary inputs. Therefore it is possible
ure. Reclosure can only occur after the to detect and indicate both the OPEN and
lockout state is reset. CLOSED position or a fault or intermedi-
ate circuit-breaker or auxiliary contact po-
sition.
The switchgear or circuit-breaker can be
controlled via:
– integrated operator panel
– binary inputs
– substation control and protection system
– DIGSI 4.

Siemens SIP February 2011 5


11 Generator Protection / 7RW80

Control and automatic functions (cont'd) Assignment of feedback to command Further functions
The positions of the circuit-breaker or
Automation / user-defined logic switching devices and transformer taps are Measured values
With integrated logic, the user can create, acquired through feedback. These indica- The r.m.s. values are calculated from the
through a graphic interface (CFC), specific tion inputs are logically assigned to the acquired voltages along with the frequency.
functions for the automation of switchgear corresponding command outputs. The The following functions are available for
or a substation. Functions are activated us- unit can therefore distinguish whether the measured value processing:
ing function keys, a binary input or indication change is a result of switching
operation or whether it is an undesired • Voltages VL1, VL2, VL3, VL1L2, VL2L3, VL3L1
through the communication interface.
spontaneous change of state. • Symmetrical components
Switching authority V1, V2, V0
Chatter disable
Switching authority is determined by set • Frequency
parameters or through communications to The chatter disable feature evaluates
whether, in a set period of time, the num- • Mean as well as minimum and maximum
the relay. If a source is set to “LOCAL”, voltage values
only local switching operations are possi- ber of status changes of indication input
ble. The following sequence for switching exceeds a specified number. If exceeded, • Operating hours counter
the indication input is blocked for a certain
authority is available: “LOCAL”; DIGSI
period, so that the event list will not record • Limit value monitoring
PC program, “REMOTE”. Limit values can be monitored using pro-
excessive operations.
There is thus no need to have a separate grammable logic in the CFC. Commands
Local/Remote switch wired to the breaker Indication filtering and delay can be derived from this limit value indi-
coils and relay. The local/remote selection cation.
Binary indications can be filtered or de-
can be done using a function key on the layed. • Zero suppression
front of the relay. In a certain range of very low measured
Filtering serves to suppress brief changes in values, the value is set to zero to suppress
Command processing potential at the indication input. The indi- interference.
This relay is designed to be easily integrated cation is passed on only if the indication
into a SCADA or control system. Security voltage is still present after a set period of Commissioning
features are standard and all the function- time. In the event of an indication delay,
Commissioning could not be easier and
ality of command processing is offered. there is a delay for a preset time. The infor-
is supported by DIGSI 4. The status of
This includes the processing of single and mation is passed on only if the indication
the binary inputs can be read individually
double commands with or without feed- voltage is still present after this time.
and the state of the binary outputs can be
back, sophisticated monitoring of the con- set individually. The operation of switch-
Indication derivation
trol hardware and software, checking of ing elements (circuit-breakers, disconnect
the external process, control actions using User-definable indications can be derived devices) can be checked using the switch-
functions such as runtime monitoring and from individual or a group of indications. ing functions of the relay. The analog
automatic command termination after These grouped indications are of great measured values are represented as wide-
output. Here are some typical applications: value to the user that need to minimize the ranging operational measured values. To
number of indications sent to the system prevent transmission of information to
• Single and double commands using 1, or SCADA interface.
1 plus 1 common or 2 trip contacts the control center during maintenance,
the communications can be disabled to
• User-definable bay interlocks prevent unnecessary data from being trans-
• Operating sequences combining several mitted. During commissioning, all indica-
switching operations such as control of tions with test tag for test purposes can be
circuit-breakers, disconnectors and connected to a control and protection
grounding switches system.
• Triggering of switching operations, Test operation
indications or alarm by combination with
existing information. During commissioning, all indications can
be passed to a control system for test pur-
poses.

6 February 2011 Siemens SIP


11 Generator Protection / 7RW80

System interface protocols (retrofittable)


Communication
IEC 61850 protocol
The relay offers flexibility with reference to Since 2004, the Ethernet-based IEC 61850 Substation
its communication to substation automa- protocol is a global standard for protection controller
tion systems and industrial SCADA or and control systems used by power utili-
DCS systems. The communication module ties. Siemens was the first manufacturer to
firmware can be changed to communicate implement this standard. This protocol
using another protocol or the modules can makes peer-to-peer communication possi- 7RW80
be changed completely for a different con- ble. It is thus possible to set up masterless
nection or protocol. It will thus be possible systems to perform interlocking or transfer
to move to future communication proto- schemes. Configuration is done using

SIP-0003.en.ai
cols like popular Ethernet-based protocols DIGSI.
with ease.
IEC 60870-5-103 protocol
USB interface
The IEC 60870-5-103 protocol is an inter-
There is an USB interface on the front of national standard for the transmission of Fig. 5
the relay. All the relay functions can be protective data and fault recordings. All IEC 60870-5-103: Radial fiber-optic connection
set using a PC and DIGSI 4 protection messages from the unit and also control
operation program. Commissioning tools commands can be transferred by means of
and fault analysis are built into the DIGSI published, Siemens-specific extensions to Option: Control
DIGSI SICAM center
program and are used through this inter- the protocol. PAS
face.
PROFIBUS-DP protocol
Interfaces
PROFIBUS-DP is a widespread protocol
A number of communication modules in industrial automation. Through
suitable for various applications can be switch
PROFIBUS-DP, SIPROTEC units make
fitted at the bottom of the housing. The their information available to a SIMATIC
modules can be easily replaced by the user. controller or receive commands from a
The interface modules support the follow- central SIMATIC controller or PLC.
ing applications: 7RW80
Measured values can also be transferred
• System/service interface to a PLC master.
Communication with a central control
MODBUS RTU protocol

SIP-0004.en.ai
system takes place through this interface.
Radial or ring type station bus topologies This simple, serial protocol is mainly
can be configured depending on the cho- used in industry and by power utilities, and
sen interface. Furthermore, the units can is supported by a number of relay manu-
exchange data through this interface via facturers. SIPROTEC units function as Fig. 6
Ethernet and the IEC 61850 protocol and MODBUS slaves, making their informa- Bus structure for station bus with Ethernet and
can also be accessed using DIGSI. tion available to a master or receiving in- IEC 61850, fiber-optic ring
• Ethernet interface formation from it. A time-stamped event
The Ethernet interface was implemented list is available.
for access to a number of protection units
DNP 3.0 protocol
using DIGSI.
Power utilities use the serial DNP 3.0 (Dis-
tributed Network Protocol) for the station
and network control levels. SIPROTEC
units function as DNP slaves, supplying
their information to a master system or
receiving information from it.

Siemens SIP February 2011 7


11 Generator Protection / 7RW80

Communication
Operating and
System solutions for protection and station monitoring
control
Units featuring IEC 60870-5-103 interfaces
can be connected to SICAM in parallel via Substation
the RS485 bus or radially by fiber-optic controller
link. Through this interface, the system is
open for the connection to other manufac-
turer systems (see Fig. 5).
Because of the standardized interfaces,
SIPROTEC units can also be integrated
into systems of other manufacturers or in

SIP-0005.en.ai
SIMATIC. Electrical RS485 or optical in-
terfaces are available. The best physical
data transfer medium can be chosen thanks
to opto-electrical converters. Thus, the
RS485 bus allows low-cost wiring in the DIGSI
cubicles and an interference-free optical
connection to the master can be estab-
7RW80 7RW80 7RW80 7RW80
lished. USB

For IEC 61850, an interoperable system DIGSI


solution is offered with SICAM. Through
DIGSI 4
the 100 Mbits/s Ethernet bus, the units are (Local for commissioning)
linked with SICAM electrically or optically
to the station PC. The interface is standard- Fig. 7
System solution/communication
ized, thus also enabling direct connection
to relays of other manufacturers and into
the Ethernet bus. With IEC 61850, how-
ever, the relays can also be used in other
manufacturers’ systems (see Fig. 6).
LSP2810.tif

Fig. 8
Optical Ethernet communication module
for IEC 61850 with integrated Ethernet switch

8 February 2011 Siemens SIP


11 Generator Protection / 7RW80

Typical connections
A
Standard connection
B
C
Surface/flush-mounting
52 52 52 housing

E9 VA
A B
E11 VB

E12

a b VC

SIP-0006.en.ai
E13
E14
SIPROTEC
A B C
Fig. 9
Example for connection type "VAN, VBN, VCN" load-side voltage connection

Fig. 10
Voltage transformer connections to two voltage transformers (phase-to-phase voltages)
and broken data winding (da-dn)

Connection for separate input Vx

Fig. 11
Example for connection type "VAB, VBC, Vx"

Siemens SIP February 2011 9


11 Generator Protection / 7RW80

Typical connections

Connection for synch-check

Fig. 12
Example for connection type “VAB, VBC, VSYN”

A
B
C
A
52 52 52
B
Surface/flush-mounting
b housing

a
E9 VPh-N
A B
a b E12
V-Transformer 2
E11
VSyn
E13

SIP-0009.en.ai
E14

A B C SIPROTEC

Fig. 13
Example for connection type "Vph-n, Vsyn"
The connection can be established at any one of the three phases.
The phase must be the same for Vph-n and Vsyn.

10 February 2011 Siemens SIP


11 Generator Protection / 7RW80

Technical data

General unit data Output relay


Rated frequency fnom 50 or 60 Hz (adjustable) Type 7RW801 7RW802
Analog voltage inputs NO contact 3 6
Rated voltage 34 to 225 V NO/NC selectable 2 (+ 1 live contact 2 (+ 1 live contact
(phase-to-ground connection) not allocatable) not allocatable)
34 to 200 V Switching capability MAKE Max. 1000 W/VA
(phase-to-phase connection)
Switching capability BREAK 40 W or 30 VA at L/R ≤ 40 ms
Measuring range 0 to 200 V
Switching voltage 250 V DC/AC
Burden at 100 V Approx. 0.005 VA
Admissible current per contact 5A
Overload capacity in voltage path (continuous)
Thermal (rms) 230 V continuous
Permissible current per contact 30 A for 1 s (NO contact)
Input voltage range UL 300 V
(close and hold)
Auxiliary voltage
DC voltage
Electrical tests
Voltage supply via an integrated
Specification
converter
Standards IEC 60255 (product standard)
Rated auxiliary voltage Vaux DC 24 to 48 V 60 to 250 V
ANSI/ IEEE C37.90 see individual
Permissible voltage ranges DC 19 to 60 V 48 to 300 V functions
AC ripple voltage, peak-to-peak, w 15 % of the auxiliary voltage VDE 0435
IEC 60255-11 for more standards see also
individual functions
Power input
Quiescent Approx. 5 W Insulation tests
Energized Approx. 12 W Standards IEC 60255-27 and IEC 60870-2-1
Bridging time for failure/ W 50 ms at V W 110 V DC High-voltage test (routine test) 2.5 kV, 50 Hz
short-circuit, IEC 60255-11 W 10 ms at V < 110 V DC All circuits except power supply,
(in the quiescent state) binary inputs, communication
AC voltage interface
Voltage supply via an integrated High-voltage test (routine test) 3.5 kV DC
converter Auxiliary voltage and binary inputs
Rated auxiliary voltage Vaux AC 115 V 230 V High-voltage test (routine test) 500 V, 50 Hz
Only isolated communication
Permissible voltage ranges AC 92 to 132 V 184 to 265 V interfaces (A and B)
Power input (at 115 V AC/230 V AC) Impulse voltage test (type test) 6 kV (peak value); 1.2/50 µs; 0.5 J;
Quiescent Approx. 5 VA All process circuits (except commu- 3 positive and 3 negative impulses at
Energized Approx. 12 VA nication interfaces) against the inter- intervals of 1 s
Bridging time for failure/short- W 10 ms at V = 115/230 V AC nal electronics
circuit (in the quiescent state) Impulse voltage test (type test) 5 kV (peak value); 1.2/50 µs; 0.5 J;
All process circuits (except commu- 3 positive and 3 negative impulses at
nication interfaces) against each intervals of 1 s
Binary inputs
other and against the productive
Type 7RW801 7RW802 conductor terminal class III
Number (marshallable) 3 7 EMC tests for immunity; type tests
Rated voltage range 24 to 250 V DC Standards IEC 60255-6 and -22
Current input, energized Approx. 0.4 mA (product standard)
(independent of the control voltage) IEC/EN 61000-6-2
VDE 0435
Secured switching thresholds (adjustable) For more standards see individual
for rated voltages Vhigh > 19 V DC functions
24 to 125 V DC Vlow < 10 V DC 1 MHz check, class III 2.5 kV (peak); 1 MHz;
for rated voltages Vhigh > 88 V DC IEC 60255-22-1; IEC 61000-4-18; τ =15 µs; 400 surges per s;
110 to 250 V DC Vlow < 44 V DC IEEE C37.90.1 test duration 2 s; Ri = 200 Ω
for rated voltages Vhigh > 176 V DC Electrostatic discharge, class IV 8 kV contact discharge;
220 and 250 V DC Vlow < 88 V DC IEC 60255-22-2 15 kV air discharge;
Maximum permissible voltage 300 V DC and IEC 61000-4-2 both polarities; 150 pF; Ri = 330 Ω

Input interference suppression 220 V DC across 220 nF at a Radio frequency electromagnetic field, 10 V/m; 80 MHz to 2.7 GHz;
recovery time between two amplitude-modulated, class III 80 % AM; 1 kHz
switching operations W 60 ms IEC 60255-22-3; or IEC 61000-4-3
Fast transient disturbance variables/ 4 kV; 5/50 ns; 5 kHz;
burst, class IV burst length = 15 ms;
IEC 60255-22-4 and repetition rate 300 ms; both polarities;
IEC 61000-4-4, IEEE C37.90.1 Ri = 50 Ω; test duration 1 min

Siemens SIP February 2011 11


11 Generator Protection / 7RW80

Technical data

EMC tests for immunity; type tests (cont'd) Climatic stress tests
High-energy surge voltages (SURGE), Impulse: 1.2/50 µs Temperatures
Installation class III
IEC 60255-22-5; IEC 61000-4-5 Standards IEC 60255-6
Auxiliary voltage Common mode: 4 kV; 12 Ω; 9 µF Type test (in acc. with IEC 60068-2-1 –25 °C to +85 °C or –13 °F to +185 °F
Diff. mode: 1 kV; 2 Ω; 18 µF and -2, Test Bd for 16 h)
Measuring inputs, binary inputs Common mode: 4 kV; 42 Ω; 0.5 µF
Permissible temporary operating –20 °C to +70 °C or –4 °F to +158 °F
and relay outputs Diff. mode: 1 kV; 42 Ω; 0.5 µF
temperature (tested for 96 h) (clearness of the display may be
HF on lines, amplitude-modulated, 10 V; 150 kHz to 80 MHz; impaired from +55 °C or +131 °F)
class III; IEC 60255-22-6; 80 % AM; 1 kHz
Recommended for permanent –5 °C to +55 °C or +23 °F to +131 °F
IEC 61000-4-6,
operation (in acc. with IEC 60255-6)
Power system frequency magnetic 30 A/m continuous; 300 A/m for 3 s
Limit temperatures for storage –25 °C to +55 °C or –13 °F to +131 °F
field; IEC 61000-4-8, class IV
Limit temperatures for transport –25 °C to +70 °C or –13 °F to +158 °F
Damped oscillations IEC 61000-4-18 2.5 kV (peak value)
100 kHz; 40 pulses per s; Storage and transport with factory packaging
test duration 2 s; Ri = 200 Ω Humidity
EMC tests for noise emission; type tests Permissible humidity Mean value per year w 75 % relative
Standard IEC/EN 61000-6-4 humidity; on 56 days of the year up
to 93 % relative humidity; condensa-
Radio noise voltage to lines, only 150 kHz to 30 MHz, limit class A
tion must be avoided!
auxiliary voltage IEC/CISPR 11
It is recommended that all devices be installed such that they are not ex-
Interference field strength 30 to 1000 MHz, limit class A
posed to direct sunlight, nor subject to large fluctuations in temperature
IEC/CISPR 11
that may cause condensation to occur.
Unit design
Mechanical stress tests
Type 7RW80**-*B 7RW80**-*/E
Vibration, shock stress and seismic vibration
Housing 7XP20
During stationary operation
Dimensions See dimension drawings
Standards IEC 60255-21 and IEC 60068
Housing width 1/6 1/6
Oscillation Sinusoidal
Weight in kg
IEC 60255-21-1, class II; 10 to 60 Hz: ± 0.075 mm amplitude;
Surface-mounting 4.5 kg (9.9 lb)
IEC 60068-2-6 60 to 150 Hz: 1 g acceleration
Flush-mounting 4 kg (8.8 lb)
Frequency sweep rate 1 octave/min
20 cycles in 3 orthogonal axes Degree of protection
Shock Semi-sinusoidal acc. to EN 60529
IEC 60255-21-2, class I; 5 g acceleration, duration 11 ms; each For equipment in the IP 50
IEC 60068-2-27 3 shocks (in both directions of 3 axes) surface-mounting housing
Seismic vibration Sinusoidal For equipment in the Front IP 51
IEC 60255-21-3, class II; 1 to 8 Hz: ± 7.5 mm amplitude flush-mounting housing Back IP 50
IEC 60068-3-3 (horizontal axis) For operator protection IP 1x for voltage terminal
1 to 8 Hz: ± 3.5 mm amplitude
(vertical axis) Degree of pollution, IEC 60255-27 2
8 to 35 Hz: 2 g acceleration
(horizontal axis)
Communication interfaces
8 to 35 Hz: 1 g acceleration
(vertical axis) Operating interface (front of unit)
Frequency sweep 1 octave/min Terminal USB, type B
1 cycle in 3 orthogonal axes
Transmission speed Up to 12 Mbit/s
During transport
Bridgeable distance 5m
Standards IEC 60255-21 and IEC 60068
Ethernet service interface (Port A)
Vibration Sinusoidal
IEC 60255-21-1, class II; 5 to 8 Hz: ± 7.5 mm amplitude Ethernet electrical for DIGSI
IEC 60068-2-6 8 to 150 Hz; 2 g acceleration Operation With DIGSI
Frequency sweep 1 octave/min Terminal At the bottom part of the housing,
20 cycles in 3 orthogonal axes mounting location “A”, RJ45 socket,
Shock Semi-sinusoidal 100BaseT in acc. with IEEE 802.3
IEC 60255-21-2, class I; 15 g acceleration, duration 11 ms, LED yellow: 10/100 Mbit/s (ON/OFF)
IEC 60068-2-27 each 3 shocks (in both directions LED green: connection/no connection
of the 3 axes) (ON/OFF)
Continuous shock Semi-sinusoidal Test voltage 500 V/50 Hz
IEC 60255-21-2, class I; 10 g acceleration, duration 16 ms, Transmission speed 10/100 Mbit/s
IEC 60068-2-29 each 1000 shocks (in both directions
of the 3 axes) Bridgeable distance 20 m (66 ft)

12 February 2011 Siemens SIP


11 Generator Protection / 7RW80

Technical data

Service interface for DIGSI 4/modem (Port B) PROFIBUS DP


Isolated RS232/RS485 RS485, isolated
Terminal At the bottom part of the housing, Terminal At the bottom part of the housing,
9-pin subminiature connector mounting location “B”, 9-pin
(SUB-D) subminiature connector (SUB-D)
Test voltage 500 V/50 Hz Test voltage 500 V/50 Hz
Transmission rate Min. 1200 Bd, max. 115200 Bd Transmission rate Up to 1.5 Mbaud
Bridgeable distance RS232 Max. 15 m/49.2 ft Bridgeable distance 1000 m/3300 ft w 93.75 kbaud;
Bridgeable distance RS485 Max. 1 km/3300 ft 500 m/1640 ft w 187.5 kbaud;
200 m/656 ft w 1.5 Mbaud
Fiber optic (FO) Fiber optic
Terminal At the bottom part of the housing, Connection fiber-optic cable ST connector, double ring
ST connector
Terminal At the bottom part of the housing,
Optical wavelength λ = 820 nm mounting location “B”
Permissible path attenuation Max. 8 dB, for glass fiber 62.5/125 µm Optical wavelength λ = 820 nm
Bridgeable distance Max. 1.5 km/0.9 miles Permissible path attenuation Max. 8 dB, for glass fiber 62.5/125 µm
System interface (Port B) Bridgeable distance Max. 2 km/1.24 miles
IEC 60870-5-103 protocol, single MODBUS RTU, DNP 3.0
RS 232/RS 485 RS485
Terminal At the bottom part of the housing, Terminal At the bottom part of the housing,
mounting location “B”, 9-pin mounting location “B”, 9-pin
subminiature connector (SUB-D) subminiature connector (SUB-D)
Test voltage 500 V/50 Hz Test voltage 500 V/50 Hz
Transmission rate Min. 1200 Bd, max. 115000 Bd, Transmission rate Up to 19200 baud
factory setting 9600 Bd
Bridgeable distance Max. 1 km/3300 ft
Bridgeable distance RS232 15 m/49.2 ft
Fiber optic
Bridgeable distance RS485 1 km/3300 ft
Connection fiber-optic cable ST connector transmitter/receiver
Fiber optic
Terminal At the bottom part of the housing,
Connection fiber-optic cable ST connector mounting location “B”
Terminal At the bottom part of the housing, Optical wavelength λ = 820 nm
mounting location “B”
Permissible path attenuation Max. 8 dB, for glass fiber 62.5/125 µm
Optical wavelength λ = 820 nm
Bridgeable distance Max. 1.5 km/0.9 miles
Permissible path attenuation Max. 8 dB, for glass fiber 62.5/125 µm
Bridgeable distance Max. 1.5 km/0.9 miles
Functions
IEC 61850 protocol
Voltage protection (ANSI 27, 59)
Ethernet, electrical (EN100) for IEC 61850 and DIGSI
Undervoltages 27-1, 27-2 (V<, V<<), Vp<
Terminal At the bottom part of the housing,
mounting location “B”, two RJ45 Measured quantity used with
connectors, 100BaseT in acc. with Three-phase connection Positive-sequence system of the voltages
IEEE 802.3 Phase-to-phase voltage
Phase-to-ground voltage
Test voltage 500 V/50 Hz
Single-phase connection Connected single-phase-to-ground
Transmission rate 100 Mbit/s voltage
Bridgeable distance Max. 20 m/65.6 ft Setting ranges
Ethernet, optical (EN100) for IEC 61850 and DIGSI Connection of phase-to-ground 10 to 120 V (in steps of 1 V)
voltage
Terminal At the bottom part of the housing, Connection of phase-to-phase 10 to 120 V (in steps of 1 V)
mounting location “B”, LC connector, voltage
100BaseT in acc. with IEEE 802.3 Connection of single phase 10 to 120 V (in steps of 1 V)
Transmission rate 100 Mbit/s Dropout ratio1) r 1.01 to 3 (in steps of 0.01)
Optical wavelength λ = 1300 nm for 27-1, 27-2 (V<, V<<)

Bridgeable distance max. 2 km/1.24 miles Dropout threshold for r · 27-1 (V<) Max. 130 V for phase-to-phase voltage
r · 27-2 (V<<) Max. 225 V for phase-to-ground volt.
r · Vp<
Hysteresis Min. 0.6 V

Time delays T27-1(V<), T27-2 (V<<), 0 to 100 s (in steps of 0.01 s)


TVp< or ∞ (disabled)

1) r = Vdropout/Vpickup

Siemens SIP February 2011 13


11 Generator Protection / 7RW80

Technical data

Overvoltages 59-1, 59-2 (V>, V>>), Vp> Times


Measured quantity used with Pickup times f >, f< Approx. 80 ms
Three-phase connection Positive-sequence system of the voltages Dropout times f >, f< Approx. 80 ms
Negative-sequence system of the voltages Dropout difference
Phase-to-phase voltage Δ f = |pickup value – dropout value| 0.02 to 1 Hz
Phase-to-ground voltage
Dropout
Single-phase connection Connected single-phase-to-ground Ratio undervoltage blocking Approx. 1.05
voltage
Tolerances
Setting ranges Pickup thresholds
Connection of phase-to-ground Frequency 81O/U f >, f< 15 mHz (with V = Vnom, f = fnom)
voltage: Undervoltage blocking 3 % of setting value or 1 V
Evaluation of phase-to-ground 20 to 150 V (in steps of 1 V) Delay times 1 % of the setting value or 10 ms
voltages
Load restoration
Evaluation of phase-to-phase 20 to 260 V (in steps of 1 V)
voltages Setting ranges
Evaluation of positive-sequence 20 to 150 V (in steps of 1 V) Number of load restoration elements 4
system Start threshold with fnom = 50 Hz 40 Hz to 60 Hz
Evaluation of negative-sequence 2 to 150 V (in steps of 1 V) (in steps of 0.01 Hz)
system Start threshold with fnom = 60 Hz 50 Hz to 70 Hz
Connection of phase-to-phase (in steps of 0.01 Hz)
voltages:
Pickup threshold 0.02 Hz to 2 Hz (in steps of 0.01 Hz)
Evaluation of phase-to-phase 20 to 150 V (in steps of 1 V)
=|Start threshold – pickup threshold|
voltage
Evaluation of positive-sequence 20 to 150 V (in steps of 1 V) Dropout threshold 0 Hz to 2 Hz (in steps of 0.01 Hz)
system =|Start threshold – dropout threshold|
Evaluation of negative-sequence 2 to 150 V (in steps of 1 V) Delay times T pickup and dropout 0 s to 10800 s (in steps of 0.01 s)
system
Delay times T CB-Close command 0.01 s to 32 s (in steps of 0.01 s)
Connection single phase 20 to 150 V (in steps of 1 V)
Dropout ratio r Times
for 59-1, 59-2 (V>, V>>) 0.90 to 0.99 (in steps of 0.01 V) Pickup times Approx. 100 ms at fnom = 50 Hz
Approx. 80 ms at fnom = 60 Hz
Dropout threshold for r · 59-1 (V>) Max. 150 V for phase-to-phase voltage
r · 59-2 (V>>) Max. 260 V for phase-to-ground volt. Dropout times Approx. 100 ms at fnom = 50 Hz
r · Vp> Approx. 80 ms at fnom = 60 Hz
Hysteresis Min. 0.6 V Tolerances
Pickup frequencies 15 mHz (with V = Vnom, f = fnom ± 5 Hz)
Time delay T59-1, T59-2 (V>, V>>), 0 to 100 s (in steps of 0.01 s) Undervoltage blocking 3 % of setting value or 1 V
TVp> or ∞ (disabled) Time delays 1 % of setting value or 10 ms
Times Overexcitation protection (ANSI 24)
Pickup times
Undervoltage 27-1, 27-2 (V<, V<<) Setting ranges
27-1 V1, 27-2 V1 , Vp< Approx. 50 ms Pickup threshold (alarm stage) 1 to 1.20 (in steps of 0.01)
Overvoltage 59-1, 59-2 V / Vnom
(V>, V>>, Vp>) Approx. 50 ms
f / f nom
Overvoltage 59-1 V1, 59-2 V1,
59-1 V2, 59-2 V2, Vp> (V1, V2) Approx. 60 ms Pickup threshold 1 to 1.40 (in steps of 0.01)
Dropout times of stage characteristic
Undervoltage 27-1, 27-2 (V<, V<<) V / Vnom
27-1 V1, 27-2 V1 , Vp< Approx. 50 ms
f / f nom
Overvoltage 59-1, 59-2
(V>, V>>, Vp>) Approx. 50 ms Time delays T V/f>, T V/f>> 0 s to 60 s or ∞ (ineffective)
Overvoltage 59-1 V1, 59-2 V1, (alarm and stage characteristic) (in steps of 0.01)
59-1 V2, 59-2 V2, Vp> (V1, V2) Approx. 60 ms Characteristic value pairs V/f 1.05/1.10/1.15/1.20/1.25/1.30/1.35/1.40
Tolerances Associated time delay for t 0 s to 20,000 s (in steps of 1 s)
Pickup voltage limits 3 % of setting value or 1 V (V/f thermal replica)
Delay times T 1 % of setting value or 10 ms
Cooling time TCOOL 0 s to 20,000 s (in steps of 1 s)
Frequency protection (ANSI 81O/U) Times
Pickup times for 1.1 · setting value Approx. 90 ms
Number of frequency elements 4, each can be set to f > or f<
Dropout times Approx. 60 ms
Setting ranges
Pickup values f > or f< 40 to 60 Hz (in steps of 0.01 Hz) Dropout ratios
for fnom = 50 Hz Dropout/pickup Approx. 0.98
Pickup values f > or f< 50 to 70 Hz (in steps of 0.01 Hz) Tolerances
for fnom = 60 Hz Pickup on V/f 3 % of setting value
Delay times T 0 to 100 s or ∞ (disabled) Delay times T 1 % of setting value or 10 ms
(in steps of 0.01 s) (Alarm and stage characteristic)
Undervoltage blocking, with 10 to 150 V (in steps of 1 V) Thermal replica (time characteristic) 5 %, related to V/f ± 600 ms
positive-sequence voltage V1

14 February 2011 Siemens SIP


11 Generator Protection / 7RW80

Technical data

Jump of voltage vector Synch-check (ANSI 25)


Setting ranges Operating mode • Synch-check
Stage Δϕ 2° to 30° (in steps of 10) Additional release conditions • Live-bus / dead line
Delay time T 0 to 60 s or ∞ (ineffective) • Dead-bus / live-line
(in steps of 0.01 s) • Dead-bus and dead-line
Reset time TReset 0 to 60 s or ∞ (ineffective) • Bypassing
(in steps of 0.01 s)
Voltages
Undervoltage blocking V1> 10 to 125 V (in steps of 0.1 V)
Max. operating voltage Vmax 20 to 140 V (phase-to-phase)
Times (in steps of 1 V)
Pickup times Δϕ Approx. 75 ms Min. operating voltage Vmin 20 to 125 V (phase-to-phase)
Dropout times Δϕ Approx. 75 ms (in steps of 1 V)
Tolerances V< for dead-line 1 to 60 V (phase-to-phase)
Angle jump 0.5° at V > 0.5 Vnom (in steps of 1 V)
Undervoltage blocking 1 % of setting value or 0.5 V V> for live-line 20 to 140 V (phase-to-phase)
Delay times T 1 % or 10 ms (in steps of 1 V)
Flexible protection functions (e.g. ANSI 27, 47, 59, 81R) Primary rated voltage of 0.1 to 800 kV (in steps of 0.01 kV)
transformer V2nom
Operating modes/measuring quantities
3-phase V, V1, V2, 3V0 Tolerances 2 % of pickup value or 2 V
1-phase V, VN, Vx Dropout ratios Approx. 0.9 (V>) or 1.1 (V<)
Without fixed phase relation f, df/dt, binary input, dV/dt Permissible differences
Pickup when Exceeding or falling below threshold Voltage difference 0.5 to 50 V (phase-to-phase)
value V2> V1; V2< V1 (in steps of 1 V)
Setting ranges Tolerance 1V
Pickup thresholds Frequency differences
Voltages V, V1, V2, 3V0 2 to 260 V (in steps of 0.1 V) (f2>f1; f2<f1) 0.01 to 2 Hz (in steps of 0.01 Hz)
Displacement voltage VN 2 to 200 V (in steps of 0.1 V) Tolerance 30 mHz
Frequency fnom = 50 Hz 40 to 60 Hz (in steps of 0.01 Hz) Angle differences 2 ° to 80 ° (in steps of 1 °)
fnom = 60 Hz 50 to 70 Hz (in steps of 0.01 Hz) α2>α1; α2<α1
Tolerance 2°
Rate-of-frequency change df/dt 0.1 to 20 Hz/s (in steps of 0.01 Hz/s) Max. phase displacement 5 ° for Δf w 1 Hz
Rate-of-voltage change 4 V/s to 100 V/s (in steps of 1 V/s) 10 ° for Δf w 1 Hz
Dropout ratio >- element 1.01 to 3 (in steps of 0.01)
Dropout ratio <- element 0.7 to 0.99 (in steps of 0.01) Vector group matching by angle 0 ° to 360 ° (in steps of 1 °)
Dropout difference f 0.02 to 1 Hz (in steps of 0.01 Hz) Different voltage transformers 0.5 to 2 (in steps of 0.01)
Pickup delay time (standard) 0 to 60 s (in steps of 0.01 s) V1/V2
Trip delay time 0 to 3600 s (in steps of 0.01 s) Times
Dropout delay time 0 to 60 s (in steps of 0.01 s) Minimum measuring time Approx. 80 ms
Times Max. duration TSYN DURATION 0.01 to 1200 s; ∞ (in steps of 0.01 s)
Pickup times Supervision time TSUP VOLTAGE 0 to 60 s (in steps of 0.01 s)
Voltage (phase quantities) Tolerance of all times 1 % of setting value or 10 ms
With 2 times the setting value Approx. 30 ms
With 10 times the setting value Approx. 20 ms Measuring values of synch-check function
Voltages (symmetrical components) Reference voltage V1 and voltage In kV primary, in V secondary
With 2 times the setting value Approx. 40 ms to be synchronized V2 or in % Vnom
With 10 times the setting value Approx. 30 ms Range 10 to 120 % of Vnom
Frequency Approx. 100 ms Tolerance*) w 1 % of measured value
Rate-of-frequency change or 0.5 % of Vnom
With 1.25 times the setting value Approx. 220 ms
Frequency of voltage V1 and V2 f1, f2 in Hz
Rate-of-voltage change
Range 25 Hz w f w 70 Hz
With 2 times the setting value Approx. 220 ms
Tolerance*) 20 mHz
Binary input Approx. 20 ms
Voltage difference (V2 – V1) In kV primary, in V secondary
Dropout times
or in % Vnom
Voltage (phase quantities) < 20 ms
Range 10 to 120 % Vnom
Voltages (symmetrical components) < 30 ms
Tolerance*) w 1 % of measured value or 0.5 %
Frequency < 100 ms
of Vnom
Rate-of-frequency change < 200 ms
Rate-of-voltage change < 220 ms Frequency difference (f2 – f1) In mHz
Binary input < 10 ms Range fnom ± 3 Hz
Tolerance*) 30 mHz
Tolerances
Pickup thresholds Angle difference (α2 – α1) In °
Voltage 3 % of setting value or 0.2 V Range 0 to 180 °
Voltage (symmetrical 4 % of setting value or 0.2 V Tolerance*) 1°
components)
Frequency 3 degrees, 15 mHz
Rate-of-frequency change 5 % of setting value or 0.05 Hz/s
Rate-of-voltage change 5 % of setting value or 2 V/s
Times 1 % of setting value or 10 ms *) With rated frequency.

Siemens SIP February 2011 15


11 Generator Protection / 7RW80

Technical data

Additional functions Trip circuit monitoring


Operational measured values With one or two binary inputs
Voltages Commissioning aids
Phase-to-ground voltages In kV primary, in V secondary Phase rotation test,
VA-N, VB-N, VC-N or in % Vnom operational measured values,
Phase-to-phase voltages circuit-breaker test by means
VA-B, VB-C, VC-A, VSYN of control function,
VN, Vph-N, Vx or V0 creation of a test fault report,
Positive-sequence component V1 creation of messages
Negative-sequence component V2
Clock
Range 10 to 120 % of Vnom
Tolerance*) 1.5 % of measured value Time synchronization Binary input,
or 0.5 % of Vnom communication
Frequency f In Hz Setting group switchover of the function parameters
Range fnom ± 5 Hz Number of available setting groups 4 (parameter group A, B, C and D)
Tolerance*) 20 mHz Switchover performed Via keypad, DIGSI using the operator
Max. / Min. report interface, protocol using port B or
binary input
Report of measured values With date and time
Breaker control
Reset, automatic Time of day adjustable (in minutes,
0 to 1439 min) Number of switching units Depends on the binary inputs and
Time frame and starting time adjust- outputs available
able (in days, 1 to 365 days, and ∞) Interlocking Freely programmable
Reset, manual Using binary input, Messages Feedback messages, closed, open,
using keypad, intermediate position
via communication Control commands Single command / double command
Min./Max. values for voltages VA-N, VB-N, VC-N (VL1-E, VL2-E, VL3-E) Switching command to circuit- 1-, 1½- and 2-pole
V1 (positive-sequence component) breaker
VA-B, VB-C, VC-A (VL1-L2, VL2-L3, Programmable logic controller PLC logic, graphic input tool
VL3-L1)
Local control Control via menu,
Local measured values monitoring assignment of function keys
Voltage asymmetry Vmax/Vmin > balance factor, Remote control Via communication interfaces,
for V>Vlim using a substation automation and
Voltage phase sequence Clockwise (ABC) / control system (e.g. SICAM),
counter-clockwise (ACB) using DIGSI 4 (e.g. via modem)
Fault event recording
Recording of indications of the last CE conformity
8 power system faults
This product is in conformity with the Directives of the European Commu-
Recording of indications of the last nities on the harmonization of the laws of the Member States relating to
3 power system ground faults electromagnetic compatibility (EMC Council Directive 89/336/EEC) and
Time stamping electrical equipment designed for use within certain voltage limits (Council
Directive 73/23/EEC).
Resolution for event log 1 ms
(operational annunciations) This unit conforms to the international standard IEC 60255, and the Ger-
man standard DIN 57435/Part 303 (corresponding to VDE 0435/Part 303).
Resolution for trip log 1 ms
(fault annunciations) Further applicable standards: ANSI/IEEE C37.90.0 and C37.90.1.
Maximum time deviation 0.01 % The unit conforms to the international standard IEC 60255, and the Ger-
(internal clock) man standard DIN 57435/Part 303 (corresponding to VDE 0435/Part 303).
This conformity is the result of a test that was performed by Siemens AG in
Battery Lithium battery 3 V/1 Ah,
accordance with Article 10 of the Council Directive complying with the
type CR 1/2 AA, message “Battery
generic standards EN 50081-2 and EN 50082-2 for the EMC Directive and
Fault” for insufficient battery charge
standard EN 60255-6 for the “low-voltage Directive”.
Oscillographic fault recording
Maximum 8 fault records saved,
Notes
memory maintained by buffer battery
in case of loss of power supply Subject to change without proir notice.
Recording time 5 s per fault record, in total up to 18 s We reserve the right to include modifications.
Sampling rate for 50 Hz 1 sample/1.00 ms Drawings are not binding.
Sampling rate for 60 Hz 1 sample/0.83 ms If not stated otherwise, all dimensions in this catalog are given in mm/inch.
Operating hours counter The information in this document contains general descriptions of the tech-
nical options available, which do not always have to be present in individual
Display range Up to 7 digits
cases. The required features should therefore be specified in each individual
case at the time of closing the contract.
*) With rated frequency.

16 February 2011 Siemens SIP


11 Generator Protection / 7RW80

Selection and ordering data Description Order No.

7RW80 voltage and frequency relay 7RW80o0 – ooooo – oooo


Measuring inputs, binary inputs and outputs
Housing 1/6 19"; 3 x V, 3 BI, 5 BO (2 Changeover/Form C),
1 Live status contact 1
see next pages
Housing 1/6 19"; 3 x V, 7 BI, 8 BO (2 Changeover/Form C),
1 Live status contact 2

Auxiliary voltage
24 V / 48 V DC 1
60 V / 110 V / 125 V / 220 V / 250 V, 115 V AC, 230 V AC 5

Construction
Surface-mounting housing, screw-type terminal B
Flush-mounting housing, screw-type terminal E

Region-specific default and language settings


Region DE, IEC, language German (language changeable), standard front A
Region World, IEC/ANSI, language English (language changeable), standard front B
Region US, ANSI, language US-English (language changeable), US front C
Region FR, IEC/ANSI, language French (language changeable), standard front D
Region World, IEC/ANSI, language Spanish (language changeable), standard front E
Region World, IEC/ANSI, language Italian (language changeable), standard front F
Region RUS, IEC/ANSI, language Russian (language changeable), standard front G
Region CHN, IEC/ANSI, language Chinese (language not changeable), Chinese front K

Siemens SIP February 2011 17


11 Generator Protection / 7RW80

Selection and ordering data Description Order No. Order


code
7RW80 voltage and frequency relay 7RW80oo – ooooo – oooo L 0 o
Port B (at bottom of device, rear)
No port 0
IEC 60870-5-103 or DIGSI 4/modem, electrical RS232 1 see next
IEC 60870-5-103 or DIGSI 4/modem, electrical RS485 2 page

IEC 60870-5-103 or DIGSI 4/modem, optical 820 nm, ST connector 3


PROFIBUS-DP Slave, electrical RS485 9 L0A
PROFIBUS-DP Slave, optical, double ring, ST connector 9 L0B
MODBUS, electrical RS485 9 L0D
MODBUS, optical 820 nm, ST connector 9 L0E
DNP 3.0, electrical RS485 9 L0G
DNP 3.0, optical 820 nm, ST connector 9 L0H
IEC 61850, 100 Mbit Ethernet, electrical, double, RJ45 connector 9 L0R
IEC 61850, 100 Mbit Ethernet, optical, double, LC connector 9 L0S

Port A (at bottom of device, in front)


No port 0
With Ethernet interface (DIGSI, not IEC 61850), RJ45 connector 6

Measuring/fault recording
With fault recording, average values, min/max values 1

18 February 2011 Siemens SIP


11 Generator Protection / 7RW80

Selection and ordering data Description Order No.


7RW80 voltage and frequency relay 7RW80o0 – ooooo – oDo0
Designation ANSI No. Description
Voltage and frequency protection
27/59 Under/overvoltage
64/59N Displacement voltage
81U/O Under/overfrequency
47 Phase rotation
74TC Trip circuit supervision
86 Lockout
Parameter changeover
Monitoring functions
Control of circuit-breaker
Flexible protection functions (voltage parameters):
Rate-of-frequency change, rate-of-voltage change A
Voltage, frequency protection and load restoration
27/59 Under/overvoltage
64/59N Displacement voltage
81U/O Under/overfrequency
Load restoration
47 Phase rotation
74TC Trip circuit supervision
86 Lockout
Parameter changeover
Monitoring functions
Control of circuit-breaker
Flexible protection functions (voltage parameters):
Rate-of-frequency change, rate-of-voltage change B
Voltage, frequency protection and synch-check
27/59 Under/overvoltage
81U/O Under/overfrequency
25 Synch-check
47 Phase rotation
74TC Trip circuit supervision
86 Lockout
Parameter changeover
Monitoring functions
Control of circuit-breaker
Flexible protection functions (voltage parameters):
Rate-of-frequency change, rate-of-voltage change C
Voltage, frequency, overexcitation protection and jump of voltage vector
27/59 Under/overvoltage
64/59N Displacement voltage
81U/O Under/overfrequency
24 Overexcitation
Jump of voltage vector
47 Phase rotation
74TC Trip circuit supervision
86 Lockout
Parameter changeover
Monitoring functions
Control of circuit-breaker
Flexible protection functions (voltage parameters):
Rate-of-frequency change, rate-of-voltage change D
Voltage, frequency, overexcitation protection, jump of voltage vector, load restoration and synch-check
27/59 Under/overvoltage
81U/O Under/overfrequency
24 Overexcitation
Jump of voltage vector
Load restoration
25 Synch-check
47 Phase rotation
74TC Trip circuit supervision
86 Lockout
Parameter changeover
Monitoring functions
Control of circuit-breaker
Flexible protection functions (voltage parameters):
Rate-of-frequency change, rate-of-voltage change E

Siemens SIP February 2011 19


11 Generator Protection / 7RW80

Sample order Position Order No. + Order code


7RW8020-5EC96-1DA0+L0G

6 I/O’s: 7 BI/8 BO, 1 live status contact 2

8 Power supply: 60 to 250 V DC, 115 V AC to 230 V AC 5


9 Unit version: Flush-mounting housing, screw-type terminals E
10 Region: US, English language (US); 60 Hz, ANSI C
11 Communication: System interface: DNP 3.0, RS485 9 L0G
12 Communication: Ethernet interface (DIGSI, not IEC 61850) 6
13 Measuring/fault recording: Extended measuring and fault records 1
14/15 Protection function package: Basic voltage and frequency protection DA

Accessories Description Order No.

DIGSI 4
Software for configuration and operation of Siemens protection units
running under MS Windows 2000/XP Professional Edition/Vista.

Basis Full version with license for 10 computers, on CD-ROM


(authorization by serial number) 7XS5400-0AA00
Professional DIGSI 4 Basis and additionally SIGRA (fault record analysis),
CFC Editor (logic editor), Display Editor (editor for default
and control displays) and DIGSI 4 Remote (remote operation) 7XS5402-0AA00
Professional + IEC 61850
Complete version:
DIGSI 4 Basis and additionally SIGRA (fault record analysis),
CFC Editor (logic editor), Display Editor (editor for default
and control displays) and DIGSI 4 Remote (remote operation)
+ IEC 61850 system configurator 7XS5403-0AA00

Terminals
Voltage terminal block C or block E C53207-A406-D181-1
Voltage terminal block D (inverse print) C53207-A406-D182-1
Voltage terminal short-circuit links (6 pieces) C53207-A406-D194-1

Manual for 7RW80


English C53000-G1140-C233-A1
German C53000-G1100-C233-A1

Mounting rail set for 19" rack C73165-A63-D200-1

20 February 2011 Siemens SIP


11 Generator Protection / 7RW80

Connection diagram

Flush and surface mounting housing

7RW801

Interference
suppression
capacitor at
relay outputs,
ceramic,
SIP-0011.en.ai

2.2 nF,
250 V

Fig. 14 7RW801 connection diagram

Siemens SIP February 2011 21


11 Generator Protection / 7RW80

Connection diagram

Flush and surface mounting housing

7RW802

Interference
suppression
capacitor at
relay outputs,
ceramic,
SIP-0012.en.ai

2.2 nF,
250 V

Fig. 15 7RW802 connection diagram

22 February 2011 Siemens SIP


11 Generator Protection / 7RW80

Dimension drawings in mm / inch

SIP-0013.en.ai

Rear view Side view Front view Panel cutout

Fig. 16
7RW80 protection relays
for panel flush mounting/cubicle mounting
SIP-0014.en.ai

Side view Front view

Fig. 17
7RW80 protection relays
for panel surface mounting

Siemens SIP February 2011 23

You might also like