Binary Input 23BE23

Applicati on
The binary input board 23BE23 is used for the
isolated input of up to 16 binary process
signals. Scanning and processing of the inputs
are executed with the high time resolution of 1
ms. Allocation of an input to a processing
function can be done according to the rules of
configuration. The board 23BE23 can process
the following types of signals:
16 single indications with time stamp
8 double indications with time stamp
2 digital measured values with 8 bit
1 digital measured value with 16 bit
16 pulse counters
Characteristics
Eight inputs each form a group with a common
return. The 16 inputs form two groups. The
inputs are potentially isolated by means of opto-
couplers. The board allows process signal
voltages from 24 to 60 V DC. The input circuit is
dimensioned in that way, that current regulative
diodes keep the signal current constant.
The board has sixteen light emitting diodes to
indicate the signal-state. The LEDs are
organized in two columns on the front plate.
The LED follows directly the input.
The maximum permissible frequency for
counter pulses is 120 Hz.



Fig. 1: Block diagram
Binary input board 23BE23






RTU560
Data Sheet Binary Input 23BE23

2 Doc. No.: 1KGT 150 571 V003 1

The binary input board 23BE23 can execute the
following processing functions for the different
types of signals:
Digital filtering to suppress contact
bounce
Suppression of technologically
caused chattering signals
Consistency check for all binary
input Intermediate position
suppression and monitoring for
double indications
Channels allocated to digital
measured values
Summation of increment pulses to
form counter values in 31 bit
counter value registers
Relocation of count values into
other relocation registers on
request
The effective functionality of the board depends
on the executed firmware version. The
selection of the requested firmware version for
RTU560 stations is done by a jumper on the
23BE23 board.
The 23BE23 board has a buffer which allows
the temporary storage of 50 time-stamped
event messages in chronological order
designated for transmission to the
communication unit.

The micro-controller on the board processes all
time-critical tasks of the parameterized
processing functions. Moreover it carries out
the interactive communication with the RTU560
system bus. All configuration data and
processing parameters are loaded from the
communication unit via the RTU560 system
bus.
The board is equipped with a serial interface to
the RTU560 system bus. This board cant be
used in the basic-subrack of a RTU232 system
(parallel system bus).
During initialization and operation the board
carries out a number of tests. If a fault occurs it
is reported to the communication unit. All fault
conditions impairing the function of the board
are displayed as common fault signal with a
light emitting diode (ST) on the front panel. A
failure of the board is detected by the
communication unit.
RTU560
Data Sheet Binary Input 23BE23

Doc. No.: 1KGT 150 571 V003 1 3
Technical Data
In addition to the RTU560 general technical data, the following applies:

Input Channels
Inputs 16, in 2 groups of 8 with
common return per group
Input voltage 24, 48, 60 V DC
log. 0: +9 V
log. 1: +18 V
Input current Typically. 2 mA
for 24 to 60 V DC

Power Supply
Supply 5 V / 140 mA

Mechanical Layout
Printed circuit
board
3HE, Euro card format
(160 x 100)
Front panel 4R, 1 Slot (20 mm)
weight approx. 0.2 kg

Connection Type
Connector Indirect, 48 pole
Type F DIN 41612

Test Voltage
AC Test Voltage
EN 61000-4-16
IEC 60870-2-1
(class VW3)
2,5 kV, 50 Hz
Test duration: 1 min
Impulse Voltage
with stand test
IEC 60255-5
IEC 60870-2-1
(class VW 3)
5 kV (1,2 / 50 s)

Immunity Test
Electrostatic
discharge
Immunity Test
IEC 61000-4-2
(level 3)
6 kV Contact
8 kV Air

Performance criteria A
Radiated Radio-
Frequency
Electromagnetic
Field Immunity
Test
IEC 61000-4-3
(level 3)
10 V/m

Performance criteria A
Immunity to
Electrical Fast
Transient / Burst
IEC 61000-4-4
(level 3)
2 kV

Performance criteria A
Surge Immunity
Test
IEC 61000-4-5
(level 3)
2 kV

Performance criteria A
Immunity to
Conducted
Disturbances,
induced by Radio-
Frequency Fields
IEC 61000-4-6
(level 3)
10 V

Performance criteria A

Environmental conditions
Temperature -10 ... 70 C
Relative humidity 5 ... 95 %
(non condensing)

Ordering Information
Front plate
plastic
Light beige
23BE23 R5001 1 KGT 012 100 R5001








RTU560
Data Sheet Binary Input 23BE23

4 Doc no.: 1KGT 150 571 V003 1







































































































































Note:
We reserve the right to make technical changes or modify the
contents of this document without prior notice. With regard to
purchase orders, the agreed particulars shall prevail. ABB AG
does not accept any responsibility whatsoever for potential errors
or possible lack of information in this document.
We reserve all rights in this document and in the subject matter
and illustrations contained therein. Any reproduction, disclosure
to third parties or utilization of its contents - in whole or in parts -
is forbidden without prior written consent of ABB AG.

Copyright2011 ABB
All rights reserved

You might also like