ISA T 3000 Primary current injection test set in action at a HV switchyard in Indonesia. T 3000 is designed to perform primary tests requested in substations commissioning. It performs different tests and measurements on current transformers, voltage transformers, power transformers, protection relays, energy meters and transducers. ⚡ Learn More https://lnkd.in/g6HXvTgh Erif Triandari #DobleTested #substations #electricalengineering
PLC and Protection Engineer at PT. Royal Energy Resources - Schweitzer Engineering Laboratories | Director of PT. Eyiptronics Solusi Engineering
Primary Current Injection Test for testing accuracy of CT Ratio. Actually, our project is only installing OLS (Over Load Shedding) Relay. but there is only installed 1 core for protection device, and the condition now the CT Protection core has been connected to 2 protection device (LCD and OCR). consider the CT burden, we cant add more device to CT connection. so we split the core. core 1 for LCD core 2 for OCR and OLS from this moment, i try the Primary Injection Test Set from Doble Engineering ISA T 3000. Thanks to PLN UP2B Jatim and PLN ULTG Probolinggo that give me the experience, i usually do secondary injection test, now i have experience to do primary injection, in the middle of HV Switchyard
-