Generation of High AC Voltage

Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1of 13

Generation of High AC voltage

POWE522 , BAU
GENERATION OF HIGH A.C. VOLTAGES

• Most of the present-day transmission and distribution networks are


operating on A.C. voltages and hence most of the testing equipment
relate to high A.C. voltages.
• Test transformers normally used for the purpose have low power rating
but high voltage ratings.
• These transformers are mainly used for short time tests on high voltage
equipment.
Cascaded Transformers
• For voltages higher than 400 KV, it is
desired to cascade two or more
transformers depending upon the
voltage requirements.
• The transformers are usually
identical, but transformers of
different designs can also be used.
• With this, the weight of the whole
unit is subdivided into single units
and, therefore, transport and erection
becomes easier.
Cascaded Transformers
• Fig.1 shows a basic scheme for cascading
three transformers.
• The primary of the first stage transformer is
connected to a low voltage supply. A voltage
is available across the secondary of this
transformer.
• The tertiary winding (excitation winding) of
first stage has the same number of turns as
the primary winding and feeds the primary of
the second stage transformer.
• The potential of the tertiary is fixed to the
potential V of the secondary winding as
shown in Fig. 1.
Cascaded Transformers

• The secondary winding of the second stage


transformer is connected in series with the
secondary winding of the first stage
transformer, so that a voltage of 2V is available
between the ground and the terminal of secondary
of the second stage transformer.
• Similarly, the stage-III transformer is connected in
series with the second stage transformer. With this
the output voltage between ground and the third
stage transformer, secondary is 3V.
Cascaded Transformers
• It is to be noted that the individual stages except the upper
most must have three-winding transformers. The upper
most, however, will be a two winding transformer.

• The tank of stage-I transformer is earthed. The tanks of


stage-II and stage-III transformers have potentials of V and
2V, respectively above earth and, therefore, these must be
insulated from the earth with suitable solid insulation.
• Through H.T. bushings, the leads from the tertiary winding
and the h.v. winding are brought out to be connected to the
next stage transformer.
Reactive Power Compensation
• The test transformers are used for testing the insulation of various electrical
equipment. This means the load connected to these transformers is highly
capacitive.
• The voltage across the load becomes higher than the rated voltage as the load
draws leading current.
• Regulate the input voltage to the test transformer
• A variable inductor should be connected across the supply
SERIES RESONANT CIRCUIT

• But cascading of transformer has also some disadvantages such as


(1) design is complicated. (2) size is bulky.
(3) costly. (4) losses are more (summation of individual transformer) and hence
efficiency reduces.

• Resonant transformer is one of the best choice for high voltage generation which
operates on resonance phenomenon (XL = Xc).

• In resonance condition, the current through test object is very large and that is
limited only by the resistance of the circuit.

• The waveform of the voltage across the test object will be purely sinusoidal.
SERIES RESONANT CIRCUIT

• L1 represents the inductance of the voltage regulator and the transformer primary.
L exciting inductance of the transformer, L2 the inductance of the transformer
secondary and C the
capacitance of the load.
• It is possible that for certain loading, resonance may occur in the circuit suddenly
and the current will then only be limited by the resistance of the circuit and the
voltage across the test specimen may go up as high as 20 to 40 times the desired
value.

With series resonance, the resonance is controlled


at fundamental frequency and hence no unwanted
resonance occurs.
SERIES RESONANT CIRCUIT

• If N is the transformation ratio and L is the


inductance on the low voltage side of the
transformer, then it is reflected with L value on
the secondary side (load side) of the transformer.
• For certain setting of the reactor, the inductive
reactance may equal the capacitive reactance of
the circuit, hence resonance will take place.
SERIES RESONANT CIRCUIT
• The inductance of these inductors can be varied over a wide range depending
upon the capacitance of the load to produce resonance.
• After the resonance condition is achieved, the output voltage can be increased by
increasing the input voltage.

where Q is the quality factor of the inductor which usually


varies between 40 and 80.
Advantages of Resonant transformer:

(1) Application: Resonant transformer is able to produce high voltage and high current
and for extremely high voltage requirement, the cascading of resonant transformer
is also possible.
(2) Output waveform: It gives an output of pure sine wave
(3) Power requirement: The power requirement is less ( only 5 to 10 % of total kVA
required )
(4) Design: Simple and compact test arrangement.
(5) Safety: If the test object is failed during testing, then there is no danger of high
power arcing and heavy current surges occurrence because , due to failure of test
object, the resonance disappears and voltage across test
object collapse.

You might also like