Panel Enhancements FACP

Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1of 57

July 19, 2016

4007ES Enhancements
Internal Launch Presentation
For Internal Use by Tyco Employees and Tyco Authorized Partners Only
4007ES Enhancements
Product Positioning and Project
Overview
The ES Family -Before Enhancements
3 Panels
One Family
One Software Platform and Programmer

4007ES 4010ES 4100ES

Target: Small Projects and Target: Medium-sized Buildings Target: Medium- to Large-
Conventional System Upgrades 250 Addressable Point capacity sized Projects
100-250 Addressable Point capacity TrueAlert ES Addressable Notification 2,500 Points capacity
TrueAlert ES Addressable Notification Supports both conventional and TrueAlert ES Addressable
Expandable from 8 to 32 Conventional addressable sensors Notification
Zones TrueInsight Supports both conventional and
4.3 Inch (10 cm) Color Touch Screen addressable sensors
Suppression Release
Supports both conventional and TrueInsight
Network Compatible
addressable sensors Suppression Release
Two models one for migrations (the Network Compatible
hybrid); one for new construction (fully
Integrated Network Voice &
addressable)
Fire Telephones
TrueInsight
3
4007ES Enhancements Overview

This 4007ES enhancements launch includes the following:

• 4007ES Network Card - functions on a 4100ES network with or without other ES family
panels (full peer-to-peer operation).
• A re-packaged network card to mount in a 4007ES
• 4007ES suppression listings
• 4007ES RS-232 Card

4
Product Portfolio North America –
with 4007ES Enhancemnts

4007ES 4010ES 4100ES

Small Projects & Medium sized buildings


Medium to Large size
Target Markets Conventional System Releasing Panel – Projects
Upgrades Network Panel

100-250 Addressable 250 Addressable Points


Point Capacity 2,500 Points
8-32 Points Conventional 8 Points Conventional

250 Points over 3 isolated 2,500 Points over 10


Loops 250 Points over 1 Loop
loops Loops

Compatible with the


Yes Yes Yes
Network

Listed for Suppression Yes Yes Yes

5
4007ES Enhancements
Network Overview
4007ES Network Node

Before the launch of 4007ES network cards:

• The 4010ES was the lowest capacity


network node in the portfolio
• This caused competitive issues in the
outlying buildings at university campuses
where only a small number of points was
required
• The 4007ES panel is more competitive in
those situations
• The cost of the Network Interface Card
(NIC) for a 4007ES is priced 5% less than
the equivalent 4010ES Network Interface
Card, further increasing our
competitiveness.

7
4007ES Networking

Networking the 4007ES does not limit any of the capacities of


the 4007ES. The panel is still able to support:

 100-250 Addressable
Point capacity
 Expansion from 8 to 32
Conventional Zones
(important for 4002
retrofits)
 All optional modules
including the network
card

• The network card fits in either the Hybrid or the IDNAC panel and functions the same way in
either panel
8
4007ES Networking

• The 4007ES uses the same programmer as the current ES network panels
• The 4007 ES provides full peer to peer networking:
 100 point limit on the number of points that can be made external
 Provides network synchronization of notification appliances
 Can act as the time keeper when required
 Is able to make all points public to an NDU, TSW or any other network node capable of
supporting external points

9
Accelerates Product Obsolescence
• There is currently no drop-in alternative for a 4002 on a 4120 or 2120 Network
• The 4007ES Network Node will serve as a drop-in solution for 4002 Standalone and 4120
Network Panels

4002 4007ES

• Conventional 32-zone panel • Addressable panel with conventional 32-zone


• 2120 Network compatible capability
• 4120 Network compatible • 250 addressable point capacity
• ESP programming • 4120 Network compatible
• ES programming

10
Network – Competitive Analysis
Silent Knight SIEMENS
SIMPLEX NOTIFIER
EST EST3 FARENHYT IFP FIREFINDER GAMEWELL- MIRCOM
Feature 4100ES HS Noti-Fire-
NETWORK 2000 XLS FCI E3 Network FLEXNET
Network Net
NETWORK NETWORK
99 64 Nodes single
Nodes per
686 (with 7 64 16 200 64 loop; 122 nodes 63
network loop
loop TSW) two loops
Distance 5,000 ft. Repeater required
between nodes 10,000 ft. between any 3 for distances >20 3,000 ft. 4,700 ft. 3,000 ft. 4,000 ft.
(#18) nodes ft.
Multiple network
7 No No No Yes 2 No
loops
4100ES,
NFS(2)-3030,
4010ES;
IFP-2000/ECS, NFS(2)-640, XLS(V),
Panel nodes 4100U/+/, EST3, EST3X E3, S3 FX-2000N
RPS-2000 NFS- MXL(V)
Classic; 4020,
320
4007ES
Network strobe
Yes ? Yes No ? Yes Yes
synchronization
DESIGO CC
Graphics FIREWORKS FIRE SAFETY
TSW No ONYXWorks FOCALPOINT OpenGN
workstation FWUL5W7 MGT
SYSTEM
Yes (includes
Client Server
Android, IOS Limited No No Yes No ?
operation
mobile clients)

11
Network Applications
4007ES Network Applications: Multi-Building
Campus, Small Building Application

TSW Client at Guard’s Shack email / Mobile


TSW Client Manager’s Office App
(supervised / full control)
(unsupervised / view only)
Agency Listed TSW Client Manager’s Home
FA Ethernet LAN (unsupervised / view only)

Customer
Customer
LAN / WAN
LAN / WAN
4100ES FA Ethernet Switch
Engineering 4100U
O PE RAT O R
P ULL TO O PEN DO OR

S YSTEM IS N ORM AL
PULL TO OPEN DOOR
EM ERG ENC Y OPER ATING
IN STRU CTION S
AL AR M OR TR OU BLE C O ND I TI ON :
- S YST EM IN D IC AT OR F LAS HI NG , TO N E ON .
Research Center
. . .. .. . .
IN TER FA CE 1 2:3 5 :1 5 a m M ON 1 2 J U N 9 5 TO AC KN O WLED GE :
- P R ESS " A CK " LO CAT ED U ND ER F LA SH IN G
F I RE PR IO R ITY 2 SY ST EM SY STE M SI GN AL S PO WE R I ND I CA TO R.
- R EPE AT O PE R ATI O N U NTI L AL LR EP O RT S AR E
PA N EL AL ARM A LAR M SU PE RV IS OR Y TR O UBL E SI L ENC ED ON A CKN O WLED G ED .

TO SI LEN C E ALA RM SI G NA LS :
- P R ESS " A LA RM S IL EN CE ".
A LAR M
A LA RM AL AR M SU PV TBL A LA RM SY STE M TO RE ST O RE SY ST EM TO N O RM A L:
AC K ACK AC K AC K SI LE NC E R ES E T - P R ESS " S YS TEM R ES ET. "
A CK NOW L EDG E - P R ESS " A CK " TO S IL EN CE T ON E DE VI CE .

P ULL TO O PEN DO OR
PULL TO OPEN DOOR
EM ERG ENC Y OPER ATING
IN STRU CTION S
O PE RAT O R AL AR M OR TR OU BLE C O ND I TI ON :
- S YST EM IN D IC AT OR F LAS HI NG , TO N E ON .
S YSTEM IS N ORM AL

. . .. .. . .
IN TER FA CE 1 2:3 5 :1 5 a m M ON 1 2 J U N 9 5 TO AC KN O WLED GE :
- P R ESS " A CK " LO CAT ED U ND ER FLA SH IN G
F I RE PR IO R ITY 2 SY ST EM SY STE M SI GN AL S PO WE R I ND I CA TO R.
- R EPE AT O PE R ATI O N U NTI L AL L REP O RT S AR E
A CKN O WLED G ED .
P AN EL AL ARM A LAR M SU PE RV IS OR Y TR O UBL E SI L ENC ED ON
TO SI LEN C E ALA RM SI G NA LS :
- P R ESS " A LA RM S IL EN CE ".
A LA
LARRM A LAR M SU PV TBL A LA RM SY STE M
AL L FE MALE AC K
AC K AC K AC K AC K SI LE NC E R ES E T TO RE ST O RE SY ST EM TO N O RM A L:
SP EAKE RS H OR N VOI CE PHON E - P R ESS " S YS TEM R ES ET. "
EVA C E VAC CI RC UIT A CK NOW L EDG E - P R ESS " A CK " TO S IL EN CE T ON E DE VI CE .

W EAT HER CH IM E BRI TIS H M ED ICA L


E VA C EME RGEN CY
W ARN IN G

FREN CH /
ALL S LOW ENG LIS H IN DUS TRI AL
CLE AR WHO OP EVA C FI RE

SP AN ISH / C HEM ICA L


6TH FL G SA EN GLI SH
SP EAKE RS TONE EVA C EM ERG ENC Y

ALL 12 0 BP M JA PANE SE HAZA RDO US


SP EAKE RS H ORN EV AC M A TERIA L

M AN UAL
SE CU RITY C HLO RIN E
AUD IO ST UTTER BYP ASS LEAK
OV ER RID E

VO IC E
PHON E
W ATCH TOUR CO DE
PA GI NG H I- LO 3- 1- 6-4

LO CAL NI GHT
SP EAKE R W AI L SE NSI TIV ITY

A LL FE MALE
VOI CE PHON E
SP EAKE RS H OR N CI RC UIT
EVA C E VAC

W EA THER BRI TIS H M ED ICA L


CH IM E
W AR NIN G E VA C EME RGE NCY

FREN CH /
ALL S LOW ENG LIS H IN DUS TRI AL
CL EAR FI RE
WHO OP EVA C

TSW Server
SP AN ISH /
6TH FL G SA C HEM IC AL
TONE EN GLI SH EM ERG ENC Y
SP EAKE RS EVA C

JA PANE SE HAZA RDO US


ALL 12 0 BP M EV AC
SP EAKE RS H ORN M A TERI AL

4100 FIRE ALARM CONTROL M AN UAL


AU DIO
OV ER RID E
ST UTTER
SE CU RITY
BYP ASS
C HLO RIN E
LEAK

VO IC E
PHON E
H I- LO W ATCH TOUR CO DE
PA GI NG 3- 1- 6-4

LO CAL NI GHT
W AI L
SP EAKE R SE NSI TIV ITY

4100 FIRE ALARM CONTROL

PULL TO OPEN DO O R
Fire Alarm Command Center
PULL TO OPEN DOOR
EM ERG ENCY O PER ATING
INSTRU CT IO NS
O PE RA TO R ALA R M O R T RO UB LE C ON D IT IO N:

SYSTEM IS NO RM AL - S YST EM I N DI C ATO R FL AS HI NG , T O N E ON .

. . .. .. . .
IN TE RFA C E 1 2 :3 5 :1 5 a m M ON 1 2 J UN 9 5 TO A CK N OW LED GE :
- P RES S " A CK " LO C AT ED U ND ER F LA SH IN G
F I RE PR I OR IT Y 2 S YS TEM SY STE M S IG N ALS P OW ER IN D IC AT O R.
- R EPE AT O PE RA TI O N UN TI L ALL R EP OR TS AR E
AC KN OW LED GE D.
P AN EL A LAR M ALA RM SU P ER VI SO R YTR O UB LE SI LEN C ED ON
TO S I LEN CE ALA RM S I G NA LS:
- P RES S " A LAR M S IL EN CE ".
A LA RM A LA RM S UP V TB L AL ARM S YS TE M
A
ACCK
K AC K AC K AC K S IL ENC E RE S ET TO R ES TO R E SY ST EM TO N O RM AL :
- P RES S " S YST EM R ESE T. "
ACKNO W E
L DGE - P RES S " A CK " T O S IL ENC E TO N E DE VI CE .

F IR E A L A R M
C O N T R O L

* * S Y S T E M SI N O R M A L * *
A LL
S PEAK ERS
HOR N
FE MA LE
VO IC E PH ONE 1 2 :0 2 :1 5 p m M o n 9 -F eb 9- 8
CI RCU IT F IR SE Y S S TY E S A MT L E A A M R C M
EVA C E VA C A L S A U R P MT E R R OS V UIL IS B E PO L N OR E C WY E E D R

W EA THER CH IM E BR ITI SH ME DIC AL


W AR NIN G E VAC EM ERGE NC Y
A L A S R U M P V A L SA YR SM T E M
A C K A C T KA R C O SK U IL B ER L N E E CS E E T

ALL SLO W
FR ENCH /
EN GLI SH I NDU STRI AL C A U T IO N
CL EAR F IRE
WH OOP E VAC

SPA NI SH/
6TH FL G SA CHE MI CAL
S PEAK ERS TON E ENG LISH EM ERGE NCY
EV AC

D IS C O N N E C T
ALL 120 B PM JA PA NES E HA ZARD OU S P O W E R B E F O R E
S PEAK ERS HOR N E VAC M ATERI AL S E R V IC IN G

M AN UAL SEC URI TY CHL ORI NE


AU DIO ST UTTER B YPA SS
O VER RID E LEAK

VOI CE
PHON E
HI -L O W ATC HTO UR COD E
PA GI NG 3- 1- 6- 4

LO CA L NI GH T
WAI L
SP EAKE R S ENS ITI VI TY

4100 FIRE ALARM CONTROL

NDU 4010
PULL TO OPEN DO O R
PULL TO OPENDOOR
EM ERG ENCY OPER ATING
INSTR UCT IONS
O P ERA TO R AL AR M OR T RO UB LE C ON D IT IO N:

SYSTE M IS NO RM AL - S YST EM I N DI C ATO R F LAS HI NG , TO N E ON .

. . .. .. 1 2 :3 5 :1 5 a m M ON 1 2 J UN 9 5
. .
TO A C KN OW LED GE :
IN TE RFA C E - P RE SS " A CK " L
O C AT ED U ND ER FLA SH I NG
FI R E PR I OR IT Y 2 SYS TEM S YSTE M S IG N ALS P OW ER I ND I CAT O R.
- R EPE AT O PE R ATI O N UN TI L AL L REP O RTS AR E
P AN EL A LAR M ALA RM S UP ER VI SO R YTR O UB LE SI LE NC ED ON
AC KN OW LED G ED.

TO S I LEN CE ALA RM SI G NA LS:


- P RE SS " A LAR M S IL EN CE ".
ALA RMM ALA RM S U PV TB L AL AR M S YS TE M
A
ACCK AC K AC K AC K S IL EN CE R ES ET TO R E STO R E SY ST EM TO N O RM A L:
- P RE SS " S YS TEM R ES ET. "
ACKN OW E
L DGE
- P RE SS " A CK " TO S IL EN CE TO N E DE VI C E.

Administration ALL
S PEA KER S
EV AC

W EA THER
W AR NIN G

ALL
CL EAR

6TH F L
S PEA KER S

A L
S PEA KER S

M AN UAL
HO RN

C HI ME

SLO W
W HOO P

GSA
TO NE

120 BPM
HO RN
FE M ALE
VO IC E
E VA C

BR ITI SH
E VAC

FR ENC H/
EN GLI SH
E VAC

SPA NI SH/
ENG LIS H
E VAC

JAPA NES E
E VAC

SEC URI TY
PH ONE
CI RCU IT

ME DIC AL
EM ERG ENC Y

I NDU STR IAL


F IRE

CHE MI CAL
EM ERGE NC Y

HA ZARD OU S
M ATERI AL

CHL ORI NE
Library
AU DIO ST UTTER B YPA SS
O VER RI DE LEA K

VOI CE
PHO NE HI -L O WAT CHTO UR COD E

& Finance
PA GI NG 3- 1- 6- 4

LO CA L N IG HT
WA IL
SP EAK ER SEN SI TIVI TY

4100 FIRE ALARM CONTROL

4020 4100
Dining Hall 4007ES Dormitory A
Gymnasium

13
4007ES Network Applications: Multi-tenant
Buildings (e.g. condominiums, assisted living, strip malls, etc)
SafeLINC Internet Interface email / Mobile
TSW Client Manager’s Office App
PC Mobile Device
(unsupervised / view only)

TSW Client Manager’s Home


(unsupervised / view only)

Customer
Customer
LAN / WAN
LAN / WAN Customer
Customer
LAN / WAN
LAN / WAN
4007ES
Bldg /Tenant A 4007ES
Bldg / Tenant G

NDU or TSW Server


at Central Office

4007ES 4007ES
Bldg / Tenant B Bldg / Tenant F

4007ES 4007ES
Bldg / Tenant C Bldg / Tenant E
4007ES
Bldg / Tenant D
14
Customer Value - 4007ES Network
NOTHING
NOTHING NEW
NEW TO
TO LEARN
LEARN

15
4007ES Enhancements Suppression
Release Overview
Current Portfolio - Simplex Suppression Panels
UL / NFPA Markets

4004-R 2 Hazard Conventional Panel (Simplex)

4007ES Multiple Hazard Addressable Panel (Simplex)

4010ES Multiple Hazard Addressable Panel (Simplex)

4100ES Multiple Hazard Addressable Panel (Simplex)

17
The ES Family of Suppression Panels

• Supports e-Services • Supports e-Services • Supports e-Services


4007 ES 100-250 Points

4100ES 2,500 Points


4010ES 250 Points (will increase to
1,000 points in late 2016)
• Addressable • Addressable • Addressable
notification with self notification with self notification with self
test capability test capability
test capability
• Network compatible • Network compatible
• Network compatible
• Multiple Hazard • Multiple Hazard
• Multiple Hazard suppression panel suppression panel
suppression panel (based on point
capacity)
• Integrated Voice for
Emergency
Communications
applications

ES Panels Lineup

18
Addressable Releasing Panels – Competitive Analysis

Simplex Simplex Simplex Kidde Aries Net Fike Cheetah Siemens FS-
Feature Autopulse 318
4007ES 4010ES 4100ES Link Panel xi50 250SRX

Multiple (based 2 with base panel


Multiple (based on Multiple (based on
# Hazards on point 10 expandable in groups ? ?
point capacity) point capacity)
capacity) of 3 up to 72 (74 total)
Qty. 1 50 point SLC,
3, 250 point total 2 SLCs with 255
1 SLC, 318 points expandable to 4
(also 32 4 (late 2016) 1,000 10, 2,500 points points each (510 total)
SLCs (159 inputs – 159 SLCs with 254 1 – 252 points
conventional points total total Expandable from 3-8
outputs) devices each (1,066
zones) (2,040 addresses)
points total)
Based on point 4 Class B 2 Class A
NACs 4-6 amps total 4-8 amps total 4 – 6 amps total 2 NACs, 2 RACs 2
capacity 6 amp
3 programmable and 1
1 with base panel 1 with base panel Built-in Alarm, 3 programmable
Up to 32 possible trouble form C relay ? (optional relays
Relays (4 relay option (4 8-relay option Trouble, and Form C 1 trouble
with I/O cards Expandable to 96 available)
card) cards) Supervisory relays relay
relays
Triple-R redundancy
(2 release commands
SRP – requires SRP – requires SRP – requires
False Discharge from the main CPU
field-mounted field-mounted box field-mounted box No NA NA
Protection combined with signal
box and 2 inputs and 2 inputs and 2 inputs
from the watchdog
timer

19
Addressable Releasing Panels – Competitive Analysis

Simplex Simplex Simplex Kidde Aries Net Fike Cheetah Siemens FS-
Feature Autopulse 318
4007ES 4010ES 4100ES Link Panel xi50 250SRX

4 X 40 display
2X40
4.3 in color touch 2X40 (InfoAlarm 2 X 40 character (English, French, 80 character LCD 80 character backlit
Display (optional 8 line
screen display late 2016) display Spanish and display LCD display
display available)
Portuguese)
Basic programming
through keypad,
NETLink
Auto programming, auto addressing.
Laptop only – Configuration Autoprogamming.
Laptop, USB Laptop only – front panel Hand held
suppression Software via PC Front keyboard
Programming port, .suppression suppression programming programmer for
wizards through USB link, (laptop not
wizards wizards through QWERTY setting addresses ,
front panel required)
keyboard USB port, Windows
programming
based C‑LINX
software
Visible Timers No No No ? ? ?. Yes. 1 in. X 3 in.
Modbus RTU
modules. Modbus
EIA-232 port for
TCP/IP and BACnet
Vesda, BACnet Vesda, BACnet printing, VIEW
Integration Computer port compatible Vesda Laserline ?
Computer port Computer port (Very Intelligent
HSSD, ASD and LHD
Early Warning)
RS-232 port for
graphics

20
Addressable Releasing Panels – Competitive Analysis

Simplex Simplex Simplex Kidde Aries Net Fike Cheetah Siemens FS-
Feature Autopulse 318
4007ES 4010ES 4100ES Link Panel xi50 250SRX

Ethernet IP
Fike Multi-
Up to 99 nodes Up to 99 nodes Up to 99 nodes
Up to 64 nodes interface-printer
Network (686 with TrueSite (686 with TrueSite (686 with TrueSite No ?
(130,560 addresses) port, connects pt
Workstation) Workstation) Workstation)
existing Cheetah
classic network
Internet
Communications Link,
ExacTech SafeLINC SafeLINC Vesda Laser Plus,
handheld
Others (TrueInsight ExacTech ExacTech Marine Listings Linear Heat ?
programming device
coming) TrueInsight TrueInsight Detection Cable
checks for duplicate
addressing

Historical Logs 2,000 1,000 1,000 800 10,000 events 3,2000 ?

21
4007ES Suppression Release
Applications
4007ES Suppression Release Peripherals and
Specifications
4007ES uses the same peripherals and specifications as 4010ES and 4100ES
suppression release systems:
• 4090 Series Suppression Release Peripheral (SRP)
‐ 4090-9005 SRP and Mounting Plate New 2080-9070
‐ 4090-9006 SRP with Enclosure (required for ULC)
• 2080 Series Maintenance Switches
‐ 2080-9059 with Lamp, Flush Mount
‐ 2080-9060 with Lamp, Surface Mount
‐ 2080-9069 without Lamp, Flush Mount - NEW
‐ 2080-9070 without Lamp, Surface Mount - NEW
• 2080 Series Abort Switches
‐ 2080-9056 Flush Mount
‐ 2080-9057 Surface Mount
• 2081-9046 Coil Supervision Module
• SRP Compatible UL/ULC/FM Approved Solenoids
Refer to S4007-0003 and S2080-0010 data sheets for additional details
23
4007ES Suppression Release Peripherals and
Specifications
FM Approved Solenoid Listings have changed “For All FM Approved Systems”
• FM has eliminated the tables for Compatible Automatic Water Control Valve Groups A
through K
• The new FM requirements consist of 4 Release Control Panel Groups that correspond to
4 categories of Compatible FM Approved Solenoid Valves
• Simplex 4100ES, 4010ES, 4007ES and 4004R Releasing Panels belong to FM Approved
Release Panel Group 3

Release Panel Group For use with FM Approved Solenoid Valves*

1 Rated 11W and below

2 Rated 16.8W and below

3 Rated 22W and below

4 Rated 22.6W and below

* Refer to the solenoid valve manufacturer's product documentation for verification


of agency listings and power requirements.
24
4007ES Hybrid Single Hazard Application
2080-9059/9060 or 2080-
9069/9070
IDNet 0-60 Second Delay on 1st Alarm
4090-9005/9006 2080-9046 Coil or 2nd Alarm (cross-zoned)
Supervision Module
RAC
Relay IAM
SRP
ACTUATOR
CSM or
Maint SOLENOID Auxiliary Controls
Switch

24VDC Aux Pwr for 0-30 Minute Soak Timer IDNet


2080-9059/9060 (0 = On Til Reset)

IDNet

1st Alarm = On until Reset IAM


(RELWVIS) Required if cross-zone or
release delay is used FIRE ALARM
ABORT
1 Alarm (x-zone) = 20bpm or Temporal
st
PULL DOW N

1st or 2nd Alarm (timer running) = 120bpm


Release = Steady, On until Silence
(RELSIG) 0-30 Second
2080-9056/9057
Delay
Release = On until Reset • Immediate
(RELVIS) Required if no cross-zone • 10 Sec Delay
and no release delay is used (> of 10 Sec or Timer)
NACs • IRI (pre-alarm only with
Notes: 10 sec delay)
1. All Audibles operate On until Silence, all Visibles operate On until Reset • Reset Original Delay
2. An Abort IAM cannot be associated with more than 1 hazard • NY City
4007ES Hybrid 3. Investigate Bell/Strobe (RELIVIS) also required for NYC Operation (adds 90 sec investigate
delay, then reloads
release delay)

25
4007ES Hybrid Application
with 4009 IDNet NAC Extender (required for 2 or more hazards)
2080-9059/9060 or 2080-
9069/9070
IDNet 4090-9005/9006
0-60 Second Delay on 1st Alarm
2080-9046 Coil or 2nd Alarm (cross-zoned)
RAC Supervision Module
Relay IAM
SRP
ACTUATOR
CSM or
Maint SOLENOID Auxiliary Controls
Switch
C A U T IO N
D IS C O N N E C T

P O W E R
B E F O R E
S E R V IC IN G

4009IDNet NACEXTENDER
T M

24VDC Aux Pwr for IDNet


0-30 Minute Soak Timer
2080-9059/9060 (0 = On Til Reset)
4009 NACs
IDNet IAM
1st Alarm = On until Reset
(RELWVIS) Required if cross-zone or
release delay is used
FIRE ALARM
ABORT
PULLDOW N

1st Alarm (x-zone) = 20bpm or Temporal


1st or 2nd Alarm (timer running) = 120bpm
Release = Steady, On until Silence 0-30 Second
(RELSIG) Delay •2080-9056/9057
Immediate
Release = On until Reset • 10 Sec Delay
(RELVIS) Required if no cross-zone (> of 10 Sec or Timer)
and no release delay is used • IRI (pre-alarm only with
10 sec delay)
• Reset Original Delay
Notes: • NY City
1. All Audibles operate On until Silence, all Visibles operate On until Reset (adds 90 sec investigate
2. An Abort IAM cannot be associated with more than 1 hazard delay, then reloads
4007ES Hybrid 3. Investigate Bell/Strobe (RELIVIS) also required for NYC Operation release delay)

26
4007ES Addressable Single Hazard Application
2080-9069/9070 without Lamp
only
IDNet 0-60 Second Delay on 1st Alarm
4090-9005/9006 2080-9046 Coil or 2nd Alarm (cross-zoned)
Supervision Module
Relay IAM
SRP
ACTUATOR
CSM or
Maint Auxiliary Controls
SOLENOID
Switch

RAC 0-30 Minute Soak Timer IDNet


(0 = On Til Reset)
Simple NAC
IDNet
1st Alarm = On until Reset IAM
(RELWVIS) Required if cross-zone or
release delay is used
FIRE ALARM
ABORT
IDNAC 1 Alarm (x-zone) = 20bpm or Temporal
st
PULLDOW N

1st or 2nd Alarm (timer running) = 120bpm


Release = Steady, On until Silence
(RELSIG) 0-30 Second
Delay 2080-9056/9057
Release = On until Reset • Immediate
(RELVIS) Required if no cross-zone • 10 Sec Delay
and no release delay is used (> of 10 Sec or Timer)
• IRI (pre-alarm only with
Notes: 10 sec delay)
1. All Audibles operate On until Silence, all Visibles operate On until Reset • Reset Original Delay
2. An Abort IAM cannot be associated with more than 1 hazard • NY City
4007ES Addressable 3. Investigate Bell/Strobe (RELIVIS) also required for NYC Operation (adds 90 sec investigate
delay, then reloads
release delay)

27
4007ES Addressable Application
with 4009 IDNet NAC Extender (required for 2 or more hazards)
2080-9059/9060 or 2080-
9069/9070
IDNet 4090-9005/9006
0-60 Second Delay on 1st Alarm
2080-9046 Coil or 2nd Alarm (cross-zoned)
RAC Supervision Module
Relay IAM
SRP
ACTUATOR
CSM or
Maint SOLENOID Auxiliary Controls
Switch
C A U T IO N
D IS C O N N E C T

P O W E R
B E F O R E
S E R V IC NI G

4009IDNet NACEXTENDER
T M

24VDC Aux Pwr for IDNet


0-30 Minute Soak Timer
2080-9059/9060 (0 = On Til Reset)
4009 NAC
IDNet IAM
1st Alarm = On until Reset
(RELWVIS) Required if cross-zone or
release delay is used
FIRE ALARM
ABORT
PULLDOWN

1st Alarm (x-zone) = 20bpm or Temporal


IDNAC 1st or 2nd Alarm (timer running) = 120bpm
Release = Steady, On until Silence 0-30 Second
(RELSIG) Delay 2080-9056/9057
• Immediate
Release = On until Reset • 10 Sec Delay
(RELVIS) Required if no cross-zone (> of 10 Sec or Timer)
and no release delay is used • IRI (pre-alarm only with
10 sec delay)
• Reset Original Delay
Notes: • NY City
1. All Audibles operate On until Silence, all Visibles operate On until Reset (adds 90 sec investigate
2. An Abort IAM cannot be associated with more than 1 hazard delay, then reloads
4007ES Addressable 3. Investigate Bell/Strobe (RELIVIS) also required for NYC Operation release delay)

28
Customer Value - 4007ES Suppression Release
NOTHING
NOTHING NEW
NEW TO
TO LEARN
LEARN

Designer End User Electrical Programmer Installation Break-Fix Tech /


Customer Value - 4007ES Suppression Release Contractor Technician Inspector
Provides a lower cost suppression release panel solution to the Simplex
family of addressable suppression panels X X X
Uses the same peripheral hardware as other Simplex addressable
releasing panels X X X X X
Audible cadence for escalation of events eliminates additional
equipment, installation, and maintenance cost for separate warning bells
and circuits X X
Uses the same ES panel programmer as 4100ES and 4010ES panels X
Suppression Release Point Types and Wizards simplify programming,
help prevent programming errors and unwanted release activation X X
Suppression Releasing Appliance Circuit Point Types are automatically
removed from Walktest to help prevent against unwanted activation of
releasing circuits X X X
SRP Dual Command Control eliminates costly false activations of
releasing circuits caused from potential electrical interference (noise) X

29
4007ES RS232 Applications
4007ES RS232 Applications
PC Annunciator Remote Client

Building Systems Integration PC Annunciator LAN / WAN


LAN / WAN
Computer Port Protocol Local Client and Server
RS232 RS232

LAN / WAN
LAN / WAN

PC Annunciator Remote Client

RS232

Maximum of (2) Printer


RS232 Ports

4007ES Hybrid
31
Customer Value - 4007ES RS-232

NOTHING
NOTHING NEW
NEW TO
TO LEARN
LEARN

Designer End User Electrical Programmer Installation Break-Fix Tech /


Customer Value - 4007ES RS232 Contractor Technician Inspector
Scalable options typically associated with higher end panels are now
available in the 4007ES for smaller buildings X X
Uses the same programmer as other Simplex ES panels X
Uses the same RS232 peripherals as other Simplex ES panels X X X X X

32
Retrofit Applications
4002 4005 4008 4010 4020
4007ES Network Retrofit: 4002, 4010, and Small 4020
Replacement
eMail / Mobile
TSW Client at Guard’s Shack TSW Client Manager’s Office App
(supervised / full control) (unsupervised / view only)

Agency Listed TSW Client Manager’s Home


FA Ethernet LAN (unsupervised / view only)

Customer
Customer
LAN / WAN
LAN / WAN
4100ES FA Ethernet Switch
Engineering 4100U
O PER AT O R
P ULL TO O PEN DO OR

SYST EM IS NO RM AL
PULL TO OPENDOOR
EM ERG ENC Y OPER ATING
INS TRUC TIONS
AL AR M OR TRO U BLE C ON D IT IO N :
- S YST EM I N DI C AT OR F LAS HI NG , TO NE ON .
Research Center
. . .. .. . .
IN TER FA CE 1 2:3 5 :1 5 a m M ON 1 2 J UN 9 5 TO A C KN OW LED GE :
- P RE SS " A CK " LO CATE D U ND ER F LA SH IN G
F IR E P R IO RI TY 2 SY ST EM S Y STE M SI GN AL S PO WER I ND I CAT O R.
- R EPE AT O PE R ATI ON UN TI L ALL R EP O RTS AR E
PA NE L ALA RM A LAR M SU PE RV IS OR Y TR OU BL E SI LE NC ED ON AC KN OW LED G ED .

TO S I LEN CE ALA RM SI G NA LS :
- P RE SS " A LAR M S ILE N CE ".
A
A LAR
LAR M
M AL AR M SU PV T BL A LAR M SY STE M
TO R E STO R E SY ST EM T O N O RM A L:
AC K A CK ACK ACK SI LEN C E R ES ET
- P RE SS " S YS TEM RE S ET. "
C
A K NOW L EDG E - P RE SS " A CK " TO SI LE N CE TO N E DE VI CE .

P ULL TO O PEN DO OR
PULL TO OPEN DOOR
EM ERG ENC Y OPER ATING
INS TRU CTIONS
O PE RAT O R AL AR M OR TRO U BLE C ON D IT IO N :
- S YST EM I N DI C AT OR F LAS HI NG , TO NE ON .
SYST EM IS NO RM AL

. . .. .. . .
TO AC KN OW LED GE :
IN TER FA CE 1 2:3 5 :1 5 a m M ON 1 2 J UN 9 5
- P RE SS " A CK " LO CATE D U ND ER F LA SH IN G
F IR E P R IO R ITY 2 SY ST EM S Y STE M SI GN AL S PO WER I ND I CAT O R.
- R EPE AT O PE R ATI O N UN TI L ALL R EP O RTS AR E
PA N EL ALA RM A LAR M SU PE RV IS OR Y TR OU BL E SI LE NC ED ON A CKN OW LED G ED .

TO SI LEN CE ALA RM SI G NA LS :
- P RE SS " A LAR M S IL EN CE ".
A LAR M AL AR M SU PV T BL A LAR M SY STE M
AL L FEM ALE AC
AC K
K ACK ACK ACK SI LEN C E R ES ET TO RE STO R E SY ST EM T O N O RM A L:
SP EAKE RS HO R N V OI CE P HON E - P RE SS " S YS TEM R ES ET. "
EV AC CI RCU IT A CK NOW L EDG E - P RE SS " A CK " TO S ILE N CE TO N E DE VI CE .
EVA C

W EAT HER B RI TISH M EDI CA L


W ARN IN G CH IM E E VA C E MER GEN CY

FR EN CH /
ALL S LOW ENG LISH IN DUS TRI AL
CLE AR FI RE
W HO OP E VA C

SP ANI SH /
6TH FL G SA CH EMI CA L
EN GLI SH
SP EAKE RS TO NE EM ERGE NC Y
EVAC

ALL 120 BPM JA PANE SE H AZA RDO US


EVA C M AT E
R IA L
SP EAKE RS H ORN

M AN UAL SE CUR ITY CH LOR IN E


AUD IO STU TTER BYP ASS LE AK
OV ER RID E

PHON E VO IC E
HI - LO W ATCHT OUR CO DE
PA GI NG 3- 1-6 -4

LO CAL N IG HT
W AI L
SP EAKE R SEN SI TIV ITY

AL L FEM ALE
V OI CE P HON E
SP EAKE RS HO R N CI RCU IT
EVA C EV AC

W EAT HER B RI TISH M EDI CA L


W ARN IN G CH IM E E VA C E MER GEN CY

R EN CH /
F
ALL IN DUS TRI AL
CLE AR S LOW ENG LISH
WHO OP E VA C FI RE

TSW Server
G SA SP ANI SH / CH EMI CA L
6TH FL
O NE
T EN GLI SH EM ERGE NC Y
SP EAKE RS EVAC

JA PANE SE H AZA RDO US


ALL 120 BPM EVA C
SP EAKE RS H ORN M AT E
R IA L

4100 FIRE ALARM CONTROL M AN UAL


AUD IO
OV ER RID E
STU TTER
SE CUR ITY
BYP ASS
CH LOR IN E
LE AK

VO IC E
PHON E W ATCHT OUR CO DE
PA GI NG HI - LO 3- 1-6 -4

LO CAL W AI L N IG HT
SP EAKE R SEN SI TIV ITY

4100 FIRE ALARM CONTROL

PU LL T O O PEN DOO R
Fire Alarm Command Center
PULL TOOPEN DOOR
EMER GE NCY O PERATI NG
IN STRU CTION S
O PER AT O R ALA RM OR TR O UB LE CO N DI TI ON :
- SY STE M I ND I CA TOR FLA SH IN G, T ON E O N .
S YSTEM IS N OR MAL
INT ER FA CE

PA NE L
. . .. ..
FI R E

A LA RM
1 2:3 5 :1 5 a m MO N 1 2 JU N 9 5
PR IO R IT Y2

A LAR M
SY ST EM S YS TE M

SU PE RV IS O RY TR OU BL E
. .
SI GN AL S

SI L ENC E D
P OWE R

ON
TO A CK NO WLE DG E:
- PR ES S " AC K" LO CA TE D UN DE R FL ASH I NG

-I R
NEDPEA
I C AT
TOOR
P .ER AT IO N U N TIL A LL R EP OR TS A RE
A C KNO WLE DG ED .

TO S ILE NC E A LAR M S I GN ALS :


- PR ES S " ALA R M SI LE NC E" .
A LAR
AL M
AR M A LAR M SU PV T BL A LA RM S YSTE M
AAC
CK AC K AC K A CK SI LE NC E R ES E T TO R ES TO RE SYS TEM T O NO R M AL :
- PR ES S " SY ST EM R ES ET ."
A CK NOW L EDG E - PR ES S " AC K" TO SI LE NC ET O NE D E VIC E.

FE MALE
AL L PHO NE
SP EAKE RS HO RN VOI CE CI RC UI T
EVA C E VAC

W EATH ER BRI TIS H M ED ICA L


W ARN ING CHI M E E VA C EME RGE NCY

FREN CH /
A LL IN DUS TRI AL
CLEA R S LOW ENG LIS H
W HO OP EVA C FI RE

SP AN ISH /
6TH FL GS A C HEM IC AL
EN GLI SH EM ER GEN CY
SP EAKE RS TO NE EVA C

JA PANE SE
ALL 12 0 BP M HAZA RDO US
EV AC M A TERI AL
SP EAKE RS H ORN

M ANU AL SE CU RITY
AUD IO STUT TER BYP ASS C HLO RIN E
OV ERR IDE LEAK

VO IC E
P HON E
HI - LO W ATCH TOUR CO DE
PAG IN G 3- 1- 6-4

LO CAL W AI L NI GHT
SPE AKER SE NSI TIV ITY

4100 FIRE ALARM CONTROL

NDU 4002
4007ES
PULL TO OPEN DO O R
PULL TO OPEN DOOR
EM ERG ENCY O PER ATING
INSTRU CT IO NS

O PE RA TO R ALA R M O R T RO UB LE C ON D IT IO N:
SYSTEM IS NO RM AL - S YST EM I N DI C ATO R FL AS HI NG , T O N E ON .

. . .. .. . .
IN TE RFA C E 1 2 :3 5 :1 5 a m M ON 1 2 J UN 9 5 TO A CK N OW LED GE :
- P RES S " A CK " LO C AT ED U ND ER F LA SH IN G
F I RE PR I OR IT Y 2 S YS TEM SY STE M S IG N ALS P OW ER IN D IC AT O R.
- R EPE AT O PE RA TI O N UN TI L ALL R EP OR TS AR E
P AN EL A LAR M ALA RM SU P ER VI SO R YTR O UB LE SI LEN C ED ON
AC KN OW LED GE D.

TO S I LEN CE ALA RM S I G NA LS:


- P RES S " A LAR M S IL EN CE ".
A LA RM A LA RM S UP V TB L AL ARM S YS TE M
A
ACCK AC K AC K AC K S IL ENC E RE S ET TO R ES TO R E SY ST EM TO N O RM AL :
- P RES S " S YST EM R ESE T. "
- P RES S " A CK " T O S IL ENC E TO N E DE VI CE .
ACKNO W E
L DGE

Administration A LL
S PEAK ERS
EVA C

W EA THER
W AR NIN G

ALL
CL EAR

6TH FL
S PEAK ERS

ALL
S PEAK ERS

M AN UAL
AU DIO
HOR N

CH IM E

SLO W
WH OOP

G SA
TON E

120 B PM
HOR N

ST UTTER
FE MA LE
VO IC E
E VA C

BR ITI SH
E VAC

FR ENCH /
EN GLI SH
E VAC

SPA NI SH/
ENG LISH
EV AC

JA PA NES E
E VAC

SEC URI TY
B YPA SS
PH ONE
CI RCU IT

ME DIC AL
EM ERGE NC Y

I NDU STRI AL
F IRE

CHE MI CAL
EM ERGE NCY

HA ZARD OU S
M ATERI AL

CHL ORI NE
Library
Library
LEAK
O VER RID E

VOI CE
PHON E W ATC HTO UR COD E

& Finance
PA GI NG HI -L O 3- 1- 6- 4

LO CA L NI GH T
WAI L
SP EAKE R S ENS ITI VI TY

4100 FIRE ALARM CONTROL

F IR E A L A R M
C O N T R O L

* * S Y S T E M SI N O R M A L * *
1 2 :0 2 :1 5 p m M o n 9 -F eb -9 8
F IR SE Y S S T Y E S A M T L E A A M R C M
A L S A U R P MT E R R OS V U IL IS B E PO L N OR E C WY EE D R

A L A S R U MTP RV O A U L B SA L YR E SM T E M
A C K A C KA C SK IL ER N E CS E E T
C A U T IO N

D IS C O N N E C T
P O W E R B E F O R E
S E R V IC IN G

4020 4100
4007ES
Dining Hall Dormitory A
Dining Hall 4010
4007ES
Gymnasium
Gymnasium

34
4007ES Suppression Retrofit: 4010 Replacement
2080-9059/9060 or 2080-
9069/9070
IDNet 0-60 Second Delay on 1st Alarm
4090-9005/9006 2080-9046 Coil or 2nd Alarm (cross-zoned)
Supervision Module
RAC
Relay IAM
SRP
ACTUATOR
CSM or
Maint SOLENOID Auxiliary Controls
Switch

24VDC Aux Pwr for 0-30 Minute Soak Timer IDNet


2080-9059/9060 (0 = On Til Reset)

IDNet

1st Alarm = On until Reset IAM


(RELWVIS) Required if cross-zone or
release delay is used FIRE ALARM
ABORT
1 Alarm (x-zone) = 20bpm or Temporal
st
PULLDOWN

1st or 2nd Alarm (timer running) = 120bpm


Release = Steady, On until Silence
(RELSIG) 0-30 Second
Delay 2080-9056/9057
Release = On until Reset • Immediate
(RELVIS) Required if no cross-zone • 10 Sec Delay
and no release delay is used (> of 10 Sec or Timer)
NACs
• IRI (pre-alarm only with
10 sec delay)
4010 Notes: • Reset Original Delay
1. All Audibles operate On until Silence, all Visibles operate On until Reset • NY City
4007ES Hybrid 2. An Abort IAM cannot be associated with more than 1 hazard
3. Investigate Bell/Strobe (RELIVIS) also required for NYC Operation
(adds 90 sec investigate
delay, then reloads
release delay)

35
4007ES RS232 Retrofit: 4010 and 4020 Replacement
PC Annunciator Remote Client

Building Systems Integration PC Annunciator LAN / WAN


Legacy LAN / WAN
Computer Port Protocol LocalCRT / Keyboard
Client and Server
RS232 RS232

LAN / WAN
LAN / WAN

PC Annunciator Remote Client

RS232

Maximum of (2) Printer


RS232 Ports – same as
4010
4020 4010 and 4020
4007ES Hybrid

36
4007ES Retrofit Compatibility


4602 series RCU/SCU
annunciators

4606 series Color Touchscreen LCD
Annunciator
4603 Annunciator

4007ES 3.04
Retrofit Compatibility Matrix

Be sure to verify all circuit, power supply, and battery charger requirements

37
4007ES Enhancements
Hardware Overview
Network Interface Card
Network Hardware: Installation

The Network Interface Card (NIC) is installed in Block L, using


a mounting bracket and standoffs.

E G
L
F H

39
Network Hardware: Installation with Zone Relay
Module(s)

Zone Relay Modules (4007-9801)

E G may be installed in blocks E, F, G,


or H.

The NIC mounting plate can be


reconfigured to accommodate
zone relay cards in Blocks G or H.
F H

40
Network Hardware: Installation

Mounting Plate and hardware kit consists of:


6 – 6-32 x ¼” Pan Head Torx screws
1 – Mounting Plate
4 – 6-32 x 1.25” male/female hex standoffs
4 - 6-32 x 5/8” male/female hex standoffs
4 - #6 lock washers

41
Network Hardware: Installation

Shorter, 5/8-inch long


standoffs are used where
there are no zone relay cards
in Blocks G or H.

NETWORK CARD MOUNTING


BRACKET INSTALLED IN 4007ES
PANEL

42
Network Hardware: Installation with Zone Relay
Module(s)

Two screws from each zone relay card are removed and replaced by 1¼-inch standoffs.

NIC mounting NIC mounting


bracket with one bracket with two
zone relay card zone relay cards

43
Network Hardware: Installation with SDACT
Module
New SDACT Mounting Bracket is Required with Fiber Media Module

If the system has a Network Interface Card with a Fiber Media Module AND an
SDACT, a new bracket is required to allow space for fiber patch cords.

The angled bracket


The new SDACT bracket (Part No. may be used for
650-1838, ordered separately) mounts copper media
the SDACT flat, closer to the back module mounted
of the box, allowing more space in over Block G or if
the box for media modules the system has no
mounted over Block H. Network Interface
Card.

SDACT with flat mounting SDACT with angled


bracket and NIC with Fiber mounting bracket
Media Module

44
Network Hardware: Installation with Copper
Media Module

Copper Media
Module oriented
over Block G

Copper Media
Module oriented
over Block H

Copper Media: The Network Card may be oriented so the copper wire media module is either over
Block G or H.
45
Network Hardware: Installation with Fiber Media
Modules

With fiber-optic media, the orientation


of the Network Card is restricted. Fiber-
optic media cards MUST BE mounted
over Block H due to patch cord bend
radius requirements.

46
Installation Job Aid: Doc. No. 579-1223

47
4007ES Enhancements
Hardware Overview
Dual RS232 Card
RS-232 Installation

RS-232, the Dual Class A Isolator (DCAI) and 25V Regulator Module are all
installed ONLY in Block E. Therefore, only ONE of them may be installed in a
4007ES panel.

Choose ONE:
RS-232
or E G
DCAI
or
25V Regulator F H

49
4007ES Enhancements
Programmer Overview
Adding the NIC and RS232 Card
Adding Network Card and RS-232 in Programmer

Programming Demonstration:
Add a Network Interface Card
and RS-232
to a 4007ES Panel

51
Resources
Resources: What else do you need to know?

New Sales PIDs

4007-9810: NIC Card


4007-9812: Dual RS-232
4007-9813: Wired Media Module
4007-9814: Fiber Optic Media Card
4007-9830: Suppression Release Appliqué
4007-9830CAF: Suppression Release Appliqué (French)
2080-9069: Maintenance Switch without Lamp, Flush
2080-9070: Maintenance Switch without Lamp, Surface

53
Resources: What else do you need to know?

New Service Parts

733-335: 4007ES NIC Harness


650-1838: SDACT Flat Mounting Bracket

54
Resources: What else do you need to know?

Sales Documentation
Description Document #
4007ES Hybrid Fire Alarm Control Panels – Data Sheet (also S4007-0001
S4007-0001_FR, French)
4007ES Fire Alarm Control Panels with IDNAC Notification – Data Sheet S4007-0002
(also S4007-0002_FR, French)
4007ES Release Control Panels – Data Sheet S4007-0003
(also S4007-0003_FR, French)
Panel Mounted SDACT S2080-0009
Suppression Release Abort and Maintenance Switches S2080-0010
Multiple Signal Fiber Optic Modems and Accessories S4100-0049
Network Overview with Applications Reference S4100-0055
Network Communications, Options and Specifications S4100-0056
4190-9013 System Printer S4190-0011
PC Annunciator S4190-0013
IDNet and MAPNET II Addressable Device Compatibility Chart S4090-0011

ES Panel Point Capacity Guidelines ES PointCapGuide

4007ES Retrofit Compatibility Matrix 4007ES Retrofit


4007ES Version 3.04 Enhancements FAQs 4007ES 3.04 FAQ

55
Resources: What else do you need to know?

Technical Documentation
Description Document #
4007ES Single Page Operating Instructions (also 579-1109
579-1109FR, French)
4007ES Operators Manual (also 579-1165FR, French) 579-1165
4007ES Installation Instructions 579-1102
4007ES Panel Programmer’s Manual 579-1167
4007ES Service Parts List 579-1110
Network Interface and Media Cards Installation Instructions 579-956
Fiber Optic Modem Installation Instructions 579-831
4007-9810 Network Interface Card Installation Job Aid 579-1223
Dual RS-232 Interface Module Installation Instructions 579-910
SDACT Installation Instructions 579-954
Suppression Release Peripheral Installation Instructions 579-385
Abort and Maintenance Switch Installation Instructions 579-416
4190-9013 Printer Installation Instructions 579-233
PC Annunciator Installation Instructions 579-492
PC Annunciator Operating Instructions 579-493
PC Annunciator Installation Instructions Protect Features (non 579-898
UL/ULC)
4009 IDNet NAC Extender Installation Instructions 574-181

56
Q&A

Questions?

Comments?

4007ES Ver 3.04


FAQs

57