Analysis of Eccentrically Loaded Columns

Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1of 9

ANALYSIS OF ECCENTRICALLY LOADED COLUMNS

BALANCED LOADING CONDITION


Columns normally fail by either tension or compression.
In between the two lies the so called balanced load
condition where failure may be of either type.
Balanced loading occurs when the tension steel just
reached its yield strain fy/Es and the concrete is
strained to 0.003. For every column there is always a
balanced loading situation where the ultimate load
Pbn placed at an eccentricity eb will produced a
moment Mbn. If the eccentricity of a column is less
than its balanced eccentricity eb(e<eb), the column
fails in compression (compression controls, fs1<fy),
otherwise tension controls (fs1>fy)
COLUMN INTERACTION DIAGRAM
It can be seen that the analysis of columns with statics
equations is very tedious and complicated. As a result,
designers resort to diagrams or computer in designing
columns.
Interaction diagram is a plot of the axial load Pn that the
column can carry versus its moment Mn capacity. This
diagram is very useful for studying the strengths of
columns with varying proportions of loads and
moments. Any combination of loading that falls inside
the curve is satisfactory, whereas any combination that
falls outside represents failure.
The diagram is made by plotting the axial load capacity
of the column at A, then the balanced B, then the
bending strength of the column if it is subjected to
pure moment only at C. In between the points A and
C, the column fails due to combination of axial and
bending. Point B is called the balanced point. In
reference to point D, the vertical and horizontal
dotted lined represents the particular load
combination of axial load and moment.
For any column, the balanced “c” is:

C= 600d/(600+fy)
EXERCISES:
1. The column in Figure 1 is reinforced with ten 32-mm bars
distributed around the perimeter. Load Pn will be applied with
eccentricity e about the strong axis. Material strengths are fc’ =
34 MPa and fy = 415 MPa. The neutral axis c = 360 mm from
extreme concrete in compression. Determine the nominal
column load and its eccentricity. Find also the ultimate column
strength ΦPn. Use 2010 NSCP.
2. The spiral column shown in Figure 2 is reinforced with eight 25-
mm diameter steel with fy = 414 MPa. Concrete cover
measured from bar centroid is 60 mm. Concrete strength fc’ =
27.6 MPa. Use the interaction diagram to determine the
following.
a) Determine the nominal load Pn when e = 100mm
b) Determine the nominal load Pn when e = 200 mm
c) The required number of 25 mm bars if Pn=2800kN and Mn =
250 kN.m.
FIGURE 1
FIGURE 2

You might also like