Lecture On ATRS & Speed-Load Control
Lecture On ATRS & Speed-Load Control
Lecture On ATRS & Speed-Load Control
on
ATRS
&
SPEED/LOAD CONTROL LOGIC
for
TG
Presented by:
Sandip Kumar
Dy. Mgr (I)
Introduction
• The 15 MW turbine-generator sets are to
generate power at 11 KV and feed power into the
132 KV bus for further distribution to the various
area sub-stations through existing 11 KV
distribution network.
• The plant is capable of operating either in
isolation or in parallel with the grid supply.
Further it is possible to operate either one or
both the turbine generator sets running in
parallel with the grid.
Description of Turbine
• The Turbine is fed with steam from the main
steam header. The main steam flows through the
start up valve (=main steam emergency stop
valve), the main steam control valves, the nozzle
groups and parallel to the turbine rotor through
the main steam casing.
• For economical use of its power potential, it
passes through several subsequent stages. In this
way the enthalpy difference of the steam is
worked off.
Description of Turbine Contd.
Step 3 L- OIL P
Step 4 MO 111 AUTO – Jack Oil Pump AC
MO 112 AUTO – Jack Oil Pump DC
MO 115 AUTO – Rotor turn device
UC 120 ON – Jack Oil Pump
Controller
Step 5 MO 115 ON
Step 6 TURN P
Turbine Start up Contd.
Step 8 No Action
Step 9 SV 108 AUTO – Drain valve for nozzle
box 1
SV 109 AUTO – Drain valve for nozzle
box 2
SV 110 AUTO – Drain valve of wheel
chamber
SV 111 AUTO – Drain valve HP2 bleed
SV 112 AUTO – Drain valve HP1 bleed
Turbine Start up Contd.
SV 110 OPEN
SV 111 OPEN
SV 112 OPEN
SV 113 OPEN
SV 114 OPEN
SV 117 OPEN
Step 11 Condensate & Drains P
Step 12 MO 114 ON
Turbine Start up Contd.
Step 26 LIVEST P
Step 27 UC 110 ON – Control Oil Pump
Controller
MO 109 AUTO – Control Oil Pump
No. 1
MO 110 AUTO – Control Oil Pump
No. 2
Step 28 C-OIL P
Turbine Start up Contd.
Step 29 No Action
Step 30 “Turbine reset message” appears on
OIU and operator acts accordingly
(on resetting, I/H gets energized through relay logic)
Turbine Start up Contd.
Turbine Start up Contd.
Step 48 No Action
(No action is defined for step 47 48. But during
this period synchro control synchronizes the
generator with grid and minimum forward load
of 2.5 MW is achieved by DCS.)
Step 49 SV 117 CLOSE
SV 111 CLOSE
SV 112 CLOSE
SV 113 CLOSE
SV 109 CLOSE
HOT, WARM & COLD Condition
• Hot Condition is achieved when-
TR-108 > 300 DegC
TR-111 > 135 DegC
TR-112 > 135 DegC
TR-100 > 450 DegC
ES-111 = 1 (i.e. TG is synchronized)
• This Hot condition is changed to Warm Condition after
1.5 hours of TG comes on turning after trip.
• And Warm condition changes to Cold Condition after
12.5 hours of TG comes on turning after trip.
How Forward Load is generated?
• As synchro control is put ON and generator
breaker is engaged, an integral control gets
active with error signal 4 and integral constant
15 to open governor valves. This integral
control becomes inactive after 15 sec or as
soon as 2.5 MW forward load is achieved.
• During this period, ‘LOAD CONTROL’ will
remain ‘OFF’ and governor control will be in
‘VALVE MODE’.
How Forward Load is generated?
Contd.