EET301 2016 Chapter 2
EET301 2016 Chapter 2
EET301 2016 Chapter 2
Basic Principle of
Power System
1
Introduction
2
Introduction
3
Introduction
4
Introduction
Voltage Level
120/240 V up to 1kV Low
up to 69kV Medium
up to 230 kV High
up to 765kV Extra High
Primary Distribution 11 33 kV
2
Base Impedance Vbase Vbase
Z base
I base Sbase
In case of impedance,
R X
Z pu R pu jX pu R pu X pu
Z base Z base
S old Vold
S pu V pu
S base 3 VbaseLL
3VbaseLL S base 3
I pu I Z pu Z old 2
S base 3
VbaseLL
Z1 () 1:N
V1 V2
V2 (p.u.)
V1 (p.u.)
35
Per-Unit Method
Example 1
Figure 1 (a) Circuit with elements in SI units.
Figure 1 (b) Circuit with elements in per-unit.
Figure 1
Example 1
Example 1 Solution
(a) Solution for Z, I, and S at Port ab in Figure 1 (a)
Z ab 8 j12 j 6 8 j 6 1036.9
Vab 1000
I 10 36.9 A
Z ab 1036.9
S VI (1000)(10 36.9)
100036.9 800 j 600VA
P 800W Q 600 var
Example 1 Solution
(b) Answer in per-unit on bases of Vbase=100 V and
Sbase=1000 V
2
Vbase (100) 2
Z base 10
Sbase 1000
Sbase 1000
I base 10 A
Vbase 100
1000
V pu 10 p.u.
100
Example 1 Solution
(b) Answer in per-unit on bases of VB=100 V and SB=1000 V
8 j12 j 6
Z pu 0.8 j 0.6 pu 1.036.9 pu
10
V pu 10
I pu 1 36.9 pu
Z pu 136.9
S pu V pu I pu (10)(1 36.9) 136.9 pu
0.8 j 0.6 pu
Example 1 Solution
(b) Converting result in (b) into SI unit
Example 2
A 200 MVA, 13.8 kV generator has a reactance of 0.85 p.u.
and is generating 1.15 p.u. voltage.
Determine:-
(a) the actual values of the line voltage, phase voltage
and reactance, and
(b) the corresponding quantities to a new base of
500 MVA, 13.5 kV.
Example 2 Solution
(a)
Line voltage p.u. voltage base line voltage
1.15 13.8kV
15.87kV
Phase voltage p.u. voltage base phase voltage
13.8kV
1.15
3
9.16kV
Reactance p.u. reactance
base line voltage
2
0.85
13.8kV
2
200 MVA
0.809 43
Per-Unit Method
Example 2 Solution
VbaseLL old
(b) Line voltage pu (new) V p.u .LL ( old )
VbaseLL new
13.8kV
1.15
13.5kV
1.176 p.u.
Vbase old
Phase voltage pu (new) V p.u.LL ( old )
Vbase new
13.8kV
1.15 3
13.5kV
3
1.176 p.u.
EET301/4 Power System
44
Engineering 2013/2014 Semester I
Per-Unit Method
Example 2 Solution
2
VbaseLL old Sbase new
Reactance pu (new) X p.u .( old )
V S
baseLL new base old
2
13.8kV 500MVA
0.85
13.5kV 200 MVA
2.22 p.u.
Example 3
Three zone of a single-phase circuit are identified in the Figure 3. The
zones are connected by transformer T1 and T2, which ratings are also
shown. Using base values of 30 kVA and 240 V in zone 1, determine the
per unit impedance, the per unit source voltage and draw the single line
diagram of the circuit in per unit. Then calculate the load current in per unit
and in amperes.
Zone 1 Zone 2 Zone 3
G
Xline = 2
T1 T2
Vs 2200 V Zload = 0.9 + j0.2
30 kVA 20 kVA
240/480 V 460/115 V
X = j0.10 p.u X = j0.10 p.u 46
Figure 3
Per-Unit Method
Solution
First the base values in each zone are determined. S base = 30 kVA is the
same for the entire network. Also, Vbase1 = 240 V as specified for zone 1.
When moving across a transformer, the voltage base is changed in
proportion to the transformer voltage rating. Thus, the base voltage of
each zone
480 115
Vbase1 240 V Vbase 2 240 480 V Vbase 3 480 120 V
240 460
47
Per-Unit Method
2
Vbase 120 V 2
Z base 3 3
0.48
Sbase 30 kVA
48
Per-Unit Method
49
Per-Unit Method
The line, which is located in zone 2, has the per unit reactance
X line j2
X line p.u . j 0.2604p.u.
Z base 2 7.68
50
Per-Unit Method
Iload
51
Per-Unit Method
52
Per-Unit Method
53
Per-Unit Method
Example 4
Figure 4 shows the schematic diagram of a three-phase radial
transmission system. The ratings and reactances of the various
components are shown. A load of 50 MW at 0.8 pf lagging is taken
from the 33 kV substation which is to be maintained at 30 kV. The
line and transformers may be represented by series reactances.
Calculate the magnitude of terminal voltage of the synchronous
machine. Choose a power of 100 MVA and base voltage of 11 kV on
the synchronous machine side.
1 2
G T1 T2 load
j100 50 MW
0.8 pf
lagging
11/132 kV 132/33 kV
50 MVA 50 MVA 30 kV
X = j0.10 p.u Figure 4 X = j0.12 p.u 54
Per-Unit Method
Solution
A base of 100 MVA will be used for circuits. The base voltage of
each zone are
132 33
Vbase1 = 11 kV Vbase 2 11 132 kV Vbase 3 132 33 kV
11 132
55
Per-Unit Method
Z base 2
2
Vbase 2
132 kV
2
174
Sbase 3 100 MVA
Z line , j100
Z line , pu j 0.575 p.u.
Z base 2 174
100
ZT 1 p.u . j 0 .1 j 0.2 p.u.
50
Per-unit reactance of the receiving end transformer
100
ZT 2 p.u . j 0.12 j 0.24 p.u.
50
XG
VS VR = 0.91
ES
Solution Example 4
The terminal voltage of the synchronous machine
VS I pu Z pu VR
0.687 0.8 j 0.6 j0.2 j0.575 j0.24 0.91 j 0
1.328 j 0.558 p.u.
VS 1.44p.u.
1.44 11 kV
15.84 kV