Autoreclosing: Protection Application Handbook

Download as ppt, pdf, or txt
Download as ppt, pdf, or txt
You are on page 1of 38

ABB Group - 1 Sep 28, 2015

Protection Application
Handbook

Autoreclosing

ABB Group - 2 Sep 28, 2015

Autoreclosing

Autoreclosing
Auto
Auto reclosing
reclosing Cycle
Cycle
OH-lines
High fault-rate
(80-90%)

Fast
simultaneous

ABB Group - 3 Sep 28, 2015

Fault clearing

Autoreclosing
AUTORECLOSING
AUTORECLOSINGCYCLE
CYCLE

OH-lines
Intermittent faults
(80-90%)

Successful
AR-rate :

ABB Group - 4 Sep 28, 2015

High (80-90%)

Autoreclosing
Auto reclosing principles

95% of faults are transient type

3 Ph autoreclosing synchrocheck is used

1 Ph autoreclosing needs identification of faulty phase

ABB Group - 5 Sep 28, 2015

Helps verify phase angles are not out of phase e.g: due to
heavy power swing

Phase identification is difficult for high resistance faults

Autoreclosing

ABB Group - 6 Sep 28, 2015

Auto reclosing principles

Autoreclosing
Autoreclosure in a Line
bay

ABB Group - 7 Sep 28, 2015

AR- Autorecloser
BFR- Breaker failure
relay
COM- Communication
COND-CB condition
DLC SC-Dead line check
and synchronism check
LP- Line protection
MAN- Manual CB control
PD- Pole discordance
relay

Autoreclosing
Auto reclosing principles

ABB Group - 8 Sep 28, 2015

Protections that start autoreclosing

Main 1 protection

Main 2 protection

Protections that block autoreclosing

CB fail detected by Breaker fail relay & Pole discrepancy relay

CB not ready

Delayed tripping ( Zone2 or3 of distance relay , Back up relay)

Manual CB operation

Communication fail

Direct transfer trip receive , BB protection , O/V protection, Reactor


protection

Autoreclosing

C on tact position

Circuit-breaker Contact Travel

t6

t2

Closed

Time

Open

ABB Group - 9 Sep 28, 2015

t1

t3

Closed

t4

t5

Autoreclosing
Dead time for Automatic Reclosing Equipment
A

B
F

Contact position

ABB Group - 10 Sep 28, 2015

1A

t2 A

6A

Closed

Open

1B

2B

Dead time
Open

Closed
6B

Interruption time

Time

Autoreclosing
Single-pole Reclosing
Single-Pole Reclosing

ABB Group - 11 Sep 28, 2015

A B C

A B C

Autoreclosing
Temporal Description of Automatic Reclosing
HSR = High-Speed Automatic Reclosing
DR = Delayed Automatic Reclosing
R = Automatic Reclosing
SR = Slow Automatic Reclosing
DR
HSR
R

SR

ABB Group - 12 Sep 28, 2015

TD
0.1

10

100

Autoreclosing
Classical Three-pole Reclosing
A

F
1A

t2A

Contact position
ABB Group - 13 Sep 28, 2015

Dead time
Closed
Open

A
6A

Interruption time

t
0

t2
1B

Closed
B

Open

B
6B

Time

Autoreclosing
Factors affecting extinction of Primary Arc

Fault current magnitude

Fault clearance time

Coupling from energized conductors

Closing or opening of resistors

Magnitude of reenergizing voltage

Point of wave for reenergizing

Magnetic forces on the fault current

Length of insulating string

ABB Group - 14 Sep 28, 2015

Weather conditions
Shape of grading ring

Autoreclosing
Minimum Dead Time (IEEE)
System Voltage
kV

ABB Group - 15 Sep 28, 2015

23
46
69
115
132
230
345
400
500

Minimum deionization time [ms]


Based on Field and
Based on Operating
Laboratory Tests
Experience
110
120
130
150
160
210
260
280
330

180
200
210
230
240
280
340
370
420

Autoreclosing
Minimum Dead Time for Three-pole Reclosing
Minimum Dead Time
Three-Pole Reclosing
ms
500
400

Based on Operating Experience

300
200
100

Based on Field and


Laboratory Tests

ABB Group - 16 Sep 28, 2015

100

200

300

400

500

System Voltage

600

kV

Autoreclosing
Double Fault on a Double-circuit Line
A B C

ABB Group - 17 Sep 28, 2015

L1

L2

A B C

Autoreclosing
Capacitive Coupling and Single-pole Tripping
A B C

A B C

Cp

Cp Cp

ABB Group - 18 Sep 28, 2015

Ce

Ce

Ce

Autoreclosing
Secondary arc

ABB Group - 19 Sep 28, 2015

Secondary arc is phasor sum of currents maintained by


capacitive and inductive coupling from the energised
phase conductors

Autoreclosing
Critical Line Lengths for Single-pole Reclosing
System Voltage
kV

ABB Group - 20 Sep 28, 2015

230
345
500
765

Critical Line Length [miles]


Successful Range
Doubtful Range
0-300
0-140
0-60
0-50

300-500
140-260
60-100
50-80

Autoreclosing

ABB Group - 21 Sep 28, 2015

Artificial extinction of secondary arc

Where high-speed automatic reclosing is to be implemented,


secondary arcs must be artificially extinguished since they would
otherwise last too long.

There are several methods to extinguish artificially the secondary


arc:

Fixed Four-Reactor Scheme

Switched Four-Reactor Scheme

High speed Earthing Switch Scheme

Autoreclosing
Fixed Four-reactor Scheme
ABC

ABC

R
Lp Lp Lp

ABB Group - 22 Sep 28, 2015

Ln

Autoreclosing
Secondary Arcing Time (Haubrich)
Secondary Arcing Time
s

T sa

Haubrich 1971

2.0
1.5
1.0

ABB Group - 23 Sep 28, 2015

0.5

I
50

100

150

ABB Group - 24 Sep 28, 2015

Autoreclosing

Autoreclosing

ABB Group - 25 Sep 28, 2015

Auto reclosing in one and a half breaker


system

Autoreclosing

ABB Group - 26 Sep 28, 2015

Auto reclosing in one and a half breaker


system

Autoreclosing

ABB Group - 27 Sep 28, 2015

Special problems

Memory Circuit

Priority circuit

Autoreclosure out of service

ABB Group - 28 Sep 28, 2015

Autoreclosing

Autoreclosing
Synchronism and Energizing check
UBus

ULine

UBus

FreqDiff < 50-300 mHz


o
PhaseDiff < 5-75
UDiff < 5-50% Ur
UHigh > 50-120% Ur

U Bus

1-ph

U Line

3-ph (or 1-ph)

ULow < 10-100% Ur

ABB Group - 29 Sep 28, 2015

SYNC-BLOCK

Fuse fail

ULine

Autoreclosing

ABB Group - 30 Sep 28, 2015

DLC and SC at Auto reclosing

ABB Group - 31 Sep 28, 2015

CBIP manual on
Protection of
Generators, generator
transformers and 220kV
and 400 kV networks

Auto Reclosing

Autoreclosing
1.0
1.0 GENERAL
GENERAL
The auto-reclosing of power lines has become a generally accepted
practice.
Reports from different parts of the world show that in
certain networks in region subject to a high lightening intensity only
about 5% of the faults are permanent.
Auto reclosing therefore provides significant advantages.
Outage times will be short compared to where station personnel
have to re-energize the lines after a fault.

ABB Group - 32 Sep 28, 2015

In interconnected networks auto-reclosing helps in maintaining


system stability

Autoreclosing
1.1
1.1 Recommendations
Recommendationsfor
forprovisions
provisionsofofauto-reclosing
auto-reclosing
Presently 1 phase high speed auto-reclosure (HSAR) at 400kV and
220kV level is widely practised including on lines emanating from
Generating Stations and the same is recommended for adoption.

ABB Group - 33 Sep 28, 2015

If 3-phase auto-reclosure is adopted in future the application of the


same on lines emanating from generating stations should be studied
and decision taken on case to case basis.

Autoreclosing
2.0
2.0 SETTING
SETTINGCRITERIA
CRITERIA
2.1
2.1 Dead
DeadTime
Time
Auto- reclosing requires a dead time which exceeds the de-ionising
time
Time required for the de-ionising of the fault path depends on:- arcing
time, fault duration, wind conditions, circuit voltage, capacitive
coupling to adjacent conductors, etc.

ABB Group - 34 Sep 28, 2015

Single phase dead time of 1.0 sec is recommended for both 400kV
and 220kV system.

Autoreclosing
2.2
2.2 Reclaim
ReclaimTime
Time
The time during which a new start of the auto-reclosing equipment is
blocked.
If reclosing shot has been carried out and the line is energized and a
new fault occurs before the reclaim time has elapsed, the auto-reclosing
equipment is blocked and a signal for definite tripping of the breaker is
obtained.

ABB Group - 35 Sep 28, 2015

After the reclaim time has elapsed, the auto-reclosing equipment


returns to the starting position and a new reclosing sequence can occur.
The reclaim time must not be set to such a low value that the intended
operating cycle of the breaker is exceeded, when two faults incidents
occur close together.

Autoreclosing
If the breaker is closed manually, the auto reclosing equipment is
blocked and cannot start again until the reclaim time has elapsed.

ABB Group - 36 Sep 28, 2015

For the breaker to be used for auto-reclosing, it is essential that it


has the operating mechanism and breaking capacity necessary for
it to be able to perform the auto-reclosing sequences required.

Autoreclosing
2.3
2.3 Circuit
CircuitBreaker
BreakerRequirement
Requirement
According to IEC Publication 56.2, a breaker must be capable of
withstanding the following operating cycle with full rated breaking
current:
O + 0.3 s + CO + 3 min + CO
The recommended operating cycle at 400kV and 220kV is as per the
IEC standard.

ABB Group - 37 Sep 28, 2015

Reclaim time of 25 sec is recommended.

ABB Group - 38 Sep 28, 2015

Autoreclosing

You might also like