Power Systems III

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

Code No: RR320205 Set No.

1
III B.Tech II Semester Supplimentary Examinations, Apr/May 2008
POWER SYSTEMS-III
(Electrical & Electronic Engineering)
Time: 3 hours Max Marks: 80
Answer any FIVE Questions
All Questions carry equal marks
⋆⋆⋆⋆⋆

1. (a) Explain briefly about traveling waves on Transmission lines.


(b) Derive the equations for voltage and current Traveling waves for a single circuit
two conductors. [8+8]

2. (a) How do earthing screen and ground wires provide protection against direct
lightning strokes?
(b) Explain why the surge diverters are located very close to the equipments to
be protected and mention the application of surge absorbers. [8+8]

3. A 50 Hz, 11 kV, three phase alternator with earthed neutral has a reactance of 5
ohm/phase and is connected to the bus-bar through a circuit breaker. The capac-
itance to earth between the alternator and the circuit breaker is 0.02 microfarad
per phase. Assume the resistance of the generator to be negligible. Calculate the
following.

(a) Maximum value of voltage across the contacts of the circuit breaker
(b) Frequency of oscillation
(c) The average rate of rise of restriking voltage up to first peak [6+4+6]

4. Explain direct testing of circuit breakers with a neat diagram. [8+8]

5. (a) Explain clearly the basic principle of Percentage Differential relay for
i. Internal fault
ii. Through fault. [4+4]
(b) Explain what you understand by pick− up and reset value of the actuating
quantity. Explain the term selectivity in protective relays. [2+2+4]

6. (a) Where are the relays having extremely inverse and very inverse characteristics
used? What types of characteristics are used for protecting rectifiers, and for
replacement of fuses? [4+4]
(b) Explain how the mho characteristic realized using a sampling comparator? [8]

7. (a) What is a direct connected generator?


(b) Mention protective schemes for a direct connected generator. Explain any one
of these schemes. [6+5+5]

8. (a) Discuss the choice between impedance, reactance and Mho type relays. [2+2+2+2]

1 of 2
Code No: RR320205 Set No. 1
(b) Transformer: 5 MVA, Y / ∆, X=6%
The transmission line sections AB and BC are to be protected by Mho distance
relays. The system is as shown in the figure8b. If the C.T. ratio is 300/5 and
C.T. ratio is 166000/110V and a 3-∅ short circuit fault of zero impedance
occurs at F, find the impedance seen by the relays and determine the setting
of the relays for high speed protection of line AB and backup protection for
line BC, when the relays are located at end A. [8]

Figure 8b

⋆⋆⋆⋆⋆

2 of 2
Code No: RR320205 Set No. 2
III B.Tech II Semester Supplimentary Examinations, Apr/May 2008
POWER SYSTEMS-III
(Electrical & Electronic Engineering)
Time: 3 hours Max Marks: 80
Answer any FIVE Questions
All Questions carry equal marks
⋆⋆⋆⋆⋆

1. A surge of 100KV travels along an overhead line towards its junction with a ca-
ble. Find the magnitude of surge transmitted over the cable provided the surge
impedance of the line and cable are 400 ohms and 50 ohms respectively. [16]
2. (a) Distinguish between neutral earthing and equipment earthing .
(b) Explain the necessity of reactance grounding. [4+4+8]
3. For a 32 kV System reactance and capacitance up to the location of the circuit
breaker is 3 ohms and 0.015 microfarad, respectively. Calculate the following
(a) The frequency of transients oscillation
(b) The maximum value of restriking voltage across the contacts of the circuit
breaker
(c) The maximum value of RRRV. [6+4+6]
4. Write short notes on the following. [4x4=16]
(a) Making capacity
(b) Short time current rating
(c) Rated voltage, current and frequency
(d) Rated operating duty
5. (a) What is meant by directional feature of a directional over current relay? De-
scribe the construction, principle of operation and application of a directional
over current relay. [2+2+2+2]
(b) What is the difference between a polarized mho and simple mho relay. What
are self-polarized and cross-polarized mho relays? [4+4]
6. (a) Write short notes on an amplitude /pulse width converter as applied in a phase
sensitive amplitude comparator. [8]
(b) Write short notes on:
i. static sine comparator
ii. integrating type amplitude comparator. [4+4]
7. (a) 3300 V, 3 phase turbo alternator has a maximum continuous rating of 2000 kW
at 0.8 p.f and reactance is 12.5%. It is equipped with Merz-Price circulating
current protection which is set to operate at fault currents not less than 200A.
Find what value of the neutral earthing resistance leaves 10% of windings
unprotected.

1 of 2
Code No: RR320205 Set No. 2
(b) Describe percentage differential protection for transformers. State the advan-
tages. [8+6+2]

8. (a) With a neat sketch, discuss the differential scheme for bus zone protection.
(b) Discuss the working principle of frame leakage protection. [8+8]

⋆⋆⋆⋆⋆

2 of 2
Code No: RR320205 Set No. 3
III B.Tech II Semester Supplimentary Examinations, Apr/May 2008
POWER SYSTEMS-III
(Electrical & Electronic Engineering)
Time: 3 hours Max Marks: 80
Answer any FIVE Questions
All Questions carry equal marks
⋆⋆⋆⋆⋆

1. Discuss why

(a) A traveling wave is usually represented as a step wave in the analysis.


(b) The inductor transformers are usually connected to the over head line through
short lengths of cable. [8+8]

2. Define the following terms:-

(a) Dry flash over voltage


(b) Wet flash over voltage
(c) Impulse flash over voltage
(d) Impulse spark over volt-time characteristics. [4+4+4+4]

3. In a 132 kV system, inductance and capacitance up to the location of the circuit


breakers are 0.4 H and 0.015 microfarad respectively. Determine

(a) The maximum value of restriking voltage across the contact of the circuit
breakers.
(b) Frequency of transient oscillations and the maximum value of RRRV. [8+8]

4. Explain direct testing of circuit breakers with a neat diagram. [8+8]

5. Determine the time of operation of the relays placed at location No. 1 and 2
assuming that fault current is 2000 amps, C.T.ratio 200/1, relay 1 set at 100% and
2 at 125% and that the relay No.1 has a time multiplier of 0.2. The time grading
margin between the relays is 0.5. sec for discrimination. Assume the relay to have
2.2 seconds I.D.M.T. Characteristic, shown in figure 5. [8+8]

Figure 5
6. (a) Explain the merits and demerits of static relays.
(b) Discuss how an amplitude comparator can be converted into a phase compara-
tor and vice versa. [8+8]

1 of 2
Code No: RR320205 Set No. 3
7. Show in detail, the protection arrangement of a 60 MW generator provided with

(a) Differential protection


(b) Back-up over − current protection through faults
(c) standby earth fault protection in neutral connection. [6+4+6]

8. (a) With a neat sketch, discuss the differential scheme for bus zone protection.
(b) Discuss the working principle of frame leakage protection. [8+8]

⋆⋆⋆⋆⋆

2 of 2
Code No: RR320205 Set No. 4
III B.Tech II Semester Supplimentary Examinations, Apr/May 2008
POWER SYSTEMS-III
(Electrical & Electronic Engineering)
Time: 3 hours Max Marks: 80
Answer any FIVE Questions
All Questions carry equal marks
⋆⋆⋆⋆⋆

1. (a) A rectangular surge of 1000 kv incident on a over head transmission line of


surge impedance of 300 Ω, meets a junction of two cables of surge impedance
150 Ω and 100 Ω. Calculate the outgoing voltages and currents on each cable
and also the over head line. Derive the formula used.
(b) Explain briefly about equivalent circuit for traveling wave studies. [4+4+8]

2. Describe the construction and working principle of a zinc oxide gapless arrester
with a neat sketch. [8+8]

3. A 50 Hz, 11 kV, three phase alternator with earthed neutral has a reactance of 5
ohm/phase and is connected to the bus-bar through a circuit breaker. The capac-
itance to earth between the alternator and the circuit breaker is 0.02 microfarad
per phase. Assume the resistance of the generator to be negligible. Calculate the
following.

(a) Maximum value of voltage across the contacts of the circuit breaker
(b) Frequency of oscillation
(c) The average rate of rise of restriking voltage up to first peak [6+4+6]

4. Explain resistance switching in detail with relevant diagrams and derive the ex-
pression of damped oscillation. [4+8+4]

5. (a) What is meant by directional feature of a directional over current relay? De-
scribe the construction, principle of operation and application of a directional
over current relay. [2+2+2+2]
(b) What is the difference between a polarized mho and simple mho relay. What
are self-polarized and cross-polarized mho relays? [4+4]

6. (a) Explain the merits and demerits of static relays.


(b) Discuss how an amplitude comparator can be converted into a phase compara-
tor and vice versa. [8+8]

7. (a) Discuss the protection employed against loss of excitation of alternator.


(b) Discuss any one of the stator protection schemes for generators above 1MW.
[8+8]

8. (a) Discuss the choice between impedance, reactance and Mho type relays. [2+2+2+2]

1 of 2
Code No: RR320205 Set No. 4
(b) Transformer: 5 MVA, Y / ∆, X=6%
The transmission line sections AB and BC are to be protected by Mho distance
relays. The system is as shown in the figure8b. If the C.T. ratio is 300/5 and
C.T. ratio is 166000/110V and a 3-∅ short circuit fault of zero impedance
occurs at F, find the impedance seen by the relays and determine the setting
of the relays for high speed protection of line AB and backup protection for
line BC, when the relays are located at end A. [8]

Figure 8b

⋆⋆⋆⋆⋆

2 of 2

You might also like