Manual Rosemount 248 Wireless Temperature Transmitter en 87846

Download as pdf or txt
Download as pdf or txt
You are on page 1of 54

Reference Manual

00809-0100-4248, Rev DE
April 2024

Rosemount™ 248 Wireless Temperature


Transmitter
Rosemount 248 Wireless Hardware Revision 1
HART Device Revision 1
Device Install Kit/DD Revision Device Revision 01, DD Revision 01 or greater
Device Type 2676

WARNING
Failure to follow these installation guidelines could result in death or serious injury.
Ensure only qualified personnel perform the installation.

Explosions could result in death or serious injury.


Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national,
and international standards, codes, and practices. Review the approvals section of the Quick Start Guide for any
restrictions associated with a safe installation.
Before connecting a Field Communicator in an explosive atmosphere, ensure the instruments are installed in
accordance with intrinsically safe or non-incendive field wiring practices.
Verify that the operating environment of the device is consistent with the appropriate hazardous locations
certifications.

Process leaks may cause harm or result in death.


Do not remove the thermowell while in operation.
Before applying pressure, install and tighten thermowells and sensors.

Electrical shock could cause death or serious injury.


Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.

This device complies with Part 15 of the Federal Communication Commission (FCC) Rules. Operation is subject
to the following conditions:
This device may not cause harmful interference.
This device must accept any interference received, including interference that may cause undesired operation.
This device must be installed to ensure a minimum antenna separation distance of 8-in. (20 cm) from all persons.
The power module may be replaced in a hazardous area. The power module has surface resistivity greater than one
gigaohm and must be properly installed in the wireless device enclosure. Care must be taken during transportation to
and from the point of installation to prevent electrostatic charge build-up.

Changes or modifications not expressly approved by Rosemount can void the user's authority to operate the
equipment.
This device contains licence-exempt transmitter(s)/receiver(s) that comply with Innovation, Science and Economic
Development Canada’s licence-exempt RSS(s).
Operation is subject to the following two conditions:

1. This device may not cause interference.

2. This device must accept any interference, including interference that may cause undesired operation of the
device.

Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’
equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict
physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the
facility.

2
CAUTION

The products described in this document are NOT designed for nuclear-qualified applications. Using non-nuclear
qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings.
For information on Emerson nuclear-qualified products, contact your local Emerson Sales Representative.

NOTICE

Read this manual before working with the product. For personal and system safety, and for optimum product
performance, ensure the contents are thoroughly understood before installing, using, or maintaining this product.
For more information, contact Emerson.com/global.

NOTICE
Before installing the wireless transmitters
The Rosemount 248 Wireless Temperature Transmitter and all other wireless devices must be installed only after the
Wireless Gateway has been installed and is functioning properly. Emerson recommends that wireless devices also be
powered up in order of proximity from the Wireless Gateway, beginning with the closest. This will result in a simpler
and faster network installation.

Shipping considerations for wireless products (lithium batteries: Green Power Module, model number
701PGNKF):
The unit was shipped without the power module installed. Prior to re-shipment, ensure that the power module has
been removed.
Each Green Power Module contains one “D” size primary lithium-thionyl chloride battery. Primary lithium batteries are
regulated in transportation by the U. S. Department of Transportation, and are also covered by IATA (International Air
Transport Association), ICAO (International Civil Aviation Organization), and ARD (European Ground Transportation of
Dangerous Goods). It is the responsibility of the shipper to ensure compliance with these or any other local
requirements. Consult current regulations and requirements before shipping.

Power Module Considerations (Green Power Module, model number 701PGNKF):


The Green Power Module with the wireless unit contains one “D” size primary lithium-thionyl chloride battery (model
number 701PGNKF). Each battery contains approximately 5.0 grams of lithium. Under normal conditions, the battery
materials are self-contained and are not reactive as long as the batteries and the pack integrity are maintained.
Ensure care is taken to prevent thermal, electrical, or mechanical damage. Contacts must be protected to prevent
premature discharge.
Battery hazards remain when cells are discharged.
Power modules must be stored in a clean and dry area. For maximum battery life, storage temperature must not
exceed 86 °F (30 °C).

3
4
Reference Manual Contents
00809-0100-4248 April 2024

Contents
Chapter 1 Introduction...............................................................................................................................7
1.1 Product recycling/disposal......................................................................................................... 7
Chapter 2 Configuration............................................................................................................................ 9
2.1 Overview....................................................................................................................................... 9
2.2 Sensor connections..................................................................................................................... 9
2.3 Bench top configuration...........................................................................................................13
2.4 Device network configuration................................................................................................. 15
2.5 Remove power module............................................................................................................ 24
Chapter 3 Installation...............................................................................................................................25
3.1 Wireless considerations............................................................................................................25
3.2 Field Communicator connections............................................................................................25
3.3 Mounting.................................................................................................................................... 27
3.4 Physical installation...................................................................................................................28
Chapter 4 Commissioning........................................................................................................................ 33
4.1 Verify operations....................................................................................................................... 33
4.2 Reference information..............................................................................................................35
Chapter 5 Operation and maintenance................................................................................................. 39
5.1 LCD display screen messages..................................................................................................39
5.2 Power module replacement.....................................................................................................41
Chapter 6 Troubleshooting...................................................................................................................... 43
6.1 Overview.....................................................................................................................................43
6.2 Device status information........................................................................................................ 43
6.3 Transmitter troubleshooting................................................................................................... 46
6.4 LCD display troubleshooting....................................................................................................47
6.5 Wireless network troubleshooting..........................................................................................47
Appendix A Reference data........................................................................................................................ 49
A.1 Product Certifications .............................................................................................................. 49
A.2 Ordering information, specifications, and drawings............................................................49
Appendix B Alert message mapping......................................................................................................... 51

Rosemount 248 5
Contents Reference Manual
April 2024 00809-0100-4248

6 Emerson.com/Rosemount
Reference Manual Introduction
00809-0100-4248 April 2024

1 Introduction
1.1 Product recycling/disposal
Recycling of equipment and packaging must be taken into consideration and disposed of in
accordance with local and national legislation/regulations.

Rosemount 248 7
Introduction Reference Manual
April 2024 00809-0100-4248

8 Emerson.com/Rosemount
Reference Manual Configuration
00809-0100-4248 April 2024

2 Configuration
2.1 Overview
This section contains information on configuration and verification that must be performed
prior to installation.
Field Communicator and AMS Device Manager instructions are given to perform
configuration functions. For convenience, Field Communicator Fast Key sequences are
labeled “Fast Keys” for each software function below the appropriate headings.

Sensor input trim example


Fast Key sequence: 1, 2, 3, etc.

2.2 Sensor connections


The Rosemount 248 Wireless Transmitter is compatible with a number of RTD and
thermocouple sensor types. Figure 2-1 shows the correct input connections to the sensor
terminals on the transmitter. To ensure a proper sensor connection, anchor the sensor
lead wires into the appropriate compression terminals and tighten the screws.

Thermocouple or millivolts inputs


The thermocouple can be connected directly to the transmitter. If mounting the
transmitter remotely from the sensor, use appropriate thermocouple extension wire.

RTD or ohm inputs


The transmitters will accept a variety of RTD or ohmic configurations, including 2-, 3- or
4-wire connections.
If the transmitter is mounted remotely from a 3- or 4-wire RTD, it will operate within
specifications, without recalibration, for lead wire resistances of up to 5 ohms per lead
(equivalent to 500 feet of 20 AWG wire). In this case, the leads between the RTD and
transmitter should be shielded.
If using a 2-wire connection, both RTD leads are in series with the sensor element, so
significant errors can occur if the lead lengths exceed 3 feet of 20 AWG wire (approximately
32 °F [0.05 °C]). For longer runs, attach a third or fourth lead to achieve a 3- or 4-wire
connection as described in previous paragraph.

Effect-RTD input
Since the lead wires are part of the RTD circuit, the lead wire resistance needs to
be compensated for to achieve the best accuracy. This becomes especially critical in
applications where long sensor and/or lead wires are used.
There are three lead wire configurations commonly available:
• 2-wire: In a 2-wire configuration, there can be no compensation for lead wire
resistance. This is because the lead wires are in series with the element and appear
to the transmitter as part of the sensor's resistance causing inherent accuracy
degradation.
• 3-wire: In a 3-wire configuration, compensation is accomplished using the third wire
with the assumption that it will be the same resistance as the other two wires and the
same compensation is applied to all three wires.

Rosemount 248 9
Configuration Reference Manual
April 2024 00809-0100-4248

• 4-wire: A 4-wire design is ideal because the lead wire resistance is inconsequential
to the measurement. It uses a measurement technique where a very small constant
current of about 150 microamps is applied to the sensor through two leads and the
voltage developed across the sensor is measured over the other two wires with a
high-impedance and high resolution measuring circuit.
In accordance with Ohm's Law, the high impedance virtually eliminates any current flow
in the voltage measurement leads. Therefore, the resistance of the leads is not a factor.
Table 2-1: Examples of Approximate Basic Error

Sensor input Approximate basic error

4-wire RTD Negligible(1)

3-wire RTD Error in reading is equivalent to unbalanced lead wire resistance(2)

2-wire RTD Error in reading is equivalent to total lead wire resistance

(1) Independent of lead wire resistance up to 5 Ω per lead.


(2) Unbalanced lead wire resistance is the maximum resistance differences between any
two leads.

Figure 2-1: Sensor Wiring

A. Thermocouple and mV
B. 4-wire RTD and Ω
C. 3-wire RTD and Ω
D. 2-wire RTD and Ω

10 Emerson.com/Rosemount
Reference Manual Configuration
00809-0100-4248 April 2024

Figure 2-2: Sensor Connections

A. 2-wire RTD and Ω


B. 3-wire RTD and Ω
C. 4-wire RTD and Ω
D. T/C and mV

Note
Emerson provides 4-wire sensors for all single element RTDs. Use these RTDs in 3- or 2-wire
configurations by leaving the unneeded leads disconnected and insulated with electrical
tape.

Figure 2-3: RTD Lead Wire Configurations per IEC 60751

A. Single element, 3-wire


B. Single element, 4-wire
C. Dual element, 3-wire
D. Red
E. Black
F. White
G. Yellow

Note
To configure a single element, 4-wire RTD as a 3-wire system, connect only one white lead.
Insulate or terminate the unused white lead in a manner that prevents shorting to the
ground. To configure a single element, 4-wire RTD as a 2-wire system, connect matching
colored wires first and then connect the paired wires to the terminal.

Rosemount 248 11
Configuration Reference Manual
April 2024 00809-0100-4248

Figure 2-4: Thermocouple Lead Wire Configurations

A. Single thermocouple, 2-wire


B. Dual thermocouple, 4-wire

IEC 60584 thermocouple colors ASTM E- 230 thermocouple colors


Type
POS (+) NEG (-) POS (+) NEG (-)

J Black White White Red

K Green White Yellow Red

T Brown White Blue Red

Note
Dual thermocouple sensors are shipped with one pair of the wires shrink-wrapped
together.

2.2.1 Sensor leads


WARNING
If the sensor is installed in a high-voltage environment and a fault condition or installation
error occurs, the sensor leads and transmitter terminals could carry lethal voltages. Use
extreme caution when making contact with the leads and terminals.

To wire the sensor and supply power to the transmitter:

Procedure
1. Remove the power module cover (if applicable).
2. Remove the transmitter enclosure cover (if applicable).
3. Remove the LCD display (if applicable).
4. Loosen the captive screws and remove LCD adapter plate (if applicable).
5. Attach the sensor leads according to Figure 2-1.
6. Reattach and secure LCD adapter plate to 5 in-lbs of torque (if applicable).

12 Emerson.com/Rosemount
Reference Manual Configuration
00809-0100-4248 April 2024

7. Reattach the LCD display (if applicable).


8. Connect the Green Power Module.
9. Verify the connection by observing the LCD display (if applicable).
10. Reattach and tighten the covers (if applicable).
Note
Always ensure a proper seal by installing the covers so that polymer contacts
polymer (i.e. no O-ring visible). Emerson recommends using Rosemount O-rings.

2.3 Bench top configuration


Bench top configuration consists of testing the transmitter and verifying transmitter
configuration data. The transmitter must be configured before installation, which may be
performed either directly or remotely.
Direct configuration can be performed using a Field Communicator, AMS Device Manager,
AMS Wireless Configurator, or any WirelessHART® Communicator.
Remote configuration can be performed using AMS Device Manager, AMS Wireless
Configurator, or the Wireless Gateway.
When using a Field Communicator, any configuration changes made must be sent to the
transmitter by using the Send (F2) key. AMS configuration changes are implemented after
the Apply button has been selected.
The power module must be installed to provide power to the Rosemount 248 Wireless for
configuration.
To communicate with the transmitter:
1. Remove the power module cover. This will expose the HART® communication
terminals located on the Green Power Module.
2. Connect the Field Communicator leads to the COMM port connections on the Green
Power Module.

Figure 2-5: Field Communicator Connections

Field Communicator
If performing device configuration directly, connect the bench equipment and turn on the
Field Communicator by pressing the ON/OFF key. When using a Field Communicator, any
configuration changes must be sent to the transmitter by using the Send (F2) key.
The Field Communicator will search for a HART®-compatible device and indicate when the
connection is made.
• If the Field Communicator fails to connect, it will indicate that no device was found.

Rosemount 248 13
Configuration Reference Manual
April 2024 00809-0100-4248

• If this occurs, then refer to Troubleshooting.

AMS Device Manager and AMS Wireless Configurator


When configuring the Rosemount 248 Wireless using AMS Device Manager or AMS
Wireless Configurator, double-click the Rosemount 248 Wireless device icon (or right-click
and select Con/Setup), then select the Configure Menu. AMS configuration changes are
implemented after the Apply button has been selected.
During direct connection configuration, AMS Device Manager will search for a HART-
compatible device and indicate when the connection is made.
• If AMS Device Manager fails to connect, it indicates that no device was found.
• If this occurs, refer to Troubleshooting.

Emerson Wireless Gateway


The Rosemount 248 Wireless Transmitter supports limited remote configuration through
the Wireless Gateway.
The Gateway allows configuration of the following device parameters:
• HART® Tag
• Short Tag
• Descriptor
• Engineering Units
• Update Rate
• Range Values

Device sensor configuration


Every temperature sensor has unique characteristics. To ensure the most accurate
measurement, the transmitter must be configured to match the specific sensor that it will
be connected to. Prior to installation, verify the configuration and connection settings of
the temperature sensor through a Field Communicator or AMS.

Default settings
The Rosemount 248 Wireless default configuration is shown below:

Sensor Type Pt 100 (α = 0.00385)

Engineering Units °C

Number of Lead Wires 4

Network ID Factory generated network parameters

Join Key Factory generated network parameters

Update Rate 1 minute

Note
The C1 option code can be used to enable factory configuration of the Update Rate, Date,
Descriptor, and Message fields. This code is not required to have the factory configure the
Sensor Type, Connection, or the Self Organizing Network parameters.

14 Emerson.com/Rosemount
Reference Manual Configuration
00809-0100-4248 April 2024

2.4 Device network configuration

2.4.1 Join to network


Fast Keys: 2, 1, 2
To communicate with the Wireless Gateway, and ultimately the Host System, the
transmitter must be configured to communicate over the wireless network. This step is
the wireless equivalent of connecting wires from a transmitter to the host system.

Procedure
1. From the Home screen, select 2: Configure.
2. Select 1: Guided Setup.
3. Select 2: Join to Network.
4. Using a Field Communicator or AMS Device Manager to communicate with the
transmitter, enter the Network ID and Join Key so they match the Network ID and
Join Key of the Wireless Gateway and the other devices in the network.
Note
If the Network ID and Join Key are not identical to those set in the Gateway, the
transmitter will not communicate with the network. The Network ID and Join Key
may be obtained from the Wireless Gateway on the Setup → Network → Settings
page on the web server.

2.4.2 Configure update rate


Fast Keys: 2, 1, 3
The Update Rate is the frequency at which a new measurement is taken and transmitted
over the wireless network. This, by default, is 1 minute. This may be changed at
commissioning, or at any time via AMS Device Manager. The update rate is user-selectable
from 1 second to 60 minutes.

Procedure
1. From the Home screen, select 2: Configure.
2. Select 1: Guided Setup.
3. Select 3: Configure Update Rate.
4. When the device configuration is completed, remove the power module and replace
the module cover.

CAUTION
Only insert the power module when the device is ready to be commissioned. Use
caution when handling the power module.

Rosemount 248 15
Configuration Reference Manual
April 2024 00809-0100-4248

Figure 2-6: Field Communicator Connections

2.4.3 HART® menu tree


Figure 2-7: Overview
Device Status
1. Refresh Alerts
2. No Active Status
3. F: Electrical Failure Identification
4. F: Terminal Block Failure 1. Tag
5. F: Sensor Failure 2. Long tag
6. F: Radio Failure 3. Model
7. F: Supply Voltage Failure 4. Final Assembly Number
8. M: Electronics Warming 5. Date
9. M: Sensor has Exceeded Limits 6. Description
10. M: Electronics Temperature 7. Message
has Exceeded Limits 8. Device ID
11. M: Terminal Temperature 9. Model Numbers Model Numbers
has Exceeded Limits 10. Device Image 1. Model Numbers I
12. M: Supply Voltage Low 2. Model Numbers II
13. A: Database Memory Warning 3. Model Numbers III
14. A: Invalid Configuration
15. A: Hi Hi Alarm Revisions
16. A: Hi Alarm 1. Universal
17. A: Lo Alarm 2. Field Device
18. A: Lo Lo Alarm 3. Software
Home 19. A. Simulation Active 4. Hardware
1. Overview Overview 5. DD Revisions
2. Cofigure 1. Device Status
3.Service Tools 2. Comm Status
If no Active Alerts present, display text
3. Sensor Value
will be “No Active Alerts:
4. Sensor Status
Radio
5. Update rate
1. MAC Address
6. Join to Network
2. Manufacturer
7. Device Information Device Information 3. Device Type
1. Identification 4. Device Revision
2. Revisions 5. Software Revision
3. Radio 6. Hardware Revision
4. Security 7. Transmit PWR Lvl
8. Min Brdcst Updt Rt

Security
1. Write Protect
2. Lock Status
3. Over the Air Upgrade

16 Emerson.com/Rosemount
Reference Manual Configuration
00809-0100-4248 April 2024

Figure 2-8: Configure


Wireless
1. Network ID
2. Join to Network
3. Broadcast Info

Sensor
1. Sensor Value
Guided Setup 2. Sensor Status
1. Configure Sensor 3. % of Range
2. Join to Network 4. % of Range Status
3. Configure Update Rate 5. Sensor Setup
(3. Configure Adv Brdcsg) 6. Configuration Configuration
4. Calibrate Sensor 1. Upper Sensor Limit
5. Configure Device Display 2. Lower Sensor Limit
6. Configure Process Alarm 3. Upper Range Value
4. Lower Range Value
Display 5. Primary Variable
1. Display Mode
Home 2. Display Items Display Items
1. Overview 1. Sensor
2. Cofigure Configure 2. Percent of Range
3.Service Tools 1. Guided Setup 3. Terminal Temperature
2. Manual Setup Manual Setup HART 4. Electronics Temperature
3. Alert Setup 1. Wireless 1. Meas Status Log 5. Supply Voltage
2. Sensor 2. Configure Data Hist
3. Display
4. HART
5. Device Temp Device Temperature
6. Device Information 1. Electronics Temp
7. Power 2. Elect Temp Status
8. Security 3. Units
4. Maximum
5. Minimum

Alert Setup
1. Hi-Hi Alarm Device Information
2. Hi Alarm 1. Tag
3. Lo Alarm 2. Long Tag
4. Lo-Lo Alarm 3. Descriptor
4. Message
5. Date
6. Country
7. SI Unit Control

Power
1. Power Mode
2. Power Source
3. AC Power Filter

Security
1. Write Protect
2. Lock Status
3. Lock/Unlock
4. Over the Air Upgrade

Rosemount 248 17
Configuration Reference Manual
April 2024 00809-0100-4248

Figure 2-9: Service Tools


Device Status
1. Refresh Alerts
2. No Active Status
3. F: Electrical Failure
4. F: Terminal Block Failure
5. F: Sensor Failure
6. F: Radio Failure
7. F: Supply Voltage Failure
8. M: Electronics Warming
9. M: Sensor has Exceeded Limits
10. M: Electronics Temperature
has Exceeded Limits
11. M: Terminal Temperature
has Exceeded Limits
12. M: Supply Voltage Low History
13. A: Database Memory Warning 1. Clear Alert History
14. A: Invalid Configuration 2. View Alert History
15. A: Hi Hi Alarm
16. A: Hi Alarm
17. A: Lo Alarm
18. A: Lo Lo Alarm Mapped Variables
19. A. Simulation Active 1. Primary Variable
Home
20. History 2. Secondary Variable
1. Overview
3. Third Variable
2. Cofigure
Service Tools 4. Fourth Vairiable
3.Service Tools
1. Alerts
2. Variables Variables
3. Trends 1. Mapped Variables
4. Communication 2. All Variables All Variables
5. Maintenance 1. Sensor Variable
6. Simulate 2. Sensor Status
Trends 3. % pf Range
1. Data History 4. % of Range Status
5. Electronics Temp
Communications 6. View Data History
1. Comm Status 7. Refresh
2. Join Mode
3. Available Neighbors Routine Maintenance
4. Advertisement 1. Measurement History
5. Join Attempts 2. Locate Device
3. Install New Power Module
Maintenance
1. Routine Maintenance
2. Calibration Calibration
3. Reset/Restore 1. Sensor Value
2. Sensor Status
3. Current Lower Trim
Simulate 4. Current Upper Trim
1. Sensor 5. Lower Sensor Trim
2. Electronics Temp 6. Upper Sensor Trim
3. Supply Voltage 7. Recall Factory Trim

Reset/Restore
1. Perform Master Reset
2. Restore Default Settings

18 Emerson.com/Rosemount
Reference Manual Configuration
00809-0100-4248 April 2024

2.4.4 Fast Key sequence


This section lists the Fast Key sequences for common transmitter functions.
Note
The Fast Key sequences assume that Device Revision 01, DD Revision 01 or greater is being
used.

Table 2-2: Fast Key Sequence

Function Key sequence Menu items

Device Information 1, 7 Identification, Revisions, Radio, Security

Lower Range Value 2, 2, 2, 6, 3, 2 Set the temperature for the 0% point to configure
the Percent of Range.

PV Range Values 2, 2, 3 Primary Variable Lower Range Value (PV LRV),


Primary Variable Upper Range Value (PV URV), LSL,
USL

Sensor Configuration 2, 1, 1 Configure Sensor Type and Units, View Current


Sensor Configuration

Sensor Trim (Calibration) 2, 1, 4 Lower Sensor Trim and Upper Sensor Trim

Upper Range Value 2, 2, 2, 6, 3, 1 Set the temperature for the 100% point to
configure the Percent of Range.

Wireless Network 2, 1, 2 N/A

2.4.5 Calibration
Calibrating the transmitter increases the measurement precision by allowing corrections to
be made to the factory-stored characterization curve. It does this by digitally altering the
transmitter’s interpretation of the sensor input.
To understand calibration, it is necessary to understand that smart transmitters operate
differently from analog transmitters. An important difference is that smart transmitters are
factory-characterized, meaning that they are shipped with a standard sensor curve stored
in the transmitter firmware. In operation, the transmitter uses this information to produce
a process variable output, in engineering units, dependent on the sensor input.
Note
Calibration of the transmitter may include Sensor Input Trim: Digitally alter the
transmitter’s interpretation of the input signal.

Trim the transmitter


The Sensor Input Trim function may be used when performing calibrations.
Sensor calibration
Fast Keys: 3, 5, 2
If the transmitter's digital value for the primary variable does not match the plant’s
standard calibration equipment, then Emerson recommends performing a sensor trim. The
sensor trim function calibrates the sensor to the transmitter in temperature units or raw
units. Unless your site-standard input source is NIST-traceable, the trim functions will not
maintain the NIST-traceability of the system.
The Sensor Input Trim command allows the transmitter’s interpretation of the input signal
to be digitally altered. The sensor reference command trims, in engineering (°F, °C, °R, K)
or raw (Ω, mV) units, the combined sensor and transmitter system to a site standard using

Rosemount 248 19
Configuration Reference Manual
April 2024 00809-0100-4248

a known temperature source. Sensor trimming is suitable for validation procedures or for
applications that require calibrating the sensor and transmitter together.
To perform a sensor trim with a transmitter:

Procedure
1. Connect the calibration device or sensor to the transmitter. Refer to Figure 2-1 or on
the device terminal block for sensor wiring diagrams.
2. Connect the communicator to the transmitter.
3. From the Home screen, select Service Tools → Maintenance → Calibration to prepare
to trim the sensor.
4. Select one:
• 6 Lower Sensor Trim
• 7 Upper Sensor Trim

Note
Emerson recommends performing lower offset trims first and upper slope trims
second.

5. Answer the prompt about configuring device for steady state sensor drive.
6. Select the appropriate sensor trim units at the prompt.
7. Adjust the calibration device to the desired trim value (must be within the selected
sensor limits).
If a combined sensor and transmitter system are being trimmed, expose the sensor
to a known temperature and allow the temperature reading to stabilize. Use a bath,
furnace or isothermal block, measured with a site-standard thermometer, as the
known temperature source.

8. After the temperature has stabilized, select OK. The communicator displays the
output value the transmitter associates with the input value provided by the
calibration device.
9. Accept new calibration.

AMS Device Manager


For AMS Device Manager, configure the sensor as indicated above.

Procedure
1. From the Overview screen, select the Calibrate button.
2. Select Lower Input Trim or Upper Limit Trim. The wizard will continue through the
process.
3. To restore the transmitter to factory default, select Service Tools → Maintenance →
Sensor Calibration → Recall Factory Trim. The wizard will revert the transmitter to
the factory trim for a given sensor.
4. Apply changes.

2.4.6 Configuring the LCD display


The LCD display configuration command allows customization of the LCD to suit
application requirements. The LCD will alternate between the selected items:
• Temperature Units
• Sensor Temperature

20 Emerson.com/Rosemount
Reference Manual Configuration
00809-0100-4248 April 2024

• % of Range
• Supply Voltage

Related information
LCD display screen messages

Enabling and configuring LCD display with a Field


Communicator
From the Home screen, enter the Fast Key sequence: 2, 1, 5
Transmitters ordered with the LCD display will be shipped with the display enabled and
installed.
If the transmitter was ordered without the LCD display (and the LCD display was ordered
as a spare part) or if the LCD display was disabled, follow these steps to enable the LCD
display on the transmitter:

Procedure
1. From the Home screen, select 2: Configure.
2. Select 1: Guided Setup.
3. Select 5: Configure Device Display.
4. Select the option Periodic.
5. Select desired display options and click Enter.

Configuring LCD display with AMS Device Manager


Procedure
1. Right-click on the device and select Configure.
2. Select Configure Device Display button under Optional Setup.
3. Select desired display options and select Enter.

Rosemount 248 21
Configuration Reference Manual
April 2024 00809-0100-4248

2.4.7 Alerts
Fast Keys: 2, 3
Alerts allow the user to configure the transmitter to output a HART® message when the
configured data point is exceeded. A process alert will be transmitter continuously if the
set points are exceeded and the alert mode is ON. An alert will be displayed on a Field
Communicator, AMS Device Manager status screen, or in the error section of the LCD
display. The alert will reset once the value returns within range.

NOTICE
HI alert value must be higher than the LO alert value. Both alert values must be within the
temperature sensor limits.

Figure 2-10: Rising Alert

A. Units of measurement
B. Alert "OFF"
C. Alert "ON"
D. Alert "OFF"
E. Deadband
F. Time
G. Assigned value
H. Alert set point

22 Emerson.com/Rosemount
Reference Manual Configuration
00809-0100-4248 April 2024

Figure 2-11: Falling Alert

A. Units of measurement
B. Alert "OFF"
C. Alert "ON"
D. Alert "OFF"
E. Assigned value
F. Alert set point
G. Deadband
H. Time

Rosemount 248 23
Configuration Reference Manual
April 2024 00809-0100-4248

Field Communicator
To configure the process alerts with a Field Communicator:

Procedure
1. From the HOME screen, follow the Fast Key sequence, 2 Configure → 3 Alert Setup:
• Select 1 for HI-HI Alarm
• Select 2 for HI Alarm
• Select 3 for LO Alarm
• Select 4 for LO-LO Alarm

2. Select 1 to configure the alert.

2.5 Remove power module


After the sensor and network have been configured, remove the Power Module and
replace the module cover. Emerson recommends inserting the power module only when
the device is ready to be commissioned.

CAUTION
Exercise caution when handling the power module. The power module may be damaged if
dropped from heights in excess of 20 feet (6 m).

24 Emerson.com/Rosemount
Reference Manual Installation
00809-0100-4248 April 2024

3 Installation
3.1 Wireless considerations

3.1.1 Power up sequence


Emerson recommends installing the Rosemount 248 Wireless Transmitter and all other
devices only after the Wireless Gateway has been installed and is functioning properly.
Wireless devices must also be powered up in order of proximity from the Gateway,
beginning with the closest. This will result in a simpler and faster network installation.
Enable Active Advertising on the Gateway to ensure new devices join the network faster.
Emerson Wireless 1410S Gateway and 781S Smart Antenna

Related information
Emerson Wireless 1410S Gateway and 781S Smart Antenna

3.1.2 Antenna position


The internal antenna is designed for multiple mounting orientations. Emerson
recommends mounting the transmitter according to best practices for your temperature
measurement application. The transmitter must be approximately 3 ft. (1 m) from any
large structure or building to allow clear communication to other devices.

3.1.3 Network design best practices


When mounting the device, follow recommended practices to achieve the best wireless
performance.

Related information
Mounting

3.2 Field Communicator connections


The power module must be installed in the device for the Field Communicator to interface
with the transmitter. The Field Communicator connections are located on the Green Power
Module.
To communicate with the transmitter:
1. Remove the power module cover. This will expose the HART® communication
terminals located on the Green Power Module.
2. Connect the Field Communicator leads to the COMM port connections on the Green
Power Module.
This transmitter uses the Green Power Module; Order Model number: 701PGNKF. The
power module is keyed and can only be inserted in one orientation. Field communication
with this device requires a HART-based Field Communicator. Refer to Figure 3-1 for
instructions on connecting the Field Communicator to the transmitter.

Rosemount 248 25
Installation Reference Manual
April 2024 00809-0100-4248

Figure 3-1: Field Communicator Connection

3.2.1 Mechanical
Location
When choosing an installation location and position, consider the need for access to the
mesh network, access to the transmitter, and to the power module compartment for ease
of power module replacement.

Electronics cover
The electronics cover is tightened so that polymer contacts polymer. When removing
the electronics cover, ensure that there is no damage done to the O-ring. If damaged,
Emerson recommends replacing it with a Rosemount O-ring. Reattach cover. Ensure
polymer contacts polymer (i.e. no O-ring visible).

3.2.2 Electrical
Power module
The transmitter is self-powered. The power module contains a primary lithium-thionyl
chloride battery (Green Power Module, model number 701PGNKF). Each battery contains
approximately 5 grams of lithium. Under normal conditions, the battery materials are
self-contained and are not reactive as long as the battery and the power module are
maintained.

CAUTION
Use caution when handling the power module. It may be damaged if dropped from heights
in excess of 20 feet.
Battery hazards remain when cells are discharged.

NOTICE
Care must be taken to prevent thermal, electrical, or mechanical damage. Contacts must
be protected to prevent premature discharge.
Power modules must be stored in a clean and dry area. For maximum power module life,
storage temperature must not exceed 86 °F (30 °C).

Sensor
Make sensor connections with the threaded 1½-in. NPT connection sensor adapter.

26 Emerson.com/Rosemount
Reference Manual Installation
00809-0100-4248 April 2024

3.2.3 Environmental
Verify that the operating atmosphere of the transmitter is consistent with the appropriate
hazardous locations certifications.

Temperature effects
The transmitter will operate within specifications for ambient temperatures between –40
and 185 °F (–40 and 85 °C). Heat from the process is transferred from the thermowell to the
transmitter housing.
If the expected process temperature is near or beyond specification limits, then consider
the use of additional thermowell and extension, or remote mounting the transmitter to
thermally isolate it from the process.

3.3 Mounting
The transmitter can be installed in one of two configurations:
• Direct Mount: This is where the sensor is connected directly to the transmitter
housing’s conduit entry.
• Remote Mount: This is where the sensor is mounted separate from the transmitter
housing, then connected to the transmitter via conduit.
Select the installation sequence that corresponds to the mounting configuration.
Figure 3-2 provides an example of the relationship between transmitter housing
temperature rise and extension length.

Figure 3-2: Temperature Rise vs. Extension Length

A. Housing Temperature Rise, above Ambient (°C [°F])


B. 815 °C (1500 °F) Process Temperature
C. 540 °C (1000 °F) Process Temperature
D. 250 °C (482 °F) Process Temperature
E. Extension Length (in.)

Example
The transmitter specification limit is 185 °F (85 °C).
If the ambient temperature is 131 °F (55 °C) and the max process temperature to be
measured is 1499 °F (815 °C), the maximum permissible temperature rise is the transmitter
specification limit minus the ambient temperature (moves 85 to 55 °C), or 86 °F (30 °C).

Rosemount 248 27
Installation Reference Manual
April 2024 00809-0100-4248

In this case, an extension of 5-in. (127 mm) meets this requirement, but 6-in. (152 mm)
provides an additional margin of thermowells protection, thereby reducing risk of ambient
thermal damage.

Temperature limits

Operating limit Storage limit

With LCD display –4 to 185 °F –40 to 185 °F


–20 to 85 °C –40 to 85 °C

Without LCD display –40 to 185 °F –40 to 185 °F


–40 to 85 °C –40 to 85 °C

3.4 Physical installation


Choose the installation sequence that corresponds to the mounting configuration.
After installation of the transmitter, ensure that the conduit entry has an installed conduit
fitting or cable gland with approved thread sealant.

3.4.1 Direct mount


The direct mount installation must not be used when installing with a Swagelok® fitting.

Procedure
1. Remove the transmitter enclosure cover.
2. Remove the LCD display (if applicable).
3. Loosen the captive screws and remove LCD display adapter plate (if applicable).
4. Attach the sensor to the transmitter housing using the threaded conduit entry.
Note
Ensure that an approved thread sealant is used on all connections.

Figure 3-3: Exploded View of LCD Display Assembly

A. Housing cover
B. LCD meter
C. Terminal screws
D. LCD adapter plate
E. Housing
F. Green power module
G. Power module cover

5. Attach the sensor wiring to the terminals as indicated on Figure 2-1.


6. Reattach and secure LCD display adapter plate to 5 in.-lb. of torque (if applicable).
7. Reattach the LCD display (if applicable).

28 Emerson.com/Rosemount
Reference Manual Installation
00809-0100-4248 April 2024

8. Reattach and tighten the transmitter enclosure cover.


9. Remove the power module cover.
10. Connect the Green Power Module.
11. Reattach and tighten the power module cover.
12. Always ensure a proper seal by installing the electronics housing cover(s) so
that polymer contacts polymer (i.e. no O-ring visible). Emerson recommends using
Rosemount O-rings.
13. Provide 1.75 in. (45 mm) of clearance for units without an LCD display. Provide 3 in.
(76 mm) of clearance for units with an LCD display for cover removal.

Figure 3-4: Direct Mount

Note
Dimensions are in inches (millimeters).
Wireless devices must be powered up in order of proximity from the Gateway,
beginning with the closest device to the Gateway. This will result in a simpler and
faster network installation.

3.4.2 Remote mount


Procedure
1. Remove the transmitter enclosure cover.
2. Remove the LCD display (if applicable).
3. Loosen the captive screws and remove LCD display adapter plate (if applicable).
4. Run wiring (and conduit, if necessary) from the sensor to the transmitter.
Note
Use a ½-in. NPT when mating conduit to the transmitter.

Rosemount 248 29
Installation Reference Manual
April 2024 00809-0100-4248

Figure 3-5: Exploded View of LCD Display Assembly

A. Housing cover
B. LCD meter
C. Terminal screws
D. LCD adapter plate
E. Housing
F. Green power module
G. Power module cover

5. Pull the wiring through the threaded conduit entry of the transmitter.
6. Attach the sensor wiring to the terminals as indicated on Figure 2-1.
7. Reattach and secure LCD display adapter plate to 5 in.-lb. of torque (if applicable).
8. Reattach the LCD display (if applicable).
9. Reattach and tighten the transmitter enclosure cover.
10. Remove the power module cover.
11. Connect the Green Power Module.
12. Reattach and tighten the power module cover.
13. Always ensure a proper seal by installing the electronics housing cover(s) so that
polymer contacts polymer (i.e. no O-ring visible). Use Rosemount O-rings.
14. Provide 1.75 in. (45 mm) of clearance for units without an LCD display. Provide 3 in.
(76 mm) of clearance for units with an LCD display for cover removal.

30 Emerson.com/Rosemount
Reference Manual Installation
00809-0100-4248 April 2024

Figure 3-6: Remote Mount

Note
Dimensions are in inches (millimeters).
Wireless devices must be powered up in order of proximity from the Wireless
Gateway, beginning with the closest device to the Gateway. This will result in a
simpler and faster network installation.

3.4.3 LCD display


Transmitters ordered with the LCD display will be shipped with the display installed.
The optional LCD display can be rotated in 90-degree increments by squeezing the two
tabs, pulling out, rotating and snapping back into place.
Use the following procedure and Figure 3-7 to install the LCD display:

Procedure
1. Remove the power module cover and Green Power Module.
2. Remove the transmitter enclosure cover.

CAUTION
When the circuit is live, do not remove the instrument covers in explosive
environments.

3. Tighten the captive screws and secure LCD adapter plate to 5 in-lb of torque.
4. Attach the LCD display on the LCD adapter plate, rotate to the desired position, and
snap into place.
5. Reattach and tighten the transmitter enclosure cover.
6. Connect the Green Power Module.
7. Reattach and tighten the power module cover.

Rosemount 248 31
Installation Reference Manual
April 2024 00809-0100-4248

8. Always ensure a proper seal by installing the covers so that polymer contacts
polymer (i.e. no O-ring visible). Emerson recommends using Rosemount O-rings.
To enable and configure the LCD display, refer to Configuring the LCD display.
Note the following LCD display temperature limits:
Operating: –40 to 185 °F (–40 to 85 °C)
Storage: –40 to 185 °F (–40 to 85 °C)
Note
Only use Rosemount wireless LCD display part number: 00753-3203-0001.
An LCD display from a wired device will not function in a wireless device.

Figure 3-7: Optional LCD Display

32 Emerson.com/Rosemount
Reference Manual Commissioning
00809-0100-4248 April 2024

4 Commissioning
4.1 Verify operations
Operations can be verified in four locations:
• At the device via the Local Display
• Using the Field Communicator
• At the Gateway's integrated web interface
• Using AMS Wireless Configurator or AMS Device Manager

4.1.1 Local display


During normal operation, the LCD display will display the PV value at the configured
update rate.
For Device Status screens, see LCD display screen messages.

4.1.2 Field Communicator


For HART® communication, a Rosemount 248 Wireless Device Driver (DD) is required. To
obtain the latest DD, see Emerson.com/Rosemount/Device-Install-Kits.
The communication status may be verified in the wireless device using the following Fast
Key sequence.
Table 4-1: Fast Key Sequence

Function Key sequence Menu items

Communications 3, 4 Comm Status, Join Mode, Available


Neighbors, Advertisement, Join Attempts

4.1.3 Emerson wireless gateway


In the integrated web interface from the Gateway, navigate to the Explorer → Status page.
This page shows whether the device has joined the network and if it is communicating
properly.
Note
It may take several minutes for the device to join the network. If the device joins
the network and immediately has an alarm present, then it is likely due to sensor
configuration. Check the sensor wiring. See Figure 4-3 and Table 4-2.

Rosemount 248 33
Commissioning Reference Manual
April 2024 00809-0100-4248

Figure 4-1: Wireless Gateway Network Settings

4.1.4 AMS wireless configurator


When the device has joined the network, it will appear in the Wireless Configurator window
as shown in Figure 4-2. For HART® communication, a Rosemount 248 Wireless DD is
required. To obtain the latest DD, see Emerson.com/Rosemount/Device-Install-Kits.

Figure 4-2: AMS Wireless Configurator

34 Emerson.com/Rosemount
Reference Manual Commissioning
00809-0100-4248 April 2024

4.2 Reference information


Figure 4-3: Sensor Wiring

A. Thermocouple and mV
B. 4-Wire RTD and Ω
C. 3-Wire RTD and Ω
D. 2-Wire RTD and Ω

Figure 4-4: Sensor Connections

A. 2-wire RTD and Ω


B. 3-wire RTD and Ω
C. 4-wire RTD and Ω
D. T/C and mV

Rosemount 248 35
Commissioning Reference Manual
April 2024 00809-0100-4248

Note
Emerson provides 4-wire sensors for all single element RTDs. Use these RTDs in 3- or 2-wire
configurations by leaving the unneeded leads disconnected and insulated with electrical
tape.

Table 4-2: Wireless HART® Fast Key Sequences

Function Key sequence Menu items

Device Information 1, 7 Identification, Revisions, Radio, Security

Guided Setup 2, 1 Join Device to Network, Configure Update


Rate, Configure Sensor, Calibrate Sensor

Manual Setup 2, 2 Wireless, Process Sensor, Percent of Range,


Device Temperatures, Device Information,
Other

Wireless Configuration 2, 2, 1 Network ID, Join to Network, Broadcast Info

Sensor Calibration 3, 5, 2 Sensor Value, Sensor Status, Current Lower


Trim, Current Upper Trim, Lower Sensor
Trim, Upper Sensor Trim, Recall Factory
Trim

Figure 4-5: RTD Lead Wire Configuration per IEC 60751

A. Single element, 3-wire


B. Single element, 4-wire
C. Dual element, 3-wire
D. Red
E. Black
F. White
G. Yellow

Note
To configure a single element, 4-wire RTD as a 3-wire system, connect only one white lead.
Insulate or terminate the unused white lead in a manner that prevents shorting to the
ground.
To configure a single element, 4-wire RTD as a 2-wire system, connect matching colored
wires first and then connect the paired wires to the terminal.

36 Emerson.com/Rosemount
Reference Manual Commissioning
00809-0100-4248 April 2024

Figure 4-6: Thermocouple Lead Wire Configurations

A. Single thermocouple, 2-wire


B. Dual thermocouple, 4-wire

IEC 60584 thermocouple colors ASTM E-230 thermocouple colors

Type Positive (+) Negative (-) Positive (+) Negative (-)

J Black White White Red

K Green White Yellow Red

T Brown White Blue Red

Note
Dual thermocouple sensors are shipped with one pair of the wires shrink-wrapped
together.

Rosemount 248 37
Commissioning Reference Manual
April 2024 00809-0100-4248

38 Emerson.com/Rosemount
Reference Manual Operation and maintenance
00809-0100-4248 April 2024

5 Operation and maintenance


5.1 LCD display screen messages

5.1.1 Startup screen sequence


Note
Use the Rosemount Wireless LCD Part Number: 00753-3203-0001.

The following screens will display when the power module is first connected to the
transmitter:

Alert Screen: There is at least one alert that is present. This


screen will not display if no alerts are present.

alert

presnt

All Segments On: This is used to visually determine if there


are any bad segments on the LCD display.

XXXXX
XXXXxxx
xxxxxx

Device Identification: This is used to determine device type.

XXXXxx

Device Information - Tag: This is the user-entered tag


which is eight characters long. It will not display if all
characters are blank.
Abcde

fgh

Rosemount 248 39
Operation and maintenance Reference Manual
April 2024 00809-0100-4248

Percent Range Screen: This is the percent range reading.

PRCNT
7. 2 1
RANGE

PV Screen: This is the process temperature, ohms, or mV


value, depending on how the device is configured.

snsr
1 0. 0 2
deg c

QV Screen: This is the voltage reading at the power supply


terminals.

Suply
3. 6 0
volts

Software Revision: This is the device software revision.

SV Screen: This is the terminal temperature value.

TRMNL
X25.00

40 Emerson.com/Rosemount
Reference Manual Operation and maintenance
00809-0100-4248 April 2024

TV Screen: This is the device temperature value.

ELEC
X25.00Xxx

5.2 Power module replacement


Expected power module life is 10 years at reference conditions.(1)
When power module replacement is required, remove the cover and remove the Green
Power Module. Replace the Green Power Module (part number 701PGNKF) and replace the
cover. Tighten to specification and verify operation.

Figure 5-1: Exploded Power Module View

5.2.1 Handling considerations


The Green Power Module with the wireless unit contains one “D” size primary lithium-
thionyl chloride battery (Green Power Module, model number 701PGNKF). Each battery
contains approximately 5.0 grams of lithium. Under normal conditions, the battery
materials are self-contained and are not reactive as long as the batteries and the pack
integrity are maintained.

CAUTION
Care must be taken to prevent thermal, electrical or mechanical damage.
Contacts must be protected to prevent premature discharge.
Use caution when handling the power module. It may be damaged if dropped from heights
in excess of 20 ft (6.1m).
Battery hazards remain when cells are discharged.

(1) Reference conditions are 70° F (21° C), transmit rate of once per minute, and routing data for three additional
network devices.

Rosemount 248 41
Operation and maintenance Reference Manual
April 2024 00809-0100-4248

NOTICE
Power modules must be stored in a clean and dry area. For maximum power module life,
storage temperature must not exceed 86 °F (30 °C).

5.2.2 Environmental considerations


As with any battery, local environmental rules and regulations must be consulted for
proper management of spent batteries. If no specific requirements exist, then Emerson
recommends recycling through a qualified recycler. For battery specific information,
consult the material’s Safety Data Sheet.

5.2.3 Shipping considerations


The unit was shipped without the power module installed. Before shipping the unit,
remove the power module.

42 Emerson.com/Rosemount
Reference Manual Troubleshooting
00809-0100-4248 April 2024

6 Troubleshooting
6.1 Overview
This section provides summarized maintenance and troubleshooting suggestions for the
most common operating problems. If malfuction is suspected, despite the absence of
any diagnostic messages on the Field Communicator display, then follow the procedures
described here to verify that transmitter hardware and process connections are in good
working order. Always deal with the most likely checkpoints first.

6.2 Device status information

6.2.1 Electronics failure


Description
An electronics error that could impact the device measurement reading has occurred.

Recommended actions
1. Reset the device.
2. Reconfirm all configuration items in the device.
3. If the condition persists, replace the electronics.

6.2.2 Electronics temperatures has exceeded limits


Description
The electronics temperature has exceeded the transmitter's maximum range.

Recommended actions
1. Verify environmental temperature is within the transmitter’s range.
2. Remote-mount the transmitter away from process and environmental
conditions.
3. Reset the device.
4. If the condition persists, replace the electronics.

6.2.3 Electronics warning


Description
The device has detected an electronics error that does not currently impact the device
measurement reading.

Recommended actions
1. Reset the device.
2. Reconfirm all configuration items in the device.
3. If the condition persists, replace the electronics.

Rosemount 248 43
Troubleshooting Reference Manual
April 2024 00809-0100-4248

6.2.4 Database memory warning


Description
The device has failed to write to the database memory. Any data written during this time
may have been lost.

Recommended actions
1. Reset the device.
2. Reconfirm all configuration items in the device.
• If logging dynamic data not needed, then this advisory can be safely
ignored.
• If the condition persists, then replace the electronics.

6.2.5 Hi alarm
Description
The primary variable has surpassed the user-defined limit.

Recommended actions
1. Verify the process variable is within user-specified limits.
2. Reconfirm the user-defined alarm limit.
3. If not needed, then disable this alert.

6.2.6 Hi Hi alarm
Description
The primary variable has surpassed the user-defined limit.

Recommended actions
1. Verify the process variable is within user-specified limits.
2. Reconfirm the user-defined alarm limit.
3. If not needed, then disable this alert.

6.2.7 Lo alarm
Description
The primary variable has surpassed the user-defined limit.

Recommended actions
1. Verify the process variable is within user-specified limits.
2. Reconfirm the user-defined alarm limit.
3. If not needed, then disable this alert.

44 Emerson.com/Rosemount
Reference Manual Troubleshooting
00809-0100-4248 April 2024

6.2.8 Lo Lo alarm
Description
The primary variable has surpassed the user-defined limit

Recommended actions
1. Verify the process variable is within user-specified limits.
2. Reconfirm the user-defined alarm limit.
3. If not needed, then disable this alert.

6.2.9 Radio failure


Description
The wireless radio has detected a failure or stopped communicating.

Recommended actions
1. Reset the device.
2. If the condition persists, replace the electronics.

6.2.10 Simulation active


Description
The device is in simulation mode and may not be reporting actual information.

Recommended actions
1. Verify simulation is no longer required.
2. Disable Simulation mode in Service Tools.
3. Reset the device.

6.2.11 Supply voltage failure


Description
The supply voltage is too low for the device to broadcast updates.

Recommended actions
Replace the power module.

6.2.12 Supply voltage low


Description
The supply voltage is low and may soon affect broadcast updates.

Recommended actions
Replace the power module.

Rosemount 248 45
Troubleshooting Reference Manual
April 2024 00809-0100-4248

6.3 Transmitter troubleshooting

6.3.1 Digital temperature output is erratic


Potential cause
Wiring

Recommended actions
Check sensor wiring integrity at all junctions to ensure proper connections.

Potential cause
Electronics module

Recommended actions
Connect a communication device and enter the Transmitter test mode to isolate
module failure.

6.3.2 High output temperature detected


Potential cause
Sensor input failure or connection

Recommended actions
1. Connect a communication device and enter the transmitter test mode to isolate
a sensor failure.
2. Check for a sensor open or short circuit.
3. Check the process variable to see if it is out of range.

Potential cause
Electronics module

Recommended actions
1. Connect a communication device and enter the Transmitter status mode to
isolate module failure.
2. Connect a communication device and check the sensor limits to ensure
calibration adjustments are within the sensor range.

6.3.3 Low output or no output


Potential cause
Sensor element

Recommended actions
1. Connect a communication device and enter the Transmitter test mode to isolate
a sensor failure.
2. Check the process variable to see if it is out of range.

46 Emerson.com/Rosemount
Reference Manual Troubleshooting
00809-0100-4248 April 2024

6.4 LCD display troubleshooting

6.4.1 LCD display not operating


Potential cause
Electronic module

Recommended actions
Ensure the LCD display in enabled.

Potential cause
Connector

Recommended actions
Ensure the LCD display pins are not bent.

Potential cause
LCD display

Recommended actions
Ensure the LCD display is properly seated with the tabs snapped in place and fully
engaged.

6.5 Wireless network troubleshooting

6.5.1 Device not joining the network


Recommended actions
1. Verify Network ID and join key.
2. Verify network is in Active network advertise.
3. Continue waiting; up to 30 minutes maximum.
4. Check power module.
5. Verify device is within range of at least one other device.
6. Power cycle device to try again.
7. Verify device is configured to join. Ensure the Join mode is configured to Join on
Powerup or Reset.

6.5.2 Limited bandwidth error


Recommended actions
1. Reduce the update rate on transmitter.
2. Increase communication paths by adding more wireless points.
3. Check that device has been on line for at least an hour.
4. Check that device is not routing through a “limited” routing node.
5. Create a new network with an additional Wireless Gateway.

Rosemount 248 47
Troubleshooting Reference Manual
April 2024 00809-0100-4248

6.5.3 Short battery life


Recommended actions
1. Check that Power Always On mode is off.
2. Verify device is not installed in extreme temperatures.
3. Verify device is not a network pinch point.
4. Check for excessive network rejoins due to poor connectivity.

48 Emerson.com/Rosemount
Reference Manual Reference data
00809-0100-4248 April 2024

A Reference data
A.1 Product Certifications
To view current Rosemount 248 Wireless Temperature Transmitter Product Certifications:

Procedure
1. Go to Emerson.com/Rosemount/Rosemount-248-Wireless.
2. Scroll as needed to the green menu bar and click Documents & Drawings.
3. Click Manuals & Guides.
4. Select the appropriate Quick Start Guide.

A.2 Ordering information, specifications, and


drawings
To view current Rosemount 248 Wireless Temperature Transmitter Ordering Information,
Specifications, and Drawings:

Procedure
1. Go to Emerson.com/Rosemount/Rosemount-248-Wireless.
2. Scroll as needed to the green menu bar and select Documents & Drawings.
3. For installation drawings, select Drawings & Schematics.
4. Select the appropriate document.
5. For ordering information, specifications, and dimensional drawings, select Data
Sheets & Bulletins and select the appropriate Product Data Sheet.

Rosemount 248 49
Reference data Reference Manual
April 2024 00809-0100-4248

50 Emerson.com/Rosemount
Reference Manual Alert message mapping
00809-0100-4248 April 2024

B Alert message mapping


This appendix outlines the most important alerts in the HART® command 84 Additional
Status Field for the transmitter. The information in this section can be used by DeltaV™ for
alert monitoring, and in the Emerson Wireless Gateway for Additional Status mapping in
Modbus®, OPC, etc.
A complete list of additional status bits is available in the Wireless Gateway.
Table B-1 to Table B-2 display the device variable and variable mapping indexes for the
transmitter.
Table B-3 to Table B-4 show a list of the most important alert messages that may be
displayed in the AMS Wireless Configurator and Field Communication together with the
location of the Alert in the HART command 48 additional status field.
To view Active Alerts, from the Home screen, go to Service Tools → Active Alerts.
Table B-1: Device Variable Index

Device variable Index

0 Supply voltage

1 Electronics temperature

2 Totalized volume

3 Average flow rate

Table B-2: Default Variable Mapping Index

Variables Index

PV Totalized volume

SV Average flow rate

TV Electronics temperature

QV Supply voltage

Note
This index can be modified.

Table B-3: Failure Alerts (F:)

Message Additional status(1) Description

Electronics Failure Byte 8 :: Bit 6 A failure has been detected in the device memory
and/or electronics.

Configuration Error Byte 2 :: Bit 6 The device has detected a configuration error
based on a change to the device.

Radio Failure Byte 1 :: Bit 6 The wireless radio has detected a failure or
stopped communicating.

Supply Voltage Failure Byte 6 :: Bit 2 The supply voltage is too low for the device to
broadcast.

(1) Location of the alert in the HART command 48 status field.

Rosemount 248 51
Alert message mapping Reference Manual
April 2024 00809-0100-4248

Table B-4: Maintenance Alerts (M:)

Message Additional status(1) Description

Totalized Volume Rollover Byte 3 :: Bit 2 The totalized volume has exceeded the
maximum value and automatically reset to
zero.

Average Flow Rate Byte 3 :: Bit 0 The average flow rate is beyond the
Saturated operating limits of the device and the
reported value is saturated.

Electronics Temperature Byte 8 :: Bit 5 The terminal temperature has exceeded


Beyond Limits the transmitter’s maximum range.

Supply Voltage Low Byte 8 :: Bit 4 The supply voltage is low and may soon
affect broadcast updates.

(1) Location of the alert in the HART command 48 status field.

52 Emerson.com/Rosemount
Reference Manual
00809-0100-4248 April 2024

Rosemount 248 53
00809-0100-4248
Rev. DE
2024

For more information: Emerson.com/global


©2024 Emerson. All rights reserved.

Emerson Terms and Conditions of Sale are available


upon request. The Emerson logo is a trademark and
service mark of Emerson Electric Co. Rosemount is a
mark of one of the Emerson family of companies. All
other marks are the property of their respective owners.

You might also like