Generator Protection Course
Generator Protection Course
Generator Protection Course
), ME,
Executive Engineer, Tel : 0461-2352521/22/23/24
Meter Relay Test Division – II, extn : 119
Tuticorin Thermal Power Station, Fax : 0461-2352457
Tamil Nadu Electricity Board, e-mail : ttps_tneb @ dataone.in
Tuticorin – 628004.
FOREWORD
I am immensely happy to bring out this Short term course material on “GENERATOR
PROTECTION FOR 210MW TURBO-GENERATORS” prepared and conducted by
Er. A. Krishnavel, B.E. (Hons.), Assistant Executive Engineer / MRT-2 / TTPS.
In a very big organization like TNEB, only a few engineers are fortunate enough to
find berth in specialized fields like Meter Relay Tests (MRT) and access to the maintenance
of Protective Gears. The Protection Engineer has to be fully conversant and knowledgeable
not only with the protection relay subjects but also with the equipments to be protected.
Similarly, maintenance engineers of the Electrical equipments, have to be so familiar with
the Protection fundamentals and basic techniques, so that the equipments could be
maintained and operated in the correct way.
I would like to thank all the participants for their enthusiasm and attentiveness in the
class, without which the sessions could not be so lively.
Sd…01.02.07
Tuticorin-4, (R. Kamaraj),
01.02.2007. Executive Engineer,
TTPS / Tuticorin-4.
TNEB / TUTICORIN THERMAL POWER STATION
A short term Advanced Course on Generator Protection
- A. Krishnavel, B.E.(Hons.),
Asst. Exe.Engineer / MRT2 / TTPS.
26.10.2006.
Generator Protection and Trip Logics
Session - 1
(i) Generator?
An electrical generator, a machine which converts mechanical energy (or power) into electrical
energy (or power), mainly consists of Stator and Rotor.
Stator assembly has vital parts of slotted – laminated – core & Insulated windings. The stator
winding has a three layer short pitched and bar type of windings having two parallel paths (double
star). Each slot accommodates two bars. Each bar consists of Solid as well as hollow conductors
with cooling water passing through the latter to ensure the optimum solution for increasing current
and to reduce losses.
Rotor body is made-up of forged steel with longitudinal slots to house the field winding. The field
winding consists of several coils inserted into the longitudinal slots of the rotor body in such a way
to form magnetic poles as required in the design. The insulation between winding turns are very
flimsy in construction to reduce the space and mass of the rotor assembly.
(ii) Protection?
Electrical Protection does not mean Prevention. It is rather minimizing the duration of the trouble
and limiting damage. Protection, though it is a science, is an art by itself. Any art can not be
defined or contained in a shell (It could be practically seen that decisions in protection field are
depending upon individuals mainly). Protective Relaying is a binary science. It is a “Go” or “No Go”
condition.
(iii) Function of Protection Relaying?
Circuit Breaker
CT
F
G
Source
Load
Protective
Relay
The CT sees the fault at point “F” and the information is passed to the Protective Relay in the form
of Input Current quantity. The Relay, “The brain of the Protective Relaying” makes the decision
based on the pre-set reference quantity. The decision of the Relay is communicated to the Breaker
by means of Output Trip [Auxiliary] Relays. The opening the Circuit Breaker is executed with the
help of Trip coil. Fault Clearing Time = Relay operating time + CB opening Time
(iv) Generator Trip Logics?
Class A : In-zone Abnormalities which could not be tolerated much (Generally electrical
abnormalities) >>> Trips Turbine, Generator Circuit breaker (GCB), field breaker and
performs UAT change over simultaneously
Class B : In-zone Abnormalities which do not call for instant isolation >>> Trips Turbine and
performs UAT changeover simultaneously. GCB and filed breaker will be tripped on
Reverse power or Low Forward Power protection after some time delay.
Class C : Out-zone Abnormalities – Generator System need not be isolated completely - Trips
GCB alone – Unit under HOUSE LOAD.
Session – 1 attachments:
SLD of 210MW Turbo-Generator system -
Turbo - Generator System Trip Logic –
Total No. of Participants: 31
230kV Bus
Y
240/15.75kV, 3x84MVA
Yd1, Z=14% 800/1A, 5P20
+ or - 10% OLTC 30VA
15.75kV Bus
< CT 1 >
< CT 2 >
10000/5A, PS
Vk<350, 35mA < CT 3 >
5000/5A, PS
Vk<175, 25mA 6.6kV 6.6kV
Note:
10000/5A, Cl:PS, Vk<350, 35mA CT 1 = 600/5A, 5P20, 30VA
CT 2 = 600/5A, PS, Vk<300V, 150mA
10000/5A, 50VA, Cl:0.2, ISF>5 CT 3 = 10000/5A, PS, Vk<500V, 150mA
CT 4 = 2350/5A, PS, Vk<300V, 150mA
10000/5A, Cl:PS, Vk<350, 35mA VT 1 = 15.75kV/110V, 250VA, Cl:0.5/0.3
VT 2 = 15.75kV/110V, 175VA, Cl:0.5
10000/5A, Cl:PS, Vk<500, 35mA VT 3 = 15.75kV/110V, 50VA, Cl:0.2
UAT-B
GT
Generator
LK7
LK1 LK2 LK10 LK8
LK4 LK6
LK9 LK3
LK5
NGT Ex.Tr
Reactor UAT-A
ak_aee1_mrt2_ttps_GP_S1_26.10.06 P-2
ak_aee1_mrt2_ttps_GP_S1_26.10.06 P-3
Composite Numerical Generator Protection Management Relays
ak_aee1_mrt2_ttps_GP_S1_26.10.06 P-4
TNEB / TUTICORIN THERMAL POWER STATION
A short term Advanced Course on Generator Protection
- A. Krishnavel, B.E.(Hons.),
Asst. Exe.Engineer / MRT2 / TTPS.
09.11.2006.
Stator Earth (Ground) Fault Protection
Session - 2
1. System Neutral and System Grounding:
Generator
R
Y
B IR
Ig
IB IY
G
G
a. Ground (Earth) fault protection is dependent on the power system grounding, which can
vary from solidly grounded (no intentional impedance from the system neutrals to ground)
to ungrounded (system grounded only through the capacitance of the system).
b. With effective (solidly grounded) grounding, the line to ground fault current is equal to or
greater than 60% of the three phase fault current
c. In solidly grounded systems, the neutrals of the star-delta power transformers are directly
connected to earth through the station ground mat. Typical values of ground mat resistance
to earth are in the order of 0.1 ohm or less in areas of low ground resistivity. Typical values
are higher in high ground resistivity areas, resulting in a large station ground mat rise
(voltage gradient) between the station area and remote grounds during ground faults
d. The term “Un-grounded” means no physical connection of any kind between the system
and ground. However, there is always distributed capacitance (Natural shunt capacitance)
between the three phases of the system and ground, the system is grounded through this
capacitance. On such systems, current flows between each conductor and ground under
normal conditions. In the event of single line – ground fault, the corresponding line – ground
capacitance is shunted out.
e. System grounding is mainly classified as Reactance Grounding and Resistance Grounding.
Reactance Grounding has three different types called High reactance grounding, resonant
grounding and Low reactance grounding. The two types of resistance grounding are Low
and high resistance grounding.
f. Unless the fault is solid (rigid / permanent), an arc whose resistance varies with the arc
length and magnitude of the fault current is usually drawn through air. Several studies
indicate that, for currents in excess of 100A, the voltage across the arc is nearly constant at
an average of approximately 440V / foot.
ak_aee1_mrt2_ttps_GP_S2 P-1
g. Neutral Grounding Vs System parameters:
Extreme Case 1 >> Ungrounded System
R
VBN VRN
B Y
N
B Y B Y
B Y B Y
ak_aee1_mrt2_ttps_GP_S2 P-2
3. Why our Generator neutral is Grounded and by Impedance Grounded?
If we provide a solid grounding to our generator neutral, a high magnitude of fault current will flow
and damage the core and other current carrying parts in the path of the fault current. Shutting
down the generator through tripping the generator breaker, field, and prime mover does not cause
the fault current to immediately go to zero. The flux trapped in the field will result in the fault current
slowly decaying over a number of seconds after the Generator is tripped which substantially
aggravates the damage.
On the other hand, operating a Generator ungrounded provides negligible fault current, but the line
to ground voltages on the unfaulted phases can rise during arcing type faults to dangerously high
levels which could cause the failure of generator insulation.
Hence, the stator neutral of Major Generators are grounded in a manner that will reduce fault
current and over voltages and yet to provide a means of detecting the ground fault condition
quickly enough to prevent core burning.
For our Generators, we have provided a High Impedance Grounding by means of a distribution
transformer whose primary is connected between Generator neutral and ground and secondary is
shunted with reactor. The reactor is selected in such a way to neutralize the Generator system
zero sequence capacitive reactance due to generator winding, bus ducts, UATs, GT etc. Using this
grounding method, the single phase to earth fault current is limited to 3 – 25 primary amperes.
4. Impact on a Generator whose neutral is solidly earthed:
Due to heavy fault current, severe arcing to the machine core burns the iron at the point of fault
and welds laminations together. Replacement of the faulty conductor may not be a very serious
matter but the damage to the core cannot be ignored, since the welding of laminations would most
likely result in local overheating. The fused metal can sometimes be cut away and replaced, but if
severe damage has occurred, it may be necessary to rebuild the core down to the fault, which
would involve extensive dismantling of the winding.
5. Grounding through VT or Distribution Transformer? Which is the best?
In the case of a generator-transformer unit, the generator winding and primary winding of the
transformer can be treated as an isolated system which is not influenced by the earthing
requirements of the transmission system. It is not desirable that such a system should be entirely
‘floating’ in potential, and a common practice formerly applied was to earth the neutral through the
primary winding of a voltage transformer; the secondary winding was then used to energize alarm
devices to signal the existence of an earth fault. This is now considered to be unsafe practice,
because enough capacitance can exist in the machine winding and the connections to the
transformer to cause a build-up of dangerous over voltages in the event of an arcing earth fault.
Moreover, the capacitance effect may also prevent the earth fault current from being limited to the
very low value corresponding to the magnetizing current of the voltage transformer. Normal
modern practice is to use a larger earthing transformer rated in the range 5-100kVA. The
secondary winding, which is designed for medium voltage (100-500volts), is loaded with a resistor
or reactor of a value which, when referred through the transformer ratio, will pass a suitable fault
current.
In TTPS, the Generator Neutral is earthed through primary of a resin – cast Neutral Grounding
Transformer with a rating of 15.75kV / 240V, 50kVA. A reactor with a value of 0.986ohms, 240V,
and 145A is connected across the secondary. The lagging current produced by this reactor will
take vital part in neutralizing the capacitive current of the Generator system.
6. Causes of Insulation Failures:
The characteristics of the Insulating materials are much affected mainly by Electrical, Mechanical
and Thermal stresses. Ageing plays a vital role in deciding the healthiness of the Insulation in
addition to the above causes. Moreover, loose laminations vibrate heavily due to magneto-striction
and erode away the bar insulation killing the healthy winding. That is, even though the winding
insulation is not originally deteriorated by electrical stresses, some other means like violent core
vibrations and core thermal stresses due to lamination shorts may damage the insulation to some
worst level as well. The Insulation failures result in break down of the equipment which in turn will
account for the total shut down of any major system. Outage involving replacement, refurbishment
etc. will be some times much more expensive and need severe attention in assuring the prompt
identification and isolation of such faults.
ak_aee1_mrt2_ttps_GP_S2 P-3
7. A brief note on Stator
Stator Winding:
The stator has a three phase double
layer short pitched and bar type of
windings having two parallel paths.
Each slot accommodates two bars.
The slot lower (bottom) bars and the
slot upper bars are displaced from
each other by one winding pitch and
connected together by bus bars
inside the stator frame in conformity
with the connection diagram.
Each bar consists of Solid as well
as hollow conductors with cooling
water passing through the latter to
ensure the optimum solution for
increasing current and to reduce
losses. Please refer the figure. In
the straight slot portion, the strands
are transposed by 360 deg. to
reduce the eddy current losses. The
transposition provides for mutual
neutralization of voltages induced in
the individual strands due to the slot
cross field and end winding field and
ensures that no circulation currents
will arise.
Bar insulation is done with epoxy mica thermosetting insulation. This insulation is void free and
possesses better mechanical properties. Thermosetting epoxy insulation is more reliable winding
insulation, especially for high voltage. It shows only a small increase in dielectric dissipation factor
(Tan delta) with increasing test voltage. The composition of the insulation and synthetic resin
permits the machine to be operated continuously under conditions corresponding to these for
Insulation Class “B”
To prevent corona discharges between insulation and the wall of the slot, the insulation in slot
portion is coated with semi conducting varnish. At the transition from Slot to overhang winding a
stress grading varnish is coated to ensure a uniform control of the electric field and to prevent the
formation of creepage sparks during operation and during HV test
Three phases and six neutral terminals are brought out from the stator frame through bushings
which are capable of withstanding high voltage and provided with gas tight joints. For this purpose,
the bushings are bolted to the bottom plate at the terminal box with their mounting flanges. The
terminal box which is welded underneath the stator frame at exciter end is made of non magnetic
steel to avoid eddy current losses and thus any inadmissible temperature rise.
Stator Core:
It houses the stator winding bars and provides a path of very low reluctance to the flux through the
stator from the field winding (Rotor). In order to minimize the magnetizing and eddy current losses
in the core portion of the stator, the entire core is built-up of thin laminations. For reasons of
manufacture, each lamination layer is made up to a number of individual segments. The segments
are stamped out with accurately finished die from sheets of cold rolled high quality silicon steel.
Ventilating ducts are provided for entering Hydrogen into the core to take away the heat generated
due to eddy current loss. Typical thickness of the core laminations are 0.5mm.
ak_aee1_mrt2_ttps_GP_S2 P-4
8. Different methods of Stator Earth Fault Protection:
UAT-B
GT
Generator
LK7
LK1 LK2 LK10 LK8
LK4 LK6
LK9 LK3
LK5
NGT Ex.Tr
Reactor UAT-A
A B D C
Where, A, B, C & D are different types of Stator Earth Fault Protection techniques
A. Neutral Over Voltage ( 95% Stator winding Earth Fault Protection) – 59N:
An over voltage relay tuned to fundamental frequency is connected across the grounding reactor to
sense the Zero sequence voltage. The relay used for this function is designed to be sensitive to
fundamental frequency voltage and insensitive to third-harmonic and other zero sequence
harmonic voltages that are present at the generator neutral. Since the grounding impedance is
large compared to the generator impedance and other impedances in the circuit, the full phase to
neutral voltage will be impressed across the grounding device for a phase to ground fault at the
generator terminal.
Since the magnitude of the neutral shift is dependent on the location in the winding of the ground
fault (neutral to ground fault produces no neutral shift) and the usual choice of relay sensitivity and
distribution transformer voltage ratio provides roughly 95% coverage of the winding, this relaying
scheme is often referred to as 95% stator winding Earth Fault protection. This scheme will not
cover 0 – 5% of the stator winding from neutral end.
B. 100% Stator winding EF Protection =
3rd Harmonic Under voltage technique (27TN) + 95% Stator winding EF protection (59N)
Due to non-linearity with in the generator, third harmonic voltage is produced in the stator winding.
Under healthy conditions, this voltage causes circulation of third harmonic capacitive charging
currents resulting in a third harmonic voltage appearing between the neutral of the generator and
ground. The value of voltage will depend on the relative values of the impedance of the earthing
device, the capacitance to earth of the stator windings and the capacitance to earth of the bus
work and transformer windings connected to the generator.
The level of 3rd harmonic voltage at the neutral and generator terminals is dependent on the
operating conditions of the generator. The voltage is higher at full load than at no load
condition. However, depending on the generator design, the reverse may be true. There is
a blind region where the 3rd harmonic voltage would be Zero. The exact position of this
region depends on operating condition and generator design.
For a ground fault at the neutral, the 3rd harmonic voltage at the neutral becomes zero. For
a fault near the neutral, the level of 3rd harmonic voltage at the neutral would decrease and
the level at the generator terminals would increase. The amount of decrease or increase
depends on the operating conditions and the location of the fault. For a ground fault at the
generator terminals, the response would be just opposite to as mentioned above.
When a fault occurs close to neutral of the generator, third harmonic voltage between neutral and
ground will reduce to a near-zero value. An under voltage relay operating from 3rd harmonic
voltage measured at the neutral end could be used to detect the faults near the neutral. Normally,
the 3rd harmonic undervoltage protection can provide adequate protection for 0 – 30% of the stator
winding measured from the neutral towards the stator terminal. The ground faults in the remaining
portion of the windings can be detected by the conventional 95% Stator winding Earth fault
protection.
3rd Harmonic voltage measured at Neutral (across grounding reactor) for TTPS Turbo generators
(Unit # 4 & 5) at full load is around 6 V
ak_aee1_mrt2_ttps_GP_S2 P-5
C. 100% Stator winding EF Protection =
3rd Harmonic Residual Over voltage technique (59X) + 95% Stator winding protection (59N):
This technique is based on the fact that for a fault near the neutral, the level of 3rd harmonic
voltage at the generator terminals increases. An over voltage relay using 3rd harmonic voltage at
the terminals of the generator can be used for detecting faults near the neutral. The ground faults
in the remaining portion of the windings can be detected by the conventional 95% protection, i.e)
an over voltage relay which operates on 50Hz neutral voltage. Both of these relays would,
therefore, provide 100% protection of stator windings by covering different portions of the windings.
The residual voltage at the machine terminals is supplied by the Wye grounded broken delta
transformer (VTs in TTPS). This voltage is passed through a 150Hz tuned filter and an over
voltage detector.
D. 100% Stator winding Earth Fault Protection – Sub-harmonic voltage Injection (64S):
Due to design variations, certain generating units may not produce sufficient 3rd harmonic voltages
to apply the ground fault protection schemes based on 3rd harmonic signals. In such cases, as an
alternate measure, voltage injection scheme is employed to detect faults by injecting a sub-
harmonic voltage at the neutral or residually in a broken delta (open delta) voltage transformer
secondary. Full ground fault protection is available when the generator is on barring gear and
during start-up provided the injected voltage source does not originate from the generator.
In this principle of protection, the sub-harmonic current (generally at 12.5 Hz or 20Hz) is measured.
When a ground fault occurs, the sub-harmonic current increases and causes the relay to operate.
Generally the sub-harmonic injection signal is synchronized with the generator voltage
(fundamental frequency).
This method of protection scheme operates with the same sensitivity for faults over the entire
range of the windings. Also it provides 100% ground fault protection INDEPENDENT of the 95%
scheme. In addition, these schemes are self monitoring and have a sensitivity independent of
system voltage, load current and frequency. The use of sub harmonic frequencies offers improved
sensitivity because of the higher impedance path of the generator capacitances at these
frequencies.
9. Numerical Technology – A great boon to Protection Engineers:
Very first in TNEB history, a fully numerical Generator Protection Package for a 210MW generator
was commissioned for unit-5 / TTPS in the early 2005. For a stator earth fault on 08.01.2006, the
package responded very promptly and isolated the healthy part of the system within a negligible
time span of 25 – 30 cycles. The damage to the main equipment was confirmed to be extremely
less. The disturbance and event records captured by the package were quite useful for post trip
analysis.
Faulty point
The useful flux on-load, therefore, differs both in magnitude and position from that existing on no-
load. This is called Armature reaction. Due to an apposing force in the form of Armature Reaction,
an energy imbalance is created. To maintain energy balance, more mechanical force is given to
Rotor and the armature reaction is being compensated at every moment.
Hence, with out Armature reaction, there can be no opposing forces necessary to balance the
energy equation and a Generator could not perform its purpose of interchanging mechanical and
Electrical power.
ak_aee1_mrt2_ttps_GP_S3 P-1
4. Rotor - Design Constraints:
Even though the primary function of the field winding is to provide the path for the DC current
needed to magnetize the field, reaching this goal is not so simple. The three design constraints
that limit the size and life of generator rotors are temperature, mechanical force and electrical
insulation.
1. Centrifugal loading on winding and associated parts.
2. Lesser space for winding slots to avoid excessive stress.
3. Sufficient insulating systems to suit for all operating environments.
4. The insulation system must be strong enough to withstand the physical wear and tear of
assembly and winding, and during operation
5. Suitable ventilation system not exceeding the stress limits of the copper.
6. The field MMF (magneto motive force) must be sinusoidal in shape and of the desired
magnitude.
7. The winding must be symmetrical and balanced to prevent unacceptable vibrations.
8. Around 30 years of Normal operating life.
5. ROTOR - components:
6. ROTOR - DISLIKES:
♣ Field overheating
♣ Abnormal frequency and voltage
♣ Motoring
♣ Electrical faults
♣ Reduced seal oil pressure
♣ Rotor or stator vibration
♣ Voltage surges
♣ Unbalanced armature currents
♣ Loss of synchronism
♣ Accidental energization
♣ Carbon, dust and oil contamination
♣ Moisture accumulation in rotor bore, under seals, during manufacturing
ak_aee1_mrt2_ttps_GP_S3 P-2
Rotor - earth fault (64F or 100F)
1. Definition:
If the field winding makes contact with rotor body which is already earthed at Turbine end, due to
deterioration of Rotor conductor / turn- turn insulation, then the Rotor is declared as Defective or
Failed Electrically.
2. Effects of 1st Rotor E/F:
Being a non-earthed Field supply system, solid earth at a single point of the Rotor winding will not
be harmful.
3. Need for Rotor E/F protection:
Electrical Damage for 2nd E/F:
Danger arises if a second earth fault occurs at a separate point in the winding, causing the current
to be diverted, in part at least, from the intervening turns. The field current of a large machine is
considerable and, when so diverted, can burn the conductor, causing serious damage very rapidly.
Mechanical Damage for 2nd E/F:
If a large portion of the winding is short circuited the flux may adopt a pattern such that the flux is
concentrated on one pole but widely dispersed over the other and intervening surfaces.
The attracting force at the surface of the rotor is given by
F = B2 A / 8 π, Where A = Area, B = Flux density
This attracting force is in consequence large on one
pole but very weak on the opposite one, while flux
on the Quadrature axis will produce a balance force
on this axis. The result is an unbalanced force,
which in large machine may be of the order of 50 –
100 tons. This force is rotating with the rotor and
hence produces a violent vibration, which may
damage
bearing surfaces or even displace the rotor by an
amount sufficient to cause it to foul the stator
Point of
External
Source
ak_aee1_mrt2_ttps_GP_S3 P-3
ROTOR E/F Protections in TTPS Units 1 – 3: DC Injection
- ve
Relay with
bias
voltage + ve
- ve
Static
Excitation
+ ve System
mA meter
Static
Excitation
System
Second Rotor
E/F Relay
R R
Aux AC
Supply with CX = Balancing
Power capacitor
Frequency CK
CR
CX
CK
ak_aee1_mrt2_ttps_GP_S3 P-4
ROTOR E/F Protection in TTPS Unit # 5: Low Frequency AC Injection
An ac signal with low frequency square wave form is injected across the rotor winding and Earth as
shown above. The frequency of the square wave is selected based on the Rotor circuit
capacitance. The leakage current with injected low frequency is being monitored and trip signal is
issued if it exceeds the set value. Usually, the set value would be in Kilo ohms not in milli amperes.
This method of Rotor E/F scheme (Low frequency AC Injection) is recommended by Central Board
of Irrigation and Power, New Delhi. The latest version of Numerical relays has confirmed the high
degree of protection reliability in TTPS / Unit # 5 by adopting this injection method.
References:
1. IEEE Tutorial on the Protection of Synchronous Generators
2. Protective Relaying Theory and applications by Walter A. Elmore
3. BHELs’ Operation and Maintenance Manual for Turbo-Generator Vol. 1
4. GEC Measurements
5. TNEB Power Engineers Hand Book 2002
Total No. of Participants: 32 <<< 000 >>>
ak_aee1_mrt2_ttps_GP_S3 P-6
TNEB / TUTICORIN THERMAL POWER STATION
A short term Advanced Course on Generator Protection
- A. Krishnavel, B.E.(Hons.),
Asst. Exe.Engineer / MRT2 / TTPS.
23.11.2006.
Overvoltage, Overfluxing & Loss of Excitation
Session - 4
OVER VOLTAGE (59G)
1. Causes & effects of Over voltages: Over voltages on a generator may occur due to
Transient surges: The source for this kind of surges is switching and atmospheric
disturbances in the transmission system.
Sustained condition at power frequency :
• Mal-operation of AVR when the machine is in isolated operation (not in grid)
• When excitation control is in Manual, a sudden variation of the load, in particular the
MVAr component, will give rise to a substantial change in voltage because of the large
voltage regulation inherent in a typical alternator
• Sudden loss of load (due to tripping of outgoing feeders, leaving the generator isolated
or feeding a very small load) may cause a sudden rise in terminal voltage due to the
trapped field flux and /or overspeed of the turbine
Sustained over voltages will account for Over excitation and Insulation failures
2. How to protect from Over voltages?
Transient over voltage surges are dealt with by co-coordinating gaps shunting the EHV
terminals to earth, or surge diverters connected to incoming lines or station bus bars. Sometimes,
surge diverters are connected also to the generator terminals; the need for installation at this point
largely depends on the relative capacitance of the generator to transformer interconnections
compared with the interwinding capacitance of the transformer. (In case of large cylindrical rotor
generators with two turns in each stator slot, surge capacitors are installed to prevent turn to turn
shorts from switching transients due to the much smaller insulation level between stator turns. Eg.
Valudhur Gas Turbine Generators)
A sustained over voltage condition is taken care by the protective relays (59). Sudden loss
of load should only cause a transient overvoltage while the voltage regulator and governor act to
correct the situation. A maladjusted voltage regulator may change over to manual, maintaining
excitation at the value prior to load loss while the generator supplies little or no load. The terminal
voltage will increase substantially, and in severe cases it would be limited only by the saturation
characteristic of the generator. A rise in speed simply compounds the problem. If load that is
sensitive to overvoltages remains connected, the consequences in terms of equipment damage
and lost revenue can be severe. Prolonged over voltages may also occur on isolated networks, or
ones with weak interconnections, due to the fault conditions.
3. Overvoltage Protection Scheme: (Input >>> Generator VT voltage)
For the above reasons, it is wise to provide power frequency overvoltage protection, in the form of
a timedelayed element, either IDMTL (Inverse Definite Minimum Time Lag) or DTL (Definite Time
Lag) type. The time delay should be long enough to prevent operation during normal regulator
action, and therefore should take account of the type of AVR fitted and its transient response.
Each unit
contributed >>
45 MVAr to unit-5
Impedance Diagram at Loss of Excitation MVAR contribution from Units# 1-3 at the time of Loss
Excitation in unit # 5
Generator at
212 MW & 32 MVAr (lag)
Negative reactance
Dip in voltage
Increase in
current
Increase in leading MVAr
= 0.687 x 247 = 170 MVAr
References:
1. Protective Relays – Application Guide by GEC-Alsthom (GEC Measurements)
2. Modern Power Station Practice Vol.D (British Electricity International, London)
3. IEEE Tutorial on the Protection of Synchronous Generators
4. Protective Relaying Theory and applications by Walter A. Elmore
5. Monitoring and Diagnosis of Turbine-driven Generators by Avelino J. Gonzalez and others.
6. TNEB Power Engineers Hand Book 2002
Total No. of Participants: 25
Protected
object Protected
object
B B
R
R
References:
1. Protective Relays – Application Guide by GEC-Alsthom (GEC Measurements)
2. IEEE Tutorial on the Protection of Synchronous Generators
3. Protective Relaying Theory and applications by Walter A. Elmore
4. TNEB Power Engineers Hand Book 2002
Total No. of Participants: 28