Fire Pumps
Fire Pumps
Fire Pumps
Ras Al Gasabah
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including all NEOM’s guidelines and
procedures, apply to this Section.
1.2 SUMMARY
A. This Section includes electric-drive, centrifugal fire pumps for building fire-
suppression systems and the following:
1.3 DEFINITIONS
A. Fire Pump: Electric-driven fire pump used to supply water at rated capacity and total
head required for fire-suppression service.
B. Fire-Pump Unit: Assembly with fire pump, driver, controller, and related accessories.
C. Split-Case Fire Pump: Axially split-case, centrifugal fire pump with its housing split
parallel to shaft.
C. Seismic Performance: Fire pumps shall withstand the effects of earthquake motions
determined according to ASCE/SEI 7, and SBC 201.
1.5 SUBMITTALS
1. For installed products indicated to comply with design loads, include structural
analysis data signed and sealed by the qualified professional engineer
responsible for their preparation.
2. Wiring Diagrams: Detail wiring for power, signal, and control systems and
differentiate between manufacturer-installed and field-installed wiring.
3. Shop Drawings may be incorporated into other fire-suppression piping systems.
E. Field Test Reports: As specified in "Field Quality Control" Article in Part 3 of this
Section. Indicate and interpret test results for compliance with performance
requirements.
B. Comply with the applicable requirements and recommendations of local Saudi Building
Code (SBC) and the latest applicable local regulations for materials, tests, installation,
and identification, as listed in, but not limited to, the “Saudi Fire Code,” SBC 801, and
the standards listed below in this section; whichever is more stringent.
A. Preparation for Shipping: After assembling and testing fire pumps and pressure
maintenance pumps, protect flanges and exposed machined metal surfaces, pipe
openings, and nozzles.
B. Retain shipping flange protective covers and protective coatings during storage.
C. Protect bearings and couplings against damage from sand, grit, or other foreign matter.
1.8 WARRANTY
D. Warranties stipulations of the contract for the terms of the Contractor's overall
"Warranty of the Works" shall prevail.
A. Furnish extra materials described below, that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
G. Seals: Stuffing box with minimum of four rings of graphite-impregnated braided yarn
and bronze packing gland.
L. Driver:
1. Standard: UL 1004-5.
2. Type: Electric motor; NEMA MG 1, polyphase Design B, totally enclosed, fan
cooled, squirrel-cage, induction motor. Motor shall comply with Division 21
Section “Common Motor Requirements for Fire Suppression Equipment”. Include
construction complying with NFPA 20 and NFPA 70 and include wiring
compatible with controller used.
3. Finish: Manufacturer's standard red paint applied to factory-assembled and -
tested unit before shipping.
M. Volts: 400 V.
N. Phase: Three.
O. Frequency 60 Hz
A. Standard: UL 448.
H. Seals: Stuffing box with minimum of four rings of graphite-impregnated braided yarn
and bronze packing gland.
M. Driver:
1. Standard: UL 1004-5.
2. Type: Electric motor; NEMA MG 1, polyphase Design B, totally enclosed, fan
cooled, squirrel-cage, induction motor. Motor shall comply with Division 21
Section “Common Motor Requirements for Fire Suppression Equipment”. Include
construction complying with NFPA 20 and NFPA 70 and include wiring
compatible with controller used.
3. Finish: Manufacturer's standard red paint applied to factory-assembled and -
tested unit before shipping.
N. Volts: 400 V.
O. Phase: Three.
P. Frequency 60 Hz
A. Description: UL 218 and NFPA 20; listed for electric-drive, fire-pump service.
C. Fire pump controllers shall be provided with surge arresters in compliance with IEEE
C62.1 or IEEE C62.11 and shall be installed in common mode to eliminate overvoltage
between each phase and earth. As an alternative, the controller shall withstand without
any damage 10 kV impulse in accordance with IEEE C62.41 or ANSI/UL 1449.
D. Method of Control:
1. Pressure-switch actuated.
a. Water-pressure-actuated switch and pressure transducer with independent
high-and low-calibrated adjustments responsive to water pressure in fire-
suppression piping.
b. System pressure recorder, electric ac driven, with spring backup.
2. Emergency Start: Mechanically operated start handle that closes and retains
the motor RUN contactor independent of all electric or pressure actuators.
G. Method of Isolation and Overcurrent Protection: Interlocked isolating switch and MCCB
(Molded-case circuit breaker); with a common, externally mounted operating handle,
and providing locked-rotor protection. Fire pump controller circuit breaker settings shall
comply with NFPA 20 requirements. The circuit breaker shall not trip when starting a
motor from rest in the across-the-line mode, whether or not the controller is of the
reduced inrush starting type.
1. Monitor, display, and control the devices, alarms, functions, and operations
listed in NFPA 20 as required for drivers and controller types used.
2. Method of Control and Indication:
a. Microprocessor-based logic controller, with multiline digital readout.
b. Membrane keypad.
c. LED alarm and status indicating lights.
I. Optional Features:
A. Match fire-pump suction and discharge ratings as required for fire-pump capacity
rating and complying with NFPA-20 requirements. Include the following:
A. Description: Factory-assembled and -wired remote panel complying with UL 508 and
requirements in NFPA 20. Include audible and visible alarms matching controller type.
1. Motor-operating condition.
2. Loss-of-line power.
3. Phase reversal.
4. Low-water alarm.
A. Factory Tests: Hydrostatically test and test run fire pumps before shipping according
to UL 448 requirements for "Operation Test" and "Manufacturing and Production
Tests." Test at 150 percent of shutoff head plus suction head, but not less than 1725
kPa (250 psig). Produce certified test curves and inspection reports showing head
capacity and brake horsepower of each pump.
B. Fire pumps will be considered defective if they do not pass tests and inspections.
2.10 GROUT
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine areas, equipment foundations, and conditions, with Installer present, for
compliance with requirements for installation and other conditions affecting fire-pump
performance.
A. Install concrete bases of dimensions indicated, or otherwise required, for fire pumps,
and controllers. Refer to Section "Cast-in-Place Concrete."
3.3 INSTALLATION
A. Comply with fire-pump, relief valves, accessories and controller manufacturers' written
installation and alignment instructions, and with NFPA 20.
B. Install pumps and controllers to provide access for periodic maintenance, including
removal of motors, impellers, couplings, and accessories.
D. Comply with requirements for vibration isolation and seismic control devices specified
in Section 210548 "Vibration and Seismic Controls for Fire-Suppression Piping and
Equipment."
E. Install suction and discharge piping equal to or greater than diameter of fire-pump
nozzles, and as required by NFPA 20.
F. Install valves that are the same size as piping connecting fire pumps, bypasses, test
headers, and other piping systems.
H. Support pumps and piping separately so weight of piping does not rest on pumps.
I. Install piping accessories, hangers and supports, anchors, valves, meters and gages,
and equipment supports according to NFPA 20.
A. Align fire-pump and driver shafts after complete unit has been leveled on foundation,
grout has set, and foundation bolts have been tightened.
B. After alignment is correct, tighten foundation bolts evenly but not too firmly. Fill
baseplate completely with grout, with metal blocks and shims or wedges in place.
Tighten foundation bolts after grout has hardened. Check alignment and make required
corrections.
1. Align pump and driver shafts for angular and parallel alignment according to HI
1.4.
2. Alignment Tolerances: Comply with manufacturer's written instructions.
D. Align vertically mounted, split-case pump and driver shafts after complete unit has been
made plumb on foundation, grout has set, and foundation bolts have been tightened.
Follow pump manufacturer's written instructions.
1. Install piping adjacent to fire pumps and equipment to allow service and
maintenance.
2. Connect fire-pump discharge piping to building fire-suppression piping.
3. Connect relief-valve discharge to point of disposal.
F. Ground equipment.
3.6 IDENTIFICATION
1. Leak Test: After installation, charge system and test for leaks. Repair leaks and
retest until no leaks exist.
2. Check suction line connections for tightness so no air gets into pumps.
3. Operational Test: After electrical circuitry has been energized, start units to
confirm proper motor rotation and unit operation. Remove malfunctioning units,
replace them with new units, and retest.
4. Test and adjust controls and safety. Replace damaged and malfunctioning
controls and equipment.
5. Furnish fire hoses in number, size, and length required to reach storm drain or
other acceptable location to dispose of fire-pump test water. Fire hoses are for
field acceptance tests only and are not property of Employer.
6. Final Checks before Startup: Perform the following preventive-maintenance
operations and checks:
a. Lubricate oil-lubrication-type bearings.
B. Perform field tests for each fire-pump unit and system piping when installation is
complete. Comply with operating instructions and procedures in NFPA 20 to
demonstrate compliance with requirements. Where possible, the field correct
malfunctioning equipment, then retest to demonstrate compliance. Replace equipment
that cannot be satisfactorily corrected or that does not perform as indicated, then retest
to demonstrate compliance. Verify that each fire pump unit performs as indicated.
Report test results in writing.
3.8 DEMONSTRATION
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including all NEOM’s guidelines and
procedures, apply to this Section.
1.2 SUMMARY
A. This Section includes electric-drive, centrifugal fire pumps for building fire-
suppression systems and the following:
C. Field Test Reports: As specified in "Field Quality Control" Article in Part 3 of this
Section. Indicate and interpret test results for compliance with performance
requirements.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
C. Finish: Red paint applied to factory-assembled and -tested unit before shipping.
F. Mounting: Pump and driver shafts are horizontal, with pump and driver on same base.
B. Horsepower Rating: Not less than 110 percent of maximum brake horsepower (after
derating for temperature and elevation according to NFPA 20).
C. Emergency Manual Operator: Factory wired for starting and operating standby engine
in case of malfunction in main controller or wiring.
D. Controls:
1. Adjustable governor.
2. Over-speed shutdown.
3. Manual reset, speed switch.
4. Instrument panel with tachometer, oil pressure gage, water temperature gage,
and hour meter.
E. Fuel System:
F. Exhaust System:
B. Circulation Relief Valves: UL 1478, bronze or cast iron, spring loaded; for installation
in pump-discharge piping.
F. Hose Valves: UL 668, bronze, with outlet threaded according to NFPA 1963 and
matching local fire-department threads.
B. Day Tank: UL 142, freestanding, factory-fabricated fuel tank assembly, with integral,
float-controlled transfer pump and the following features:
C. Base-Mounted Fuel Oil Tank: Factory installed and piped, complying with UL 142 fuel
oil tank. Features include the following:
2.7 GROUT
B. Characteristics: Non shrink and recommended for interior and exterior applications.
A. Testing: Test and inspect fire pumps according to UL 448 requirements for
"Operation Test" and "Manufacturing and Production Tests."
B. Fire pumps will be considered defective if they do not pass tests and inspections.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine equipment bases and anchorage provisions, with Installer present, for
compliance with requirements and for conditions affecting performance of fire pumps.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION
A. Fire-Pump Installation Standard: Comply with NFPA 20 for installation of fire pumps,
relief valves, and related components.
B. Equipment Mounting:
D. Install fire-pump suction and discharge piping equal to or larger than sizes required
by NFPA 20.
E. Support piping and pumps separately, so weight of piping does not rest on pumps.
H. Install piping hangers and supports, anchors, valves, gages, and equipment supports
according to NFPA 20.
J. Install water supply and drain piping for diesel-engine heat exchangers. Extend drain
piping from heat exchangers to point of disposal.
K. Install exhaust-system piping for diesel engines. Extend to point of termination outside
structure. Install pipe and fittings with welded joints; install components having flanged
connections with gasketed joints.
N. Wiring Method: Conceal conductors and cables in accessible ceilings, walls, and
floors where possible.
3.3 ALIGNMENT
A. Align split-case pump and driver shafts after complete unit has been leveled on
concrete base, grout has set, and anchor bolts have been tightened.
B. After alignment is correct, tighten anchor bolts evenly. Fill baseplate completely with
grout, with metal blocks and shims or wedges in place. Tighten anchor bolts after grout
has hardened. Check alignment and make required corrections.
D. Align pump and driver shafts for angular and parallel alignment according to HI 1.4
and to tolerances specified by manufacturer.
3.4 CONNECTIONS
A. Install piping adjacent to pumps and equipment to allow service and maintenance.
3.5 IDENTIFICATION
3.7 DEMONSTRATION
PART 1 - GENERAL
1.2 SUMMARY
A. Section Includes:
1.3 DEFINITIONS
B. Controller shall comply with UL 508 factory assembled, wired, and tested across-the-
line for combined automatic and manual operation
C. Pump Equipment, Accessory, and Specialty Pressure Rating: 175 psig (1200 kPa)
minimum unless higher pressure rating is indicated.
D. Seismic Performance: Fire pumps shall withstand the effects of earthquake motions
determined according to ASCE/SEI 7, and SBC 201.
a. The term "withstand" means "the unit will remain in place without separation
of any parts from the device when subjected to the seismic forces specified
and the unit will be fully operational after the seismic event."
A. Product Data: For each type of product indicated. Include rated capacities, operating
characteristics, performance curves, electrical characteristics, and furnished
specialties and accessories
B. Shop Drawings: For pumps, accessories, and specialties. Include plans, elevations,
sections, details, and attachments to other work.
B. Comply with the applicable requirements and recommendations of local Saudi Building
Code (SBC) and the latest applicable local regulations for materials, tests, installation,
and identification, as listed in, but not limited to, the “Saudi Fire Code”, SBC 801, and
the standards listed below in this section; whichever is more stringent.
H. Comply with NFPA 20, "Installation of Stationary Pumps for Fire Protection," for
pressure maintenance pumps, drivers, controllers, accessories, and installation.
1.7 COORDINATION
A. Coordinate sizes and locations of concrete bases with actual equipment provided.
B. Retain shipping flange protective covers and protective coatings during storage.
C. Protect bearings and couplings against damage from sand, grit, or other foreign matter.
1.9 WARRANTY
D. Warranties stipulations of the contract for the terms of the Contractor's overall
"Warranty of the Works" shall prevail.
A. Furnish extra materials described below, that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
2.1 MANUFACTURERS
B. Pump Construction:
C. Motor: Single speed with permanently lubricated ball bearings and rigidly mounted to
pump head. Comply with requirements in Division 21 Section "Common Motor
Requirements for Fire Suppression Equipment."
A. Comply with NEMA designation, temperature rating, service factor, enclosure type, and
efficiency requirements for motors specified in Division 21 Section "Common Motor
Requirements for Fire Suppression Equipment."
2.6 GROUT
PART 3 - EXECUTION
3.3 ADJUSTING