LCD Alarm Manual
LCD Alarm Manual
LCD Alarm Manual
Installation and
Maintenance
Manual
Alarm Systems
Contents
Features & Benefits ---------------------- 2 Master point NFPA labels --------------- 24
Introduction ------------------------------- 4 Repeater Delay---------------------------- 25
Major components------------------------ 5 Units of Measure-------------------------- 25
Alarm Panel Installation------------- 6 Digital Calibration ------------------------ 25
Rough-In Box Installation --------------- 6 Com ID------------------------------------- 25
Wiring/AC--------------------------------- 7 Gas Service -------------------------------- 26
Plumbing the riser extension tubes ----- 8 Language & Latching/Non-Latching--- 26
Installing the hinges ---------------------- 9 View Screen ------------------------------- 26
Installing the alarm front panel --------- 9 Text & E Text Gas (Area) --------------- 27
Wiring alarm front panel ---------------- 10 Text & E Text Master (dry contacts) --- 28
Installing the transducers (not remote) - 10 4-20mA Master Module ------------------ 28
Installing the transducers (remote) ----- 11 Ethernet/rabbit ---------------------------- 29
Connecting transducer wiring ----------- 12 Create Receive Connector------------- 30-32
Wiring remote devices (dry contacts) -- 13 Programming the Ethernet/Rabbit Board 32-
Wiring remote devices (transducers) --- 14 34
Wiring remote devices (4-20mA)------- 15 E mail text notifications --------------- 35-36
Wiring general fault (dry contacts) ----- 16 Rabbit board programing commands 37
Power on----------------------------------- 17 Modbus interface ----------------------- 38
Alarm Displays & Functions-------- 18 Website ---------------------------------- 38-39
Button module displays & functions --- 18 BACnet interface----------------------- 40-44
Gas (Area) module ----------------------- 19 Appendix A Glossary of Terms ------------- 45
Alarm conditions ------------------------- 19 Appendix B Specifications ------------------- 46
Emergency instructions (gas module)-- 19 Appendix C Master Signal wire log ------- 47
Master module (dry contacts) ----------- 20 Appendix D Master Alarm Signal listing - 48
Emergency instructions Appendix E Wiring Diagram (AC and DC)
(master modules) ------------------------- 20 Standard Area or Master Alarm ------------ 49
Master module (transducer inputs) ----- 20 Appendix F Wiring Diagram
Master module (4 – 20 mA input) ------ 20 Area Alarm Remote Transducers ------------ 50
Alarm Operation ---------------------- 21 Appendix G Wiring Diagram
Silencing the alarm----------------------- 21 (Master Equipment) --------------------------- 51
Repeater Delay---------------------------- 21 Appendix H Wiring Diagram
Testing the alarm ------------------------- -21 (Master Remote Transducer) ----------------- 52
Gas (Area) modules ---------------------- 21 Appendix I Wiring Diagram
Master module (dry contacts) ----------- 21 Master 4-20mA Signals ----------------------- 53
Master module (transducer inputs) ----- 22 Appendix J Wiring Diagram
Master module (4 – 20 mA input) ------ 22 Ethernet Communication ---------------------- 54
Ethernet module -------------------------- 22 Appendix K Wiring Diagram (AC and DC)
BACnet gateway module ---------------- 22 BACnet ------------------------------------------ 55
Programming the Alarm ----------- 23 Appendix L Wiring Diagram
Accessing the Program Mode ----------- 23 BACnet Communication ---------------------- 56
High & Low Alarm Pressure set points 24 Appendix M Text Message Carriers -------- 57-
61
Appendix N Ethernet/Rabbit Board
Programming Log ------------------------------ 62
3
Alarm Systems
Introduction
This manual covers the installation and operation of the “T” series of Med Touch Alarm Systems. It applies to
three different back boxes and front panel sizes that are described as 2 slot, 3 slot, and 5 slot. These panels can
have a maximum of 4 modules in a 2 slot alarm, 8 modules in a 3 slot alarm, or 16 modules in a 5 slot alarm. Refer
to our Submittal Data Sheet 99-0488 for Master Alarms, 99-0489 for Area Alarms and 99-0490 for Combination
Alarms for details on the physical size and module options in each of these Alarm Systems. These can be found on
our website at pattonsmedical.com and look under Pipeline Products to find the type of Med Touch Alarm Submit-
tal Data (Specification) sheet needed.
The LCD Medical gas alarm system monitors the status of the medical gas distribution system and provides audi-
ble and visual indicators. The master alarm can be furnished with either Modbus or BACnet building management
interface circuit board(s) to communicate status information to the building management system. Any type of
alarm may be equipped with an optional Ethernet board which will; launch a website, send text notifications to five
addresses, maintain a rolling history / event log of 100 recent events and a file of 1,000 events, and provide a Mod-
bus interface. A BACnet interface option may be added to any master alarm with the Ethernet
option. The Medical alarm system monitors the status of the medical gas sources in accordance
with NFPA 99 and CSA Z7396.1.
The Medical gas alarm system is an assembly comprised of a rough-in box, a front panel and
transducers (if it is an area, combination or transducer master alarm).
Rough-in box
The rough-in box houses the power supply, fuse, on/off switch, and a terminal strip for electri-
cal wiring. An isolated transformer reduces the 110V or 220V AC input to low voltage DC.
Front panel
The front panel includes enclosed printed circuit boards with programming circuitry.
The Push Button module includes a power on indicator, quick view information buttons, the
silence button and an audible alarm.
The Remote Signal dry contacts module(s) can monitor up to 8 signals per circuit board. Mul-
tiple remote signal modules can be ordered in a single alarm which would be in communication
with dry contact sensors. The signals can be configured to display an abnormal condition on either
a normally closed (NC) or a normally open (NO) circuit. Each signal may also be turned off if it is
not being utilized.
The Remote Signal transducer contacts module(s) can monitor up to 8 signals from 4 transduc-
ers per circuit board. Multiple remote signal modules can be ordered in a single alarm which
would be in communication with transducer sensors. The signals can be configured to display an
abnormal condition on either a normally closed (NC) or a normally open (NO) circuit. Each signal
may also be turned off if it is not being utilized. The benefits of transducers over dry contacts are:
improved safety (an alarm is immediately triggered when a transducer fails), greater accuracy / re-
peatability, ease of setting (push button vs mechanical adjustment) and lower cost in most cases.
The Remote Signal 4–20 mA contacts module monitors a single 4–20 mA transmitter. The user is
able to program and name the units of measure represented by the bar graph generated by the mod-
ule. The user is also able to set the high and low alarm set points
The Gas (Area) module(s) on the front panel are identified with gas specific, color coding (per
NFPA 99 or CSA Z7396.1). The display shows the actual gas pressure along with an indication of
the pressure being within the Normal, High or Low pressure range. The gas pressure may be dis-
played in PSI, In Hg, BAR or kPa. The unit is pre-programmed to display PSI / In Hg from the fac-
tory, but may be re-programmed in the field to display BAR or kPa. In addition the display will
indicate System and Program failures. Each module is supplied with dry contacts for remote signal-
ing of high and low pipeline pressure.
4
Alarm Systems
Transducers
The transducer converts pressure to an electrical signal and supplies the electrical signal to the alarm Gas and/or
Remote signal transducer modules. After the initial 24 hour 150 psi standing pres-
sure test (required per NFPA 99) has been completed the pressure/vacuum trans-
ducers may be connected to the medical gas pipeline. The transducers may be remotely
attached to the piping system at distances up to 5,000 feet using standard 18 gauge
stranded twisted pair wire. Patton’s Medical recommends mounting the transducers in
the zone appropriate zone valve box (utilizing the E Z Backfeed™ and E Z Find™
features) or in the alarm back box. Should a transducer require service or replacement it is considerably more of a
safety issue and more time consuming to locate and replace transducers which have been remotely located above
the ceiling and eliminates contamination issues – such as having to set up a tent in order to remove ceiling tiles.
Risers
DISS x ½ O.D. tube gas specific risers with our Frontall™ front loaded check valve
are provided for each gas service corresponding to the gas boards ordered in an area or
combination alarm. The risers may be installed in the alarm back box or remotely on
the pipeline.
Transducers Risers
5
Alarm Systems
Alarm Installation
Installation of the Pattons Medical alarm involves installing the rough-in box, the risers & the transducers (if it is
an area alarm or combination alarm) and front panel and making the necessary conduit, plumbing and electrical
connections. All installation and testing should be done in accordance with NFPA 99 or CSA Z7396.1.
WARNING: Electrical power intended for the alarm to be installed should be disconnected prior to installation.
WARNING: This device should only be installed by qualified personnel. Installation should not be attempted by
anyone not having general experience with the installation of devices of this nature.
Wiring
Field Ground
7
Alarm Systems
Note: It is recommended that gas piping system tubing be connected from the riser extension tube to the ceiling
for a future or blank gas display even though a transducer is not being installed. Cap the unused tube above the
ceiling. This will simplify future expansion. AU89xx series riser extension tubes are sold separately.
Note: It is also possible to install the transducers remotely (not in the alarm box). In this type of installation the
risers are connected to the gas piping system up to 5,000 feet away from the alarm panel.
Note: Pattons Medical recommends mounting the transducers either in the zone valve box (remote) in conjunction
with the E Z Backfeed™ and E Z Find™ products or in the alarm back box – not remotely above the ceiling.
Should a transducer require service, testing or replacement it is considerably more time consuming to locate and
replace or service transducers remotely located above the ceiling.
8
Alarm Systems
9
Alarm Systems
10
Alarm Systems
11
Alarm Systems
12
Alarm Systems
Wiring the Remote Devices to Remote Signal Master Board (dry contacts)
13
Alarm Systems
Wiring the Remote Devices to Remote Signal Master Board (transducer sen-
sors)
14
Alarm Systems
Wiring the Remote Devices to Remote Signal Master Board (4-20mA transmitters)
15
Alarm Systems
Wiring general fault dry contacts to building automation system or remote alarm
16
Alarm Systems
17
Alarm Systems
Alarm Silence
In the event of an alarm condition an audible alarm Power on Indicator Test button
sounds. The audible alarm can be silenced by
pressing the alarm silence button. The alarm will
alternate displaying the rooms/area monitored with ▲ (up arrow)
the emergency instructions until the alarm condi- The up arrow may be pressed & held at any time to
tion is rectified. Depressing the silence button will display the high line pressure alarm set points of the
silence the alarm for approximately 10 minutes gas module (area) boards, the remote signal trans-
(factory setting). After approximately 10 minutes, ducer boards and the 4 – 20mA boards.
the audible alarm will sound again. (See alarm op-
eration section on page 21 for more detail). ▼ (down arrow)
The down arrow may be pressed & held at any
View Last Event Alarm History Button time to display the low line pressure alarm set
The Last Event History button may be pressed and points of the gas module (area) boards, the remote
held at any time to view last event alarm history. signal transducer boards and the 4 – 20mA
Viewing alarm history is only active while the Last boards .
Event History button is pressed, releasing the but-
ton returns the alarm to normal operation. Pressing ► (right arrow)
the Last Event History Button will display the fol- The right arrow may be pressed & held at any time
lowing: to display the gas service for which the gas mod-
ules (area) boards are currently programmed. (See
Gas (Area) and Remote Signal Transducer Mod- list on page 26).
ules - The High and/or Low Pressure indication
will be displayed along with the actual highest or ◄ (left arrow)
lowest pressure which occurred. The left arrow may be pressed & held at any time
to display the type of transducer that is connected
Remote Signal (Master) Module – If there was an to each gas module (area) board. The 3 types are 0
alarm condition for any Remote Signal the Red – 30 In Hg, 0 – 100 psig and 0 – 250 psig. When
LCD will be illuminated. All other LCD’s will be the left arrow is pressed “30” will be displayed for
off. a 0 – 30 In Hg transducer, “100” will be displayed
for a 0 – 100 psig transducer and “250” will be
4–20 mA Module - The High and/or Low value displayed for a 0 – 250 psig transducer.
indication will be displayed along with the actual
highest or lowest value which occurred
18
Alarm Systems
19
Alarm Systems
Alarm signal #1
Alarm signal #2
Master (dry contact) modules will provide up to 8 Emergency instructions may also be input (by the user)
alarm signals when used in communication with dry for each of the signal points. The normal display will
contact sensors. For each signal point a ‘label’ must appear and react just like a conventional remote signal
be selected from a pre-loaded database of NFPA 99 master dry contact display (shown on the left side of this
master alarm signals. You also have the option of page), but a touch of the display will change the display
creating your own ‘label’. Emergency instructions (for 30 seconds) to look and react similar to an area
may also be input (by the user) for each of the sig- alarm gas display (photo above). The advantages of us-
nal points. The master boards are pre-programmed ing transducers over pressure switches are;
with all signal points programmed NC (normally • Digital display of actual gas pressure
closed). There is an alarm condition indicator for • Greater accuracy / repeatability
each signal point. The alarm condition indicator will • Improved safety (an alarm condition notification is
be green when the signal is in a normal state and red created immediately should a transducer fail)
when in an alarm state. When an alarm condition • Easy / fast push button re-setting of alarm set points
occurs in addition to the condition indicator turning • Lower cost (in most cases)
red, the signal will flash on and off and the emer-
gency instructions will alternate being displayed Master 4 – 20 mA Remote Signal
with the alarm signal label. Monitors the status of a source of the medical gas distri-
bution system (i.e. – liquid level of bulk oxygen) in com-
Emergency Text munication with one 4 – 20 mA signal transmitter and
(displays in red) displays a bar graph with user defined units, provides
high & low alarms with user defined set-points and pro-
vides the emergency instructions (programmed by the
user). Other applications may include monitoring flow
rates, levels, concentrations, humidity, etc.
Scale Reading
User entered Equipment Name
Alarm Operation
This section deals with the daily operational aspects of the alarm panel. After installation has been completed
and the final user programming of the panel has been properly configured, it is ready for operation.
21
Alarm Systems
Ethernet Module
This optional module may be added to any alarm
panel. It will provide the following features:
• Webserver – allows a remote user access to the
alarm’s web page – viewing a graphic image of the
alarm with all signal conditions, pressure and event /
history log information
• Text notification of alarm conditions (up to 5
addresses)
• Event / history log – maintains a rolling list of
the 100 most recent alarm condition events
and a file of the 1,000 most recent alarm
conditions
• Modbus interface
22
Alarm Systems
Programming the Alarm
This section covers the procedures to follow in order to configure a module with site specific information such as;
master alarm signals, room / area coverage information, or emergency preparedness instructions. The Program-
ming The Alarm section is also used when adding or deleted a module to an alarm panel.
The alarm has been programmed at the factory prior Accessing the Alarm Program Mode
to shipment. Programming of the alarm may be neces- To program the alarm, the circuit boards must be placed
sary if: individually, one at a time in the program mode. To place
• a) the high or low pressure limits for a gas a circuit board in the programming mode, simply touch
need to be modified the board to be programmed (once for all other panels and
• b) to identify the rooms or area covered twice for a remote signal transducer input board) until you
• c) to provide custom user emergency response see this security screen:
instructions with each area gas and with each All alarm panels have been pre-
master signal point programmed to allow access with
• d) if a gas service is being changed the pin # 0711. Type in 0711 and
• e) if a remote signal alarm point needs to be re- touch Enter. You will have 30
configured or de-activated seconds to make selections when
• f) if a remote signal module is being added in programming. After 30 seconds
the place of a blank module of no key touch, the display will
• g) if the Com ID number needs to be changed return to its standard view and
• h) you wish to change the repeater delay time any information which has not
• i) you wish to change the units of measure from been saved will be lost.
psig and In Hg to either BAR or kPa
• j) you wish to have master remote signal alarm The next screen which will ap-
notifications repeat pear is the function options.
• k) you wish to have alarm notifications There are eleven different func-
‘latched’ (requiring manual acknowledge- tion options. Simply touch the
ment by pressing the Silence button to clear icon representing the function
an alarm after the source of the alarm initia- you wish to program. The fol-
tion has been rectified lowing table provides a brief
description of each function:
Note: Only authorized personnel should program
the alarm! It is important to note that while the panel
being programmed is in the program mode, it is not
monitoring the medical gas system and alarm condi-
tions will not trigger an alarm. Function Description
High Set high alarm set point
Low Set low alarm set point
Gas Set gas service
Repeat Set repeater delay (in minutes)
Cal Change calibration of pressure reading
Units Change units of measure
ComID Change Com ID number
Text Input room / area and emergency instruc-
tions & master alarm signal selection
menu
23
Alarm Systems
Re-Programming the Remote Signal (Master)
Programming the High & Low Alarm Pressure set
Alarm Points (NO or Disable)
points
After placing the board in the
After placing the board in the
program mode and touching the
program mode and touching
Input function icon, the remote
the High function icon, the
signal input screen (shown here)
high line pressure set point and
is displayed. The input number
programming keypad is dis-
displayed on the top line of the
played. The currently pro-
white box corresponds to the
grammed high pressure alarm
signal being programmed. You
set point is displayed in the
may toggle to the next or previ-
white box in the top left corner.
ous signal by using the double
If the gas module being pro-
arrow buttons in the bottom row. The master boards
grammed is a typical 50 psig
are pre-programmed with all signal points pro-
delivery pressure, the board has been pre-programmed
grammed NC (normally closed) in compliance with
at the factory with the high line pressure set point at 60
NFPA 99. You may re-program each individual signal
psig, so the display should show the number 60. If you
as NO (normally open) or you may Disable each indi-
wish to change this setting, simply
vidual signal point by touching the NO or Disable
• type in the new High pressure
button. You may re-program all of the signal points
• touch Enter,
(up to 8) before
• on the next screen touch Back
• touching the OK button
• on the next screen touch Save to adjust the pres-
• on the next screen touch Back
sure setting.
• on the next screen touch Save.
After placing the board in the program mode and touch-
Programming the Remote Signal (Master) Alarm
ing the Low function icon, the low line pressure set
Points – NFPA alarm menu
point and programming keypad
is displayed. The currently
programmed low pressure
alarm set point is displayed in
the white box in the top left
corner. If the gas module being
programmed is a typical 50
psig delivery pressure, the
board has been pre-
programmed at the factory
with the low line pressure set
point at 40 psig, so the display
After placing the board in the program mode and
should show the number 40. If you wish to change this
touching the Text function icon (see left display
setting, simply
above), the remote signal input screen (right above) is
• type in the new Low pressure
displayed. The input number displayed on the top of
• touch Enter
the second white box corresponds to the signal being
• on the next screen touch Back
programmed. You may toggle to the next or previous
• on the next screen touch Save to adjust the pres-
signal by using the Down or Up buttons. When you
sure setting.
are on the label number that you wish to program, use
the double arrow buttons in the bottom row to toggle
Note: The alarm is designed with a safety feature so
thru the database of NFPA 99 master alarm signals.
that the high and low set points must be at least 1 (psig /
The sequence of the master alarm signals is per Ap-
in Hg), 1 (bar) or 1 (kPa) increments apart. The high set
pendix D. You may program all of the signal points
point will not be able to be set below the low set point
(up to 8) before
and vice versa.
• touching the OK button
• on the next screen touch Back
• on the next screen touch Save.
24
Alarm Systems
Programming the Repeater Delay
After placing the board in the program mode and touch-
After placing the board in the program mode and ing the CAL function icon, the calibration input screen
touching the Repeat function (shown here) is displayed. The alarm panel has been cali-
icon, the remote signal input brated and programmed and does not ever require recali-
screen (shown here) is dis- bration. If you wish to slightly change the calibration
played. The current repeater (usually to match another alarm panel in immediate area)
delay programmed is dis- you may. The number displayed in the white box at the
played in the white box at top of the display is the current pressure reading.
the top. In the example Simply
shown here, Rp 10 means • touch the Down or the Up button until you achieve
the repeater delay is pro- the pressure reading desired
grammed for 10 minutes. • touch OK
Entering zero will disable • on the next screen touch Back
the repeater. Use the keypad • on the next screen touch Save
to type in the number of minutes you would like
(maximum is 240),
• then touch Enter
Programming the Board Com ID
• on the next screen touch Back
• on the next screen touch Save Note: This feature is used when the alarm is used in con-
junction with the optional Ethernet module or as a com-
ponent in a wireless master panel.
Programming the Units of Measure
After placing the board in the Note: When used in conjunction with the Ethernet mod-
program mode and touching ule, each circuit board must have a sequential Identifica-
the Units function icon, the tion Number from 1 to 16 based on its position in the
units input screen (shown alarm panel. 1 thru 4 would be from the top of the second
here) is displayed. The alarm slot to the bottom of the second slot. 5 – 8 would be from
panel has been pre- the top of the third slot to the bottom of the third slot, etc.
programmed with the units
desired based on the part Note: When used as a component in a wireless master.
number which was ordered. Each 8 remote signal dry contact circuit board must have
The positive gas service op- a UNIQUE sequential Identification Number from 1 to 8
tions are; PSI, kPa and BAR. based on its position in the alarm panel. For additional
The negative gas service options are; inHg and information see the Pattons Medical Wireless Master
mmHg. Simply Alarm literature.
• touch the button you would like to re-program the
units After placing the board in the program mode and touch-
• then touch Enter ing the COMID function icon, the remote signal input
• on the next screen touch Back screen (shown here) is displayed.
• on the next screen touch Save The current Com ID # pro-
grammed is displayed in the
Adjusting the Digital Pressure Calibration white box at the top. Entering
zero will disable the Com ID for
The digital line pressure may this board. Use the keypad to;
be adjusted slightly (per the • type in the Com ID number
chart below) by following you would like
the simple procedure below. • then touch Enter
This can be done by one per- • on the next screen touch
son at the alarm panel – no Back
need to open/adjust the • on the next screen touch
transducers! Save.
Range of adjustment:
VAC or EVAC /WAGD ± 1
inHg
100 psig transducers ± 3 PSI
250 psig transducers ± 5 PSI
25
Alarm Systems
Programming the Gas Service (area alarm) screen. The first line provides the software version.
The Cal value represents any re-programmed change
After placing the board in from the factory calibration. The High and Low Limit
the program mode and values are the high and low pressure alarm set points.
touching the GAS function The Units value is the units of measure. The Repeat
icon, the gas input screen value is the number of minutes in which an alarm will
(shown here) is displayed. be repeated after it has been silenced but remaining in
The alarm panel has been an alarm condition. The Gas Type number is a code
pre-programmed with the (see table below) which corresponds to the gas ser-
gas service desired based on vice which has been programmed for the board. The
the part number which was Com ID number is the communication ID number
ordered. To select a different which has been programmed for the board. The Lan-
gas service use the double guage Set is an abbreviation for the label set which
arrow left or right buttons to has been programmed for the board. The Alarm Logic
scroll thru the database of gas services until you find is the latching or non-latching software which has
the one you need been programmed for the board. MSG 1 are the
• then touch Enter rooms or area(s) covered by the alarm. MSG 2 are the
• on the next screen touch Back emergency instructions programmed for the board.
• on the next screen touch Save
The gas boards are pre-programmed for a specific gas
Programming language and latching or non- service from the factory. After placing a gas board in
latching alarm relays the program mode, it is possible to change the gas
After placing the board in service of the board. It is an NFPA 99 requirement
the program mode and that the transducer gas service match the gas service
touching the Set function of the gas board to which it is connected. The follow-
icon, the sets input screen ing list cross references the number that is actually
(shown here) is displayed. displayed on the gas board numeric display with the
The alarm panel has been full names of the gases:
pre-programmed with the
language desired based on Gas # Gas service Transducer
the part number which was displayed type
ordered. Choose a different
language set by simply 12 Nitrogen 250
touching the button you 24 Oxygen 100
would like. Your selection will take you immediately
to the next screen on which you should touch Back 04 Nitrous oxide 100
and on the next screen touch Save. You will need to 08 CO2 or CO2-O2 mix 100
re-enter the program mode and again select the Set
function icon to choose Latching (LATCH) or Non- 22 Medical Vacuum 30
Latching (NLATCH) software. Your selection will 32 Wagd / AGSS 30
take you immediately to the next screen on which you
should touch Back and on the next screen touch Save. 16 Medical air 100
View screen 06 Helium or Heliox 100
After placing the board in
the program mode and H16 Instrument air 250
touching the VIEW function H24 Hyperbaric oxygen 100
icon, the view screen
(shown here) is displayed. H08 Medium pressure carbon 100
The view screen provides a dioxide
summary view of all of the
SP Gas mixture 100
programming for the circuit
board. It does not provide HSP High Pressure gas mix 250
any programming options. It
3SP Tri-Gas 100
is simply a view only
26
Alarm Systems
Programming Text and E Text (gas / area E Text instructions are entered in the same method as
alarm & transducer master boards) described above. Note that E Text instructions will
appear in red and will be displayed alternately with the
After placing the board in the normal display screen only when the board is in an
program mode and touching the alarm condition.
Text function icon, the text in-
put screen (shown here) is dis-
played. To enter text such as the
room(s) or area(s) monitored by
the alarm panel, touch the Text
button. To enter emergency
instruction text, touch the EText
button. The two white areas
represent a top and bottom line
of text which will be displayed at the bottom of the gas
board or transducer master board display. Touch the
top white area to enter the top
line of text or the bottom white
area to enter the bottom line of Programming E Text (master boards with dry
text. Use the character keypad contacts)
(shown here) to enter the text
message you would like dis- After placing the board in the
played. Note: each text display program mode and touching
line is limited to 20 total char- the Text function icon, the
acters or spaces. When fin- Alarm Label / E Text input
ished touch Enter, on the next screen (top photo) is displayed.
screen touch OK, on the next
screen touch Back and on the To enter emergency instruction
next screen touch Save. text touch the EText button, the
screen shown (second photo)
will appear. The two white
Below are examples of a completed Text display areas represent a top and bot-
screen and how it appears as displayed as part of the tom line of text which will be
gas or transducer master display. When an alarm oc- displayed at the bottom of the
curs the emergency instructions will appear alternately master board display. Touch the
with the normal information label Note: the text will top white area to enter the top
automatically be centered. line of text or the bottom white
area to enter the bottom line of
text.
27
Alarm Systems
Below are examples of a completed Text display The HIGH and LOW icons are used to set the respec-
screen and how it appears as displayed as part of the tive numeric values that will trigger these alarms
master board display. When an alarm occurs the E based on the units that are selected.
Text emergency instructions will appear alternately
with the normal alarm signal label. Note: the text will Programming the equipment Name or Units of
automatically be centered. measure;
28
Alarm Systems
Installing the Ethernet/ Rabbit boards
CAUTION: The Ethernet/ Rabbit boards should only Integrating the Ethernet/ Rabbit boards into a net-
be installed after all wall construction and finishing is work
completed to prevent ingress of dust and debris. This
contamination can adversely affect their proper func- To integrate the Ethernet/ Rabbit boards into your facil-
tion. ities network and allow communication to the internet,
various setting must be checked and/or changed in the
The Ethernet/rabbit board networks Router and Server. Refer to the check list
module (photo at right) may below for configuring your network.
be ordered initially as part
of the alarm or added later Note: networking options only work when used with
as a simple retro-fit assem- manufactured supported software systems (currently)
bly. To install the Ethernet Windows 7 or newer.
kit, follow the installation
instructions included with 1. Configure Router Port
the kit. Refer to Appendix J The port on the router, that the Ethernet cable from the
for proper Ethernet and Rabbit board will be plugged into, must be configured
Ribbon cable connections. for half duplex. Most routers will auto set for this how-
ever if you experience communication difficulties, the
Always turn the power off router port setting should be checked.
to the alarm panel before
making any electrical con- 2. Check the Local Network Settings on your Server
nections or disconnections. The E-mail server in the rabbit board resides
on port 587. Your server gateway IP address
needs to be assigned to port 587 and the IP
address of each rabbit board added as a remote
server. See pages 30-32 for an example of how
to do this. Note: The IP address of the Rabbit
board is defaulted to 192.168.0.99 as shipped.
The IP address must be unique for each Rabbit
board and may need to be changed to be com-
patible with your network. The IP address in
the Rabbit board can be changed during step 3.
5. Website Access
If multiple alarm panels are to be viewed as
websites from outside the facility, a reverse
proxy server needs to be set up in the facility
with each alarm panel having a unique name
i.e. westwing.pattonsmedical.com etc. See
page 38 for more information.
29
Alarm Systems
Create Receive Connector – Exchange 2007/2010
“SMTP” (Simple Mail Transfer Protocol) is one of the most common ways of sending e-mail. SMTP is a simple
text conversation across a TCP/IP connection. The Email Server resides on port 587, and so, that is what the rabbit
board SMTP _ PORT is currently defined.
30
Alarm Systems
31
Alarm Systems
Programming the Ethernet/Rabbit boards (e Always turn the power off to the alarm panel before
mail/text messages, accessing alarm website, inter- making any electrical connections or disconnections.
face Modbus with building automation system & Warning: Uncoupling the rabbit board from the
access event log). NOTES: Networking options Ethernet board (red and green boards in photo be-
only work when used with manufacturer support- low) will result in loss of all of the programming.
ed software systems (currently Windows 7 or After the Ethernet kit is installed in the alarm panel
newer). System router ports must be configured and the Real Term: Serial Capture Program soft-
for ‘half duplex’. ware is installed on a laptop and the 35-3033 rabbit
board programming kit is connected properly, you are
To program the rabbit board, you will need to down- ready to begin.
load Real Term: Serial Capture Program.
This is a free software download available on the
internet. You will want to install the Real Term soft-
ware on a laptop so that you have the mobility to
bring the laptop close to the alarm panel. You will
also need a 35-3033 rabbit board programming kit.
Note: If your operating system doesn’t pull in the
driver for the 35-5069 cable, you must download
the driver from the website.
http://www.ftdchip.com/Drivers/VCP.htm
32
Alarm Systems
Launch the Real Term: Serial Capture Program. The set-up screen should look like this. Under the Display Tab
check the Half Duplex Box.
33
Alarm Systems
PPN (program panel name) – this command programs the name of the alarm panel as it will be displayed on the
website and recorded in the event log. In the example below, we have named the alarm panel West Wing.
PDT (program date/time) – this command programs the date and time as it will be displayed on the website and
recorded in the event log.
PIP (program panel IP) – this command programs the rabbit board’s IP address
34
Alarm Systems
To set up users to receive e-mail or text notifications when alarm conditions occur, the following 4 commands
must be completed:
PMI (program SMTP mail server IP) – this command establishes the mail server IP address.
PUN (program user name) – this command establishes the SMTP user name. In the example below, we have used
TRI-Tech@ wolfcreekmicro.com.
PUP (program user password) – this command programs the SMTP password. In the example below, we have
used Foastt29. (Case Sensitive)
PCx (program contact) – this command is used to program a contact to be notified where x is the contact number.
The contact number(s) will be displayed on the event log. Up to five contacts may be programmed. See Appendix
M for Text Message carriers access information.
35
Alarm Systems
To set up communication through the facilities network server with the internet, the Program Gateway must be
used.
PGW (program gateway) – this command establishes communication from the alarm rabbit board through the fa-
cilities network server to the internet.
Below is an illustration of a simplified typical managed network at a facility. Both the rabbit boards IP address and
network gateway IP address must be programmed into the rabbit board of any alarm panel desired to be connected
to the internet.
Area Alarm
Area Alarm Area Alarm
Server
Hub or Switch
Master Alarm
Network Router
Computer
Master Alarm
36
Alarm Systems
The following additional commands are available for reviewing and testing:
SCx (show contact) – this command is used to verify the contact entry. For example - SC2 would display the con-
tact entry for user #2.
MCx (test command) – this command is used to verify that a contact and e mail server is set up correctly. It sends
a test e mail to that contact.
All commands are issued from the command prompt over the serial port. Set the PC's serial port to 9600 8N1.
Boot the rabbit board.
SCx // SHOW CONTACT where x is contact number 1-5. Usage: SC1 will show email contact 1 of 5.
PPN // PROGRAM PANEL NAME. Usage: PPNMyPanel will set the Panel Name to MyPanel.
PMB // PROGRAM MODBUS ID. Usage: PMB01 will set the Modbus ID to 1.
PDT // PROGRAM DATE/TIME. Usage: PDT0129160842 will set RTC to Jan 29th, 2016 at 8:42am.
PDT0203162042 will set rtc to Feb 3rd, 2016 at 8:42pm.
PIP // PROGRAM IP. Usage: PIP192.168.0.50 will set the rabbit board IP address to 192.168.0.50
PGW // PROGRAM GATEWAY. Usage: PGW192.168.0.1 will set the gateway IP address to 192.168.0.1
PMI // PROGRAM SMTP MAIL SERVER IP. Usage: PMI192.168.0.50 will set the SMTP mail server to
192.168.0.50 PMI will clear the SMTP mail server.
PUN // PROGRAM USER NAME. Usage:PUNMyUserName will set the SMTP user name to MyUserName
PUN will clear the user name.
PUP // PROGRAM USER PASSWORD. Usage:PUPMyPassword will set the SMTP password to MyPassword,
(Case Sensitive) PUN will clear the password.
PCx // PRGRAM CONTACT where x is contact number 1-5. Usage: [email protected] will set contact 1 to
[email protected] PC1 will delete the contact.
MCx // MAIL CONTACT where x is contact number 1-5. Usage: MC1 will send contact 1 a test email.
37
Alarm Systems
Modbus Interface-
The command list on the previous page includes commands for Modbus ID and Gateway IP programming. The
only setup needed to run Modbus is the Modbus ID. The Gateway IP address is used for getting messages out of
the local area network. This is typically a router on the LAN.
An example Modmap is shown on page 44. The Read Scan Lines are generated automatically by the Ethernet /
Rabbit board and will match the configuration of the alarm panel. Individual informational items may be selected
from the complete Modbus map to be communicated to the building management system or to the BACnet module
for use on the building automation system.
See page 43 for an example of the complete Modbus map.
If it is desired to communicate with the building management system using Modbus only (not BACnet) – then only
the Ethernet module is required.
Website Access–
Web access to the overview and alarm log pages can be done in several ways.
Viewing the Website of the Alarms Panels from within your facility ONLY:
Add the IP address of each rabbit board to your local network as a remote server.
You can then point a web browser at each of the alarms panels to view their webpage using their unique IP ad-
dresses. Consult your network administrator if you want to assign a name to each of the panels in your facility in-
stead of using the IP address. It is recommended that the same panel name used when programming the rabbit
board be used here to avoid confusion.
Viewing the Website of the Alarm Panels from outside your facility over the Internet:
If there are multiple alarm panels on the network in a facility then a reverse proxy server must be set up
with software such as Microsoft TMG (Threat Management Gateway) or other similar software to manage
the multiple panel traffic. The website uses port 80 by default. Each alarm panel must be assigned a
unique name such as west wing.pattonsmedical.com and the name DNS mapped to the corresponding
alarm panels rabbit board IP address. It is recommended that the same panel name used when program-
ming the rabbit board be used here to avoid confusion. This mapping is set up using the software chosen
for the reverse proxy server.
38
Alarm Systems
This is an example of how the website would look for a one gas (oxygen) area alarm module with a 4 – 20 mA
master module for oxygen liquid level. Note there will be 16 ‘boxes’, one for each of the potential circuit boards
on the alarm panel.
Below is an illustration of the event log. The event log is viewed by clicking on the Alarm Log button on the left
side of the website (see above). This event log will display up to 100 recent events with the most recent event on
the top line and the oldest event on the bottom line.
39
Alarm Systems
BACnet Interface –
REQUIRED TOOLS AND DATA
OVERVIEW
• The 460MMBS Gateway
The 460MMBS Gateway device seamlessly connects
• The provided CD-ROM
Modbus RTU Slave devices to a BACnet/IP client. By follow-
ing this guide, you will be able to configure the 460MMBS
• The provided Ethernet Crossover Cable
Gateway for basic operation. You will set the devices network
settings and parameters to the proper configuration for initial
• A Working PC (Windows based)
operation and physically place the device in the network.
CAUTION: The Gateway device should only be installed after all wall construction and finishing is completed to prevent ingress
of dust and debris. This contamination can adversely affect its proper function.
An Ethernet/Rabbit board should have already been installed in the back box and programmed as described in the previous
pages. See the section on Integrating the Ethernet/Rabbit boards into a network.
The Gateway device configuration should be done at the Alarm panel. The device can be clipped to the provided bracket in
the top right hand corner of the back box or be loose near the PC being used to configure the device.
The power for the 460MMBS Gateway device will come from the Orange (+) and Black (-) wires in the Alarm back box. Con-
nect the orange wire to the plug labeled RED (+) and the black wire to the plug labeled BLACK (-). Refer to the wiring diagram
on the page 55 for proper connections.
The RS485 data wires, blue, white and black, have been pre-wired to the input plug of the 460MMBS gateway. Connect the
ends of these wires the “MODBUS/RS485” plug on the rabbit board, White wire to the “A” port, Blue wire to the “B” port and
Black wire to “GRD” port. Refer to the wiring diagram on page 56 for proper connections.
Always turn the power off to the alarm panel before making any electrical connections or disconnections.
40
Alarm Systems
Before you can configure the gateway itself, you must configure the network settings to connect the gateway. The
following steps will connect the gateway properly.
1. Using the provided Ethernet crossover cable, connect the device to the PC.
3. The gateway device is shipped with a default IP Address of 192.168.0.100 and a Subnet of 225.255.255.0.
Change the IP Address and Subnet of your PC, if necessary, to allow communication to the gateway device.
4. Open a Web browser and enter the device IP Address in the URL.
7. Next to Device Configuration. Click the Edit button to modify the Network Settings.
8. Enter the new IP Address, Subnet, and Default Gateway to work in your network.
9. Click Save Parameters to save the network setting. Restart the gateway by clicking Restart Now.
10. Change your PC back to its original IP and Subnet setting for your network.
11. Enter the gateway’s new IP Address in the Web browser to launch the Main Page.
NOTE - Browser configuration is compatible with Chrome, Internet Explorer, and Firefox.
41
Alarm Systems
1. On the Main Page, click on Port Configuration. It should appear as shown below.
3. Set Serial Baud to 9600, Parity: None, Data Bits: 8, and Stop Bits 1.
If you are experiencing any difficulty programming the gateway device, insert the provided CD-ROM and refer to
the trouble shooting section and other applicable tools on the CD.
42
Alarm Systems
A complete Modbus map for the largest Pattons Medical alarm panel is embedded in the rabbit board. An example
of what the Modbus map looks like is shown below. The Board ID numbers in the left hand column refer to the
boards COM ID numbers as explained on page 25. On the Modbus map, there is also an explanation of the values
used within the map such as Board Type character 1 is a Gas Board or 2 is a Master Board etc.
43
Alarm Systems
Modbus Interface -
From the Main Page of the RTA website, click on Modbus RTU Master. An example Modmap of what is dis-
played is shown below. The Read Scan Lines are generated automatically by the Ethernet/Rabbit board and will
match the configuration of the alarm panel. Individual informational items may be selected to communicated to the
BACnet module for use on the building automation system.
2. Enter the Device instance that the 460MMBS will have on the BACnet/ IP Network. Note that this must be
unique amongst all BACnet devices on the network.
4. The Description and Location fields are optional. Filling in this information is recommended to identify the
device on a network.
5. Beneath the Read Groups, verify the number of Analog Input (AI), Analog Outlet (AO), Binary Input (BI)
and Binary Output (BO) objects that you will be exposing to the BACnet/ IP Client.
7. To save changes and force the gateway back to running mode, click on the Reboot Now button and after 5
seconds hit the Refresh button. You should see the gateway appear in the Mode: Running.
44
Alarm Systems
Appendix A
Glossary of Terms
45
Alarm Systems
Input Fuse: 5 amp input AC line fuse protects the input wiring to power supply
Dimensions
Rough-in Box - All dimensions are in inches and cover the basic box only (mounting flange excluded)
Front Panel
Transducers: Housing dimensions: 1.990W x 1.990H x 3.625 Length including inlet fittings
46
Alarm Systems
47
Alarm Systems
The master alarm signals which are pre-loaded in the database (see page 24) will appear in the sequence below
starting at the top of the first column to the bottom of the first column, then to the top of the second column to the
bottom of the second column, etc. Using the back double arrow will start at the bottom of the fourth column and
progress backwards.
Master alarm signal has pre-loaded language sets please refer to page 26 on Programming language.
48
Alarm Systems
49
Alarm Systems
50
Alarm Systems
51
Alarm Systems
52
Alarm Systems
53
Alarm Systems
54
Alarm Systems
55
Alarm Systems
56
Alarm Systems
57
Alarm Systems
Text Message Carriers
char Carriers[SMS_MAX_CARRIERS][2][64] = {
58
Alarm Systems
Text Message Carriers
char Carriers[SMS_MAX_CARRIERS][2][64] = {
59
Alarm Systems
Text Message Carriers
char Carriers[SMS_MAX_CARRIERS][2][64] = {
60
Alarm Systems
Text Message Carriers
char Carriers[SMS_MAX_CARRIERS][2][64] = {
"@omnipoint.com", "Omnipoint",
"@omnipointpcs.com", "Omnipoint",
"@onemail.at", "One Connect Austria",
"@onlinebeep.net", "OnlineBeep",
"@optusmobile.com.au", "Optus Mobile",
"@sms.orange.nl", "Orange-NL/Dutchtone",
"@orangemail.co.in", "Orange Mumbai",
"@orange.net", "Orange",
"@mujoskar.cz", "Oskar",
"@sms.luxgsm.lu", "P&T Luxembourg",
"@pacbellpcs.net", "Pacific Bell",
"@airmessage.net", "PageMart Advanced/2way",
"@pmcl.net", "PageMart Canada",
"@pagemart.net", "PageMart",
"@pagegate.pagenet.ca", "PageNet Canada",
"@page1nw.com", "PageOne NorthWest",
"@pcsone.net", "PCS One",
"@pelephone.net.il", "Pelephone Israel",
"@pcom.ru", "Personal Communication",
"@msg.pioneerenidcellular.com", "Pioneer/Enid Cellular",
"@text.plusgsm.pl", "PlusGSM",
"@bplmobile.com", "Pondicherry BPL Mobile",
"@voicestream.net", "Powertel",
"@txt.bell.ca", "President's Choice",
"@mobilecell1se.com", "Price Communications",
"@sms.primtel.ru", "Primtel",
"@page.propage.net", "ProPage",
"@sms.pscel.com", "Public Service Cellular",
"@pager.qualcomm.com", "Qualcomm",
"@qwestmp.com", "Qwest",
"@ram-page.com", "RAM Page",
"@pcs.rogers.com", "Rogers AT&T Wireless",
"@pcs.rogers.com", "Rogers Canada",
"@safaricomsms.com", "Safaricom",
"@satelindogsm.com", "Satelindo GSM",
"@satellink.net", "Satellink",
"@paging.acswireless.com", "SBC Ameritech Paging",
"@email.swbw.com", "Southwestern Bell",
"@messaging.sprintpcs.com", "Sprint",
"@scs-900.ru", "SCS-900",
"@sfr.fr", "SFR France",
"@text.simplefreedom.net", "Simple Freedom",
"@email.skytel.com", "Skytel Pagers",
"@skytel.com", "Skytel Pagers",
"@mysmart.mymobile.ph", "Smart Telecom",
"@page.southernlinc.com", "Southern LINC",
"@email.swbw.com", “Southwestern Bell",
"@messaging.sprintpcs.com", "Sprint PCS",
"@sprintpaging.com", "Sprint",
61
Alarm Systems
Text Message Carriers
char Carriers[SMS_MAX_CARRIERS][2][64] = {
62
Alarm Systems
63
3201 South Boulevard
Charlotte, NC 28209
1-866-960-0087
www.pattonsmedical.com