Unc100 Axiom
Unc100 Axiom
Unc100 Axiom
new generation
building security
Trademark
AxiomV™ is the trademark of RBH Access Technologies Inc. Windows is a trademark of Microsoft
Corporation. All other product names mentioned herein are the property of their respective owners.
Use of a term in this book should not be regarded as affecting the validity of any trademark or service
mark.
Disclaimer
This book is provided as is, without warranty of any kind, either express or implied, including but not
limited to performance, merchantability, or fitness for any particular purpose. Neither RBH Access
Technologies Inc. nor its dealers or distributors shall be liable to any person or entity with respect to any
liability, loss, or damage, caused, or alleged to have been caused directly or indirectly by this
information. Further RBH Access Technologies Inc. reserves the right to revise this publication, and to
make changes to the content hereof from time to time, without the obligation of RBH Access
Technologies Inc. to notify any person or organization of such revision or changes.
Panel Graphics
ULC-S319-05 III
For ULC-S319-05 III compliance, all wiring into the panel’s cabinet must enter through metal conduit.
Also be sure to mount the panel in a protected area.
Communication
The UNC100 has one RS485 port and an Ethernet 10/100 interface. Communications from the host
computer running Axiom software can be achieved in the following ways; either via the Ethernet
interface or via RS485 through a direct connection to a designated channel. The UNC100’s RS485
channel may be programmed as HOST, DNET, UNC-NET, or LAN. Use the DIP switch to select baud rate
for Host communications as 9600, 38400, 57600, or 115200.
Networks
There are three networks supported by the UNC100 these are:
1) Host Communications through the Ethernet or direct connection.
2) Device Communications for devices such as additional RC-2s starting at address 2, Alarm Keypads,
IOC-16 controllers, and PC100.
3) Controller Communications for controllers such as additional UNC500s or for NC100s via UNC-NET
which is protocol designed for RS485 communications between UNC500s and UNC100s only.
DIP Switch
DIP Switch Function
1-4 Controller Address
5 Ethernet Secure Mode1
6,7 Controller Baud Rate
8 Not used
1
DIP switch 5 up will enables Ethernet Secure Mode. This will prevent access to the panel’s programming through
the Ethernet.
UNC100 Axiom Hardware Manual V1.2 RBH Access Technologies Inc.
Page 8 of 25
Controller Addressing
Use DIP switches 1, 2, 3, and 4 to select the controller address. The address is binary coded and the
switch settings for all fifteen possible addresses are given below.
Controller Addressing
Switch 1 Switch 2 Switch 3 Switch 4 Address
On On On Off 7 (Slave)
On On Off On 11 (Slave)
On Off On On 13 (Slave)
Off On On On 14 (Slave)
On On On On 15 (Slave)
Slave Controller
All controllers addressed 2 through 15 are referred to as slave controllers.
Host Connection
The master controller is connected to either a serial port on the PC or through the local Ethernet via a
static IP address. The means of communication is configured in the AxiomV™ software under Network
Properties/Port Type.
Cable Specification
Twisted pair, shielded, 18 to 22 AWG
For ULC-S319-05 III compliance, all wiring into the panel’s cabinet must enter through metal conduit.
Also be sure to mount the panel in a protected area.
For ULC-S319-05 III compliance, all wiring into the panel’s cabinet must enter through metal conduit.
Also be sure to mount the panel in a protected area.
A password is required in order to change user parameters. The default password is “password”. The
password can be changed by the user. After entering the password the following items are available for
the use to alter.
IP GATEWAY 0.0.0.0 For future use when DNS option becomes available.
ALT PORT NUMBER 3003 Alternate port number applies to “LAN” application.
RS485 HOST Set the RS485 to HOST in order to connect via RS485 to the PC.
This is a string of up to 10 characters that allows the user access
Telnet Password password
to this program.
When combining UNC500s and UNC100s; connect the RS485 of the previous
UNC100 to CH3 (Configured as NC-NET) of the UNC500.
Battery Charger
The battery charger routes input power from the 13.8v input source or POE module and constantly
monitors the battery voltage.
Battery Test
A battery test cycle is operator initiated or scheduled. When initiated the charger is turned off and a
24Ω resistor provides a load to the battery for about ten seconds. If during this period the voltage drops
below 10 volts a battery alarm message is sent to the host, otherwise a battery normal message is sent.
Fuse Monitoring
Besides monitoring the battery voltage the UNC100 also monitors the input voltage (DC), auxiliary
voltage (aux) and the reader voltage (reader) and reports to the host whenever the state changes.
Diagnostic LED’s
The RS485 circuit has a red and green LED to indicate when a signal is received or transmitted.
Host Comms LED is a bicolour LED when red indicates receiving data from the host and when green
indicates transmission of data.
Run LED will flash slowly when connected to the host and quickly when not connected.
Trouble LED will flash when a power problem such as a low battery or low auxiliary power is detected.
Tamper Detection
A tamper wire may be connected to JP1 located close to the center of the board. A short to this input is
normal and an open is alarm.
UNC100 Axiom Hardware Manual V1.1 RBH Access Technologies Inc.
Page 15 of 25
RAM Memory
The static ram memory holds the database from the host (capable of handling 50k cards) that is
downloaded using Axiom software. The coin cell provides power to the memory as well as the real time
clock.
The D-NET connects IOC-16, RC-2, SafeSuite™ panels, PC-100, NRC2000, and NURC2000 devices in a daisy
chain fashion (parallel connection) to the network controller. Device controllers do not have to be
addressed sequentially. However, using sequential device controller addressing is recommended as this
makes your cabling diagrams easier to follow and simplifies troubleshooting as the devices are in the
correct numerical sequence.
*** UNC100 D-NETs comprising SafeSuite™ panels, PC-100, NIRC2000, and NURC2000 devices must
have the last unit in the line terminated.
5 – 20 IOC-16, PC-100
* The first RC2 is on the NC100 – Therefore, the first physical RC2 to be connected will start at address 2.
UNC100 Axiom Hardware Manual V1.1 RBH Access Technologies Inc.
Page 17 of 25
D-NET (Device Network) Connection Example
Reader Connection
For ULC-S319-05 III compliance, all wiring into the panel’s cabinet must enter through metal conduit.
Also be sure to mount the panel in a protected area.
1
Reader wire colours may vary for different reader manufactures. Please verify your wiring.
UNC100 Axiom Hardware Manual V1.1 RBH Access Technologies Inc.
Page 19 of 25
Access Point Operating Modes
Two Person
The Red LED flashes slowly.
In Two Person Mode, two valid cards are required for access. The reader Buzzer beeps rapidly after the
first card is presented. A second valid card must be presented within ten seconds for access to be
granted.
High Security
The Red LED flashes quickly.
In High Security Mode, only cardholders with High Security Privilege are allowed access.
Unlocked
The green LED turns on to indicate the door is unlocked.
Tamper
The Buzzer sounds continuously.
Lockout Alarm
The Buzzer beeps rapidly.
A lockout alarm occurs when a user-defined number of „Access Denied‟ messages occur.
These messages can include „Invalid Card Number‟, „No Access at this Time‟, „No Access at this Reader‟,
or „Invalid PIN Code‟.
Access Granted
The Buzzer emits one long beep and the green LED turns on for the duration of the unlock time.
Access Denied
The Buzzer emits two short beeps and the red LED flashes twice.
Lock Output
For magnetic locks, the relay should be configured from the PC as On State de-energized for fail-safe
operation. If power fails (AC and battery) the power to the magnetic lock is removed and the door is
opened.
Forced / Tamper
The Forced/Tamper output turns on if the door is forced open or if a reader tamper is detected. This
output remains on for as long as the alarm condition exists.
Alarm Shunt
The alarm shunt output turns on when the door is unlocked. This output turns off when the door is re-
locked if the door is closed at that time; otherwise the output turns off when the door closes. Normally
the shunt output is used to bypass a door contact monitored by a secondary alarm panel.
Input Applications
Each input has four states: Restore, Alarm, Trouble, and Illegal. Trouble is reported if a short or break is
detected on a supervised circuit and illegal is reported if the measured loop resistance lies between valid
states. For example, if the circuit type is programmed as “2 resistor normally closed”, 1k represents a
restored state and 2k represents an alarm state. If the loop resistance changes by more than 15% but
not enough to enter the next state, an illegal state is reported.
This circuit type is used where normally open and normally closed contacts are used in the same loop.
For ULC-S319-05 III compliance, all wiring into the panel’s cabinet must enter through metal conduit.
Also be sure to mount the panel in a protected area.
Cable Specification
Circuit Function Cable type Length