ARND153DCR4
Split Compact DOAS
1500 CFM Indoor Unit
Performance: Operating Range²:
Total Cooling Capacity (Btu/h) 120,000 Outdoor Temperature (°F DB) 14-122
Heating Capacity (Btu/h) 51,000 Outdoor Temperature (°F WB) 14‐78
Cooling Nominal Test Conditions: Heating Nominal Test Conditions: Unit Data:
Outdoor: 95°F DB/75°F WB Outdoor: 44°F DB/40.3°F WB
Leaving Air: 52.9°F DB/52.5°F WB Leaving Air: 70°F DB Refrigerant Type R410A
Electrical: Refrigerant Control EEV
Power Supply (V/Hz/Ø) 208‐230/60/1 Sound Power dB(A) 75
MCA (A) 7.5 Sound Pressure dB(A) 56
MOP (A) 15 Filter Type 2" thick, MERV 8
MCA ‐ Minimum Circuit Amps MOP ‐ Maximum Overcurrent Protection Filter Quantity 2
Piping¹: Filter Panel Size 25" x 20" x 2"
Refrigerant: Net Unit Weight (lbs) 390
Liquid Line (in, OD) 1/2 Shipping Weight (lbs) 448
High Pressure Vapor Line (in, OD) 3/4 Fan:
Low Pressure Vapor Line (in, OD) 1-1/8 Type 3D Plug
Condensate: Quantity 1
Condensate Pump Line (in, Plain) 1 Motor/Drive ECM Direct
Gravity Drain (in, OD) 1 Airflow Rate (CFM) 1500
Factory Installed Pump Yes External Static Pressure (in wg) 2.0
ECM ‐ Electronically Commutated Motor
Reheat Coil:
Standard Features:
Heat Capacity (Btu/h) 24,000
•Main and recovery coils internally piped to factory installed heat
Test Conditions:
Entering Air Temperature: 54°F DB/53°F WB
recovery unit
Reheat Leaving Air Temperature 75°F DB
•Factory mounted discharge air temperature sensor
•Factory installed AHU controller that can be directly connected to
Accessories: a PC, or connected to TCP/IP network for web access.
•Direct integra on into BACnet® building automation systems
•Can be connected to AC Smart 5 and ACP 5
Notes:
1.Connec on Rules:
• Combination ratio should be 50%‐110%
• Cannot be combined with standard IDU
• Compatible with Multi V 5 Heat Recovery only
2.For outdoor design temperatures lower than 14°F, a field provided preheat coil or ERV can be
installed upstream of the DOAS unit and interlocked to DOAS controls.
3.All communica on cable to be minimum 18 AWG, 4‐conductor, stranded, shielded and must
comply with applicable local and national code.
4.Power wiring cable size must comply with the applicable local and na onal code.
5.This data is rated 0 above sea level, with 25 of refrigerant line per indoor unit and a 0
level difference between outdoor and indoor units.
6.Must follow installa on instruc ons in the applicable LG installa on manual.
7. Standard (1) year parts warranty.
8. Do not locate the Split Compaq DOAS product in an un-conditioned space where the relative
humidity level of the surrounding air could exceed 60% RH. Temperature range in the mounted
location must be maintained between 55 F and 90 F DB.
For continual product development, LG reserves the right to change specifications without notice. SB_DOAS_ARND153DCR4_2024_08_28_135218
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com Page 1 of 2
Job Name/Location:
ARND153DCR4 Tag #:
Split Compact DOAS Date:
1500 CFM Indoor Unit PO No.:
For continual product development, LG reserves the right to change specifications without notice. SB_DOAS_ARND153DCR4_2024_08_28_135218
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com Page 2 of 2