Inform Modbus Setup Guide Q-1314B
Inform Modbus Setup Guide Q-1314B
Inform Modbus Setup Guide Q-1314B
Modbus
SETUP GUIDE
Inform™ Modbus Setup Guide
TABLE OF CONTENTS
by
1. Installation Instructions.........................................................................3
2. Modbus Configuration............................................................................4
2.1. Modbus Commands.....................................................................4
2.2. Supported Functions...................................................................4
2.3. Configuration Registers..............................................................4
2.4. Measurement Registers..............................................................5
2.5. Device Information Registers.....................................................6
2.6. Sensor Data Format.....................................................................7
2.6.1. Voltage Format...................................................................7
2.6.2. Current Format...................................................................7
2.6.3. Temperature Format.........................................................7
2.6.4. Humidity Format.................................................................7
2.6.5. Ground Continuity..............................................................7
2.6.6. Liquid Accumulation..........................................................7
2.6.7. Switch Position...................................................................7
2.7. Error Detection.............................................................................8
2.7.1. Voltage alarms...................................................................8
2.7.2. Ground Continuity Alarm..................................................8
2 leviton.com/inform
Inform™ Modbus Setup Guide
1. INSTALLATION INSTRUCTIONS
1.2.1. Cabling
RS-485 is a three-wire bus. One twisted pair is required
for the two data signal wires, plus an additional wire for
a common reference, which does not need to be twisted.
A cable with two twisted pairs may also be used, where
one or both conductors of the second pair is/are used
for the common.
1.2.2. Shielding
A shield may not be needed for short networks, but is recommended and required for long networks
or networks in an electrically noisy environment. The shield must be connected to a ground point at
ONE side only. Although the shield can be used for the common reference, it is preferable to use a
separate wire for the common.
1.2.3. Termination
RS-485 (EIA-485) networks typically require a termination resistor of 120Ω. Depending on the bus, a
termination resistor may be needed. Additional bias resistors may also be needed.
1.2.4. Topology
Utilize a daisy-chain bus configuration for connecting
up to 32 devices.
1.2.5. Connection
The terminal block on the Modbus communication PCBA
can accommodate 24 – 16 AWG cable. Connect the
communication cable to the terminal block on the
Modbus PCBA.
leviton.com/inform 3
Inform™ Modbus Setup Guide
2. MODBUS CONFIGURATION
4 leviton.com/inform
Inform™ Modbus Setup Guide
leviton.com/inform 5
Inform™ Modbus Setup Guide
3-7 characters,
plus null terminator:
1P+N+E = Single Phase, Neutral,
Ground
2P+E = Single (split) Phase,
Ground
2P+N+E = Single (split) Phase,
Neutral, Ground
3P+E = Three-phase, Ground
3P+N+E = Three-phase, Neutral,
Ground
3PB+E = 4-wire Delta B leg high
Wiring Config 31001 1000 3E8 6 String* 3PB+N+E = 5-wire Delta B leg
high
DIP switch-based
Voltage Config 31007 1006 3EE 2 uint16
user-configured nominal voltage
31013-
Reserved 87
31100
6 leviton.com/inform
Inform™ Modbus Setup Guide
leviton.com/inform 7
Inform™ Modbus Setup Guide
8 leviton.com/inform
Inform™ Modbus Setup Guide
3. SOFTWARE
3.1. INTRODUCTION
Leviton devices with Inform Technology incorporate firmware that provides critical functions,
including sensor element interface, sensor value processing, error detection, and Modbus operation.
The firmware includes a boot loader for in-field firmware updates via Leviton’s Inform Mobile App. It is
recommended that installer check for updated firmware after the initial installation and, if available,
perform the update as described in section 3.1.2.
Additionally, the Inform Mobile App provides a utility for setting the Modbus device ID and network
communication parameters
leviton.com/inform 9
Inform™ Modbus Setup Guide
NOTES:
CONTACT INFORMATION
User Support
Tech Line: 1-800-824-3005
Monday - Friday 8 AM - 10 PM ET
Saturday 9 AM - 7 PM ET
Sunday 9 AM - 5 PM ET
Email: [email protected]
Website: leviton.com/inform