ACTUATOR FOR DAMPERS

Ty p e 2 3 8
Actuator with spring return 15 Nm

For the application with Room ventilation techniques VAV Valves

Page:
2 3 4 10 11 12 9

Content:
General overview Summary 238, 15 Nm Technical characteristics, Type 238, 15 Nm Specific characteristics of continuous control Notes Your way to Gruner

GR

UNER he frie t

alte dly n

rnative

GRUNER AG PF 1149, D-78560 Wehingen

Tel. (++49) 74 26 / 948 - 0 Fax (++49) 74 26 / 948 - 200

http://www.gruner.de E-Mail: [email protected]

06/04 CI51E Copyright by Gruner AG Technical changes are reserved

GENERAL OVERVIEW: ACTUATORS WITH ROTATION DRIVE

without spring return


= Standard = Optional

with spring return

Type
Torque

227
2

232
2

231
2

228
2

238

5 Nm (appr.1 m ) 15 Nm (appr.3 m ) 20 Nm (appr.4 m ) 5 Nm (appr.1 m ) 15 Nm (appr.3 m2) 8 Nm (appr.1.6 m2) 30 Nm (appr.6 m2)

Control
Tri-state On / Off Continuous (0) 2...10 VDC or (0) 4...20 mA with 500

Power supply
24 VAC/DC 230 VAC

Options
Potentiometer Auxiliary switch(es) LON Interface VAV Interface Universal locking clamp Form locking

Applications
Motorised control of dampers, ball and butterfly valves. Application in mixed air and shut-offer damper control. For primary HVAC air-handling and zone units. Smoke and air isolation shut-off damper control for ventilation systems Ball valve control for domestic and drinking water, condensation water, air (i.e. zone units). The actuator 231L has digital communication capabilities and can be networked with a LON-Bus system. All actuators correspond to the UL, CSA & DIN-VDE standards, CE guidelines.

GRUNER AG PF 1149, D-78560 Wehingen

Tel. (++49) 74 26 / 948 - 0 Fax (++49) 74 26 / 948 - 200

http://www.gruner.de E-Mail: [email protected]

06/04 CI51E Copyright by Gruner AG Technical changes are reserved

SUMMARY TYPE 238, 15 Nm

23 802 415 23 802 415 23 -S 82 23 015 23

Type
Torque Control Tri-state On / Off Continuous control (0) 2...10 VDC or (0) 4...20 mA

15 Nm 15 Nm 15 Nm 15 Nm 15 Nm

Power supply
24 VAC/DC 230 VAC 4 4 6 6 8

Options
Feedback signal Auxiliary switch(es) Page

All actuators dispose of the manual override option by crank. Actuators according to US-standard available upon demand.

GRUNER AG PF 1149, D-78560 Wehingen

Tel. (++49) 74 26 / 948 - 0 Fax (++49) 74 26 / 948 - 200

823 015 23 -S

= Optional

06/04 CI51E Copyright by Gruner AG Technical changes are reserved

8C 2 -0 24 -1 5
http://www.gruner.de E-Mail: [email protected]

= Standard

238-024-15, 238-024-15-S2
Applications
To regulate dampers, valves or other regulatory functions: sturdy drive maintenance-free torque 15 Nm position indication Adjustment of the direction of rotation by mounting back to front auxiliary switch adjustable from outside electromagnetic compatibility controlled

Technical characteristics
Control Connecting voltage Power consumption Transformer size Angle of rotation Direction of rotation Running time Torque Auxiliary switches Switching power auxiliary switch Connection Safety class Protection Dimensions Ambient temperature Maintenance CE Weight On / Off 24 VAC (50/60 Hz) / DC 20% Motion: 6.0 W / Power safe mode: 4.0 W 8.0 VA / 5.0 VA 100 (-5...+95) can be selected by back to front mounting Actuator: 150 s / Spring: < 20 s 15 Nm 2, adjustable from outside 250 VAC / 5.0 (2.5) A, change-over switch cable 900 mm / 0.75 mm2 III IP54 (cable downwards) 250 x 98 x 58 mm -20...+50 C maintenance-free 73/23 EWG, 89/336 EWG 1,800 g

238-024-15
Connection scheme

238-024-15-S2
Connection scheme

S1

S2
Auxiliary switches

1 2 3 4 5 6 BU BN BU BN

GRUNER AG PF 1149, D-78560 Wehingen

Tel. (++49) 74 26 / 948 - 0 Fax (++49) 74 26 / 948 - 200

http://www.gruner.de E-Mail: [email protected]

06/04 CI51E Copyright by Gruner AG Technical changes are reserved

238-024-15, 238-024-15-S2
1
1

Fixing of the shaft (fig. 1)


by the locking clamp to the damper shaft: 10...16 mm 9...20 mm
S2

.2 1 .6 .8

.4

Selection of the direction of rotation (fig. 1 + 2)


0

The direction of rotation can be selected by back to front mounting.


.2 0 .8 .6 S1 .4

2
1

Adjustment of the auxiliary switches (fig. 2)


The scale at the adjusting knob corresponds to a percentage graduation, related to 0 to 90. Choose the requested switching position by turning the knob to the right or left respectively, i.e. .2 = 20%. The
.2 1 .6 .8
S2

.4

switches can be adjusted regardless of the momentarily angle of rotation.

.4 .6
S1
8.

.2
0

Technical drawing
238-024-15
10 2
2 R1

21 24 43

98

58

20

6 250

GRUNER AG PF 1149, D-78560 Wehingen

Tel. (++49) 74 26 / 948 - 0 Fax (++49) 74 26 / 948 - 200

http://www.gruner.de E-Mail: [email protected]

06/04 CI51E Copyright by Gruner AG Technical changes are reserved

15

4
2 R1

83

238-230-15, 238-230-15-S2
Applications
To regulate dampers, valves or other regulatory functions: sturdy drive maintenance-free torque 15 Nm position indication Adjustment of the direction of rotation by mounting back to front auxiliary switch adjustable from outside electromagnetic compatibility controlled

Technical characteristics
Control Connecting voltage Power consumption Transformer size Angle of rotation Direction of rotation Running time Torque Auxiliary switches Switching power auxiliary switch Connection Safety class Protection Dimensions Ambient temperature Maintenance CE Weight On / Off 230 VAC (50/60 Hz) 15% Motion: 9.0 W / Power safe mode: 7.0 W 10.0 VA / 8.0 VA 100 (-5...+95) can be selected by back to front mounting Actuator: 150 s / Spring: < 20 s 15 Nm 2, adjustable from outside 250 VAC / 5.0 (2.5) A, change-over switch cable 900 mm / 0.75 mm2 II IP54 (cable downwards) 250 x 98 x 58 mm -20...+50 C maintenance-free 73/23 EWG, 89/336 EWG 1,800 g

238-230-15
Connection scheme

238-230-15-S2
Connection scheme

S1

S2
Auxiliary switches

1 2 3 4 5 6 BU BN BU BN

N L

N L

GRUNER AG PF 1149, D-78560 Wehingen

Tel. (++49) 74 26 / 948 - 0 Fax (++49) 74 26 / 948 - 200

http://www.gruner.de E-Mail: [email protected]

06/04 CI51E Copyright by Gruner AG Technical changes are reserved

238-230-15, 238-230-15-S2
1
1

Fixing of the shaft (fig. 1)


by the locking clamp to the damper shaft: 10...16 mm 9...20 mm
S2

.2 1 .6 .8

.4

Selection of the direction of rotation (fig. 1 + 2)


0

The direction of rotation can be selected by back to front mounting.


.2 0 .8 .6 S1 .4

2
1

Adjustment of the auxiliary switches (fig. 2)


The scale at the adjusting knob corresponds to a percentage graduation, related to 0 to 90. Choose the requested switching position by turning the knob to the right or left respectively, i.e. .2 = 20%. The
.2 1 .6 .8
S2

.4

switches can be adjusted regardless of the momentarily angle of rotation.

.4 .6
S1
8.

.2
0

Technical drawing
238-230-15
10 2
2 R1

21 24 43

98

58

20

6 250

GRUNER AG PF 1149, D-78560 Wehingen

Tel. (++49) 74 26 / 948 - 0 Fax (++49) 74 26 / 948 - 200

http://www.gruner.de E-Mail: [email protected]

06/04 CI51E Copyright by Gruner AG Technical changes are reserved

15

4
2 R1

83

238C-024-15
Applications
To regulate dampers, valves or other regulatory functions: sturdy drive maintenance-free torque 15 Nm position indication direction of rotation changeable from outside control range adjustable from outside electromagnetic compatibility controlled

Technische Daten
Control Control signal Y Continuous control 0...10 VDC or 2...10 VDC (Standard) or 0...20 mA or 4...20 mA Feedback signal U 0...10 VDC or 2...10 VDC (Standard) or 10 VDC or 15 VDC Connecting voltage Power consumption Transformer size Angle of rotation Direction of rotation Running time Torque Connection Safety class Protection Dimensions 24 VAC (50/60 Hz) / DC 20% 7.0 W 9.0 VA 100 (-5...+95) can be selected by back to front mounting Actuator: 150 s / Spring: < 20 s 15 Nm cable 900 mm / 0.75 mm2 III IP54 (cable downwards) 250 x 98 x 58 mm -20...+50 C maintenance-free 73/23 EWG, 89/336 EWG 1,800 g

238C-024-15
Connection scheme (Continuous control)

Ambient temperature Maintenance CE Weight

BUBN BK GY Y U

GRUNER AG PF 1149, D-78560 Wehingen

Tel. (++49) 74 26 / 948 - 0 Fax (++49) 74 26 / 948 - 200

http://www.gruner.de E-Mail: [email protected]

06/04 CI51E Copyright by Gruner AG Technical changes are reserved

238C-024-15
1
1

Fixing of the shaft (fig. 1)


by the locking clamp to the damper shaft: 10...16 mm 9...20 mm

Selection of the direction of rotation


0

The direction of rotation can be selected by back to front mounting.

Modification of the control direction (fig. 2)


Spring clockwise Spring counter-clockwise R 90 0 L 90 0 R 0 90

L
L R L R L R

R
L R

Direction of rotation switch Y = (0) 2 VDC Y = 10 VDC


Y=0

L 0 90

Direction of rotation switch


Y=0 Y=0 Y=0

Technical drawing
238C-024-15
10 2
2 R1

21 24 43

98

58

20

6 250

GRUNER AG PF 1149, D-78560 Wehingen

Tel. (++49) 74 26 / 948 - 0 Fax (++49) 74 26 / 948 - 200

http://www.gruner.de E-Mail: [email protected]

06/04 CI51E Copyright by Gruner AG Technical changes are reserved

15

4
2 R1

83

10

SPECIFIC CHARACTERISTICS OF CONTINUOUS CONTROL


Wiring configuration and recommended cable length

- +

238C

- +

238C

BU BN BK GY
L2 L1 max. cable length
24VAC

BU BN BK GY

(I +I ) R >
A G L max. cable length L2 L1
24VAC

transformer

R < L

transformer

DC 0(2)...10V by the controller

DC 0(2)...10V

DC 0(2)...10V

by the actuator

by the controller

DC 0(2)...10V by the actuator

current of set valve selector actuator current cable cross section cable resistance 0,75 mm2 1 cable length cable cross section mm2 1,5 mm2 2,5 mm2 23 m 31 m 46 m max. cable length

76 m For several actuators switched in parallel the max. cable length must be divided by the number of actuators.

Teach-in of range of angle > 30


1. Actuator stand by 2. Adjusting mechanical endstops 3. 15 VDC at Y 4. Power on actuator 5. Actuator starts teach-in process of range of angle (60...120 s) 6. Remove 15 VDC at Y

BUBN BK GY
15 VDC

GRUNER AG PF 1149, D-78560 Wehingen

Tel. (++49) 74 26 / 948 - 0 Fax (++49) 74 26 / 948 - 200

http://www.gruner.de E-Mail: [email protected]

06/04 CI51E Copyright by Gruner AG Technical changes are reserved

NOTES

11

GRUNER AG PF 1149, D-78560 Wehingen

Tel. (++49) 74 26 / 948 - 0 Fax (++49) 74 26 / 948 - 200

http://www.gruner.de E-Mail: [email protected]

06/04 CI51E Copyright by Gruner AG Technical changes are reserved

YOUR WAY TO GRUNER

Stuttgart

A8

Mnchen

Balingen Karlsruhe
Schmberg

Freudenstadt

A81

Wehingen
B27
Gosheim Frittlingen Denkingen

Tuttlingen

Strasbourg

Rottweil B14
Schramberg Aldingen

Spaichingen

Offenburg A5 B33 Freiburg B31

34
B27

Donaueschingen

Singen Zrich

Basel N1 N3

GRUNER AG PF 1149, D-78560 Wehingen

Tel. (++49) 74 26 / 948 - 0 Fax (++49) 74 26 / 948 - 200

http://www.gruner.de E-Mail: [email protected]

06/04 CI51E Copyright by Gruner AG Technical changes are reserved