TurbineMeter-RMG TRZ 03
TurbineMeter-RMG TRZ 03
TurbineMeter-RMG TRZ 03
max
A A A
max
N
3
A
A
3
max
3
N
3
max
3
A A
3
the turbine wheel (HF3) or the reference wheel (HF2),
each of them is connected separately using a Binder
plug at the front of the device:
Pulse outputs
The meter head is fitted with a reed contact as LF
pulse transmitter as standard feature. But optionally,
another two sensors can be fitted, e.g. another LF
pulse transmitter (inductive sensor with output pulses
complying with NAMUR or r ) and an HF1
pulse transmitter (NAMUR).
Connection is made by means of a 7-pin Binder plug:
eed contact
p = p p A A
QA N
Qmax 0.83
2
p = 4 1.1 mbar = 2.7 mbar A
250 1.29
400 0.83
2
Nominal Max. flow rate V * p HF pulse trans-
size DN Q mitter (option)
mm in. m /h m mbar HF2 HF3
LF
max
3 3
50 2"
65 0.1 3
100 0.1 5
160 1 2
80 3" 250 1 6
400 1 14
250 1 2
100 4" 400 1 4
650 1 10
650 1 2
150 6" 1000 1 6
1600 10 12
200 8"
1600 10 3
2500 10 8
1600 10 2
250 10" 2500 10 3
4000 10 7
300 12"
4000 10 4
6500 10 9
400 16"
6500 10 3
10000 10 8
500 20"
10000 10 4
16000 100 9
600 24"
16000 100 4
25000 100 9
- -
-
- not available
available for all pressure classes
*V : Volume at actual con-
ditions per LF pulse
LF
1
2
3 4
5
+
+
+
-
-
-
6
1
2
3 4
5
+
-
6
1, 4: LF (reed contact)
3, 6: HF2 or HF3
signal
2, 5: LF or HF1 signal
3, 6: HF1 (NAMUR)
If only one LF pulse transmitter is fitted, it is always
connected to the contacts 1 and 4; a single HF1
pulse transmitter is always connected to the contacts
3 and 6.
If high-frequency pulse transmitters (with output pulses
complying with NAMUR) are fitted which scan either
The contacts 1, 2, 4 and 5 are not assigned.
All pulse transmitters are intrinsically safe and may be
connected only to certified intrinsically safe circuits for
use in areas subject to explosion hazards.
LF: 0.3 Hz HF1: 300 Hz
HF2: 2.1 kHz HF3: 2.1 kHz
The phase displacement between the signals from the
HF2 and HF3 pulse transmitters is 180.
Maximum frequencies: pulse transmitter
Types of gas
The TRZ 03 standard design is suitable for use with all
gases in compliance with the DVGW code of practice
G260. The materials used are appropriate for gases
and fuel gases, such as natural gas, refinery gas,
gaseous liquid gases and their mixtures, nitrogen, CO
(dry), air and all inert gases.
For aggressive gases (e.g. biogas, acid gas or
ethylene), there are special designs available with
PTFE lining, special material, special lubrication, etc.
2.5 times
2
Maintenance
Mounting and operating instructions
Order information
All turbine meters are fitted with a lubricator (DN 50
and DN 80: oil nipple or pushbutton pump, DN 100
through DN 200: pushbutton pump, from DN 250:
lever pump).
Lubrication must be performed in compliance with the
operating instructions (see also the lubrication
instruction plate of the gas meter). If clean gas is used,
lubrication is to be performed at 3-month intervals,
whereas lubrication must be performed more
frequently if dust- and/or condensate-laden gas is
used.
The TRZ 03 turbine meters can be operated in any
mounting position up to the nominal size of DN 200.
From the nominal size of DN 250, they can only be
installed in a horizontal position.
The gas meter has been designed for short-term
overload operation at up to 1.2 times the value of
Q . Such load conditions should be avoided,
however, in order to protect the TRZ 03 from any
unnecessarily high flow rates.
The gas flow must be free of shocks or pulsations,
foreign particles, dust or liquids. Otherwise it is
recommended that filters and separators be installed.
No components affecting the gas flow are permitted
directly upstream of the turbine meter (see DVGW
guidelines and PTB guideline G 13).
In each case, an inlet pipe is required whose length as
specified in the type approval may be shorter than that
specified in the Technical Guideline G 13. The lengths
of the inlet and outlet pipes must be at least 2 DN,
while also a bend may be used as outlet pipe. If there
is a heavy flow perturbation (e.g. due to a gas
pressure controller) upstream of the inlet pipe, it is
additionally necessary to use a perforated-plate
straightener. There are perforated-plate straighteners
available complying with ISO 5167-1 or of the type
RMG LP-35, the latter resulting in a pressure loss
which is lower than that of the standardized
flow straightener.
Reducers or expansion fittings must be installed
upstream of the inlet pipe and their opening angle
must not exceed 30.
The gas meter must be installed in weather-proof
locations. For outside installations, appropriate guards
must be provided against direct weathering influences.
Nominal size of the pipeline
Size G
Operating pressure (min/max) in bar g or bar a
Operating temperature (min/max)
Ambient temperature (min/max)
Type of gas to be used
Pressure rating and DIN or ANSI flange design
Direction of flow / mounting position
Accessories: inlet section, volume corrector, etc.
Options: HF pulse outputs, etc.
Special designs, e.g. for aggressive gases
Special instructions for startup and operation:
Turbine meters are precise measuring instruments
and must therefore be carefully handled during
transport, storage and operation.
Do not fill any downstream pipelines or station
sections via the turbine meter. This may result in
excessive flow rates with resultant damage to the
turbine wheel.
max
d
e
d
DN
DN
d = e = 0.13 DN
LP-35 perforated-plate straightener
2 DN
2
D
N
1 DN
Perforated-plate straightener
DN Size Measuring range DN Pressure rating / Approx. weight Dimensions
mm Q : Q (m /h) mm mm
in. 1:10/1:20 1:30 in. PN kg ANSI kg H C L
50 G 40 13-65* 50
10/16 13 150 13
2" G 65 10-100 2"
25/40 21 300 13 210 60 150
64/100 21 600 21
80
G 100 16-160
80
10/16 20 150 20
3"
G 160 13-250
3"
25/40 25 300 25 230 96 240
G 250 20-400 64/100 34 600 36
100
G 160 13-250
100
10/16 25 150 30 240
4"
G 250 20-400
4"
25/40 32 300 35 260 120 300
G 400 32-650 20-650 64/100 45 600 55 270
150
G 400 32-650
150
10/16 50 150 50 265
6"
G 650 50-1000 32-1000
6"
25/40 60 300 65 265 180 450
G 1000 80-1600 50-1600 64/100 70/90 600 100 285
200 G 1000 80-1600 50-1600 200
10/16 75 150 100 300
8" G 1600 130-2500 80-2500 8"
25/40 95 300 120 320 240 600
64/100 150/160 600 160 320
250
G 1000 80-1600
250
10/16 100/110 150 110
10"
G 1600 130-2500 80-2500
10"
25/40 135/150 300 160 330 300 750
G 2500 200-4000 130-4000 64/100 180/225 600 260
300 G 2500 200-4000 130-4000 300
10/16 138/150 150 155
12" G 4000 320-6500 200-6500 12"
25/40 225/265 300 230 360 360 900
64/100 275/290 600 310
400 G 4000 320-6500 200-6500 400
10/16 280/290 150 350
16" G 6500 500-10000 320-10000 16"
25/40 350/440 300 460 400 480 1200
64/100 525/580 600 575
500 G 6500 500-10000 320-10000 500
10/16 560/610 150 620
20" G 10000 800-16000 500-16000 20"
25/40 640/700 300 650 450 600 1500
64/100 830/1060 600 1075
600 G 10000 800-16000 500-16000 600
10/16 900/940 150 950
24" G 16000 1300-25000 800-25000 24"
25/40 980/1075 300 1000 500 720 1800
64/100 1230/1570 600 1600
min max
3
RMG Metechnik GmbH Publication No. 3.161-E
P.O.Box 280 D-35502 Butzbach (Germany)
Phone: +49 (0)6033 897-0 Fax: +49 (0)6033 897-130
E-mail: [email protected] Web site: http://www.rmg.de
Turbine meter
TRZ 03
Measuring ranges Dimensions
Issue: 04/2000 Subject to technical
modification without notice
L
H
D
N
C
* Measuring range 1:5
From DN 80 to DN 300, the turbine meters with a
pressure rating of PN 10/16 can be fitted with a
thermowell to accommodate a temperature sensor.