Technical Data
RXM-R
EEDEN23
TABLE OF CONTENTS
RXM-R
1 Features 4
RXM-R4
2 Specifications 5
3 Electrical data 29
4 Capacity tables 36
Cooling/Heating Capacity Tables 36
5 Dimensional drawings 56
6 Centre of gravity 58
7 Piping diagrams 60
8 Wiring diagrams 62
Wiring Diagrams - Single Phase 62
9 Sound data 64
Sound Pressure Spectrum 64
10 Operation range 68
3
RXM-R
1 Features
1-1 RXM-R
›› Choosing for an R-32 product, reduces the environmental impact ›› Outdoor units are fitted with a swing compressor, renowned for its
with 68% compared to R-410A and leads directly to lower energy low noise and high energy efficiency
1 consumption thanks to its high energy efficiency ›› Outdoor units for pair application
›› Daikin outdoor units are neat, sturdy and can easily be mounted ›› Anti-corrosion treated outdoor heat exchanger fin
on a roof or terrace or simply placed against an outside wall
Outdoor
unit silent
operation
4 RXM-R
R
XM-R
2 Specifications
2-1 Specifications
Technical Specifications RXM25R RXM35R RXM50R RXM60R
Casing Colour Ivory white
Dimensions Unit Height mm 552 734
Width
Depth
mm
mm
840
350
954
401
2
Packed unit Height mm 612 820
Width mm 906 1,050
Depth mm 402 480
Weight Unit kg 32 49.0
Packed unit kg 34 53
Packing Weight kg - 4
Heat exchanger Length mm 805 920
Rows Quantity 2
Fin pitch mm 1.4 1.40
Stages Quantity 24 32
Passes Quantity 3.0 2.0
Tube type ø7 Hi-XD 7.0 Hi-XD
Fin Type Waffle fin (PE)
Fan Type Propeller fan
Air flow rate Cooling Nom. m³/min 28.3 36.0 46.6
cfm 999 1,271 1,645
Heating Nom. m³/min 28.3 44.1
cfm 999 1,557
Fan motor Model DFC05A3VA D55F-31
Output W 50 55
Speed Cooling High rpm 860 920 760
Nom. rpm 800 860 740
Low rpm 400 640
Heating High rpm 860 720
Nom. rpm 800 720
Low rpm 400 660
Compressor Model 1YC25GXD#C 2YC40JXD#C
Oil Amount cm³ 375 650
Type Hermetically sealed swing compressor
Output W 800 1,300.0
Oil Type FW68DA
Operation range Cooling Ambient Min. °CDB -10
Operation range Cooling Ambient Max. °CDB 50 (1) / 46 (2) 50 (4) / 46 (5)
Heating Ambient Min. °CWB -15 -21
°CDB -20 (1) / -15 (2) -20 (4) / -15 (5)
Max. °CWB 18
°CDB 24
Sound power level Heating Nom. dBA - 62.0 63.0
Sound pressure level Cooling Nom. dBA 46 49 48.0
Heating Nom. dBA 47 49 49.0
Refrigerant Type R-32
Charge kg 0.76 1.15
Charge TCO2Eq 0.52 -
Control Expansion valve
GWP 675 675.0
Piping connections Liquid OD mm 6
Gas OD mm 9.50 12.7
Drain OD mm 18 16
Piping OU - IU Max. m 20 30
length System Chargeless m 10
Additional refrigerant charge kg/m 0.02 (for piping length exceeding 10m)
Level IU - OU Max. m 15 20.0
difference
Heat insulation Both liquid and gas pipes
Capacity control Method Variable (inverter)
R
XM-R 5
R
XM-R
2 Specifications
2-1 Specifications
Technical Specifications RXM25R RXM35R RXM50R RXM60R RXM20R RXM42R RXM71R
Heat exchanger Length mm 805 920 805 920
Rows Quantity 2
2 Fin pitch
Stages Quantity
mm 1.4
24
1.40
32
1.4
24
1.40
32
Passes Quantity 3.0 2.0 3.0 2.0
Tube type ø7 Hi-XD 7.0 Hi-XD ø7 Hi-XD 7.0 Hi-XD ø7 Hi-XD
Fin Type Waffle fin (PE)
Fan Type Propeller fan
Air flow rate Cooling Nom. m³/min 28.3 36.0 46.6 36.0 46.6 -
cfm 999 1,271 1,645 1,271 1,645 1,730
Medium m³/min - 49.0
Heating Nom. m³/min 28.3 44.1 28.3 44.1 -
cfm 999 1,557 999 1,557 1,632
Medium m³/min - 46.2
Fan motor Model DFC05A3VA D55F-31 DFC05A3VA D55F-31 D90B-37
Output W 50 55 50 55 128
Speed Cooling High rpm 860 920 760 920 760 880
Nom. rpm 800 860 740 800 740 780
Low rpm 400 640 400 640 700
Heating High rpm 860 720 860 720 780
Nom. rpm 800 720 800 690 740
Low rpm 400 660 400 500 680
Compressor Model 1YC25GXD#C 2YC40JXD#C 1YC25GXD#C 2YC40JXD#C 2YC71DXD#C
Oil Amount cm³ 375 650 375 650 900
Type Hermetically sealed swing compressor
Output W 800 1,300.0 800 1,300.0 2,400.0
Compressor Oil Type FW68DA
Operation range Cooling Ambient Min. °CDB -10
Max. °CDB 50 (1) / 46 (2) 50 (4) / 46 (5) 50 (1) / 46 (2) 50 (4) / 46 (5) 46
Heating Ambient Min. °CWB -15 -21 -15 -21 -15
°CDB -20 (1) / -15 (2) -20 (4) / -15 (5) -20 (1) / -15 (2) -20 (4) / -15 (5) -15
Max. °CWB 18
°CDB 24
Sound power level Heating Nom. dBA - 62.0 63.0 - 62.0 67.0
Sound pressure level Cooling Nom. dBA 46 49 48.0 46 48.0 47.0
Heating Nom. dBA 47 49 49.0 47 48.0
Refrigerant Type R-32
Charge kg 0.76 1.15 0.76 1.10 1.15
Charge TCO2Eq 0.52 - 0.52 -
Control Expansion valve
GWP 675 675.0 675 675.0
Piping connections Liquid OD mm 6
Gas OD mm 9.50 12.7 9.50 15.9
Drain OD mm 18 16 18 16 18
Piping OU - IU Max. m 20 30 20 30
length System Chargeless m 10
Additional refrigerant charge kg/m 0.02 (for piping length exceeding 10m)
Level IU - OU Max. m 15 20.0 15 20.0
difference
Heat insulation Both liquid and gas pipes
Capacity control Method Variable (inverter)
Standard accessories: Drain plug;Quantity: 1;
Standard accessories: Installation manual;Quantity: 1;
Standard accessories: Refrigerant charge label;Quantity: 1;
Standard accessories: Multilingual fluorinated greenhouse gases labels;Quantity: 1;
Standard accessories: Drain cap (1);Quantity: 6;
Standard accessories: Drain cap (2);Quantity: 3;
6 R
XM-R
R
XM-R
2 Specifications
2-1 Specifications
Electrical Specifications RXM25R RXM35R RXM50R RXM60R RXM20R RXM42R RXM71R
Power supply Phase 1~
Frequency Hz 50
Wiring connections
Voltage
For power supply Quantity
V 220-240
3
2
Remark Earth wire included
For connection with indoor Quantity 4
Remark Earth wire included
Current - 50Hz Maximum fuse amps (MFA) A 13 16 10 13 20
(1)Only possible in combination with CTXM*N2V1B, ATXM*N2V1B, FTXM*N2V1B |
(2)Only possible in combination with CTXM*M2V1B, ATXM*M2V1B, FTXM*M2V1B, FVXM*FV1B, FCAG*AVEB, FFA*A2VEB9,FBA*A2VEB9, FHA*AVEB9, FDXM*F3V1B9, FNA*A2VEB9, ADEA*A2VEB· |
See separate drawing for operation range |
See separate drawing for electrical data |
Contains fluorinated greenhouse gases
Technical specifications FDXM25F9 + RXM25R FDXM35F9 + RXM35R FDXM50F9 + RXM50R FDXM60F9 + RXM60R
Cooling capacity Min. kW 1.30 1.40 1.70
Min. Btu/h 4,435 4,800 5,800
Min. kcal/h 1,117 1,204 1,462
Nom. kW 2.40 3.40 5.00 6.00
Nom. Btu/h 8,189 11,600 17,100 20,500
Nom. kcal/h 2,064 2,923 4,299 5,159
Max. kW 3.00 3.80 5.30 6.50
Max. Btu/h 10,236 13,000 18,100 22,200
Max. kcal/h 2,579 3,267 4,557 5,589
Heating capacity Min. kW 1.30 1.40 1.70
Min. Btu/h 4,435 4,800 5,800
Min. kcal/h 1,117 1,200 1,500
Nom. kW 3.20 4.00 5.80 7.00
Nom. Btu/h 10,919 13,600 19,800 23,900
Nom. kcal/h 2,752 3,439 4,987 6,019
Max. kW 4.50 5.00 6.00 7.10
Max. Btu/h 15,354 17,100 20,500 24,200
Max. kcal/h 3,869 4,299 5,159 6,105
Power input Cooling Nom. kW 0.64 1.14 1.63 2.05
Heating Nom. kW 0.80 1.15 1.87 2.18
Nominal efficiency EER 3.77 2.98 3.06 2.93
COP 4.00 3.48 3.10 3.21
Annual energy consumption kWh 318 570 817 1,024
Energy Cooling A C B C
labeling Heating A B D C
Directive
Space cooling Energy efficiency class A+ A A+ A
Capacity Pdesign kW 2.40 3.40 5.00 6.00
SEER 5.68 5.26 5.77 5.56
Annual energy consumption kWh/a 148 226 303 378
Space heating (Average Energy efficiency class A+ A
climate) Capacity Pdesign kW 2.60 2.90 4.00 4.60
SCOP/A 4.24 3.88 3.93 3.80
SCOPnet/A 4.27 3.91 3.95 3.83
Pdh Heating capacity at -10° kW 2.16 2.41 3.54 3.94
Annual energy consumption kWh/a 858 1,046 1,424 1,693
Required back up heating cap at design conditions kW 0.44 0.49 0.46 0.66
Space heating (Warm Energy efficiency class A+++ A++ A+
climate) Capacity Pdesignh kW 1.40 1.57 2.16 2.48
SCOP 5.38 4.88 4.41 4.47
SCOPnet 5.46 4.95 4.46 4.51
Annual energy consumption kWh/a 365 450 685 777
Required back up heating cap at design conditions kW 0.00
Space cooling A Condition Pdc kW 2.40 3.40 5.00 6.00
(35°C - 27/19) EERd 3.77 2.98 3.06 2.93
Power input kW 0.64 1.14 1.63 2.05
B Condition Pdc kW 1.76 2.50 3.69 4.43
(30°C - 27/19) EERd 5.38 4.08 4.96 4.64
Power input kW 0.33 0.61 0.74 0.95
C Condition Pdc kW 1.27 1.61 2.37 2.85
(25°C - 27/19) EERd 8.92 8.05 8.21 6.96
Power input kW 0.14 0.20 0.29 0.41
D Condition Pdc kW 1.31 1.46 2.26
(20°C - 27/19) EERd 10.90 9.65 9.47 10.44
Power input kW 0.12 0.15 0.24 0.22
R
XM-R 7
RXM-R
2 Specifications
2-1 Specifications
Technical specifications FDXM25F9 + RXM25R FDXM35F9 + RXM35R FDXM50F9 + RXM50R FDXM60F9 + RXM60R
Space heating (Average TOL Tol (temperature operating limit) °C -15
climate) Pdh (declared heating cap) kW 1.93 2.15 3.54 3.72
2 COPd (declared COP)
Power input kW
2.20
0.88
2.01
1.07
1.89
1.87
1.91
1.95
TBivalent Tbiv (bivalent temperature) °C -7
Pdh (declared heating cap) kW 2.30 2.57 3.54 4.07
COPd (declared COP) 2.81 2.60 2.87 2.58
Power input kW 0.82 0.99 1.23 1.58
A Condition Pdh (declared heating cap) kW 2.30 2.57 3.54 4.07
(-7°C) COPd (declared COP) 2.81 2.60 2.87 2.58
Power input kW 0.82 0.99 1.23 1.58
B Condition Pdh (declared heating cap) kW 1.40 1.57 2.16 2.48
(2°C) COPd (declared COP) 4.21 3.84 4.10 3.92
Power input kW 0.33 0.41 0.53 0.63
C Condition Pdh (declared heating cap) kW 1.00 1.02 1.62
(7°C) COPd (declared COP) 5.54 4.94 4.56 4.52
Power input kW 0.18 0.21 0.36
D Condition Pdh (declared heating cap) kW 1.17 1.19 1.92
(12°C) COPd (declared COP) 6.84 6.08 5.49 5.46
Space heating (Average D Condition Power input kW 0.17 0.20 0.35
climate) (12°C)
Power consumption in Crankcase Cooling PCK kW - 0.000 -
other than active mode heater Heating PCK kW - 0.000 -
mode
Off mode Cooling POFF kW 14.0 0.014 -
Heating POFF kW 14.0 0.014 -
Standby Cooling PSB kW 14.0 0.014 -
mode Heating PSB kW 14.0 0.014 -
Thermo- Cooling PTO kW 7.0 0.007 -
stat-off Heating PTO kW 7.0 0.007 -
mode
Space heating (Warm TOL Tol (temperature operating limit) °C -15
climate) Pdh (declared heating cap) kW 1.93 2.15 3.54 3.72
COPd (declared COP) 2.20 2.01 1.89 1.91
Power input kW 0.88 1.07 1.87 1.95
TBivalent Tbiv (bivalent temperature) °C 2
Pdh (declared heating cap) kW 1.40 1.57 2.16 2.48
COPd (declared COP) 4.21 3.84 4.10 3.92
Power input kW 0.33 0.41 0.53 0.63
B Condition Pdh (declared heating cap) kW 1.40 1.57 2.16 2.48
(2°C) COPd (declared COP) 4.21 3.84 4.10 3.92
Power input kW 0.33 0.41 0.53 0.63
C Condition Pdh (declared heating cap) kW 1.00 1.02 1.62
(7°C) COPd (declared COP) 5.54 4.94 4.56 4.52
Power input kW 0.18 0.21 0.36
D Condition Pdh (declared heating cap) kW 1.17 1.19 1.92
(12°C) COPd (declared COP) 6.84 6.08 5.49 5.46
Power input kW 0.17 0.20 0.35
Power consumption in Thermo- PTO Heating W - 9
other than active mode stat-off Cooling W - 9
mode
Standby Cooling PSB W - 15
mode Heating PSB W - 15
Off mode POFF W - 15
Cooling Cdc (Degradation cooling) 0.25
Heating Cdh (Degradation heating) 0.25
Cooling function included Yes
Heating function included Yes
Average climate included Yes
Cold season included No
Warm season included Yes
Ecolabel logo No -
Eurovent Sound Cooling Nom. dBA 59 61 62 63
power level
outdoor
Sound Cooling Nom. dBA 53 55 56
power level
indoor
Piping Cooling Measuring condition m 5.0 5.00
length
Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. |
Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. |
See separate drawing for operation range |
See separate drawing for electrical data
8 RXM-R
RXM-R
2 Specifications
2-1 Specifications
Technical specifications FFA25A9 + RXM25R FFA35A9 + RXM35R FFA50A9 + RXM50R FFA60A9 + RXM60R
Cooling capacity Nom. kW 2.50 3.40 5.00 5.70
Nom. Btu/h 8,530 11,600 17,100 19,400
Heating capacity
Nom.
Nom.
kcal/h
kW
2,150
3.20
2,923
4.20
4,299
5.80
4,884
7.00
2
Nom. Btu/h 10,919 14,300 19,800 23,900
Nom. kcal/h 2,752 3,611 4,987 6,019
Power input Cooling Nom. kW 0.55 0.89 1.54 1.86
Heating Nom. kW 0.82 1.20 1.66 2.05
Nominal efficiency EER 4.57 3.81 3.24 3.05
COP 3.90 3.50 3.49 3.41
Annual energy consumption kWh 273 446 772 931
Energy Cooling A B
labeling Heating A B
Directive
Space cooling Energy efficiency class A++ A+
Capacity Pdesign kW 2.50 3.40 5.00 5.70
SEER 6.17 6.38 5.98 5.76
Annual energy consumption kWh/a 142 186 293 346
Space heating (Average Energy efficiency class A+ A A+
climate) Capacity Pdesign kW 2.31 3.10 3.84 3.96
SCOP/A 4.24 4.10 3.90 4.04
SCOPnet/A 4.27 4.19 3.92 4.06
Pdh Heating capacity at -10° kW 2.03 2.04 3.40 3.50
Annual energy consumption kWh/a 762 1,058 1,378 1,373
Required back up heating cap at design conditions kW 0.28 1.06 0.44 0.46
Space heating (Warm Energy efficiency class A+++ A++
climate) Capacity Pdesignh kW 1.24 2.09 2.14
SCOP 5.29 5.10 4.79 4.74
SCOPnet 5.37 5.18 4.83 4.79
Annual energy consumption kWh/a 329 341 611 631
Required back up heating cap at design conditions kW 0.00
Space cooling A Condition Pdc kW 2.50 3.40 5.00 5.70
(35°C - 27/19) EERd 4.57 3.81 3.24 3.05
Power input kW 0.55 0.89 1.54 1.86
B Condition Pdc kW 1.84 2.51 3.69 4.20
(30°C - 27/19) EERd 6.60 5.79 5.38 5.34
Power input kW 0.28 0.43 0.69 0.79
Space cooling C Condition Pdc kW 1.41 1.45 2.37 2.71
(25°C - 27/19) EERd 9.11 9.13 7.85 7.24
Power input kW 0.16 0.30 0.37
D Condition Pdc kW 1.24 1.26 2.15 2.27
(20°C - 27/19) EERd 11.95 11.99 10.67 9.66
Power input kW 0.10 0.11 0.20 0.23
Space heating (Average TOL Tol (temperature operating limit) °C -15
climate) Pdh (declared heating cap) kW 2.03 3.40 3.50
COPd (declared COP) 2.23 2.10 1.99 2.05
Power input kW 0.91 0.97 1.71
TBivalent Tbiv (bivalent temperature) °C -7
Pdh (declared heating cap) kW 2.04 3.40 3.51
COPd (declared COP) 3.00 2.89 2.62 2.84
Power input kW 0.68 0.71 1.30 1.24
A Condition Pdh (declared heating cap) kW 2.04 3.40 3.51
(-7°C) COPd (declared COP) 3.00 2.89 2.62 2.84
Power input kW 0.68 0.71 1.30 1.24
B Condition Pdh (declared heating cap) kW 1.24 2.09 2.14
(2°C) COPd (declared COP) 4.16 4.00 3.97 4.12
Power input kW 0.30 0.31 0.53 0.52
C Condition Pdh (declared heating cap) kW 1.03 1.47 1.49
(7°C) COPd (declared COP) 5.57 5.37 4.81 4.74
Power input kW 0.19 0.31
D Condition Pdh (declared heating cap) kW 1.21 1.71 1.74
(12°C) COPd (declared COP) 6.90 6.65 5.94 5.88
Power input kW 0.18 0.29 0.30
Power consumption in Crankcase Cooling PCK kW - 0.000 -
other than active mode heater Heating PCK kW - 0.000 -
mode
Off mode Cooling POFF kW 14.0 0.014 -
Heating POFF kW 14.0 0.014 -
Standby Cooling PSB kW 14.0 0.014 -
mode Heating PSB kW 14.0 0.014 -
Thermo- Cooling PTO kW 7.0 0.007 -
stat-off Heating PTO kW 7.0 0.007 -
mode
RXM-R 9
RXM-R
2 Specifications
2-1 Specifications
Technical specifications FFA25A9 + RXM25R FFA35A9 + RXM35R FFA50A9 + RXM50R FFA60A9 + RXM60R
Space heating (Warm TOL Tol (temperature operating limit) °C -15
climate) Pdh (declared heating cap) kW 2.03 3.40 3.50
2 Space heating (Warm TOL
COPd (declared COP)
Power input kW
2.23
0.91
2.10
0.97
1.99
1.71
2.05
Technical specifications FNA25A9 + RXM25R FNA35A9 + RXM35R FNA50A9 + RXM50R FNA60A9 + RXM60R
Cooling capacity Nom. kW 2.60 3.40 5.00 6.00
Nom. Btu/h 8,872 11,600 17,100 20,500
Nom. kcal/h 2,236 2,923 4,299 5,159
Heating capacity Nom. kW 3.20 4.00 5.80 7.00
Nom. Btu/h 10,919 13,600 19,800 23,900
Nom. kcal/h 2,752 3,439 4,987 6,019
Power input Cooling Nom. kW 0.68 1.10 1.48 2.22
Heating Nom. kW 0.80 1.15 1.74 2.25
Nominal efficiency EER 3.80 3.09 3.38 2.70
COP 4.00 3.48 3.34 3.11
Annual energy consumption kWh 342 550 740 1,111
Energy Cooling A B A D
labeling Heating A B C D
Directive
Space cooling Energy efficiency class A+ A
Capacity Pdesign kW 2.60 3.40 5.00 6.00
SEER 5.68 5.70 5.77 5.56
Annual energy consumption kWh/a 160 209 303 378
Space heating (Average Energy efficiency class A+
climate) Capacity Pdesign kW 2.80 2.90 4.00 4.60
SCOP/A 4.24 4.05 4.09 4.16
SCOPnet/A 4.28 4.08 4.12 4.19
Pdh Heating capacity at -10° kW 2.16 2.41 3.54 3.94
Annual energy consumption kWh/a 924 1,002 1,368 1,547
Required back up heating cap at design conditions kW 0.64 0.49 0.46 0.66
10 RXM-R
RXM-R
2 Specifications
2-1 Specifications
Technical specifications FNA25A9 + RXM25R FNA35A9 + RXM35R FNA50A9 + RXM50R FNA60A9 + RXM60R
Space heating (Warm Energy efficiency class A+++ A++
climate) Capacity Pdesignh kW 1.51 1.57 2.16 2.48
SCOP
SCOPnet
5.43
5.50
5.10
5.17
4.88
4.93
5.02
5.08
2
Annual energy consumption kWh/a 389 431 620 691
Required back up heating cap at design conditions kW 0.00
Space cooling A Condition Pdc kW 2.60 3.40 5.00 6.00
(35°C - 27/19) EERd 3.80 3.09 3.38 2.70
Power input kW 0.68 1.10 1.48 2.22
B Condition Pdc kW 1.92 2.50 3.69 4.43
(30°C - 27/19) EERd 5.17 4.41 5.02 4.64
Power input kW 0.37 0.57 0.74 0.95
Space cooling C Condition Pdc kW 1.27 1.61 2.37 2.85
(25°C - 27/19) EERd 8.97 9.38 7.23 7.20
Power input kW 0.14 0.17 0.33 0.40
D Condition Pdc kW 1.33 1.46 1.74 2.34
(20°C - 27/19) EERd 10.18 10.14 10.72 10.44
Power input kW 0.13 0.14 0.16 0.22
Space heating (Average TOL Tol (temperature operating limit) °C -15
climate) Pdh (declared heating cap) kW 1.93 2.15 3.54 3.72
COPd (declared COP) 2.20 2.21 1.88 1.78
Power input kW 0.88 0.97 1.88 2.09
TBivalent Tbiv (bivalent temperature) °C -7
Pdh (declared heating cap) kW 2.48 2.57 3.54 4.07
COPd (declared COP) 2.80 2.71 2.90 2.82
Power input kW 0.89 0.95 1.22 1.44
A Condition Pdh (declared heating cap) kW 2.48 2.57 3.54 4.07
(-7°C) COPd (declared COP) 2.80 2.71 2.90 2.82
Power input kW 0.89 0.95 1.22 1.44
B Condition Pdh (declared heating cap) kW 1.51 1.57 2.16 2.48
(2°C) COPd (declared COP) 4.18 4.01 4.13 4.22
Power input kW 0.36 0.39 0.52 0.59
C Condition Pdh (declared heating cap) kW 1.00 1.02 1.66 1.59
(7°C) COPd (declared COP) 5.51 5.16 5.08
Power input kW 0.18 0.20 0.33 0.31
D Condition Pdh (declared heating cap) kW 1.17 1.19 1.96 1.95
(12°C) COPd (declared COP) 6.80 6.35 6.16 6.19
Power input kW 0.17 0.19 0.32
Power consumption in Crankcase Cooling PCK kW - 0.000 -
other than active mode heater Heating PCK kW - 0.000 -
mode
Off mode Cooling POFF kW 14.0 0.014 -
Heating POFF kW 14.0 0.014 -
Standby Cooling PSB kW 14.0 0.014 -
mode Heating PSB kW 14.0 0.014 -
Thermo- Cooling PTO kW 7.0 0.007 -
stat-off Heating PTO kW 7.0 0.007 -
mode
Space heating (Warm TOL Tol (temperature operating limit) °C -15
climate) Pdh (declared heating cap) kW 1.93 2.15 3.54 3.72
COPd (declared COP) 2.20 2.21 1.88 1.78
Space heating (Warm TOL Power input kW 0.88 0.97 1.88 2.09
climate) TBivalent Tbiv (bivalent temperature) °C 2
Pdh (declared heating cap) kW 1.51 1.57 2.16 2.48
COPd (declared COP) 4.18 4.01 4.13 4.22
Power input kW 0.36 0.39 0.52 0.59
B Condition Pdh (declared heating cap) kW 1.51 1.57 2.16 2.48
(2°C) COPd (declared COP) 4.18 4.01 4.13 4.22
Power input kW 0.36 0.39 0.52 0.59
C Condition Pdh (declared heating cap) kW 1.00 1.02 1.66 1.59
(7°C) COPd (declared COP) 5.51 5.16 5.08
Power input kW 0.18 0.20 0.33 0.31
D Condition Pdh (declared heating cap) kW 1.17 1.19 1.96 1.95
(12°C) COPd (declared COP) 6.80 6.35 6.16 6.19
Power input kW 0.17 0.19 0.32
Power consumption in Thermo- PTO Heating W - 9
other than active mode stat-off Cooling W - 9
mode
Standby Cooling PSB W - 15
mode Heating PSB W - 15
Off mode POFF W - 15
Cooling Cdc (Degradation cooling) 0.25
Heating Cdh (Degradation heating) 0.25
RXM-R 11
R
XM-R
2 Specifications
2-1 Specifications
Technical specifications FNA25A9 + RXM25R FNA35A9 + RXM35R FNA50A9 + RXM50R FNA60A9 + RXM60R
Cooling function included Yes
Heating function included Yes
2 Average climate included
Cold season included
Yes
No
Warm season included Yes
Ecolabel logo No -
Eurovent Sound Cooling Nom. dBA 59 61 62 63
power level
outdoor
Sound Cooling Nom. dBA 53 56
power level
indoor
Piping Cooling Measuring condition m 5.0 5.00
length
Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. |
Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. |
See separate drawing for operation range |
See separate drawing for electrical data
12 R
XM-R
R
XM-R
2 Specifications
2-1 Specifications
Technical specifications FBA35A9 + RXM35R FBA50A9 + RXM50R FBA60A9 + RXM60R
Space heating (Average TOL Tol (temperature operating limit) °C -15
climate) Pdh (declared heating cap) kW 2.15 3.47 3.85
COPd (declared COP)
Power input kW
2.37
0.91
1.95
1.78
2.11
1.82
2
TBivalent Tbiv (bivalent temperature) °C -7
Pdh (declared heating cap) kW 2.57 3.90 4.09
COPd (declared COP) 2.73 3.09 3.01
Power input kW 0.94 1.26 1.36
A Condition Pdh (declared heating cap) kW 2.57 3.90 4.09
(-7°C) COPd (declared COP) 2.73 3.09 3.01
Power input kW 0.94 1.26 1.36
B Condition Pdh (declared heating cap) kW 1.57 2.37 2.44
(2°C) COPd (declared COP) 4.03 4.20 4.18
Power input kW 0.39 0.56 0.58
C Condition Pdh (declared heating cap) kW 1.02 1.61 1.60
(7°C) COPd (declared COP) 5.18 4.55 4.41
Power input kW 0.20 0.35 0.36
D Condition Pdh (declared heating cap) kW 1.19 1.58 1.79
(12°C) COPd (declared COP) 6.38 5.23 5.32
Power input kW 0.19 0.30 0.34
Power consumption in Crankcase Cooling PCK kW 0.000 -
other than active mode heater Heating PCK kW 0.000 -
mode
Off mode Cooling POFF kW 0.007 -
Heating POFF kW 0.007 -
Standby Cooling PSB kW 0.007 -
mode Heating PSB kW 0.007 -
Thermo- Cooling PTO kW 0.007 -
stat-off Heating PTO kW 0.007 -
mode
Space heating (Warm TOL Tol (temperature operating limit) °C -15
climate) Pdh (declared heating cap) kW 2.15 3.47 3.85
COPd (declared COP) 2.37 1.95 2.11
Space heating (Warm TOL Power input kW 0.91 1.78 1.82
climate) TBivalent Tbiv (bivalent temperature) °C 2
Pdh (declared heating cap) kW 1.57 2.37 2.48
COPd (declared COP) 4.03 4.20 4.18
Power input kW 0.39 0.56 0.59
B Condition Pdh (declared heating cap) kW 1.57 2.37 2.44
(2°C) COPd (declared COP) 4.03 4.20 4.18
Power input kW 0.39 0.56 0.58
C Condition Pdh (declared heating cap) kW 1.02 1.61 1.60
(7°C) COPd (declared COP) 5.18 4.55 4.41
Power input kW 0.20 0.35 0.36
D Condition Pdh (declared heating cap) kW 1.19 1.58 1.79
(12°C) COPd (declared COP) 6.38 5.23 5.32
Power input kW 0.19 0.30 0.34
Power consumption in Thermo- PTO Heating W - 2
other than active mode stat-off Cooling W - 2
mode
Standby Cooling PSB W - 13
mode Heating PSB W - 13
Off mode POFF W - 13
Cooling Cdc (Degradation cooling) 0.25
Heating Cdh (Degradation heating) 0.25
Cooling function included Yes
Heating function included Yes
Average climate included Yes
Cold season included No
Warm season included Yes
Eurovent Sound Cooling Nom. dBA 61 62 63
power level
outdoor
Sound Cooling Nom. dBA 60 56
power level
indoor
Piping Cooling Measuring condition m 5.00
length
Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. |
Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. |
See separate drawing for operation range |
See separate drawing for electrical data
R
XM-R 13
RXM-R
2 Specifications
2-1 Specifications
Technical specifications FVXM25A + RXM25R FVXM35A + RXM35R FVXM50A + RXM50R
Cooling capacity Min. kW 1.30 1.40
Min. Btu/h 4,400 4,800
2 Min.
Nom.
kcal/h
kW
1,118
2.40 3.40
1,204
5.00
Nom. Btu/h 8,200 11,600 17,100
Nom. kcal/h 2,064 2,923 4,299
Max. kW 3.50 4.00 5.80
Max. Btu/h 11,900 13,600 19,800
Max. kcal/h 3,009 3,439 4,987
Cooling capacity - Low Min. kcal/h -
sound mode (Stb. 2020, Max. kcal/h -
189)
Heating capacity Min. kW 1.30 1.40
Min. Btu/h 4,400 4,800
Min. kcal/h 1,100 1,200
Nom. kW 3.40 4.50 5.80
Nom. Btu/h 11,600 15,400 19,800
Nom. kcal/h 2,923 3,869 4,987
Max. kW 4.70 5.80 8.10
Max. Btu/h 16,000 19,800 27,600
Max. kcal/h 4,041 4,987 6,965
Power input Cooling Nom. kW 0.54 0.85 1.31
Heating Nom. kW 0.75 1.15 1.52
Nominal efficiency EER 4.47 4.01 3.81
COP 4.55 3.90 3.81
Annual energy consumption kWh 268 424 656
Energy Cooling A
labeling Heating A
Directive
Space cooling Energy efficiency class A+++ A++
Capacity Pdesign kW 2.40 3.40 5.00
SEER 8.55 8.11 7.30
Annual energy consumption kWh/a 98 147 240
Space heating (Average Capacity Pdesign kW 2.30 2.80 4.10
climate) Energy efficiency class A++ A+
SCOP/A 4.65 4.63 4.31
SCOPnet/A 4.68 4.67 4.35
Pdh Heating capacity at -10° kW 2.03 2.34 3.58
Space heating (Average Annual energy consumption kWh/a 693 847 1,330
climate) Required back up heating cap at design conditions kW 0.27 0.46 0.52
Space heating (Warm Capacity Pdesignh kW 1.24 1.51 2.21
climate) Energy efficiency class A+++ A++
SCOP 5.50 5.71 4.85
SCOPnet 5.61 5.80 4.94
Annual energy consumption kWh/a 316 370 638
Required back up heating cap at design conditions kW 0.00
Space cooling A Condition Pdc kW 2.40 3.40 5.00
(35°C - 27/19) EERd 4.47 4.01 3.81
Power input kW 0.54 0.85 1.31
B Condition Pdc kW 1.77 2.51 3.69
(30°C - 27/19) EERd 6.50 5.82 5.49
Power input kW 0.27 0.43 0.67
C Condition Pdc kW 1.23 1.62 2.37
(25°C - 27/19) EERd 10.51 9.63 8.59
Power input kW 0.12 0.17 0.28
D Condition Pdc kW 1.18 1.12 2.20
(20°C - 27/19) EERd 14.90 15.17 12.51
Power input kW 0.08 0.07 0.18
14 RXM-R
RXM-R
2 Specifications
2-1 Specifications
Technical specifications FVXM25A + RXM25R FVXM35A + RXM35R FVXM50A + RXM50R
Space heating (Average TOL Tol (temperature operating limit) °C -15
climate) Pdh (declared heating cap) kW 2.01 2.12 3.49
COPd (declared COP)
Power input kW
2.24
0.90
1.94
1.09
1.82
1.92
2
TBivalent Tbiv (bivalent temperature) °C -7
Pdh (declared heating cap) kW 2.04 2.48 3.63
COPd (declared COP) 3.46 3.24 3.16
Power input kW 0.59 0.77 1.15
A Condition Pdh (declared heating cap) kW 2.04 2.48 3.63
(-7°C) COPd (declared COP) 3.46 3.24 3.16
Power input kW 0.59 0.77 1.15
B Condition Pdh (declared heating cap) kW 1.24 1.51 2.21
(2°C) COPd (declared COP) 4.67 4.58 4.45
Power input kW 0.27 0.33 0.50
C Condition Pdh (declared heating cap) kW 1.02 1.03 1.67
(7°C) COPd (declared COP) 5.67 5.80 5.15
Power input kW 0.18 0.32
Space heating (Average D Condition Pdh (declared heating cap) kW 1.06 1.18 1.84
climate) (12°C) COPd (declared COP) 7.16 7.13 5.98
Power input kW 0.15 0.17 0.31
Space heating (Warm TOL Tol (temperature operating limit) °C -15
climate) Pdh (declared heating cap) kW 2.01 2.12 3.49
COPd (declared COP) 2.24 1.94 1.82
Power input kW 0.90 1.09 1.92
TBivalent Tbiv (bivalent temperature) °C 2
Pdh (declared heating cap) kW 1.24 1.51 2.21
COPd (declared COP) 4.67 4.58 4.45
Power input kW 0.27 0.33 0.50
B Condition Pdh (declared heating cap) kW 1.24 1.51 2.21
(2°C) COPd (declared COP) 4.67 4.58 4.45
Power input kW 0.27 0.33 0.50
C Condition Pdh (declared heating cap) kW 1.02 1.03 1.67
(7°C) COPd (declared COP) 5.67 5.80 5.15
Power input kW 0.18 0.32
D Condition Pdh (declared heating cap) kW 1.06 1.18 1.84
(12°C) COPd (declared COP) 7.16 7.13 5.98
Power input kW 0.15 0.17 0.31
Power consumption in Crankcase PCK W 0
other than active mode heater
mode
Off mode POFF W 1
Standby Cooling PSB W 1
mode Heating PSB W 1
Thermo- PTO Cooling W 6 7
stat-off Heating W 8 15
mode
Cooling Cdc (Degradation cooling) 0.25
Heating Cdh (Degradation heating) 0.25
Cooling function included Yes
Heating function included Yes
Average climate included Yes
Cold season included No
Warm season included Yes
Eurovent Sound Cooling Nom. dBA 59 61 62
power level
outdoor
Sound Cooling Nom. dBA 52 53 61
power level
indoor
Piping Cooling Measuring condition m 5.00
length
RXM-R 15
RXM-R
2 Specifications
2-1 Specifications
Technical specifications FVXM25A9 + RXM25R FVXM35A9 + RXM35R FVXM50A9 + RXM50R
Cooling capacity Min. kW 1.30 1.40
Min. Btu/h 4,400 4,800
2 Min.
Nom.
kcal/h
kW
1,118
2.40 3.40
1,204
5.00
Nom. Btu/h 8,200 11,600 17,100
Nom. kcal/h 2,064 2,923 4,299
Max. kW 3.50 4.00 5.80
Max. Btu/h 11,900 13,600 19,800
Max. kcal/h 3,009 3,439 4,987
Cooling capacity - Low Min. kcal/h -
sound mode (Stb. 2020, Max. kcal/h -
189)
Heating capacity Min. kW 1.30 1.40
Min. Btu/h 4,400 4,800
Min. kcal/h 1,100 1,200
Nom. kW 3.40 4.50 5.80
Nom. Btu/h 11,600 15,400 19,800
Nom. kcal/h 2,923 3,869 4,987
Max. kW 4.70 5.80 8.10
Max. Btu/h 16,000 19,800 27,600
Max. kcal/h 4,041 4,987 6,965
Power input Cooling Nom. kW 0.54 0.85 1.31
Heating Nom. kW 0.75 1.15 1.52
Nominal efficiency EER 4.47 4.01 3.81
COP 4.55 3.90 3.81
Annual energy consumption kWh 268 424 656
Energy Cooling A
labeling Heating A
Directive
Space cooling Energy efficiency class A+++ A++
Capacity Pdesign kW 2.40 3.40 5.00
SEER 8.55 8.11 7.30
Annual energy consumption kWh/a 98 147 240
Space heating (Average Capacity Pdesign kW 2.30 2.80 4.10
climate) Energy efficiency class A++ A+
SCOP/A 4.65 4.63 4.31
SCOPnet/A 4.68 4.67 4.35
Pdh Heating capacity at -10° kW 2.03 2.34 3.58
Space heating (Average Annual energy consumption kWh/a 693 847 1,330
climate) Required back up heating cap at design conditions kW 0.27 0.46 0.52
Space heating (Warm Capacity Pdesignh kW 1.24 1.51 2.21
climate) Energy efficiency class A+++ A++
SCOP 5.50 5.71 4.85
SCOPnet 5.61 5.80 4.94
Annual energy consumption kWh/a 316 370 638
Required back up heating cap at design conditions kW 0.00
Space cooling A Condition Pdc kW 2.40 3.40 5.00
(35°C - 27/19) EERd 4.47 4.01 3.81
Power input kW 0.54 0.85 1.31
B Condition Pdc kW 1.77 2.51 3.69
(30°C - 27/19) EERd 6.50 5.82 5.49
Power input kW 0.27 0.43 0.67
C Condition Pdc kW 1.23 1.62 2.37
(25°C - 27/19) EERd 10.51 9.63 8.59
Power input kW 0.12 0.17 0.28
D Condition Pdc kW 1.18 1.12 2.20
(20°C - 27/19) EERd 14.90 15.17 12.51
Power input kW 0.08 0.07 0.18
16 RXM-R
RXM-R
2 Specifications
2-1 Specifications
Technical specifications FVXM25A9 + RXM25R FVXM35A9 + RXM35R FVXM50A9 + RXM50R
Space heating (Average TOL Tol (temperature operating limit) °C -15
climate) Pdh (declared heating cap) kW 2.01 2.12 3.49
COPd (declared COP)
Power input kW
2.24
0.90
1.94
1.09
1.82
1.92
2
TBivalent Tbiv (bivalent temperature) °C -7
Pdh (declared heating cap) kW 2.04 2.48 3.63
COPd (declared COP) 3.46 3.24 3.16
Power input kW 0.59 0.77 1.15
A Condition Pdh (declared heating cap) kW 2.04 2.48 3.63
(-7°C) COPd (declared COP) 3.46 3.24 3.16
Power input kW 0.59 0.77 1.15
B Condition Pdh (declared heating cap) kW 1.24 1.51 2.21
(2°C) COPd (declared COP) 4.67 4.58 4.45
Power input kW 0.27 0.33 0.50
C Condition Pdh (declared heating cap) kW 1.02 1.03 1.67
(7°C) COPd (declared COP) 5.67 5.80 5.15
Power input kW 0.18 0.32
Space heating (Average D Condition Pdh (declared heating cap) kW 1.06 1.18 1.84
climate) (12°C) COPd (declared COP) 7.16 7.13 5.98
Power input kW 0.15 0.17 0.31
Space heating (Warm TOL Tol (temperature operating limit) °C -15
climate) Pdh (declared heating cap) kW 2.01 2.12 3.49
COPd (declared COP) 2.24 1.94 1.82
Power input kW 0.90 1.09 1.92
TBivalent Tbiv (bivalent temperature) °C 2
Pdh (declared heating cap) kW 1.24 1.51 2.21
COPd (declared COP) 4.67 4.58 4.45
Power input kW 0.27 0.33 0.50
B Condition Pdh (declared heating cap) kW 1.24 1.51 2.21
(2°C) COPd (declared COP) 4.67 4.58 4.45
Power input kW 0.27 0.33 0.50
C Condition Pdh (declared heating cap) kW 1.02 1.03 1.67
(7°C) COPd (declared COP) 5.67 5.80 5.15
Power input kW 0.18 0.32
D Condition Pdh (declared heating cap) kW 1.06 1.18 1.84
(12°C) COPd (declared COP) 7.16 7.13 5.98
Power input kW 0.15 0.17 0.31
Power consumption in Crankcase PCK W 0
other than active mode heater
mode
Off mode POFF W 1
Standby Cooling PSB W 1
mode Heating PSB W 1
Thermo- PTO Cooling W 6 7
stat-off Heating W 8 15
mode
Cooling Cdc (Degradation cooling) 0.25
Heating Cdh (Degradation heating) 0.25
Cooling function included Yes
Heating function included Yes
Average climate included Yes
Cold season included No
Warm season included Yes
Eurovent Sound Cooling Nom. dBA 59 61 62
power level
outdoor
Sound Cooling Nom. dBA 52 53 61
power level
indoor
Piping Cooling Measuring condition m 5.00
length
RXM-R 17
RXM-R
2 Specifications
2-1 Specifications
Technical specifications FCAG35B + RXM35R FCAG50B + RXM50R FCAG60B + RXM60R
Cooling capacity Nom. kW 3.50 5.00 5.70
Nom. Btu/h 11,900 17,100 19,400
2 Cooling capacity - Low
Nom.
Min.
kcal/h
kcal/h
3,009 4,299
-
4,884
18 RXM-R
RXM-R
2 Specifications
2-1 Specifications
Technical specifications FCAG35B + RXM35R FCAG50B + RXM50R FCAG60B + RXM60R
Space heating (Warm TOL Tol (temperature operating limit) °C -15
climate) Pdh (declared heating cap) kW 2.04 3.86 4.04
COPd (declared COP)
Power input kW
2.50
0.82
2.04
1.89
2.08
1.94
2
TBivalent Tbiv (bivalent temperature) °C 2
Pdh (declared heating cap) kW 1.79 2.35 2.54
COPd (declared COP) 4.98 4.39 4.31
Power input kW 0.36 0.54 0.59
B Condition Pdh (declared heating cap) kW 1.79 2.35 2.54
(2°C)
Space heating (Warm B Condition COPd (declared COP) 4.98 4.39 4.31
climate) (2°C) Power input kW 0.36 0.54 0.59
C Condition Pdh (declared heating cap) kW 1.15 1.54 1.64
(7°C) COPd (declared COP) 6.20 5.31 5.28
Power input kW 0.19 0.29 0.31
D Condition Pdh (declared heating cap) kW 1.24 1.79 1.46
(12°C) COPd (declared COP) 7.88 6.47 6.51
Power input kW 0.16 0.28 0.22
Power consumption in Off mode POFF W - 8
other than active mode Standby Cooling PSB W - 8
mode Heating PSB W - 8
Thermo- PTO Cooling W - 5
stat-off Heating W - 15
mode
Cooling Cdc (Degradation cooling) 0.25
Heating Cdh (Degradation heating) 0.25
Cooling function included Yes
Heating function included Yes
Average climate included Yes
Cold season included No
Warm season included Yes
Eurovent Sound Cooling Nom. dBA 61 62 63
power level
outdoor
Sound Cooling Nom. dBA 49 51
power level
indoor
Piping Cooling Measuring condition m 5.00
length
Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. |
Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. |
See separate drawing for operation range |
See separate drawing for electrical data
RXM-R 19
RXM-R
2 Specifications
2-1 Specifications
Technical specifications FHA35A9 + RXM35R FHA50A9 + RXM50R FHA60A9 + RXM60R
Space heating (Warm Capacity Pdesignh kW 1.67 2.35 2.54
climate) Energy efficiency class A+++ A+ A++
2 SCOP
SCOPnet
5.72
5.83
4.59
4.64
4.61
4.67
Annual energy consumption kWh/a 409 716 771
Required back up heating cap at design conditions kW 0.00
Space cooling A Condition Pdc kW 3.40 5.00 5.70
(35°C - 27/19) EERd 3.73 3.21 3.29
Power input kW 0.91 1.56 1.73
B Condition Pdc kW 2.51 3.69 4.20
(30°C - 27/19)
Space cooling B Condition EERd 5.28 5.04 4.88
(30°C - 27/19) Power input kW 0.48 0.73 0.86
C Condition Pdc kW 1.68 2.37 2.71
(25°C - 27/19) EERd 9.59 8.25 8.34
Power input kW 0.18 0.29 0.33
D Condition Pdc kW 1.64 2.31 2.26
(20°C - 27/19) EERd 11.71 10.39 10.97
Power input kW 0.14 0.22 0.21
Space heating (Average TOL Tol (temperature operating limit) °C -15
climate) Pdh (declared heating cap) kW 2.47 3.85 3.92
COPd (declared COP) 2.23 1.97
Power input kW 1.11 1.95 1.99
TBivalent Tbiv (bivalent temperature) °C -7
Pdh (declared heating cap) kW 2.74 3.85 4.12
COPd (declared COP) 2.94 2.61 2.64
Power input kW 0.93 1.48 1.56
A Condition Pdh (declared heating cap) kW 2.74 3.85 4.17
(-7°C) COPd (declared COP) 2.94 2.61 2.64
Power input kW 0.93 1.48 1.56
B Condition Pdh (declared heating cap) kW 1.67 2.35 2.54
(2°C) COPd (declared COP) 4.32 3.95 3.96
Power input kW 0.39 0.59 0.64
C Condition Pdh (declared heating cap) kW 1.14 1.54 1.63
(7°C) COPd (declared COP) 5.83 4.62 4.60
Power input kW 0.20 0.33 0.35
D Condition Pdh (declared heating cap) kW 1.34 1.80 1.74
(12°C) COPd (declared COP) 7.24 5.65
Power input kW 0.19 0.32 0.31
Space heating (Warm TOL Tol (temperature operating limit) °C -15
climate) Pdh (declared heating cap) kW 2.47 3.85 3.92
COPd (declared COP) 2.23 1.97
Power input kW 1.11 1.95 1.99
TBivalent Tbiv (bivalent temperature) °C 2
Pdh (declared heating cap) kW 1.67 2.35 2.54
COPd (declared COP) 4.32 3.95 3.96
Power input kW 0.39 0.59 0.64
B Condition Pdh (declared heating cap) kW 1.67 2.35 2.54
(2°C)
Space heating (Warm B Condition COPd (declared COP) 4.32 3.95 3.96
climate) (2°C) Power input kW 0.39 0.59 0.64
C Condition Pdh (declared heating cap) kW 1.14 1.54 1.63
(7°C) COPd (declared COP) 5.83 4.62 4.60
Power input kW 0.20 0.33 0.35
D Condition Pdh (declared heating cap) kW 1.34 1.80 1.74
(12°C) COPd (declared COP) 7.24 5.65
Power input kW 0.19 0.32 0.31
Power consumption in Crankcase PCK W - 0
other than active mode heater
mode
Off mode POFF W - 15
Standby Cooling PSB W - 15
mode Heating PSB W - 15
Thermo- PTO Cooling W - 10
stat-off Heating W - 10
mode
Cooling Cdc (Degradation cooling) 0.25
Heating Cdh (Degradation heating) 0.25
Cooling function included Yes
Heating function included Yes
Average climate included Yes
Cold season included No
Warm season included Yes
20 RXM-R
RXM-R
2 Specifications
2-1 Specifications
Technical specifications FHA35A9 + RXM35R FHA50A9 + RXM50R FHA60A9 + RXM60R
Eurovent Sound Cooling Nom. dBA 61 62 63
power level
outdoor
Sound Cooling Nom. dBA 53 54
2
power level
indoor
Piping Cooling Measuring condition m 5.00
length
Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. |
Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. |
See separate drawing for operation range |
See separate drawing for electrical data
RXM-R 21
RXM-R
2 Specifications
2-1 Specifications
FTXM20R + FTXM25R + FTXM35R + FTXM42R + FTXM50R + FTXM60R +
Technical specifications
RXM20R RXM25R RXM35R RXM42R RXM50R RXM60R
Space heating (Average TOL Tol (temperature operating limit) °C -20
2 climate) Pdh (declared heating cap) kW 2.14 2.67 3.12
COPd (declared COP) 2.29 2.50 1.99 2.04
Power input kW 0.93 0.86 1.34 1.53
TBivalent Tbiv (bivalent temperature) °C -7
Pdh (declared heating cap) kW 2.04 2.13 2.22 3.76 4.07 4.26
COPd (declared COP) 3.51 3.60 3.55 3.16 2.95 2.68
Power input kW 0.58 0.59 0.63 1.19 1.38 1.59
A Condition Pdh (declared heating cap) kW 2.04 2.13 2.22 3.76 4.07 4.26
(-7°C) COPd (declared COP) 3.51 3.60 3.55 3.16 2.95 2.68
Power input kW 0.58 0.59 0.63 1.19 1.38 1.59
B Condition Pdh (declared heating cap) kW 1.24 1.29 1.35 2.16 2.48 2.63
(2°C) COPd (declared COP) 5.16 5.14 5.11 4.54 4.80 4.31
Power input kW 0.24 0.25 0.26 0.48 0.52 0.61
C Condition Pdh (declared heating cap) kW 0.96 0.94 0.93 1.43 1.70 1.67
(7°C) COPd (declared COP) 6.34 6.26 6.25 6.32 6.02 5.64
Power input kW 0.15 0.23 0.28 0.30
Space heating (Average D Condition Pdh (declared heating cap) kW 0.99 1.08 1.54 1.98 1.96
climate) (12°C) COPd (declared COP) 7.99 7.85 7.72 7.69 7.18 6.82
Power input kW 0.12 0.14 0.20 0.28 0.29
Space heating (Warm TOL Tol (temperature operating limit) °C -20
climate) Pdh (declared heating cap) kW 2.14 2.67 3.12
COPd (declared COP) 2.29 2.50 1.99 2.04
Power input kW 0.93 0.86 1.34 1.53
TBivalent Tbiv (bivalent temperature) °C 2
Pdh (declared heating cap) kW 1.24 1.29 1.35 2.16 2.48 2.63
COPd (declared COP) 5.16 5.14 5.11 4.54 4.80 4.31
Power input kW 0.24 0.25 0.26 0.48 0.52 0.61
B Condition Pdh (declared heating cap) kW 1.24 1.29 1.35 2.16 2.48 2.63
(2°C) COPd (declared COP) 5.16 5.14 5.11 4.54 4.80 4.31
Power input kW 0.24 0.25 0.26 0.48 0.52 0.61
C Condition Pdh (declared heating cap) kW 0.96 0.94 0.93 1.43 1.70 1.67
(7°C) COPd (declared COP) 6.34 6.26 6.25 6.32 6.02 5.64
Power input kW 0.15 0.23 0.28 0.30
D Condition Pdh (declared heating cap) kW 0.99 1.08 1.54 1.98 1.96
(12°C) COPd (declared COP) 7.99 7.85 7.72 7.69 7.18 6.82
Power input kW 0.12 0.14 0.20 0.28 0.29
Power consumption in Crankcase PCK W 0
other than active mode heater
mode
Off mode POFF W 1
Standby Cooling PSB W 1
mode Heating PSB W 1
Thermo- PTO Cooling W 6 7 12
stat-off Heating W 7 13 14
mode
Cooling Cdc (Degradation cooling) 0.25
Heating Cdh (Degradation heating) 0.25
Cooling function included Yes
Heating function included Yes
Average climate included Yes
Cold season included No
Warm season included Yes
Eurovent Sound Cooling Nom. dBA 59 58 61 62 63
power level
outdoor
Sound Cooling Nom. dBA 57 58 60 58 60
power level
indoor
Piping Cooling Measuring condition m 5.00
length
22 RXM-R
RXM-R
2 Specifications
2-1 Specifications
Technical specifications FTXM71R + RXM71R
Cooling capacity Min. kW 2.30
Min. Btu/h 7,800
Min.
Nom.
kcal/h
kW
1,978
7.10
2
Nom. Btu/h 24,200
Nom. kcal/h 6,105
Max. kW 8.50
Max. Btu/h 29,000
Max. kcal/h 7,309
Cooling capacity - Low Min. kcal/h -
sound mode (Stb. 2020, Max. kcal/h -
189)
Heating capacity Min. kW 2.30
Min. Btu/h 7,800
Min. kcal/h 2,000
Nom. kW 8.20
Nom. Btu/h 28,000
Nom. kcal/h 7,051
Max. kW 10.20
Max. Btu/h 34,800
Max. kcal/h 8,770
Power input Cooling Nom. kW 2.34
Heating Nom. kW 2.57
Nominal efficiency EER 3.03
COP 3.19
Annual energy consumption kWh 1,172
Energy Cooling B
labeling Heating D
Directive
Space cooling Energy efficiency class A++
Capacity Pdesign kW 7.10
SEER 6.20
Annual energy consumption kWh/a 401
Space heating (Average Capacity Pdesign kW 6.20
climate) Energy efficiency class A+
SCOP/A 4.10
SCOPnet/A 4.13
Pdh Heating capacity at -10° kW 5.01
Space heating (Average Annual energy consumption kWh/a 2,117
climate) Required back up heating cap at design conditions kW 1.19
Space heating (Warm Capacity Pdesignh kW 3.34
climate) Energy efficiency class A+++
SCOP 5.74
SCOPnet 5.81
Annual energy consumption kWh/a 814
Required back up heating cap at design conditions kW 0.00
Space cooling A Condition Pdc kW 7.10
(35°C - 27/19) EERd 3.03
Power input kW 2.34
B Condition Pdc kW 5.24
(30°C - 27/19) EERd 4.88
Power input kW 1.07
C Condition Pdc kW 3.37
(25°C - 27/19) EERd 7.39
Power input kW 0.46
D Condition Pdc kW 2.60
(20°C - 27/19) EERd 9.69
Power input kW 0.27
RXM-R 23
RXM-R
2 Specifications
2-1 Specifications
Technical specifications FTXM71R + RXM71R
Space heating (Average TOL Tol (temperature operating limit) °C -15
climate) Pdh (declared heating cap) kW 4.23
2 COPd (declared COP)
Power input kW
1.75
2.42
TBivalent Tbiv (bivalent temperature) °C -7
Pdh (declared heating cap) kW 5.49
COPd (declared COP) 2.14
Power input kW 2.57
A Condition Pdh (declared heating cap) kW 5.49
(-7°C) COPd (declared COP) 2.14
Power input kW 2.57
B Condition Pdh (declared heating cap) kW 3.34
(2°C) COPd (declared COP) 4.18
Power input kW 0.80
C Condition Pdh (declared heating cap) kW 2.32
(7°C) COPd (declared COP) 5.80
Power input kW 0.40
Space heating (Average D Condition Pdh (declared heating cap) kW 2.38
climate) (12°C) COPd (declared COP) 7.17
Power input kW 0.33
Space heating (Warm TOL Tol (temperature operating limit) °C -15
climate) Pdh (declared heating cap) kW 4.23
COPd (declared COP) 1.75
Power input kW 2.42
TBivalent Tbiv (bivalent temperature) °C 2
Pdh (declared heating cap) kW 3.34
COPd (declared COP) 4.18
Power input kW 0.80
B Condition Pdh (declared heating cap) kW 3.34
(2°C) COPd (declared COP) 4.18
Power input kW 0.80
C Condition Pdh (declared heating cap) kW 2.32
(7°C) COPd (declared COP) 5.80
Power input kW 0.40
D Condition Pdh (declared heating cap) kW 2.38
(12°C) COPd (declared COP) 7.17
Power input kW 0.33
Power consumption in Crankcase PCK W 0
other than active mode heater
mode
Off mode POFF W 1
Standby Cooling PSB W 1
mode Heating PSB W 1
Thermo- PTO Cooling W 12
stat-off Heating W 13
mode
Cooling Cdc (Degradation cooling) 0.25
Heating Cdh (Degradation heating) 0.25
Cooling function included Yes
Heating function included Yes
Average climate included Yes
Cold season included No
Warm season included Yes
Eurovent Sound Cooling Nom. dBA 66
power level
outdoor
Sound Cooling Nom. dBA 62
power level
indoor
Piping Cooling Measuring condition m 5.00
length
24 RXM-R
RXM-R
2 Specifications
2-1 Specifications
Electrical specifications FTXM71R + RXM71R
Power factor Nominal Cooling % 99.80
Heating % 99.50
Current Nominal running current
(RLA)
Cooling A 9.67
2
Nominal running current Heating A 10.47
(RLA) - 50Hz
Current - 50Hz Maximum fuse amps (MFA) A 20.00
See separate drawing for operation range |
See separate drawing for electrical data |
Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. |
Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
RXM-R 25
RXM-R
2 Specifications
2-1 Specifications
Technical specifications FVXM25F + RXM25R FVXM35F + RXM35R FVXM50F + RXM50R
Space heating (Average TOL Tol (temperature operating limit) °C -15
climate) Pdh (declared heating cap) kW 2.09 2.12 3.96
2 COPd (declared COP)
Power input kW
2.24
0.93
1.94
1.09
1.82
2.18
TBivalent Tbiv (bivalent temperature) °C -7
Pdh (declared heating cap) kW 2.12 2.57 3.72
COPd (declared COP) 3.25 2.40 2.20
Power input kW 0.65 1.07 1.69
A Condition Pdh (declared heating cap) kW 2.12 2.57 3.72
(-7°C) COPd (declared COP) 3.25 2.40 2.20
Power input kW 0.65 1.07 1.69
B Condition Pdh (declared heating cap) kW 1.29 1.56 2.27
(2°C) COPd (declared COP) 4.39 4.03 4.32
Power input kW 0.29 0.39 0.53
C Condition Pdh (declared heating cap) kW 0.83 1.03 1.80
(7°C)
Space heating (Average C Condition COPd (declared COP) 5.79 5.11 5.13
climate) (7°C) Power input kW 0.14 0.20 0.35
D Condition Pdh (declared heating cap) kW 0.78 1.08 1.91
(12°C) COPd (declared COP) 7.27 7.24 6.25
Power input kW 0.11 0.15 0.31
Space heating (Warm TOL Tol (temperature operating limit) °C -15
climate) Pdh (declared heating cap) kW 2.09 2.12 3.96
COPd (declared COP) 2.24 1.94 1.82
Power input kW 0.93 1.09 2.18
TBivalent Tbiv (bivalent temperature) °C 2
Pdh (declared heating cap) kW 1.29 1.56 2.27
COPd (declared COP) 4.39 4.03 4.32
Power input kW 0.29 0.39 0.53
B Condition Pdh (declared heating cap) kW 1.29 1.56 2.27
(2°C) COPd (declared COP) 4.39 4.03 4.32
Power input kW 0.29 0.39 0.53
C Condition Pdh (declared heating cap) kW 0.83 1.03 1.80
(7°C) COPd (declared COP) 5.79 5.11 5.13
Power input kW 0.14 0.20 0.35
D Condition Pdh (declared heating cap) kW 0.78 1.08 1.91
(12°C) COPd (declared COP) 7.27 7.24 6.25
Power input kW 0.11 0.15 0.31
Power consumption in Off mode POFF W 2.0
other than active mode Standby Cooling PSB W 2.0
mode Heating PSB W 2.0
Thermo- PTO Cooling W 8.0
stat-off Heating W 8.0
mode
Cooling Cdc (Degradation cooling) 0.25
Heating Cdh (Degradation heating) 0.25
Cooling function included Yes
Heating function included Yes
Average climate included Yes
Cold season included No
Warm season included Yes
Ecolabel logo No
Eurovent Sound Cooling Nom. dBA 59 61 62
power level
outdoor
Sound Cooling Nom. dBA 52 57
power level
indoor
Eurovent Piping Cooling Measuring condition m 5.0
length
See separate drawing for electrical data |
See separate drawing for operation range |
Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. |
Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
26 RXM-R
RXM-R
2 Specifications
2-1 Specifications
Technical specifications FTXM20N + RXM20R FTXM25N + RXM25R FTXM35N + RXM35R
Cooling capacity Min. kW 1.30 1.40
Min. Btu/h 4,400 4,800
Min.
Nom.
kcal/h
kW 2.00
1,118
2.50
1,204
3.40
2
Nom. Btu/h 6,800 8,500 11,600
Nom. kcal/h 1,720 2,150 2,923
Max. kW 2.60 3.20 4.00
Max. Btu/h 8,900 10,900 13,600
Max. kcal/h 2,236 2,752 3,439
Cooling capacity - Low Min. kcal/h -
sound mode (Stb. 2020, Max. kcal/h -
189)
Heating capacity Min. kW 1.30 1.40
Min. Btu/h 4,400 4,800
Min. kcal/h 1,100 1,200
Nom. kW 2.50 2.80 4.00
Nom. Btu/h 8,500 9,600 13,600
Nom. kcal/h 2,150 2,408 3,439
Max. kW 3.50 4.70 5.20
Max. Btu/h 11,900 16,000 17,700
Max. kcal/h 3,009 4,041 4,471
Power input Cooling Nom. kW 0.44 0.56 0.80
Heating Nom. kW 0.50 0.56 0.99
Nominal efficiency EER 4.57 4.50 4.23
COP 5.00 4.04
Annual energy consumption kWh 219 278 402
Energy Cooling A
labeling Heating A
Directive
Space cooling Energy efficiency class A+++
Capacity Pdesign kW 2.00 2.50 3.40
SEER 8.65
Annual energy consumption kWh/a 81 101 138
Space heating (Average Capacity Pdesign kW 2.30 2.40 2.50
climate) Energy efficiency class A+++
SCOP/A 5.10
Space heating (Average SCOPnet/A 5.14
climate) Pdh Heating capacity at -10° kW 2.24 2.30 2.35
Annual energy consumption kWh/a 632 659 687
Required back up heating cap at design conditions kW 0.06 0.10 0.15
Space heating (Warm Capacity Pdesignh kW 1.24 1.29 1.35
climate) Energy efficiency class A+++
SCOP 6.19 6.15 6.18
SCOPnet 6.31 6.26 6.30
Annual energy consumption kWh/a 280 294 305
Required back up heating cap at design conditions kW 0.00
Space cooling A Condition Pdc kW 2.00 2.50 3.40
(35°C - 27/19) EERd 4.57 4.50 4.23
Power input kW 0.44 0.56 0.80
B Condition Pdc kW 1.47 1.84 2.51
(30°C - 27/19) EERd 6.88 6.60 6.25
Power input kW 0.21 0.28 0.40
C Condition Pdc kW 1.18 1.61
(25°C - 27/19) EERd 10.52 10.03 10.19
Power input kW 0.11 0.12 0.16
D Condition Pdc kW 1.05 1.07
(20°C - 27/19) EERd 16.53 16.37 16.36
Power input kW 0.06 0.07
RXM-R 27
RXM-R
2 Specifications
2-1 Specifications
Technical specifications FTXM20N + RXM20R FTXM25N + RXM25R FTXM35N + RXM35R
Space heating (Average TOL Tol (temperature operating limit) °C -20
climate) Pdh (declared heating cap) kW 2.14
2 COPd (declared COP)
Power input kW
2.29
0.93
2.49
0.86
TBivalent Tbiv (bivalent temperature) °C -7
Pdh (declared heating cap) kW 2.03 2.12 2.21
COPd (declared COP) 3.64 3.60 3.50
Power input kW 0.56 0.59 0.63
A Condition Pdh (declared heating cap) kW 2.03 2.12 2.21
(-7°C) COPd (declared COP) 3.64 3.60 3.50
Power input kW 0.56 0.59 0.63
B Condition Pdh (declared heating cap) kW 1.24 1.29 1.34
(2°C) COPd (declared COP) 5.10 5.13
Power input kW 0.24 0.25 0.26
C Condition Pdh (declared heating cap) kW 0.93 0.94 0.95
(7°C)
Space heating (Average C Condition COPd (declared COP) 6.28 6.22
climate) (7°C) Power input kW 0.15
D Condition Pdh (declared heating cap) kW 0.97 0.98 1.09
(12°C) COPd (declared COP) 7.99 7.81
Power input kW 0.12 0.14
Space heating (Warm TOL Tol (temperature operating limit) °C -20
climate) Pdh (declared heating cap) kW 2.14 2.59
COPd (declared COP) 2.29 2.49
Power input kW 0.93 1.04
TBivalent Tbiv (bivalent temperature) °C 2
Pdh (declared heating cap) kW 1.24 1.29 1.34
COPd (declared COP) 5.10 5.13
Power input kW 0.24 0.25 0.26
B Condition Pdh (declared heating cap) kW 1.24 1.29 1.34
(2°C) COPd (declared COP) 5.10 5.13
Power input kW 0.24 0.25 0.26
C Condition Pdh (declared heating cap) kW 0.93 0.94 0.95
(7°C) COPd (declared COP) 6.28 6.22
Power input kW 0.15
D Condition Pdh (declared heating cap) kW 0.97 0.98 1.09
(12°C) COPd (declared COP) 7.99 7.81
Power input kW 0.12 0.14
Power consumption in Off mode POFF W 1
other than active mode Standby Cooling PSB W 1
mode Heating PSB W 1
Thermo- PTO Cooling W 6
stat-off Heating W 7
mode
Cooling Cdc (Degradation cooling) 0.25
Heating Cdh (Degradation heating) 0.25
Cooling function included Yes
Heating function included Yes
Average climate included Yes
Cold season included No
Warm season included Yes
Ecolabel logo No
Eurovent Sound Cooling Nom. dBA 59 58 61
power level
outdoor
Sound Cooling Nom. dBA 57 58
power level
indoor
Eurovent Piping Cooling Measuring condition m 5.00
length
28 RXM-R
RXM-R
3 Electrical data
3-1 Electrical Data
RXM20-35R
Unit combination restrictions Power supply COMP OFM IFM
Outdoor unit Indoor unit Hz Voltage Voltage range MCA MFA RHz RLA kW FLA kW FLA
Symbols
RXM20N5V1B9 FTXM20R2V1B
50
50
220
230
MAX. 50Hz 264V
8,93 10 32,5
1,7
1,6 0,048 0,320 0,029 0,30
MCA:
MFA:
Minimum Circuit Ampere [A]
Maximum Fuse Ampere [A]
3
MIN. 50Hz 198V RLA: Rated load amps [A]
50 240 1,6
50 220 2,3 OFM: Outdoor fan motor
MAX. 50Hz 264V
RXM25N5V1B9 FTXM25R2V1B 50 230 9,71 13 46,0 2,2 0,040 0,280 0,025 0,30 IFM: Indoor fan motor
MIN. 50Hz 198V FLA: Full load amps [A]
50 240 2,1
50 220 3,3 kW: Fan motor rated output [kW]
MAX. 50Hz 264V
RXM35N5V1B9 FTXM35R2V1B 50 230 9,76 13 60,0 3,2 0,048 0,320 0,030 0,30 RHz: Rated operating frequency [Hz]
MIN. 50Hz 198V
50 240 3,0
50 220 MAX. 50Hz 264V 2,3
ARXM25N5V1B9 ATXM25R2V1B 50 230 9,71 13 46,0 2,2 0,040 0,280 0,025 0,30
MIN. 50Hz 198V
50 240 2,1
50 220 MAX. 50Hz 264V 3,3
ARXM35N5V1B9 ATXM35R2V1B 50 230 9,76 13 60,0 3,2 0,048 0,320 0,030 0,30
MIN. 50Hz 198V
50 240 3,0
50 220 MAX. 50Hz 264V 1,7
RXM20N5V1B9 FTXM20R5V1B 50 230 8,93 10 32,5 1,6 0,048 0,320 0,029 0,30
MIN. 50Hz 198V
50 240 1,6
50 220 MAX. 50Hz 264V 2,3
RXM25N5V1B9 FTXM25R5V1B 50 230 9,71 13 46,0 2,2 0,040 0,280 0,025 0,30
MIN. 50Hz 198V
50 240 2,1
50 220 MAX. 50Hz 264V 3,3
RXM35N5V1B9 FTXM35R5V1B 50 230 9,76 13 60,0 3,2 0,048 0,320 0,030 0,30
MIN. 50Hz 198V
50 240 3,0
50 220 MAX. 50Hz 264V 2,3
ARXM25N5V1B9 ATXM25R5V1B 50 230 9,71 13 46,0 2,2 0,040 0,280 0,025 0,30 Notes
MIN. 50Hz 198V
50 240 2,1 1) The ·RLA· is based on the following
50 220 3,3 conditions.
MAX. 50Hz 264V
ARXM35N5V1B9 ATXM35R5V1B 50 230 9,76 13 60,0 3,2 0,048 0,320 0,030 0,30 Outdoor temperature ·35·°C DB
MIN. 50Hz 198V
50 240 3,0 Indoor temperature ·27·°C DB / ·19·°C
50 220 2,0 WB
MAX. 50Hz 264V
RXM20R5V1B FTXM20N2V1B 50 230 8,84 10 35,0 2,1 0,048 0,320 0,022 0,22 2) Select the wire size according to the
MIN. 50Hz 198V MCA.
50 240 2,2
50 220 MAX. 50Hz 264V 2,6 3) The maximum allowable voltage that is
RXM25R5V1B FTXM25N2V1B 50 230 9,63 13 46,0 2,7 0,040 0,280 0,022 0,22 unbalanced between phases is ·2·%.
MIN. 50Hz 198V
50 240 2,8 4) Use a circuit breaker instead of a
50 220 4,2 fuse.
MAX. 50Hz 264V
RXM35R5V1B FTXM35N2V1B 50 230 9,70 13 60,0 4,4 0,048 0,320 0,027 0,25
MIN. 50Hz 198V
50 240 4,6
50 220 MAX. 50Hz 264V 2,6
ARXM25R5V1B ATXM25N2V1B 50 230 9,63 13 46,0 2,7 0,040 0,280 0,022 0,22
MIN. 50Hz 198V
50 240 2,8
50 220 MAX. 50Hz 264V 4,2
ARXM35R5V1B ATXM35N2V1B 50 230 9,70 13 60,0 4,4 0,048 0,320 0,027 0,25
MIN. 50Hz 198V
50 240 4,6
4D130653
RXM-R 29
RXM-R
3 Electrical data
3-1 Electrical Data
ARX25-35R
RXM20-35R Unit combination restrictions Power supply COMP OFM IFM
Symbols
MCA: Minimum Circuit Ampere [A] Notes
MFA: Maximum Fuse Ampere [A] 1) The ·RLA· is based on the following conditions.
RLA: Rated load amps [A] Outdoor temperature ·35·°C DB
OFM: Outdoor fan motor Indoor temperature ·27·°C DB / ·19·°C WB
IFM: Indoor fan motor 2) Select the wire size according to the MCA.
RHz: Rated operating frequency [Hz] 3) The maximum allowable voltage that is unbalanced
FLA: Full Load Ampere [A] between phases is ·2·%.
kW: Fan motor rated output [kW] 4) Use a circuit breaker instead of a fuse.
4D130519C
30 RXM-R
RXM-R
3 Electrical data
3-1 Electrical Data
RXM42R
SYMBOLS
MCA: Minimum Circuit Ampere [A]
MCA: Minimum Circuit Ampere [A]
MFA: Maximum Fuse Ampere [A]
RLA: Rated load amps [A]
OFM: Outdoor fan motor
IFM:Indoor fan motor
FLA: Full Load Ampere [A]
kW: Fan motor rated output [kW]
RHz: Rated operating frequency [Hz]
NOTES:
3D133950
RXM-R 31
R
XM-R
3 Electrical data
3-1 Electrical Data
RXM42-71R(2) Unit combination
Power supply COMP OFM IFM
ARXM50-71R(2) restrictions
Outdoor unit Indoor unit Hz Voltage Voltage range MCA MFA RHz RLA kW FLA kW FLA
3 50 220 5,2
Maximum ·50·Hz ·264·V
ARXM50R2V1B ADEA50A2VEB 50 230 15,42 16 55 5,0 0,06 0,37 0,089 1,40
50 240 Minimum ·50·Hz ·198·V 4,8
50 220 6,2
Maximum ·50·Hz ·264·V
ARXM60R2V1B ADEA60A2VEB 50 230 15,86 16 66 6,0 0,06 0,37 0,070 1,30
50 240 Minimum ·50·Hz ·198·V 5,7
50 220 8,2
Maximum ·50·Hz ·264·V
ARXM71R2V1B ADEA71A2VEB 50 230 15,83 16 81 7,8 0,06 0,37 0,070 1,30
50 240 Minimum ·50·Hz ·198·V 7,5
50 220 8,1
Maximum ·50·Hz ·264·V
ARXM71R2V1B FCAG71BVEB 50 230 14,93 16 81 7,7 0,06 0,37 0,054 0,40
50 240 Minimum ·50·Hz ·198·V 7,4
50 220 8,2
Maximum ·50·Hz ·264·V
ARXM71R2V1B FBA71A2VEB9 50 230 15,83 16 81 7,8 0,06 0,37 0,070 1,30
50 240 Minimum ·50·Hz ·198·V 7,5
50 220 8,3
Maximum ·50·Hz ·264·V
ARXM71R2V1B FAA71BUV1B 50 230 14,93 16 83 7,9 0,06 0,37 0,048 0,40
50 240 Minimum ·50·Hz ·198·V 7,6
50 220 4,3
Maximum ·50·Hz ·264·V
RXM42R2V1B FTXM42R2V1B 50 230 10,36 13 48 4,1 0,06 0,37 0,034 0,30
50 240 Minimum ·50·Hz ·198·V 4,0
50 220 4,3
Maximum ·50·Hz ·264·V
RXM42R2V1B FTXM42R5V1B 50 230 10,36 13 48 4,1 0,06 0,37 0,034 0,30
50 240 Minimum ·50·Hz ·198·V 4,0
50 220 4,7
Maximum ·50·Hz ·264·V
RXM50R2V1B FTXM50R2V1B 50 230 14,54 16 54 4,5 0,06 0,37 0,046 0,60
50 240 Minimum ·50·Hz ·198·V 4,3
50 220 4,7
Maximum ·50·Hz ·264·V
ARXM50R2V1B ATXM50R2V1B 50 230 14,54 16 54 4,5 0,06 0,37 0,046 0,60
50 240 Minimum ·50·Hz ·198·V 4,3
50 220 5,2
Maximum ·50·Hz ·264·V
RXM50R2V1B FCAG50BVEB 50 230 14,21 16 58 5,0 0,06 0,37 0,048 0,30
50 240 Minimum ·50·Hz ·198·V 4,8
50 220 5,2
Maximum ·50·Hz ·264·V
RXM50R2V1B FBA50A2VEB9 50 230 15,42 16 55 5,0 0,06 0,37 0,089 1,40
50 240 Minimum ·50·Hz ·198·V 4,8
50 220 5,5
Maximum ·50·Hz ·264·V
RXM50R2V1B FHA50AVEB99 50 230 14,54 16 64 5,3 0,06 0,37 0,090 0,60
50 240 Minimum ·50·Hz ·198·V 5,2
50 220 5,6
Maximum ·50·Hz ·264·V
RXM50R2V1B FFA50A2VEB9 50 230 14,32 16 62 5,4 0,06 0,37 0,050 0,40
50 240 Minimum ·50·Hz ·198·V 5,3
50 220 4,9
Maximum ·50·Hz ·264·V
RXM50R2V1B FDXM50F3V1B9 50 230 14,87 16 55 4,7 0,06 0,37 0,060 0,90
50 240 Minimum ·50·Hz ·198·V 4,5
50 220 4,9
Maximum ·50·Hz ·264·V
RXM50R2V1B FNA50A2VEB9 50 230 14,43 16 55 4,7 0,06 0,37 0,060 0,50
50 240 Minimum ·50·Hz ·198·V 4,5
50 220 5,4
Maximum ·50·Hz ·264·V
RXM50R2V1B FVXM50FV1B9 50 230 14,32 16 60 5,2 0,06 0,37 0,048 0,10
50 240 Minimum ·50·Hz ·198·V 5,0
50 220 6,6
Maximum ·50·Hz ·264·V
RXM60R2V1B FTXM60R2V1B 50 230 15,09 16 70 6,3 0,06 0,37 0,046 0,60
50 240 Minimum ·50·Hz ·198·V 6,0
50 220 6,5
Maximum ·50·Hz ·264·V
RXM60R2V1B FCAG60BVEB 50 230 14,76 16 71 6,3 0,06 0,37 0,048 0,30
50 240 Minimum ·50·Hz ·198·V 6,2
50 220 6,1
Maximum ·50·Hz ·264·V
RXM60R2V1B FBA60A2VEB9 50 230 15,86 16 66 6,0 0,06 0,37 0,070 1,30
50 240 Minimum ·50·Hz ·198·V 5,8
50 220 5,5
Maximum ·50·Hz ·264·V
RXM60R2V1B FHA60AVEB99 50 230 15,09 16 62 5,3 0,06 0,37 0,091 0,60
50 240 Minimum ·50·Hz ·198·V 5,1
50 220 6,5
Maximum ·50·Hz ·264·V
RXM60R2V1B FFA60A2VEB9 50 230 15,09 16 70 6,3 0,06 0,37 0,050 0,60
50 240 Minimum ·50·Hz ·198·V 6,2
50 220 6,7
Maximum ·50·Hz ·264·V
RXM60R2V1B FDXM60F3V1B9 50 230 15,42 16 73 6,5 0,06 0,37 0,060 0,90
50 240 Minimum ·50·Hz ·198·V 6,4
50 220 6,7
Maximum ·50·Hz ·264·V
RXM60R2V1B FNA60A2VEB9 50 230 15,09 16 73 6,5 0,06 0,37 0,060 0,60
50 240 Minimum ·50·Hz ·198·V 6,4
50 220 9,4
Maximum ·50·Hz ·264·V
RXM71R2V1B FTXM71R2V1B 50 230 19,78 20 54 8,9 0,13 0,38 0,052 0,60
50 240 Minimum ·50·Hz ·198·V 8,6
Symbols Notes
MCA: Minimum Circuit Ampere [A] 1) The ·RLA· is based on the following conditions.
MFA: Maximum Fuse Ampere [A] Outdoor temperature ·35·°C DB
RLA: Rated load amps [A] Indoor temperature ·27·°C DB / ·19·°C WB
OFM: Outdoor fan motor 2) Select the wire size according to the MCA.
IFM: Indoor fan motor 3) The maximum allowable voltage that is unbalanced
FLA: Full load amps [A] between phases is ·2·%.
kW: Fan motor rated output [kW] 4) Use a circuit breaker instead of a fuse.
RHz: Rated operating frequency [Hz]
4D131055B
32 R
XM-R
RXM-R
3 Electrical data
3-1 Electrical Data
RXM50R
3
Unit combination restrictions Power supply COMP OFM IFM
Indoor unit Outdoor unit Hz Voltage Voltage range MCA MFA RHz RLA kW FLA kW FLA
50 220 4.4
RXM42N2V1B9 FTXM42N2V1B 50 230 Maximum ·50·Hz ·264·V 11.62 13 49 4.2 0.056 0.37 0.028 0.22
50 240 Minimum ·50·Hz ·198·V 3.9
50 220 3.8
RXM50N2V1B9 FTXM50N2V1B 50 230 Maximum ·50·Hz ·264·V 12.00 13 52 3.5 0.056 0.37 0.046 0.6
50 240 Minimum ·50·Hz ·198·V 3.2
50 220 3.8
ARXM50N2V1B9 ATXM50N2V1B 50 230 Maximum ·50·Hz ·264·V 12.00 13 52 3.5 0.056 0.37 0.046 0.6
50 240 Minimum ·50·Hz ·198·V 3.2
50 220 5.2
RXM50N2V1B9 FCAG50AVEB 50 230 Maximum ·50·Hz ·264·V 11.70 13 58 5.0 0.056 0.37 0.048 0.3
50 240 Minimum ·50·Hz ·198·V 4.8
50 220 5.2
RXM50N2V1B9 FBA50AVEB 50 230 Maximum ·50·Hz ·264·V 12.80 13 55 5.0 0.056 0.37 0.089 1.4
50 240 Minimum ·50·Hz ·198·V 4.8
50 220 5.5
RXM50N2V1B9 FHA50AVEB 50 230 Maximum ·50·Hz ·264·V 12.00 13 64 5.3 0.056 0.37 0.090 0.6
50 240 Minimum ·50·Hz ·198·V 5.2
50 220 5.6
RXM50N2V1B9 FFA50A2VEB 50 230 Maximum ·50·Hz ·264·V 11.80 13 62 5.4 0.056 0.37 0.050 0.4
50 240 Minimum ·50·Hz ·198·V 5.3
50 220 4.9
RXM50N2V1B9 FDXM50F3V1B 50 230 Maximum ·50·Hz ·264·V 12.30 13 55 4.7 0.056 0.37 0.060 0.9
50 240 Minimum ·50·Hz ·198·V 4.5
50 220 4.9
RXM50N2V1B9 FNA50A2VEB 50 230 Maximum ·50·Hz ·264·V 11.90 13 55 4.7 0.056 0.37 0.060 0.5
50 240 Minimum ·50·Hz ·198·V 4.5
50 220 5.4
RXM50N2V1B9 FVXM50FV1B 50 230 Maximum ·50·Hz ·264·V 11.50 13 60 5.2 0.056 0.37 0.048 0.1
50 240 Minimum ·50·Hz ·198·V 5.0
50 220 5.9
RXM60N2V1B9 FTXM60N2V1B 50 230 Maximum ·50·Hz ·264·V 15.13 16 66 5.7 0.056 0.37 0.046 0.6
50 240 Minimum ·50·Hz ·198·V 5.5
50 220 6.5
RXM60N2V1B9 FCAG60AVEB 50 230 Maximum ·50·Hz ·264·V 14.83 16 71 6.3 0.056 0.37 0.048 0.3
50 240 Minimum ·50·Hz ·198·V 6.2
50 220 6.1
RXM60N2V1B9 FBA60AVEB 50 230 Maximum ·50·Hz ·264·V 15.83 16 66 6.0 0.056 0.37 0.070 1.3
50 240 Minimum ·50·Hz ·198·V 5.8
50 220 5.5
RXM60N2V1B9 FHA60AVEB 50 230 Maximum ·50·Hz ·264·V 15.13 16 62 5.3 0.056 0.37 0.091 0.6
50 240 Minimum ·50·Hz ·198·V 5.1
50 220 6.5
RXM60N2V1B9 FFA60A2VEB 50 230 Maximum ·50·Hz ·264·V 15.13 16 70 6.3 0.056 0.37 0.050 0.6
50 240 Minimum ·50·Hz ·198·V 6.2
50 220 6.7
RXM60N2V1B9 FDXM60F3V1B 50 230 Maximum ·50·Hz ·264·V 15.43 16 73 6.5 0.056 0.37 0.060 0.9
50 240 Minimum ·50·Hz ·198·V 6.4
50 220 6.7
RXM60N2V1B9 FNA60A2VEB 50 230 Maximum ·50·Hz ·264·V 15.13 16 73 6.5 0.056 0.37 0.060 0.6
50 240 Minimum ·50·Hz ·198·V 6.4
50 220 5.3
RXM50R2V1B FVXM50A2V1B 50 230 Maximum ·50·Hz ·264·V 14.04 16 58 5.1 0.056 0.37 0.037 0.14
50 240 Minimum ·50·Hz ·198·V 4.9
50 220 4.7
RXM50N2V1B9 FTXM50R2V1B 50 230 Maximum ·50·Hz ·264·V 10.69 13 54 4.5 0.056 0.37 0.046 0.6
50 240 Minimum ·50·Hz ·198·V 4.3
50 220 4.7
ARXM50N2V1B9 ATXM50R2V1B 50 230 Maximum ·50·Hz ·264·V 10.69 13 54 4.5 0.056 0.37 0.046 0.6
50 240 Minimum ·50·Hz ·198·V 4.3
50 220 6.6
RXM60N2V1B9 FTXM60R2V1B 50 230 Maximum ·50·Hz ·264·V 13.44 16 70 6.3 0.056 0.37 0.046 0.6
50 240 Minimum ·50·Hz ·198·V 6.0
50 220 7.9
RXM71N2V1B FTXM71R2V1B 50 230 Maximum ·50·Hz ·264·V 18.30 20 54 7.2 0.128 0.38 0.052 0.34
50 240 Minimum ·50·Hz ·198·V 6.9
SYMBOLS
MCA: Minimum Circuit Ampere [A]
MFA: Maximum Fuse Ampere [A]
RLA: Rated load amps [A]
OFM: Outdoor fan motor
IFM: Indoor fan motor
RHz: Rated operating frequency [Hz]
FLA: Full Load Ampere [A]
kW : Fan motor rated output [kW]
Notes
1)The ·RLA· is based on the following conditions.
Outdoor temperature ·35·°C DB
Indoor temperature ·27·°C DB / ·19·°C WB
2)Select the wire size according to the MCA.
3)The maximum allowable voltage that is unbalanced between phases is ·2·%.
4)Use a circuit breaker instead of a fuse.
3D120639C
RXM-R 33
RXM-R
3 Electrical data
3-1 Electrical Data
RXM50R
SYMBOLS
NOTES:
3D133949
34 RXM-R
R
XM-R
3 Electrical data
3-1 Electrical Data
RXM42-60R(5)
ARXM50-71R(5)
Unit combination restrictions Power supply COMP OFM IFM
3
Outdoor unit Indoor unit Hz Voltage Voltage range MCA MFA RHz RLA kW FLA kW FLA
50 220 5,2
Maximum ·50·Hz ·264·V
ARXM50R5V1B ADEA50A2VEB 50 230 15,42 16 55 5,0 0,056 0,37 0,089 1,40
50 240 Minimum ·50·Hz ·198·V 4,8
50 220 6,2
Maximum ·50·Hz ·264·V
ARXM60R5V1B ADEA60A2VEB 50 230 15,86 16 66 6,0 0,056 0,37 0,070 1,30
50 240 Minimum ·50·Hz ·198·V 5,7
50 220 8,2
Maximum ·50·Hz ·264·V
ARXM71R5V1B ADEA71A2VEB 50 230 15,83 16 81 7,8 0,056 0,37 0,070 1,30
50 240 Minimum ·50·Hz ·198·V 7,5
50 220 8,1
Maximum ·50·Hz ·264·V
ARXM71R5V1B FCAG71BVEB 50 230 14,93 16 81 7,7 0,056 0,37 0,054 0,40
50 240 Minimum ·50·Hz ·198·V 7,4
50 220 8,2
Maximum ·50·Hz ·264·V
ARXM71R5V1B FBA71A2VEB9 50 230 15,83 16 81 7,8 0,056 0,37 0,070 1,30
50 240 Minimum ·50·Hz ·198·V 7,5
50 220 8,3
Maximum ·50·Hz ·264·V
ARXM71R5V1B FAA71BUV1B 50 230 14,93 16 83 7,9 0,056 0,37 0,048 0,40
50 240 Minimum ·50·Hz ·198·V 7,6
50 220 4,3
Maximum ·50·Hz ·264·V
RXM42R5V1B FTXM42R2V1B 50 230 10,36 13 48 4,1 0,056 0,37 0,034 0,30
50 240 Minimum ·50·Hz ·198·V 4,0
50 220 4,3
Maximum ·50·Hz ·264·V
RXM42R5V1B FTXM42R5V1B 50 230 10,36 13 48 4,1 0,056 0,37 0,034 0,30
50 240 Minimum ·50·Hz ·198·V 4,0
50 220 4,7
Maximum ·50·Hz ·264·V
RXM50R5V1B FTXM50R2V1B 50 230 14,54 16 54 4,5 0,056 0,37 0,046 0,60
50 240 Minimum ·50·Hz ·198·V 4,3
50 220 4,7
Maximum ·50·Hz ·264·V
ARXM50R5V1B ATXM50R2V1B 50 230 14,54 16 54 4,5 0,056 0,37 0,046 0,60
50 240 Minimum ·50·Hz ·198·V 4,3
50 220 5,2
Maximum ·50·Hz ·264·V
RXM50R5V1B FCAG50BVEB 50 230 14,21 16 58 5,0 0,056 0,37 0,048 0,30
50 240 Minimum ·50·Hz ·198·V 4,8
50 220 5,2
Maximum ·50·Hz ·264·V
RXM50R5V1B FBA50A2VEB9 50 230 15,42 16 55 5,0 0,056 0,37 0,089 1,40
50 240 Minimum ·50·Hz ·198·V 4,8
50 220 5,5
Maximum ·50·Hz ·264·V
RXM50R5V1B FHA50AVEB9 50 230 14,54 16 64 5,3 0,056 0,37 0,090 0,60
50 240 Minimum ·50·Hz ·198·V 5,2
50 220 5,6
Maximum ·50·Hz ·264·V
RXM50R5V1B FFA50A2VEB9 50 230 14,32 16 62 5,4 0,056 0,37 0,050 0,40
50 240 Minimum ·50·Hz ·198·V 5,3
50 220 4,9
Maximum ·50·Hz ·264·V
RXM50R5V1B FDXM50F3V1B9 50 230 14,87 16 55 4,7 0,056 0,37 0,060 0,90
50 240 Minimum ·50·Hz ·198·V 4,5
50 220 4,9
Maximum ·50·Hz ·264·V
RXM50R5V1B FNA50A2VEB9 50 230 14,43 16 55 4,7 0,056 0,37 0,060 0,50
50 240 Minimum ·50·Hz ·198·V 4,5
50 220 5,4
Maximum ·50·Hz ·264·V
RXM50R5V1B FVXM50FV1B9 50 230 14,32 16 60 5,2 0,056 0,37 0,048 0,10
50 240 Minimum ·50·Hz ·198·V 5,0
50 220 6,6
Maximum ·50·Hz ·264·V
RXM60R5V1B FTXM60R2V1B 50 230 15,09 16 70 6,3 0,056 0,37 0,046 0,60
50 240 Minimum ·50·Hz ·198·V 6,0
50 220 6,5
Maximum ·50·Hz ·264·V
RXM60R5V1B FCAG60BVEB 50 230 14,76 16 71 6,3 0,056 0,37 0,048 0,30
50 240 Minimum ·50·Hz ·198·V 6,2
50 220 6,1
Maximum ·50·Hz ·264·V
RXM60R5V1B FBA60A2VEB9 50 230 15,86 16 66 6,0 0,056 0,37 0,070 1,30
50 240 Minimum ·50·Hz ·198·V 5,8
50 220 5,5
Maximum ·50·Hz ·264·V
RXM60R5V1B FHA60AVEB9 50 230 15,09 16 62 5,3 0,056 0,37 0,091 0,60
50 240 Minimum ·50·Hz ·198·V 5,1
50 220 6,5
Maximum ·50·Hz ·264·V
RXM60R5V1B FFA60A2VEB9 50 230 15,09 16 70 6,3 0,056 0,37 0,050 0,60
50 240 Minimum ·50·Hz ·198·V 6,2
50 220 6,7
Maximum ·50·Hz ·264·V
RXM60R5V1B FDXM60F3V1B9 50 230 15,42 16 73 6,5 0,056 0,37 0,060 0,90
50 240 Minimum ·50·Hz ·198·V 6,4
50 220 6,7
Maximum ·50·Hz ·264·V
RXM60R5V1B FNA60A2VEB9 50 230 15,09 16 73 6,5 0,056 0,37 0,060 0,60
50 240 Minimum ·50·Hz ·198·V 6,4
50 220 9,4
Maximum ·50·Hz ·264·V
RXM71R5V1B FTXM71R2V1B 50 230 19,78 20 54 8,9 0,128 0,38 0,052 0,60
50 240 Minimum ·50·Hz ·198·V 8,6
Symbols Notes
MCA: Minimum Circuit Ampere [A] 1. The ·RLA· is based on the following conditions.
MFA: Maximum Fuse Ampere [A] Outdoor temperature ·35.0·°C DB
RLA: Rated load amps [A] Indoor temperature ·27.0·°C DB / ·19.0·°C WB
OFM: Outdoor fan motor 2. Select the wire size according to the MCA.
IFM: Indoor fan motor 3. The maximum allowable voltage that is unbalanced between
OFM: Outdoor fan motor phases is ·2·%.
FLA: Full Load Ampere [A] 4. Use a circuit breaker instead of a fuse.
KW: Fan motor rated output [kW]
RHz: Rated operating frequency [Hz]
3D133951A
R
XM-R 35
RXM-R
4 Capacity tables
4-1 Cooling/Heating Capacity Tables
FTXM20N / RXM20R
AFR 11,1
Cooling ·220-240V 50Hz· BF 0,16
Symbols
4
③ TC: Total capacity [kW]
① ② PI: Power input [kW]
20 25 30 32 35 40 SHC: Sensible heat capacity [kW]
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI AFR: Air flow rate [m³/min]
14 20 2,05 1,76 0,34 1,96 1,72 0,37 1,86 1,68 0,40 1,83 1,66 0,42 1,77 1,64 0,44 1,68 1,59 0,47 BF: Bypass factor
16 22 2,14 1,76 0,34 2,05 1,69 0,37 1,95 1,65 0,41 1,92 1,64 0,42 1,86 1,62 0,44 1,77 1,58 0,47
18 25 2,23 1,85 0,34 2,14 1,81 0,38 2,05 1,78 0,41 2,01 1,76 0,42 1,95 1,74 0,44 1,86 1,70 0,47
19 27 2,28 1,98 0,34 2,19 1,95 0,38 2,09 1,91 0,41 2,06 1,90 0,42 2,00 1,88 0,44 1,91 1,84 0,47
22 30 2,42 1,92 0,35 2,32 1,89 0,38 2,23 1,86 0,41 2,19 1,85 0,42 2,14 1,83 0,44 2,05 1,80 0,47
24 32 2,51 1,88 0,35 2,42 1,86 0,38 2,32 1,83 0,41 2,29 1,82 0,43 2,23 1,80 0,44 2,14 1,77 0,48
Notes
1. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5.0· m
Level difference: ·0·m
FTXM20R / RXM20R
AFR 10,48
Cooling 50Hz 220 -240V BF 0,08
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. Nominal capacity and nominal input
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table (figures
not in the table may not be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values in
direct proportion.
5. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
6. The air flow rate and bypass factor are mentioned in the table.
4D130634
36 RXM-R
RXM-R
4 Capacity tables
4-1 Cooling/Heating Capacity Tables
FDXM25F9 / RXM25R
Cooling 50Hz 220-240V AFR 8,7
BF 0,17
Indoor
Outdoor temperature [°C DB]
4
temperature
EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14,0 20 2,46 1,94 0,49 2,35 1,88 0,54 2,24 1,83 0,59 2,19 1,81 0,61 2,12 1,78 0,63 2,01 1,73 0,68
16,0 22 2,57 1,91 0,50 2,46 1,86 0,54 2,35 1,81 0,59 2,30 1,79 0,61 2,23 1,76 0,64 2,12 1,71 0,68
18,0 25 2,68 2,01 0,50 2,57 1,97 0,55 2,46 1,92 0,59 2,41 1,90 0,61 2,34 1,87 0,64 2,23 1,83 0,69
19,0 27 2,74 2,14 0,50 2,62 2,09 0,55 2,51 2,05 0,59 2,47 2,03 0,61 2,40 2,00 0,64 2,29 1,96 0,69
22,0 30 2,90 2,07 0,50 2,79 2,03 0,55 2,68 1,99 0,60 2,63 1,97 0,62 2,57 1,95 0,65 2,45 1,91 0,69
24,0 32 3,01 2,02 0,51 2,90 1,98 0,55 2,79 1,95 0,60 2,74 1,93 0,62 2,68 1,91 0,65 2,56 1,88 0,70
Indoor
temperature
Outdoor temperature [°C WB] Symbols
EDB -15 -10 -5 0 6 10
°C TC PI TC PI TC PI TC PI TC PI TC PI AFR: Air flow rate [m³/min]
15,0 1,49 0,64 1,79 0,68 2,09 0,71 2,39 0,74 3,31 0,78 3,60 0,81 BF: Bypass factor
20,0 1,40 0,66 1,70 0,69 2,00 0,73 2,30 0,76 3,20 0,80 3,49 0,83 EVB: Entering wet-bulb temperature (°C WB)
22,0 1,36 0,67 1,66 0,70 1,96 0,73 2,26 0,77 3,16 0,81 3,44 0,83 EDB: Entering dry-bulb temperature (°C DB)
24,0 1,32 0,68 1,62 0,71 1,92 0,74 2,22 0,77 3,11 0,81 3,40 0,84 TC: Total capacity [kW]
25,0 1,30 0,68 1,60 0,71 1,90 0,75 2,20 0,78 3,09 0,82 3,38 0,84 SHC: Sensible heat capacity [kW]
27,0 1,27 0,69 1,57 0,72 1,87 0,75 2,17 0,79 3,05 0,83 3,33 0,85 PI: Power input [kW]
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. On the figure the · · mark shows the rated capacity and rated coefficient of the power input.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table (figures not in the table may not be
used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values in direct proportion.
3D110078B
FFA25A9 / RXM25R
50Hz 220-240V AFR 9,0
Cooling BF 0,24
Symbols
Indoor temperature Outdoor temperature [°C WB]
EDB -15 -10 -5 0 6 10 AFR: Air flow rate [m³/min]
°C TC PI TC PI TC PI TC PI TC PI TC PI BF: Bypass factor
15,0 1,49 0,66 1,79 0,69 2,09 0,73 2,39 0,76 3,31 0,80 3,60 0,83 EWB: Entering wet-bulb temperature (°C WB)
20,0 1,40 0,68 1,70 0,71 2,00 0,75 2,30 0,78 3,20 0,82 3,49 0,85 EDB: Entering dry-bulb temperature (°C DB)
22,0 1,36 0,69 1,66 0,72 1,96 0,75 2,26 0,79 3,16 0,83 3,44 0,85 TC: Total capacity [kW]
24,0 1,32 0,69 1,62 0,73 1,92 0,76 2,22 0,79 3,11 0,84 3,40 0,86 SHC: Sensible heat capacity [kW]
25,0 1,30 0,70 1,60 0,73 1,90 0,76 2,20 0,80 3,09 0,84 3,38 0,87 PI: Power input [kW]
27,0 1,27 0,70 1,57 0,74 1,87 0,77 2,17 0,81 3,05 0,85 3,33 0,87
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. On the figure the ·□· mark shows the rated capacity and rated coefficient of the power input.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table (figures not in the table may not
be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values in direct proportion.
3D110082B
RXM-R 37
RXM-R
4 Capacity tables
4-1 Cooling/Heating Capacity Tables
FNA25A9 / RXM25R
50Hz 220 - 240V AFR 8,7
Cooling BF 0,17
4 Indoor
temperature
Outdoor temperature [°C DB]
EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14,0 20 2,66 2,04 0,52 2,54 1,98 0,58 2,42 1,92 0,63 2,37 1,90 0,65 2,30 1,86 0,68 2,18 1,81 0,73
16,0 22 2,78 2,00 0,53 2,66 1,95 0,58 2,54 1,89 0,63 2,49 1,87 0,65 2,42 1,84 0,68 2,30 1,78 0,73
18,0 25 2,90 2,11 0,53 2,78 2,06 0,58 2,66 2,00 0,63 2,61 1,98 0,65 2,54 1,95 0,68 2,42 1,90 0,73
19,0 27 2,96 2,23 0,53 2,84 2,18 0,58 2,72 2,13 0,63 2,67 2,11 0,65 2,60 2,08 0,68 2,48 2,04 0,73
22,0 30 3,14 2,16 0,54 3,02 2,11 0,59 2,90 2,07 0,64 2,85 2,05 0,66 2,78 2,02 0,69 2,66 1,98 0,74
24,0 32 3,26 2,10 0,54 3,14 2,06 0,59 3,02 2,02 0,64 2,97 2,01 0,66 2,90 1,98 0,69 2,78 1,94 0,74
Indoor
Outdoor temperature [°C WB]
temperature Symbols
EDB -15 -10 -5 0 6 10
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. On the figure the ·□· mark shows the rated capacity and rated coefficient of the power input.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table (figures not in the table may not
be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values in direct proportion.
FVXM25F / RXM25R
Cooling 50Hz 220 - 240V AFR 8,2
BF 0,1
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. On the figure the ·□· mark shows the rated capacity and rated coefficient of the power input.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table (figures not in the table may not be
used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values in direct proportion.
38 RXM-R
RXM-R
4 Capacity tables
4-1 Cooling/Heating Capacity Tables
FTXM25N / RXM25R
AFR 11,1
③ 4
Symbols
① ②
20 25 30 32 35 40
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC: Total capacity [kW]
14 20 2,56 1,95 0,40 2,44 1,90 0,45 2,32 1,85 0,51 2,28 1,83 0,53 2,21 1,79 0,55 2,09 1,74 0,60 PI: Power input [kW]
16 22 2,68 1,92 0,43 2,56 1,87 0,47 2,44 1,82 0,51 2,40 1,80 0,53 2,33 1,76 0,56 2,21 1,71 0,60 SHC: Sensible heat capacity [kW]
18 25 2,79 2,02 0,43 2,68 1,97 0,47 2,56 1,92 0,52 2,51 1,90 0,53 2,44 1,88 0,56 2,33 1,83 0,60 AFR: Air flow rate [m³/min]
19 27 2,85 2,14 0,43 2,73 2,09 0,48 2,62 2,05 0,52 2,57 2,03 0,53 2,50 2,00 0,56 2,38 1,95 0,60 BF: Bypass factor
22 30 3,02 2,07 0,44 2,91 2,03 0,48 2,79 1,98 0,52 2,74 1,97 0,54 2,67 1,94 0,56 2,56 1,90 0,61
24 32 3,14 2,02 0,44 3,02 1,98 0,48 2,90 1,94 0,52 2,86 1,92 0,54 2,79 1,90 0,57 2,67 1,87 0,61
15 1,33 0,36 1,60 0,38 1,87 0,40 2,52 0,52 2,90 0,55 3,15 0,57 ③ Outdoor air temperature [°C DB]
20 1,25 0,37 1,52 0,39 1,79 0,41 2,42 0,53 2,80 0,56 3,05 0,58
22 1,22 0,37 1,49 0,40 1,76 0,42 2,38 0,53 2,76 0,57 3,01 0,59 ④ Outdoor air temperature [°C WB]
24 1,19 0,38 1,45 0,40 1,72 0,42 2,34 0,54 2,72 0,57 2,98 0,59
25 1,17 0,38 1,44 0,40 1,71 0,42 2,32 0,54 2,70 0,57 2,96 0,59
27 1,14 0,39 1,41 0,41 1,67 0,42 2,29 0,55 2,66 0,58 2,92 0,60
Notes
1. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5.0· m
Level difference: ·0·m
FVXM25A / RXM25R
AFR 8,7
Cooling ·220-240V 50Hz· BF 0,09
Notes Symbols
1. The capacities are based on the following conditions: TC: Total capacity [kW]
Corresponding refrigerant piping length: ·5,0· m PI: Power input [kW]
Level difference: ·0·m SHC: Sensible heat capacity [kW]
2. The bold cells indicate the standard conditions. AFR: Air flow rate [m³/min]
BF: Bypass factor
3D130939
RXM-R 39
RXM-R
4 Capacity tables
4-1 Cooling/Heating Capacity Tables
FTXM25R / RXM25R
50Hz 220 -240V AFR 10,49
Cooling BF 0,25
4 INDOOR
EWB EDB 20 25
Outdoor temperature [°C DB]
30 32 35 40
℃ ℃ TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14 20 2,56 1,90 0,43 2,44 1,86 0,47 2,33 1,82 0,51 2,28 1,81 0,52 2,21 1,79 0,55 2,10 1,77 0,59
16 22 2,68 1,81 0,43 2,56 1,77 0,47 2,44 1,73 0,51 2,40 1,72 0,53 2,33 1,70 0,55 2,21 1,67 0,59
18 25 2,79 1,90 0,43 2,68 1,87 0,47 2,56 1,84 0,51 2,51 1,83 0,53 2,44 1,82 0,55 2,33 1,81 0,60
19 27 2,85 2,05 0,43 2,73 2,03 0,47 2,62 2,02 0,51 2,57 2,02 0,53 2,50 2,02 0,56 2,38 2,03 0,60
22 30 3,02 1,86 0,44 2,91 1,83 0,48 2,79 1,81 0,52 2,74 1,80 0,53 2,67 1,80 0,56 2,56 1,79 0,60
24 32 3,14 1,74 0,44 3,02 1,71 0,48 2,90 1,69 0,52 2,86 1,68 0,54 2,79 1,67 0,56 2,67 1,66 0,60
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. Nominal capacity and nominal input
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table (figures not
in the table may not be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values in direct
proportion.
5. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
6. The air flow rate and bypass factor are mentioned in the table. 4D130635
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. The bold cells indicate the standard conditions.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the
table (figures not in the table may not be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two
values in direct proportion.
5. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
6. The air flow rate and bypass factor are mentioned in the table.
3D110075C
40 RXM-R
RXM-R
4 Capacity tables
4-1 Cooling/Heating Capacity Tables
FBA35A9 / RXM35R
AFR 15,0
Cooling ·220-240V 50Hz· BF 0,08
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. The bold cells indicate the standard conditions.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table
(figures not in the table may not be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values in
direct proportion.
5. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
6. The air flow rate and bypass factor are mentioned in the table.
3D110072B
FDXM35F9 / RXM35R
AFR 8,7
Cooling ·220-240V 50Hz· BF 0,17
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. The bold cells indicate the standard conditions.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table
(figures not in the table may not be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values in
direct proportion.
5. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
6. The air flow rate and bypass factor are mentioned in the table.
3D110079B
RXM-R 41
RXM-R
4 Capacity tables
4-1 Cooling/Heating Capacity Tables
FFA35A9 / RXM35R
AFR 10,0
Cooling ·220-240V 50Hz· BF 0,25
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. The bold cells indicate the standard conditions.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the
figures in the table (figures not in the table may not be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation
between two values in direct proportion.
5. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
6. The air flow rate and bypass factor are mentioned in the table.
3D110083B
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. The bold cells indicate the standard conditions.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the
figures in the table (figures not in the table may not be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation
between two values in direct proportion.
5. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
6. The air flow rate and bypass factor are mentioned in the table.
3D110086B
42 RXM-R
RXM-R
4 Capacity tables
4-1 Cooling/Heating Capacity Tables
FNA35A9 / RXM35R
AFR 8,7
Cooling ·220-240V 50Hz· BF 0,17
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. The bold cells indicate the standard conditions.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the
figures in the table (figures not in the table may not be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation
between two values in direct proportion.
5. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
6. The air flow rate and bypass factor are mentioned in the table.
3D110090B
FVXM35F / RXM35R
AFR 8,5
Cooling ·220-240V 50Hz· BF 0,11
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. The bold cells indicate the standard conditions.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the
table (figures not in the table may not be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two
values in direct proportion.
5. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
6. The air flow rate and bypass factor are mentioned in the table.
3D110094B
RXM-R 43
RXM-R
4 Capacity tables
4-1 Cooling/Heating Capacity Tables
FTXM35N / RXM35R
AFR 12,3
Cooling ·220-240V 50Hz· BF 0,21
Symbols
TC: Total capacity [kW] BF: Bypass factor
PI: Power input [kW] EWB: Entering wet-bulb temperature (°C WB)
SHC: Sensible heat capacity [kW] EDB: Entering dry-bulb temperature (°C DB)
AFR: Air flow rate [m³/min]
Notes
1. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
2. The bold cells indicate the standard conditions.
Rated operating frequency [Hz]
3D120716A
FVXM35A / RXM35R
AFR 9,2
Cooling ·220-240V 50Hz· BF 0,11
Notes Symbols
1. The capacities are based on the following conditions: TC: Total capacity [kW]
Corresponding refrigerant piping length: ·5,0· m PI: Power input [kW]
Level difference: ·0·m SHC: Sensible heat capacity [kW]
2. The bold cells indicate the standard conditions. AFR: Air flow rate [m³/min]
BF: Bypass factor
3D130940
44 RXM-R
RXM-R
4 Capacity tables
4-1 Cooling/Heating Capacity Tables
FTXM35R / RXM35R
Cooling 50Hz 220 -240V AFR 11,33
BF 0,20
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. Nominal capacity and nominal input
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table (figures not
in the table may not be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values in direct
proportion.
5. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
6. The air flow rate and bypass factor are mentioned in the table.
4D130636
FTXM42R / RXM42R
4D130637A
RXM-R 45
RXM-R
4 Capacity tables
4-1 Cooling/Heating Capacity Tables
FBA50A9 / RXM50R
AFR 15,0
Cooling ·50· Hz ·220 - 240· V BF 0,13
4 Indoor
Outdoor temperature [°C DB]
temperature
EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14,0 20 5,12 3,84 1,08 4,89 3,72 1,18 4,66 3,61 1,29 4,56 3,56 1,33 4,42 3,49 1,39 4,19 3,38 1,50
16,0 22 5,35 3,77 1,09 5,12 3,66 1,19 4,89 3,55 1,29 4,79 3,51 1,34 4,65 3,45 1,40 4,42 3,34 1,50
18,0 25 5,58 3,95 1,09 5,35 3,85 1,20 5,12 3,75 1,30 5,02 3,71 1,34 4,88 3,66 1,40 4,65 3,56 1,51
19,0 27 5,70 4,18 1,10 5,47 4,08 1,20 5,23 3,98 1,30 5,14 3,94 1,35 5,00 3,89 1,41 4,77 3,79 1,51
22,0 30 6,04 4,03 1,11 5,81 3,94 1,21 5,58 3,86 1,31 5,49 3,82 1,35 5,35 3,77 1,42 5,11 3,69 1,52
24,0 32 6,27 3,92 1,11 6,04 3,85 1,22 5,81 3,77 1,32 5,72 3,74 1,36 5,58 3,69 1,42 5,34 3,62 1,53
AFR 15,0
Indoor
temperature
Outdoor temperature [°C WB]
Symbols
EDB -15 -10 -5 0 6 10
°C TC PI TC PI TC PI TC PI TC PI TC PI AFR: Air flow rate [m³/min]
15,0 2,56 1,16 3,07 1,21 3,59 1,27 4,10 1,33 5,69 1,40 6,19 1,45 BF: Bypass factor
20,0 2,40 1,19 2,92 1,25 3,43 1,31 3,95 1,37 5,50 1,44 6,00 1,48 EWB: Entering wet-bulb temperature (°C WB)
22,0 2,34 1,20 2,85 1,26 3,37 1,32 3,88 1,38 5,42 1,45 5,92 1,50 EDB: Entering dry-bulb temperature (°C DB)
24,0 2,27 1,21 2,79 1,27 3,30 1,33 3,82 1,39 5,35 1,46 5,84 1,51 TC: Total capacity [kW]
25,0 2,24 1,22 2,76 1,28 3,27 1,34 3,79 1,40 5,31 1,47 5,81 1,52 SHC: Sensible heat capacity [kW]
27,0 2,18 1,23 2,69 1,29 3,21 1,35 3,73 1,41 5,23 1,48 5,73 1,53 PI: Power input [kW]
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. On the figure the ·□· mark shows the rated capacity and rated coefficient of the power input.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table
(figures not in the table may not be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values
in direct proportion.
5. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
6. The air flow rate and bypass factor are mentioned in the table. 3D110073C
FCAG50B / RXM50R
AFR 12,6
Cooling ·50· Hz ·220 - 240· V BF 0,22
Indoor
Outdoor temperature [°C DB]
temperature
EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14,0 20 4,03 2,98 0,91 4,03 2,98 1,04 4,03 2,98 1,17 4,03 2,98 1,23 4,03 2,98 1,31 4,03 2,98 1,46
16,0 22 5,13 3,37 1,05 5,12 3,37 1,18 4,89 3,25 1,28 4,79 3,21 1,33 4,65 3,14 1,39 4,42 3,03 1,49
18,0 25 5,58 3,61 1,08 5,35 3,50 1,19 5,12 3,39 1,29 5,02 3,35 1,33 4,88 3,28 1,39 4,65 3,18 1,50
19,0 27 5,70 3,77 1,09 5,47 3,66 1,19 5,23 3,55 1,29 5,14 3,51 1,34 5,00 3,45 1,40 4,77 3,35 1,50
22,0 30 6,04 3,62 1,10 5,81 3,52 1,20 5,58 3,43 1,30 5,49 3,39 1,34 5,35 3,34 1,41 5,11 3,25 1,51
24,0 32 6,27 3,51 1,10 6,04 3,42 1,21 5,81 3,34 1,31 5,72 3,30 1,35 5,58 3,25 1,41 5,34 3,17 1,52
Indoor
Outdoor temperature [°C WB]
temperature Symbols
EDB -15 -10 -5 0 6 10
°C TC PI TC PI TC PI TC PI TC PI TC PI AFR: Air flow rate [m³/min]
15,0 2,79 1,30 3,35 1,37 3,91 1,44 4,48 1,50 6,21 1,59 6,75 1,64 BF: Bypass factor
20,0 2,62 1,34 3,18 1,41 3,74 1,47 4,31 1,54 6,00 1,62 6,54 1,68 EWB: Entering wet-bulb temperature (°C WB)
22,0 2,55 1,36 3,11 1,42 3,67 1,49 4,24 1,56 5,92 1,64 6,31 1,69 EDB: Entering dry-bulb temperature (°C DB)
24,0 2,48 1,37 3,04 1,44 3,61 1,50 4,17 1,57 5,83 1,65 5,86 1,70 TC: Total capacity [kW]
25,0 2,45 1,38 3,01 1,44 3,57 1,51 4,13 1,58 5,63 1,66 5,63 1,71 SHC: Sensible heat capacity [kW]
27,0 2,38 1,39 2,94 1,46 3,50 1,53 4,06 1,59 5,18 1,67 5,18 1,73 PI: Power input [kW]
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. On the figure the ·□· mark shows the rated capacity and rated coefficient of the power input.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table
(figures not in the table may not be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values
in direct proportion.
5. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
6. The air flow rate and bypass factor are mentioned in the table.
3D110076D
46 RXM-R
RXM-R
4 Capacity tables
4-1 Cooling/Heating Capacity Tables
FDXM50F9 / RXM50R AFR 15,8
Cooling ·50· Hz ·220 - 240· V BF 0,11
Indoor
temperature
Outdoor temperature [°C DB] 4
EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14,0 20 4,38 3,24 1,15 4,38 3,24 1,30 4,38 3,24 1,46 4,38 3,24 1,53 4,38 3,24 1,61 4,17 3,13 1,75
16,0 22 5,35 3,56 1,27 5,12 3,44 1,40 4,89 3,33 1,52 4,79 3,28 1,57 4,65 3,22 1,62 4,37 3,08 1,75
18,0 25 5,58 3,70 1,28 5,35 3,59 1,40 5,12 3,48 1,52 5,02 3,44 1,57 4,88 3,38 1,63 4,58 3,24 1,75
19,0 27 5,70 3,87 1,28 5,47 3,76 1,41 5,23 3,66 1,53 5,14 3,62 1,58 5,00 3,56 1,63 4,68 3,42 1,75
22,0 30 6,04 3,72 1,30 5,81 3,63 1,42 5,58 3,54 1,54 5,49 3,50 1,59 5,35 3,45 1,65 4,97 3,31 1,75
24,0 32 6,27 3,61 1,30 6,04 3,53 1,42 5,81 3,45 1,55 5,72 3,41 1,60 5,58 3,36 1,66 5,17 3,22 1,75
AFR 15,8
Heating ·50· Hz ·220 - 240· V
Indoor
temperature
Outdoor temperature [°C WB] Symbols
EDB -15 -10 -5 0 6 10
°C TC PI TC PI TC PI TC PI TC PI TC PI AFR: Air flow rate [m³/min]
15,0 2,70 1,51 3,24 1,58 3,78 1,66 4,33 1,74 6,00 1,83 6,52 1,89 BF: Bypass factor
20,0 2,53 1,55 3,07 1,62 3,62 1,70 4,16 1,78 5,80 1,87 6,32 1,93 EWB: Entering wet-bulb temperature (°C WB)
22,0 2,46 1,56 3,01 1,64 3,55 1,72 4,10 1,80 5,72 1,89 6,24 1,95 EDB: Entering dry-bulb temperature (°C DB)
24,0 2,40 1,58 2,94 1,66 3,49 1,74 4,03 1,81 5,64 1,90 5,96 1,97 TC: Total capacity [kW]
25,0 2,36 1,59 2,91 1,67 3,45 1,74 4,00 1,82 5,60 1,91 5,73 1,97 SHC: Sensible heat capacity [kW]
27,0 2,30 1,61 2,84 1,68 3,39 1,76 3,93 1,84 5,27 1,93 5,27 1,99 PI: Power input [kW]
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. On the figure the ·□· mark shows the rated capacity and rated coefficient of the power input.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table
(figures not in the table may not be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values
in direct proportion.
5. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
6. The air flow rate and bypass factor are mentioned in the table.
3D110080C
FVXM50A / RXM50R
AFR 11,6
Cooling ·50Hz 220-240V· BF 0,11
4D134323
RXM-R 47
RXM-R
4 Capacity tables
4-1 Cooling/Heating Capacity Tables
FFA50A9 / RXM50R
AFR 12,7
4 Indoor
temperature
Outdoor temperature [°C DB]
EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14,0 20 4,14 3,06 1,03 4,14 3,06 1,17 4,14 3,06 1,32 4,14 3,06 1,38 4,14 3,06 1,47 4,14 3,06 1,63
16,0 22 5,26 3,46 1,18 5,12 3,39 1,30 4,89 3,27 1,42 4,79 3,23 1,46 4,65 3,16 1,53 4,42 3,05 1,65
18,0 25 5,58 3,64 1,20 5,35 3,53 1,31 5,12 3,42 1,43 5,02 3,37 1,47 4,88 3,31 1,54 4,65 3,21 1,65
19,0 27 5,70 3,80 1,20 5,47 3,69 1,31 5,23 3,59 1,43 5,14 3,54 1,47 5,00 3,48 1,54 4,77 3,38 1,66
22,0 30 6,04 3,65 1,21 5,81 3,55 1,33 5,58 3,46 1,44 5,49 3,42 1,48 5,35 3,37 1,55 5,11 3,28 1,67
24,0 32 6,27 3,54 1,22 6,04 3,45 1,33 5,81 3,37 1,45 5,72 3,34 1,49 5,58 3,29 1,56 5,34 3,20 1,67
AFR 12,7
Heating ·50· Hz ·220 - 240· V
Indoor
temperature
Outdoor temperature [°C WB]
Symbols
EDB -15 -10 -5 0 6 10
°C TC PI TC PI TC PI TC PI TC PI TC PI AFR: Air flow rate [m³/min]
15,0 2,70 1,34 3,24 1,41 3,78 1,47 4,33 1,54 6,00 1,62 6,52 1,68 BF: Bypass factor
20,0 2,53 1,37 3,07 1,44 3,62 1,51 4,16 1,58 5,80 1,66 6,32 1,72 EWB: Entering wet-bulb temperature (°C WB)
22,0 2,46 1,39 3,01 1,46 3,55 1,53 4,10 1,59 5,72 1,68 6,21 1,73 EDB: Entering dry-bulb temperature (°C DB)
24,0 2,40 1,40 2,94 1,47 3,49 1,54 4,03 1,61 5,64 1,69 5,77 1,75 TC: Total capacity [kW]
25,0 2,36 1,41 2,91 1,48 3,45 1,55 4,00 1,62 5,55 1,70 5,55 1,75 SHC: Sensible heat capacity [kW]
27,0 2,30 1,43 2,84 1,50 3,39 1,56 3,93 1,63 5,10 1,71 5,10 1,77 PI: Power input [kW]
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. On the figure the ·□· mark shows the rated capacity and rated coefficient of the power input.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table
(figures not in the table may not be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values
in direct proportion.
5. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
6. The air flow rate and bypass factor are mentioned in the table.
3D110085C
FHA50A9 / RXM50R
AFR 15,0
Indoor
Outdoor temperature [°C DB]
temperature
EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14,0 20 5,05 3,73 1,18 4,89 3,65 1,31 4,66 3,53 1,43 4,56 3,49 1,47 4,42 3,42 1,54 4,19 3,30 1,66
16,0 22 5,35 3,70 1,20 5,12 3,59 1,32 4,89 3,48 1,43 4,79 3,44 1,48 4,65 3,37 1,55 4,42 3,27 1,66
18,0 25 5,58 3,87 1,21 5,35 3,77 1,32 5,12 3,66 1,44 5,02 3,62 1,49 4,88 3,56 1,55 4,65 3,47 1,67
19,0 27 5,70 4,08 1,21 5,47 3,98 1,33 5,23 3,88 1,44 5,14 3,84 1,49 5,00 3,78 1,56 4,77 3,69 1,67
22,0 30 6,04 3,93 1,22 5,81 3,84 1,34 5,58 3,75 1,45 5,49 3,72 1,50 5,35 3,67 1,57 5,11 3,58 1,68
24,0 32 6,27 3,82 1,23 6,04 3,74 1,34 5,81 3,66 1,46 5,72 3,63 1,51 5,58 3,59 1,58 5,34 3,51 1,69
AFR 15,0
Heating ·50· Hz ·220 - 240· V
Indoor
Outdoor temperature [°C WB]
temperature Symbols
EDB -15 -10 -5 0 6 10
°C TC PI TC PI TC PI TC PI TC PI TC PI AFR: Air flow rate [m³/min]
15,0 2,79 1,44 3,35 1,51 3,91 1,59 4,48 1,66 6,21 1,75 6,75 1,81 BF: Bypass factor
20,0 2,62 1,48 3,18 1,56 3,74 1,63 4,31 1,70 6,00 1,79 6,54 1,85 EWB: Entering wet-bulb temperature (°C WB)
22,0 2,55 1,50 3,11 1,57 3,67 1,64 4,24 1,72 5,92 1,81 6,46 1,87 EDB: Entering dry-bulb temperature (°C DB)
24,0 2,48 1,51 3,04 1,59 3,61 1,66 4,17 1,73 5,83 1,82 6,38 1,88 TC: Total capacity [kW]
25,0 2,45 1,52 3,01 1,60 3,57 1,67 4,13 1,74 5,79 1,83 6,33 1,89 SHC: Sensible heat capacity [kW]
27,0 2,38 1,54 2,94 1,61 3,50 1,69 4,06 1,76 5,71 1,85 6,25 1,91 PI: Power input [kW]
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. On the figure the ·□· mark shows the rated capacity and rated coefficient of the power input.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table
(figures not in the table may not be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values
in direct proportion.
5. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
6. The air flow rate and bypass factor are mentioned in the table.
3D110087C
48 RXM-R
RXM-R
4 Capacity tables
4-1 Cooling/Heating Capacity Tables
FNA50A9 / RXM50R
AFR 16,0
Cooling ·50· Hz ·220 - 240· V BF 0,12
Indoor
Outdoor temperature [°C DB]
4
temperature
EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14,0 20 5,12 3,94 1,13 4,89 3,83 1,24 4,66 3,71 1,35 4,56 3,67 1,40 4,42 3,60 1,46 4,19 3,49 1,57
16,0 22 5,35 3,87 1,14 5,12 3,77 1,25 4,89 3,66 1,36 4,79 3,62 1,40 4,65 3,56 1,47 4,42 3,45 1,58
18,0 25 5,58 4,08 1,15 5,35 3,98 1,26 5,12 3,88 1,37 5,02 3,84 1,41 4,88 3,78 1,48 4,65 3,69 1,59
19,0 27 5,70 4,32 1,15 5,47 4,22 1,26 5,23 4,13 1,37 5,14 4,09 1,41 5,00 4,04 1,48 4,77 3,94 1,59
22,0 30 6,04 4,17 1,16 5,81 4,09 1,27 5,58 4,00 1,38 5,49 3,97 1,42 5,35 3,92 1,49 5,11 3,84 1,60
24,0 32 6,27 4,07 1,17 6,04 3,99 1,28 5,81 3,92 1,39 5,72 3,89 1,43 5,58 3,84 1,50 5,34 3,77 1,60
AFR 16,0
Heating ·50· Hz ·220 - 240· V
Indoor
Outdoor temperature [°C WB]
temperature Symbols
EDB -15 -10 -5 0 6 10
°C TC PI TC PI TC PI TC PI TC PI TC PI AFR: Air flow rate [m³/min]
15,0 2,70 1,40 3,24 1,47 3,78 1,54 4,33 1,61 6,00 1,70 6,52 1,75 BF: Bypass factor
20,0 2,53 1,44 3,07 1,51 3,62 1,58 4,16 1,65 5,80 1,74 6,32 1,79 EWB: Entering wet-bulb temperature (°C WB)
22,0 2,46 1,45 3,01 1,52 3,55 1,59 4,10 1,67 5,72 1,75 6,24 1,81 EDB: Entering dry-bulb temperature (°C DB)
24,0 2,40 1,47 2,94 1,54 3,49 1,61 4,03 1,68 5,64 1,77 6,16 1,83 TC: Total capacity [kW]
25,0 2,36 1,48 2,91 1,55 3,45 1,62 4,00 1,69 5,60 1,78 6,12 1,83 SHC: Sensible heat capacity [kW]
27,0 2,30 1,49 2,84 1,56 3,39 1,63 3,93 1,71 5,52 1,79 6,04 1,85 PI: Power input [kW]
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. On the figure the ·□· mark shows the rated capacity and rated coefficient of the power input.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table
(figures not in the table may not be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values
in direct proportion.
5. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
6. The air flow rate and bypass factor are mentioned in the table.
3D110091C
FVXM50F / RXM50R
AFR 10,1
Cooling ·50· Hz ·220 - 240· V BF 0,13
Indoor
temperature
Outdoor temperature [°C DB]
EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14,0 20 3,82 2,82 0,98 3,82 2,82 1,12 3,82 2,82 1,27 3,82 2,82 1,33 3,82 2,82 1,42 3,82 2,82 1,57
16,0 22 4,86 3,20 1,12 4,86 3,20 1,27 4,86 3,20 1,42 4,79 3,16 1,47 4,65 3,09 1,54 4,42 2,98 1,65
18,0 25 5,58 3,56 1,20 5,35 3,45 1,32 5,12 3,34 1,43 5,02 3,29 1,48 4,88 3,23 1,54 4,65 3,12 1,66
19,0 27 5,70 3,71 1,20 5,47 3,60 1,32 5,23 3,49 1,43 5,14 3,45 1,48 5,00 3,39 1,55 4,77 3,28 1,66
22,0 30 6,04 3,56 1,21 5,81 3,46 1,33 5,58 3,37 1,44 5,49 3,33 1,49 5,35 3,27 1,56 5,11 3,18 1,67
24,0 32 6,27 3,45 1,22 6,04 3,36 1,34 5,81 3,27 1,45 5,72 3,24 1,50 5,58 3,19 1,57 5,34 3,10 1,68
AFR 11,8
Heating ·50· Hz ·220 - 240· V
Indoor
temperature
Outdoor temperature [°C WB] Symbols
EDB -15 -10 -5 0 6 10
°C TC PI TC PI TC PI TC PI TC PI TC PI AFR: Air flow rate [m³/min]
15,0 2,70 1,29 3,24 1,35 3,78 1,42 4,33 1,48 6,00 1,56 6,52 1,61 BF: Bypass factor
20,0 2,53 1,32 3,07 1,39 3,62 1,45 4,16 1,52 5,80 1,60 6,32 1,65 EWB: Entering wet-bulb temperature (°C WB)
22,0 2,46 1,34 3,01 1,40 3,55 1,47 4,10 1,53 5,72 1,61 6,24 1,66 EDB: Entering dry-bulb temperature (°C DB)
24,0 2,40 1,35 2,94 1,42 3,49 1,48 4,03 1,55 5,64 1,63 5,79 1,68 TC: Total capacity [kW]
25,0 2,36 1,36 2,91 1,42 3,45 1,49 4,00 1,55 5,57 1,63 5,57 1,69 SHC: Sensible heat capacity [kW]
27,0 2,30 1,37 2,84 1,44 3,39 1,50 3,93 1,57 5,13 1,65 5,13 1,70 PI: Power input [kW]
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. On the figure the ·□· mark shows the rated capacity and rated coefficient of the power input.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table
(figures not in the table may not be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values
in direct proportion.
5. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
6. The air flow rate and bypass factor are mentioned in the table.
3D110095C
RXM-R 49
RXM-R
4 Capacity tables
4-1 Cooling/Heating Capacity Tables
FTXM50N / RXM50R
AFR 16,1
Cooling ·50· Hz ·220 - 240· V BF 0,13
4 Indoor
temperature
Outdoor temperature [°C DB]
EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14,0 20 4,11 3,04 1,07 3,88 2,93 1,14 3,65 2,83 1,21 3,55 2,78 1,28 3,41 2,72 1,34 3,18 2,62 1,44
16,0 22 5,26 3,46 1,08 5,03 3,35 1,15 4,80 3,25 1,22 4,70 3,20 1,29 4,56 3,14 1,35 4,33 3,04 1,44
18,0 25 5,58 3,66 1,08 5,35 3,55 1,15 5,12 3,45 1,22 5,02 3,40 1,29 4,88 3,34 1,36 4,65 3,24 1,45
19,0 27 5,70 3,83 1,09 5,47 3,72 1,16 5,23 3,62 1,23 5,14 3,58 1,30 5,00 3,52 1,36 4,77 3,42 1,45
22,0 30 6,04 3,68 1,09 5,81 3,59 1,16 5,58 3,50 1,23 5,49 3,46 1,30 5,35 3,40 1,37 5,11 3,32 1,46
24,0 32 6,27 3,57 1,09 6,04 3,49 1,16 5,81 3,40 1,23 5,72 3,37 1,30 5,58 3,32 1,38 5,34 3,24 1,47
AFR 17,1
Heating ·50· Hz ·220 - 240· V
Indoor
temperature
Outdoor temperature [°C WB]
Symbols
EDB -15 -10 -5 0 6 10
°C TC PI TC PI TC PI TC PI TC PI TC PI AFR: Air flow rate [m³/min]
15,0 2,76 0,93 3,32 0,98 3,88 1,03 4,43 1,35 6,00 1,42 6,52 1,47 BF: Bypass factor
20,0 2,59 0,96 3,15 1,01 3,71 1,05 4,26 1,38 5,80 1,45 6,32 1,50 EWB: Entering wet-bulb temperature (°C WB)
22,0 2,52 0,97 3,08 1,02 3,64 1,07 4,19 1,39 5,72 1,46 6,24 1,51 EDB: Entering dry-bulb temperature (°C DB)
24,0 2,46 0,98 3,01 1,03 3,57 1,08 4,12 1,40 5,64 1,48 6,16 1,52 TC: Total capacity [kW]
25,0 2,42 0,99 2,98 1,03 3,54 1,08 4,09 1,41 5,60 1,48 6,12 1,53 SHC: Sensible heat capacity [kW]
27,0 2,35 1,00 2,91 1,04 3,47 1,09 4,02 1,42 5,52 1,50 6,04 1,54 PI: Power input [kW]
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. On the figure the ·□· mark shows the rated capacity and rated coefficient of the power input.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table
(figures not in the table may not be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values
in direct proportion.
5. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
6. The air flow rate and bypass factor are mentioned in the table.
3D120632A
FTXM50R / RXM50R
Cooling ·50· Hz ·220-240· V AFR 15,45
BF 0,21
Notes
1) The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2) On the figure the · · mark shows the rated capacity and rated coefficient of the power input.
3) The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table (figures not in the table may not be
used in the calculation).
4) In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values in direct proportion.
3D131701
50 RXM-R
R
XM-R
4 Capacity tables
4-1 Cooling/Heating Capacity Tables
FBA60A9 / RXM60R
AFR 18,0
Cooling ·50· Hz ·220 - 240· V BF 0,15
Indoor
temperature
Outdoor temperature [°C DB] 4
EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14,0 20 5,84 4,42 1,26 5,57 4,28 1,38 5,31 4,16 1,50 5,20 4,10 1,55 5,04 4,03 1,62 4,78 3,90 1,74
16,0 22 6,10 4,34 1,26 5,84 4,22 1,38 5,57 4,09 1,51 5,47 4,05 1,55 5,31 3,97 1,63 5,04 3,86 1,75
18,0 25 6,36 4,56 1,27 6,10 4,44 1,39 5,83 4,33 1,51 5,73 4,29 1,56 5,57 4,22 1,63 5,30 4,11 1,76
19,0 27 6,50 4,82 1,27 6,23 4,71 1,40 5,97 4,60 1,52 5,86 4,56 1,57 5,70 4,49 1,64 5,43 4,39 1,76
22,0 30 6,89 4,65 1,29 6,62 4,55 1,41 6,36 4,46 1,53 6,25 4,42 1,58 6,09 4,36 1,65 5,83 4,27 1,77
24,0 32 7,15 4,53 1,29 6,89 4,44 1,41 6,62 4,36 1,54 6,52 4,32 1,58 6,36 4,27 1,66 6,09 4,18 1,78
AFR 18,0
Heating ·50· Hz ·220 - 240· V
Indoor
Outdoor temperature [°C WB]
temperature Symbols
EDB -15 -10 -5 0 6 10
°C TC PI TC PI TC PI TC PI TC PI TC PI AFR: Air flow rate [m³/min]
15,0 3,39 1,52 4,08 1,60 4,76 1,67 5,44 1,75 7,24 1,84 7,87 1,91 BF: Bypass factor
20,0 3,18 1,56 3,87 1,64 4,55 1,72 5,23 1,79 7,00 1,89 7,63 1,95 EWB: Entering wet-bulb temperature (°C WB)
22,0 3,10 1,58 3,78 1,66 4,47 1,73 5,15 1,81 6,90 1,90 7,54 1,97 EDB: Entering dry-bulb temperature (°C DB)
24,0 3,02 1,59 3,70 1,67 4,38 1,75 5,07 1,83 6,81 1,92 7,44 1,98 TC: Total capacity [kW]
25,0 2,97 1,60 3,66 1,68 4,34 1,76 5,03 1,84 6,76 1,93 7,39 1,99 SHC: Sensible heat capacity [kW]
27,0 2,89 1,62 3,57 1,70 4,26 1,78 4,94 1,85 6,66 1,95 7,29 2,01 PI: Power input [kW]
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. On the figure the ·□· mark shows the rated capacity and rated coefficient of the power input.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table
(figures not in the table may not be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values
in direct proportion.
5. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
6. The air flow rate and bypass factor are mentioned in the table.
3D110074C
FCAG60B / RXM60R
AFR 13,6
Cooling ·50· Hz ·220 - 240· V BF 0,2
Indoor
Outdoor temperature [°C DB]
temperature
EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14,0 20 4,47 3,30 1,12 4,47 3,30 1,28 4,47 3,30 1,44 4,47 3,30 1,51 4,47 3,30 1,61 4,47 3,30 1,78
16,0 22 5,68 3,73 1,27 5,68 3,73 1,43 5,57 3,68 1,58 5,47 3,63 1,63 5,31 3,55 1,71 5,04 3,42 1,84
18,0 25 6,36 4,09 1,34 6,10 3,96 1,16 5,83 3,83 1,59 5,73 3,78 1,64 5,57 3,71 1,72 5,30 3,59 1,85
19,0 27 6,50 4,26 1,34 6,23 4,14 1,47 5,97 4,01 1,59 5,86 3,97 1,65 5,70 3,89 1,72 5,43 3,78 1,85
22,0 30 6,89 4,09 1,35 6,62 3,98 1,48 6,36 3,87 1,61 6,25 3,83 1,66 6,09 3,76 1,73 5,83 3,66 1,86
24,0 32 7,15 3,96 1,36 6,89 3,86 1,49 6,62 3,76 1,61 6,52 3,73 1,66 6,36 3,67 1,74 6,09 3,57 1,87
AFR 13,6
Heating ·50· Hz ·220 - 240· V
Indoor
Outdoor temperature [°C WB]
temperature
Symbols
EDB -15 -10 -5 0 6 10
°C TC PI TC PI TC PI TC PI TC PI TC PI AFR: Air flow rate [m³/min]
15,0 3,39 1,67 4,08 1,75 4,76 1,84 5,44 1,92 7,24 2,02 7,87 2,09 BF: Bypass factor
20,0 3,18 1,71 3,87 1,80 4,55 1,88 5,23 1,97 7,00 2,07 7,63 2,14 EWB: Entering wet-bulb temperature (°C WB)
22,0 3,10 1,73 3,78 1,82 4,47 1,90 5,15 1,99 6,90 2,09 7,54 2,16 EDB: Entering dry-bulb temperature (°C DB)
24,0 3,02 1,75 3,70 1,84 4,38 1,92 5,07 2,01 6,81 2,11 7,38 2,18 TC: Total capacity [kW]
25,0 2,97 1,76 3,66 1,84 4,34 1,93 5,03 2,02 6,76 2,12 7,13 2,19 SHC: Sensible heat capacity [kW]
27,0 2,89 1,78 3,57 1,86 4,26 1,95 4,94 2,03 6,64 2,14 6,64 2,20 PI: Power input [kW]
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. On the figure the ·□· mark shows the rated capacity and rated coefficient of the power input.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table
(figures not in the table may not be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values
in direct proportion.
5. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
6. The air flow rate and bypass factor are mentioned in the table.
3D110077D
R
XM-R 51
RXM-R
4 Capacity tables
4-1 Cooling/Heating Capacity Tables
FDXM60F9 / RXM60R
AFR 16,0
Cooling ·50· Hz ·220 - 240· V BF 0,12
4 Indoor
temperature
Outdoor temperature [°C DB]
EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14,0 20 5,78 4,27 1,53 5,78 4,27 1,72 5,59 4,17 1,89 5,48 4,11 1,95 5,31 4,03 2,03 4,37 3,58 2,01
16,0 22 6,42 4,38 1,59 6,14 4,24 1,74 5,86 4,11 1,90 5,75 4,06 1,96 5,59 3,98 2,04 4,59 3,53 2,01
18,0 25 6,70 4,57 1,60 6,42 4,44 1,75 6,14 4,32 1,91 6,03 4,27 1,97 5,86 4,20 2,05 4,81 3,75 2,01
19,0 27 6,84 4,80 1,60 6,56 4,68 1,76 6,28 4,56 1,91 6,17 4,51 1,97 6,00 4,44 2,05 4,92 4,00 2,01
22,0 30 7,25 4,62 1,62 6,97 4,52 1,77 6,69 4,41 1,92 6,58 4,37 1,98 6,41 4,31 2,07 5,24 3,89 2,01
24,0 32 7,53 4,50 1,63 7,25 4,40 1,78 6,97 4,30 1,93 6,86 4,26 1,99 6,69 4,21 2,07 5,46 3,80 2,01
AFR 16,0
Heating ·50· Hz ·220 - 240· V
Indoor
temperature
Outdoor temperature [°C WB]
Symbols
EDB -15 -10 -5 0 6 10
°C TC PI TC PI TC PI TC PI TC PI TC PI AFR: Air flow rate [m³/min]
15,0 3,39 1,75 4,08 1,84 4,76 1,93 5,44 2,02 7,24 2,13 7,87 2,20 BF: Bypass factor
20,0 3,18 1,80 3,87 1,89 4,55 1,98 5,23 2,07 7,00 2,18 7,63 2,25 EWB: Entering wet-bulb temperature (°C WB)
22,0 3,10 1,82 3,78 1,91 4,47 2,00 5,15 2,09 6,90 2,20 7,54 2,27 EDB: Entering dry-bulb temperature (°C DB)
24,0 3,02 1,84 3,70 1,93 4,38 2,02 5,07 2,11 6,81 2,22 7,44 2,29 TC: Total capacity [kW]
25,0 2,97 1,85 3,66 1,94 4,34 2,03 5,03 2,12 6,76 2,23 7,39 2,30 SHC: Sensible heat capacity [kW]
27,0 2,89 1,87 3,57 1,96 4,26 2,05 4,94 2,14 6,66 2,25 7,29 2,32 PI: Power input [kW]
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. On the figure the ·□· mark shows the rated capacity and rated coefficient of the power input.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in
the table (figures not in the table may not be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between
two values in direct proportion.
5. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
6. The air flow rate and bypass factor are mentioned in the table.
3D110081C
FFA60A9 / RXM60R
AFR 14,5
Cooling ·50· Hz ·220 - 240· V BF 0,11
Indoor
Outdoor temperature [°C DB]
temperature
EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14,0 20 5,30 3,91 1,36 5,30 3,91 1,53 5,30 3,91 1,71 5,20 3,86 1,77 5,04 3,78 1,85 4,78 3,65 1,99
16,0 22 6,10 4,12 1,44 5,84 3,99 1,58 5,57 3,86 1,72 5,47 3,81 1,77 5,31 3,73 1,86 5,04 3,61 1,99
18,0 25 6,36 4,29 1,45 6,10 4,17 1,59 5,83 4,05 1,73 5,73 4,00 1,78 5,57 3,93 1,86 5,30 3,82 2,00
19,0 27 6,50 4,50 1,45 6,23 4,38 1,59 5,97 4,27 1,73 5,86 4,22 1,79 5,70 4,16 1,87 5,43 4,05 2,01
22,0 30 6,89 4,33 1,47 6,62 4,23 1,61 6,36 4,13 1,74 6,25 4,09 1,80 6,09 4,03 1,88 5,78 3,91 2,01
24,0 32 7,15 4,21 1,48 6,89 4,12 1,61 6,62 4,02 1,75 6,52 3,99 1,81 6,36 3,93 1,89 6,01 3,82 2,01
AFR 14,5
Heating ·50· Hz ·220 - 240· V
Indoor
Outdoor temperature [°C WB]
temperature Symbols
EDB -15 -10 -5 0 6 10
°C TC PI TC PI TC PI TC PI TC PI TC PI AFR: Air flow rate [m³/min]
15,0 3,39 1,65 4,08 1,74 4,76 1,82 5,44 1,91 7,24 2,01 7,87 2,07 BF: Bypass factor
20,0 3,18 1,70 3,87 1,78 4,55 1,87 5,23 1,95 7,00 2,05 7,63 2,12 EWB: Entering wet-bulb temperature (°C WB)
22,0 3,10 1,72 3,78 1,80 4,47 1,89 5,15 1,97 6,90 2,07 7,54 2,14 EDB: Entering dry-bulb temperature (°C DB)
24,0 3,02 1,73 3,70 1,82 4,38 1,90 5,07 1,99 6,81 2,09 7,44 2,16 TC: Total capacity [kW]
25,0 2,97 1,74 3,66 1,83 4,34 1,91 5,03 2,00 6,76 2,10 7,39 2,17 SHC: Sensible heat capacity [kW]
27,0 2,89 1,76 3,57 1,85 4,26 1,93 4,94 2,02 6,66 2,12 7,29 2,19 PI: Power input [kW]
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. On the figure the ·□· mark shows the rated capacity and rated coefficient of the power input.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table
(figures not in the table may not be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values
in direct proportion.
5. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
6. The air flow rate and bypass factor are mentioned in the table. 3D110084C
52 RXM-R
RXM-R
4 Capacity tables
4-1 Cooling/Heating Capacity Tables
FHA60A9 / RXM60R
AFR 19,5
Cooling ·50· Hz ·220 - 240· V BF 0,2
Indoor
temperature
Outdoor temperature [°C DB] 4
EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14,0 20 5,84 4,45 1,33 5,57 4,32 1,46 5,31 4,19 1,59 5,20 4,13 1,64 5,04 4,06 1,71 4,78 3,93 1,84
16,0 22 6,10 4,37 1,34 5,84 4,25 1,47 5,57 4,13 1,59 5,47 4,08 1,64 5,31 4,01 1,72 5,04 3,89 1,85
18,0 25 6,36 4,59 1,34 6,10 4,48 1,47 5,83 4,37 1,60 5,73 4,32 1,65 5,57 4,26 1,73 5,30 4,15 1,86
19,0 27 6,50 4,86 1,35 6,23 4,75 1,48 5,97 4,64 1,60 5,86 4,60 1,66 5,70 4,54 1,73 5,43 4,43 1,86
22,0 30 6,89 4,69 1,36 6,62 4,60 1,49 6,36 4,50 1,62 6,25 4,46 1,67 6,09 4,41 1,74 5,83 4,31 1,87
24,0 32 7,15 4,57 1,37 6,89 4,49 1,50 6,62 4,40 1,62 6,52 4,36 1,68 6,36 4,31 1,75 6,09 4,23 1,88
AFR 19,5
Heating ·50· Hz ·220 - 240· V
Indoor
Outdoor temperature [°C WB]
temperature Symbols
EDB -15 -10 -5 0 6 10
°C TC PI TC PI TC PI TC PI TC PI TC PI AFR: Air flow rate [m³/min]
15,0 3,49 1,74 4,19 1,83 4,90 1,92 5,60 2,01 7,45 2,12 8,10 2,19 BF: Bypass factor
20,0 3,27 1,79 3,98 1,88 4,68 1,97 5,38 2,06 7,20 2,17 7,85 2,24 EWB: Entering wet-bulb temperature (°C WB)
22,0 3,19 1,81 3,89 1,90 4,59 1,99 5,30 2,08 7,10 2,19 7,75 2,26 EDB: Entering dry-bulb temperature (°C DB)
24,0 3,10 1,83 3,81 1,92 4,51 2,01 5,21 2,10 7,00 2,21 7,65 2,28 TC: Total capacity [kW]
25,0 3,06 1,84 3,76 1,93 4,47 2,02 5,17 2,11 6,95 2,22 7,60 2,29 SHC: Sensible heat capacity [kW]
27,0 2,97 1,86 3,68 1,95 4,38 2,04 5,08 2,13 6,85 2,24 7,50 2,31 PI: Power input [kW]
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. On the figure the ·□· mark shows the rated capacity and rated coefficient of the power input.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table
(figures not in the table may not be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values
in direct proportion.
5. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
6. The air flow rate and bypass factor are mentioned in the table. 3D110088C
FNA60A9 / RXM60R
AFR 16,0
Cooling ·50· Hz ·220 - 240· V BF 0,12
Indoor
Outdoor temperature [°C DB]
temperature
EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14,0 20 5,78 4,27 1,66 5,78 4,27 1,86 5,59 4,17 2,03 5,48 4,11 2,10 5,31 4,03 2,20 3,82 3,32 2,01
16,0 22 6,42 4,38 1,71 6,14 4,24 1,88 5,86 4,11 2,04 5,75 4,06 2,11 5,59 3,98 2,21 4,02 3,28 2,01
18,0 25 6,70 4,57 1,72 6,42 4,44 1,89 6,14 4,32 2,05 6,03 4,27 2,12 5,86 4,20 2,22 4,22 3,51 2,01
19,0 27 6,84 4,80 1,73 6,56 4,68 1,89 6,28 4,56 2,06 6,17 4,51 2,12 6,00 4,44 2,22 4,32 3,77 2,01
22,0 30 7,25 4,62 1,74 6,97 4,52 1,91 6,69 4,41 2,07 6,58 4,37 2,14 6,41 4,31 2,24 4,62 3,67 2,01
24,0 32 7,53 4,50 1,75 7,25 4,40 1,92 6,97 4,30 2,08 6,86 4,26 2,15 6,69 4,21 2,25 4,82 3,60 2,01
AFR 16,0
Heating ·50· Hz ·220 - 240· V
Indoor
temperature
Outdoor temperature [°C WB]
Symbols
EDB -15 -10 -5 0 6 10
°C TC PI TC PI TC PI TC PI TC PI TC PI AFR: Air flow rate [m³/min]
15,0 3,39 1,81 4,08 1,90 4,76 2,00 5,44 2,09 7,24 2,20 7,87 2,27 BF: Bypass factor
20,0 3,18 1,86 3,87 1,95 4,55 2,05 5,23 2,14 7,00 2,25 7,63 2,32 EWB: Entering wet-bulb temperature (°C WB)
22,0 3,10 1,88 3,78 1,97 4,47 2,07 5,15 2,16 6,90 2,27 7,54 2,35 EDB: Entering dry-bulb temperature (°C DB)
24,0 3,02 1,90 3,70 1,99 4,38 2,09 5,07 2,18 6,81 2,29 7,44 2,37 TC: Total capacity [kW]
25,0 2,97 1,91 3,66 2,00 4,34 2,10 5,03 2,19 6,76 2,30 7,39 2,38 SHC: Sensible heat capacity [kW]
27,0 2,89 1,93 3,57 2,03 4,26 2,12 4,94 2,21 6,66 2,32 7,29 2,40 PI: Power input [kW]
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. On the figure the ·□· mark shows the rated capacity and rated coefficient of the power input.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table
(figures not in the table may not be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values in
direct proportion.
5. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
6. The air flow rate and bypass factor are mentioned in the table.
3D110092C
RXM-R 53
RXM-R
4 Capacity tables
4-1 Cooling/Heating Capacity Tables
FTXM60N / RXM60R
FTXM60R / RXM60R
AFR 17,1
Cooling BF 0,17
4
·50· Hz ·220 - 240· V
Indoor
temperature
Outdoor temperature [°C DB]
EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14,0 20 5,10 3,76 0,19 4,82 3,63 0,31 4,55 3,51 0,80 4,38 3,45 1,66 4,26 3,38 1,75 4,09 3,26 1,88
16,0 22 6,31 4,18 0,20 6,04 4,05 0,33 5,76 3,93 0,81 5,64 3,87 1,67 5,47 3,80 1,76 5,30 3,68 1,88
18,0 25 6,70 4,39 0,20 6,42 4,26 0,34 6,14 4,14 0,82 6,02 4,08 1,67 5,86 4,00 1,77 5,58 3,88 1,89
19,0 27 6,84 4,59 0,22 6,56 4,46 0,34 6,28 4,34 0,82 6,17 4,29 1,69 6,00 4,22 1,77 5,72 4,10 1,89
22,0 30 7,25 4,41 0,22 6,97 4,30 0,34 6,70 4,20 0,83 6,59 4,15 1,70 6,42 4,08 1,78 6,13 3,98 1,90
24,0 32 7,52 4,28 0,22 7,25 4,18 0,34 6,97 4,08 0,83 6,86 4,04 1,70 6,70 3,98 1,79 6,41 3,88 1,92
AFR 17,7
Heating ·50· Hz ·220 - 240· V
Indoor
Outdoor temperature [°C WB]
temperature Symbols
EDB -15 -10 -5 0 6 10
°C TC PI TC PI TC PI TC PI TC PI TC PI AFR: Air flow rate [m³/min]
15,0 3,33 1,24 4,01 1,31 4,68 1,38 6,29 1,81 7,24 1,90 7,87 1,97 BF: Bypass factor
20,0 3,13 1,29 3,80 1,35 4,48 1,41 6,05 1,85 7,00 1,94 7,63 2,01 EWB: Entering wet-bulb temperature (°C WB)
22,0 3,04 1,30 3,72 1,37 4,39 1,43 5,95 1,86 6,90 1,95 7,53 2,02 EDB: Entering dry-bulb temperature (°C DB)
24,0 2,97 1,31 3,63 1,38 4,31 1,45 5,85 1,87 6,81 1,98 7,43 2,03 TC: Total capacity [kW]
25,0 2,92 1,33 3,60 1,38 4,27 1,45 5,80 1,89 6,76 1,98 7,39 2,05 SHC: Sensible heat capacity [kW]
27,0 2,84 1,34 3,51 1,39 4,19 1,46 5,71 1,90 6,66 2,01 7,29 2,06 PI: Power input [kW]
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. On the figure the ·□· mark shows the rated capacity and rated coefficient of the power input.
3. The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table
(figures not in the table may not be used in the calculation).
4. In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values
in direct proportion.
5. The capacities are based on the following conditions:
Corresponding refrigerant piping length: ·5· m
Level difference: ·0·m
6. The air flow rate and bypass factor are mentioned in the table.
3D117546B
FTXM60R / RXM60R
AFR 16,22
Notes
1) The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2) On the figure the · · mark shows the rated capacity and rated coefficient of the power input.
3) The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table (figures not in the table may not be used in the
calculation).
4) In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values in direct proportion.
3D131702
54 RXM-R
RXM-R
4 Capacity tables
4-1 Cooling/Heating Capacity Tables
FTXM71R / RXM71R
·50· Hz ·220-240· V AFR 15,95
Cooling BF 0,06
Notes
1) The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2) On the figure the · · mark shows the rated capacity and rated coefficient of the power input.
3) The total capacity, power input and sensible heat capacity must be calculated by interpolation, using the figures in the table (figures not in the table may not be used in the
calculation).
4) In case the sensible heat capacity is not mentioned in the table, please calculate it using an approximation between two values in direct proportion.
3D131703
RXM-R 55
RXM-R
5 Dimensional drawings
5-1 Dimensional Drawings
RXM20-35R
Drain outlet
574 105.5
13
490
5
29.5
311
350 840
284.2 12 765 63 Manufacturer label
44.9 Brand name label In case of removing the stop valve cover. Outdoor air temperature thermistor
Handle
·Ø6.4· CuT
165
105
19
Gas stop valve
Product liability label 231
Nameplate ·Ø9.5· CuT
150
100
150
300
50
50 50
100
100
3D119881A
RXM42R
19
734
401 23
353
373
Caution label
100
50
Liquid stop valve
·Ø6.4· CuT
50
Gas stop valve
50
·Ø9.5· CuT
350
165
105
100
350
Service port
3D134937
170
56 RXM-R
R
XM-R
5 Dimensional drawings
5-1 Dimensional Drawings
RXM42-60R
Handle
Brand name label
Wiring intake area
5
954
Outdoor air temperature thermistor
13 320 56 ( 14 ) 870 70
Nameplate
Manufacturer label
19
Product liability label
734
23
401
353
373
ø6.4 CuT
100
100
50
105
50
350
170
100
Service port
350
3D114108B
Nameplate
Manufacturer label
734
Product liability 19
label
23
401
4 holes for anchor bolts 600 125
·M8· or ·M10·
10
17.2
353
373
ø6.4 CuT
ø15.9 CuT
50 50
50
165
105
350
100
3D100867E
R
XM-R 57
R
XM-R
6 Centre of gravity
6-1 Centre of Gravity
RXM20-35R
350.1
840
6
765 62.9
552
248
394 136
311
85.4 574
4D119880
RXM42-60R
870 70 55 320
734
307
408 169
4D117299
58 R
XM-R
R
XM-R
6 Centre of gravity
6-1 Centre of Gravity
RXM71R
6
280
196 184.1
584 125 368
4D100855B
R
XM-R 59
RXM-R
7 Piping diagrams
7-1 Piping Diagrams
RXM20-35R
7 Outdoor unit
7.0 CuT Heat exchanger
Outdoor air temperature thermistor
7.0 CuT
9.5 CuT
6.4 CuT
4.8 CuT
Muffler with filter
M Muffler with filter
Ø.4.0 x ID.2.0 CuT
Propeller fan
9.5 CuT
9.5 CuT
Muffler with filter
6.4 CuT
4-way valve
ON: heating
Field piping
7.9 CuT
6.4 CuT
Liquid stop valve
9.5 CuT
Muffler
Muffler
Discharge pipe thermistor
9.5 CuT
9.5 CuT
Field piping
7.9 CuT
Compressor 9.5 CuT
Accumulator Muffler Gas stop valve
Refrigerant flow
Cooling
Heating
3D091995B
RXM42R
Outdoor unit Refrigerant flow
Heat exchanger Outdoor air temperature thermistor Cooling
·7.0· CuT
Heat exchanger thermistor Heating
·7.0· CuT
Capillary tube ·1·
·12.7· CuT
M
Propeller fan Filter
·6.4· CuT
·12.7· CuT
4-way valve
ON: heating
·12.7· CuT ·12.7· CuT
·6.4· CuT
Muffler
Discharge pipe thermistor
·9.5· CuT
·9.5· CuT
Liquid receiver
·6.4· CuT
Muffler Muffler
HPS Field piping
High pressure switch ·6.4· CuT
Automatic reset Liquid stop valve
3D128942
60 RXM-R
R
XM-R
7 Piping diagrams
7-1 Piping Diagrams
RXM50-60R
Outdoor unit Refrigerant flow
Heat exchanger Outdoor air temperature thermistor Cooling 7
·7.0· CuT
Heat exchanger thermistor Heating
·7.0· CuT
Capillary tube ·1·
·12.7· CuT
M
Propeller fan Filter
Muffler
Discharge pipe thermistor
·9.5· CuT
·9.5· CuT
Liquid receiver
3D128943
RXM71R
Refrigerant flow
Outdoor unit
Cooling
Heat exchanger Outdoor air temperature thermistor
Heating
·7.0· CuT
·7.0· CuT Heat exchanger thermistor
Capillary tube ·1·
·12.7· CuT
M
Propeller fan Filter
·12.7· CuT
·6.4· CuT
4-way valve
ON: heating
·12.7· CuT ·12.7· CuT
·9.5· CuT
High pressure switch
Automatic reset
3D128864
R
XM-R 61
RXM-R
8 Wiring diagrams
8-1 Wiring Diagrams - Single Phase
RXM20-35R
Field wiring Wiring diagram For the power requirements, refer to the nameplate.
8
Indoor X1M F4U A1P IPM1
L 30A DB1
HL1 MRM10
1 BLK + +
1
2 HN1 +
N 2 WHT V2 Z1F PAM C7
3 3 RED S MRM20
- -
Z3C V3
L WVU
N MR30 FU1 V150 PS FU2
SA1 3.15A 3.15A
GRN/YLW
E1 3 1
MR30_A MR30_B MR4
E2 IPM2 - V + S30
U W
1 2 1 S50 2 1 S20 5 1 3 1 6 1 3 5
GRN
Z2C
GRN
BLK
BRN
BRN
BLK
BLK
BLK
BLK
BLK
WHT
BLU
YLW
RED
YLW
RED
GRY
ORG
RED
YLW
BLK
GRY
BLK
YLW
YLW
C7 : Capacitor X11A t t t
WV U
DB1 : Diode bridge M MS
BLK
BLK
IPM1 Y1S MS 3~
R1T R2T R3T
IPM2 : Intelligent power module Q1L Y1E Outdoor Discharge
L : Live Condenser M1F M1C
M1C : Compressor motor
M1F : Fan motor FU1,FU2,F4U : Fuse BLK : Black : Protective earth
N : Neutral MR4,MR30 WHT : White : Earth
PAM : Pulse-amplitude modulation MRM10,MRM20 : Magnetic relay BRN : Brown
A1P : Printed circuit board R1T,R2T,R3T : Thermistor RED : Red
PS : Switching power supply S20,S30,S40,S70 GRN : Green
Q1L : Overload protector S80,S90,X11A : Connector YLW : Yellow
SA1 : Surge arrestor V2,V3,V150 : Varistor ORG : Orange
X1M : Terminal strip Z1C,Z2C,Z3C : Ferrite core BLU : Blue
Y1E : Electronic expansion valve coil Z1F : Noise filter GRY : Grey
Y1S : Reversing solenoid valve coil
Notes
Size: 140 x 80
Refer to purchasing specification AS303002, unless otherwise specified. 4D120154
RXM42R
Field wiring Wiring diagram For the power requirements, refer to the nameplate.
Indoor
FU3 IPM1
X1M Z3C 30A DB1 PAM
HL1 MRM10 +
1 L 1 BLK +
2 N 2 WHT HN1 V2 MRM20 +
3 S ZF C7
3 RED U +tv -
N=5 -
L V3 V1
GRN/YLW
MR30 U
FU2 W VU
N U
3.15A
FU1
3.15A D1 D2
Z2C
SA1
BLU
YLW
RED
E1 MRCW PS
N=4 E2
GRN
1 7 1 3 1 6 1 6 1 4 1 4 7 Z1C
PCB S2 S80 S20 S90 S40 S70 N=4
GRN
X11A
BLK
BLK
BLK
BLK
BLK
BLK
GRY
GRY
BLK
BLK
WHT
ORG
BRN
BLU
RED
RED
WHT
YLW
ORG
BLU
PPL
PPL
BLU
YLW
RED
M tv tv tv MS
Y1S R1T R2T R3T P> WV U
Outdoor Y1E Outdoor Discharge
Condenser S1PH Q1L
MS
3~
M1F
C7 : Capacitor M1C
D1, D2 : Diode
DB1 : Diode bridge Q1L : Overload protector
E1, E2, HL1, R1T, R2T, R3T : Thermistor
HN1,S, U, V, W : Connection S1PH : High pressure switch
FU1, FU2, FU3 : Fuse S2, S20, S40,
IPM1 : Intelligent power module S70, S80, S90 : Terminal connector
L : Live SA1 : Surge arrestor BLK : Black
M1C : Compressor motor V1, V2, V3 : Varistor BLU : Blue
M1F : Fan motor X11A : Connector BRN : Brown
MR30, MRCW, X1M : Terminal strip GRN : Green
MRM10, MRM20 : Magnetic relay Y1E : Electronic expansion valve coil GRY : Grey
N : Neutral Y1S : Reversing solenoid valve coil ORG : Orange
N=4, N=5 : Number of passes Z1C, Z2C, Z3C : Ferrite core RED : Red
PAM : Pulse-amplitude modulation ZF : Noise filter WHT : White
PCB : Printed circuit board : Earth YLW : Yellow
PS : Switching power supply : Protective earth PPL : Purple
3D130905A
62 RXM-R
R
XM-R
8 Wiring diagrams
8-1 Wiring Diagrams - Single Phase
RXM50-60R
Field wiring Wiring diagram For the power requirements, refer to the nameplate. 8
Indoor
FU3 IPM1
X1M Z3C 30A DB1 PAM
HL1 MRM10 +
1 L 1 BLK +
2 N 2 WHT HN1 V2 MRM20 +
3 S ZF C7
3 RED U +tv -
N=5 -
L V3 V1
GRN/YLW
MR30 U
FU2 W VU
N U
3.15A
FU1
3.15A D1 D2
MR30_A
MR30_B
Z2C
SA1
BLU
YLW
RED
E1 MRCW PS
N=4
E2
GRN
GRN
3 1 1 7 1 3 1 6 1 6 1 4 1 4 7 Z1C
PCB S50 S2 S80 S20 S90 S40 S70 N=4
X11A
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
WHT
ORG
BRN
BLU
RED
GRY
GRY
BLK
BLK
WHT
YLW
ORG
BLU
RED
BRN
BRN
PPL
PPL
BLU
YLW
RED
4 1
M tv tv tv MS
X12A Y1S R1T R2T R3T P> WV U
Outdoor Y1E Outdoor Discharge
S1PH Q1L
MS
3~
BLK
BLK
Condenser M1F
M1C
C7 : Capacitor
D1, D2 : Diode : Overload protector
Q1L
DB1 : Diode bridge : Thermistor
R1T, R2T, R3T
E1, E2, HL1,
S1PH : High pressure switch
HN1,S, U, V, W : Connection
S2, S20, S40,
FU1, FU2, FU3 : Fuse : Terminal connector
S 50,S70,S80,S90
IPM1 : Intelligent power module : Surge arrestor BLK : Black
SA1
L : Live : Varistor BLU : Blue
V1, V2, V3
M1C : Compressor motor : Connector BRN : Brown
X11A, X12A
M1F : Fan motor GRN : Green
X1M : Terminal strip
MR30, MRCW, GRY : Grey
: Magnetic relay
Y1E : Electronic expansion valve coil
MRM10, MRM20
: Neutral
Y1S : Reversing solenoid valve coil ORG : Orange
N
N=4, N=5 : Number of passes
Z1C, Z2C, Z3C : Ferrite core RED : Red
ZF : Noise filter WHT : White
PAM : Pulse-amplitude modulation
PCB : Printed circuit board : Earth YLW : Yellow
PS : Switching power supply : Protective earth PPL : Purple
3D130906A
RXM71R
MR30 3.15A W V U
Z2C SA1 3.15A
E1 PS
Power supply MRCW Z1C
E2 n=4
BLU
YLW
RED
PCB
GRN
X11A
Outdoor
BLK
BLK
YLW
BLK
BLK
BLK
BLK
WHT
GRY
BLU
BLU
BLU
RED
GRY
WHT
ORG
BRN
BLU
RED
ORG
t t t
C7 : Capacitor W V U
Y1S
D1,D2 : Diode M
P> MS MS
3~
DB1 : Diode bridge Y1E
R1T R2T R3T
Outdoor Discharge S1PH Q1L
IPM1 : Intelligent power module M1F M1C
Condenser
L : Live
M1C (MS 3~) : Compressor motor
M1F (MS) : Fan motor
N : Neutral
PAM : Pulse-amplitude modulation FU1, FU2, FU3 : Fuse GRY : Grey : Protective earth
PCB : Printed circuit board MR30, MRM10, BLK : Black : Earth
PS : Switching power supply MRM20, MRCW : Magnetic relay WHT : White
Q1L : Overload protector R1T, R2T, R3T : Thermistor BRN : Brown
S1PH : High pressure switch S20, S40, S70, S80, RED : Red
SA1 : Surge arrestor S90, X11A, X14A : Connector GRN : Green
X1M : Terminal strip V1, V2, V3 : Varistor YLW : Yellow
Y1E (M) : Electronic expansion valve coil Z1C, Z2C, Z3C : Ferrite core ORG : Orange
Y1S : Reversing solenoid valve coil HL1, HN1, S, BLU : Blue
ZF : Noise filter E1, E2, W, V, U : Connection n=4, n=5 : Number of passes through ferrite core
3D130907A
R
XM-R 63
RXM-R
9 Sound data
9-1 Sound Pressure Spectrum
RXM20R
NR75 NR75
A B A B
dBA 46 dBA 47
Notes
1 Background noise already taken into account.
2 Operating conditions: power source 220-240 V/220 V 50/60 Hz; JIS standard
3 Operating noise varies depending on operation and ambient conditions.
4 The operation noise measuring method is in accordance with JISC9612.
5 Measuring location: anechoic chamber
3D110121A
RXM25R
70 NR75 70 70 NR75 70
65 NR70 65 NR70
60 NR65 60 60 NR65 60
55 NR60 55 NR60
50 NR55 50 50 NR55 50
45 NR50 45 NR50
40 NR45 40 40 NR45 40
35 NR40
35 NR40
30 NR35 30 30 NR35 30
25 NR30 25 NR30
20 NR25 20 20 NR25 20
15 NR0 NR20 15 NR0
NR15 NR20
NR5 NR10 NR5 NR10 NR15
10 10 10 10
63 125 250 500 1000 2000 4000 8000 dBA 63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz] Octave band centre frequency [Hz]
Legend
dBA = A-weighted sound pressure level (A scale according to IEC).
A Scale
Notes
B Fan speed: High
1 Background noise already taken into account.
2 Operating conditions: power source 220-240 V/220 V 50/60 Hz; JIS standard
Location of microphone 3 Operating noise varies depending on operation and ambient conditions.
4 The operation noise measuring method is in accordance with JISC9612.
5 Measuring location: anechoic chamber
A B A B
dBA 46 dBA 47
3D110122A
64 RXM-R
RXM-R
9 Sound data
9-1 Sound Pressure Spectrum
RXM35R
Legend
dBA = A-weighted sound pressure level (A scale according to IEC).
A Scale
Notes
B Fan speed: High 1 Background noise already taken into account.
2 Operating conditions: power source 220-240 V/220 V 50/60 Hz; JIS standard
3 Operating noise varies depending on operation and ambient conditions.
Location of microphone 4 The operation noise measuring method is in accordance with JISC9612.
5 Measuring location: anechoic chamber
A B A B
dBA 49 dBA 49
3D110123A
RXM42R
Cooling mode Heating mode
90 90 90 90
85 NR90 85 NR90
80 NR85 80 80 NR85 80
75 NR80 75 NR80
Sound pressure level [dB]
70 70 70 NR75 70
Sound pressure level [dB]
NR75
65 NR70 65 NR70
60 NR65 60 60 NR65 60
55 NR60 55 NR60
50 NR55 50 50 NR55 50
45 NR50 45 NR50
40 NR45 40 40 NR45 40
35 NR40
35 NR40
30 NR35 30 30 NR35 30
25 NR30
25 NR30
20 20 20 20
15 NR0 NR25 15 NR0 NR25
10 NR5 NR10 NR15 NR20 10 10 NR5 NR10 NR15 NR20 10
63 125 250 500 1000 2000 4000 8000 dBA 63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz] Octave band centre frequency [Hz]
Legend
dBA = A-weighted sound pressure level (A scale according to IEC).
Cooling Total dB Heating Total dB
A Scale
A B A B
B Fan speed: High
Notes
1. Operating conditions: power source 220-240 V/220 V 50/60 Hz; JIS standard
RXM-R 65
R
XM-R
9 Sound data
9-1 Sound Pressure Spectrum
RXM50R
Cooling mode Heating mode
90 90
90 90 85 NR90
85 NR90
9 80 NR85 80 80
75
NR85 80
70 NR75 70 70 NR75 70
65 NR70 65 NR70
60 NR65 60 60 NR65 60
55 NR60 55 NR60
50 NR55 50 50 NR55 50
45 NR50 45 NR50
40 NR45 40 40 NR45 40
35 NR40 35
30 30 NR40
NR35 30 NR35 30
25 NR30 25
20 20 NR30
NR0 NR25 20 20
15 15 NR0 NR25
10 NR5 NR10 NR15 NR20 10 NR5 NR10 NR15 NR20
10 10
63 125 250 500 1000 2000 4000 8000 dBA 63 125 250 500 1000200040008000 dBA
Octave band centre frequency [Hz] Octave band centre frequency [Hz]
Legend
dBA = A-weighted sound pressure level (A scale according to IEC). Cooling Total dB Heating Total dB
A Scale
A B A B
B Fan speed: High
dBA 48 dBA 49
Location of microphone
Notes
1. Operating conditions: power source 220-240 V/220 V 50/60 Hz; JIS standard
2. Background noise already taken into account.
3. Operating noise varies depending on operation and ambient conditions.
4. The operation noise measuring method is in accordance with JISC9612.
5. Measuring location: anechoic chamber
3D131753
RXM60R
Cooling mode Heating mode
90 90 90 90
85 NR90 85 NR90
80 NR85 80 80 NR85 80
75 NR80 75 NR80
70 70
Sound pressure level [dB]
70 70 NR75
Sound pressure level [dB]
NR75
65 65 NR70
NR70 60 60
60 NR65 60 NR65
55 55 NR60
NR60 50 50
50 NR55 50 NR55
45 45 NR50
NR50 40 40
40 NR45 40 NR45
35 35 NR40
30 NR40
30 30 NR35 30
25
NR35 25 NR30
20 NR30
20 20 20
NR0 NR25 15 NR0 NR25
15 NR5 NR10 NR15 NR20
10 NR5 NR10 NR15 NR20 10 10 10
63 125 250 500 1000 2000 4000 8000 dBA 63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz] Octave band centre frequency [Hz]
Legend
Notes
1. Operating conditions: power source 220-240 V/220 V 50/60 Hz; JIS standard
66 R
XM-R
R
XM-R
9 Sound data
9-1 Sound Pressure Spectrum
RXM71R
Cooling mode Heating mode
90 90 90 90
85 NR90 85 NR90
80 NR85 80 80 NR85 80 9
75 NR80 75 NR80
NR75 NR75
65 NR70 65 NR70
60 NR65 60 60 NR65 60
55 NR60 55 NR60
50 NR55 50 50 NR55 50
45 NR50 45 NR50
40 NR45 40 40 NR45 40
35 35 NR40
NR40 30 30
30 NR35 30 NR35
25 25 NR30
NR30 20 20
20 20 NR0 NR25
15 NR0 NR25 15
NR5 NR10 NR15 NR20 10 NR5 NR10 NR15 NR20 10
10 10
63 125 250 500 1000 2000 4000 8000 dBA 63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz] Octave band centre frequency [Hz]
Legend
dBA = A-weighted sound pressure level (A scale according to IEC). Cooling Total dB Heating Total dB
A Scale
A B A B
B Fan speed: High
dBA 47 dBA 48
Location of microphone
Notes
1. Operating conditions: power source 220-240 V/220 V 50/60 Hz; JIS standard
R
XM-R 67
R
XM-R
10 Operation range
10 - 1 Operation Range
ARXM50R
10 RXM42-60R
Cooling Heating
18vCDB 32vCDB 37vCDB
50
20
24vCDB
18
40
15
10
30
Outdoor temperature [°C WB]
Continuous operation
5
Outdoor temperature [°C DB]
20
Continuous operation
10
-5
-10
0
-15
-10
-20 -20vCDB
-21
10 14 20 23 28 30 10 20 30
Notes
1. The ·graph· is based on the following conditions.
Corresponding refrigerant piping length: ·5· m
Level difference: ·0
·m flow rate High
Air
4D132631
68 R
XM-R
R
XM-R
10 Operation range
10 - 1 Operation Range
ARXM25-50R(2)Cooling Heating
RXM20-60R(2)
50
18vCDB 32vCDB
37vCDB
20
18 24vCDB 10
40 15
10 Notes
30 Pull-down operation range
5
Continuous operation
Continuous operation
20
0
Corresponding refrigerant piping length: ·5· m
10 -5
10 14 2023 2830 10 20 30
Indoor temperature [°C DB]
Indoor temperature [°C WB]
Only possible in combination with ·ATXM*N2V1B, FTXM*N2V1B, ATXM*R2V1B, ATXM*R5V1B, FTXM*R2V1B, FTXM*R5V1B·
Cooling Heating
32vCDB
18vCDB
46 37vCDB
40 20 24vCDB
18
15
30
Outdoor temperature [°C DB]
10
Continuous operation
Continuous operation
20
5
10 0
-5
0
-10
-10 -15vCDB
-15
10 20 30
10 14 2023 2830
Indoor temperature [°C WB] Indoor temperature [°C DB]
Only possible in combination with ·ATXM*M2V1B, FTXM*M2V1B, FVXM*FV1B, FCAG*AVEB, FFA*A2VEB9, FBA*A2VEB9, FHA*AVEB9, FDXM*F3V1B9, FNA*A2
VEB9, ADEA*A2VEB, FVXM*A2V1B·
3D119882E
RXM71R
Cooling Heating
18°C DB 37°C DB
50
20
24°C DB
18
46
15
Outdoor temperature [°C WB]
40
10
Outdoor temperature [°C DB]
30
Pull-down operation range
5
Continuous operation
Continuous operation
20
0
10
-5
0
-10
-10 -15°C DB
-15
10 14 20 23 28 30 10 20 30
Notes
1. The graphs is based on the following conditions.
Corresponding refrigerant piping length: 5 m
Level difference: 0m
Air flow rate High
3D120207
R
XM-R 69
Daikin Europe N.V. Naamloze Vennootschap · Zandvoordestraat 300 · 8400 Oostende · Belgium · www.daikin.eu · BE 0412 120 336 · RPR Oostende (Responsible Editor)
EEDEN23 05/2023
The present publication is drawn up by way of information only and does not constitute an offer binding upon
Daikin Europe N.V. / Daikin Central Europe HandelsGmbH. Daikin Europe N.V. / Daikin Central Europe HandelsGmbH
have compiled the content of this publication to the best of their knowledge. No express or implied warranty is
given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and
services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. / Daikin
Central Europe HandelsGmbH explicitly rejects any liability for any direct or indirect damage, in the broadest sense,
arising from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin
Europe N.V.