Climaveneta Technical Documentation

i-FX-W_(1+i)-G05/H_1402_4652_202102_ML

REGULATION (EU) N. 2016/2281 FOR COMFORT


CHILLERS
Ecodesign requirements for cooling products

WATER TO WATER HEAT PUMPS, REVERSIBLE ON HYDRAULIC SIDE

i-FX-W (1+i)-G05/H 1402 - 4652


Cooling Capacity Range 488 - 1636 [kW] - (EN14511 VALUE)
Nominal Cooling Capacity at TdesignC Range 488 - 1636 [kW]
i-FX-W (1+i)-G05

1. REGULATION (EU) N. 2016/2281 FOR COMFORT


CHILLERS
1.1 Scope of the document 3
1.2 REGULATION (UE) N. 2016/2281 description 3
1.3 Description of the data declared by Mitsubishi 3
Electric Hydronics & IT Cooling Systems
2. CLIMAVENETA CONTENTS UNIT
2.1 Table index 4

3. TECHNICAL PARAMETERS
3.1 i-FX-W (1+i)-G05 /CA 5

ELCA_Engine ver. 4.5.1.0 - DB ver. 0.0.0.0 i-FX-W_(1+i)-G05/H_1402_4652_202102_ML


2
i-FX-W (1+i)-G05

1. REGULATION (EU) N. 2016/2281 FOR COMFORT


CHILLERS
1.1 Scope of the document
This document is compliant with the Commission Regulation (EU) N.
2016/2281 regarding “REQUIREMENTS FOR PRODUCT INFORMATION”
(Annex II, Point 5). In particular, it deals with comfort chillers and contains
information required by Table 10 of the above-mentioned regulation, which
is entitled “Information requirements for comfort chillers”.

1.2 REGULATION (UE) N. 2016/2281 description


The COMMISSION REGULATION (EU) N. 2016/2281 of 30 November
2016, implementing Directive 2009/125/EC of the European Parliament and
of the Council, establishes eco-design requirements for the placing on the
market and/or putting into service of: air heating products with a rated
heating capacity which does not exceed 1MW, cooling products and high
temperature process chillers with a rated cooling capacity which do not
exceed 2 MW, and all fan coil units. All these energy-related products are
defined in Article 2 of the Regulation in question.

1.3 Description of the data declared by Mitsubishi Electric Hydronics &


IT Cooling Systems
- Comfort chiller: a cooling product designed with the aim of attaining and
maintaining the desired indoor temperature for the thermal comfort of
human beings, whose evaporator extracts heat from a water-based
cooling system designed to operate at leaving chilled water
temperatures greater than or equal to +2°C.
- Rated cooling capacity (Prated,c): the cooling capacity of a comfort
chiller when providing space cooling at standard rating conditions,
expressed in kW.
- Low temperature application: application where the comfort chiller
delivers its declared capacity for cooling at an indoor heat exchanger
outlet temperature of 7°C.
- Medium temperature application: application where the comfort chiller
delivers its declared capacity for cooling at an indoor heat exchanger
outlet temperature of 18°C.
- Seasonal energy efficiency of the space cooling (ηs,c): ratio between
the space cooling demand pertaining to the designated cooling season,
and the annual energy consumption required to meet this demand,
expressed in %.
- Seasonal Energy Efficiency Ratio (SEER): the overall energy efficiency
ratio of the comfort chiller, representative for the cooling season,
calculated as the reference annual cooling demand divided by the
annual energy consumption for cooling.
- Degradation coefficient for chillers: measure of efficiency loss due to
cycling of the chiller.
- Off mode: a condition in which the chiller is connected to the main
power source and is not providing any function.
- Thermostat off-mode: condition corresponding to the hours with no
cooling load and activated cooling function, whereby the cooling function
is switched on but the chiller is not operational.
- Crankcase heater mode: condition in which a heating device is activated
to avoid the refrigerant migrating to the compressor so as to limit the
refrigerant concentration in oil when the compressor is started.
- Standby mode: condition where the chiller is connected to the mains
power source and depends on energy input from the mains power
source to work as intended. The unit provides only the following
functions, which may persist for an indefinite time: reactivation function,
or reactivation function and only an indication of enabled reactivation
function, and/or information or status display.
- Capacity control: the ability of a chiller to change its cooling capacity by
changing the volumetric flow rate of at least one of the fluids needed to
operate the refrigeration cycle.
- Sound power level (LWA): the A-weighted sound power level, indoors
and/or outdoors, expressed in dB.
- Global warming potential (GWP) of the refrigerant: the 100-year climatic
warming potential of one kilogram of a greenhouse gas relative to one
kilogram of dioxide (CO2).

ELCA_Engine ver. 4.5.1.0 - DB ver. 0.0.0.0 i-FX-W_(1+i)-G05/H_1402_4652_202102_ML


3
i-FX-W (1+i)-G05

2. CLIMAVENETA CONTENTS UNIT


2.1 Table index
WATER TO WATER HEAT PUMPS, REVERSIBLE ON HYDRAULIC SIDE

i-FX-W (1+i)-G05/H 1402 - 4652


Cooling Capacity Range 488 - 1636 [kW]
Nominal Cooling Capacity at TdesignC Range 488 - 1636 [kW]

Units Version Size Pag.


i-FX-W CA 1402 1752 1902 2152 2602 5
(1+i)-G05
3002 3402 3852 4252 4652

ELCA_Engine ver. 4.5.1.0 - DB ver. 0.0.0.0 i-FX-W_(1+i)-G05/H_1402_4652_202102_ML


4
<<< BACK INDEX UNITS
i-FX-W (1+i)-G05

i-FX-W (1+i)-G05 /H /CA /1402


-
Outdoor side heat exchanger of chiller air or water/brine Water/brine
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 487,6
Seasonal energy efficiency of the space cooling ηs,c [%] 316,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 488
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 359
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 231
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 147
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 5,18
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 6,52
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 9,22
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 11,10
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,692
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,093
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 98,0
GWP of the refrigerant [Kg CO2eq] 631
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] -
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] 99
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

ELCA_Engine ver. 4.5.1.0 - DB ver. 0.0.0.0 i-FX-W_(1+i)-G05/H_1402_4652_202102_ML


5
<<< BACK INDEX UNITS
i-FX-W (1+i)-G05

i-FX-W (1+i)-G05 /H /CA /1752


-
Outdoor side heat exchanger of chiller air or water/brine Water/brine
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 609,4
Seasonal energy efficiency of the space cooling ηs,c [%] 314,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 609
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 449
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 289
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 178
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 5,29
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 6,53
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 9,09
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 10,90
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,962
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,105
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 98,0
GWP of the refrigerant [Kg CO2eq] 631
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] -
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] 124
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

ELCA_Engine ver. 4.5.1.0 - DB ver. 0.0.0.0 i-FX-W_(1+i)-G05/H_1402_4652_202102_ML


6
<<< BACK INDEX UNITS
i-FX-W (1+i)-G05

i-FX-W (1+i)-G05 /H /CA /1902


-
Outdoor side heat exchanger of chiller air or water/brine Water/brine
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 660,7
Seasonal energy efficiency of the space cooling ηs,c [%] 313,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 661
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 487
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 313
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 197
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 5,28
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 6,56
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 9,05
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 10,90
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,924
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,175
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 98,0
GWP of the refrigerant [Kg CO2eq] 631
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] -
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] 134
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

ELCA_Engine ver. 4.5.1.0 - DB ver. 0.0.0.0 i-FX-W_(1+i)-G05/H_1402_4652_202102_ML


7
<<< BACK INDEX UNITS
i-FX-W (1+i)-G05

i-FX-W (1+i)-G05 /H /CA /2152


-
Outdoor side heat exchanger of chiller air or water/brine Water/brine
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 751,5
Seasonal energy efficiency of the space cooling ηs,c [%] 317,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 751
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 554
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 356
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 224
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 5,28
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 6,61
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 9,23
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 11,10
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 1,168
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,175
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 100,0
GWP of the refrigerant [Kg CO2eq] 631
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] -
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] 153
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

ELCA_Engine ver. 4.5.1.0 - DB ver. 0.0.0.0 i-FX-W_(1+i)-G05/H_1402_4652_202102_ML


8
<<< BACK INDEX UNITS
i-FX-W (1+i)-G05

i-FX-W (1+i)-G05 /H /CA /2602


-
Outdoor side heat exchanger of chiller air or water/brine Water/brine
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 916,2
Seasonal energy efficiency of the space cooling ηs,c [%] 321,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 916
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 675
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 434
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 275
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 5,29
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 6,52
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 9,44
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 11,30
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 1,165
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,178
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 100,0
GWP of the refrigerant [Kg CO2eq] 631
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] -
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] 186
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

ELCA_Engine ver. 4.5.1.0 - DB ver. 0.0.0.0 i-FX-W_(1+i)-G05/H_1402_4652_202102_ML


9
<<< BACK INDEX UNITS
i-FX-W (1+i)-G05

i-FX-W (1+i)-G05 /H /CA /3002


-
Outdoor side heat exchanger of chiller air or water/brine Water/brine
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 1048,0
Seasonal energy efficiency of the space cooling ηs,c [%] 321,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1048
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 772
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 496
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 315
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 5,32
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 6,71
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 9,28
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 11,20
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 1,431
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,178
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 100,0
GWP of the refrigerant [Kg CO2eq] 631
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] -
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] 213
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

ELCA_Engine ver. 4.5.1.0 - DB ver. 0.0.0.0 i-FX-W_(1+i)-G05/H_1402_4652_202102_ML


10
<<< BACK INDEX UNITS
i-FX-W (1+i)-G05

i-FX-W (1+i)-G05 /H /CA /3402


-
Outdoor side heat exchanger of chiller air or water/brine Water/brine
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 1189,0
Seasonal energy efficiency of the space cooling ηs,c [%] 315,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1189
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 876
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 563
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 356
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 5,37
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 6,66
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 9,04
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 10,80
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 1,730
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,178
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 100,0
GWP of the refrigerant [Kg CO2eq] 631
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] -
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] 241
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

ELCA_Engine ver. 4.5.1.0 - DB ver. 0.0.0.0 i-FX-W_(1+i)-G05/H_1402_4652_202102_ML


11
<<< BACK INDEX UNITS
i-FX-W (1+i)-G05

i-FX-W (1+i)-G05 /H /CA /3852


-
Outdoor side heat exchanger of chiller air or water/brine Water/brine
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 1351,0
Seasonal energy efficiency of the space cooling ηs,c [%] 318,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1351
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 995
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 640
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 404
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 5,41
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 6,71
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 9,17
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 10,80
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 1,895
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,238
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 100,0
GWP of the refrigerant [Kg CO2eq] 631
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] -
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] 274
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

ELCA_Engine ver. 4.5.1.0 - DB ver. 0.0.0.0 i-FX-W_(1+i)-G05/H_1402_4652_202102_ML


12
<<< BACK INDEX UNITS
i-FX-W (1+i)-G05

i-FX-W (1+i)-G05 /H /CA /4252


-
Outdoor side heat exchanger of chiller air or water/brine Water/brine
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 1485,0
Seasonal energy efficiency of the space cooling ηs,c [%] 311,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1485
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1094
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 703
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 404
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 5,33
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 6,46
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 8,87
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 10,80
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 1,749
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,238
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 102,0
GWP of the refrigerant [Kg CO2eq] 631
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] -
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] 302
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

ELCA_Engine ver. 4.5.1.0 - DB ver. 0.0.0.0 i-FX-W_(1+i)-G05/H_1402_4652_202102_ML


13
<<< BACK INDEX UNITS
i-FX-W (1+i)-G05

i-FX-W (1+i)-G05 /H /CA /4652


-
Outdoor side heat exchanger of chiller air or water/brine Water/brine
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 1636,0
Seasonal energy efficiency of the space cooling ηs,c [%] 310,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 1636
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 1205
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 775
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 402
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 5,27
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 6,42
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 9,16
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 10,10
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 2,248
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,238
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 102,0
GWP of the refrigerant [Kg CO2eq] 631
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] -
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] 333
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy

ELCA_Engine ver. 4.5.1.0 - DB ver. 0.0.0.0 i-FX-W_(1+i)-G05/H_1402_4652_202102_ML


14
i-FX-W (1+i)-G05

ENGLISH ITALIANO FRANCAISE DEUTSCH ESPANOL


Outdoor side heat exchanger of Refrigeratore a scambiatore di Échangeur de chaleur côté Wärmetauscher des Kühlers Intercambiador de calor de
chiller calore esterno extérieur du refroidisseur (außen) exterior de la enfriadora
Indoor side heat exchanger chiller Refrigeratore a scambiatore di Échangeur de chaleur côté Wärmetauscher des Kühlers Intercambiador de calor de
calore interno intérieur du refroidisseur (innen) interior de la enfriadora
Type Tipo Type Bauart Tipo
Driver of compressor Tipo di azionamento del Type d'entraînement du Antrieb des Verdichters Accionamiento del compresor
compressore compresseur
Rated cooling capacity Capacità di raffreddamento Puissance frigorifique nominale Nennkühlleistung Potencia nominal de refrigeración
nominale
Seasonal energy efficiency of the Efficienza energetica stagionale Efficacité énergétique saisonnière Raumkühlungs- Eficiencia energética estacional
space cooling del raffreddamento d'ambiente pour le refroidissement des Jahresnutzungsgrad de refrigeración de espacios
locaux
Declared cooling capacity for Capacità di raffreddamento Puissance frigorifique déclarée Angegebene Kühlleistung bei Potencia de refrigeración
part load at given outdoor dichiarata a carico parziale a à charge partielle pour des Teillast und bestimmten declarada para carga parcial a
temperatures Tj temperature esterne date Tj températures extérieures Außentemperaturen Tj las temperaturas exteriores
données Tj dadas Tj
Declared cooling capacity at Capacità di raffreddamento Puissance frigorifique déclarée à Angegebene Kühlleistung bei Potencia de refrigeración
given outdoor temperatures Tj = dichiarata a temperatura esterna la température extérieure Tj = Teillast und einer declarada para carga parcial a la
35°C Tj = 35°C 35°C Außentemperatur Tj = 35°C temperatura exterior Tj = 35°C
Declared cooling capacity at Capacità di raffreddamento Puissance frigorifique déclarée à Angegebene Kühlleistung bei Potencia de refrigeración
given outdoor temperatures Tj = dichiarata a temperatura esterna la température extérieure Tj = Teillast und einer declarada para carga parcial a la
30°C Tj = 30°C 30°C Außentemperatur Tj =30°C temperatura exterior Tj = 30°C
Declared cooling capacity at Capacità di raffreddamento Puissance frigorifique déclarée à Angegebene Kühlleistung bei Potencia de refrigeración
given outdoor temperatures Tj = dichiarata a temperatura esterna la température extérieure Tj = Teillast und einer declarada para carga parcial a la
25°C Tj = 25°C 25°C Außentemperatur Tj =25°C temperatura exterior Tj = 25°C
Declared cooling capacity at Capacità di raffreddamento Puissance frigorifique déclarée à Angegebene Kühlleistung bei Potencia de refrigeración
given outdoor temperatures Tj = dichiarata a temperatura esterna la température extérieure Tj = Teillast und einer declarada para carga parcial a la
20°C Tj = 20°C 20°C Außentemperatur Tj =20°C temperatura exterior Tj = 20°C
Degradation coefficient for Coefficiente di degradazione per i Coefficient de dégradation pour Minderungsfaktor von Kühlern Coeficiente de degradación de
chillers refrigeratori les refroidisseurs las enfriadoras
Declared energy efficiency Indice di efficienza energetica Coefficient d'efficacité Angegebene Leistungszahl Factor de eficiencia energética
ratio or gas utilisation dichiarato o efficienza dell'uso énergétique déclaré ou oder declarado o eficiencia del uso
efficiency/auxiliary energy del gas/fattore di energia rendement de la Gaswirkungsgrad/Hilfsenergiefaktor
de gas o factor de energía
factor for part load at given ausiliaria a carico parziale alle consommation de gaz/indice bei Teillast und bestimmten auxiliar para carga parcial a las
outdoor temperatures Tj temperature esterne date Tj énergétique auxiliaire à charge Außentemperaturen Tj temperaturas exteriores dadas
partielle pour des températures Tj
extérieures données Tj
Declared energy efficiency ratio Indice di efficienza energetica Coefficient d'efficacité Angegebene Leistungszahl bei Factor de eficiencia energética
at given outdoor temperatures Tj dichiarato con temperatura énergétique déclaré à la Teillast und einer declarado a la temperatura
= 35°C esterna Tj = 35°C température extérieure Tj = 35°C Außentemperatur Tj = 35°C exterior Tj = 35°C
Declared energy efficiency ratio Indice di efficienza energetica Coefficient d'efficacité Angegebene Leistungszahl bei Factor de eficiencia energética
at given outdoor temperatures Tj dichiarato con temperatura énergétique déclaré à la Teillast und einer declarado a la temperatura
= 30°C esterna Tj = 30°C température extérieure Tj = 30°C Außentemperatur Tj = 30°C exterior Tj = 30°C
Declared energy efficiency ratio Indice di efficienza energetica Coefficient d'efficacité Angegebene Leistungszahl bei Factor de eficiencia energética
at given outdoor temperatures Tj dichiarato con temperatura énergétique déclaré à la Teillast und einer declarado a la temperatura
= 25°C esterna Tj = 25°C température extérieure Tj = 25°C Außentemperatur Tj = 25°C exterior Tj = 25°C
Declared energy efficiency ratio Indice di efficienza energetica Coefficient d'efficacité Angegebene Leistungszahl bei Factor de eficiencia energética
at given outdoor temperatures Tj dichiarato con temperatura énergétique déclaré à la Teillast und einer declarado a la temperatura
= 20°C esterna Tj = 20°C température extérieure Tj = 20°C Außentemperatur Tj = 20°C exterior Tj = 20°C
Power consumption in modes Consumo di energia in modi Consommation d'énergie dans Stromverbrauch in anderen Consumo de energía en modos
other than "active mode" diversi dal «modo attivo» les modes autres que le mode Betriebsarten als dem „aktiven distintos del modo activo
actif Betrieb“
Off mode Modo «spento» Mode arrêt AUS-Zustand Modo desactivado
Thermostat-off mode Modo «termostato spento» Mode arrêt par thermostat Thermostat-AUS- Zustand Modo desactivado por termostato
Crankcase heater mode Modo «riscaldamento del carter» Mode résistance de carter active Betriebszustand mit Modo de calentador del cárter
Kurbelwannenheizung activado
Standby mode Modo «stand-by» Mode veille Bereitschaftszustand Modo de espera
Other items Altri elementi Autres caractéristiques Sonstige Produktdaten Otros elementos
Capacity control Dispositivo di controllo della Régulation de la puissance Leistungsregelung Control de la potencia
capacità
Sound power level, outdoor Livello di potenza sonora esterno Niveau de puissance acoustique, Schallleistungspegel, außen Nivel de potencia acústica
à l'extérieur (exterior)
GWP of the refrigerant GWP del refrigerante PRP du fluide frigorigène Treibhausgaspotenzial des PCA del refrigerante
Kältemittels
For air-to-water comfort chillers: Per i refrigeratori d'ambiente Pour les refroidisseurs de confort Bei Luft-Wasser- Komfortkühlern: Enfriadoras de confort aire-agua:
air flow rate, outdoor measured aria-acqua: flusso d'aria, misurato air-eau: débit d'air, mesuré à Luftdurchsatz, außen gemessen caudal de aire (exterior)
all'esterno l'extérieur
For water/brine-to-water chillers: Per i refrigeratori Pour les refroidisseurs eau/eau Bei Wasser/Sole- Enfriadoras agua-agua/
Rated brine or water flow rate, acqua/salamoia-acqua: flusso glycolée-eau: débit nominal d'eau Wasser-Kühlern: Wasser- oder salmuera-agua: caudal nominal
outdoor side heat exchanger d'acqua o salamoia nominale, glycolée ou d'eau, Sole- Nenndurchsatz, de salmuera o agua,
scambiatore di calore esterno Wärmetauscher außen intercambiador de calor de
exterior

ELCA_Engine ver. 4.5.1.0 - DB ver. 0.0.0.0 i-FX-W_(1+i)-G05/H_1402_4652_202102_ML


15
i-FX-W (1+i)-G05

ENGLISH ITALIANO FRANCAISE DEUTSCH ESPANOL


Standard rating conditions used: Condizioni nominali standard Conditions de perfomance Norm-Prüfbedingungen: Condiciones estándar utilizadas:
usate: nominales applicables:
Notes: Note: Remarques: Hinweise: Notas:
The parameters are declared for I parametri sono dichiarati per Les paramètres sont déclarés Die Parameter sind für eine Los parámetros se declararán
application at medium l’applicazione a temperatura pour l’application à moyenne Mitteltemperaturanwendung para aplicaciones de media
temperature, except in the case media, tranne per le pompe di température, excepté pour les anzugeben, außer für temperatura, excepto si se trata
of low temperature heat pumps. calore a bassa temperatura. Per pompes à chaleur basse Niedertemperatur-Wärmepumpen. de bombas de calor de baja
For low temperature heat pumps, le pompe di calore a bassa température. Pour les pompes à Für temperatura. En el caso de las
the parameters are declared for temperatura, i parametri sono chaleur basse température, les Niedertemperatur-Wärmepumpen bombas de calor de baja
application at low temperature. dichiarati per l’applicazione a paramètres sont déclarés pour sind die Parameter für eine temperatura, los parámetros se
bassa temperatura. l’application à basse température. Niedertemperaturanwendung declararán para aplicaciones de
anzugeben. baja temperatura.
Unit in standard Unità in configurazione ed Unité en configuration et Gerät mit Standard-Konfiguration Unidad en configuración y
configuration/execution, without esecuzione standard, priva di exécution standard, sans und -Ausführung, ohne ejecución estándar, sin
optional accessories. accessori opzionali. accessoires optionnels. wunschweises Zubehör. accesorios opcionales.

ELCA_Engine ver. 4.5.1.0 - DB ver. 0.0.0.0 i-FX-W_(1+i)-G05/H_1402_4652_202102_ML


16
Tel (+39) 0424 509 500 - Fax (+39) 0424 509 509