A - ATG - PR 2013 0112 GB - Chiller GL Serie - BA - K0 11 2013 - 150dpi
A - ATG - PR 2013 0112 GB - Chiller GL Serie - BA - K0 11 2013 - 150dpi
A - ATG - PR 2013 0112 GB - Chiller GL Serie - BA - K0 11 2013 - 150dpi
Operation Manual
ÉåÖáåÉÉêáåÖ=Ñçê=~=ÄÉííÉê=ïçêäÇ db^=eÉ~í=bñÅÜ~åÖÉêë
Chillers and Heat Pumps
Table of Contents GL Series
Table of Contents
7 Mounting .................................................................................... 21
7.1 Positioning the unit ................................................................................... 21
7.2 Assembling the unit .................................................................................. 22
7.3 Rubber anti-vibration isolators ................................................................. 24
7.4 Spring anti-vibration isolators ................................................................... 27
10 Commissioning ......................................................................... 53
10.1 Requirements ........................................................................................... 53
10.2 Commissioning procedure ....................................................................... 53
11 Operation ................................................................................... 59
11.1 Overview of operator elements ................................................................. 59
11.2 POWER OFF and ON ............................................................................... 59
11.3 Operating controller .................................................................................. 60
11.4 Overview of operator elements ................................................................. 62
11.5 POWER OFF and ON ............................................................................... 63
11.6 Draining water circuit ................................................................................ 70
11.7 What to do in case of alarm and error messages ..................................... 70
15 Appendix .................................................................................... 90
15.1 Technical Requirements for Function Testing or Maintenance
of Chiller/Heat Pump 91
15.2 Commissioning Report ............................................................................. 92
15.3 Measuring Report ..................................................................................... 94
15.4 Generally accepted translation of diagrams, plans and drawings
in order-related documentation 126
15.1 Log Book for Chillers, Heat Pumps and Compressor/Condenser Units . 134
Item number
Serial number
Year of manufacture
Operating weight
Refrigerant
Oil type
Power supply
Fig. 1-1
GEA Chiller
No. of compressors
Operating mode
or
GEA GL Series
Supply voltage
Capacity stage
condensing
Refrigerant
GEA Heat Pumps
version
Design
Series
GL GEA Large
Air cooled
A (outdoor installation)
D Air cooled (indoor installation)
F Air cooled with free-cooling function (outdoor installation)
R without condenser (indoor installation)
W Water cooled (indoor installation)
C Chiller
H Heat pump
2 2 compressors
3 3 compressors
4 4 compressors
- Standard
.SL SL unit - (especially quiet model)
.HE HE unit - high-efficiency version - Eurovent class A
.LT LT-Version: heating at low ambient temperatures, only for heat pumps
NOTICE!
For detailed planning please only use the order related documentation. Detailed
dimensional drawings can be obtained on request from your relevant GEA sales
office. Specifications and technical data are subject to regular updates. The manu-
facturer reserves the right to make necessary changes to information without prior
written notice.
3.1 Series
For detailed technical specifications on individual unit series refer to the Data&Facts
catalogue or your quotation for the unit.
NOTICE!
Use only provided order-related documentation for commissioning, maintenance
and service of the unit. It is not allowed to use general data which may not include
specifications of actually installed individual components and special accessories.
RECYCLING!
This symbol is used to highlight instructions for the proper recycling of packaging
material and assembly groups no longer in use (separated according to recyclable
materials).
WEAR GLOVES!
This symbol points out that you must wear proper gloves.
PERSONAL INJURY!
This section specifies procedures and precautions for preventing personal injury.
ENVIRONMENTAL DAMAGE!
This symbol warns you about damage to the environment and turns
your attention to all existing national environmental protection regulations.
ENVIRONMENTAL DAMAGE!
Do not pollute the environment with liquid products, refrigerants or oils.
Dispose of the latter in accordance with local laws and regulations by avoiding harm
to the environment.Ethylene glycol and propylene glycol are categorised as Water
Hazard Class 1 in accordance with the catalogue of water pollutants (mild water pol-
lutants). This also applies to mixtures with water.
• Please comply with the installation and shipping instructions for GEA units.
• Observe the pre-commissioning check points.
• Always make sure that the GEA unit is accessible only to authorized and trained
technical personnel. If necessary, use appropriate equipment to keep unauthorized
persons away from the unit.
• Have all leaks eliminated by the GEA Service or a specialist refrigeration company
immediately (refer to section 4.10).
• The safety sheet stating the type of refrigerant charged on the given unit must be
firmly secured in the machine room of the unit in a well visible manner (refer to unit
identification plate or operation manual for the unit).
• Ensure that proper trays or similar vessels are mounted below the unit in order to
reliably capture oil and glycol liquids and prevent contact with the environment.
First aid First aid measures directly after or during contact with refrigerants:
– Ensure your own protection against leaking refrigerant.
– Under all circumstances - call a doctor or and/an ambulance.
– Remove clothes contaminated by the refrigerant.
Inhalation Additional measures after inhalation of refrigerants:
– Take the injured person to a well-ventilated location.
– Ensure that the injured person is in a stable lateral position.
– Consumption of food and beverages must be avoided.
– If the injured person collapses or loses consciousness – perform mouth-to-mouth
respiration.
Skin contact Additional measures after skin contact with refrigerants:
– Rinse the affected body parts using lukewarm water for at least 15 min.
Eye contact Additional measures after eye contact with refrigerants:
– Do not rub your eyes.
– Remove contact lenses if you have any.
– Rinse your eyes with much water.
Improper use Any use other than that described above is considered improper. The manufacturer/
supplier is not liable for damage arising from improper use. The user alone bears the
risk.
4.8 Disposal
Main and operating supply materials must be disposed of according to material type in
a safe and environmentally friendly manner - please refer to section 14.2 "Disposal".
5 Technical Description
Directives and regulations Units meet the following directives and regulations:
– Directive on Machinery 2006/42/EC
– Low Voltage Directive 89/336/EEC & 2006/95/EC
– Electromagnetic Compatibility 2004/108/EC
– Pressure Equipment Directive 97/23/EC according to module H1
– Certified Corporate Quality Management System ISO 9001
5.1.1 Components
For installed components on the individual unit series refer to the Data&Facts cata-
logue or your quotation for the unit.
Fig. 1: Display
Alternative display for units with screw compressor and GLFC unit series
5.1.5 GLAC - air cooled chillers designed for outside installation and GLDC - air cooled chillers for inside
installation
Refrigeration circuit The refrigeration system generates a refrigeration output in a thermodynamic cycle by
means of heat removal, this is used to cool a water circuit (indirect cooling).
4
5
1
Fig. 5-1
The compressor (1), condenser (2), expansion device (3) and evaporator (4) are
linked together in a closed thermodynamic system. A refrigerant circulates within this
circuit.
The electrically driven compressor (1) draws in overheated gaseous refrigerant and
compresses it to a high pressure/temperature level.
The gaseous overheated refrigerant is cooled and liquefied by releasing its thermal
energy in the air-cooled condenser (2).
Liquid refrigerant under high pressure is now in front of the expansion valve (3).
Taking into account the pressure and the temperature at the evaporator outlet (4) the
expansion valve (3) sprays liquid refrigerant into the evaporator (4).
The liquid refrigerant vaporises completely in the evaporator (4) and absorbs the heat.
The necessary thermal energy needed for this is taken from the chilled water
system (5) which in turn is cooled.
5.1.7 GLFC - air cooled chillers with a free-cooling function for outside installation
Summer operation:
During summer operation a 3-way valve directs
water for cooling not through an additional air
cooled heat exchanger but directly into the evapo-
rator. In such a way the water-side pressure drop
is reduced to a minimum. Evaporating refrigerant
cools water in the heat exchanger, cooled water is
supplied then to different consumers. Free cooling
function is deactivated and the unit operates as a
chiller - refer to chapter GLAC - air cooled chillers
for outside installation and GLDC - air cooled chill-
ers for inside installation.
Fig. 5-2
Transition time:
During transition seasons in spring and autumn the
unit operates with an additional air-cooled free-
cooling heat exchanger as well as using usual
evaporative cooling. As soon as outdoor air tem-
perature falls 1 °C below the set return tempera-
ture of the chilled water system, the 3-way valve is
activated and a connection with a free-cooling heat
exchanger is enabled. The fans increase their
speed in order to cool water as much as possible
and thus reduce compressor run time and associ-
ated electric power consumption. Now water pass-
es through both heat exchangers. Missing cooling
energy, which is not recovered by free-cooling, is
provided by the one or multiple compressors. Al-
ready during transition seasons significant energy
Fig. 5-3
savings can be achieved.
Winter operation:
Only free-cooling heat exchanger is activated dur-
ing winter season. The temperature difference be-
tween outdoor air and water setpoint is large
enough to operate completely without compressor
activation. The only energy consumers of the unit
are fan motors, that considerably reduce their
speed with falling outdoor temperatures and thus
contribute to further energy conservation.
Fig. 5-4
Refrigeration circuit The refrigeration system generates a refrigeration output in a thermodynamic cycle by
means of heat removal, this is used to cool a water circuit (indirect cooling).
5
1
The compressor (1), condenser (2), expansion valve (3) and evaporator (5) are linked
together in a closed thermodynamic system. A refrigerant circulates within this circuit.
The electrically driven compressor (1) draws in overheated gaseous refrigerant and
compresses it to a high pressure/temperature level.
The gaseous overheated refrigerant is cooled and liquefied by releasing its thermal
energy in the water-cooled (4) condenser (2).
Liquid refrigerant under high pressure is now in front of the expansion valve (3).
Taking into account the pressure and the temperature at the evaporator outlet (5) the
expansion valve (3) sprays liquid refrigerant into the evaporator (5).
The liquid refrigerant vaporises completely in the evaporator (5) and absorbs the heat.
The necessary thermal energy, which this process requires, is removed from the
chilled water circuit (6) resulting in its cooling.
5.1.10 GLWH-BD2 - water cooled heat pumps for inside installation with integrated 4-way valve
Refrigeration circuit The refrigeration system generates a refrigeration output in a thermodynamic cycle by
means of heat removal, this is used to cool a water circuit (indirect cooling).
5
1
The compressor (1), condenser (2), expansion valve (3) and evaporator (5) are linked
together in a closed thermodynamic system. A refrigerant circulates within this circuit.
The electrically driven compressor (1) draws in overheated gaseous refrigerant and
compresses it to a high pressure/temperature level.
The gaseous overheated refrigerant is cooled and liquefied by releasing its thermal
energy in the water-cooled (4) condenser (2).
Liquid refrigerant under high pressure is now in front of the expansion valve (3).
Taking into account the pressure and the temperature at the evaporator outlet (5) the
expansion valve (3) sprays liquid refrigerant into the evaporator (5).
The liquid refrigerant vaporises completely in the evaporator (5) and absorbs the heat.
The necessary thermal energy, which this process requires, is removed from the
chilled water circuit (6) resulting in its cooling.
Heating circuit The GLWH unit series are additionally equipped with a 4-way valve. In such way it is
possible to supply heat additionally to dissipating heat in a chiller mode.
The water-cooled condenser (2) becomes an evaporator and absorbs heat from
medium flow. The evaporator (4) becomes a condenser and transfers heat to the con-
nected water or water/glycol circuit. Thus a chiller turns into a heat pump.
Refrigeration circuit The refrigeration system generates a refrigeration output in a thermodynamic cycle by
means of heat removal, this is used to cool a water circuit (indirect cooling).
4
1
The compressor (1), condenser (2), expansion valve (3) and evaporator (4) are linked
together in a closed thermodynamic system. A refrigerant circulates within this circuit.
The electrically driven compressor (1) draws in overheated gaseous refrigerant and
compresses it to a high pressure/temperature level.
The gaseous overheated refrigerant is cooled and liquefied by releasing its thermal
energy in the condensing water (5) of the water-cooled condenser (2).
Liquid refrigerant under high pressure is now in front of the expansion valve (3).
Taking into account the pressure and the temperature at the evaporator outlet (4) the
expansion valve (3) sprays liquid refrigerant into the evaporator (4).
The liquid refrigerant vaporises completely in the evaporator (4) and absorbs the heat.
The necessary thermal energy, which this process requires, is removed from the
chilled water circuit (6) resulting in its cooling.
Heating circuit The unit series GLWH are supplied with additional two temperature sensors for the
common condenser inlet and outlet. The temperature sensors must be mounted by
others on site and connected according to the wiring diagram.
As soon as the unit changes its operating mode from cooling into heating (or the other
way round) - the setpoints that control and adjust the unit's capacity are changed auto-
matically. In cooling mode it is either a sensor at the inlet or outlet of the evaporator
(depending on controller's configuration) that requires individual capacity stages of the
unit using the microprocessor. In heating mode it is either a temperature sensor at
common condenser inlet or outlet (depending on controller's configuration) that acti-
vates or deactivates individual capacity stages of the unit.
For unit operating limits refer to Data&Facts catalogue of the relevant unit series or
web-based unit selection and layout software Aid@ (www.aida.geagroup.com) for
chillers and heat pumps.
NOTICE!
– Protect all water-conducting components from freezing at ambient temperatures
below 5°C. GEA recommends to use at least 30% ethylene glycol.
– Protect all water-conducting components from freezing at water temperatures
below 5°C. For operational reasons water must be protected from freezing by
adding glycol.
– Maintain the maximum chilled water outlet temperature for safe operation of the
unit immediately after the compressor is started. For maximum chilled water out-
let temperature refer to the Data&Facts catalogue of the relevant unit series or
web-based unit selection and layout software Aid@ (www.aida.geagroup.com)
for chillers and heat pumps.
– Maintain the minimum warm water outlet temperature for safe operation of the
unit immediately after the compressor is started. For minimum warm water outlet
temperature refer to the Data&Facts catalogue of the relevant unit series or web-
based unit selection and layout software Aid@ (www.aida.geagroup.com) for
chillers and heat pumps. (only for heat pumps).
– At low outside-air temperature install the unit in a wind-protected area with wind
velocity below 0.5 m/s. For exact outside-air temperature refer to the Data&Facts
catalogue of the relevant unit series or web-based unit selection and layout soft-
ware Aid@ (www.aida.geagroup.com) for chillers and heat pumps.
– The relative humidity during operation must not exceed 90 %.
6.1 Delivery
Upon receipt of the GEA unit and prior to unloading, inspect the unit for damage and
verify that the shipment is complete (refer to section 3.2 "Packaged content") according
to the freight bill.
It is necessary to take photographs of all visible transit damage.
NOTICE!
Missing parts or claims of shipping damage shall only be reported to the transport
insurance, if the damage has been confirmed by the delivering carrier.
NOTICE!
We recommend to keep the equipment in the original packaging for protection, ease
of handling, shipping and storage.
Only remove the original packaging just before installation.
If the unit is stored for a period of time before installation or commissioning, protect
it from damage through elements, build-up of dust and dirt!
6.2 Transport
PERSONAL INJURY!
In order to prevent injury, damage and ensure safety, use proper lifting gear (crane
equipment) for lifting and handling.
Never use a fork lift truck or pallet truck, as there is a risk of the unit toppling over.
For unit weight - refer to the order-related documentation and the unit identification
plate.
• Only transport the GEA units using the transport lugs or lifting points provided by
the manufacturer. For locating lifting points refer to the order-related dimensional
drawing or strickers on the unit.
• Never attach lifting hooks or similar gear directly to the unit construction - only
proper lifting gear must be used (refer to Fig. 6-1).
• When handling and shipping, do not tilt the unit by more than 15°.
• For your own safety wear gloves and safety footwear when lifting or shipping the
unit.
• Before lifting or shipping the unit, make sure that all mountings are fixed and
secured.
• Only use lifting gear with sufficient load-bearing capacity.
• Never use damaged lifting equipment.
• Ropes/chains must not be knotted and/or be exposed to sharp edges.
• Only use ropes/chains of the same length.
• Only use the designated lifting gear (refer to Fig. 6-1) (provided by others).
• Move the unit carefully without jerky movements.
• Always set the unit down gently, without bumping it.
• If necessary, use a specialist company to transport the unit.
LIFTING USE N°4 LIFTING ROPES WITH EQUAL LENGHT ONLY (min.3000)
c1 C2
Fig. 6-1: Example of unit shipment procedure - air cooled chiller for outdoor installation For exact positioning refer to the order-
related dimensional drawing.
NOTICE!
Use only supplied documentation and enclosed detailed dimensional drawings when
transporting the unit.
6.3 Storage
Allowable storage conditions / allowable air condition for non-installed units
Air temperature: -20 °C to +46 °C
Air humidity: up to 85 % (relative humidity with no condensation)
7 Mounting
NOTE ON UNIT ASSEMBLY AND INSTALLATION!
Here you will find information on how to assemble and install the unit.
Placement, installation and assembly must only be carried out by qualified licensed
staff or other individuals with proper professional training and experience in the rel-
evant accident prevention regulations, as well as other generally recognized safety
and occupational health codes.
NOTICE ON MOVING THE UNIT!
If the GEA units have been moved from one plant/location to another, repeated com-
missioning is required, refer to the description in chapter "Commissioning".
NOTICE!
Use only supplied order related documentation and enclosed detailed dimensional
drawings when transporting the unit.
The unit must be installed at a location that fulfils the following requirements:
– Ensure that the site is level and that it can support the weight of the equipment, so
that no vibrations or operating noise occur when the unit is operating.
– The unit should be installed in such a way that it is only accessible to trained and
authorized technical personnel. If necessary, use appropriate equipment to keep
unauthorized persons away from the unit.
– Sufficient clearance around the unit to carry out maintenance or repair work must
be ensured. For required clearances refer to the Data&Facts catalogue for your unit
or order-related dimensional drawing.
– If two or more units are installed next to each other, the relevant clearances must
be kept for each unit. (see Fig. 7-1) Overlapping of clearances is not allowed!
– The area where the unit is installed must have sufficient ventilation.
– Make sure that possibly leaking media do not damage the installation site or the
environment.
– Choose the installation location so that operating noise does not cause a distur-
bance.
– Check if requirements for the installation site
defined by EN 378-3 are fulfilled (refrigerating
systems and heat pumps - safety and environ-
mental requirements Part 3: installation site and
personal protection). These requirements es-
pecially apply to units for indoor installation.
– There must be sufficient clearance around the
unit to carry out maintenance or repair work.
A B
R2 R1 R2 R1
Clearances Clearances Clearances
Fig. 7-1
Further notices on air cooled units GLAC, GLAH, GLFC and GLCU series:
Clearances for air supply!
R2 – Unit must freely discharge air to top. Air short-
circuiting must be impossible!
– The necessary clearances near and over the
unit may exceed the depicted maintenance
R3 R4 clearance by many times.
R1
Fig. 7-2: Clearances
R2 R1
Clearances Clearances
Fig. 7-3
• The unit must be fixed in position and secured according to the order-related
dimensional drawing using anti-vibration isolators (also see Fig. 7-4 and following
pages) or other suitable gear at each of the fixing points W1 to Wn.
• Connect and secure the anti-vibration isolators with the foundation/frame
construction.
R2
W1 W3
N° 4 HOLES M12
R3 R4
W2 W4
R1
BOLT
BASEMENT BASEMENT
LITTLE PLANE WASHER
45
66
NUT
BASEMENT
OF NUT
OH
E
NUT
C
B
OG
D
B
Fig. 7-5: Mounting rubber anti-vibration isolators
Tab. 7-1
Type A B C D E ØF ØG ØH
AA100N 60 80 67 6.5 60 25 6.5 M12
AA200N 75 108 90 9.0 60 40 8.5 M12
AA300N 81 135 110 12.5 60 60 10.5 M14
AA400N 95 155 125 15.0 60 65 12.5 M14
AA1000N 145 200 162 19 60 100 16 M20
AA1500N 155 220 182 19 100 80 17 M20
Type A B C D E F G H I
AA600N 175 100 77 70 14 140 15 M16 30
AA800N 180 120 92 75 15 150 16 M18 35
Tab. 9- Size in [mm]
45
66
ØA
75 Fz
Li
f
DH L Ø C
50
F
A
140
f [mm] = F/k
50
12 116 12
Fig. 7-8
8 Medium Connections
Medium connections must only be carried out by qualified licensed staff or other indi-
viduals with proper professional training and experience in the relevant accident pre-
vention regulations, as well as other generally recognized safety and occupational
health codes (also refer to section 4.10 „Personnel selection and qualification“).
8.1 Requirements
Keep in mind:
• The entire chilled water system must be designed and implemented in accordance
with the current standards and guidelines.
Components • Hydraulic circuit components supplied as standard with the unit, e.g. expansion
tanks, are dimensioned primarily for the unit and not for on-site hydraulic circuits
with arbitrary ratings. That is why - check which parts are still necessary for proper
and regulation conform arrangement of the entire hydraulic system.
8.1.1 Glycols
PERSONAL INJURY!
Glycols and other antifreeze agents are harmful for humans and animals,
if swallowed. Contact a doctor immediately if ingested by mistake.
ENVIRONMENTAL DAMAGE!
Ethylene glycol and propylene glycol are in Water Hazard Class 1 (slightly water
endangering) of the catalogue of water-endangering substances. This also applies
to mixtures with water.
• Use only ethylene or propylene glycols that are suitable for closed chilled water
systems and used materials. Observe the manufacturer's information regarding
safe handling of glycols as well as information on their application and disposal.
• There are considerable differences between water and water-glycol mixtures in
terms of their thermodynamic and physical properties. This affects the performance
values of the unit and all components and, consequently, the design of the entire
hydraulic system.
• If glycol is mixed with the medium, the result is a lower specific heat capacity, higher
viscosity and heat transfer and, consequently,
– an increased flow rate,
– increased pressure drops,
– an increased power and current consumption of the pump
– a lower cooling/heating capacity
• A water-glycol mixture does not have a burst effect starting from frost resistance of
-20 °C, as slush ice forms when the mixture is cooled below the freezing point.
• Do not use Teflon seals if using water-glycol mixtures.
• Charge the system with a prepared water-glycol mixture.
• After having filled the system, check the glycol concentration with a suitable and
approved measuring instrument.
• When designing the system, remember that thermal expansion of a water/glycol
mixture is far more larger than water.
• Use only one sort of glycol, do not mix different types.
• Maximum glycol concentration must not exceed 50 %.
Effects in case of
Description Icon Values
difference
• Flush the piping system by others and draw up a cleaning report. Enclose the
cleaning report to Appendix I „Technical Requirements for Function Testing or
Chiller/Heat Pump Maintenance".
• Connect the pipe system by others to the water inlet and outlet.
• For exact positions of the water inlet and outlet refer to the order-related
documentation and compare these positions with data on the unit stickers.
• For terminological overview and better understanding refer to Chapter 15.4
"Generally accepted translation of diagrams, plans and drawings in order-related
documentation" on page 126
• Contact your GEA sales office in case of queries or unclear points.
NOTICE!
For detailed planning please only use the order related documentation. Detailed
dimensional drawings can be obtained on request from your relevant GEA sales
office. Specifications and technical data are subject to regular updates. The manu-
facturer reserves the right to make necessary changes to information without prior
written notice.
8.2.2 Check and adjust inlet pressure in expansion tank (for units with installed hydraulic or pump module
with expansion tank)
To find out if an expansion tank is included in the packaged content, refer to the
hydraulic circuit diagram in the supplied order-related documentation, Data&Facts cat-
alogue or unit quotation text.
When charging the unit with water or a water-glycol mixture, the initial pressure in ex-
pansion tank of hydraulic or pump module must be checked and adjusted. Only cor-
rectly adjusted expansion tank can can perform the following tasks:
– Provision of water receiver
– Intake of temperature conditioned volume increase of unit water
Besides, the system pressure has to be measured at the unit and adjusted in order to
ensure correct operation of the expansion tank.
[ m ] + 0, 3
Inlet pressure (estimated): Pv = H
-------------
10, 2
Pv : Initial pressure [bar], measured at pressure connection of expansion tank. Minimum setting 0.5 bar
H : Height of water column over expansion tank.
PAmin : Minimum plant filling pressure [bar], measured at unit
PAmax: Maximum plant filling pressure, measured at unit
Psv : Safety valve pressure at opening
NOTICE!
– For adjusting the inlet pressure the hydraulic circuit must be completely drained.
– Only dry nitrogen is allowed to adjust the calculated inlet pressure.
– The minimum inlet pressure of the expansion tank may not exceed 0.5 bar.
– The maximum inlet pressure of the expansion tank must amount to a minimum of
0.3 bar below the opening pressure of the safety valve.
D. 1
2,5
Initial pressure of expansion tank Pv [bar]
1,5
0,5
0
0 5 10 15 20 25
NOTICE!
Ensure constant water flow rate in the evaporator during unit operation when the
remote ON/OFF is closed. The volume flow rate must correspond to the unit layout
parameters.
If 3-way valves are fitted in the (primary) chilled water circuit, ensure that volume flow
is provided in the water cooled heat exchanger regardless of valve position.
NOTICE!
Glycol may be used; however the concentration must not exceed 50% of the content
of the entire system.
A higher quantity can cause operating faults.
8.2.5 Single circuit buffer tank with one pump for the entire system
GEA unit
Purpose: With a single circuit buffer tank, the buffer tank serves primarily to increase the volume
in the hydraulic system in order to guarantee the compressor's minimum runtime and
to prevent the unit from being repeatedly switched on and off unnecessarily.
Application: With small to medium-sized air-conditioning systems, a single circuit buffer tank sys-
tem is used, wherever possible, with identical consumers requiring the same volume
flow and identical water temperatures.
Hydraulics: The water flows at the required capacity reduction from the buffer tank via the water
pump into the unit. The water is cooled/heated. The chilled/warm water now flows via
the consumer(s) and is heated/cooled again. The 3-way valve is fully open in position
A - AB. The bypass line B is closed. If the load reduction of the consumers drops, the
bypass line B is opened. This ensures a constant water/volume flow across the unit,
regardless of the load reduction. The unit requires a constant water/volume flow for
trouble-free operation. Therefore, pumps that are speed-regulated during operation
must not be used. If the bypass line B is fully open due to a missing load reduction,
water in consumers stops circulating. The water temperature approaches the setpoint
of the unit and the compressor switches off gradually. The water pump continuously
remains in operation in order to record the current water temperatures in the system.
If the load reduction increases again, the unit switches on the individual compressors
again depending on how far the temperature deviates from the setpoint.
Control: The external enabling of the unit should, for example, be switched by a timer and/or
the outside air temperature. Switching the external enabling via the water temperature
or the position of the 3-way valve is not permitted, as this would prevent the unit from
automatically regulating the capacity to optimise energy consumption. This would
cause an undesirable cycle operation. The compressor's capacity is controlled
depending on the temperature difference (setpoint and actual value) from the unit.
Depending on the unit configuration, the water pump control function can be withdrawn
from the unit. The consumers and the 3-way valve are controlled by others.
Hydraulic or pump Depending on unit configuration and the selected accessories, the unit can also be
modules: supplied with one or two water pumps, a buffer tank and other hydraulic components
(see the available accessories).
8.2.6 Dual circuit buffer tank with multiple pumps for the entire system
GEA unit
The hydraulic integration of the dual circuit buffer tank as illustrated above can be used for both chilled and warm water circuits. With the warm
water circuit, however, it must be noted that the pump for the primary circuit takes the supply from the buffer tank from below, where the chilled
water collects. The water is conveyed to the unit by the primary pump. The supply to the pump for the secondary circuit must be taken from the
buffer tank from above, as the warmest water can be taken from here. The secondary pump conveys the water to the consumers.
Purpose: In the case of a dual circuit buffer tank, the buffer tank fulfils two main tasks. First, the
buffer tank increases the volume. A generously dimensioned buffer tank not only guar-
antees the compressor's minimum running time, it also achieves proper thermal layer-
ing within the buffer tank.
The second task is to separate the water volume flows on the primary and secondary
sides. This enables the most diverse of consumers to be individually supplied and reg-
ulated in the secondary side.
Application: A dual circuit buffer tank is used mainly in medium to large air-conditioning systems
containing a number of different consumers. The required water volume flow of the
individual consumers can vary. The consumer can be supplied by various, speed-reg-
ulated secondary pumps.
Chilled water operation: The water flows at the required capacity reduction out of the buffer tank from below
and into the unit via the water pump in the primary circuit. The water is cooled and
returned to the buffer tank from below. The chilled water in the secondary circuit is
taken from the buffer tank from below and fed to the consumers via additional second-
ary pumps. The heated water flows back to the buffer tank from above.
Warm water operation: The water flows at the required capacity reduction out of the buffer tank from below
and into the unit via the water pump in the primary circuit. The water is heated and
returned to the buffer tank from above. The warm water in the secondary circuit is
taken from the buffer tank from above and fed to the consumers via additional second-
ary pumps. The cooled water flows back to the buffer tank from below.
A constant water volume flow across the unit must be ensured in the primary circuit.
The water volume flow on the secondary side, i.e. at the consumers, can vary due to
hydraulic separation, thus enabling the use of speed-regulated pumps. With a dual-cir-
cuit buffer tank, individual consumer circuits can also be switched off and on depending
on demand. The transported volume of the primary pumps must be greater than the
total transported volume on the secondary side. This ensures that the return flow tem-
peratures of the secondary circuit do not influence the inlet temperatures of the sec-
ondary circuit.
If the water temperature in the buffer tank approaches the setpoint, the compressors
are switched off gradually via the unit control system. The water pump on the primary
side continuously remains in operation in order to record the current water tempera-
tures in the system. If the load reduction increases again, the unit switches on the indi-
vidual compressors again depending on how far the temperature deviates from the
setpoint.
Control: The external enabling of the unit should, for example, be switched by a timer and/or
the outside air temperature. Switching the external enabling via the water temperature
in the buffer tank is not permitted, as this would prevent the unit from automatically reg-
ulating the capacity to optimise energy consumption. This would cause an undesirable
cycle operation. The compressor's capacity is controlled depending on the tempera-
ture difference (setpoint and actual value) from the unit. Depending on the unit config-
uration, the water pump control function can be withdrawn from the unit. The
consumers and the secondary pumps are controlled by others.
Hydraulic or pump Depending on unit configuration and the selected accessories, the unit can also be
modules: supplied with one or two water pumps, a buffer tank and other hydraulic components
(see the available accessories).
8.3 Connecting cooling water circuit (only GLWC and GLWH units)
For connecting cooling water circuit the points specified in Chapter 8.2 also apply:
– Connecting water circuit (chilled and warm water)
– Description of pipe connections
– Check and adjust nominal inlet pressure in expansion tank
– Charging water circuit
The following two hydraulic circuits are presented as examples for conceptual knowledge and do not substitute proper
planning and layout of the entire system.
Fig. 8-3: Heat rejection circuit with cooling water pump with speed control and/or speed control of the heat rejection unit
Fig. 8-4: Heat rejection circuit with a 3-way valve and/or fan speed control of the heat rejection unit
Freeze protection The GEA chiller and heat pumps of the GLWC and GLWH series are designed for
indoor installation. Therefore protection of the chilled water circuit from frost at chilled
water temperatures above 5 °C is usually not required. It is assumed that chilled water
lines are run frost-safe inside a building. If this is not the case use the antifreeze agent.
In most common cases the cool water circuit of the heat rejection unit has to be frost
protected, because the latter is usually installed outdoor and is exposed to weather
effects. As antifreeze agent GEA recommends to use ethylene glycol.
Dimensioning Dimension the GEA heat rejection unit in such a way that the cooling water tempera-
ture within the operating limits remains as low as possible. The lower the cooling water
temperature, the higher the achieved refrigeration capacity and the lower the energy
consumption of the unit.
Design the cooling water circuit between inlet and outlet lines of the condenser and the
heat rejection unit for a temperature difference of 5 K.
Minimum cooling water outlet To ensure safe operation of the unit, operator must maintain minimum cooling water
temperature outlet temperature. For minimum cooling water outlet temperature refer to Data&Facts
catalogue of the relevant unit series, quotations for the unit or web-based unit selection
and layout software Aid@ (www.aida.geagroup.com) for chillers and heat pumps. This
situation is not always the case because of cold weather. Therefore there are several
technical possibilities to ensure the minimum cooling water outlet temperature.
Possibility 1: – Option 1 enables control the fan speed depending on the cooling water outlet tem-
perature. For all circumstances GEA recommends to control the fan speed in order
to ensure continuous operation of the unit under constant conditions.
Possibility 2: – Option 2 should be implemented if, despite the speed control of fan motors resulting
from e.g. a year-round unit operation, the minimum cooling water temperature can
not be ensured. In this case the operator can use the cooling water pump if the limits
for minimum and maximum water volume in heat exchanger are adhered to (refer
to Fig. 8-3 on page 36). The cooling water pump is regulated by the cooling water
outlet temperature.
Possibility 3: – Option 3 can also be used in order to provide for the minimum cool water outlet tem-
perature of the unit. In this case a 3-way valve is installed in cooling water inlet addi-
tionally to the fan speed control to provide valve regulation depending on the
cooling water outlet temperature (refer to Fig. 8-4 on page 37).
Observe the unit operating limits when switching between heating and cooling mode
of a heat pump.
8.4 Connecting refrigeration circuit to an external condenser (by others, only GLRC)
DANGER DUE TO LOW TEMPERATURES!
Contact with a liquid refrigerant can result in skin burns or injury to other organs.
Exercise due caution and attention when carrying out jobs and avoid contact with a
refrigerant.
Condensers
Set the condensing temperature for the chiller. Consider the operating limits of the unit.
Refer to section 5.4. for the corresponding operating limits.
Large temperature- The larger difference between condensing temperature and ambient temperature in
difference... the layout stage, the smaller condenser can be selected. Disadvantages of a smaller-
dimensioned condenser are increased noise levels as a result of high air velocity and/
or increased energy consumption because of higher condensing temperature together
with reduced cooling capacity.
Small temperature The smaller difference between condensing temperature and ambient temperature in
difference... the layout stage, the larger condenser should be dimensioned. Through a large-dimen-
sioned condenser the condensing temperature can be maintained low, which
enhances capacity and energy efficiency. The disadvantage is about larger refrigerant
charge volume for the designed condenser and increased installation space require-
ments.
Depending on the region, practical values for temperature difference between con-
densing temperature and ambient temperature in the layout stage amount to 10 to
15 K, i.e. condensing temperature exceeds the layout parameters of ambient temper-
ature by 10 to 15 Kelvin.
Fan regulation and control Under all circumstances the condenser must be selected at least with the correspond-
ing fan regulation or optimally with a fan speed control in order to ensure constant con-
densing pressure throughout the year. Significant fluctuations in condensing pressure
should be avoided. In any case, the minimum condensing pressure after compressor
start must be ensured. Maximum allowed condensing temperature must not be
exceeded.
single circuit or dual circuit To find out if the unit is equipped with one or two refrigeration circuits, refer to the unit
description in the Data&Facts catalogue, unit quotation text or order-related dimen-
sional drawing.
– For units with one refrigeration circuit select a single-circuit condenser.
– For units with two refrigeration circuits select a double-circuit condenser.
Using a single-circuit condenser for units with two refrigeration circuits is not allowed
because of different oil and refrigerant flow.
Subcooler circuit Select a condenser with an integrated subcooler circuit. Minimum subcooling must
amount to at least 3 K, because only under these conditions the expansion valve
receives a bubble-free liquid in case of 10 m rising liquid line. If the subcooling is
smaller or the height difference is greater, the expansion valve can be damaged and
the unit must operate with a reduced output anyway.
Refer to the relevant documentation provided by the manufacturer for further details on
layout and installation of air cooled condensers.
Refrigerant lines
Only copper refrigerant lines meeting DIN EN12735-1 standards must be used.
The relevant requirements especially apply to:
– Quality of internal surfaces
– Sealed pipe ends
– Pipe labelling
– Testing
– Pressure resistance
Oil traps
With long and winding pipe runs and often low load reduction combined with short com-
pressor running times it is reasonable to install an oil separator in the field-provided dis-
charge line. Consider the manufacturer's instructions regarding the layout of an oil
separator and the relevant manual for the installation.
Refrigerant receiver
Installing a refrigerant receiver is not mandatory. With long pipe runs and year-round
operation of the unit it is, however, recommended to install a refrigerant receiver. In
case of a year-round operation, ensure that a minimum condensing temperature is
maintained. If necessary, winter start regulation must be installed to maintain a mini-
mum condensing temperature. If a receiver is not installed, the refrigerant must be
selected and charged with due care. When charging the unit with refrigerant at low
ambient temperature, ensure that the system is not overfilled and the unit can be trou-
ble-free operated at high ambient temperature as well.Consider the manufacturer's
instructions on layout of a refrigerant receiver and installation manual for mounting a
receiver.
Example 1
GLRC chiller and condenser at the same vertical level with horizontal pipe routing.
GLRC chiller
Liquid line
Circuit 2
Fig. 8-6: GLRC chiller and condenser at the same vertical level
If necessary, a liquid-line solenoid valve can be optionally ordered. (.R01) The solenoid valve
can be regulated by a dry contact using a GLRC switch box.
Example 2
GLRC chiller above the condenser at different vertical levels.
GLRC chiller
Discharge line
1 % slope (1 cm/m)
Circuit 2
Condensers
Discharge line
1 % slope (1 cm/m)
Liquid line
If necessary, a liquid-line solenoid valve can be optionally ordered. (.R01) The solenoid valve
can be regulated by a dry contact using a GLRC switch box.
Example 3
GLRC chiller below the condenser at different vertical levels.
Condensers
Discharge line
1 % slope (1 cm/m)
Discharge line
1 % slope (1 cm/m)
Liquid line
Circuit 2
If necessary, a liquid-line solenoid valve can be optionally ordered. (.R01) The solenoid valve
can be regulated by a dry contact using a GLRC switch box.
Top oil trap is mandatory! 1 x 90° bend, 2 x 45° bend
Bottom oil trap is mandatory! 2 x 90° bend, 2 x 45° bend
Top oil trap is mandatory! 1 x 90° bend, 2 x 45° bend
NOTES!
– The maximum equivalent pipe length must not exceed 50 m.
– The maximum vertical difference between the GLRC chiller and condenser must
not exceed 10 m.
NOTICE!
To find out if the unit is equipped with one or two refrigeration circuits, refer to the unit
description in the Data&Facts catalogue, unit quotation text or order-related dimen-
sional drawing.
Two refrigeration circuits must be performed separately. Uniting these refrigeration
circuits is not allowed.
Dimensions of pipe connections on the unit are not decisive for the refrigerant lines
to be routed. For dimensioning of piping refer to Chapter 8.4.1.
• Pipes should always be routed with a slight slope to the flow direction.
9 Thus, the refrigerant oil return to the compressor is facilitated. The refrigerant flows
in gaseous state under high pressure and temperature to the condenser. From the
condenser liquid refrigerant flow under high pressure back to the liquid line
connection of the unit.
• Consider temperature-related changes in length!
Cutting To cut pipes use a pipe cutter, apply slow cutting method to avoid copper pipe defor-
mation.
Deburring Cut surfaces must be deburred. Ensure that copper chips do not penetrate into the
pipe.
Avoid oxidation during • Connect a pressure reducing valve at the nitrogen bottle.
brazing • Mount a flow meter on the nitrogen bottle.
• Nitrogen should be directed in the refrigerant pipe to be brazed using a copper pipe.
• Seal the intermediate space between the nitrogen and refrigerant pipe to prevent
nitrogen leakage.
9 While nitrogen is flowing through refrigerant lines, the opposite pipe end must
remain open.
• Use the pressure reducing valve to set the value below 0.05 m³/h or 0.2 bar for the
nitrogen flow.
• After brazing/soldering maintain the nitrogen supply until the refrigerant pipe has
cooled down to a manual-contact temperature.
• After brazing/soldering completely remove the remaining flux.
Drying systems
NOTICE!
When replacing components within the refrigeration circuit, the drier must
always be replaced too!
At the same time the drier must always be replaced last. The new drier is vacuum-
packed. After opening the vacuum packing, commence with brazing as soon as pos-
sible. Evacuation must be performed within 2 hours.
The drier must also be replaced, if the entire refrigerant escaped because of a leak.
Insulation
Insulation for the liquid line is not mandatory. Proper thermal insulation for the dis-
charge line must be provided, in order to prevent scalding risk posed by hot refrigera-
tion pipework. Moreover, fire protection regulations must be observed. If the thermal
insulation is subjected to direct sunlight, proper materials must be used in this case.
NOTICE!
Refer to DIN EN 378-2 for further instructions on proper running of refrigerant lines.
a pressure-reducing valve on the cylinder valve of the unit. The control gauge on the
pressure-reducing valve must be set to the maximum test pressure of the system.
• Increase pressure in the system in steps, first to 0.1 MPa (1 bar) overpressure and
then to around 0.5 MPa (5 bar) overpressure.
• All pipe connections must be leak tested using foaming Leak Detection Spray.
• If no leaks are detected at 0.5 MPa (5 bar) overpressure, pressure is increased to
the maximum allowed test pressure.
• Perform the pressure test using the maximum allowed test pressure for at least two
hours.
• After that overpressure in the system can be reduced.
8.4.5 Evacuation
Reasons for evacuation Before charging the system with a refrigerant, the refrigeration circuit must be evacu-
ated using a vacuum pump in order to remove air and humidity.
Air in the refrigeration circuit has the following effects:
– Increase in energy consumption of compressors
– Reduction in cooling capacity
– Increase of discharge temperature
– Poor heat transfer in the condenser.
High pressure failures can be the consequence already at relatively low ambient tem-
peratures.
Humidity in the refrigeration circuit has the following effects:
– Internal ice formation in the expansion valve and capillary ducts.
– Origination of acid in connection with refrigeration oil
– Copper cladding
– Chemical disintegration of refrigerant.
Procedure for evacuation Reducing pressure in the unit components to values below the water vapour pressure
leads to evaporation of water. The higher the ambient temperature, the faster and more
efficiently humidity can be removed thanks to a higher vapour pressure. Because of
this reason, it is not always possible to sufficiently dry the refrigeration circuit at low
ambient temperature.
• Connect the service manometer assembly to the service ports. Compare the order-
related refrigeration circuit diagrams. For evacuation - use the vacuum pump
(0.0003 bar) fitted with a high-grade pressure gauge a with 0 to 150 mbar abs scale
range, to reach a pressure below water vapour pressure at the current ambient
temperature.
Tab. 8-2
At ambient temperature of 15 °C water begins to evaporate at a pressure of 0.0017 MPa (0.017 bar).
2
0,012 Humid and leak-free
at Ta = +10 °C
0,01
0,008
0,006
0,004
3
0,002
Dry and leak-free
0
0 5 10 15 20 25 30
Time [h]
8.4.6 Charging
DANGER OF LOW TEMPERATURE AND HIGH PRESSURE!
When charging a refrigeration system with a refrigerant, there is a risk of injury from
contacting liquid refrigerant or fluids/gases escaping at high pressure. Contact with
a liquid refrigerant can result in skin burns or injury to other organs.Exercise due cau-
tion and attention when carrying out jobs on the unit and avoid contact with the refrig-
erant.
R-410A The system is certified to be operated with a R-410A refrigerant. R-410A is almost an
azeotropic mixture, consisting two individual refrigerants. As this mixture reaches its
defined composition only in the liquid state, it is only allowed to charge a liquid R-
410A refrigerant.
• Use the service port of the liquid line to charge liquid refrigerant in each refrigeration
circuit of the unit. For refrigerant volume for charging or its approximate calculation
refer to the Data&Facts catalogue of the relevant unit series.To avoid overcharging,
first charge around 80% of the calculated volume. Use the liquid refrigerant to fill
into each liquid line of the unit refrigeration circuit.
• After breaking the vacuum with a liquid refrigerant all shut off valves of the unit must
be opened.
During the function test and for topping up the refrigerant, observe the liquid flow
through the liquid line sight glass to receive an overall picture.
• Check for bubble-free flow in the sight glass!
9 Electrical Connection
Electrical connections must only be carried out by qualified licensed staff or other
individuals with proper professional training and experience in the relevant accident
prevention regulations, as well as other generally recognized safety and occupa-
tional health codes.
Ensure and observe protective measures!
When installing and connecting the unit, observe all protective measures for low-volt-
age systems according to the EU Directive as well as regulations and codes of the
local utility provider.
Ensure potential equalization and the earthing of the unit with all connected compo-
nents.
NOTICE!
The cabling must be carried out according to the enclosed unit-specific wiring dia-
grams.
Only separate mains power cable may be used. Never connect other units to this
mains power cable.
9.1 Requirements
Before you start setting up the unit’s electrical connections, check the following:
– The properties of the mains power supply must comply with EN 60204-1 regulations
and the power requirements of the unit.
– Voltage tolerance of mains power supply must not exceed
tolerances ± 10% with a maximum phase difference of 3%. Do not operate the
motors, if the voltage difference between the phases exceeds 3%, as this will inval-
idate the warranty. To check, use the following formula (see example).
max. voltage imbalance from average value
Voltage imbalance [%] Δ U max = ------------------------------------------------------------------------------------------------------- × 100
average voltage U m
NOTICE!
When connecting the supply voltage, make sure you observe
the clockwise rotation direction! If the rotation direction is wrong, change the
phases at the main power supply of the unit. Change the phase sequence of the
power supply line by others – never change the wiring in the unit switch box.
EXAMPLE
Calculate and determine specific in- Voltage between ➔ L1/L2 = 409 V; L2/L3 = 398 V; L1/L3 = 396 V
put data and measurements before- phases
hand.
1 Q S1
L1 L2 L3 N PE
400V / 3 / 50Hz
1 Q S1
L1 L2 L3 PE
400 V / 3 / 50 Hz
Contact 230V/50Hz/2A
Remote On/Off* Flow
switch Relay by others
By others
Relay Common
fault signal
Pump control
Operation on/off
Unit
As soon as the external control (contact E-F) of the unit closes, the contacts P1-P2
close (pump control contact) and the pump (by others) is activated. The heat
exchanger(s) is(are) circulated with water and the compressor(s) is(are) activated
NOTICE!
Even if the remote ON/OFF contact is open, failures in the frost protection function
can occur, if the temperature for frost protection sensor falls below the set limit for
frost protection as a result of very low ambient temperature.
10 Commissioning
This information applies to initial commissioning of the GEA units as well as re-com-
missioning after an extended shut-down period.
All commissioning work must only be entrusted to qualified licensed staff or other
individuals with proper professional training and experience in the relevant regula-
tions and codes of practice!
10.1 Requirements
Specific requirements for unit commissioning must be met. The function test must be
carried out by GEA Service or specialist refrigeration company (see section 4.10) and
the commissioning report must be drawn up and sent to GEA.
We recommend that the checklist “Technical requirements for commissioning report/
Recommendation! client witness test or maintenance of chillers/heat pumps” is used to ensure that the on-
Pre-Commissioning site requirements for drawing up the commissioning report are met. This can also save
Checklist additional work and costs because GEA Service or a specialist refrigeration company
(see section 4.10) will possibly have to visit your unit again, if the on-site requirements
are not met by others beforehand. This check list can be found in Appendix I.
Obligatory! The commissioning report must be drawn up by GEA Service or a specialist refrigera-
Send Commissioning report tion company (see section 4.10). You must send the commissioning report to GEA
to GEA - for exact form - see Appendix II.If you do not send the commissioning report to
GEA, the warranty for your GEA unit will be rendered null and void!
Obligatory! With refrigeration units / chillers / heat pumps with a refrigerant charge exceeding 3 kg,
Create a unit report the owner or operator must draw up and continuously update the unit report after the
system is commissioned.
• For all checks and tests the following protective clothes are mandatory, e.g.:
– Sealing protective goggles
– PVA or leather gloves
– Protective clothes for entire body
– Safety boots
– If necessary, an autonomous breathing apparatus
NOTICE!
Follow the commissioning procedure as described below.
Ensure to carefully check each specified work step.
• Check if a pump contact (terminals C-D) in units with screw compressors without
an integrated hydraulic module is wired according to the wiring diagram (refer to
section 9.2.4 „Pump enabling“).
DAMAGE TO THE UNIT!
The pump can be damaged, if the unit is operated without water flowing through a
water cooled heat exchanger, e.g. if the shut off valves are closed. Besides, the heat
exchanger and the unit itself can be destroyed by freezing water.
Unit
GLAC/H GLWC/H GLRC GLDC GLFC GLCU
• Disconnect the unit from the power supply. Re-tighten all electrical connections in
the switch box and in terminal board of consumers. Check that all connections are
tight.
• Check that the earth conductors are connected correctly and that the earth
terminals are securely tightened.
• Check the inside of the switch box for damaged components.
• Ensure that wiring by others is carried out in accordance with the instructions and
requirements specified in chapter "Electrical Connection". This chapter stipulates
observing instructions in the electrical wiring diagrams and setting up the electrical
connection in accordance with European, national and local regulations of utility
providers.
• Check electrical connection of the mains isolator.
• Check the on-site wiring in the unit control cabinet.
– Digital inputs are single ended! It is not allowed to connect a field-provided
potential.
– Digital outputs are volt free contacts. The maximum voltage and electrical load
must not be exceeded (230 V / 50 Hz / ~ / 2 A).
• Check supply voltage. The voltage must match the details on the nameplate/
identification or the unit-specific documentation.
• Check the phase tolerance.
• Check if the clockwise rotating field is applied.It is important that the rotating
direction is correct for proper unit operation: clockwise rotating field!
• If necessary, check the rotating direction using a rotating field measuring
equipment.
Depending on the unit model, the correct direction of the rotating field is indicated by
an LED on the phase-sequence safety relay in the switch box.
• Check the compressor and piping for damage and escaping medium or oil. If you
find a refrigerant or oil leak please consult GEA Service.
ENVIRONMENTAL DAMAGE!
Dispose of any escaping media or oil immediately in an environmentally-friendly
manner and in compliance with local laws and regulations.
Procedure:
• Deactivate all compressors and refrigeration circuits (unit menu) and switch on
the pump.
• Stop the water flow.
• The unit controller must deactivate the system. An alarm message is displayed
on the controller (AL003, AL045, AL 046).
• Restore unobstructed water flow again.
• Reset this alarm (refer to chapter 12)
• Check if oil heater of compressors has been activate for at least 8 hours, before the
unit is switched on for the first time.
Calibration
8 hours of uninterrupted oil heater operation will ensure that there is no more refriger-
ant in the oil. The unit can now be put into operation and calibrated.
• Activate the 1st compressor (unit menu) and measure the current consumption and
refrigerant pressure.
Reliable recording of correctly measured values is only possible during stable opera-
tion of the unit. A stable operating state is reached approximately 0.5 h following the
unit activation. Only then calibration can begin.
• Record measured values and enter them in the commissioning report (Appendix II).
• After 30 minutes have elapsed, measure the following parameters of compressors:
– High and low pressure
– Suction gas temperature, superheat temperature
– Discharge temperature
– Fluid temperature
– Current consumption of activated consumers
– Inlet and outlet temperature of heat exchanger
• If the unit is operating under design and layout conditions, check the sight glass for
bubbles in the refrigeration circuit.
• Check if safety devices are installed in the refrigeration circuit.
• Repeat the above-mentioned steps regarding 1st compressor for the remaining
compressors.
• Check various controller settings, e.g.:
– Type of temperature regulation
– Setpoints
– External enabling (ON/OFF)
– Notification of maintenance intervals
– Alarm readings including frost protection
– etc.
if necessary, perform corresponding adjustments (refer to chapter 11).
• Activate all compressors and fill in the commissioning report in the Appendix II.
• For complete and full documenting of commissioning, it is recommended to fill in the
Measuring Report in Appendix III.
In the table below you will find typical temperature and pressure values of the unit.
Compare the values below with your measured readings. Operating limits may vary
depending on the unit series. Refer to Data&Facts catalogue of the relevant unit series,
quotations for the unit or web-based unit selection and layout software Aid@
(www.aida.geagroup.com) for specific unit data.
Water circuit:
Inlet: min. -5 °C – max. 23 °C
Evaporator: Outlet: min. -8 °C – max. 15 °C
ΔT: min. 3 K – max. 8 K
Inlet: min. 10 °C – max. 47-51 °C
Condenser (GLWC/GLWH) Outlet: min. 26 °C – max. 51-55 °C
ΔT: min. 4 K – max. 16 K
Outside air/
See unit operating range (compare chapter 5.4)
condensation temperature
Superheating: 5 - 10 K
Subcooling: 3-5K
Refrigeration circuit:
Discharge temperature: Max. 120°C
Suction pressure Economiser: 1.5 - 2 bar > suction pressure
Tab. 10-1
NOTICE!
You must send the commissioning report to GEA! If you do not send the commission-
ing report to GEA, the warranty for your GEA unit will be rendered null and void!
11 Operation
DAMAGE TO THE UNIT!
The unit must not be operated unless proper function test has been carried out.
Ensure that all steps specified in chapter 10 „Commissioning“ are carried out.
Operator ele-
Description
ment
Allows the user to go back to the next higher level in the screen tree from the
title screen; also allows the user to return to the start page.
Use the Enter key to confirm the selection and to place the cursor below pa-
rameters that need to be changed.
11.2.1 Switching on
ATTENTION!
Before switching the unit on, make sure you are aware of the operating mode
HEATING or COOLING (only for GLAH and GLWH)
Contacts G-H open = HEATING
Contacts G-H open = COOLING
• If "Com.: off" is not displayed, press the "Esc" key until "Com.: off" appears in
the display.
• If "Com.: on" is not displayed, press the "Esc" key until "Com.: on" appears in
the display.
• In the “User” menu use the arrow keys to set “Ing. dig. enabled: on/off ” Set
enable via Dig.Input: on/off“).
9 When the digital contact is open the unit is off and “OFF dig. in.” is displayed on the
start screen. If the digital contact is closed, the unit is activated and “ON dig. in.”
appears on the start screen.
– "by steps" With GEA HVAC systems Step II controller, the standard setpoint of
"INPUT": 7°C is displayed here, which in the preset proportional band corre-
sponds to the actual setpoint of 12°C (7.0°C + 5.0°C P-band = 12.0°C).
With GEA HVAC systems Step I controller, the standard setpoint of
9.5°C is displayed here, which in the preset proportional band corre-
sponds to the actual setpoint of 12°C (9.5°C + 2.5°C P-band = 12.0°C).
– "Quick Mind" as control mode, "INPUT": standard setpoint 11.0 °C is displayed
here.„OUTPUT“: standard setpoint 7.0 °C is displayed here
NOTICE!
Changing the setpoint downwards may trigger a frost protection malfunction warning.
(AL 010: evaporator frost protection; standard switch value +4 °C chilled water outlet)
Operator
Description
element
Fig. 11-2: Alternative display of unit Provides access to the main menu.
Display LED
element colour Description
If the LED is permanently on, the compressor is switched. If the LED is flash-
Green ing - the compressor is requested to switch, however, it is blocked due to the
internal safety time.
Red The compressor is blocked by a compressor or circuit alarm.
11.5.1 Switching on
• If "Com.: off" is not displayed, press the "Esc" key until "Com.: off"
appears in the display.
NOTICE!
The oil preheating remains active!
NOTICE!
Changing the setpoint downwards may trigger a frost protection malfunction warning
(AL 010: frost protection for evaporator; standard switching value of +4°C at evapo-
rator water outlet).
Proportional control via chilled water inlet temperature - unit with 2 capacity stages
Example cooling:
Capacity
Water inlet
Setpoint
Proportional band 2.5 K
In the following example it is assumed that the temperature difference in the evaporator
amounts to 5 K at 100 % cooling capacity of the unit and that the water content in the
unit is sufficient.
The setpoint is adjusted to 9.5 °C (standard value with inlet temperature control) and
proportional band of 2.5 K (also standard value). Thanks to its two compressors the
unit has two capacity stages. The proportional band is distributed among these two
capacity stages in appropriately equal ranges. This results in the following:
2.5 K / 2 capacity stages = 1.25 K / capacity stage
If the water inlet temperature amounts to 12.0 °C or more, both compressors are run-
ning (setpoint 9.5 °C + proportional band 2.5 K = 12.0 °C). If the water temperature
entering the evaporator makes up 12.0 °C, the water outlet temperature amounts to 7
°C (12.0 °C water inlet temperature - 5 K temperature difference in the evaporator at
100 % unit duty = 7.0 °C). At 10.75°C the water outlet temperature will only reach 5.75
°C. At 10.75 °C one of the compressors switches off, and the cooling capacity is
reduced to 50 %. Therefore the temperature difference across the evaporator goes
down as well by 50 % to 2.5 K. As a result, the water outlet temperature rises at water
inlet temperature of 10.75 °C from 5.75 °C with two active compressors to 8.25 °C with
only one active compressor. With water inlet temperature of 9.5 °C and water outlet
temperature of 7 °C the last compressor switches off.
At 10.75 °C (setpoint 9.5 °C + proportional band/2 1.25 K = 10.75 °C) one compressor
is activated again.
With this kind of temperature control and assuming continuous operation, the water
outlet temperature will fluctuate between 5.75 °C and 8.25 °C.
Proportional control via chilled water inlet temperature - unit with 4 capacity stages
Example cooling:
Capacity
Setpoint
Proportional band 5 K
In the following example it is assumed that the temperature difference in the evaporator
amounts to 5 K at 100 % cooling capacity of the unit and that the water content in the
unit is sufficient.
The setpoint is adjusted to 7.0 °C (standard value with inlet temperature control) and
proportional band of 5.0 K (also standard value). Thanks to its four compressors in two
independent refrigeration circuits the unit has four capacity stages. The proportional
band is distributed among these four capacity stages in appropriately equal ranges.
This results in the following:
5.0 K / 4 capacity stages = 1.25 K / capacity stage
If the water inlet temperature amounts to 12.0 °C or more, all compressors are running
(setpoint 7.0 °C + proportional band 5.0 K = 12.0 °C). If the water temperature entering
the evaporator makes up 12.0 °C, the water outlet temperature amounts to 7.0 °C (12.0
°C water inlet temperature - 5 K temperature difference in the evaporator at 100 % unit
duty = 7.0 °C). At 10.75°C the water outlet temperature will only reach 5.75 °C. At 10.75
°C one of the compressors switches off, and the cooling capacity is reduced to 75 %.
Therefore the temperature difference in the evaporator goes down as well by 25 % to
3.75 K. As a result, at water inlet temperature of 10.75 °C the water outlet temperature
rises from 5.75 °C with four active compressors to 7.0 °C with three active compres-
sors. The described sequence is thus continued.
With water inlet temperature of 7.0 °C the evaporators water outlet temperature
amounts to 5.75 °C with one active compressor corresponding to 25% total capacity.
At 7.0 °C the last compressor switches off. At 8.25 °C (setpoint 7.0 °C + proportional
band/4 1.25 K = 8.28 °C) one compressor is activated again. With this kind of temper-
ature control and assuming continuous operation, the water outlet temperature will
fluctuate between 5.75 °C and 8.25 °C.
Proportional control via chilled water inlet temperature - unit with 2 capacity stages
Example heating:
Capacity
Water inlet
Setpoint
In the following example it is assumed that the temperature difference across the plate
heat exchanger amounts to 5 K at 100 % heating capacity of the unit and that the water
content of the unit is sufficient.
The setpoint is adjusted to 42.5 °C (standard value with inlet temperature control) and
proportional range of 2.5 K (also standard value). Thanks to its two compressors the
unit has two capacity stages. The proportional range is distributed among these two
capacity stages in appropriately equal ranges. This results in the following:
Proportional control via chilled water inlet temperature - unit with 4 capacity stages
Example heating:
Capacity
Water inlet
Setpoint
Setpoint
Proportional band 5 K
In the following example it is assumed that the temperature difference across the heat
exchanger amounts to 5 K at 100 % heating capacity of the unit and that the water con-
tent of the unit is sufficient.
The setpoint is adjusted to 42.5 °C (standard value with inlet temperature control) and
proportional range of 5.0 K (also standard value). Thanks to its four compressors in two
independent refrigeration circuits the unit has four capacity stages. The proportional
range is distributed among these four capacity stages in appropriately equal ranges.
This results in the following:
5.0 K / 4 capacity stages = 1.25 K / capacity stage
If the water inlet temperature amounts to 37.5 °C or less, all compressors will be run-
ning (setpoint 42.5 °C - proportional band 5.0 K = 37.5 °C). If the water temperature
entering the evaporator makes up 37.5 °C, the outlet temperature will amount to 42.5
°C (37.5 °C water inlet temperature + 5 K temperature difference across the evaporator
at 100 % = 42.5 °C). At 38.75°C the water outlet temperature will reach 43.75 °C. At
38.75 °C one of the compressors switches off, and the heating capacity is reduced to
75 %. Therefore the temperature difference in the heat exchanger goes down as well
by 25 % to 3.75 K.As a result the water outlet temperature goes down to 42.5 °C,
because only 3 compressors are in operation. The described sequence is thus contin-
ued.
With water inlet temperature of 42.5 °C the evaporator water outlet temperature
amounts to 43.75 °C with one active compressor corresponding to 25% total capacity.
At 42.5 °C the last compressor switches off. At 41.25 °C (setpoint 42.5 °C + propor-
tional band /4 1.25 K = 41.25 °C) one compressor is activated again. With this kind of
temperature control and assuming continuous operation, the water outlet temperature
will fluctuate between 42.5 °C and 43.75 °C.
Auto-adaptive control with neutral range via water outlet or inlet temperature
Setpoint cooling/heating
Capacity ↓ Capacity↑
Neutral zone
Temperature
Variable zone
Fig. 11-7: Auto-adaptive control
With this type of control system the chilled water inlet or outlet temperature is used as
the control variable. In this case only the setpoint is specified, and the controller auto-
matically determines all other switching thresholds in dynamic mode during operation.
With this self-adjusting algorithm for temperature control of the unit the setpoint stays
within a neutral range. If the evaporator water temperature is within the neutral range,
the number of active compressors and/or capacity stages is not changed.
If load fluctuations in the system result in temperature values outside the neutral range,
compressors and capacity stages are activated or deactivated to return the tempera-
ture to the neutral range.
If this is not possible due to the decreased load, another capacity stage is activated or
deactivated. The width of the neutral range depends on the dynamic properties of the
system, especially the system content and the decreased load. The self-adjusting algo-
rithm is able to determine the dynamics of the system. The neutral range is calculated
so that the compressor switching times and the max. permissible start-up frequency
(e.g. 8 times per hour) only cause very small temperature deviations from the setpoint.
Other implemented functions reduce the compressors’ start-up frequency at low loads.
Capacity stages are activated and deactivated not only as a result of wide setpoint var-
iances, but also in relation to the temperature change-over time, which allows to make
conclusions about the output.
Disconnecting the unit from the power supply
DAMAGE TO THE UNIT!
– Frost protection using internal frost protection heating is not provided.
– The oil preheating is no longer active.
• Connect tubes to all drain valves to ensure controlled draining of water or water-
glycol mixture.
• Ensure leak-free condition of the unit: oil, water-glycol mix must not be released to
the environment.
• Properly collect all liquids and dispose of in an environmentally-friendly way in
accordance with local codes and regulations.
• Open all hydraulic shut-off valves
• Open shut-off valves on the drain valves.
• Open air vent valves to ensure trouble-free water draining.
• Avoid negative pressure in unit and connected hydraulic circuit.
• Following draining of the hydraulic circuit, use compressed air to blow out the unit
and connected hydraulic circuit to eliminate remaining water and water-glycol mix.
DAMAGE TO THE UNIT!
– Residual water can freeze and destroy the unit.
– If the unit is equipped with a pump enabling function (see chapter 9.3.4 pump
enabling) pump block-up protection is activated. This function regularly activates
pumps which are controlled by the main unit to prevent pump blockage during
extensive shutdown periods. The pump block-up protection is also active even
the unit is deactivated via keyboard or digital contact of external remote ON/OFF.
– Evaporator trace heating and where available frost protection heating in the buff-
er tank can result in serious unit damage.
– Therefore, before activating the main isolator check that the hydraulic network,
evaporator and, where available, buffer tank are filled and air vented.
– Before the hydraulic network is drained, ensure that the main isolator of the unit
is deactivated, the unit is de-energised to prevent inadvertent activation.
12.1 Alarms
What to do in case of alarms:
1. Inform GEA Service.
2. Have GEA Service attend to the cause of failure.
3. Only GEA Service is allowed to reset the fault.
104 Isolation expansion See alarm message 091 "Isolation expansion with address 1" only for extension 4
A U
Slave with address 4 of Slave
105 Isolation expansion See alarm message 091 "Isolation expansion with address 1" only for extension 5 A U
Slave with address 5 of Slave
111 Oil compressor 1 Oil level of compressor Nr.1 too low.
Following compressor start alarm message of oil level switch is bridged for 90 s.
If oil level switch opens for more than 10 s following first 90 s of compressor opera-
tion, the compressor duty is raised to 100 % in order to ensure oil return. If in the
following 80 s the oil level does not rise, the compressor is blocked and isolated.
Possible reasons to be investigated:
Refrigeration circuit
– Insufficient oil due to leak
– Insufficient refrigerant
– Faulty expansion valve
– Defective oil level switch
– Defective solenoid valves of compressors
M CO
– Defective input of controller PCB
– Defective output of controller PCB for solenoid valve(s)
– Incorrect wiring
– Loose cable connection
– Cable failure
Before resetting alarm, it is absolutely mandatory to check oil level of corresponding
compressor.
Never reset alarm, if oil level did not reach the minimum mark. Destruction of com-
pressor can be the consequence.
Only charge oil specified on the unit identification plate. Excessive oil level should
be avoided to prevent compressor from damage.
This alarm message is valid only for units with screw compressors.
112 Oil compressor 2 See alarm message 111 „Oil compressor 1“ only for compressor 2 M CO
113 Oil compressor 3 See alarm message 111 „Oil compressor 1“ only for compressor 3 M CO
114 Oil compressor 4 See alarm message 111 „Oil compressor 1“ only for compressor 4 M CO
131 Fault, compressor 1 Motor protection relay and/or automatic circuit breaker tripped for compressor 1.
Possible reasons to be investigated:
Refrigeration circuit
– Insufficient refrigerant
– Faulty expansion valve
– Operation outside operating limits
– Acidic oil
– Faulty solenoid valve for liquid injection/missing liquid injection
– Mechanical blockage of compressor
– Faulty compressor
Electrical system:
– Malfunction of one or more phases
– Power supply outside tolerance range
M - A/M CO
– Phase asymmetry too high
– Load contactor does not switch one or more phases
– Contact resistance of load contactor too high
– Coil short circuit of compressor motors -> perform oil acidity test a.s.a.p.
– Winding short circuit of compressor motor -> perform oil acidity test a.s.a.p.
– Earth fault of compressor motors -> perform oil acidity test a.s.a.p.
– Faulty compressor
– Defective input on controller
– Incorrect wiring
– Loose cable connection
– Cable failure
Never reset alarm as long as the reason for failure is not established. Destruction
of compressor can be the consequence.
132 Fault, compressor 2 See alarm message 131 „Fault compressor 1“ only for compressor 2 M - A/M CO
133 Fault, compressor 3 See alarm message 131 „Fault compressor 1“ only for compressor 3 M - A/M CO
134 Fault, compressor 4 See alarm message 131 „Fault compressor 1“ only for compressor 4 M - A/M CO
135 Fault, compressor 5 See alarm message 131 „Fault compressor 1“ only for compressor 5 M - A/M CO
136 Fault, compressor 6 See alarm message 131 „Fault compressor 1“ only for compressor 6 M - A/M CO
137 Fault, compressor 7 See alarm message 131 „Fault compressor 1“ only for compressor 7 M - A/M CO
138 Fault, compressor 8 See alarm message 131 „Fault compressor 1“ only for compressor 8 M - A/M CO
151 Maintenance, compressor 1 Sum of operating hours exceeds maintenance interval stored in controller.
General alarm contact is closed, but the unit continues to operate.
Automatic notification about maintenance intervals can be deactivated using a serv- S -
ice password.
To rest an alarm the service password is required as well.
154 Maintenance, compressor 4 See alarm message 151 „Maintenance compressor 1“ (only for units with 4 com-
S -
pressors).
155 Maintenance, compressor 5 See alarm message 151 „Maintenance compressor 1“ (only for units with 5 com- S -
pressors).
156 Maintenance, compressor 6 See alarm message 151 „Maintenance compressor 1“ (only for units with 6 com-
S -
pressors).
157 Maintenance, compressor 7 See alarm message 151 „Maintenance compressor 1“ (only for units with 7 com- S -
pressors).
158 Maintenance, compressor 8 See alarm message 151 „Maintenance compressor 1“ (only for units with 8 com-
pressors). S -
As standard alarm value of the high-pressure sensor is set higher than the trigger
value of the high-pressure switch. If "Alarm 241" is active check the corresponding
high-pressure switch.
242 High pressure converter 2 See alarm message 241 „High pressure through converter 1“, but for refrigeration
circuit 2 M CI
243 High pressure converter 3 See alarm message 241 „High pressure through converter 1“, but for refrigeration
M CI
circuit 3
244 High pressure converter 4 See alarm message 241 „High pressure through converter 1“, but for refrigeration M CI
circuit 4
251 Timeout start of circuit 1 If low pressure reading with requested but not yet activated compressor lower or
equals value of low pressure alarm, the unit switches in error mode.
Possible reasons to be investigated:
Refrigeration circuit
– Insufficient refrigerant
– Faulty expansion valve
– Faulty solenoid valve for liquid line
Electrical system:
– Faulty low pressure sensor
-> Check indicated pressure in controller with actual A CI
pressure measured by pressure gauge.
-> Use a 4-20 mA encoder by others to simulate the corresponding signal
and evaluate the result displayed the controller.
– Deactivated low pressure sensor
– Defective input on controller
– Incorrect wiring
– Loose cable connection
– Cable failure
This alarm is valid only for units with a low pressure sensor.
252 Timeout start of circuit 2 See alarm message 251 „Timeout start of circuit 1“, but for refrigeration circuit 2 A CI
253 Timeout start of circuit 3 See alarm message 251 „Timeout start of circuit 1“, but for refrigeration circuit 3 A CI
284 Evaporating pressure See alarm message 281 "Insufficient evaporating pressure circuit 1", only for
M CI
insufficient in circuit 4 refrigeration circuit 4
631 Pre-alarm low pressure Pre-alarm is a signal message transmitted to building management system Unit
Circuit 1 continues to operate and informs beforehand about expected fault message. Gen-
eral alarm contact is not closed.
Pre-alarm must activated in controller menu and the corresponding signal value
must be entered as a positive difference to alarm value. S -
As a remedy for „Pre-alarm low pressure circuit 1“ see alarm message 231 „Low
pressure circuit 1“.
For displaying pre-alarm 631 only measured value of low pressure sensor is evalu-
ated.
632 Pre-alarm low pressure See alarm message 631 „Pre-alarm low pressure circuit 1“, but for refrigeration cir-
cuit 2 S -
Circuit 2
633 Pre-alarm low pressure See alarm message 631 „Pre-alarm low pressure circuit 1“, but for refrigeration cir-
cuit 3 S -
Circuit 3
634 Pre-alarm low pressure See alarm message 631 „Pre-alarm low pressure circuit 1“, but for refrigeration cir-
cuit 4 S -
Circuit 4
This alarm only applies for units with screw compressors and requires high and low
pressure sensors per each refrigeration circuit as well as a discharge temperature
sensor.
652 Checking operating range: Refer to alarm message 651 „Checking operating range: discharge temperature too
discharge temperature too low in circuit 1“, only for refrigeration circuit 2 M CI
low for circuit 2
653 Checking operating range: Refer to alarm message 651 „Checking operating range: discharge temperature too
discharge temperature too low in circuit 1“, only for refrigeration circuit 3 M CI
low for circuit 3
654 Checking operating range: Refer to alarm message 651 „Checking operating range: discharge temperature too
discharge temperature too low in circuit 1“, only for refrigeration circuit 4 M CI
low for circuit 4
This alarm only applies for units with screw compressors and requires high and low
pressure sensors per each refrigeration circuit as well as a discharge temperature
sensor.
662 Checking operating range: Refer to alarm message 661 „Checking operating range: discharge temperature too
discharge temperature too high in circuit 1“, only for refrigeration circuit 2 M CI
high for circuit 2
663 Checking operating range: Refer to alarm message 661 „Checking operating range: discharge temperature too
discharge temperature too high in circuit 1“, only for refrigeration circuit 3 M CI
high for circuit 3
664 Checking operating range: Refer to alarm message 661 „Checking operating range: discharge temperature too
discharge temperature too high in circuit 1“, only for refrigeration circuit 4 M CI
high for circuit 4
671 Checking operating range: Alarm indicates that high pressure fell below minimum allowed high pressure while
high pressure too low for cir- in operation.
cuit 1 If the high pressure remains below the set alarm value 120 s following compressor
start or deactivation or 30 s during the operation, the refrigeration circuit is deacti-
vated as a result of a fault.
The bridging time of 120 s also applies after the changeover of operating mode, dur-
ing pump downtime or defrost cycle.
Possible reasons to be investigated:
Refrigeration circuit:
– Insufficient refrigerant (sight glass must be without bubbles following around 10
min of operation)
– Faulty expansion valve (measure overheat, 5 to 10 K following 10 min of opera-
tion)
– Operation outside operating limits
Additionally for air cooled units:
– Too low air inlet temperature M CI
– Condenser is not installed in a wind protected location (refer to operating limits)
Additionally for water cooled units:
– Water temperature at condenser is too low (refer to operating limits)
Electrical system:
– Faulty low pressure sensor
-> Check pressure displayed in controller against the actual pressure measured by
pressure gauge.
-> Use a 4-20 mA encoder by others to simulate the corresponding signal and
evaluate the result displayed by the controller.
– Defective input on controller
– Incorrect wiring
– Loose cable connection
– Cable failure
This alarm requires high and low pressure sensors per each refrigeration circuit.
Tab. 12-1
Tab. 12-2
60
50
40
Resistance [kOhm]
30
20
10
0
-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45
Temperature [°C]
Fig. 12-1: Diagram for temperature resistance of GEA HVAC systems controller
13.2 Maintenance
Unit report With refrigeration units / chillers / heat pumps with a refrigerant charge exceeding 3 kg
the owner or operator has to create and continuously update the unit report. According
to the EN 378-4 standard, the unit report must be updated following the unit mainte-
nance or service. You can find the unit report in Appendix IV „Log book for chillers, heat
pumps and compressor/condenser units“. Enter the data specified on the unit code
plate in chapter 1. In such a way a clear relationship is established between the unit,
the current operation manual and the unit report.
Maintenance Unit maintenance must only be carried out by GEA Service or a licensed refrigeration
company! Consider the instructions specified in section 4.10 "Personnel selection and
qualification". During maintenance work all safety-relevant codes and practices must
be observed.
Mandatory! Have the system serviced at least once a year!
A minimum Depending on the refrigerant charge, legal codes and regulations require to have this
1 annual maintenance maintenance conducted, at the same time the latter also constitutes the condition for
the validity of the warranty.
Moreover, the following legally mandatory maintenance intervals must be observed:
Maintenance
Maintenance Condition Responsible
frequency
30-300 kg yes
Check that the entire system is tight
GEA Service or li-
3-30 kg - censed refrigeration
every 12 months company
Check proper function of the leakage detection - -
system (if available)
every 24 months
Check water glycol mixture for corrosion protec-
- -
tion properties
For exact refrigerant charge volume - refer to the unit identification plate.
Use this report to verify whether all specified maintenance jobs and measurements
have been carried out.
Also consider legal requirements regarding maintenance of refrigeration chill-
ers/heat pumps and connected systems apply in addition to previously men-
tioned regulations.
Recommendation! We recommend that you have your unit serviced twice a year.
2 maintenance services per
year
NOTICE!
If case of leaking refrigerant, liquids or oil - switch off the unit immediately and inform
GEA Service.
ENVIRONMENTAL DAMAGE!
All leaking media must be disposed of in accordance with the current regulations,
local codes and practices.
ENVIRONMENTAL DAMAGE!
Have qualified licensed staff dismantle and dispose of the unit!
14.1 Dismantling
To dismantle the units proceed as follows:
DANGER OF ELECTRICAL CURRENT!
When carrying out decommissioning and dismantling work on the unit, disconnect all
power supply connections, ensure the power cannot be inadvertently energized and
verify that electric lines have been disconnected. Earth and short-circuit them, and
cover or otherwise isolate any neighboring live parts. Non-compliance can lead to
death or serious injury.
PERSONAL INJURY
Secure the unit against slipping.
14.2 Disposal
NOTICE!
The operator of the refrigeration unit is responsible for taking all necessary precau-
tionary measures and ensures that only certified and licensed staff properly recov-
ers, recycles, processes and disposes of fluorinated refrigerants containing
greenhouse gases (F-Gases).
ENVIRONMENTAL DAMAGE!
Dispose of all components and materials (such as oil, refrigerants and water-glycol
mixture) in an environmentally friendly manner in accordance with the local codes,
practices and environmental regulations.
15 Appendix
The following pages contain check lists and reports:
On 15.1 Appendix I Technical Requirements for Function Testing or Maintenance
of Chiller/Heat Pump
See Appendix I For commissioning:
We recommend to use the checklist “Technical requirements for commissioning report/
client witness test of chiller/heat pump” to ensure that the on-site requirements for
drawing up the commissioning report are fulfilled ("Commissioning report" in Appendix
II). This can also save additional work and costs because GEA Service will possibly
have to visit your unit again, if the on-site requirements were not met beforehand.
Pre-maintenance jobs:
Prior to maintenance jobs and creation of Maintenance and Measuring Report
(Appendix III), “Technical requirements for maintenance of chiller/heat pump” must be
fulfilled as well.
NOTICE!
You must send the commissioning report to GEA!If you do not send the commission-
ing report to GEA, the warranty for your GEA unit will be rendered null and void!
Siehe “Schematic representation of various hydraulic circuits (examples)” auf Seite 33.
Glycol
Glykol charged
Glycol on: von: by:
added/checked
eingefüllt / geprüft Glycol
Glycol charged
added/checked
Glykol eingefüllt on1): von
/ geprüft by1)1)::
Glycol added/checked by: Glycol added/checked by1):
91
15.2 Appendix II Report
Commissioning
Commissioning Report
Funktionsprüfungsprotokoll
GEA Company name: Customer / Operator name: Installer´s name:
Name GEA Firma Name Kunde / Betreiber: Name Anlagenbauer:
Customer / Operator name: Unit data:
Kunden-
Company: / Betreiber Daten Gerätedaten
Type: Order:
Firma:
Street: Typ: Number:
Serial A.-Nr.:
Straße:
City: SerienNummer:
Buffer tank S.N.:
Stadt:
Witnessed by: Phone: Pufferspeicher
Condenser S.N.:
S.N.:
Vertreter:
Commissioning requested by: Telefone: Verflüssiger S.N.:
Funktionsprüfung angefordert von
Operating data:
Betriebsdaten: T in [°C] @100 % T out [°C] @100 % deltaT [K] @100 % Chilled water Pump
Evaporator: T in [°C] @100 % T aus [°C] @100 % deltaT [K] @100 % Type: Kalt-/Warmwasserpumpe
Verdampfer: Typ:
Condenser: Current: / /
Verflüssiger: Stromaufn.: / /
Outside temp.: Control Voltage: Power supply: Type Glycol
Außentemperatur: Steuerspannung: Spannungsversorgung: Typ Glykol
[°C] [V] [V] / / %
[°C] [V] [V] / / %
Compressor N°N° 11 22 33 44 5
5
6
6
7
7
8
8
Verdichter
Evaporating press. bar
Verdampfungsdruck bar
Condesing press.
Verflüssigungsdruck bar
bar
Discharge temp.
Heißgastemperatur °C°C
Suction line temp.
Sauggastemperatur °C°C
Liquid line temp.
Flüssigkeitstemperatur °C°C
Current consump.
Stromaufnahme L1 L1 AA
Stromaufnahme L2 L2 AA
Current consump.
Current consump.
Stromaufnahme L3 L3 AA
CapacityGerät
Leistung unit @measurem.
bei Messung %% %
% %
% %
% %
% %
% %
% %
%
Measure.
Werte @working mode
bei Betriebsart: Chiller
Kaltwasser Heat pump
Wärmepumpe Chiller- and Heat pump mode
Kalt- und Warmwasserbetrieb
Circuit 1 1
Kreislauf Circuit 2 2
Kreislauf Circuit 33
Kreislauf Circuit 44
Kreislauf
Cond. fanLüfter
Stromauf. current
L1 L1 AA
Cond. fanLüfter
Stromauf. current
L2 L2 AA
Cond. fanLüfter
Stromauf. current
L3 L3 AA
Hydraulic system
Überprüfung check (see(Nr.
Wasserkreislauf OM): siehe BA): Unit check:
Geräteprüfung:
1. Manometer
1. Pressure gauge Yes
Ja No
Nein Electric connectionsgeprüft:
Kabelverbindungen checked: JaYes No
Nein
2. Absperrventile
2. Shut off valveManometer
press. gauge Yes
Ja No
Nein Wert: Prüfung:
3.
3. Automatische Entlüftung
Autom. Air venting Ja
Yes Nein Low
No Niederdruckschalter
press. switch bar
bar JaYes Nein
No
4 Rohrleitungskompensatoren
Vibration damping point Ja
Yes Nein High
No Hochdruckschalter
press. switch bar
bar JaYes Nein
No
6.
6. Wasserfilter
Water filter Ja
Yes Nein Anti
No Frostschutz
freeze value °C°C JaYes Nein
No
7.
7. Entleerungsventil
Drain valve Ja
Yes Nein Set
No Sollwert
pointGeräte
Unit °C°C JaYes Nein
No
8.
8. Pumpe
Pump (Gerätekreislauf)
(Unit circuit) Ja
Yes Nein Hydr.
No Hydr.Diff.drucksch.
diff. press. switch bar
bar JaYes Nein
No
9
9 Sicherheitsventil
Safety valve: : barbar Ja
Yes Nein
No Einstellungen geprüft
Check funct. & setting JaYes Nein
No
10.
10. Ausdehnungsgefäß
Expansion vessel Ja
Yes Nein Free
No Freiraum
spaceum das Gerät:
around the unit
11.
11. Füllventil
Filling valve Ja
Yes Nein
No R1:
R1: cm
cm
12. Paddelströmungswächter
12. Flow switch (Paddle type) Ja
Yes Nein
No R1
13. R1
13. Durchflussregulierventil
Regulation valve Ja
Yes Nein
No R2:
R2: cm
cm
14. R
R R
R
14. 2.2Pumpe
nd
Pump/ 3-Wege-Ventil
/ 3-way-valve Ja
Yes Nein
No 3 4
16.
15. Pufferspeicher:
Buffer tank: Liter
litre Ja
Yes Nein
No 3 4 R3:
R3: cm
cm
- - Pumpenkontakt
Pump operation contact Ja
Yes Nein
No R2
R2
- - Absperrventil
Shut-Off valve (Verdampfer)
(Evaporator) Ja
Yes Nein
No R4:
R4: cm
cm
- - Hydraulikkreislauf fertig
Hydraulic circuit finished Ja
Yes Nein
No
Schwingungsdämpfer
Anti Vibration rubbersunter Gerätbelow
installed lt. Maßzeichnung
the unit installiert:Yes Ja No Nein N°Anzahl Schw.dämpfer
of AV rubbers
Kommentar:
Notes:
92
Appendix II
Commissioning Report
Legend:
Installation
Buffer tank Water filter position of 3-way-
Pump (vertical) Flow switch
valve
Shut-off valve Safety valve
Buffer tank Temperature sensor
(horizontal) Flow regulating
Unit valve
Pressure gauge
No return valve
Hydraulic
switch 2-way-valve
93
Anhang III A
Page 1 of 6
94
R. Refrigeration circuit Serial Nr. unit: Date
Measured unit Measured values
Refrigeration circuit 1 2 3 4 Unit
Values at load %
R.1 Condensing pressure bar
R.2 Condensing temp. °C
R.3 Liquid temp. °C
R.4 Sub cooling K
R.5 Discharge temperature °C
R.6 Suction pressure bar
R.7 Evaporation temp. °C
R.8 Suction gas temp. °C
R.9 Superheating K
R.10 Safety valve bar
R.11 Tested HP switch point bar
R.12 Tested LP switch point bar
Page 2 of 6
95
EW. Evaporator Serial Nr. unit: Date
Type Serial number of evaporator
Medium Glycol %/ °C Glycol type Water
Measured unit Measured values
Values at full load (100%) Circuit 1 Circuit 2 Circuit 3 Circuit 4 Unit
EW.1 Medium inlet temperature °C
EW.2 Medium outlet temperature °C
EW.3 ǻT K
EW.4 Inlet water pressure bar
EW.5 Outlet water pressure bar
EW.6 ǻp bar
EW.7 GEA GLHM / GLPE available yes no by others
EW.8 Type of hydraulic module Serial Nr.
EW.9 Buffer tank available / size litre Single circuit tank Dual circuit tank
EW.10 Strainer available yes no Cleaned yes no
EW.11 Flow switch available yes no Function ok not ok
EW.12 Pressure gauge available yes no
EW.13 Shut off valves available yes no
EW.14 Expansion tank available yes no
EW.15 Safety valve available yes no Pressure bar
EW.16 Current consumption of pumps L1 L2 L3
EW.17 Chilled water pump 1 A
EW.18 Chilled water pump 2 A
EW.19 Chilled water pump type 1 Serial Nr.
EW.20 Chilled water pump type 2 Serial Nr.
Notes
R1 mm
R2 mm
R3 mm
R4 mm
Page 3 of 6
96
CA. Condenser Serial Nr. unit: Date
Type Serial number
Measured unit Measured values
Circuit 1 Circuit 2 Circuit 3 Circuit 4 Unit
CA.1 Cleaning of fins necessary Yes / No
CA.2 Cleaning of fins done Yes / No
CA.3 Air heat exchanger inlet °C
CA.4 Air heat exchanger outlet °C
CA.5 ǻT K
CA.6 Condensing temp. °C
CA.7 Refrigerant outlet temperature °C
CA.8 Difference CA.7 zu CA.3 K
CA.9 Current consumption of motors L1 L2 L3
CA.10 Fan motor 1 A
CA.11 Fan motor 2 A
CA.12 Fan motor 3 A
CA.13 Fan motor 4 A
CA.14 Fan motor 5 A
CA.15 Fan motor 6 A
CA.16 Fan motor 7 A
CA.17 Fan motor 8 A
CA.18 Fan motor 9 A
CA.19 Fan motor 10 A
CA.20 Fan motor 11 A
CA.21 Fan motor 12 A
Speed control
CA.22 Start speed min. bar Speed %
CA.23 Start speed max. bar Speed %
Speed regulation
CA.24 Start fan speed 1 bar Difference bar
CA.25 Start fan speed 2 bar Difference bar
CA.26 Start fan speed 3 bar Difference bar
CA.27 Start fan speed 4 bar Difference bar
Notes
Page 4 of 6
97
C. Controller and Settings Serial Nr. unit: Date
Used controller Software version
Set parameters Note
Page 5 of 6
98
G Check / visual inspection Serial Nr. unit: Date
o. k. Not O.K. Comment / action required
G.1 Compressor
G.2 Condenser
G.3 Evap.
G.3 Fans
Check for secured position, debris, damage
G.3.1
and corrosion.
G.3.2 Check for unbalanced impeller
Page 6 of 6
99
Measuring Report air cooled Heat Pumps: GLAH
Service engineer Cost Date
GEA Order Nr. Service-Nr.
GEA Order No (bottom of unit type plate)
Plant operator
Contact person Tel.
Address Fax.
Postal code / City E-Mail
Plant manufacturer
Contact person Tel.
Address Fax.
Postal code / City E-Mail
Page 1 of 7
100
R. Ref. circuit cooling Serial Nr. unit: Date:
Measured unit Measured values
Refrigeration circuit 1 2 3 4 Unit
Values at load %
R.1 Condensing pressure bar
R.2 Condensing temp. °C
R.3 Liquid temp. °C
R.4 Subcooling K
R.5 Discharge temperature °C
R.6 Suction pressure bar
R.7 Evaporation temp. °C
R.8 Suction gas temp. °C
R.9 Superheating K
R.10 Safety valve bar
R.11 Tested HP switch point bar
R.12 Tested LP switch point bar
Page 2 of 7
101
EW. Evaporator in cooling mode Serial Nr. unit: Date:
Type: Serial number of evaporator:
Medium Glycol %/ °C Glycol type: Water
Measured unit Measured values
Values at full load (100%) Circuit 1 Circuit 2 Circuit 3 Circuit 4 Unit
EW.1 Medium inlet temperature °C
EW.2 Medium outlet temperature °C
EW.3 ǻT K
EW.4 Inlet water pressure bar
EW.5 Outlet water pressure bar
EW.6 ǻp bar
EW.7 GEA GLHM available yes no by others
EW.8 Type of hydraulic module Serial Nr.
EW.9 Buffer tank available / size litre Single circuit tank Dual circuit tank
EW.10 Strainer available yes no Cleaned yes no
EW.11 Flow switch available yes no Function ok not ok
EW.12 Pressure gauge available yes no
EW.13 Shut off valves available yes no
EW.14 Expansion tank available yes no
EW.15 Safety valve available yes no Pressure bar
EW.16 Current consumption of pumps L1 L2 L3
EW.17 Water pump 1 A
EW.18 Water pump 2 A
EW.19 Water pump type 1 Serial Nr.
EW.20 Water pump type 2 Serial Nr.
Notes
R1 mm
R2 mm
R3 mm
R4 mm
Page 3 of 7
102
CA. Condenser in cooling mode Serial Nr. unit: Date:
Type: Serial number:
Measured unit Measured values
Circuit 1 Circuit 2 Circuit 3 Circuit 4 Unit
CA.1 Cleaning of fins necessary Yes / No
CA.2 Cleaning of fins done Yes / No
CA.3 Air heat exchanger inlet °C
CA.4 Air heat exchanger outlet °C
CA.5 ǻT K
CA.6 Condensing temp. °C
CA.7 Refrigerant outlet temperature °C
CA.8 Difference CA.7 to CA.3 K
CA.9 Current consumption of motors L1 L2 L3
CA.10 Fan motor 1 A
CA.11 Fan motor 2 A
CA.12 Fan motor 3 A
CA.13 Fan motor 4 A
CA.14 Fan motor 5 A
CA.15 Fan motor 6 A
CA.16 Fan motor 7 A
CA.17 Fan motor 8 A
CA.18 Fan motor 9 A
CA.19 Fan motor 10 A
CA.20 Fan motor 11 A
CA.21 Fan motor 12 A
Speed control
CA.22 Start speed min. bar Speed %
CA.23 Start speed max. bar Speed %
Speed regulation
CA.24 Start fan speed 1 bar Difference bar
CA.25 Start fan speed 2 bar Difference bar
CA.26 Start fan speed 3 bar Difference bar
CA.27 Start fan speed 4 bar Difference bar
Notes
Page 4 of 7
103
R. Ref. circuit heating
Measured unit Measured values
Refrigeration circuit 1 2 3 4 Unit
Values at load %
R.28 Condensing pressure bar
R.29 Condensing temp. °C
R.30 Liquid temp. °C
R.31 Subcooling K
R.32 Discharge temperature °C
R.33 Suction pressure bar
R.34 Evaporation temp. °C
R.35 Suction gas temp. °C
R.36 Superheating K
Page 5 of 7
104
C. Controller and Settings Serial Nr. unit: Date
Used controller Software version
Set parameters Note
Page 6 of 7
105
G Check / visual inspection Serial Nr. unit: Date
o. k. Not O.K. Comment / action required
G.1 Compressor
G.2 Condenser
G.3 Evaporator
G.3 Fans
Check for secured position, debris, damage
G.3.1
and corrosion.
G.3.2 Check for unbalanced impeller
Page 7 of 7
106
Measuring Report Chiller: GLRC
Service engineer Cost Date
GEA Order Nr. Service-Nr.
GEA Order No (bottom of unit type plate)
Plant operator
Contact person Tel.
Address Fax.
Postal code / City E-Mail
Plant manufacturer
Contact person Tel.
Address Fax.
Postal code / City E-Mail
page 1 of 6
107
R. Refrigeration Circuit Serial Nr. Date
Measured unit Measured values
Refrigeration circuit 1 2
Compressor 1 2 3 4 Unit
Values at load 100 100 100 100 %
R.1 Condensing pressure bar
R.2 Condensing temperature °C
R.3 Fluid temperature °C
R.4 Subcooling (Bubble Point) K
R.5 Discharge temperature °C
R.6 Suction pressure bar
R.7 Evaporation temperature °C
R.8 Suction gas temperature °C
R.9 Overheating (dew point) K
R.10 Blow off pressure safety valve bar
R.11 Tested HP switch point bar
R.12 Tested LP switch point bar
page 2 of 6
108
EW. Evaporator Serial Nr. Date
Type Serial number of evaporator
Medium Glycol %/ °C Glycol type Water
Measured unit Measured values
Values at full load (100%) Circuit 1 Circuit 2 Unit
EW.1 Medium inlet temperature °C
EW.2 Medium outlet temperature °C
EW.3 ǻT K
EW.4 Inlet water pressure bar
EW.5 Outlet water pressure bar
EW.6 ǻp bar
EW.7 GEA GLPE available yes no by others
EW.8 Type GLPE pump module Serial Nr.
EW.9 Buffer tank available / size Litre Single circuit tank Dual circuit tank
EW.10 Strainer available yes no Cleaned yes no
EW.11 Flow switch available yes no Function ok not ok
EW.12 Pressure gauge available yes no
EW.13 Shut off valves available yes no
EW.14 Expansion tank available yes no
EW.15 Safety valve available yes no Pressure bar
EW.16 Current consumption of pumps L1 L2 L3
EW.17 Chilled water pump 1 A
EW.18 Chilled water pump 2 A
EW.19 Chilled water pump type 1 Serial Nr.
EW.20 Chilled water pump type 2 Serial Nr.
Notes
R1 mm
R2 mm
R3 mm
R4 mm
page 3 of 6
109
!!! BY OTHERS !!!
CA. Air Cooled Condenser Serial Nr. Date
Type Serial number
Measured unit Measured values
Refrigeration circuit 1 Refrigeration circuit 2 Unit
CA.1 Cleaning of fins necessary Yes / No
CA.2 Cleaning of fins done Yes / No
CA.3 Air heat exchanger inlet °C
CA.4 Air heat exchanger outlet °C
CA.5 ǻT K
CA.6 Condensing temperature °C
CA.7 Refrigerant outlet temperature °C
CA.8 Difference CA.7 to CA.3 K
CA.9 Current consumption of motors L1 L2 L3
CA.10 Fan motor 1 A
CA.11 Fan motor 2 A
CA.12 Fan motor 3 A
CA.13 Fan motor 4 A
CA.14 Fan motor 5 A
CA.15 Fan motor 6 A
CA.16 Fan motor 7 A
CA.17 Fan motor 8 A
CA.18 Fan motor 9 A
CA.19 Fan motor 10 A
CA.20 Fan motor 11 A
CA.21 Fan motor 12 A
Speed control
CA.22 Start speed min. bar Speed %
CA.23 Start speed max. bar Speed %
Speed regulation
CA.24 Start fan speed 1 bar Difference bar
CA.25 Start fan speed 2 bar Difference bar
CA.26 Start fan speed 3 bar Difference bar
CA.27 Start fan speed 4 bar Difference bar
Notes
page 4 of 6
110
C. Controller and Settings Serial Nr. Date
Used controller Software version
page 5 of 6
111
G Check / visual inspection Serial Nr. Date
o. k. Not O.K. Comment / action required
G.1 Compressor
G.2 Condenser
G.3 Evaporator
G.3 Fans
Check for secured position, debris, damage
G.3.1
and corrosion.
G.3.2 Check for unbalanced impeller
page 6 of 6
112
Measuring Report GLWC Chiller
Service engineer Cost Date
GEA Order Nr. Service-Nr.
GEA Order No (bottom of unit type plate)
Plant operator
Contact person Tel.
Address Fax.
Postal code / City E-Mail
Plant manufacturer
Contact person Tel.
Address Fax.
Postal code / City E-Mail
Vers.02/2012-1 by TK
Page 1 of 6
113
R. Refrigeration circuit Serial Nr. unit: Date:
Measured unit Measured values
Refrigeration circuit 1 2 3 4 Unit
Values at load %
R.1 Condensing pressure bar
R.2 Condensing temp. °C
R.3 Liquid temp. °C
R.4 Subcooling K
R.5 Discharge temperature °C
R.6 Suction pressure bar
R.7 Evaporation temp. °C
R.8 Suction gas temp. °C
R.9 Superheating K
R.10 Safety valve bar
R.11 Tested HP switch point bar
R.12 Tested LP switch point bar
Page 2 of 6
114
EW. aporator in cooling
Eva c mod
de Serial Nr. unit: Daate:
Type: Serial number of evaporator:
e
Medium G
Glycol %/ °C
C Glyco
ol type: Water
W
Measu
ured unit Measu
ured values
Values at full loa
ad (100%) Circcuit 1 Cirrcuit 2 Circuit 3 C
Circuit 4 Unit
EW.1 Med
dium inlet temperature °C
EW.2 Med
dium outlet temperature °C
EW.3 ǻT K
EW.4 Inle
et water pressure bar
EW.5 Outtlet water pre
essure bar
EW.6 ǻp bar
EW.7 GEA
A GLPE ava
ailable yes no by others
EW.8 mp module tyype
Pum Serrial Nr.
EW.9 Bufffer tank avaiilable / size Liter Single
S circuit Dual circuit tank
tank
k
EW.10 Stra
ainer availab
ble yes no Cle
eaned yess no
o
EW.11 Flow
w switch ava
ailable yes no Fun
nction okk no
ot ok
EW.12 Pre
essure gauge
e available yes no
EW.13 Shu
ut off valves available yes no
pansion tankk available
EW.14 Exp yes no
EW.15 Saffety valve ava
ailable yes no essure
Pre bar
EW.16 Currrent consum
mption of pum
mps L1 L2 L3
EW.17 Wa
ater pump 1 A
EW.18 Wa
ater pump 2 A
EW.19 Typ
pe of water pump
p 1 Serrial Nr.
EW.20 Typ
pe of water pump
p 2 Serrial Nr.
Notes
R1 mm
R2 mm
R3 mm
R4 mm
Page 3 of 6
115
CW. Condenser in cooling mode Serial Nr. unit: Date:
Type: Serial number:
Measured unit Measured values
Circuit 1 Circuit 2 Circuit 3 Circuit 4 Unit
CW.1 Medium inlet temperature °C
CW.2 Medium outlet temperature °C
CW.3 ǻT: K
CW.4 Inlet water pressure bar
CW.5 Outlet water pressure bar
CW.6 ǻp bar
CW.7 Difference R.3 to CW.2 K
CW.8 GEA GLPC available yes no by others
CW.9 Type of hydraulic module: Serial Nr.:
CW.10 Strainer available yes no Cleaned: yes no
CW.11 Flow switch available yes no Function: O.K. Not O.K.
CW.12 Pressure gauge available yes no
CW.13 Shut off valves available yes no
CW.14 Expansion tank available yes no
CW.15 Safety valve available yes no Press. bar
CW.16 Current consumption of pumps L1 L2 L3
CW.17 Cool water pump 1 A
CW.18 Cool water pump 2 A
CW.19 Type of cool water pump 1 Serial Nr.
CW.20 Type of cool water pump 2 Serial Nr.
CW.21 3-way valve available yes no GEA by others
CW.22 Regulation of 3-way valve yes no GEA by others
Notes
Page 4 of 6
116
C. Controller and Settings Serial Nr. unit: Date
Used controller Software version
Set parameters Comment
Page 5 of 6
117
G Check / visual inspection Serial Nr. unit: Date
o. k. Not O.K. Comment / action required
G.1 Compressor
G.2 Condenser
G.3 Evaporator
G.3 Fans
Check for secured position, debris, damage
G.3.1
and corrosion.
G.3.2 Check for unbalanced impeller
Page 6 of 6
118
Measuring Report GLWH Chiller / Heat Pump
Service engineer Cost Date
GEA Order Nr. Service-Nr.
GEA Order No (bottom of unit type plate)
Plant operator
Contact person Tel.
Address Fax.
Postal code / City E-Mail
Plant manufacturer
Contact person Tel.
Address Fax.
Postal code / City E-Mail
Vers.02/2012-1 by TK
Page 1 of 7
119
R. Refrigeration circuit Serial Nr. unit: Date:
Measured unit Measured values
Refrigeration circuit 1 2 3 4 Unit
Values at load %
R.1 Condensing pressure bar
R.2 Condensing temp. °C
R.3 Liquid temp. °C
R.4 Subcooling K
R.5 Discharge temperature °C
R.6 Suction pressure bar
R.7 Evaporation temp. °C
R.8 Suction gas temp. °C
R.9 Superheating K
R.10 Safety valve bar
R.11 Tested HP switch point bar
R.12 Tested LP switch point bar
Page 2 of 7
120
EW. aporator in cooling
Eva c mod
de Serial Nr. unit: Daate:
Type: Serial number of evaporator:
e
Medium G
Glycol %/ °C
C Glyco
ol type: Water
W
Measu
ured unit Measu
ured values
Values at full loa
ad (100%) Circcuit 1 Cirrcuit 2 Circuit 3 C
Circuit 4 Unit
EW.1 Med
dium inlet temperature °C
EW.2 Med
dium outlet temperature °C
EW.3 ǻT K
EW.4 Inle
et water pressure bar
EW.5 Outtlet water pre
essure bar
EW.6 ǻp bar
EW.7 GEA
A GLPE ava
ailable yes no by others
EW.8 mp module tyype
Pum Serrial Nr.
EW.9 Bufffer tank avaiilable / size Liter Single
S circ. ta
ank Dual circuit tank
EW.10 Stra
ainer availab
ble yes no Cle
eaned yess no
o
EW.11 Flow
w switch ava
ailable yes no Fun
nction okk no
ot ok
EW.12 Pre
essure gauge
e available yes no
EW.13 Shu
ut off valves available yes no
EW.14 Exp
pansion tankk available yes no
EW.15 Saffety valve ava
ailable yes no essure
Pre bar
EW.16 Currrent consum
mption of pum
mps L1 L2 L3
EW.17 Wa
ater pump 1 A
EW.18 Wa
ater pump 2 A
EW.19 Typ
pe of water pump
p 1 Serrial Nr.
EW.20 Typ
pe of water pump
p 2 Serrial Nr.
Notes
R1 mm
R2 mm
R3 mm
R4 mm
Page 3 of 7
121
CW. Condenser in cooling mode Serial Nr. unit: Date:
Type: Serial number:
Measured unit Measured values
Circuit 1 Circuit 2 Circuit 3 Circuit 4 Unit
CW.1 Medium inlet temperature °C
CW.2 Medium outlet temperature °C
CW.3 ǻT: K
CW.4 Inlet water pressure bar
CW.5 Outlet water pressure bar
CW.6 ǻp bar
CW.7 Difference R.3 to CW.2 K
CW.8 GEA GLPC available yes no by others
CW.9 Type of hydraulic module: Serial Nr.:
CW.10 Strainer available yes no Cleaned: yes no
CW.11 Flow switch available yes no Function: O.K. Not O.K.
CW.12 Pressure gauge available yes no
CW.13 Shut off valves available yes no
CW.14 Expansion tank available yes no
CW.15 Safety valve available yes no Press. bar
CW.16 Current consumption of pumps L1 L2 L3
CW.17 Cool water pump 1 A
CW.18 Cool water pump 2 A
CW.19 Type of cool water pump 1 Serial Nr.
CW.20 Type of cool water pump 2 Serial Nr.
CW.21 3-way valve available yes no GEA by others
CW.22 Regulation of 3-way valve yes no GEA by others
Notes
Page 4 of 7
122
R. Circuit in heating mode Serial Nr.: Date:
Measured unit Measured values
Refrigeration circuit 1 2 3 4 Unit
Values under load %
R.28 Condensation pressure: bar
R.29 Condensing temperature: °C
R.30 Fluid temperature: °C
R.31 Subcooling (Bubble Point): K
R.32 Discharge temperature °C
R.33 Suction pressure: bar
R.34 Evaporating temperature: °C
R.35 Suction gas temperature: °C
R.36 Overheating (dew point): K
Page 5 of 7
123
C. Controller and Settings Serial Nr. unit: Date
Used controller Software version
Set parameters Comment
Page 6 of 7
124
G Check / visual inspection Serial Nr. unit: Date
o. k. Not O.K. Comment / action required
G.1 Compressor
G.2 Condenser
G.3 Evaporator
G.3 Fans
Check for secured position, debris, damage
G.3.1
and corrosion.
G.3.2 Check for unbalanced impeller
Page 7 of 7
125
Chillers and Heat Pumps
Appendix GL Series
English German
Air inlet Luft Eintritt
Air outlet Luft Austritt
Anti vibration mounts Gummischwingungsdämpfer
ATTN: Use N° X Lifting ropes with equal length only Achtung: Verwenden Sie X Trageseile mit gleicher Länge
Centre of Gravity Gewichtsschwerpunkt
Compressor Verdichter
Condenser connections Anschluss Verflüssiger
Condenser water inlet Verflüssiger Eintritt
Condenser water outlet Verflüssiger Austritt
Condensing side Verflüssigerseite
Connection Verbindung
Desuperheater connection(s) Anschluss Enthitzer
Desuperheater water inlet Enthitzer Wassereintritt
Desuperheater water outlet Enthitzer Wasseraustritt
Discharge line connection Anschluss Heißgasleitung
Electrical board side Schaltschrankseite
Evaporator Verdampfer
Evaporator (water) inlet Verdampfer (Wasser) Eintritt
Evaporator (water) outlet Verdampfer (Wasser) Austritt
Evaporator side Verdampferseite
Flanged connection Flansch Anschluss
Groovelock connection Victaulic Anschluss
H.P. relief valve Sicherheitsventil Hochdruckseite
High pressure head Verstärkte Förderhöhe der Pumpe
L.P. relief valve Sicherheitsventil Niederdruckseite
Lifting Hebepunkte / Transport
Lifting holes Hebepunkte
Liquid line connection Anschluss Flüssigkeitsleitung
Low pressure head Standard Förderhöhe der Pumpe
Main isolator (handle) Hauptschalter
minimum clearance minimale Freifläche
N° X Holes X Bohrungen insgesamt
Only for nur für
Only for shipping nur für den Transport
Optional Option / Zubehör
Optional evaporator (water) inlet optionaler Verdampfer (Wasser) Eintritt
Optional evaporator (water) outlet optionaler Verdampfer (Wasser) Austritt
Optional external water connection außenliegende Wasseranschlüsse (optional)
Optional flanged connections Flansch Anschluss (optional)
Optional groovelock connection Victaulic Anschluss (optional)
Pallet Palette
Power Inlet Spannungsversorgung Eingang
Tab. 15-1
English German
Power Inlet (Hole pre-cut) Spannungsversorgung Eingang (Loch vorgestanzt)
Removable abnehmbar
Removable lifting brackets abnehmbare Hebehalterungen
Shipping weight Transportgewicht
Size/Version Größe/Version
Suction line connection Anschluss Sauggasleitung
Supplied loose only for evap. lose geliefert - nur für Verdampfer
Supporting Basement Grundrahmen / Aufstellungsfläche
Total gesamt
Type Typ
User water inlet Wasser für Verbraucher-/Gebäudeseite Eintritt
User water outlet Wasser für Verbraucher-/Gebäudeseite Austritt
Version Ausführung
View table beachte Tabelle
Weight distribution Gewichtsverteilung
Weight for unit with Copper/Copper coils Gewichte für Geräte mit Cu/Cu Verflüssiger
Well/Tower water inlet Brunnenwasser/Rückkühlerwasser Eintritt
Well/Tower water outlet Brunnenwasser/Rückkühlerwasser Austritt
with mit
without ohne
Working weight for unit with copper/copper finned coils Betriebsgewicht für Geräte mit Cu/Cu Verflüssigern
Tab. 15-1
Tab. 15-2
Tab. 15-2
Tab. 15-2
English German
Black Schwarz
Blue Blau
Brown Braun
Tab. 15-3
English German
Circuit Kreislauf
Coil electrical heater Elektrische Heizung Wärmetauscher
Compr. Verdichter
Condenser circuit Kreislauf Verflüssiger
Connection Delta Anschluss Dreieckschaltung
Connection Star Anschluss Sternschaltung
Description Beschreibung
Discharge temp. compr. Heißgastemperaturfühler Verdichter
EV driver Treiber für elektronisches Expansionsventil
Evap. inlet probe Temperaturfühler Verdampfer Eintritt
Evap. outlet probe Temperaturfühler Verdampfer Austritt
Evaporator circuit Kreislauf Verdampfer
Fault vent. circuit Fehler Lüfter Kreislauf
Field card Interne Kommunikationskarte (Feldkarte)
For Remote start unit Externer Betriebsfreigabekontakt
General fault Allgemeine Störmeldung
Green Grün
H2O valve Wasserventil
High pressure circuit Druckaufnehmer / Druckschalter Hochdruck
Identifying symbol of device Eindeutige Bezeichnung des Bauteils
Low pressure circuit Druckaufnehmer / Druckschalter Niederdruck
Modulating valve two or three way Modulierendes 2 oder 3-Wege Ventil
One pump Eine Pumpe
Only for tank Nur für den Pufferspeicher
Operating Compr. Betriebsmeldung Verdichter
OPT. 1 Pump Option mit 1 Pumpe
OPT. 2 Pumps Option mit 2 Pumpe
Optional Zubehör
Piping anti freeze heater Rohrbegleitheizung
Remote set point Externe Sollwertverschiebung
Reversing valve 4-Wege Ventil
Secondary set (point) 2. Sollwert
Sequence phase relay Phasenfolgerelais
Standard Standard
Standard without pump Standard ohne Pumpe
Start rely pump Pumpenstartrelais
Summer / Winter (remote) Umschaltung Heizen / Kühlen
Thermal Compr. Motorvollschutz Verdichter
Two pumps Zwei Pumpen
Unit Gerät
Ventilation circuit Lüfter Kreislauf
White Weiß
Yellow Gelb
Tab. 15-3
Tab. 15-4
Tab. 15-4
English German
Chiller Betrieb Kaltwassererzeuger
Discharge to refrigerant system Austritt Gerät zum externen Kältekreislauf
H2O Wasser
Heat pump Betrieb Wärmepumpe
In Eintritt
Legend Legende
Off Aus
On Ein
Out Austritt
Return from refrigerant system Eintritt Gerät vom externen Kältekreislauf
Tab. 15-5
Tab. 15-6
Tab. 15-6
English German
Discharge to hydraulic system Wasseraustritt Gerät
Legend Legende
Only with 2 pumps nur bei 2 Pumpen
Optional 2 pumps circuit Optional: Kreislauf mit 2 Pumpen
Return from hydraulic system Wassereintritt Gerät
Tube Rohrbündelwärmetauscher
Tab. 15-7
System Data
Producer Refrigerant
Type Refrigerant charge kg
Serial number Oil type
Year of manufacture Oil charge volume kg
Type of system Chiller Heat pump Comp./condenser unit
Max. allowed pressure High pressure side bar Low pressure side bar
Power supply V/Ph/Hz Max. current A
Leak test without leakage detection system Once a year from 3 kg refrigerant charge weight
Twice a year at 30 to 299 kg refrigerant charge
4 times a year from 300 kg refrigerant charge
Plant operator
Contact person Tel.
Address Fax.
Postal code / City E-Mail
Service company
Contact person Tel.
Address Fax.
Postal code / City E-Mail
Certification number
Date of commissioning
Commissioning by Service technician Certificate Nr.:
Service through Service technician Certificate Nr.:
Service through Service technician Certificate Nr.:
Service through Service technician Certificate Nr.:
Notes
Vers. 08/2010-1 by TK
134
Date / Visit Nr. Company: Certificate Nr.:
/ Service technician: Certificate Nr.:
Leak testing yes / Result:
Refrigerant charged yes / Reason:
Refrigerant evacuated yes / Reason:
Leak system test yes / Result:
Repairs
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
135
Date / Visit Nr. Company: Certificate Nr.:
/ Service technician: Certificate Nr.:
Leak testing yes / Result:
Refrigerant charged yes / Reason:
Refrigerant evacuated yes / Reason:
Leak system test yes / Result:
Repairs
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
136
Date / Visit Nr. Company: Certificate Nr.:
/ Service technician: Certificate Nr.:
Leak testing yes / Result:
Refrigerant charged yes / Reason:
Refrigerant evacuated yes / Reason:
Leak system test yes / Result:
Repairs
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
137
Date / Visit Nr. Company: Certificate Nr.:
/ Service technician: Certificate Nr.:
Leak testing yes / Result:
Refrigerant charged yes / Reason:
Refrigerant evacuated yes / Reason:
Leak system test yes / Result:
Repairs
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
138
Date / Visit Nr. Company: Certificate Nr.:
/ Service technician: Certificate Nr.:
Leak testing yes / Result:
Refrigerant charged yes / Reason:
Refrigerant evacuated yes / Reason:
Leak system test yes / Result:
Repairs
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
139
Date / Visit Nr. Company: Certificate Nr.:
/ Service technician: Certificate Nr.:
Leak testing yes / Result:
Refrigerant charged yes / Reason:
Refrigerant evacuated yes / Reason:
Leak system test yes / Result:
Repairs
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
140
Date / Visit Nr. Company: Certificate Nr.:
/ Service technician: Certificate Nr.:
Leak testing yes / Result:
Refrigerant charged yes / Reason:
Refrigerant evacuated yes / Reason:
Leak system test yes / Result:
Repairs
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
141
Date / Visit Nr. Company: Certificate Nr.:
/ Service technician: Certificate Nr.:
Leak testing yes / Result:
Refrigerant charged yes / Reason:
Refrigerant evacuated yes / Reason:
Leak system test yes / Result:
Repairs
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
142
Date / Visit Nr. Company: Certificate Nr.:
/ Service technician: Certificate Nr.:
Leak testing yes / Result:
Refrigerant charged yes / Reason:
Refrigerant evacuated yes / Reason:
Leak system test yes / Result:
Repairs
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
Required measures
Units leak tested, safety devices checked and function test passed.
Name Signature
143
We live our values.
Excellence r Passion r Integrity r Responsibility r)'#XGTUKV[
GEA Group is a global engineering company with multi-billion euro sales and operations in more than
|EQWPVTKGU(QWPFGFKPVJGEQORCP[KUQPGQHVJGNCTIGUVRTQXKFGTUQHKPPQXCVKXGGSWKROGPVCPF
process technology. GEA Group is listed in the STOXX® Europe 600 Index.
www.gea-airtreatment.com