STULZ CyberAir DX Engineering Manual
STULZ CyberAir DX Engineering Manual
STULZ CyberAir DX Engineering Manual
Engineering Manual
Perimeter Mounted Precision Air Conditioners
21 kW - 105 kW / 60 Hz
CY B E R A I R ® DX E N G I N E E R I N G M A N UA L
ABOUT STULZ
Since it was founded in 1947, the STULZ company has
evolved into one of the world’s leading system suppliers of
computer room air conditioners and air handlers.
STULZ has seen continual international expansion of its
precision cooling business, specialising in temperature and
humidity control for data centers and telecommunications
installations.
STULZ has ten production plants (2 in Germany, 2 in the USA,
Italy, Great Britain, Spain, 2 in China, Brazil and India) and
twenty subsidiaries (in Germany, USA, France, Italy, Great
Britain, Belgium, Brazil, the Netherlands, New Zealand, Mexico,
Austria, Poland, Spain, Singapore, China, India, Indonesia,
South Africa, Sweden, and Australia).
STULZ works with sales and service partners in over 140
other countries, and therefore boasts an international network
of cooling specialists.
This document contains information protected by copyright. All rights are reserved. The owner
of the equipment for which this manual is written may photocopy the contents of this manual for
internal use only. No part of this document may be photocopied, reproduced, or translated into
another language for use by anyone other than the owner of the equipment for which this manual is
written without the prior written consent of STULZ Air Technology Systems, Inc.
This document contains confidential and proprietary information of STULZ Air Technology Systems,
Inc. Distributing or photocopying this document for external distribution is in direct violation of U.S.
copyright laws and is strictly prohibited without the express written consent of STULZ.
Unpublished rights reserved under the copyright laws of the United States and of other countries.
Other brands and trade names are trademarks of their respective owners.
4
Model Nomenclature
CFX-XXX-XXX-X-XX
Additional
Air Capacity Cooling Number of Heat Secondary Fan
Model Special
Pattern (kW) Method Circuits Rejection Cooling Options Location
Options
021
D = Downflow 0 = None 0 = Standard
028 A = Air
CyberAir 035
Floor 2 = Dual F = Water-Side
U = Upflow 042 D = DX G = Glycol Economizer I = In Unit T = Tandem
Mounted 053 Circuit Compressors
Solution R = Rear 070 W= Water W= Alternate
Return 088 Water Source S = Special
105
CF D 105 D 2 W 0 I 0
Example:105 kW Capacity, Dual Circuit, Water Cooled, Direct Expansion, Downflow, Floor Mounted System; with
Internal EC Fans, and No Additional Options: CFD-105-D2W-0-I0
5
Selected Features
Downflow / Upflow Models 021 - 105
Temperature Control
Optional
Evaporator Side Feed Hot Gas Bypass
(not available on models with Tandem Compressors)
6
Electronic Expansion Valves Standard
Refrigerant Sight Glass & Filter/ Drier Strainer Standard
Blowers / Motors
Backward Inclined, Plenum Style Fan, with an EC Motor
Standard
and high efficient composite impeller
Electrical
3-Phase Power Supply See Electrical Table
Multi-Voltage Control Transformer (24V Class 2) Standard
Modular Motor Controllers with Integral Circuit Breakers Standard
Safety Features
Audible/ Visual Local & Remote Alarms Standard
Main Power Circuit Breaker Unit Mounted Standard
High/ Low Refrigerant Pressure Switches Standard
Motor Overload Protection Standard
Specific Model Standard Features:
Air Cooled
Remote Outdoor, Air Cooled Condenser rated for -20°F to
95°F Ambient Standard
Low Ambient Control to -30°F and High Ambient to 105°F Optional
Water / Glycol Cooled
2-Way, 600 psig Water / Glycol Regulating Valves Standard
3-Way, 600 psig Water / Glycol Regulating Valves Optional
Free Cooling / Alternate Water Source Systems
2-Way, 600 psig Water/Glycol Control Valve Standard (AWS)
3-Way, 400 (042-105 kW systems) or 600( 021-035 kW
Standard (FC); Optional (AWS)
systems) psig Water/Glycol Control Valve
Code Conformance
NRTL Conformance Compliance to UL 1995 Standard Standard
7
Performance / Capacity Data
Air Cooled Systems – Downflow / Upflow Models 021 – 042
Hot Gas Line, in. OD (2 per Unit) 5/8 5/8 5/8 5/8 5/8 5/8 7/8 7/8
Liquid Line, in. OD (2 per Unit) 1/2 1/2 1/2 1/2 1/2 1/2 5/8 5/8
AWS In & Out, OD in. 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 2 1/8 2 1/8
Condensate Drain without Pump, OD in. 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8
Condensate Drain with Pump, OD in. 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2
Humidifier Inlet, OD in. 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4
Hot Water Reheat In & Out, OD in. 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8
Physical Data
Approximate Unit Weight, lbs 1,750 1,950 1,750 1,950 1,750 1,950 2,200 2,400
Approximate Shipping Weight, lbs 1,850 2,050 1,850 2,050 1,850 2,050 2,350 2,550
88.1 x 77.4 x 40.3 88.1x 77.4 x 40.3 88.1 x 77.4 x 40.3 88.1 x 88.2 x 40.3
(91.1 x 77.4 x 40.3 (91.1x 77.4 x 40.3 (91.1 x 77.4 x 40.3 (91.1 x 88.2 x 40.3
Unit Dimensions, H in. x W in. x D in. 76.2 x 77.4 x 40.3 w/ Hot Gas/Water 76.2 x 77.4 x 40.3 w/ Hot Gas/Water 76.2 x 77.4 x 40.3 w/ Hot Gas/Water 76.2 x 89.1 x 40.3 w/ Hot Gas/Water
Reheat) Reheat) (Reheat) Reheat)
95.0 x 80.0 x 46.0 95.0 x 80.0 x 46.0 95.0 x 80.0 x 46.0 95.0 x 95.0 x 46.0
(98.0 x 80.0 x 46.0 (98.0 x 80.0 x 46.0 (98.0 x 80.0 x 46.0 (98.0 x 95.0 x 46.0
Shipping Dimensions, H in. x W in. x D in. 83.0 x 80.0 x 46.0 w/ Hot Gas/Water 83.0 x 80.0 x 46.0 w/ Hot Gas/Water 83.0 x 80.0 x 46.0 w/ Hot Gas/Water 83.0 x 95.0 x 46.0 w/ Hot Gas/Water
Reheat) Reheat) Reheat) Reheat)
8
Performance / Capacity Data
Air Cooled Systems – Downflow / Upflow Models 053 – 105
Models CFD-053-D2A CFU-053-D2A CFD-070-D2A CFU-070-D2A CFD-088-D2A CFU-088-D2A CFD-105-D2A CFU-105-D2A
Evaporator Blower / Motor - Backward Inclined Direct Driven EC
Nominal Horsepower per Blower, hp 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7
Rated Air Flow, CFM @ 0.2 in. H2O ESP 9,000 9,000 10,000 10,000 15,750 15,750 15,750 15,750
Quantity of Blowers 2 2 2 2 3 3 3 3
Evaporator Coil - Aluminum Fin, Copper Tube
Direct Expansion (DX) Coil
Rows (Face Area, ft2) 3 (24.7) 3 (24.7) 3 (24.7) 3 (24.7) 3 (39.8) 3 (39.8) 3 (39.8) 3 (39.8)
Face Velocity, fpm 364 364 404 404 395 395 395 395
Alternate Water Source (AWS) Coil
Coil Rows (Face Area, ft2) 4 (24.7) 4 (24.7) 4 (24.7) 4 (24.7) 4 (39.8) 4 (39.8) 4 (39.8) 4 (39.8)
Face Velocity, fpm 364 364 404 404 395 395 395 395
CV (AWS valve, 3-way 400 PSI) 20 20 20 20 28 28 28 28
Compressors - R-410A
Type (Qty) Scroll (2) Scroll (2) Scroll (2) Scroll (2) Scroll (2) Scroll (2) Scroll (2) Scroll (2)
Input per Compressor, W 7,900 7,900 10,390 10,390 13,320 13,320 15,640 15,640
Total Heat of Rejection, kW (MBH) 73.7 (252) 73.7 (252) 92.7 (317) 92.7 (317) 125.7 (429) 125.7 (429) 139.8 (477) 139.8 (477)
Reheat - Performance Capacities Do Not Include Evaporator Motor Heat @ Rated CFM & ESP
Electric Reheat - Finned Tubular
Number of Stages 2 2 2 2 3 3 3 3
Total Nominal Capacity, kW (MBH) 18.0 (61) 18.0 (61) 18.0 (61) 18.0 (61) 27.0 (92) 27.0 (92) 27.0 (92) 27.0 (92)
Hot Gas Reheat - with 3-Way Heat Reclaim Valve
Total Capacity, kW (MBH) 7.9 (26) 7.9 (26) 10.3 (35) 10.3 (35) 13.3 (45) 13.3 (45) 15.6 (53) 15.6 (53)
Hot Water Reheat - Rated at 180°F EWT / 160°F LWT & 72°FDB/60.0°FWB EAT
Total Capacity, kW (MBH) 25.5 (87) 31.1 (106) 26.6 (91) 32.2 (110) 45 (153) 56.1 (191) 45 (153) 56.1 (191)
Flow Rate, GPM / (Pressure Drop, ft H2O) 9 / (6) 11 / (9) 10 / (6) 12 / (9) 16 / (18) 20 / (27) 16 / (18) 20 / (27)
Control Valve Modulating Modulating Modulating Modulating Modulating Modulating Modulating Modulating
Steam Reheat - Rated at 5 psig & 72°FDB EAT
Total Capacity, kW (MBH) 62.8 (214) 84.7 (289) 66.8 (228) 89.1 (304) 105.2 (359) 146.8 (501) 105.2 (359) 146.8 (501)
Condensate, lbs/hr 223 301 237 316 374 521 374 521
Control Valve Modulating Modulating Modulating Modulating Modulating Modulating Modulating Modulating
Humidification - Electrode Steam Canister with Adjustable Output
Steam Output, lbs/hr (Power Input, kW) 4-15 (5.1) 4-15 (5.1) 4-15 (5.1) 4-15 (5.1) 4-25 (8.5) 4-25 (8.5) 4-25 (8.5) 4-25 (8.5)
Control Type Modulating Modulating Modulating Modulating Modulating Modulating Modulating Modulating
Filters - Disposable, MERV 8 Average Dust Spot Efficiency (Standard), MERV 11 Average Dust Spot Efficiency (Optional)
35.9 x 24.8 x 3.8 35.9 x 24.8 x 3.8 35.9 x 24.8 x 3.8 35.9 x 24.8 x 3.8
37.0 x 21.0 x 3.8 (2) 37.0 x 21.0 x 3.8 (2) 37.0 x 18.5 x 3.8 (3) 37.0 x 18.5 x 3.8 (3)
Actual Size, H in. x W in. x D in. (Qty) 24.8 x 21.0 x 3.8 24.8 x 21.0 x 3.8 24.8 x 21.0 x 3.8 24.8 x 21.0 x 3.8
(3) (3) (5) (5)
(1) (1) (2) (2)
Connection Sizes - Copper
Hot Gas Line, in. OD (2 per Unit) 7/8 7/8 7/8 7/8 1 3/8 1 3/8 1 3/8 1 3/8
Liquid Line, in. OD (2 per Unit) 5/8 5/8 5/8 5/8 7/8 7/8 7/8 7/8
AWS In & Out, OD in. 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8
Condensate Drain without Pump, OD in. 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8
Condensate Drain with Pump, OD in. 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2
Humidifier Inlet, OD in. 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4
Hot Water Reheat In & Out, OD in. 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8
Physical Data
Approximate Unit Weight, lbs 2,200 2,400 2,200 2,400 2,900 3,100 2,900 3,100
Approximate Shipping Weight, lbs 2,350 2,550 2,350 2,550 3,100 3,300 3,100 3,300
88.1 x 88.2 x 40.3 88.1 x 88.2 x 40.3 88.1 x 118.4 x 40.3 88.1 x 118.4 x 40.3
(91.1 x 88.2 x 40.3 (91.1 x 88.2 x 40.3 76.02 x 118.4 (91.1 x 118.4 x (91.1 x 118.4 x
Unit Dimensions, H in. x W in. x D in. 76.2 x 89.1 x 40.3 76.0 x 87.3 x 38.4 76.2 x 118.4 x 40.3
w/ Hot Gas/Water w/ Hot Gas/Water x 40.3 40.3 w/ Hot Gas/ 40.3 w/ Hot Gas/
Reheat) Reheat) Water Reheat) Water Reheat)
95 x 95 x 46 95 x 95 x 46 95 x 124 x 46 95 x 124 x 46
Shipping Dimensions, H in. x W in. x D in. (98 x 95 x 46 w/ (98 x 95 x 46 w/ (98 x 124 x 46 w/ (98 x 124 x 46 w/
83 x 95 x 46 Hot Gas/Water 83 x 95 x 46 Hot Gas/Water 83 x 124 x 46 Hot Gas/Water 83 x 124 x 46 Hot Gas/Water
Reheat) Reheat) Reheat) Reheat)
9
Performance / Capacity Data
Water Cooled Systems – Downflow / Upflow Models 021 – 042
Models: CFD-021-D2W CFU-021-D2W CFD-028-D2W CFU-028-D2W CFD-035-D2W CFU-035-D2W CFD-042-D2W CFU-042-D2W
Evaporator Blower / Motor - Backward Inclined Direct Driven EC
Nominal Horsepower per Blower, hp 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7
Rated Air Flow, CFM @ .3 in. H2O ESP 6,000 6,000 6,000 6,000 6,000 6,000 8,000 8,000
Quantity of Blowers 1 1 1 1 1 1 2 2
Evaporator Coil - Aluminum Fin, Copper Tube
Direct Expansion (DX) Coil
Rows (Face Area, ft2) 2 (21.6) 2 (21.6) 2 (21.6) 2 (21.6) 2 (21.6) 2 (21.6) 3 (24.7) 3 (24.7)
Face Velocity, fpm 278 278 278 278 278 278 323 323
Free Cooling (FC) Water Economizer / Alternate Water Source (AWS) Coil (Optional)
Coil Rows (Face Area, ft2) 4 (21.6) 4 (21.6) 4 (21.6) 4 (21.6) 4 (21.6) 4 (21.6) 4 (24.7) 4 (24.7)
Face Velocity, fpm 278 278 278 278 278 278 323 323
CV (FC Valve, 3-way, 400 PSI) 16 16 16 16 20 20 20 20
CV (AWS valve, 3-way, 400 PSI) 11 11 11 11 11 11 20 20
Compressors - R-410A
Type (Qty) Scroll (2) Scroll (2) Scroll (2) Scroll (2) Scroll (2) Scroll (2) Scroll (2) Scroll (2)
Input per Compressor, W 2,970 2,970 3,630 3,630 4,250 4,250 4,660 4,660
Water Cooled Condensers - Micro-Plate (Based on 0% Glycol Solution)
Total Heat of Rejection, kW (MBH) 39.1 (134) 39.1 (134) 45.1 (154) 45.1 (154) 49.9 (170) 49.9 (170) 60.1 (206) 60.1 (206)
Flow Rate, GPM @ 85°F EWT / 95°F LWT 27 27 31 31 35 35 42 42
Unit Pressure Drop, ft H2O 15 15 18 18 21 21 15 15
Reheat - Performance Capacities DO NOT Include Evaporator Motor Heat @ Rated CFM & ESP
Electric Reheat - Finned Tubular
Number of Stages 1 1 1 1 1 1 2 2
Total Nominal Capacity, kW (MBH) 9.0 (30) 9.0 (30) 9.0 (30) 9.0 (30) 9.0 (30) 9.0 (30) 18.0 (61) 18.0 (61)
Hot Gas Reheat - with 3-Way Heat Reclaim Valve
Total Capacity, kW (MBH) 2.9 (10) 2.9 (10) 3.6 (12) 3.6 (12) 4.2 (14) 4.2 (14) 4.6 (15) 4.6 (15)
Hot Water Reheat - Rated at 180°F EWT / 160°F LWT & 72°FDB/60.0°FWB EAT
Total Capacity, kW (MBH) 19.4 (66) 23.8 (81) 19.4 (66) 23.8 (81) 19.4 (66) 23.8 (81) 24.2 (82) 29.8 (101)
Flow Rate, GPM (Pressure Drop, ft H2O) 7 (4) 9 (5) 7 (4) 9 (5) 7 (4) 9 (5) 9 (5) 11 (8)
Control Valve Modulating Modulating Modulating Modulating Modulating Modulating Modulating Modulating
Steam Reheat - Rated at 5 psig & 72°FDB EAT
Total Capacity, kW (MBH) 44.5 (152) 61.9 (211) 44.5 (152) 61.9 (211) 44.5 (152) 61.9 (211) 58.2 (198) 79.2 (270)
Condensate, lbs/hr 158 220 158 220 158 220 207 281
Control Valve Modulating Modulating Modulating Modulating Modulating Modulating Modulating Modulating
Humidification - Electrode Steam Canister with Adjustable Output
Steam Output, lbs/hr (Power Input, kW) 4-15 (5.1) 4-15 (5.1) 4-15 (5.1) 4-15 (5.1) 4-15 (5.1) 4-15 (5.1) 4-15 (5.1) 4-15 (5.1)
Standard Control Modulating Modulating Modulating Modulating Modulating Modulating Modulating Modulating
Filters - Disposable, MERV 8 Average Dust Spot Efficiency (Standard), MERV 11 Average Dust Spot Efficiency (Optional)
35.9 x 24.8 x 3.8 (1) 35.9 x 24.8 x 3.8 (1) 35.9 x 24.8 x 3.8 (1)
37.0 x 18.5 x 3.8 (3) 35.9 x 18.9 x 3.8 (1) 37.0 x 18.5 x 3.8 (3) 35.9 x 18.9 x 3.8 (1) 37.0 x 18.5 x 3.8 (3) 35.9 x 18.9 x 3.8 (1) 37.0 x 21.0 x 3.8 (3) 35.9 x 24.8 x 3.8 (2)
Actual Size, H in. x W in. x D in. (Qty)
21.0 x 18.9 x 3.8 (1) 21.0 x 18.9 x 3.8 (1) 21.0 x 18.9 x 3.8 (1) 24.8 x 21.0 x 3.8 (1)
Connection Sizes - Copper
Condenser In & Out, OD in. 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 2 1/8 2 1/8
AWS In & Out, OD in. 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 2 1/8 2 1/8
Condensate Drain without Pump, OD in. 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8
Condensate Drain with Pump, OD in. 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2
Humidifier Inlet, OD in. 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4
Hot Water Reheat In & Out, OD in. 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8
Physical Data
Approximate Unit Weight, lbs 1,800 2,000 1,800 2,000 1,800 2,000 2,300 2,500
Approximate Shipping Weight, lbs 1,900 2,100 1,900 2,100 1,900 2,100 2,450 2,650
88.1 x 77.4 x 40.3 88.1 x 77.4 x 40.3 88.1 x 77.4 x 40.3 88.1 x 88.2 x 40.3
(91.1 x 77.4 x 40.3 (91.1 x 77.4 x 40.3 (91.1 x 77.4 x 40.3 (91.1 x 88.2 x 40.3
Unit Dimensions, H in. x W in. x D in. 76.2 x 77.4 x 40.3 w/ Hot Gas/Water 76.2 x 77.4 x 40.3 w/ Hot Gas/Water 76.2 x 77.4 x 40.3 w/ Hot Gas/Water 76.2 x 89.1 x 40.3 w/ Hot Gas/Water
Reheat) Reheat) Reheat) Reheat
95.0 x 80.0 x 46.0 95.0 x 80.0 x 46.0 95.0 x 80.0 x 46.0 95.0 x 95.0 x 46.0
(98.0 x 80.0 x 46.0 (98.0 x 80.0 x 46.0 (98.0 x 80.0 x 46.0 (98.0 x 95.0 x 46.0
Shipping Dimensions, H in. x W in. x D in. 83.0 x 80.0 x 46.0 w/ Hot Gas/Water 83.0 x 80.0 x 46.0 w/ Hot Gas/Water 83.0 x 80.0 x 46.0 w/ Hot Gas/Water 83.0 x 95.0 x 46.0 w/ Hot Gas/Water
Reheat) Reheat) Reheat) Reheat)
10
Performance / Capacity Data
Water Cooled Systems – Downflow / Upflow Models 053 – 105
35.9 x 24.8 x 3.8 (2) 35.9 x 24.8 x 3.8 (2) 35.9 x 24.8 x 3.8 (3) 35.9 x 24.8 x 3.8 (3)
Actual Size, H in. x W in. x D in. (Qty) 37.0 x 21.0 x 3.8 (3)
24.8 x 21.0 x 3.8 (1) 37.0 x 21.0 x 3.8 (3) 24.8 x 21.0 x 3.8 (1) 37.0 x 18.5 x 3.8 (5) 24.8 x 21.0 x 3.8 (2) 37.0 x 18.5 x 3.8 (5) 24.8 x 21.0 x 3.8 (2)
11
Performance / Capacity Data
Glycol Cooled Systems – Downflow / Upflow Models 021 – 042
Models: CFD-021-D2G CFU-021-D2G CFD-028-D2G CFU-028-D2G CFD-035-D2G CFU-035-D2G CFD-042-D2G CFU-042-D2G
Evaporator Blower / Motor - Backward Inclined Direct Driven EC
Nominal Horsepower per Blower, hp 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7
Rated Air Flow, CFM @ .3 in. H2O ESP 6,000 6,000 6,000 6,000 6,000 6,000 8,000 8,000
Quantity of Blowers 1 1 1 1 1 1 2 2
Evaporator Coil - Aluminum Fin, Copper Tube
Direct Expansion (DX) Coil
Rows (Face Area, ft2) 2 (21.6) 2 (21.6) 2 (21.6) 2 (21.6) 2 (21.6) 2 (21.6) 3 (24.7) 3 (24.7)
Face Velocity, fpm 278 278 278 278 278 278 323 323
Free Cooling (FC) Glycol Economizer / Alternate Water Source (AWS) Coil
Coil Rows (Face Area, ft2) 4 (21.6) 4 (21.6) 4 (21.6) 4 (21.6) 4 (21.6) 4 (21.6) 4 (24.7) 4 (24.7)
Face Velocity, fpm 278 278 278 278 278 278 323 323
CV (FC Valve, 3-way, 400 PSI) 16 16 16 16 20 20 20 20
CV (AWS valve, 3-way, 400 PSI) 11 11 11 11 11 11 20 20
Compressors - R-410A
Type (Qty) Scroll (2) Scroll (2) Scroll (2) Scroll (2) Scroll (2) Scroll (2) Scroll (2) Scroll (2)
Input per Compressor, W 4,170 4,170 5,040 5,040 5,650 5,650 6,240 6,240
Glycol Cooled Condensers - Micro-Plate (Based on 40% Ethylene Glycol Solution)
Total Heat of Rejection, kW (MBH) 37.9 (129) 37.9 (129) 43.8 (150) 43.8 (150) 47.9 (164) 47.9 (164) 57.6 (197) 57.6 (197)
Flow Rate, GPM @ 110°F EGT / 120°F LGT 29 29 34 34 36 36 44 44
Unit Pressure Drop, ft H2O 17 17 21 21 24 24 16 16
Reheat / Heat - Performance Capacities DO NOT Include Evaporator Motor Heat @ Rated CFM & ESP
Electric Reheat - Finned Tubular
Number of Stages 1 1 1 1 1 1 2 2
Total Nominal Capacity, kW (MBH) 9.0 (30) 9.0 (30) 9.0 (30) 9.0 (30) 9.0 (30) 9.0 (30) 18.0 (61) 18.0 (61)
Hot Gas Reheat - with 3-Way Heat Reclaim Valve
Total Capacity, kW (MBH) 4.1 (14) 4.1 (14) 5.0 (17) 5.0 (17) 5.6 (19) 5.6 (19) 6.2 (21) 6.2 (21)
Hot Water Reheat - Rated at 180°F EWT / 160°F LWT & 72°FDB/60.0°FWB EAT
Total Capacity, kW (MBH) 19.4 (66) 23.8 (81) 19.4 (66) 23.8 (81) 19.4 (66) 23.8 (81) 24.2 (82) 29.8 (101)
Flow Rate, GPM (Pressure Drop, ft H2O) 7 (4) 9 (5) 7 (4) 9 (5) 7 (4) 9 (5) 9 (5) 11 (8)
Control Valve Modulating Modulating Modulating Modulating Modulating Modulating Modulating Modulating
Steam Reheat - Rated at 5 psig & 72°FDB EAT
Total Capacity, kW (MBH) 44.5 (152) 61.9 (211) 44.5 (152) 61.9 (211) 44.5 (152) 61.9 (211) 58.2 (198) 79.2 (270)
Condensate, lbs/hr 158 220 158 220 158 220 207 281
Control Valve Modulating Modulating Modulating Modulating Modulating Modulating Modulating Modulating
Humidification - Electrode Steam Canister with Adjustable Output
Steam Output, lbs/hr / (Power Input, kW) 4-15 / (5.1) 4-15 / (5.1) 4-15 / (5.1) 4-15 / (5.1) 4-15 / (5.1) 4-15 / (5.1) 4-15 / (5.1) 4-15 / (5.1)
Control Type Modulating Modulating Modulating Modulating Modulating Modulating Modulating Modulating
Filters - Disposable, MERV 8 Average Dust Spot Efficiency (Standard), MERV 11 Average Dust Spot Efficiency (Optional)
35.9 x 24.8 x 3.8 (1) 35.9 x 24.8 x 3.8 (1) 35.9 x 24.8 x 3.8 (1)
Actual Size, H in. x W in. x D in. (Qty) 35.9 x 24.8 x 3.8 (2)
37.0 x 18.5 x 3.8 (3) 35.9 x 18.9 x 3.8 (1) 37.0 x 18.5 x 3.8 (3) 35.9 x 18.9 x 3.8 (1) 37.0 x 18.5 x 3.8 (3) 35.9 x 18.9 x 3.8 (1) 37.0 x 21.0 x 3.8 (3)
21.0 x 18.9 x 3.8 (1) 21.0 x 18.9 x 3.8 (1) 21.0 x 18.9 x 3.8 (1) 24.8 x 21.0 x 3.8 (1)
Connection Sizes - Copper
Condenser In & Out, OD in. 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 2 1/8 2 1/8
AWS In & Out, OD in. 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 2 1/8 2 1/8
Condensate Drain without Pump, OD in. 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8
Condensate Drain with Pump, OD in. 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2
Humidifier Inlet, OD in. 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4
Hot Water Reheat In & Out, OD in. 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8
Physical Data
Approximate Unit Weight, lbs 1,800 2,000 1,800 2,000 1,800 2,000 2,300 2,500
Approximate Shipping Weight, lbs 1,900 2,100 1,900 2,100 1,900 2,100 2,450 2,650
88.1 x 77.4 x 40.3 88.1 x 77.4 x 40.3 88.1 x 77.4 x 40.3 88.1 x 89.1 x 40.3
76.2 x 77.4 x 40.3 76.2 x 77.4 x 40.3 76.2 x 77.4 x 40.3 76.0 x 89.1 x 38.4
(91.1 x 77.4 x 40.3 (91.1 x 77.4 x 40.3 (91.1 x 77.4 x 40.3 (91.1 x 89.1 x 40.3
Unit Dimensions, H in. x W in. x D in. w/ Hot Gas/Water w/ Hot Gas/Water w/ Hot Gas/Water w/ Hot Gas/Water
Reheat) Reheat) Reheat) Reheat)
95.0 x 80.0 x 46.0 95.0 x 80.0 x 46.0 95.0 x 80.0 x 46.0 95.0 x 95.0 x 46.0
Shipping Dimensions, H in. x W in. x D in. (98.0 x 80.0 x 46.0 (98.0 x 80.0 x 46.0 (98.0 x 80.0 x 46.0 (98.0 x 95.0 x 46.0
83.0 x 80.0 x 46.0 w/ Hot Gas/Water 83.0 x 80.0 x 46.0 w/ Hot Gas/Water 83.0 x 80.0 x 46.0 w/ Hot Gas/Water 83.0 x 95.0 x 46.0 w/ Hot Gas/Water
Reheat) Reheat) Reheat) Reheat)
12
Performance / Capacity Data
Glycol Cooled Systems – Downflow / Upflow Models 053 – 105
Models: CFD-053-D2G CFU-053-D2G CFD-070-D2G CFU-070-D2G CFD-088-D2G CFU-088-D2G CFD-105-D2G CFU-105-D2G
Evaporator Blower / Motor - Backward Inclined Direct Driven EC
Nominal Horsepower per Blower, hp 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7
Rated Air Flow, CFM @ .3 in. H2O ESP 9,000 9,000 10,000 10,000 15,750 15,750 15,750 15,750
Quantity of Blowers 2 2 2 2 3 3 3 3
Evaporator Coil - Aluminum Fin, Copper Tube
Direct Expansion (DX) Coil
Rows (Face Area, ft2) 3 (24.7) 3 (24.7) 3 (24.7) 3 (24.7) 3 (39.8) 3 (39.8) 3 (39.8) 3 (39.8)
Face Velocity, fpm 364 364 404 404 395 395 395 395
Free Cooling (FC) Glycol Economizer / Alternate Water Source (AWS) Coil
Coil Rows (Face Area, ft2) 4 (24.7) 4 (24.7) 4 (24.7) 4 (24.7) 4 (39.8) 4 (39.8) 4 (39.8) 4 (39.8)
Face Velocity, fpm 364 364 404 404 395 395 395 395
CV (FC Valve, 3-way, 400 PSI) 28 28 35.4 35.4 48 48 48 48
CV (AWS valve, 3-way, 400 PSI) 20 20 20 20 28 28 28 28
Compressors - R-410A
Type / (Qty) Scroll / (2) Scroll / (2) Scroll / (2) Scroll / (2) Scroll / (2) Scroll / (2) Scroll / (2) Scroll / (2)
Input per Compressor, W 8,370 8,370 11,070 11,070 14,090 14,090 16,600 16,600
Glycol Cooled Condensers - Micro-Plate (Based on 40% Ethylene Glycol Solution)
Total Heat of Rejection, kW (MBH) 73.2 (250) 73.2 (250) 92.4 (316) 92.4 (316) 124.7 (426) 124.7 (426) 138.8 (474) 138.8 (474)
Flow Rate, GPM @ 110°F EGT / 120°F LGT 56 56 70 70 95 95 105 105
Unit Pressure Drop, ft H2O 17 17 20 20 23 23 28 28
Reheat - Performance Capacities DO NOT Include Evaporator Motor Heat @ Rated CFM & ESP
Electric Reheat - Finned Tubular
Number of Stages 2 2 2 2 3 3 3 3
Total Nominal Capacity, kW (MBH) 18.0 (61) 18.0 (61) 18.0 (61) 18.0 (61) 27.0 (92) 27.0 (92) 27.0 (92) 27.0 (92)
Hot Gas Reheat - with 3-Way Heat Reclaim Valve
Total Capacity, kW (MBH) 8.3 (28) 8.3 (28) 11.0 (37) 11.0 (37) 14.0 (48) 14.0 (48) 16.6 (56) 16.6 (56)
Hot Water Reheat - Rated at 180°F EWT / 160°F LWT & 72°FDB/60.0°FWB EAT
Total Capacity, kW (MBH) 25.5 (87) 31.1 (106) 26.6 (91) 32.2 (110) 45 (153) 56.1 (191) 45 (153) 56.1 (191)
Flow Rate, GPM (Pressure Drop, ft H2O) 9 (6) 11 (9) 10 (6) 12 (9) 16 (18) 20 (27) 16 (18) 20 (27)
Control Valve Modulating Modulating Modulating Modulating Modulating Modulating Modulating Modulating
Steam Reheat - Rated at 5 psig & 72°FDB EAT
Total Capacity, kW (MBH) 62.8 (214) 84.7 (289) 66.8 (228) 89.1 (304) 105.2 (359) 146.8 (501) 105.2 (359) 146.8 (501)
Condensate, lbs/hr 223 301 237 316 374 521 374 521
Control Valve Modulating Modulating Modulating Modulating Modulating Modulating Modulating Modulating
35.9 x 24.8 x 3.8 (2) 35.9 x 24.8 x 3.8 (2) 35.9 x 24.8 x 3.8 (3) 35.9 x 24.8 x 3.8 (3)
Actual Size, H in. x W in. x D in. (Qty) 37.0 x 21.0 x 3.8 (3) 24.8 x 21.0 x 3.8 (1) 37.0 x 21.0 x 3.8 (3) 24.8 x 21.0 x 3.8 (1) 37.0 x 18.5 x 3.8 (5) 24.8 x 21.0 x 3.8 (2) 37.0 x 18.5 x 3.8 (5) 24.8 x 21.0 x 3.8 (2)
13
Performance / Capacity Data
Air Cooled Systems – Downflow / Upflow Models 021 – 105
Models: CFD/U- 021-D2A 028-D2A 035-D2A 042-D2A 053-D2A 070-D2A 088-D2A 105-D2A
NET DX COOLING CAPACITY - (Includes Motor Heat @ Rated CFM & ESP)
80°FDB/62.9°FWB, 38% RH, 52.3°FDP
Total, kW (MBH) 27.1 (92) 31.4 (107) 34.4 (117) 40.1 (136) 51.6 (176) 65.6 (224) 89.7 (306) 99.1 (338)
Sensible, kW (MBH) 27.1 (92) 31.4 (107) 34.4 (117) 40.1 (136) 51.6 (176) 64.1 (218) 89.7 (306) 99.1 (338)
72°FDB/60.0°FWB, 50% RH, 52.3°FDP
Total, kW (MBH) 24.0 (82) 28.5 (97) 31.8 (108) 35.1 (120) 46.4 (158) 62.1 (212) 80.9 (276) 92.4 (315)
Sensible, kW (MBH) 23.2 (79) 27.8 (95) 30.2 (103) 33.6 (114) 42.0 (143) 58.3 (199) 77.3 (263) 88.1 (300)
NET AWS COOLING CAPACITY - Based on 45°F EWT / 55°F LWT, 0% Glycol Solution (Includes Motor Heat @ Rated CFM & ESP)
14
Performance / Capacity Data
Water Cooled Systems – Downflow / Upflow Models 021 – 105
Models: CFD/U- 021-D2W 028-D2W 035-D2W 042-D2W 053-D2W 070-D2W 088-D2W 105-D2W
NET DX COOLING CAPACITY - (Includes Motor Heat @ Rated CFM & ESP) 80°FDB/62.9°FWB, 38% RH, 52.3°FDP
Total, kW (MBH) 29.9 (102) 34.7 (118) 38.1 (130) 44.5 (152) 56.8 (194) 74.1 (252) 98.9 (337) 110.4 (376)
Sensible, kW (MBH) 29.9 (102) 34.7 (118) 38.1 (130) 44.5 (152) 56.8 (194) 73.5 (250) 98.9 (337) 110.4 (376)
72°FDB/60.0°FWB, 50% RH, 52.3°FDP
Total, kW (MBH) 26.9 (91) 32.3 (110) 35.8 (122) 39.9 (136) 52.9 (180) 69.7 (237) 92.2 (314) 104.8 (357)
Sensible, kW (MBH) 26.9 (91) 30.5 (104) 30.4 (103) 39.0 (133) 50.2 (171) 54.1 (184) 87.9 (299) 93.1 (317)
NET FC COOLING CAPACITY - Based on 45°F EWT, 0% Glycol Solution (Includes Motor Heat @ Rated CFM & ESP)
80°FDB/62.9°FWB, 38% RH, 52.3°FDP
Total, kW (MBH) 39.9 (136) 41.6 (142) 43.0 (146) 52.5 (179) 59.3 (202) 66.1 (225) 102.9 (351) 104.9 (357)
Sensible, kW (MBH) 39.9 (136) 41.6 (142) 43.0 (146) 52.5 (179) 59.3 (202) 66.1 (225) 102.9 (351) 104.9 (357)
Flow Rate, GPM (Unit Press. Drop, ft H2O) 27 (26) 31 (33) 35 (36) 42 (34) 52 (35) 67 (46) 89 (46) 99 (56)
72°FDB/60.0°FWB, 50% RH, 52.3°FDP
Total, kW (MBH) 30.2 (103) 34.1 (116) 35.0 (119) 42.5 (145) 47.6 (162) 52.8 (180) 83.0 (283) 84.2 (287)
Sensible, kW (MBH) 30.2 (103) 32.5 (111) 33.2 (113) 40.6 (138) 46.0 (157) 51.4 (175) 80.7 (275) 81.7 (278)
Flow Rate, GPM (Unit Press. Drop, ft H2O) 27 (26) 31 (33) 35 (36) 42 (34) 52 (35) 67 (46) 89 (46) 99 (56)
NET AWS COOLING CAPACITY - Based on 45°F EWT / 55°F LWT, 0% Glycol Solution (Includes Motor Heat @ Rated CFM & ESP)
80°FDB/62.9°FWB, 38% RH, 52.3°FDP
Total, kW (MBH) 41.3 (141) 41.3 (141) 41.3 (141) 51.6 (176) 56.3 (192) 60.6 (207) 97.8 (333) 97.8 (333)
Sensible, kW (MBH) 41.3 (141) 41.3 (141) 41.3 (141) 51.6 (176) 56.3 (192) 60.6 (207) 97.8 (333) 97.8 (333)
Flow Rate, GPM (Unit Press. Drop, ft H2O) 31 (28) 31 (28) 31 (28) 40 (21) 43 (23) 46 (26) 74 (36) 74 (36)
72°FDB/60.0°FWB, 50% RH, 52.3°FDP
Total, kW (MBH) 27.2 (93) 27.2 (93) 27.2 (93) 33.7 (115) 36.9 (125) 39.8 (136) 64.2 (219) 64.2 (219)
Sensible, kW (MBH) 27.2 (93) 27.2 (93) 27.2 (93) 33.7 (115) 36.9 (125) 39.8 (136) 64.2 (219) 64.2 (219)
Flow Rate, GPM (Unit Press. Drop, ft H2O) 21 (15) 21 (15) 21 (15) 28 (13) 30 (14) 32 (15) 51 (20) 51 (20)
15
Performance / Capacity Data
Glycol Cooled Systems – Downflow / Upflow Models 021 – 105
Models: CFD/U- 021-D2G 028-D2G 035-D2G 042-D2G 053-D2G 070-D2G 088-D2G 105-D2G
NET DX COOLING CAPACITY - (Includes Motor Heat @ Rated CFM & ESP)
80°FDB/62.9°FWB, 38% RH, 52.3°FDP
Total, kW (MBH) 26.3 (89) 30.5 (104) 33.4 (114) 38.8 (132) 50.1 (171) 63.9 (218) 87.1 (297) 96.2 (328)
Sensible, kW (MBH) 26.3 (89) 30.5 (104) 33.4 (114) 38.8 (132) 50.1 (171) 63.9 (218) 87.1 (297) 96.2 (328)
72°FDB/60.0°FWB, 50% RH, 52.3°FDP
Total, kW (MBH) 23.2 (79) 27.4 (93) 30.7 (104) 34.0 (116) 44.9 (153) 59.8 (204) 78.3 (267) 89.0 (303)
Sensible, kW (MBH) 23.2 (79) 27.2 (92) 29.5 (100) 34.0 (116) 44.3 (151) 57.0 (194) 78.3 (267) 85.9 (293)
NET FC COOLING CAPACITY - Based on 45°F EGT, 40% Ethylene Glycol Solution (Includes Motor Heat @ Rated CFM & ESP)
80°FDB/62.9°FWB, 38% RH, 52.3°FDP
Total, kW (MBH) 30.8 (105) 32.5 (111) 33.1 (113) 41.9 (143) 49.4 (168) 56.7 (193) 84.3 (287) 88.0 (300)
Sensible, kW (MBH) 30.8 (105) 32.5 (111) 33.1 (113) 41.9 (143) 49.4 (168) 56.7 (193) 84.3 (287) 88.0 (300)
Flow Rate, GPM (Unit Press. Drop, ft H2O) 29 (31) 34 (39) 36 (40) 44 (38) 56 (42) 70 (56) 95 (56) 105 (69)
72°FDB/60.0°FWB, 50% RH, 52.3°FDP
Total, kW (MBH) 23.1 (78) 24.4 (83) 24.9 (85) 30.9 (105) 36.7 (125) 42.4 (144) 62.9 (214) 65.8 (224)
Sensible, kW (MBH) 23.1 (78) 24.4 (83) 24.9 (85) 30.9 (105) 36.7 (125) 42.4 (144) 62.9 (214) 65.8 (224)
Flow Rate, GPM (Unit Press. Drop, ft H2O) 29 (31) 34 (39) 36 (40) 44 (38) 56 (42) 70 (56) 95 (56) 105 (68)
NET AWS COOLING CAPACITY - Based on 45°F EWT / 55°F LWT, 0% Glycol Solution (Includes Motor Heat @ Rated CFM & ESP)
80°FDB/62.9°FWB, 38% RH, 52.3°FDP
Total, kW (MBH) 41.3 (141) 41.3 (141) 41.3 (141) 51.6 (176) 56.3 (192) 60.6 (207) 97.8 (333) 97.8 (333)
Sensible, kW (MBH) 41.3 (141) 41.3 (141) 41.3 (141) 51.6 (176) 56.3 (192) 60.6 (207) 97.8 (333) 97.8 (333)
Flow Rate, GPM (Unit Press. Drop, ft H2O) 31 (28) 31 (28) 31 (28) 40 (21) 43 (23) 46 (26) 74 (36) 74 (36)
72°FDB/60.0°FWB, 50% RH, 52.3°FDP
Total, kW (MBH) 27.2 (93) 27.2 (93) 27.2 (93) 33.7 (115) 36.9 (125) 39.8 (136) 64.2 (219) 64.2 (219)
Sensible, kW (MBH) 27.2 (93) 27.2 (93) 27.2 (93) 33.7 (115) 36.9 (125) 39.8 (136) 64.2 (219) 64.2 (219)
Flow Rate, GPM (Unit Press. Drop, ft H2O) 21 (15) 21 (15) 21 (15) 28 (13) 30 (14) 32 (15) 51 (20) 51 (20)
16
Electrical Data — Dual Compressor Systems (Air, Water, Glycol)
208/3/60 No 58.1 70.0 60.6 70.0 69.6 80.0 100.4 110.0 106.9 125.0 114.0 125.0 - - - -
208/3/60 Yes 60.2 70.0 62.7 70.0 71.7 90.0 102.5 110.0 109.0 125.0 116.1 125.0 - - - -
460/3/60 No 26.7 30.0 28.9 35.0 29.8 35.0 50.9 60.0 53.6 60.0 60.0 70.0 85.3 100.0 86.1 100.0
460/3/60 Yes 27.5 30.0 29.7 35.0 30.6 35.0 51.7 60.0 54.4 60.0 60.8 70.0 86.1 100.0 86.9 100.0
575/3/60 No 22.6 25.0 22.3 25.0 23.9 30.0 39.6 40.0 42.0 45.0 46.0 50.0 69.9 80.0 74.6 90.0
575/3/60 Yes 23.2 25.0 22.9 25.0 24.6 30.0 40.3 45.0 42.7 45.0 46.7 50.0 70.5 80.0 75.3 90.0
208/3/60 No 54.9 60.0 56.3 60.0 61.3 70.0 100.4 110.0 106.9 110.0 114.0 125.0 - - - -
208/3/60 Yes 57.0 60.0 58.4 60.0 63.4 70.0 102.5 110.0 109.0 125.0 116.1 125.0 - - - -
460/3/60 No 26.7 30.0 28.6 30.0 29.1 30.0 50.9 60.0 53.6 60.0 60.0 70.0 85.3 90.0 86.1 100.0
460/3/60 Yes 27.5 30.0 29.4 30.0 29.9 35.0 51.7 60.0 54.4 60.0 60.8 70.0 86.1 100.0 86.9 100.0
575/3/60 No 22.5 25.0 22.3 25.0 23.3 25.0 39.6 40.0 42.0 45.0 46.0 50.0 69.9 80.0 74.6 90.0
575/3/60 Yes 23.1 25.0 22.9 25.0 23.9 25.0 40.3 45.0 42.7 45.0 46.7 50.0 70.5 80.0 75.3 90.0
208/3/60 No 58.1 70.0 60.6 70.0 69.6 80.0 86.0 100.0 97.7 125.0 110.5 125.0 - - - -
208/3/60 Yes 60.2 70.0 62.7 70.0 71.7 90.0 88.1 100.0 99.8 125.0 112.6 125.0 - - - -
460/3/60 No 25.5 30.0 28.9 35.0 29.8 35.0 39.9 50.0 44.9 50.0 56.3 70.0 77.2 100.0 78.6 100.0
460/3/60 Yes 26.3 30.0 29.7 35.0 30.6 35.0 40.7 50.0 45.7 50.0 57.1 70.0 78.0 100.0 79.4 100.0
575/3/60 No 22.6 25.0 22.1 25.0 23.9 30.0 30.2 35.0 34.4 40.0 41.6 50.0 64.9 80.0 73.5 90.0
575/3/60 Yes 23.2 25.0 22.8 25.0 24.6 30.0 30.8 35.0 35.1 40.0 42.3 50.0 65.6 80.0 74.1 90.0
Cooling Only
208/3/60 No 43.9 50.0 46.4 60.0 55.4 70.0 71.8 90.0 82.5 110.0 96.3 125.0 146.9 175.0 157.0 200.0
208/3/60 Yes 46.0 60.0 48.5 60.0 57.5 70.0 73.9 90.0 85.6 110.0 98.4 125.0 149.0 200.0 159.1 200.0
460/3/60 No 18.9 25.0 22.2 30.0 23.1 30.0 33.2 40.0 38.2 50.0 49.7 60.0 66.1 80.0 67.4 90.0
460/3/60 Yes 19.7 25.0 23.0 30.0 23.9 30.0 34.0 40.0 39.0 50.0 50.5 60.0 66.9 80.0 68.2 90.0
575/3/60 No 17.3 20.0 16.8 20.0 18.6 25.0 24.8 30.0 29.1 35.0 36.3 45.0 56.0 70.0 64.6 80.0
575/3/60 Yes 17.9 20.0 17.4 20.0 19.2 25.0 25.5 30.0 29.8 35.0 37.0 45.0 56.7 70.0 65.2 80.0
NOTE: High short circuit current rating available on most models. For voltages not shown, call STULZ.
17
Electrical Data — Tandem Compressor Systems (Air, Water, Glycol)
460/3/60 Yes 54.4 60.0 60.8 70.0 86.1 100.0 86.9 100.0
575/3/60 Yes 42.7 45.0 46.7 50.0 70.5 80.0 75.3 90.0
460/3/60 Yes 54.4 60.0 60.8 70.0 86.1 100.0 86.9 100.0
575/3/60 Yes 42.7 45.0 46.7 50.0 70.5 80.0 75.3 90.0
460/3/60 Yes 45.5 50.0 55.6 70.0 80.5 100.0 81.3 100.0
575/3/60 Yes 37.5 45.0 42.7 50.0 64.9 80.0 69.6 90.0
Cooling Only
208/3/60 Yes 87.0 110.0 104.3 125.0 147.7 175.0 158.5 200.0
460/3/60 Yes 38.8 50.0 49.0 60.0 69.4 90.0 70.1 90.0
575/3/60 Yes 32.2 40.0 37.4 50.0 56.0 70.0 60.7 80.0
NOTE: High short circuit current rating available on most models. For voltages not shown, contact STULZ.
18
Electrical Data — Advanced Humidification
Dual Compressor Systems (Air, Water, Glycol)
208/3/60 No 69.4 70.0 71.9 80.0 80.9 90.0 122.8 125.0 134.5 150.0 147.3 150.0 - - - -
208/3/60 Yes 71.5 80.0 74.0 80.0 83.0 90.0 124.9 125.0 136.6 150.0 149.4 150.0 - - - -
460/3/60 No 33.0 35.0 36.4 40.0 37.3 40.0 61.5 70.0 66.4 70.0 77.9 90.0 108.4 110.0 109.8 125.0
460/3/60 Yes 33.8 35.0 37.2 40.0 38.1 40.0 62.3 70.0 67.2 70.0 78.7 90.0 109.2 110.0 110.6 125.0
575/3/60 No 28.5 30.0 28.1 30.0 29.9 30.0 47.3 50.0 51.6 60.0 58.8 60.0 89.8 100.0 98.3 110.0
575/3/60 Yes 29.1 30.0 28.7 30.0 30.5 35.0 48.0 50.0 52.3 60.0 59.5 60.0 90.4 100.0 99.0 110.0
208/3/60 No - - - -
69.4 70.0 71.9 80.0 80.9 90.0 122.8 125.0 134.5 150.0 147.3 150.0
208/3/60 Yes - - - -
71.5 80.0 74.0 80.0 83.0 90.0 124.9 125.0 136.6 150.0 149.4 150.0
460/3/60 No
33.0 35.0 36.4 40.0 37.3 40.0 61.5 70.0 66.4 70.0 77.9 90.0 108.4 110.0 109.8 125.0
460/3/60 Yes
33.8 35.0 37.2 40.0 38.1 40.0 62.3 70.0 67.2 70.0 78.7 90.0 109.2 110.0 110.6 125.0
575/3/60 No
28.5 30.0 28.1 30.0 29.9 30.0 47.3 50.0 51.6 60.0 58.8 60.0 89.8 100.0 98.3 110.0
575/3/60 Yes
29.1 30.0 28.7 30.0 30.5 35.0 48.0 50.0 52.3 60.0 59.5 60.0 90.4 100.0 99.0 110.0
Cooling w/ Humidification (No Electric Reheat)
208/3/60 No - - - -
58.1 70.0 60.6 70.0 69.6 80.0 86.0 100.0 97.7 125.0 110.5 125.0
208/3/60 Yes - - - -
60.2 70.0 62.7 70.0 71.7 90.0 88.1 110.0 99.8 125.0 112.6 125.0
460/3/60 No
25.5 30.0 28.9 35.0 29.8 35.0 39.9 50.0 44.9 50.0 56.3 70.0 77.2 100.0 78.6 100.0
460/3/60 Yes
26.3 30.0 29.7 35.0 30.6 35.0 40.7 50.0 45.7 50.0 57.1 70.0 78.0 100.0 79.4 100.0
575/3/60 No
22.6 25.0 22.1 25.0 23.9 30.0 30.2 35.0 34.4 40.0 41.6 50.0 64.9 80.0 73.5 90.0
575/3/60 Yes
23.2 25.0 22.8 25.0 24.6 30.0 30.8 35.0 35.1 40.0 42.3 50.0 65.6 80.0 74.1 90.0
Cooling Only
208/3/60 No
43.9 50.0 46.4 60.0 55.4 70.0 71.8 90.0 83.5 110.0 96.3 125.0 146.9 175.0 157.0 200.0
208/3/60 Yes
46.0 60.0 48.5 60.0 57.5 70.0 73.9 90.0 85.6 110.0 98.4 125.0 149.0 200.0 159.1 200.0
460/3/60 No
18.9 25.0 22.2 30.0 23.1 30.0 33.2 40.0 38.2 50.0 49.7 60.0 66.1 80.0 67.4 90.0
460/3/60 Yes
19.7 25.0 23.0 30.0 23.9 30.0 34.0 40.0 39.0 50.0 50.5 60.0 66.9 80.0 68.2 90.0
575/3/60 No
17.3 20.0 16.8 20.0 18.6 25.0 24.8 30.0 29.1 35.0 36.3 45.0 56.0 70.0 64.6 80.0
575/3/60 Yes
17.9 20.0 17.4 20.0 19.2 25.0 25.5 30.0 29.8 35.0 37.0 45.0 56.7 70.0 65.2 80.0
NOTE: High short circuit current rating available on most models. For voltages not shown, call STULZ.
19
Electrical Data — Advanced Humidification
Tandem Compressor Systems (Air, Water, Glycol)
460/3/60 Yes 67.0 70.0 77.2 80.0 111.7 125.0 112.5 125.0
575/3/60 Yes 54.7 60.0 59.9 60.0 89.7 100.0 94.5 110.0
460/3/60 Yes 67.0 70.0 77.2 80.0 111.7 125.0 112.5 125.0
575/3/60 Yes 54.7 60.0 59.9 60.0 89.7 100.0 94.5 110.0
460/3/60 Yes 45.5 50.0 55.6 70.0 80.5 100.0 81.3 100.0
575/3/60 Yes 37.5 45.0 42.7 50.0 64.9 80.0 69.6 90.0
Cooling Only
208/3/60 Yes 87.0 110.0 104.3 125.0 147.7 175.0 158.5 200.0
460/3/60 Yes 38.8 50.0 49.0 60.0 69.4 90.0 70.1 90.0
575/3/60 Yes 32.2 40.0 37.4 50.0 56.0 70.0 60.7 80.0
NOTE: High short circuit current rating available on most models. For voltages not shown, contact STULZ.
20
CyberAir® DX Engineering Manual
Dimensional Drawings
CFD-021/028/035-D – Downflow
Free Return or with Optional Ducted Return AIR IN
AIR IN
POWER CONNECTION
AIR OUT
AIR OUT
NOTE Standard piping connections terminate
inside the cabinet at the bottom, right hand side.
Adjustable Floor Stand, Non-Seismic
21
CyberAir® DX Engineering Manual
Dimensional Drawings
CFD-042/053/070-D - Downflow
Free Return or with optional Ducted Return
AIR IN
AIR IN
AIR OUT
AIR OUT
NOTE: Standard piping connections terminate inside the cabinet at the bottom, right hand side.
22
CyberAir® DX Engineering Manual
Dimensional Drawings
CFD-088/105-D - Downflow
Free Return or with optional Ducted Return
AIR ININ
AIR
AIR IN
PIPING
CONNECTIONS
POWER
CONNECTIONS
AIR
AIR OUTOUT
AIR OUT
NOTE: Piping connections terminate inside the cabinet at the bottom, right hand side.
23
CyberAir® DX Engineering Manual
Dimensional Drawings
CFU-021/028/035-D – Upflow
Ducted or Provided with Optional 2- or 3-way Plenum Box
POWER
CONNECTIONS
77.4” (OVERALL)
)
88.1” (OVERALL)
40.3” (OVERALL)
24
Dimensional Drawings
CFU-042/053/070-D – Upflow
Ducted or Provided with Optional 2 or 3-Way Plenum Box
POWER
OPTIONAL HOT CONNECTIONS
WATER
REHEAT PIPING
PLENUM CONNECTIONS
AIR OUT
AIR OUT
3.0” OPTIONAL HOT
WATER REHEAT
PLENUM
89.1”
(OVERALL)
88.1” (OVERALL
40.3” (OVERALL)
25
Dimensional Drawings
CFU-088/105-D – Upflow
Ducted or Provided with Optional 2 or 3-Way Plenum Box
POWER CONNECTIONS
AIR OUT
AIR OUT 3.0” OPTIONAL HOT WATER REHEAT PLENUM
118.4 ”(BASE)
88.1”(BASE)
40.3”(BASE)
26
Supply Air Plenum and Return Air Plenum Extension — Upflow
Plenum extension
boxes may be
stacked
Typical seismic rated floor stands are below. Enclosed, non-seismic rated floor
stands also available.
27
Guide Specifications
CyberAir® DX
Summary
This specification describes requirements for a precision environmental control system. The
CyberAir floor-mounted air conditioning system shall provide precision temperature and/or
humidity control for computer rooms or rooms containing communications or other highly
sensitive heat load equipment where continuous 24 hour a day, 365 days a year air conditioning
is required.
Designed for front service access, CyberAir systems require minimal floor space. The units are
designed with a wide range of options to handle all precision cooling applications.
Design Requirements
The environmental control system shall be a CyberAir factory-assembled unit. The unit shall be
designed for corner installation requiring front access through hinged and removable front
access panels. No allowance for side service access shall be required. CyberAir units are
especially adapted for both raised and non-raised floors.
Quality Assurance
The manufacturer shall maintain a set of international standards of quality management to
ensure product quality. Prior to shipment each system shall be subject to a complete operational
and functional testing based on predefined procedures. The air conditioner manufacturer shall
be ISO 9001:2015 certified.
Cabinet
Downflow
Access panels shall be fabricated from 18 gauge galvannealed steel. Door jambs and top
cabinet frame shall be fabricated from 16 gauge galvannealed steel. Bottom cabinet frame shall
be fabricated from 10 gauge galvannealed steel.
The panels shall be lined with ½” (13 mm), 2 lb (.90 kg), high-density sound and thermal
insulation and sealed with a self-extinguishing gasket conforming to NFPA 90A and 90B. The
main unit color shall be black, extra fine texture.
Upflow
Access panels shall be fabricated from 18 gauge galvannealed steel. Door jambs and top
cabinet frame shall be fabricated from 16 gauge galvannealed steel. Bottom cabinet frame shall
be fabricated from 10 gauge galvannealed steel.
28
The panels shall be lined with ½” (13 mm), 2 lb (.90 kg), high-density sound and thermal
insulation and sealed with a self-extinguishing gasket conforming to NFPA 90A and 90B. The
main unit color shall be black, extra fine texture.
Downflow (CFD)
The air conditioner shall be configured for a downflow air pattern with top free return air and
conditioned supply air discharge through the bottom of the system into the raised floor.
Upflow (CFU)
The air conditioner shall be configured for an upflow air pattern with free return air through front
filtered grille or ducted rear return air and conditioned supply air discharge through the top of the
unit.
Air Filtration
All units shall be supplied with disposable air filters classified as UL 900 or UL 586. Filters shall
be 4” deep (nominal). Filters shall be pleated with a Minimum Efficiency Reporting Value
(MERV) of 8. Filters shall be installed in a front accessible, steel holding frame, and accessible
through the front of the unit (except for the rear return configuration).
Optional: Filters rated up to MERV 11 shall be available.
Mechanical Components
Backward Inclined Plenum Style Fan with an EC Motor
The blower(s) shall be direct driven, single inlet, backward curved centrifugal with an
electronically commutated motor for maintenance free operation. The motor shall include:
Integrated electronic control board and direct microprocessor control signaling for fan
speed control
Soft-starting capabilities
RS-485 BUS connection
Integrated current limitations
Each fan shall be low noise, low vibration manufactured with a fiberglass reinforced
polypropylene impeller. Each fan impeller shall be dynamically and statically balanced in two
planes to minimize vibration during operation.
Evaporator Coil
The system shall be configured for draw-thru air pattern to provide uniform air distribution over
the coil face. The coils shall be a V-Frame design to provide maximum coil surface area and
minimum depth to provide a high sensible cooling capacity. The coils shall be configured as
dual refrigeration circuits comprising seamless drawn copper tubes, mechanically bonded to
29
tempered aluminum fins. Coil end plates shall be hot dipped galvanized steel. The evaporator
coil shall be mounted in an insulated stainless-steel condensate drain. Refrigerant flow for each
circuit shall be controlled by electronic expansion valves.
Refrigeration System
All refrigerant piping shall be refrigerant grade tubing. Each refrigeration circuit shall include, as
a minimum a refrigerant drier/strainer sight glass with moisture detector, an electronic
expansion valve, an evaporator coil, a compressor, a high-pressure switch with manual reset,
and a low pressure switch with automatic reset. All high-pressure joints shall be brazed, and the
entire system shall be pressure tested at the factory with dry nitrogen.
An electronically operated expansion valve shall be installed to precisely control the flow of
liquid refrigerant into the evaporator coil while maintaining the desired superheat across a wide
range of operating conditions.
The unit shall be provided with two independently circuited, high efficiency, high reliability, and
low noise scroll compressors. Each compressor shall be complete with rotolock service valves,
charging and service shraeder ports, internal vibration isolation, internal thermal overloads, an
internal pressure relief valve, an internal discharge gas vibration eliminator, and external
vibration mounting isolation.
Optional: Tandem scroll compressors are also available on STULZ models CFD-053 and larger
for additional capacity control and energy savings. Rotolock service valves are not used with the
tandem option.
The CyberAir floor-mounted air conditioning system shall incorporate a snap acting hot gas
bypass system to provide modulation of the unit’s cooling capacity and evaporator coil freeze
protection under low load conditions.
The air-cooled system shall incorporate a low ambient, variable speed fan, head pressure
control. The pressure control shall be for year-round air conditioning system operation down to -
20°F DB minimum ambient air temperature.
30
-30°F Flooded Control
The air-cooled system shall incorporate a low ambient, flooded head, pressure control. The
pressure control shall be for year-round system operation down to -30°F DB minimum ambient
air temperature. Liquid refrigerant receivers, with receiver liquid-level sight glass and head
pressure regulator valves (for flooded condenser operation) shall be included. The receiver and
heat pressure control valve ships separately as field installed.
Each refrigerant circuit head pressure shall be controlled by a factory installed 2-way
water/glycol regulating valve rated for 600 psig w.w.p. The 2-way condenser water modulating
valve shall automatically meter the flow of water to the condenser. It shall do so, in response to
a proportional signal (0-10 VDC) provided to the valve by the microprocessor controller.
The refrigerant circuit head pressure shall be controlled by a factory installed 3-way water/glycol
regulating valve rated for 600 psig w.w.p. The 3-way condenser water modulating valve shall
automatically meter the flow of water/glycol to the condenser. It shall do so in response to a
proportional signal (0-10 VDC) provided to the valve by the microprocessor controller.
The humidifier shall have a modulating output between 20% and 100% of rated capacity. The
unit shall include draw in water tempering to ensure the drain water do not exceed 140 °F during
automatic drain cycles.
31
Electric Heat/Reheat
A factory mounted and wired low-watt density, plated fin tubular design electric resistance
heater shall be included to provide automatic sensible re-heating as required during the
dehumidification cycle and automatic heating mode.
Electric heaters shall be provided with miniature thermal/magnetic circuit breakers, which shall
protect each ungrounded conductor. Also included will be one automatic reset and one manual
reset over-temperature safety device (pilot duty).
The electric heat/reheat shall be controlled through a zero crossing silicon controlled rectifier
(SCR) with an extruded aluminum heat sink and solid-state logic system to provide close dry
bulb temperature control.
Electrical System
The electrical system shall conform to National Electrical Code requirements. The control circuit
shall be 24 volts AC, wired in accordance with NEC Class II requirements. The control circuit
wire shall not be smaller than 18 AWG. All wiring shall be neatly wrapped and routed in bundles.
Each wire shall end with a service loop and be securely fastened by an approved method. Each
wire in the unit shall be numbered for ease of service tracing.
All electrically actuated components shall be easily accessible from the front of the unit without
reaching over exposed high voltage components or rotating parts. Each high voltage circuit shall
be individually protected by circuit breakers or manual motor starters on all three phases. Line
voltage and 24-volt control circuit wiring shall be routed in separate bundles.
The electric box shall be positioned for service convenience and shall include all the contactors,
starters, fuses, circuit breakers, terminal boards and control transformer required for operation
of the unit and shall allow for full service access.
32
Main Power Service Switch
The unit shall be provided with a unit mounted main power service non-fused disconnect switch.
Included in the system’s electrical control circuit shall be a 2-pin terminal connection for remote
stop/start of the CyberAiR CW air conditioner by remote source.
Two individual main power input disconnect switches shall be provided, one for each incoming
power source. In the event the primary power fails, or a phase loss/imbalance occurs, the
automatic transfer switch immediately transfers power to the secondary power source.
Once the primary power has been restored, the transfer switch automatically shifts the power
load back to the primary power. The transfer time from one source to the other is adjustable to
allow staging or to sequence restart of load.
In addition to the automatic transfer switch, the local controller display shall indicate which
power source has failed. This indication is a visual depiction that allows the user to determine
the status of the input source. This status shall be conveyed though the BMS serial
communications link. A through-the-door indicator light shall be included for a fast and local
notification of available power sources
Airflow Control
EC Fan Speed Control
The system shall include a variable fan speed control package. The purpose of this feature is to
allow the use of the energy saving capabilities of the EC fan without running into the problems
associated with ice formation on the coil or excessive latent cooling. When the suction pressure
and therefore suction temperature is equal to the minimum allowable coil temperature, the E²
controller will prevent the EC fans from any further decrease in speed until that suction
pressure/temperature rises. The minimum allowable suction temperature is a customer
selectable parameter.
In the event of a fan failure, the controller shall automatically enable all remaining EC fans to
increase to the maximum fan speed setting.
E² Series Controller
The advanced microprocessor based E² Series controller shall be equipped with flexible
software capable of meeting the specific needs of the application. The setpoints shall be default
33
and their ranges shall be easily viewed and adjusted from the user interface display. The
program and operating parameters shall be permanently stored on a non-volatile system in the
event of power failure. The controller shall be designed to manage temperature and relative
humidity (RH) levels to a user defined setpoint via control output signals to the CyberAiR
system. Control parameters have variable outputs from 0 to 100% of the full rated capacity. The
controller shall receive inputs for measurable control conditions (temperature, relative humidity,
and dew point) via return air or room mounted sensors. The internal logic will then determine if
the conditions require cooling, humidification or dehumidification. Control setpoints shall be
established to maintain design conditions of the installation. The controller will respond
accordingly to changes in these conditions and control the output/demand for the appropriate
mode of operation until user defined conditions are achieved.
The large bezel touch screen user interface display panel features a high-resolution backlit
liquid-crystal graphical display equipped with contrast adjustment and LED illuminated function
keys. The screens that appear on the user interface display panel present data that is from the
controller.
The controller offers an alarm log plus four different interface menu levels to the operator:
Information, Control, Service, and Factory. These menus permit the user to easily view, control,
and configure operating parameters for the CyberAir system.
Field Configurable
The program for the E² Series controller shall be field configurable, allowing the operator the
capability of selecting control setpoints specific to the application.
Password Protection
Access to the Info Menu, Alarms Log, and the ability to monitor room conditions shall be allowed
without the use of a password. Modifications to the control setpoints shall require the use of a
password. The controller shall be programmed to recognize predetermined security levels
before allowing access to display screens containing critical variables.
Three secured menu levels (Control, Service, and Factory) will support unique passwords that
must be entered to access the menu screens so only authorized personnel may perform
modifications to the settings.
34
The setpoints for the system may be re-adjusted in the Control menu at any time. If it becomes
necessary, the customer may restore the setpoints back to the Customer Default setpoint
values or to the original Factory (primary) setpoint values.
Multiple CyberAir systems consisting of up to eight floor-mounted air conditioners equipped with
like controllers may be controlled and monitored via the E² series controller. With multiple
CyberAir systems, each unit can be selectively configured as Active to operate as a primary
A/C, Capacity Assist for staged operation, or as Standby to come online in case of a failed air
conditioning unit to ensure continuous availability.
The controller may also be configured to rotate units with timed duty cycling to promote equal
run- time and assure that each CyberAir system within the rotating group is operationally
exercised on a periodic timed basis.
Summary Alarm
Alarm conditions shall activate a red LED indicator that backlights the alarm function key. As an
option, an alarm condition may also be enunciated by an audible alarm signal. An alarm is
acknowledged by pressing the alarm key.
This calls up alarm display screens that provides a text message detailing the alarm conditions.
After an alarm condition is corrected, the alarm can be cleared by pressing the alarm key.
Included in the system’s electrical control circuit shall be a 2-pin terminal connection for remote
start/stop of the CyberAir CW air conditioner by a remote source.
The control package shall include a Ultracap Constant Contact short term power supply for the
E² Series Controller to allow the controller to manage the power transfer switch from one
35
primary power source to another while maintaining communications with an active monitoring
system. The E² Ultracap Constant Contact shall permit a minimum of one-minute ride thru
period.
Optional Alarms
CyberAir floor-mounted air conditioning system standard features can be deleted and/or
substituted with optional features to allow you the flexibility to select the configuration best
suited for your application.
An adjustable floor stand shall be provided to enable ease of installation of the CyberAir floor-
mounted air conditioning system onto a raised floor environment. Floor stand height shall be
adjustable and shipped separately for field installation.
Condensate Pump
A condensate pump shall be factory installed within the CyberAir floor-mounted air conditioning
system for automatic removal of condensate and humidifier flush water (if applicable).
The condensate pump shall include an internal overflow safety float which, when wired to the
remote start/stop terminals, shall open the unit’s control circuit, thereby shutting the unit down in
the event of a condensate overflow.
The condensate pump shall be specifically designed to operate with the higher condensate
temperatures caused by the flush and drain cycle of the electrode canister humidifiers.
Smoke Detection
A photo-electric smoke detector shall be factory installed and wired in the return air section of
the CyberAir floor mounted air conditioning system. The photo-electric detector shall include
built-in circuitry that performs a functional test of all detection circuits at least once every 40
seconds without the need for generating smoke. The UL-listed velocity range shall be 0-3000
fpm. The air conditioner will shut down upon sensing smoke in the return air stream.
36
Firestat
The CyberAir floor-mounted air conditioning system shall be provided with a factory wired and
mounted firestat. The firestat will shut down the air conditioner upon sensing a high return air
temperature.
A 20 ft. remote strip/cable type water/leak detector shall be provided for remote field installation.
Upon sensing a water leak, the normally closed water detector control circuit shall open, thereby
shutting down the CyberAir floor-mounted air conditioning unit’s water producing components.
A 2- or 3-way plenum discharge box shall be provided. The plenum box shall include double-
deflecting, adjustable grilles. It shall be selectable for upflow units only.
A return air plenum extension shall be provided to raise the return air connection. The plenum
extension shall be coated to match the CyberAir air conditioning system.
The CyberAir floor-mounted air conditioning system shall be rated for a short circuit current
rating for a maximum of 65k AIC. The higher short circuit current rating shall include safe touch
fusing upstream of the unit’s main power disconnect switch.
37
Free-Cooling Mode (Optional)
DX Water/Glycol Cooled systems with Free-Cooling are provided with the following standard DX
head pressure and Free-Cooling valve combination:
DX Valves – 3-way, 600 psig
FC Valve – 3-way, 600 psig (021-035 kW Systems) 3-way, 400 psig (042-105 kW
Systems)
A Free-Cooling economizer cycle shall be provided to take advantage of low ambient air
temperature conditions to provide compressor less cooling. The air conditioner shall have three
modes of operation:
100% Free-Cooling cycle during low ambient air conditions
Assist FC + Stage DX Mode to provide partial free-cooling with one DX compressor as
an assist mode
2-stage DX operation without Free-Cooling active due to higher ambient temperatures
An alternative water source cooling cycle shall be provided to use building chilled water supply
when available as the primary cooling cycle with dual compressor, DX refrigerant cooling as a
backup. The air conditioner shall have two cooling systems: The primary code of cooling shall
be chilled water/glycol circuit with alternative water source cooling coil and the
secondary/backup mode of cooling shall be a dual compressor, DX refrigerant circuit.
The E² microprocessor’s Alternative Water Source program algorithm shall analyze input data
from factory provided and installed room air temperature and relative humidity sensors.
Based on this data, the E² controller shall automatically control the sequencing of the primary
AWS chilled water to and from the secondary /backup dual compressor DX modes of operation.
If chilled water is available the system will operate like a chilled water unit, without the
compressor operating. When the water temperature is too high, or the water flow rate is not
sufficient, the air conditioner automatically switches to the dual compressor, DX refrigerant
cycle.
Alternate water source cooling shall be controlled by the following standard and optional control
valves:
2-way, 600 psig (Standard)
3-way (Optional) 600 psig Rated (021-035 kW Systems)
400 psig Rated (042-105 kW Systems)
Modulating AWS cooling control valve (2-way standard, 3-way optional) shall be factory
installed. Precision cooling control shall be accomplished via an analog control signal to the
proportionally actuating control valve.
38
Air-Side Economizer Controls
The CyberAir floor-mounted air conditioning system controller shall be equipped with a unique
air-side economizer mode for applications using outdoor air-side economizing.
The Air-Side economizer control package shall include an outdoor temperature and humidity
sensor, remote space return air sensor, and supply air sensor for proper control during
economizer operation. An individual analog output signal (0-10 VDC) is provided to control the
external outdoor air intake damper. Damper provided by others.
Control settings shall be included for both temperature and humidity properties of the outdoor
air. A damper signal lockout shall be included if the outdoor air conditions reaches user
adjustable limits. The economizing damper signal shall allow a minimum output setting for
minimum outside air control to meet ventilation requirements.
Code Conformance
The supplied system shall be provided with certification by a NRTL to the following standards:
CETL US listed to UL 1995 (2011 Ed. 4)
CSA C22.2 No. 236 (2011 Ed. 4)
39
STULZ North American Headquarters
STULZ AIR TECHNOLOGY SYSTEMS (STULZ USA) , INC.
1572 Tilco Drive
Frederick, MD 21704
Tel: 301.620.2033 | Fax: 301.662.5487 | [email protected]
Technical Manage-
Advice Maintenance Implementation Test Center Climate Customized Service-Portal
ment Facility
STULZ Subsidiaries
STULZ Australia Pty. Ltd. STULZ España S.A. STULZ México S.A. de C.V. STULZ Singapore Pte Ltd.
34 Bearing Road Avenida de los Castillos 1034 Avda. Santa Fe No. 170 33 Ubi Ave 3 #03-38 Vertex
Seven Hills NSW 21 47 28918 Leganés (Madrid) Oficina 2-2-08, German Centre Singapore 408868
Delegación Alvaro Obregon [email protected]
STULZ Austria GmbH STULZ France S. A. R. L. MX- 01210 México
Industriezentrum NÖ – SÜD, 107, Chemin de Ronde Distrito Federal STULZ Air Technology and
Straße 15, Objekt 77, Stg. 4, Top 7 78290 Croissy-sur-Seine Services Shanghai Co., Ltd.
2355 Wiener Neudorf [email protected] STULZ GROEP B. V. Room 406, Building 5
STULZ S.p.A. Postbus 75 457 North Shanxi Road
STULZ Belgium BVBA Via Torricelli, 3 180 AB Amstelveen Shanghai 200040
Tervurenlaan 34 37067 Valeggio sul Mincio (VR)
1040 Brussels STULZ New Zealand Ltd. STULZ South Africa Pty. Ltd.
STULZ-CHSPL Office 71, 300 Richmond Rd. Unit 3, Jan Smuts Business Park
STULZ Brasil (India) Pvt. Ltd. Grey Lynn, Auckland Jet Park, Boksburg
Ar Condicionado Ltda. 006, Jagruti Industrial Estate Gauteng, South Africa
Rua Cancioneiro de Évora, 140 Mogul Lane, Mahim STULZ Polska SP. Z O.O.
Bairro - Santo Amaro São Mumbai - 400 016 Budynek Mistral. STULZ U. K. Ltd.
Paulo-SP, CEP 04708-010 Al. Jerozolimskie 162 First Quarter,
02 – 342 Warszawa Blenheim Rd. Epsom
Surrey KT 19 9 QN
QECS010F 6/16/2021 © STULZ USA – Specifications subject to change without notice. www.stulz-usa.com