Neutral Grounding

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Neutral Grounding Resistors

for Limiting Fault Current


White Paper
Revision: July 2018
Neutral Grounding Resistors
for Limiting Fault Current

A Neutral Grounding Resistor (NGR) is an effective means for limiting fault current in industrial power distribution sys-
tems. This paper describes NGR design, its function in grounding systems, and its proper application for limiting faults.
An NGR can be applied only after a complete evaluation of a systems design, capabilities and fault current coordina-
tion scheme. Specifying engineers are responsible for evaluating system parameters and determining the correct NGR
rating for the application.

System Grounding
Providing sufficient grounding is essential when designing an industrial power system. It is important to understand
that “System Grounding” refers to the grounding arrangement of the current carrying conductors in a power distribu-
tion system. It does not refer to “equipment grounding”, which is provided for equipment operation and personnel
safety. Industrial power systems can be either “Ungrounded”, “Effectively (Solidly) Grounded” or “Resistance Ground-
ed”.

Ungrounded Systems
Ungrounded systems do not have a direct electrical connection
between the generator (or the transformer secondary) and a Source
3Ic a
ground point on the power distribution system. However, these
systems have sufficient capacitance to safely manage potential
N 3Ic b
faults. In ungrounded systems, the reference voltage of the
neutral conductor will approach ground potential when ground c
faults are absent from all phases of the system. Ungrounded 3Ic
systems can continue to operate with a single ground fault on O
any phase, which allows for repair of the fault without interrupt-
ing power to the load. A single ground fault will raise the ground
potential between the remaining two ungrounded phases to 3Ic
their full line-to-line value. The shift of phase-to-ground potential
will place additional stresses on equipment connected to the Figure 1: Ungrounded System
system.
The ability of an ungrounded system to operate with a single ground fault may be an advantage for certain facilities
where an unplanned shutdown could create an unsafe condition. While operation may continue, any ground fault
condition should be investigated and repaired as soon as possible.

2
Effectively Grounded Systems
Effectively Grounded systems feature a solid connection between
the power system and a ground point. The grounding connection
Source
may be made without installing an impedance device or it may use 3Ic a
a device to impart resistance or reactance to limit ground fault
currents and mitigate their potentially damaging effects. An effec- N 3Ic b
tively grounded system will clear a ground fault by opening a circuit
breaker or fuse. c
Arcing ground faults can produce significant damage by the energy
IF O Ic Ic
they dissipate. Arcing ground faults may burn insulation and vapor-
ize conductors. At levels below the fusing current, sustained faults Ic
can continue without tripping overcurrent protection devices, a
scenario that is more likely in an ungrounded system. In a ground-
ed system, a phase-to-ground fault would trip an over-current Figure 2: Solidly Grounded System
protection device to clear the fault. Proper application of a neutral
grounding resistor can limit the ground fault current and resultant
damage.
The occurrence of resonant conditions can create serious over-voltages when ground faults occur. The capacitance
of the power distribution system and the inductance of the source (transformer or generator) windings can, under
certain conditions, allow voltages in excess of the nominal system voltage and cause additional damage. A similar
condition can occur during a re-striking ground fault, which can raise voltage to six times the nominal system voltage.
A grounded neutral system prevents this voltage build-up by controlling the system phase-to-ground voltages to their
nominal phase-to-neutral values.

Resistance Grounding
Resistance Grounded systems use a resistive device that is installed
Source
between the neutral and ground conductors. This method offers a
the advantages of both ungrounded and effectively grounded
N 3Ic b
systems and avoids most of their disadvantages. For example, po-
tentially dangerous system over-voltages caused by arcing ground
c
faults are suppressed by dissipating the energy at the resistor. Per-
3Ic
sonnel safety and system stability are also significantly improved. O
IF IF
Resistance grounding systems can be classified as low or high 3Ic
resistance systems. Low Resistance systems use a neutral ground
resistor to absorb 200 to 1200 amps of ground fault current. Low
Figure 3: Resistance Grounded System

3
resistance grounding is typically used in systems with voltages exceeding 1000 volts line-to-line. High Resistance
Grounding is typically limited to fault currents of 10 amps or less, and is used in systems operating below 1000 volts
line-to-line due to the lower ground fault currents and associated higher resistance.

Neutral Grounding Resistors


Neutral Grounding Resistors are installed in series with
a power system’s neutral grounding connection. By pro-
viding impedance, these devices can limit the ground
fault current and mitigate damage that might otherwise
result from a phase-to-phase grounding fault. The neu-
tral grounding resistor provides a terminal for connect-
ing the power system neutral conductor to the NGR.
The opposite side of the NGR is connected directly to a
suitable ground. In some cases, the resistor may actu-
ally be wired to the secondary of a single-phase trans-
former, which has its primary wired in series with the
power system’s neutral-to-ground connection.
The NGR also provides a convenient point for monitor-
ing the ground fault current. A current transformer is
often placed at the neutral connection to operate pro-
tective relay systems. In most cases, the current trans-
former ratio of the primary will be the same rating as
the resistor. For example, a 400 amp resistor will have a
400:5 amp current transformer. Neutral Grounding Resistors, 15kV enclosure above left
and 5kV enclosure above right.
The neutral ground resistor will be rated for both cur-
rent (in amps) and time (in seconds). IEEE Standard 32-
1972 specifies the proper design criteria for 10 second,
extended time, and continuous rated neutral grounding
resistors.

C.T.
NEUTRAL FROM NEUTRAL GROUND
H1 H2 TO EARTH
GENERATOR OR
GROUND
TRANSFORMER
R
X1 X2

TO RELAY

Figure 4: Typical Neutral Grounding Resistor Schematic with Current Transformer

4
Installation System Voltage
Line to Neutral Initial Current
Ohms +/- 10%
Voltage Amps
Neutral grounding resistors are typically installed 2400 1390 100 13.9
outdoors, on a suitable concrete pad as a part of the 2400 1390 200 6.9
transformer/switchgear structure. For these applica- 2400 1390 400 3.4
tions, their enclosures must be rated for outdoor use, 2400 1390 600 2.3
and may use internal neutral and ground connec- 2400 1390 800 1.7
tions. 2400 1390 1000 1.4
4160 2400 100 24.0
Ratings 4160 2400 200 12.0

It is beyond the scope of this paper to specify ratings 4160 2400 400 6.0
for the neutral grounding resistor. The specifying en- 4160 2400 600 4.0
gineer must coordinate the neutral grounding resistor 4160 2400 800 3.0
with the overall design on the electrical distribution 4160 2400 1000 2.4
system and its specific characteristics. The selection 7200 4160 100 41.6
of the ampere rating of the neutral grounding resis- 7200 4160 200 20.8
tor current and time parameters must be selected 7200 4160 400 10.4
to operate safely with the available fault current and 7200 4160 600 6.9
overcurrent protective system. 7200 4160 800 5.2
7200 4160 1000 4.2
13800 8000 100 80
13800 8000 200 40
Summary 13800 8000 400 20
13800 8000 600 13.3
There is an increasing demand for service continu-
13800 8000 800 10
ity of power distribution systems. Proper grounding
13800 8000 1000 8
of electrical power systems can significantly improve
both reliability and safety. To achieve maximum sys- Table 1: Common Neutral Grounding Resistor Ratings
tem availability and obtain the benefits of grounding,
resistive grounding is often the method of choice.

5
w w w . a v t r o n p o w e r . c o m

Avtron Power Solutions


6255 Halle Drive Cliffe Road, Easton-on-the-Hill
Cleveland, OH 44125, USA Stamford PE9 3NP, United Kingdom
Tel: 216 573 7600 Tel: +44 (0) 1780 480033
[email protected]

© 2023 Avtron Power Solutions. All Rights Reserved.

You might also like