TG 1 - Sistema de Limpeza Do Condensador - Manual de Instalação
TG 1 - Sistema de Limpeza Do Condensador - Manual de Instalação
TG 1 - Sistema de Limpeza Do Condensador - Manual de Instalação
INDEX
PART 1
PART 2
CONTENTS OF PART 2
S. No. DESCRIPTION No of Sheets
1 MECHANICAL DATASHEET 8
2 DATASHEET FOR ACTUATOR 4
3 MOTOR DATASHEET 3
4 INSTRUMENT DATASHEET 4
5 STARTUP & COMMISSIONING SPARE PARTS LIST 2
6 LUBRICANT LIST 1
7 CONTROL PHILOSOPHY 15
8 P&I DIAGRAM (incl. Legend) 2
9 GENERAL ARRANGEMENT OF BALL STRAINER 1
10 GENERAL ARRANGEMENT OF BALL RECIRCULATING SKID
1
AND FOUNDATION DETAILS
11 GENERAL ARRANGEMENT OF BALL DISTRIBUTOR & BALL
6
INJECTION PIPE
12 HOOK UP DIAGRAM 1
PART 3
CONTENTS OF PART 3
S. No. DESCRIPTION No of Sheets
1 WORM GEAR FOR BALL STRAINER 49
2 ACTUATOR FOR BALL STRAINER 62
3 ACTUATOR FOR BALL VALVE 66
4 MECHANICAL SEAL FOR PUMP 13
5 MOTOR FOR BALL RECIRCULATING PUMP 13
6 D.P. TRANSMITTER 20
7 CLEANING BALLS 6
8 BALL RECIRCULATING MONITOR 18
CONTENTS
PART 1
DES/OMM/TCS/DS Sheet 1
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
DES/OMM/TCS/DS Sheet 2
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
DES/OMM/TCS/DS Sheet 3
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
SECTION 1 INTRODUCTION
1.1.1 DESCRIPTION
Condensers/Heat Exchanges play a key role in Power, Desalination & Process Industries. A lower
back pressure of the turbine results in a higher generation of power and this largely depends on the
performance of the Condenser.
It is essential to maintain the heat transfer rate and co-efficient close to the design parameters for
improved steam condensation. Hence the cleanliness of the condenser tubes should be kept as close
as possible to the design values in order to increase the condenser efficiency which will result in an
optimum Power Generation. Similarly, highly efficient heat transfer rate of the heat exchangers can
lower energy cost of the Processing Industries.
Tube Cleaning System of the Condensers/Heat Exchangers by using Sponge Rubber Balls has been
in use all over the world, for more than a four decades now. This system is found to be an effective
solution for maintaining the cleanliness factor at the optimum level.
Sponge rubber balls with a special composition and size 1 to 3mm greater than the inner diameter
of the Condenser Tubes are injected into the Cooling Water stream at the inlet. These balls with
specific gravity close to the cooling water are carried into the Condenser by the velocity of the inlet
water. Cleaning balls are then pushed through the tubes by the differential pressure existing across
the Condenser. While passing through the Condenser tubes, the balls are pressed against the walls
of the tubes removing all deposits on the inner surface of the tubes. A specially designed screen
arrangement called the Ball Separator, separates the balls from the main Cooling Water system and
the balls are collected in the Ball Collector. The balls are injected into the Cooling Water through the
Ball Recirculating Pump.
DES/OMM/TCS/DS Sheet 4
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
1.1.2 SERVICE
DES/OMM/TCS/DS Sheet 5
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
Ball Separator (Ball Strainer) is specially designed to facilitate the smooth passage of the Cleaning
Balls to the extraction point. The unique design of the Ball Separator ensures that the Cleaning Balls
will have to move through only a small angle, since larger angles may result in the balls sticking to
the screen in case of adverse conditions.
Ball Separator is of shell type construction with flanged ends. The Ball Separator consists of two
screens, which are mounted on two independent shafts. These shafts are fitted one end with bearing
and another end with a separate drive that facilitates independent operation of screens and easier
maintenance.
Screen separate the Cleaning Balls from the Ball Separator and guide them to Ball Extraction Pipes.
The screen can be set in either OPERATION POSITION or in BACKWASH POSITION. Actuator
with Worm Gear arrangement enables the movement of screen to the required position.
In this position, Cleaning Balls are separated from the cooling water and are guided to the Ball
Extraction Nozzle.
Screens in the Ball Separator are in an inverted position. In this position, balls are not in circulation
and the screens are thoroughly backwashed, when the Differential Pressure across the Ball Separator
exceeds a preset value due to the fouling of screen.
DES/OMM/TCS/DS Sheet 6
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
Differential Pressure across the Ball Separator Screens is constantly monitored by a Differential
Pressure Measuring System, wherein the measured value is sensed by a Differential Pressure
Transmitter. This is to monitor the Differential Pressure across the Ball Separator Screen. When the
Differential Pressure exceeds the value, the screen automatically will move to Backwash Position.
The above system consists of
- D.P. Transmitter senses the Differential Pressure and transforms this into an electrical output.
- Isolation Valves isolate the D.P. Transmitter from the Cooling Water in case of Service
requirements.
The Ball Recirculating Skid transport the Cleaning Balls to the Ball Injection Point at the Main
Cooling Water Pipe Line.
- Ball Recirculating Pump is a non-clog centrifugal pump with specially designed impeller,
capable of handling Cleaning Balls under suitable pressure for injection and collection of sponge
rubber balls in the inlet and outlet of the condenser respectively.
- Motor for the Ball Recirculating Pump is a totally enclosed fan Cooled squirrel cage induction
motor.
- Pressure Gauge measures the discharge pressure of the Ball Re-circulating Pump.
- Ball transport Piping is provided for the movement of the balls to the condenser.
- Ball Collector (Ball Vessel) is specially designed with no moving parts and hence it is
maintenance free. It is used for charging and collection of cleaning balls. The Ball Collector has
a perforated screen basket which traps the balls inside the Ball Collector during collection mode.
The Ball Collector acts as a reservoir for the sponge balls when the system is not in operation.
- Valves are given in the Ball Collector for charging, collecting and bypassing the water from the
Ball Collector.
- Valves are provided in the Ball Collector for venting and draining purpose whenever required.
V-Piece is provided in case of its requirement to branch off the Ball Transport Pipe into two separate
pipelines. Sight glass in the V-Piece to monitor the movement of Cleaning Balls.
DES/OMM/TCS/DS Sheet 7
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
Manually operated valves are provided in the Ball Extraction, Ball Injection and other isolation areas
for service requirements. These Valves are operated manually by a lever.
Actuator operated valves are normally provided in the Ball Collector for Ball Collection and
Distribution purpose. They can be provided in other areas also depends upon the requirement.
Ball Transport Pipes are installed between the Ball Separator Extraction Nozzle and the Injection
Nozzle. These pipes are used to transport the cleaning balls from the Ball Extraction Nozzle to
Injection Nozzle.
Cleaning Balls are used for preventing formation of deposits and scales inside the Condenser tubes.
The composition of balls is based on a natural rubber mixture containing fillers and chemicals.
To ensure uniform distribution of cleaning balls to all the Condenser tubes, the cleaning balls have
been designed to have a specific gravity close to that of the Cooling Water.
Ball life strongly depends on Water Quality, Cleaning frequency and surface condition of the
condenser tubes. Scaled and corroded surfaces are having a detrimental effect on ball life.
For every fresh charge of cleaning balls in the Ball Collector, squeezing in water is mandatory to
release the air to avoid floating of balls on top of the condenser and uniform ball circulation.
Ball Gauge is made of polymer bin, fitted with Stainless Steel Gauge Plate. The Gauge Plate has
Sieves for separating the oversize balls. The sieve size is equal to the internal diameter of the tube
size.
The balls collected from the Ball collector, after the water is completely squeezed out, are to be spread
over the sieve plate. The undersize balls are passed through the sieve and collected in the Bin. The
oversize balls will stay over the sieve plate.
The operator has to collect the oversize balls and to add new balls to compensate the worn-out balls.
The same shall be charged in the Ball Collector for circulation.
Ball Gauge mounted on castor wheels for mobility is termed as Ball Gauge Trolley.
DES/OMM/TCS/DS Sheet 8
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
Injection Pipe facilitates transportation and even distribution of the balls in the branches. The balls
are injected towards counter-flow direction for homogeneous mixing and distribution over the tube
sheets.
The Injection Pipes are installed at the Cooling Water inlet pipe. Cleaning Balls are injected through
these pipes into the system. For a good ball distribution, the end of the injection pipe is directed
against the Flow.
In addition to the above, following components are provided optionally to the equipment. They are:
The Ball Monitoring System (W01) continuously monitors the size & quantity and displays the status
of percentage of effective cleaning balls and the total number of balls in circulation.
Ball Recirculating Monitor monitors the sufficient number of cleaning balls in circulation in the
condenser. BRM initiates an alarm when the number of circulating balls falls below the set value
while the preset measuring time elapses.
BROM is the common panel where Ball Recirculating Monitor (BRM) and Ball Oversize Monitor
(Ball Monitoring System (BMS)) can be operated or monitored the status individually or
simultaneously.
DP Ball Sorter is for sorting out the undersize balls. Ball Sorter Valve and Draining Valve are
provided for collect the undersize balls and draining the water respectively.
Control Panel is provided to perform functional operations (ON/OFF; OPEN/CLOSE for the system
Field drives) of the Field equipments. This panel is having Electrical starters (Motor Protection
Circuit Breaker, Power Contactor etc.), PLC units, HMI, Control circuits for the system Field
equipments. Automatic operation for the system is performed and monitored in this panel through
Panel HMI. All the Functional requirements/Process conditions/Process monitoring/Alarms are
performed in this CONTROL PANEL. DCS interface signals shall be transmitted through this
control panel.
DES/OMM/TCS/DS Sheet 9
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
Starter Panel (is provided to perform functional operations (ON/OFF for Ball Recirculating Pump
Motor) of Motors. This panel is having Electrical starters (Motor Protection Circuit Breaker, Power
Contactor, etc.) for the system Field equipments. Automatic operation for the system shall be
performed and monitored from plant DCS. DCS interface signals shall be transmitted from Field
through this Starter Panel.
DES/OMM/TCS/DS Sheet 10
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
SECTION 3 PRECONDITION
PRE-SCREENING
The prescreening must be good. There must be no coarse debris such as mussels, fish, wood,
twigs, stones, leaves, grass, deposits, etc. which can enter the condenser. Should the
prescreening be inadequate deposits can form on the tube sheet and partial blockage of the
tubes can occur thereby blocking the movement of cleaning balls. Moreover, the efficiency of
the condenser is lowered by
- a loss in heat transfer because of the lack of adequate cleaning by the balls.
- partial blockage of the tubes by coarse debris.
Equipments, pipes and rods are to be kept on wood plank without touching the mud.
All machined surfaces shall be preserved by rust preventive coating and covered by
Polythene Sheet. Machined surfaces shall not be kept in such a way that damages can occur.
Cover the finished goods with Tarpaulin/Polythene sheet to keep away from dust and rain.
Then they should be packed in wooden box and stored in a group with tag nos. for easy
identification. Cannibalization should be avoided.
All Motors and actuators shall be away from areas where water or water droplet are likely
to fall.
Electrical and Electronic goods are to be covered with 3 types of packing like thermo coal,
air bubbled sheet and polythene sheet, as applicable.
A) BALL SEPARATOR
Drain out the Circulating Water outlet line up to the bottom level of Ball Separator.
DES/OMM/TCS/DS Sheet 11
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
3.4.1 GENERAL
Purpose
To meet the accident free and also to achieve all the erection activities as per the guidance of
safety instructions.
Scope
This is applicable to staff, skilled and unskilled manpower deputed during execution of
erection & commissioning of Automatic Condenser Tube Cleaning System.
Responsibilities
It is every one responsibility to follow the safety instructions during erection work in order
to meet the accident free day.
Procedure
Obtain the line clearance (Permit) from the engineer incharge before starting up the erection
activities in case of retrofit.
During erection of heavy activities, isolate the area of erection before starting up the work.
Use the proper scaffolding and ladder whenever required to work in elevated locations.
Use the safety belts to the manpower deputed to carry out the work in elevated locations.
Follow the use if helmets, safety shoes in day-to-day activities inside the plant premises.
Ensure that all the flammables and wastages are kept away from the working area.
Ensure that the welders use appropriate shielding glass during welding activity.
Ensure that the grinders use the goggles and apron during the grinding works.
DES/OMM/TCS/DS Sheet 12
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
Ensure that the load is lifted within the safe working load of the crane, rope, chain, D-shackle
etc.
Lifting angle of the rope or chain shall be within the safety limit.
3.3.2 ELECTRICAL
Always use proper Lockout/Tag out procedures while de-energizing electrical components
as per site procedures.
Power take up points of cables provided with proper socket pin arrangement.
Always switch off the power supply after using electrical equipment.
Inspect for abnormal smell in the electrical items. And find the Root cause for the same.
Turn off and unplug any electrical device before attempting to service or repair it.
3.3.3 PRESSURE
Our equipment is designed to the Design Pressure and hydrostatic test pressure as specified
in GA Drawing. Hence, the equipment is safe for the given operating pressure condition.
3.3.4 TEMPERATURE
DES/OMM/TCS/DS Sheet 13
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
DES/OMM/TCS/DS Sheet 14
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
All the components have to be checked for physical verification with the packing list of the
consignments to make sure that the required items are totally available to take up the
Installation. This can also be crosschecked with the P&I Diagram.
P&I Diagram for the entire system has to be studied thoroughly and the respective
components for installation are to be kept separately. Necessary tools & tackles have to be
made ready and the safety instructions have to be followed strictly. The major components
such as Ball Separator, Ball Recirculating Unit and DP Measuring System can be erected in
the sequence based on the site progress and the site front availability.
If any actuators used should only be attached after the general assembly shortly before
Commissioning, adjustment of the limit switch depends on momentum and path is to be
carried out according to the separate operating instructions for actuators.
Installation is according to Plant layout / Installation Plan / P&I Diagram & GA Drawings.
Please observe the direction of flow.
PROCEDURE
1) Check matching flange fit up and welding of flange to the Cooling Water outlet pipe.
Welding is to be done by a qualified welder. Proper welding procedure should be
followed and the suitable welding rods should be used
2) Check the final dimension and install the Ball Separator as per Installation Plan.
3) Insert Gasket between both flanges and tighten the fasteners by applying uniform
torque.
4) Check the pipeline for any leakage. To avoid leakage in the pipeline the fasteners
should be tightened with uniform torque.
Note
After installation of the Ball Separator in the pipeline, at initial start up of the system the
screens shall be turned to the backwash position. In case the continuous operation of the
Condenser Tube Cleaning System is not maintained (e.g. incomplete control system) screens
shall be in operating position. Depending on debris load in the water frequent backwashing
of the Ball Separator screens has to be ensured to avoid damage to the screens.
DES/OMM/TCS/DS Sheet 15
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
Dead Spots (Dead Zones) are areas that lie outside the free flowing water segment where the
water either stagnates or eddies. There is a danger that balls will get trapped in these areas
(in extreme cases, several thousand balls can also be lodged) and will no longer be available
for cleaning the tubes. Dead Spots therefore have to be screened off with perforated metal
sheets for equalizing the pressure differences. Holes in the metal sheet / or gap between the
sheet and the wall should not be larger than 6mm. Similarly, Vent, Drain, Tap-off pipelines
to Plate Heat Exchangers within the ball recirculating loop should also be screened. These
screening portions should have more free flow area considering the pipe cross section.
The complete arrangement should be so installed that the foundations are capable of
absorbing all external forces and moments.
The bed plate, with the equipment mounted on it, should be carefully adjusted with a spirit
level. Metallic packing should be placed close to the bosses of the anchor bolts. To prevent
sagging of the base plate, metallic packing should be placed midway between the bosses
where necessary.
The anchor bolts should be embedded in quick-setting cement. Following this treatment the
bolts should be tightened uniformly. The base plate can then be grouted.
After removing the coupling from packing, thoroughly inspect to ensure that they is/are
as ordered & there no is transit damage or loss.
DES/OMM/TCS/DS Sheet 16
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
Remove protective coating/lubricant from bores & keyways. Remove all the bolts & nuts
and dismantle the assembly.
Mount hubs/adapter on their respective shafts with keys such that the shaft ends are flush
with inner face of the adapter & tighten the set screw over the keys.
For spacer type of couplings, the spacer length is normally equal to the distance between
shaft ends (DBSE) of the equipment’s. Refer the following figure.
For normal applications the shaft ends should be flush with inner face of hub/adapter. They
can protrude beyond the inner face of hub or remain inside if required. But sufficient gap
should be allowed to take care of end float of both shafts. Ensure that the effective length of
key is sufficient to transmit the rated torque of the coupling.
For RRS coupling, mount the outer ring on one of the adapters and slide it towards the
nearest equipment.
DBSE is 100mm (inclusive of G Gap 94mm + 3mm (Drive Side) + 3mm (Driven Side) (G) Gap
= 100mm. Refer Installation manual attached herewith for more details.
An alignment of the couplings is absolutely necessary in order to ensure that the pump is
mechanically free to rotate and additionally to avoid damage to the coupling. First, care
should be taken to maintain the prescribed separation (Fig. 1) between the two halves of the
coupling. Furthermore, the center axis of the shaft should join up smoothly with the coupling
(no kinks). Possible non-alignments either side-ways and / or vertical (Fig. 3) or at an angle
(Fig. 4) should be eliminated.
Alignment can be controlled using either a straight edge, or feeler gauge or calipers (Fig. 1 &
2). A coupling is judged to be aligned when a straight edge placed across both halves of the
coupling and parallel to the shaft, should have the same distance from the shaft over the
whole coupling.
After ensuring that the equipment’s are aligned properly, insert the spacer between RRS
hubs mounted earlier as explained in mounting procedure.
DES/OMM/TCS/DS Sheet 17
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
Installation shall be done according to Plant layout / Installation Plan / P&I Diagram & GA
Drawings.
PROCEDURE
PARALLEL
MIS-ALIGNMENT
FIG. 1
Using Straight Edge: Align straight edge on OD of one half measure gap at 4 places 90° apart
without rotating shafts. Allowable initial parallel misalignment of the gap is 0.1mm. The maximum
permissible parallel misalignment is 0.4mm
DES/OMM/TCS/DS Sheet 18
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
ANGULAR
MIS-ALIGNMENT
FIG. 2
Using Feeler Gauge : Measure the gap using feeler gauge at 4 places 90° apart without rotating
shafts. The difference in maximum & minimum gap will be the Total Indicated Reading (TIR), which
will be the angular misalignment present. The permissible TIR of the coupling is 0.740mm, i.e., the
angular misalignment of 0.5º. The maximum permissible TIR is 1.4mm (1º angular misalignment).
MAGNETIC V BLOCK
FIG. 3
Using Dial Gauge : Fix the dial gauge on the hub of one of the half & set plunger on the OD of
another half. Rotate the coupling slowly to one complete revolution by taking dial gauge reading at
4 places 90° apart. The permissible parallel misalignment is half of the Total Indicated Reading (TIR)
of dial gauge, i.e., 0.1mm. The maximum permissible parallel misalignment is 0.4mm
DES/OMM/TCS/DS Sheet 19
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
MAGNETIC V BLOCK
FIG. 4
Using Dial Gauge : Fix the dial gauge on hub OD of one of the halves & set plunger on the
face of the another half. Rotate the coupling slowly to one complete revolution by taking dial
readings at 4 intervals 90° apart. The Total Indicated Readings (TIR) will be the angular
misalignment. The permissible TIR of the coupling is 0.740mm, i.e., the angular
misalignment of 0.5º. The maximum permissible TIR is 1.4mm (1º angular misalignment).
Installation shall be done according to Plant layout / Installation Plan / P&I Diagram & GA
Drawings.
PROCEDURE
1) Ball Collector is horizontally mounted on the base frame of the Ball Recirculating Skid.
2) Check the Ball Collector alignment with spirit level and Tighten Base Bolts
3) All the interconnecting valves are mounted on Ball Collectors in line with drawing
orientation.
4) Check for any leakage, and if required tighten the fasteners at the inter-connecting
flanges with uniform torque.
5.10 V-PIECE
Installation is according to Plant layout / Installation Plan / P&I Diagram & GA Drawings.
Installation of Ball Distributor should be done in an easily accessible place where it can be
freely observed.
Pipes branching out or coming together at Ball Distributor should be of equal length and
should join symmetrically and without stresses.
DES/OMM/TCS/DS Sheet 20
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
PROCEDURE
1) Measure the dimensions from the center line of the sight glass to the ball transport pipes.
2) Install the Ball Distributor in between the branching pipe lines so that the connecting
flanges are perfectly matching with the center.
3) Check the overall dimensions with respect to Ball Distributor centerline.
4) Provide Gaskets on all the three connecting flanges and tighten the fasteners uniformly.
5) Check for any leakage and if required tighten the fasteners with uniform torque.
Installation shall be done according to Plant layout / Installation Plan / P&I Diagram & GA
Drawings.
Install such that the inlet bend (ball injection) faces against the cooling water flow.
PROCEDURE
1) As per installation plan mark and cut Nozzle opening in cooling water inlet pipe.
2) Fit-up and weld the injection nozzles.
3) Insert the Ball Injection Pipes into the flange nozzle along with gasket.
4) Fasten the flange and tighten uniformly.
5) Check for any leakage, if required tighten with uniform torque.
6) Care should be taken while positioning the injection nozzle in counter flow direction
Installation shall be done according to Plant layout / Installation Plan / P&I Diagram & GA
Drawings.
PROCEDURE
DES/OMM/TCS/DS Sheet 21
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
Installation shall be done according to Plant layout / Installation Plan / P&I Diagram & GA
Drawings.
PROCEDURE
When the pipes are fabricated at site, the following points are to be ensured :
1) Ball circulation pipe lengths to be marked and cut as per Installation plan.
2) Pipe edges to be ground suitably to suit matching pipe joint and weld.
3) Connecting pipe should not be under stress
4) Make sure that there are sufficient pipe supports provided.
5) Ensure for no sharp edges and burr in the pipe to avoid severing of balls
Assembly and arrangement are as per General Arrangement Drawing and the Operation
Manual of the DP Transmitter.
Note : Once the system has been assembled, the Isolation Valves should be closed.
GENERAL
Panel should be installed in such way that direct sunlight and water drippings to be avoided.
DES/OMM/TCS/DS Sheet 22
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
DES/OMM/TCS/DS Sheet 23
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
DES/OMM/TCS/DS Sheet 24
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
3.3 Motor Overload relay (not Start motor (should operate) Check
tripped) fault display (no signal).
6.6 V-PIECE
DES/OMM/TCS/DS Sheet 25
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
DES/OMM/TCS/DS Sheet 26
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
SECTION 7 COMMISSIONING
PRE REQUIREMENT
- Min./max. quantity of Cooling Water does not fall below or exceed that given in the specification
- Main CW system is to be filled by opening CW inlet/outlet Valve and vented after receiving line
clearance from the control room of the end user
- All the valves for Tube Cleaning System are closed
- the screen positions have been checked and the screens are in operation position
DES/OMM/TCS/DS Sheet 27
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
PRE REQUIREMENT
Differential Pressure across the Ball Separator screens is measured and displayed by D.P. Measuring
System. When the screens are moved to Backwash Position, the DP display should show 0 mbar.
Turbulences caused by the operation can lead to different values. In this case resetting to relative
0 mbar is to be undertaken by our Service Department.
Refer P&I Diagram for KKS Nos.
Ball Collector Inlet Valve Open Ball Collector Inlet Valve is opened
Ball Collector Outlet Valve Open Ball Collector Outlet valve is opened and
the system is in operation
Ball Separator Screen Turn the screens to Screens are turned to backwash position
backwash position
DP Measuring System
DP Transmitter DP Value is to be reset Must read 0 mbar in clean condition at
to 0 normal flow
Ball Separator Screen Turn the screens to Screens are turned to operation position
operation position
DP Measuring System
DP Transmitter Observe Must read the designed value in clean
condition at normal flow
Ball Collector Outlet Valve Close Ball Collector Outlet Valve is closed
Ball Collector Inlet Valve Close Ball Collector Inlet Valve is Closed
After checking the D.P. Measuring System, Charging of Cleaning Balls is to be followed.
Note : Cleaning Balls should be squeezed well in the water before charging
DES/OMM/TCS/DS Sheet 28
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
Basic Charge Qty. of Cleaning Squeezed balls are charged in the Ball
Charging
Balls in the Ball Collector Collector
After charging the Cleaning Balls in the Tube Cleaning System, the system can be operated now as
described in Control Philosophy in PART 2. Position of valves is also to be checked according to
Control Philosophy before starting the operation.
DES/OMM/TCS/DS Sheet 29
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
FREQUENCY
COMPONENTS / OPERATIONS
OF CHECK
Inspect general condition of the screens, screen shaft
Y
and funnel assembly.
Check smooth movement of the shafts. M
Check whether the indications on the screen shaft is
in line with marking on the shaft disc and worm gear
W
labelling at "Operating Position" & "Backwash
Position" respectively.
FREQUENCY
COMPONENTS / OPERATIONS
OF CHECK
Check for Cleanliness W
Check “O” Ring and change if necessary W
Clean Sight Glass W
Check the Gasket and change if necessary W
FREQUENCY
COMPONENTS / OPERATIONS
OF CHECK
Ball Recirculating Pump
Inspect shaft, impeller Y
Check Mechanical Seal condition and change if
W
necessary
Check oil level W
Motor
FREQUENCY
COMPONENTS / OPERATIONS
OF CHECK
Check electrical function of DP Transmitter M
DES/OMM/TCS/DS Sheet 30
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
FREQUENCY
COMPONENTS / OPERATIONS
OF CHECK
Actuator Motors
8.6 VALVES
FREQUENCY
COMPONENTS / OPERATIONS
OF CHECK
Change : Ball Seat, Stem, Gasket, Sealing, if
Y
necessary due to leakage
Check Tightness, movability and fastening M
FREQUENCY
COMPONENTS / OPERATIONS
OF CHECK
Inspect Panel internal components Y&V
Check wiring for any loose connections
M&V
and clean the wires & Terminal Blocks if required.
Check all the panel components healthiness Y&V
Legend : D - Daily
W - Weekly
M - Month
Y - Yearly
2Y - Every 2 years
HY - Half Yearly
V - Verify
DES/OMM/TCS/DS Sheet 31
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
Dismantling
1) Loosen all three hex nuts. Turn the bolts by 90 degree & pull towards you.
2) Now the pointer cover is free for removal from its seat. Check the condition of O-ring.
3) Clean the cavity below the pointer cover of any residual grease & water.
4) Clean the O-ring seat.
Fixing
Note: Measure the bolt length projecting out from the pointer cover surface in the beginning as
reference for comparison with the same after fixing the cover back in its location (slight
difference in measurement can be ignored).
This will enable you to conclude that the pointer cover is secured firmly.
DES/OMM/TCS/DS Sheet 32
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
SECTION 9 TROUBLESHOOTING
Following guidelines to identify and rectify minor faults that may occur in Equipment during
operation.
Balls stay in long, Circulating water rate is too low. Increase flow rate, use
horizontal pipes harder balls without
deaerating them, install
turbulence plate.
DES/OMM/TCS/DS Sheet 33
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
DES/OMM/TCS/DS Sheet 34
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
Pump requires Foreign material in impeller. Open Pump and check impeller.
excessive power Remove any foreign material
present.
Misalignment Check and correct
misalignment.
Shaft bent Straighten or change shaft
Mechanical Seal Excessive heat built-up, shaft Check and take preventive
vibration, shaft deflection & measure to avoid cavitation
bearing failure due to excessive
Cavitation.
Pump vibrates and Operation at very low capacity Check and take corrective action
noisy
Cavitation Check and take corrective action
DES/OMM/TCS/DS Sheet 35
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
DES/OMM/TCS/DS Sheet 36
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
Motor fails to start Main supply switched off. Check and correct
Open circuit in one line (single Check fuse and switch contacts
phasing). May be due to blown and test lines for continuity.
fuse, faulty switch contact or
broken lead.
Motor may be overloaded Reduce starting load
DES/OMM/TCS/DS Sheet 37
KEY BENEFITS OF GEA BGR
TUBE CLEANING SYSTEM & DEBRIS FILTER
DES/OMM/TCS/DSA XXI
OPERATION & MAINTENANCE MANUAL
FOR AUTOMATIC CONDENSER TUBE CLEANING SYSTEM
PART 2
CONTENTS OF PART 2
S. No. DESCRIPTION No of Sheets
1 MECHANICAL DATASHEET 8
2 DATASHEET FOR ACTUATOR 4
3 MOTOR DATASHEET 3
4 INSTRUMENT DATASHEET 4
5 STARTUP & COMMISSIONING SPARE PARTS LIST 2
6 LUBRICANT LIST 1
7 CONTROL PHILOSOPHY 15
8 P&I DIAGRAM (incl. Legend) 2
9 GENERAL ARRANGEMENT OF BALL STRAINER 1
10 GENERAL ARRANGEMENT OF BALL RECIRCULATING SKID
1
AND FOUNDATION DETAILS
11 GENERAL ARRANGEMENT OF BALL DISTRIBUTOR & BALL
6
INJECTION PIPE
12 HOOK UP DIAGRAM 1
Eder 21/03/22
INDEX
Condenser Details
- Frequency variation % +5
Angle of rotation
- Operation Deg 25
3.7
- Backwash Deg 5
4
d10 For manual operation
d1
4
d1
h11
t1
z
s
h11
c
e
h2
b1
F
d4
R
Valve attachment
R
GS 125.3 – F30 h3
d1
d3
d5
B1
d1
d2
d3
h1 L max. a
E
1)
2)
c
e
E1
E2
Version N K
without spigot
d4
h2
J I
F
B A H H
Ø d6
Ø d2
C
a. Size DN 25
c. Quantity Nos. 8
a. Size DN 80
c. Quantity Nos. 10
a. Size DN 80
c. Quantity Nos. 4
Material of construction
d) Seat PTFE
4.13 Flange / Drilling Standard Dimensions shall be as per ASME B16.5 Cl.150.SORF
Material of construction
Eder 30/03/22
INDEX
1.5 Enclosure IP 68
o
1.6 Design ambient temperature C 40°
2 Nos. - 2 NO + 2NC contacts
1.7 Position Limit Switches
(1 each in open and close position)
2 Nos. - 2 NO + 2NC contacts
1.8 Torque Switches
(1 each in open and close position)
1.9 Rating of switches 5V AC/DC – 0.004A to 50V AC/DC - 0.4A.
1.21 Insulation class Class "F" with temp. rise limited to Class "B"
1.26 Actuator Lamp Color Open - Green ; Failure - Red ; Close - Yellow
DES-TDS-AUMA-BS-ACT-SA10.2 AM01.1-60HZ GI 5320 100 09 008 Rev.A
Sheet 03 of 04
CONDENSER TUBE CLEANING SYSTEM
PURCHASER : SIEMENS ENERGY BRASIL LTDA
PROJECT : CERRADO (43150 & 43151)
2.5 Enclosure IP 68
o
2.6 Design ambient temperature C 40
2 Nos. - 2 NO + 2 NC contacts
2.7 Position Limit Switches Nos.
(1 each in open and close position)
2 Nos. - 2 NO + 2 NC contacts
2.8 Torque Switches Nos.
(1 each in open and close position)
2.9 Rating of switches 5V AC/DC – 0.004A to 50V AC/DC - 0.4A
2.21 Insulation class Class "F" with temp. rise limited to Class "B"
2.26 Actuator Lamp Color Open - Green ; Failure - Red ; Close - Yellow
DES-TDS-AUMA-ACT-SQ05.2 AM01.1-60HZ GI 5320 100 09 008 Rev.A
Sheet 04 of 04
Rev No Date Description Prepared Checked Approved
A 22-03-2022 FOR APPROVAL SANTHOSH.K SUDHARSAN.I RAVIKUMAR.N
Eder 30/03/22
INDEX
Permissible variation
1.15 a) Voltage % + 10
b) Frequency % +5
Eder 21/03/22
INDEX
Material
Performance data
Range Quantity
Material of construction
- Bourdon SS 316
2.9 Enclosure IP 65
Dial Linear
X
Eder 21/03/22
S. No Description Quantity
Push Buttons
4 1 Set.
(Normal - 1 No, Illuminated - 1 No)
8 Cleaning Balls for One Year Operation (RB / Dia 26 mm) 8060 Nos.
LUBRICANT LIST
Lubricant is
filled at site in
Ball Recirculating MOBIL - MOBIL
INDIAN OIL - SERVO 6 months (with every order to aviod
4 F01 Pump TPP - 80 / 210 Bearing Housing 0.60 Ltr SHELL - VITREA 33 VACTRA HEAVY Oil 0.60 ltr
SYSTEM 150 200 hrs.of checking) oil leakage in the
Make : Sam Turbo DUTY
bearing housing
during transit
This Bearing is
sealed type
6308ZZ C3,
6208ZZ C3. This
Motor for Ball Squirrel cage
Life lubricated, SHELL - GRADUS S2 GULF - HYPERBAR has to be
5 T91 Recirculating Pump induction motor, Bearings ESSO - UNIREX N3 Grease Not required Not required
sealed bearing V 220 LCM 3 replaced with
Make : Marathon TEFC
new after its
wornness.
Refilling is not
possible.
Rev No Date Description Prepared Checked Approved
A 15-03-2022 FOR INFORMATION PRASANNA.C VIDYAKUMAR.P RAVIKUMAR.N
X
Eder 21/03/22
PROJECT: CERRADO
(43150 & 43151)
GEA BGR ENERGY SYSTEM INDIA LIMITED
INDEX
DES/TCS/CONTROL PHILOSOPHY_1_A
PROJECT CERRADO (43150 & 43151)
CLIENT SIEMENS ENERGY BRAZIL LTDA
SYSTEM CONDENSER TUBE CLEANING SYSTEM (DN 1400)
DOCUMENT CONTROL PHILOSOPHY- CONDENSER TUBE CLEANING SYSTEM SHEET 3 of 15
DOC. No. GI 5320 106 09 014 REV.A
DES/TCS/CONTROL PHILOSOPHY_1_A
PROJECT CERRADO (43150 & 43151)
CLIENT SIEMENS ENERGY BRAZIL LTDA
SYSTEM CONDENSER TUBE CLEANING SYSTEM (DN 1400)
DOCUMENT CONTROL PHILOSOPHY- CONDENSER TUBE CLEANING SYSTEM SHEET 4 of 15
DOC. No. GI 5320 106 09 014 REV.A
1. GI 5320 100 01 001 _P&ID (INCL. LEGEND) - CONDENSER TUBE CLEANING SYSTEM
2. GI 5320 106 07 013_GENERAL ARRANGEMENT & WIRING DIAGRAM FOR CONTROL
PANEL- CONDENSER TUBE CLEANING SYSTEM.
Note:
1. This document has to be reviewed along with the P&I diagram.
3. Electric Actuators for the Ball Strainer Screens and the Ball Valves are provided with end
travel limit switches.
4. Indication and audible alarm, in the form of feedback signal, has been provided in the panel
for all failure signals.
5. 4-20mA Analog signal from the Differential Pressure Transmitters are used for DP
measurement across Ball Strainer.
6. Ready to start indication will glow only when all the electrical drives are in "HEALTHY"
condition. The "HEALTHY" condition is defined as a condition when all "FAIL"
indications are in OFF, these conditions and the availability of the "CTCS Start Permissive
(CW PUMP running feedback)" signal from the DCS will lead to switch “ON" the "READY
TO START" indication. The Ready to start indication will be on only when the system is
selected in AUTO MODE.
8. Summary failure indication is for failures in the power circuitry of individual drives.
Sequence failure indication is for run time failure of actuators during the operation of the
system.
9. When the system is in "AUTO" mode (either in LOCAL AUTO MODE OR REMOTE
AUTO MODE), it will not respond for any manual pressing of Individual buttons and
selection of mode selector in HMI. And will respond only after the system is stopped.
DES/TCS/CONTROL PHILOSOPHY_1_A
PROJECT CERRADO (43150 & 43151)
CLIENT SIEMENS ENERGY BRAZIL LTDA
SYSTEM CONDENSER TUBE CLEANING SYSTEM (DN 1400)
DOCUMENT CONTROL PHILOSOPHY- CONDENSER TUBE CLEANING SYSTEM SHEET 5 of 15
DOC. No. GI 5320 106 09 014 REV.A
10. If Power fails, in any stage of the logic sequence - all equipment will come to initial position
when power is restored excepts screens, and manual interference is required for restarting.
I.e. when the power fails all the drives will be in their current position either open or close
and operation or backwash. Upon resumption of power the valves will come to close
position if in open position
Note: Indication, selector mentioned in this section of document is referring to soft indication
available in the Touch screen HMI, which is located in the CTCS LOCAL CONTROL PANEL.
For MANUAL mode of operation, Manual mode selection has to be selected in the Local Panel HMI.
The system can be operated through Local Panel HMI by activating function keys for individual
drives.
This Manual mode is used predominantly for testing & commissioning purposes.
Note: Please note there will be no interlocking of equipments in manual mode. Any equipment
can be operated without any interlock.
e. Valves (BALL COLLECTOR VENT VALVE, BALL COLLECTOR DRAIN VALVE &
BALL COLLECTOR BYPASS VALVE) to be in closed position.
g. All FAIL Indications and Summary/Sequence Failure Indications shall be in OFF position.
h. Start Permissive from DCS shall be available. (CW Pump running feedback shall be available).
This feedback signal is required to ensure the water flow inside the system. Based on this Auto
operation shall be started.
DES/TCS/CONTROL PHILOSOPHY_1_A
PROJECT CERRADO (43150 & 43151)
CLIENT SIEMENS ENERGY BRAZIL LTDA
SYSTEM CONDENSER TUBE CLEANING SYSTEM (DN 1400)
DOCUMENT CONTROL PHILOSOPHY- CONDENSER TUBE CLEANING SYSTEM SHEET 6 of 15
DOC. No. GI 5320 106 09 014 REV.A
i. If the INITIAL CONDITIONS are satisfied, the operation of the system can be executed in
the following sequence. In case the initial conditions are not met, then the relevant
equipment will be brought to the required state to meet the INITIAL CONDITIONS.
j. Select LOCAL AUTO/REMOTE AUTO function to “LOCAL AUTO” position.
k. READY TO START Indication will be ON.
l. "AUTO STOP" indication will be ON.
m. Press the "AUTO START” function key to start the system in "LOCAL AUTO" mode.
5.2. SYSTEM OPERATION SEQUENCE
When the System is Healthy, Initial conditions are fulfilled then on pressing the
AUTO START the following operations take place in sequence.
a. AUTO START indication will start to blink and the AUTO STOP indication will be
switched OFF.
b. Simultaneously Ball Collector Inlet Valve will move from close position to open position
and The Ball Recirculating Pump Motor is switched ON, as soon as the Ball Collector
Inlet Valve starts opening.
c. A time-gap of 5 minutes is given by the PLC (Watering Timer – PLC internal timer) for
the water to be absorbed by the sponge rubber balls. This cycle is known as the
WATERING CYCLE.
d. After the end of 5 minutes. The Ball Collector Outlet Valve is opened. The cleaning balls
are now being injected into the CW inlet pipeline. The AUTO START indication will
glow steadily
e. The SYSTEM CYCLE RUN TIMER (System Cycle Run Timer - PLC Internal Timer)
picks up for 4 hrs.
f. After 4 hrs. SYSTEM CYCLE RUN TIMER elapses and the following sequence of
operation takes place.
g. The Ball Collector Outlet Valve is closed.
h. There should be a time gap of 30 minutes to allow for ball collection in the Ball Collector
(Ball Collection Timer - PLC Internal Timer)
i. The Ball Collector Inlet Valve is closed.
j. Ball Recirculating Pump Motor is switched OFF, after the Ball Collector Inlet Valve is
fully closed.
k. The system will be in Idle Timer (PLC Internal Timer - 20 Hours) mode.
l. After Idle Timer the system will start again and cycles has been repeated. In the
Consequent cycles the watering Cycle is not carried out and skipped. As the balls are in
circulation, the needed watering of balls is met automatically. The watering cycle is
performed whenever a new cycle is started by pressing AUTO START.
DES/TCS/CONTROL PHILOSOPHY_1_A
PROJECT CERRADO (43150 & 43151)
CLIENT SIEMENS ENERGY BRAZIL LTDA
SYSTEM CONDENSER TUBE CLEANING SYSTEM (DN 1400)
DOCUMENT CONTROL PHILOSOPHY- CONDENSER TUBE CLEANING SYSTEM SHEET 7 of 15
DOC. No. GI 5320 106 09 014 REV.A
m. Hence after Idle Timer, system cycle operation shall be continued followed by the next
cycle of operations. This cycle of operation continuously running up to Auto
Stop/Sequence stop/Trip conditions.
5.3 BACKWASH SEQUENCES
If the Differential pressure across the Ball Strainer exceeds 40 mbar* (DP Value may vary
depending on the site condition) the BACKWASH SEQUENCE will be carried out.
During the AUTO Mode of operation, BACKWASH sequence can occur in the following
conditions:
Note: Once the BACKWASH operation is started in any of the conditions said above, the
BACKWASH sequence will be completed even if the DP is reduced in the middle of the cycle.
During AUTO Mode of operation, when the SYSTEM CYCLE RUN TIMER is
ON, if the differential pressure across the Ball Strainer exceeds 40 mbar*, the following
operations are carried out.
i. A time gap of 30 seconds (BACKWASH SEQUENCE LEAD TIMER - PLC internal
timer, 30seconds) is given to ensure that the increase in differential pressure is not due to
any momentary surge.
ii. If the differential pressure remains above 40 mbar* for more than 30 seconds, the
BACKWASH Indication will glow.
iii. The System Cycle Run Timer will hold its present value.
iv. The Ball Collector Outlet Valve is closed.
v. There will be a time gap of 30minutes (BALL COLLECTION TIMER – PLC internal
timer) to allow for ball collection in the Ball Collector.
vi. After the elapse of Ball Collection Timer, the Ball Collector Inlet Valve is closed.
vii. The Ball Recirculating Pump Motor is switched off, after the Ball Collector Inlet Valve is
fully closed.
DES/TCS/CONTROL PHILOSOPHY_1_A
PROJECT CERRADO (43150 & 43151)
CLIENT SIEMENS ENERGY BRAZIL LTDA
SYSTEM CONDENSER TUBE CLEANING SYSTEM (DN 1400)
DOCUMENT CONTROL PHILOSOPHY- CONDENSER TUBE CLEANING SYSTEM SHEET 8 of 15
DOC. No. GI 5320 106 09 014 REV.A
viii. The Ball Strainer Screens are moved from the "OPERATION" position to the
“BACKWASH" position.
ix. A time gap of 30minutes (BACKWASH TIME – PLC internal timer) is given for washing
the screens off the debris. The Ball Strainer Screens are moved from the "BACKWASH"
position to the "OPERATION" position.
x. A time gap of 2 Minutes is given for DP to stabilize after the screen comes to operation
position (DP stabilizing timer – (PLC Internal Timer).
xi. If the DP is less than 40 mbar*, the BACKWASH indication will be switched OFF. And
following steps will be carried out.
a) Ball Collector Inlet Valve will move from close position to open position.
b) The Ball Recirculating Pump Motor is switched ON, as soon as the Ball Collector Inlet
Valve starts opening.
c) The Ball Collector Outlet Valve is opened.
d) The System Cycle Run Timer will continue from the hold value.
xii. If there is no reduction still, then the Ball Strainer Screens will go to backwash again then
the BACKWASH indication will start to blink and the alarm is switched ON, System
Cycle Run Timer Will Reset and the screens will remain in BACKWASH POSITION.
Press FAULT ACKNOWLEDGE, the BACKWASH indication will glow steadily and the
alarm is switched OFF. Then Manual intervention is required to ascertain the cause of
continuous increase in DP. After rectification of DP, press FAULT RESET the
BACKWASH indication will go off. The system must be restarted by selecting the AUTO
MODE.
5.3. A.2 BACKWASH OPERATION –WHEN IDLE TIMER ON
During AUTO Mode of operation, when the IDLE TIMER is ON, if the differential
pressure across the Ball Strainer exceeds 40 mbar*, the following operations are carried
out.
i. A time gap of 30 seconds (BACKWASH SEQUENCE LEAD TIMER - PLC internal
timer, 30 seconds) will be given to ensure that the increase in differential pressure is not
due to any momentary surge. BACKWASH Indication ON. The IDLE Timer will hold
its present value.
ii. The Ball Strainer Screens will be moved from the "OPERATION" position to the
"BACKWASH" position.
iii. A time gap of 30 minutes (BACKWASH TIME – PLC internal timer) is given for
washing the screens off the debris. After 30 minutes of backwash, the Ball Strainer
Screens are moved from the "BACKWASH" position to the "OPERATION" position.
iv. A time gap of 2 Minutes is given for DP to stabilize after the screen comes to operation
position (DP stabilizing timer – PLC Internal Timer)
DES/TCS/CONTROL PHILOSOPHY_1_A
PROJECT CERRADO (43150 & 43151)
CLIENT SIEMENS ENERGY BRAZIL LTDA
SYSTEM CONDENSER TUBE CLEANING SYSTEM (DN 1400)
DOCUMENT CONTROL PHILOSOPHY- CONDENSER TUBE CLEANING SYSTEM SHEET 9 of 15
DOC. No. GI 5320 106 09 014 REV.A
v. If the DP is less than 40 mbar*, the BACKWASH indication will be switched OFF.
The system will be continuing idle timer from the hold value.
vi. If there is no reduction still, then the Ball Strainer Screens will go to backwash again
then the BACKWASH indication will start to blink and the alarm is switched ON, Idle
timer will reset and the screens will remain in Backwash Position. Press Fault
Acknowledge, the BACKWASH indication will glow steadily and the alarm is switched
OFF. Then Manual intervention is required to ascertain the cause of continuous increase
in DP. After rectification of DP, press Fault Reset the BACKWASH will go off. The
system must be restarted by selecting the AUTO MODE.
5.3. B. BACKWASH DURING MANUAL Mode
During Manual mode of operation, if the differential pressure across the Ball Strainer exceeds
40 mbar*, the following operations are to be carried out.
1. A time gap of 30 seconds (BACKWASH SEQUENCE LEAD TIMER - PLC internal
timer, 30 seconds) will be given to ensure that the increase in differential pressure is not
due to any momentary surge.
2. The Hooter is switched ON. And BACKWASH will start to blink.
3. Press Fault Acknowledge. The Hooter will be cut-off. And the BACKWASH indication
will glow steadily.
4. Move the Ball Strainer Screens to Backwash position by pressing the Backwash.
5. After 30 minutes of backwashing, bring the Ball Strainer Screens to operation position.
6. Check the DP across the screens. If the DP > 40 mbar* still, then repeat the procedure
from 4 to 6, as said above.
7. If the DP reduces i.e. DP < 40 mbar*. Press Fault Reset, then the BACKWASH
indication is turned OFF.
5.4. AUTO STOP SEQUENCES
When the AUTO STOP is pressed, AUTO STOP sequence is carried out. The AUTO STOP
can take place in following conditions.
During the AUTO operation, when the WATERING TIMER is ON, if AUTO STOP is
pressed, following sequence of operations will take place:
DES/TCS/CONTROL PHILOSOPHY_1_A
PROJECT CERRADO (43150 & 43151)
CLIENT SIEMENS ENERGY BRAZIL LTDA
SYSTEM CONDENSER TUBE CLEANING SYSTEM (DN 1400)
DOCUMENT CONTROL PHILOSOPHY- CONDENSER TUBE CLEANING SYSTEM SHEET 10 of 15
DOC. No. GI 5320 106 09 014 REV.A
b. As soon as the feedback for Ball Collector Inlet Valve close is received, the Ball Recirculating
Pump Motor will be stopped.
5.4.B AUTO STOP SEQUENCES - WHEN THE SYSTEM CYCLE RUN TIMER ON
During the AUTO operation, when the SYSTEM CYCLE RUN TIMER is ON, if AUTO
STOP is pressed, following sequence of operation will take place:
b. There will be a time gap of 30minutes (BALL COLLECTION TIMER –Adjustable PLC
internal timer) to allow for ball collection in the Ball Collector G01.
d. As soon as the feedback for Ball Collector Inlet Valve close is received, the Ball Recirculating
Pump Motor will be switched off.
During the AUTO operation, when the BALL COLLECTION TIMER is ON, if AUTO
STOP is pressed, following sequence of operation will take place:
a. System continues the ball collection till the Ball Collection Timer elapses.
b. At the end of Ball Collection Timer elapses, Ball Collector Inlet Valve will be closed.
c. As soon as the feedback for Ball Collector Inlet Valve close is received, the Ball
Recirculating Pump Motor will be stopped.
During the AUTO operation, when the IDLE TIMER is ON, if AUTO STOP is pressed then
following sequence of operation will take place:
DES/TCS/CONTROL PHILOSOPHY_1_A
PROJECT CERRADO (43150 & 43151)
CLIENT SIEMENS ENERGY BRAZIL LTDA
SYSTEM CONDENSER TUBE CLEANING SYSTEM (DN 1400)
DOCUMENT CONTROL PHILOSOPHY- CONDENSER TUBE CLEANING SYSTEM SHEET 11 of 15
DOC. No. GI 5320 106 09 014 REV.A
"CTCS Start Permissive (CW PUMP running feedback)" signal from DCS shall enable the
permission for the CONDENSER TUBE CLEANING SYSTEM. When this signal comes from
DCS and initial condition are met, then we can start the CTCS by Local Auto/Remote Auto.
i.e. Auto start in Local panel/Remote Auto start from DCS. However, if this start permissive is
cut off during operation then Auto operation will be stopped.
a. Press the BRM ON function key manually in the PLC panel HMI, during system running
operation (Ball Injection cycle).
And the following operation takes place.
1. BRM Counting timer will be started (Adjustable timer – 10 Minutes, Present inside the
PLC panel).
b. 12 – 24 V DC supply is given to sensor. (12-24 V DC is generated by the BRM counter
provided in the PLC panel).
c. During this 10 Minutes of operation if counting input will be met set value* the system is
considered to be operating with sufficient number of balls.
During this 10 Minutes of operation if counting input will be not met set value* the system is
considered to be operating with insufficient number of balls. And BRM fail indication will be
generated. This BRM fail indication shall be monitored in the panel HMI.
d. Operator has to press reset function key (HMI). BRM fail indication shall be off.
Based on the balls output, system shall be allowed to continue for further system operation.
Note: * For setting value arriving procedure refer O&M Manual (Submitted during final
engineering).
DES/TCS/CONTROL PHILOSOPHY_1_A
PROJECT CERRADO (43150 & 43151)
CLIENT SIEMENS ENERGY BRAZIL LTDA
SYSTEM CONDENSER TUBE CLEANING SYSTEM (DN 1400)
DOCUMENT CONTROL PHILOSOPHY- CONDENSER TUBE CLEANING SYSTEM SHEET 12 of 15
DOC. No. GI 5320 106 09 014 REV.A
a. All the drives excepting the one under failure move to INITIAL position.
b. Audio alarm ON, Corresponding drive Fail Indication
Starts Blinking and Summary or Sequence Fail Indication Starts Blinking.
c. Press FAULT ACKNOWLEDGE to reset audio alarm.
The Corresponding Drive Fail Indication glows steadily and Summary or Sequence Fail Indication
glows steadily.
d. The operation sequence will reset to initial condition and AUTO START will be OFF and
AUTO STOP indication is ON.
e. Bring the system to Manual Mode.
f. AUTO STOP indication goes OFF. Rectify the fault.
g. RESET Fault by pressing the FAULT RESET.
h. Corresponding drive Fail Indication switch OFF and Summary or Sequence
Fail Indication switch OFF.
i. Bring the System to Auto Mode
j. READY TO START & AUTO STOP indications are ON and the system
is ready for auto operation as per normal automatic sequence.
1. If Power Supply fails during Auto Operation, on resume of power, all the drives will be brought to
initial condition automatically.
2. If the START PERMISSIVE signal goes OFF during the auto operation, the system stops
immediately as per SEQUENCE STOP Logic.
3. The System can be operated in MANUAL mode to select MANUAL mode the selector (in LCP) to
be selected to MANUAL mode. This mode is predominately used for testing and commissioning
purposes. There is no interlock between the equipment’s in MANUAL mode.
2. The System can be operated in REMOTE AUTO mode to select REMOTE AUTO mode the
selector (in the LCP) to be selected to REMOTE AUTO mode. This mode of operation is same as
of LOCAL AUTO MODE except the start and stop are initiated from DCS instead from Local
panel.
DES/TCS/CONTROL PHILOSOPHY_1_A
PROJECT CERRADO (43150 & 43151)
CLIENT SIEMENS ENERGY BRAZIL LTDA
SYSTEM CONDENSER TUBE CLEANING SYSTEM (DN 1400)
DOCUMENT CONTROL PHILOSOPHY- CONDENSER TUBE CLEANING SYSTEM SHEET 13 of 15
DOC. No. GI 5320 106 09 014 REV.A
3. When the system is in "AUTO" mode (either in LOCAL AUTO MODE OR REMOTE AUTO
MODE), it will not respond for any manual pressing of Individual buttons and selector buttons in
the HMI.
4. However Manual override is possible by pressing the "Sequence stop" button in the Local panel.
Then system will come to initial condition immediately. Which means motors shall be switched Off
and Actuators shall move towards close position.
5. Ball Recirculating Pump Motor has to be switched off after completion of Ball Collector Inlet
Valve fully closed.
After the equipment is checked for the healthiness, reset the Motor Protection Circuit Breaker.
Press FAULT RESET, so that FAIL Indication goes OFF.
If Collective Fault (Thermal Fail or torque fail) occurs in the actuator, corresponding actuator
FAIL will glow and the Corresponding command will de-energize, hooter is switched on. Press
FAULT ACKNOWLEDGE Key, Indication will glow steadily. And alarm is switched off.
After bringing the actuator to healthy condition, press FAULT RESET, FAIL Indication goes
OFF.
11.3 RUN TIME ERROR
During running period, if time taken by the Actuator is over headed, respective command will
be de-energized by PLC Internal Timer called runtime error timer and FAIL will blink.
ACTUAL SETTING
RUNNING PERIOD FOR FAIL
1. Screen Actuators 22 Sec. 26 Sec.
2. Valve Actuator 16 Sec. 20 Sec.
Press FAULT ACKNOWLEDGE, FAIL indication will glow steadily and after the End Travel
limit, press FAULT RESET, and FAIL indication will go OFF.
During operation of the equipment, if problem in the Power Circuit i.e. problem in Over Load
Relay and Main Circuit Breaker, torque operation, and thermal switch open will cut off supply
to the particular equipment. The corresponding FAIL INDICATION will blink along with the
SUMMARY FAILURE Indication.
DES/TCS/CONTROL PHILOSOPHY_1_A
PROJECT CERRADO (43150 & 43151)
CLIENT SIEMENS ENERGY BRAZIL LTDA
SYSTEM CONDENSER TUBE CLEANING SYSTEM (DN 1400)
DOCUMENT CONTROL PHILOSOPHY- CONDENSER TUBE CLEANING SYSTEM SHEET 14 of 15
DOC. No. GI 5320 106 09 014 REV.A
During operation of the equipment, if problem in the Control Circuit i.e. runtime error, supply
to the particular equipment will cut off. The corresponding FAIL indication will blink along
with the SEQUENCE FAILURE indication.
The SEQUENCE / SUMMARY FAILURE indication will blink along-with the corresponding
equipment FAIL indication for fault condition. The alarm will also be ON.
Press FAULT ACKNOWLEDGE, the SEQUENCE / SUMMARY FAILURE and
corresponding equipment FAIL indications will glow steadily. The alarm will be switched
OFF.
After rectification of the fault, Press FAULT RESET, SEQUENCE / SUMMARY FAILURE
indication and corresponding equipment FAIL indication will go OFF.
If at any point during the operation of the CONDENSER TUBE CLEANING SYSTEM in the
“AUTO” mode, manual over-ride is possible by pressing the EMERGENCY STOP. The
CONDENSER TUBE CLEANING SYSTEM will be brought to the initial condition
immediately.
If power fails, in any of the logic sequence – manual interference is required for restarting.
a. On resume of Power Supply all the drives will be brought to initial position
(OFF/CLOSE/OPERATION) automatically.
b. Ensure the Bypass Valve in open condition.
c. Simultaneously Switch on the Ball Recirculating Pump Motor and Ball Collector Inlet
Valve manually by pressing Open.
d. Wait for 30 Minutes for Ball Collection.
e. After 30 Minutes all balls in the system will be collected in the Ball Collector.
f. Now close the Ball Collector Inlet Valve.
g. Switch off the Ball Recirculating Pump Motor
h. Bring the system to Auto mode.
i. Start the system in Auto mode using Auto start selection. Auto sequence will commence as
per normal operation sequence.
DES/TCS/CONTROL PHILOSOPHY_1_A
PROJECT CERRADO (43150 & 43151)
CLIENT SIEMENS ENERGY BRAZIL LTDA
SYSTEM CONDENSER TUBE CLEANING SYSTEM (DN 1400)
DOCUMENT CONTROL PHILOSOPHY- CONDENSER TUBE CLEANING SYSTEM SHEET 15 of 15
DOC. No. GI 5320 106 09 014 REV.A
BACKWASH
6. OFF CLOSE CLOSE BACKWASH
CYCLE
DES/TCS/CONTROL PHILOSOPHY_1_A
X
Eder 20/04/22
X
Eder 30/03/22
X
Eder 27/06/22
Rev Date Description Prepared Checked Approved
No
A 14-03-2022 FOR APPROVAL K. SANTHOSH S. SHANTHI A.K. MANOHARAN
Eder 21/03/22
Sl.
DESCRIPTION
No.
H11 -- 100 80 80 141.4 200 161 200 100 200 38 Kg. 1 No. 1 No.
H12 -- 80 80 80 141.4 200 161 200 100 200 36 Kg. 1 No. 1 No.
DESIGN DATA :
BALL DISTRIBUTOR
PART MATERIAL QTY./
DESCRIPTION REMARKS
No. SPECIFICATION TAG No.
CARBON STEEL
1 SHELL 1
A 106 Gr.B
CARBON STEEL
2 COVERING PLATE 1
A 516 Gr.70
CARBON STEEL
3 PIPE (N1) 1
A 106 Gr.B
CARBON STEEL
4 FLANGE (N1) 1
A 105
CARBON STEEL
5 PIPE (N2 & N3) 2
A 106 Gr.B
CARBON STEEL
6 FLANGE (N2 & N3) 2
A 105
CARBON STEEL
7 SHELL FLANGE 1
A 516 Gr.70
CARBON STEEL
9 SPECIAL FLANGE 1
A 516 Gr.70
STUD, DOMED NUT STAINLESS STEEL
10 8 SET
AND WASHER SS 316 (A4)
DES-TDS-BD-ASME-RF-CS-106B
GI 5320 104 02 004
SHEET 4 OF 6
2. BALL INJECTION PIPE
DESIGN DATA :
PART 3
CONTENTS OF PART 3
S. No. DESCRIPTION No of Sheets
1 WORM GEAR FOR BALL STRAINER 49
2 ACTUATOR FOR BALL STRAINER 62
3 ACTUATOR FOR BALL VALVE 66
4 MECHANICAL SEAL FOR PUMP 13
5 MOTOR FOR BALL RECIRCULATING PUMP 13
6 D.P. TRANSMITTER 20
7 CLEANING BALLS 6
8 BALL RECIRCULATING MONITOR 18
2
GS 50.3 – GS 250.3
Table of contents
3
GS 50.3 – GS 250.3
Safety instructions
1. Safety instructions
1.1. Basic information on safety
Standards/directives Our products are designed and manufactured in compliance with recognised
standards and directives. This is certified in a Declaration of Incorporation and an
EU Declaration of Conformity.
The end user or the contractor must ensure that all legal requirements, directives,
guidelines, national regulations and recommendations with respect to assembly,
electrical connection, commissioning and operation are met at the place of installation.
Safety instructions/warn- All personnel working with this device must be familiar with the safety and warning
ings instructions in this manual and observe the instructions given. Safety instructions
and warning signs on the device must be observed to avoid personal injury or property
damage.
Qualification of staff Assembly, electrical connection, commissioning, operation, and maintenance must
be carried out exclusively by suitably qualified personnel having been authorised by
the end user or contractor of the plant only.
Prior to working on this product, the staff must have thoroughly read and understood
these instructions and, furthermore, know and observe officially recognised rules
regarding occupational health and safety.
Work performed in potentially explosive atmospheres is subject to special regulations
which have to be observed. The end user or contractor of the plant are responsible
for respect and control of these regulations, standards, and laws.
Commissioning Prior to commissioning, it is important to check that all settings meet the requirements
of the application. Incorrect settings might present a danger to the application, e.g.
cause damage to the valve or the installation. The manufacturer will not be held
liable for any consequential damage. Such risk lies entirely with the user.
Maintenance To ensure safe device operation, the maintenance instructions included in this manual
must be observed.
Any device modification requires prior consent of the manufacturer.
1.2. Range of application
AUMA part-turn gearboxes are designed for the operation of industrial valves, e.g.
butterfly valves, ball valves and dampers.
Other applications require explicit (written) confirmation by the manufacturer.
4
GS 50.3 – GS 250.3
Safety instructions
Information The term Information preceding the text indicates important notes and information.
5
GS 50.3 – GS 250.3
Safety instructions
6
GS 50.3 – GS 250.3
Identification
2. Identification
2.1. Name plate
Figure 1: Arrangement of name plates
7
GS 50.3 – GS 250.3
Identification
Order number The product can be identified using this number and the technical data as well as
order-related data pertaining to the device can be requested.
Please always state this number for any product inquiries.
On the Internet at http://www.auma.com, we offer a service allowing authorised
users to download order-related documents such as wiring diagrams and technical
data (both in German and English), inspection certificates and the operation
instructions when entering the order number.
Serial number
Description of the serial number (with the example of 0512CG12345)
05 15 CG12345
05 Positions 1 + 2 : Assembly in week = week 05
15 Positions 3 + 4 : Year of manufacture = 2015
CG12345 Internal number for unambiguous product identification
Reduction ratio The reduction ratio within gearing and primary reduction gearing reduces the required
input torques and increases the operating time.
Factor Mechanical conversion factor for actuator size determination:
Input torque = required valve torque (output torque)/factor
Type of lubricant AUMA abbreviation for type of lubricant used in the gear housing.
Duty class The duty class specifies the application range of a gearbox relating to the lifetime
requirements. The duty class is only specified for gearboxes in operation mode class
A (OPEN-CLOSE duty).
● Duty class 1: suitable for motor operation, meets the lifetime requirements of
EN 15714-2
● Duty class 2: suitable for motor operation of rarely or infrequently operated
valves which do not exceed 1,000 operations across their total lifetime.
● Duty class 3: suitable (exclusively) for manual operation with approximately
250 operations, in compliance with the specified lifetime requirements in EN
1074-2.
Please refer to separate Technical data for further information on duty classes.
Version The first letter of the version indicates the position of the worm shaft in relation to
the worm wheel (view on input shaft).
The second letter indicates the direction of rotation at the output drive (view on
housing cover) for clockwise rotation at the input shaft.
8
GS 50.3 – GS 250.3
Identification
Versions: Worm shaft position and direction of rotation of output drive GS 50.3 – GS 250.3
RR LL RL LR
Initials Direction of rotation at input shaft Position of worm shaft Direction of rotation at output drive
RR Clockwise Right Clockwise
LL Clockwise Left Counterclockwise
RL Clockwise Right Counterclockwise
LR Clockwise Left Clockwise
Data Matrix code When registered as authorised user, you may use the AUMA Support App to scan
the Data Matrix code and directly access the order-related product documents without
having to enter order number or serial number.
Figure 4: Link to the App store:
9
GS 50.3 – GS 250.3
Transport, storage and packaging
The coupling is not secured within the gearbox. Risk of falling out!
Injury hazard.
→ Remove coupling from gearbox housing prior to transport.
Figure 5: Coupling
Hovering load!
Risk of death or serious injury.
→ Do NOT stand below hovering load.
→ Attach ropes or hooks for the purpose of lifting by hoist only to housing and NOT
to handwheel.
→ Check eyebolts for tight seat in housing (verify reach of the screws).
→ Observe manufacturer specifications for fixing lifting straps and round slings.
→ Respect total weight of combination (gearbox, primary reduction gearing, actu-
ator).
Information Up to size 125.3, gearboxes are not equipped with special transport threads. Sus-
pension is possible using lifting straps/round slings.
From size 160.3, transport threads are provided for fixing with eyebolts. Eyebolts
are not included in the scope of delivery.
10
GS 50.3 – GS 250.3
Transport, storage and packaging
11
GS 50.3 – GS 250.3
Transport, storage and packaging
Strap/sling arrangement
[1] View on front
[2] View on rear
Table 1:
Weights including grease filling in gear housing
Type Standard version Version with base and lever
[kg]1) [kg]
GS 50.3 7 10
GS 63.3 12 23
GS 80.3 16 29
GS 100.3 (52:1/107:1) 33 58
GS 100.3 (126:1/160:1/208:1) 39 64
GS 125.3 (52:1) 40 89
GS 125.3 (126:1/160:1/208:1) 46 95
GS 160.3 (54:1) 80 139
GS 160.3 (218:1/442:1/880:1) 91 150
GS 200.3 (53:1) 140 258
GS 200.3 (214:1/434:1) 160 278
GS 200.3 (864:1/1 752:1) 170 288
GS 250.3 (52:1) 273 467
GS 250.3 (210:1/411:1) 296 490
GS 250.3 (848:1/1 718:1) 308 502
Additional weights when mounting extension flanges
F30 for GS 125.3 18
F35 for GS 160.3 33
F40 for GS 200.3 48
F48 for GS 250.3 75
3.2. Storage
Long-term storage For long-term storage (more than 6 months), observe the following points:
12
GS 50.3 – GS 250.3
Transport, storage and packaging
1. Prior to storage:
Protect uncoated surfaces, in particular the output drive parts and mounting
surface, with long-term corrosion protection agent.
2. At an interval of approx. 6 months:
Check for corrosion. If first signs of corrosion show, apply new corrosion protec-
tion.
3.3. Packaging
Our products are protected by special packaging for transport when leaving the
factory. The packaging consists of environmentally friendly materials which can easily
be separated and recycled. We use the following packaging materials: wood,
cardboard, paper, and PE foil. For the disposal of the packaging material, we
recommend recycling and collection centres.
13
GS 50.3 – GS 250.3
Assembly
4. Assembly
1. For input shafts with keyway: Place retaining ring [1] onto input shaft [2].
2. If required, fit spacer [3].
3. Slip handwheel [4] onto input shaft.
4. If required, fit spacer [5].
5. Secure handwheel [4] using the retaining ring [6] supplied.
6. Fit ball handle [7] to handwheel.
4.3. Chainwheel: mount
For gearboxes to be operated via chainwheel, the chainwheel is supplied separately.
Fitting is performed on site according to the description below.
Information Use in explosion-proof atmospheres is not permitted!
Gearboxes supplied without chainwheel can be retrofitted with a chainwheel. For
sizes 50.3 – 80.3, a special bearing cover is to be mounted for retrofitting.
14
GS 50.3 – GS 250.3
Assembly
15
GS 50.3 – GS 250.3
Assembly
16
GS 50.3 – GS 250.3
Assembly
Refer to the operation instructions pertaining to the multi-turn actuator for indications
on how to mount multi-turn actuators to gearboxes.
This chapter supplies basic information and instructions which should be considered
in addition to the operation instructions of the multi-turn actuator.
Screws to actuator
Screws are included in the scope of delivery of the gearbox for mounting AUMA
multi-turn actuators. When mounting other actuators, the screws might be either too
long or too short (insufficient reach of screws).
Risk of actuator falling off in case inappropriate screws used should shear.
Risk of death or serious injury!
→ Check length of screws.
→ Only use screws with strength class specified herein.
The reach of screws must be sufficient for the internal threads to ensure the
supporting strength of the device and to accept the lateral forces due to the applied
torque.
Screws which are too long could make contact with the housing parts, presenting
the risk that the device performs a radial shift with respect to the gearbox. This can
lead to shearing of the screws.
4.4.1. Mounting positions Multi-turn actuators with part-turn gearboxes
GS versions LL and LR
A1) B C D
1) Caution: For multi-turn actuators SA/SAR 14.2 and 14.6 with GS 125.3, mounting position C is not possible for RR and RL versions;
mounting position A is not possible for LL and LR versions.
Please consider possible space constraints on site when selecting the mounting
position.
Mounting positions may easily be changed at a later date.
17
GS 50.3 – GS 250.3
Assembly
Table 2:
Suitable input mounting flanges
Gearboxes Reduction ratio Input shaft Input mounting flange for mounting multi-turn actuators
[mm] EN ISO 5210 DIN 3210
GS 50.3 51:1 16 F07, F10 G0
51:1 20
GS 63.3 F07, F10 G0
82:1 20
53:1 20
GS 80.3 F07, F10 G0
82:1 20
52:1 30/(20) F14 (F10) G1/2 (G0)
107:11) 30 F14 (F10) G1/2 (G0)
GS 100.3 126:11) 30 F10 G0
260:11) 30 F10 G0
208:11) 30 F10 G0
52:1 30 F14 G1/2
126:11) 30/(20) F14 (F10) (G0)
GS 125.3
160:11) 30/(20) F14 (F10) (G0)
208:11) 20 F10, F14 G0
54:1 30 F16 (F14) G3 (G1/2)
218:11) 30/(20) F14 (F10) G1/2 (G0)
GS 160.3
442:11) 20 F10 G0
880:11) 20 F10 G0
53:1 40 F25 (F16) (G3)
1) 30 F14 G1/2
GS 200.3 434:11) 30/(20) F14 (F10) G1/2 (G0)
864:11) 20 F14 G0
1,752:11) 20 F10 G0
52:1 50 F30 (F25) –
210:11) 40/(30) F16 (F14) G3 (G1/2)
GS 250.3 411:11) 30 F14 G1/2
848:11) 30/(20) F14 (F10) G1/2 (G0)
1 718:11) 20 F10 G0
1) Equipped with primary reduction gearing or planetary gearing to reduce input torques.
Assembly steps 1. Clean mounting faces, thoroughly degrease uncoated mounting surfaces.
Figure 15: Mounting example, input mounting flange fitted to gearbox with primary
reduction gearing
18
GS 50.3 – GS 250.3
Assembly
The gearbox is mounted to the valve using a coupling (standard) or via lever. Separate
instructions are available for actuator mounting to the valve when equipped with
base and lever.
4.5.1. Output drive for coupling
Assembly steps 1. If required, move gearbox in same end position as valve using the handwheel.
2. Clean mounting faces, thoroughly degrease uncoated mounting surfaces.
Information: To avoid contact corrosion, we recommend applying a surface
sealing agent on the uncoated contact surfaces for gearboxes without powder
coating.
19
GS 50.3 – GS 250.3
Assembly
[1] Coupling
[2] Valve shaft
[3] Grub screw
[4] Clamping washer and screw with curved spring lock washer
Figure 18: Mounting positions for coupling
Table 4:
Dimensions [mm] GS 50.3 GS 63.3 GS 80.3 GS 100.3 GS 125.3
EN ISO 5211 F05 F10 F10 F12 F12 F14 F14 F16 F16 F25 F301)
X max. 6 14 7 10 13 23 22 22 17 17 35
Y max. 5 5 18 13 18 5 13 8 35 27 0
L max. 61 61 61 73 76 78 88 123 123 126 126
Table 5:
Dimensions [mm] GS 160.3 GS 200.3 GS 250.3
EN ISO 5211 F25 F301) F35 F30 F35 F401) F35 F40 F481)
X max. 15 30 30 19 44 44 8 13 20
Y max. 11 0 0 19 0 0 8 0 5
L max. 130 140 130 160 190 160 220 230 220
20
GS 50.3 – GS 250.3
Assembly
Information Ensure that the spigot (if provided) fits uniformly in the recess and that the flanges
are in complete contact.
21
GS 50.3 – GS 250.3
Indications
5. Indications
5.1. Mechanical position indicator/running indication
Mechanical position indicator:
● continuously indicates the valve position
(pointer cover [2] follows the valve movement)
● indicates whether the actuator is moving (running indication)
● indicates that end positions have been reached
(mark on pointer cover [3] points to symbols OPEN [4] or CLOSED [5])
Figure 20: Mechanical position indicator
22
GS 50.3 – GS 250.3
Commissioning
6. Commissioning
Information ● In general, gearboxes with a swing angle > 190° are multi-turn (without end
stops). Consequently, end position setting is not possible. Therefore, no protect-
ive function is available for the valve.
● In general, only one end stop (either OPEN or CLOSED) must be set, due to
the fact that the swing angle was already set in the factory.
Figure 21: End stop (left: up to size 125.3, right: from size 160.3)
[1] Screws
[2] End stop
[3] Housing
2. Turn valve via handwheel to position CLOSED. Check whether end stop [2]
rotates simultaneously.
→ Otherwise: Turn end stop [2] clockwise to the stop.
23
GS 50.3 – GS 250.3
Commissioning
3. With mounted multi-turn actuator (not required for manual operation): Turn end
stop [2] counterclockwise by 1/4 turn.
➥ This ensures that the gearbox end stop cannot be approached during motor
operation if a multi-turn actuator is mounted and that the valve can close tightly
for torque seating.
4. In case the four holes of the end stop [2] do not match the four threaded bores
within the housing [3]: Remove end stop [2] until it disengages from the toothing
and replace in correct position.
5. Fasten screws [1] crosswise with a torque according to table <Tightening torques
for screws at end stop> .
Table 7:
Tightening torques for screws at end stop
Gearbox Screws [1] Tightening torque TA [Nm]
GS 50.3 M6 10
GS 50.3 – GS 80.3 M8 24
GS 100.3 – GS 125.3 M12 82
GS 160.3 M10 48
GS 200.3 M12 82
GS 250.3 M16 200
Figure 22: End stop (left: up to size 125.3, right: from size 160.3)
[1] Screws
[2] End stop
[3] Housing
2. Turn valve via handwheel in position OPEN. Check whether end stop [2] rotates
simultaneously.
→ Otherwise: Turn end stop [2] counterclockwise to the stop.
24
GS 50.3 – GS 250.3
Commissioning
3. With mounted multi-turn actuator (not required for manual operation): Turn end
stop [2] clockwise by 1/4 turn.
➥ This ensures that the gearbox end stop cannot be approached during motor
operation if a multi-turn actuator is mounted and that the valve can close tightly
for torque seating.
4. In case the four holes of the end stop [2] do not match the four threaded bores
within the housing [3]: Remove end stop [2] until it disengages from the toothing
and replace in correct position.
5. Fasten screws [1] crosswise with a torque according to table <Tightening torques
for screws at end stop>.
Further settings hereafter:
● If the gearbox is equipped with a pointer cover: Check whether the mark aligns
with the symbol OPEN. Refer to <Mechanical position indicator: set>.
● If the gearbox is mounted to a multi-turn actuator, set the seating in end position
OPEN straight after completion of the current setting: <Seating in end positions
via multi-turn actuator>.
6.2. Seating in end positions via multi-turn actuator
This chapter supplies basic information and notes which should be considered in
addition to the operation instructions of the multi-turn actuator.
● The valve manufacturer has to determine whether the valve is limit or torque
seated.
● End position seating must be set in compliance with the operating instructions
pertaining to the multi-turn actuator.
● When setting the torque switching within the multi-turn actuator, make sure that
the tripping torque for both directions does not exceed the max. gearbox input
torque (refer to technical data or name plate).
● Set the torque switching within the multi-turn actuator to the following value to
prevent damage to the valve:
Tripping torque = valve torque/factor (refer to name plate)
● If the swing angle set in the factory for opening and closing the valve is not
sufficient: refer to <Swing angle>.
6.2.1. Seating in end position CLOSED: set
25
GS 50.3 – GS 250.3
Commissioning
26
GS 50.3 – GS 250.3
Commissioning
27
GS 50.3 – GS 250.3
Commissioning
[1] Screws
[2] Protective cap
[3] Screw with curved spring lock washer
[4] Clamping washer
[5] Setting ring
[6] End stop nut
[7] Travelling nut
[8] Pairs of safety wedge discs (for OPEN and CLOSE)
1. Remove all four screws [1] and pull off protective cap [2].
2. Remove the screw with the curved spring lock washer [3] and clamping washer
[4].
3. Pull off setting ring [5].
4. Swing angle increase:
4.1 Turn end stop nut [6] counterclockwise.
4.2 Move valve manually to the desired end position OPEN.
4.3 Turn end stop nut [6] clockwise until it is tight to the travelling nut [7].
5. Swing angle reduction:
5.1 Move valve manually to the desired end position OPEN.
5.2 Turn end stop nut [6] clockwise until it is tight to the travelling nut [7].
6. Fit setting ring [5], secure with clamping washer [4], as well as screw and curved
spring lock washer [3].
7. Check whether O-ring at protective cap is in good condition, replace if damaged.
8. Place protective cap [2] and fasten screws [1] crosswise with a torque according
to table <Tightening torques for screws at end stop>.
Information If the gearbox is mounted to a multi-turn actuator, the limit switching for the end po-
sition OPEN must be set first in compliance with the operation instructions of the
multi-turn actuator.
End position CLOSED 1. Move valve to end position CLOSED and check setting.
➥ The setting is correct if the mark aligns with the symbol CLOSED.
28
GS 50.3 – GS 250.3
Commissioning
29
GS 50.3 – GS 250.3
Servicing and maintenance
AUMA
AUMA offers extensive service such as servicing and maintenance as well as
Service & Support customer product training. For the relevant contact addresses, please refer to
<Addresses> in this document or to the Internet (www.auma.com)
30
GS 50.3 – GS 250.3
Servicing and maintenance
31
GS 50.3 – GS 250.3
Technical data
8. Technical data
Information The following tables include standard and optional features. For detailed information
on the customer-specific version, refer to the order-related data sheet. The technical
data sheet can be downloaded from the Internet in both German and English at ht-
tp://www.auma.com (please state the order number).
General information
For motor or manual operation of valves (e.g. butterfly valves, ball and plug valves).
For special applications, e.g. dampers, gas diverters, flue gas dampers, toggle arm driven diverters and guillotine isolators, specific sizing
is required. Separate technical data apply for these applications.
Type GS 200.3
Reduction ratio 53:1 67:1 214:1 434:1 864:1 1752:1
[Nm] 8,000 250 2,000 1,000 500 250
Type GS 250.3
Reduction ratio 52:1 210:1 411:1 848:1 1718:1
[Nm] 8,000 2,000 1,000 500 250
Swing angle GS 50.3 – GS 125.3 Standard: Fixed swing angle between 10° and max. 100°; set in the factory to 92° unless ordered
otherwise.
Options: Adjustable in steps of:
10° – 35°, 35° – 60°, 60° – 80°, 80° – 100°, 100° – 125°, 125° – 150°, 150° – 170°,170°
– 190°
Swing angles > 190° are only possible with a worm wheel made of bronze and without
end stops. For swing angles > 100°, we recommend a worm wheel made of bronze.
Worm wheel made of bronze; Multi-turn version without end stop, up to max. 10 turns of
worm wheel permissible Heed special sizing!
Swing angle GS 160.3 – GS 250.3 Standard: Adjustable 80° – 100°; set in the factory to 92° unless ordered otherwise.
Options: Adjustable in steps of:
0° – 20°, 20° – 40°, 40° – 60°, 60° – 80°, 90° – 110°, 110° – 130°, 130° – 150°, 150° –
170°, 170° – 190°
Swing angles > 190° are only possible with a worm wheel made of bronze and without
end stops. For swing angles > 100°, we recommend a worm wheel made of bronze.
Worm wheel made of bronze; Multi-turn version without end stop, up to max. 10 turns of
worm wheel permissible. Heed special sizing!
Swing angle for special reduction Standard: Adjustable 80° – 100°; set in the factory to 92° unless ordered otherwise.
ratio Options: Swing angle range different from standard range available on request
(worm wheel made of bronze only) Multi-turn version without end stop, up to max. 10 turns of worm wheel permissible. Heed
special sizing!
32
GS 50.3 – GS 250.3
Technical data
Operation
Motor operation ● Via electric multi-turn actuator
● Input mounting flanges for multi-turn actuator
Shorter operating times can be achieved with worm wheels made of bronze, refer to Technical data GS
50.3 – GS 250.3 for modulating duty and shorter operating times.
Due to gear tooth geometry and the material characteristics of bronze, worm gearboxes with a worm
wheel made of bronze can transmit lower torques.
Calculation of operating time for a 90° swivel movement
33
GS 50.3 – GS 250.3
Technical data
Operation
Manual operation Standard: ● Handwheel made of aluminium with electrophoretic coating
● Handwheel with ball handle
Type GS 250.3
Reduction ratio 52:1 210:1 411:1 848:1 1718:1
Handwheel Ø [mm] 500
– 800 400 315
630
34
GS 50.3 – GS 250.3
Technical data
Valve attachment
Valve attachment Dimensions according to EN ISO 5211: The maximum torques of mounting flanges according to EN
ISO 5211 are to be met.
Spigot Flanges with spigot. Up to GS 125.3, spigots are implemented by means of spigot rings (option). From
GS 160.3 to GS 250.3, spigots are directly integrated into the housing.
Plane flanges Up to GS 125.3, plane flanges are implemented by means of recesses. From GS 160.3 to GS 250.3,
the housing is plane machined (option).
Bore for parallel pins (option) Two bores for parallel pins shifted by 180°. The parallel pins are not included in the scope of delivery.
Refer to Dimensions Output mounting flange GS 50.3 – GS 125.3 (Y000.854) and Dimensions Output
mounting flange GS 160.3 – GS 250.3 (Y005.001). Further pitch circle diameters for locating pins on
request.
Splined coupling for connection to Standard: ● Without bore or pilot bore from GS 160.3
the valve shaft
● Worm gearbox can be mounted on coupling
Options: Finish machining with bore and keyway, square bore or two-flat with grub screw for secure
fixing to valve shaft.
Service conditions
Mounting position Any position
Ambient temperature Standard: –40 °C to +80 °C
Options: –60 °C to +60 °C
0 °C to +120 °C
Enclosure protection according to Standard: IP68, dust-tight and water-tight up to max. 8 m head of water
EN 60529 Options: IP68-20, dust-tight and water-tight up to max. 20 m head of water
Corrosion protection Standard: GS 50.3 – GS 80.3: KS
GS 100.3 – GS 250.3: KN
Options: GS 50.3 – GS 80.3: KX
GS 100.3 – GS 250.3: KS/KX
KN Suitable for installation in industrial units, in water or power plants with a low pollutant
concentration
KS Suitable for use in areas with high salinity, almost permanent condensation, and high
pollution.
KX Suitable for use in areas with extremely high salinity, permanent condensation, and high
pollution.
Coating GS 50.3 – GS 80.3: Double layer powder coating
GS 100.3 – GS 250.3: Two-component iron-mica combination
Colour AUMA silver-grey (similar to RAL 7037)
Option: Available colours on request
35
GS 50.3 – GS 250.3
Technical data
Service conditions
AUMA load spectrum For open-close duty with worm wheel made of spheroidal cast iron:
Duty class 2: Lifetime for 90° swivel movement for valves which are infrquently operated.
36
GS 50.3 – GS 250.3
Technical data
Special features for use in potentially explosive atmospheres in accordance with ATEX 2014/34 EU
Explosion protection in accordance Standard: II2G c IIC T4
with ATEX 2014/34 EU II2D c T130 °C
Option II2G c IIC T3
II2D c T190 °C
IM2 c
Type of duty Maximum 3 cycles (OPEN - CLOSE - OPEN) in accordance with AUMA load spectrum (90° swivel
(open-close duty, with worm wheel movement) and maximum permissible input speeds, or with mean constant output torques according
made of spheroidal cast iron) to table:
Type of duty Standard: Intermittent duty S4 – 25 % with modulating torque and max. input speed
(modulating duty with worm wheel
made of bronze) Type GS 50.3 GS 63.3 GS 80.3 GS 100.3
Reduction ratio 51:1 51:1 53:1 52:1 126:1 160:1 208:1
Max. speed at GS
input with SA 45 45 45 45 90 125 180
[rpm]
Type GS 200.3
Reduction ratio 53:1 67:1 214:1 434:1 864:1 1,752:1
Max. speed at GS
input with SA 11 11 45 90 180 180
[rpm]
Type GS 250.3
Reduction ratio 52:1 210:1 441:1 848:1 1,718:1
Max. speed at GS
input with SA 11 45 90 180 180
[rpm]
37
GS 50.3 – GS 250.3
Technical data
Special features for use in potentially explosive atmospheres in accordance with ATEX 2014/34 EU
Ambient temperature Duty classes 1 and 3
(open-close duty, with worm wheel Standard: –40 °C to +60 °C (II2G c IIC T4; II2D c T130 °C)
made of spheroidal cast iron)
Option –60 °C to +60 °C (II2G c IIC T4; II2D c T130 °C)
–40 °C to +40 °C (II2G c IIC T4; II2D c T130 °C)
–40 °C to +80 °C (II2G c IIC T3; II2D c T190 °C)
0 °C to +120 °C (II2G c IIC T3; II2D c T190 °C)
–20 °C to +40 °C (IM2 c)
Duty class 2
Standard: –40 °C to +60 °C (II2G c IIC T3; II2D c T190 °C); T4 on request with individual test
Option –60 °C to +40 °C (II2G c IIC T4; II2D c T130 °C)
–60 °C to +60 °C (II2G c IIC T3; II2D c T190 °C); T4 on request with individual test
–40 °C to +40 °C (II2G c IIC T4; II2D c T130 °C)
–40 °C to +80 °C (II2G c IIC T3; II2D c T190 °C)
–20 °C to +40 °C (IM2 c)
Further temperature classes or loads exceeding the average torque of the AUMA load spectrum on re-
quest.
Ambient temperature Standard: –40 °C to +40 °C (II2G c IIC T4; II2D c T130 °C)
(modulating duty with worm wheel –40 °C to +60 °C (II2G c IIC T4; II2D c T130 °C)
made of bronze) –50 °C to +60 °C (II2G c IIC T4; II2D c T130 °C)
–60 °C to +60 °C (II2G c IIC T4; II2D c T130 °C)
Options: –40 °C to +80 °C (II2G c IIC T3; II2D c T190 °C)
0 °C to +120 °C (II2G c IIC T3; II2D c T190 °C)
–20 °C to +40 °C (IM2 c)
Further information
EU Directives ATEX Directive: (2014/34/EU)
Machinery Directive: (2006/42/EC)
38
GS 50.3 – GS 250.3
Spare parts
9. Spare parts
9.1. Part-turn gearboxes GS 50.3 – GS 125.3
39
GS 50.3 – GS 250.3
Spare parts
Please state device type and our order number (see name plate) when ordering spare parts. Only original AUMA spare parts should be used.
Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Delivered spare parts may slightly vary from the
representation in these instructions.
40
GS 50.3 – GS 250.3
Spare parts
41
GS 50.3 – GS 250.3
Spare parts
Please state device type and our order number (see name plate) when ordering spare parts. Only original AUMA spare parts should be used.
Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Delivered spare parts may slightly vary from the
representation in these instructions.
42
GS 50.3 – GS 250.3
Spare parts
43
GS 50.3 – GS 250.3
Spare parts
Please state device type and our order number (see name plate) when ordering spare parts. Only original AUMA spare parts should be used.
Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Delivered spare parts may slightly vary from the
representation in these instructions.
44
GS 50.3 – GS 250.3
Spare parts
9.4. Primary reduction gearings for GS 160.3 (218:1/442:1) GS 200.3 (214:1/434:1) GS 250.3 (210:1/411:1)
45
GS 50.3 – GS 250.3
Spare parts
Please state device type and our order number (see name plate) when ordering spare parts. Only original AUMA spare parts should be used.
Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Delivered spare parts may slightly vary from the
representation in these instructions.
46
GS 50.3 – GS 250.3
Spare parts
47
GS 50.3 – GS 250.3
Spare parts
Please state device type and our order number (see name plate) when ordering spare parts. Only original AUMA spare parts should be used.
Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Delivered spare parts may slightly vary from the
representation in these instructions.
48
Y003.822/003/en/2.17
Reference documents:
Reference documents can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA
(refer to <Addresses>).
2
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Table of contents
3
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Table of contents AM 01.1/AM 02.1
4
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Safety instructions
1. Safety instructions
1.1 Basic information on safety
Standards/directives AUMA products are designed and manufactured in compliance with recognised
standards and directives. This is certified in a Declaration of Incorporation and an
EC Declaration of Conformity.
The end user or the contractor must ensure that all legal requirements, directives,
guidelines, national regulations and recommendations with respect to assembly,
electrical connection, commissioning and operation are met at the place of installation.
Safety instructions/war- All personnel working with this device must be familiar with the safety and warning
nings instructions in this manual and observe the instructions given. Safety instructions
and warning signs on the device must be observed to avoid personal injury or property
damage.
Qualification of staff Assembly, electrical connection, commissioning, operation, and maintenance must
be carried out exclusively by suitably qualified personnel having been authorised by
the end user or contractor of the plant only.
Prior to working on this product, the staff must have thoroughly read and understood
these instructions and, furthermore, know and observe officially recognised rules
regarding occupational health and safety.
Commissioning Prior to commissioning, it is important to check that all settings meet the requirements
of the application. Incorrect settings might present a danger to the application, e.g.
cause damage to the valve or the installation. The manufacturer will not be held
liable for any consequential damage. Such risk lies entirely with the user.
Maintenance To ensure safe device operation, the maintenance instructions included in this manual
must be observed.
Any device modification requires prior consent of the manufacturer.
1.2 Range of application
AUMA multi-turn actuators are designed for the operation of industrial valves, e.g.
globe valves, gate valves, butterfly valves, and ball valves.
Other applications require explicit (written) confirmation by the manufacturer.
5
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Safety instructions AM 01.1/AM 02.1
● Escalators
● Continuous operation
● Buried service
● Permanent submersion (observe enclosure protection)
● Potentially explosive areas, with the exception of zone 22
● Radiation exposed areas in nuclear power plants
No liability can be assumed for inappropriate or unintended use.
Observance of these operation instructions is considered as part of the device's
designated use.
Information These operation instructions are only valid for the "clockwise closing" standard
version, i.e. driven shaft turns clockwise to close the valve.
1.3 Applications in Ex zone 22 (option)
Actuators of the indicated series basically meet the requirements for applications in
dust hazardous locations of ZONE 22 in compliance with the ATEX directive 94/9/EC.
The actuators are designed to meet enclosure protection IP 68 and fulfil the
requirements of EN 50281-1-1:1998 section 6 - Electrical apparatus for use in
presence of combustible dust, requirements for category 3 electrical equipment -
protected by enclosures.
To comply with all requirements of EN 50281-1-1:1998, it is imperative that the
following points are observed:
● In compliance with the ATEX directive 94/9/EC, the actuators must be equipped
with an additional identification – II3D IP6X T150 °C.
● The maximum surface temperature of the actuators, based on an ambient
temperature of +40 °C in accordance with EN 50281-1-1 section 10.4, is +150
°C. In accordance with section 10.4, an increased dust deposit on the equipment
was not considered for the determination of the maximum surface temperature.
● The correct connection of the thermoswitches or the PTC thermistors as well
as fulfilling the requirements of the duty type and the technical data are prere-
quisites for compliance with the maximum surface temperature of devices.
● The connection plug may only be plugged in or pulled out when device is dis-
connected from the mains.
● The cable glands used also have to meet the requirements of category II3 D
and must at least comply with enclosure protection IP 67.
● The actuators must be connected by means of an external ground connection
(accessory part) to the potential compensation or integrated into an earthed
piping system.
● The screw plug (part no. 511.0) or the stem protection tube with protective cap
(part nos. 568.1 and 568.2) for sealing the hollow shaft must imperatively be
mounted to guarantee tightness and therefore the combustible dust hazard
protection.
● As a general rule, the requirements of EN 50281-1-1 must be respected in dust
hazardous locations. During commissioning, service, and maintenance, special
care as well as qualified and trained personnel are required for the safe opera-
tion of actuators.
1.4 Warnings and notes
6
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Safety instructions
Information The term Information preceding the text indicates important notes and information.
7
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Identification AM 01.1/AM 02.1
2. Identification
2.1 Name plate
Each device component (actuator, controls, motor) is equipped with a name plate.
Figure 1: Arrangement of name plates
8
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Identification
Commission number An order-specific commission number is assigned to each device. This commission
number can be used to directly download the wiring diagram, inspection records and
further information regarding the device from the Internet: http://www.auma.com.
Control
24 V DC = Control via parallel interface at 24 V DC control voltage.
115 V AC = Control via parallel interface at 115 V AC control voltage.
0/4 – 20 mA = Control via parallel interface via analogue input 0/4 – 20 mA.
2.2 Short description
9
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Transport, storage and packaging AM 01.1/AM 02.1
Hovering load!
Risk of death or serious injury.
→ Do NOT stand below hovering load.
→ Attach ropes or hooks for the purpose of lifting by hoist only to housing and NOT
to handwheel.
→ Actuators mounted on valves: Attach ropes or hooks for the purpose of lifting
by hoist to valve and NOT to actuator.
→ Actuators mounted to gearboxes: Attach ropes or hooks for the purpose of lifting
by hoist only to the gearbox using eyebolts and NOT to the actuator.
→ Actuators mounted to controls: Attach ropes or hooks for the purpose of lifting
by hoist only to the actuator and NOT to the controls.
3.2 Storage
Long-term storage If the device must be stored for a long period (more than 6 months) the following
points must be observed in addition:
1. Prior to storage:
Protect uncoated surfaces, in particular the output drive parts and mounting
surface, with long-term corrosion protection agent.
2. At an interval of approx. 6 months:
Check for corrosion. If first signs of corrosion show, apply new corrosion protec-
tion.
3.3 Packaging
Our products are protected by special packaging for transport when leaving the
factory. The packaging consists of environmentally friendly materials which can easily
be separated and recycled. We use the following packaging materials: wood,
cardboard, paper, and PE foil. For the disposal of the packaging material, we
recommend recycling and collection centres.
10
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Assembly
4. Assembly
AUMA actuators and actuator controls can be operated without restriction in any
mounting position.
Figure 4: Handwheel
[1] Spacer
[2] Input shaft
[3] Handwheel
[4] Circlip
11
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Assembly AM 01.1/AM 02.1
4.3.1.1 Multi-turn actuator (with output drive types B1 – B4 or E): mount to valve/gearbox
12
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Assembly
✔ This working step is only required if stem nut is supplied unbored or with pilot
bore.
Figure 6: Design of output drive type A
13
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Assembly AM 01.1/AM 02.1
1. If the output drive type A is already mounted to the multi-turn actuator: Loosen
screws [3] and remove output drive type A [2].
2. Check if the flange of output drive type A matches the valve flange [4].
3. Apply a small quantity of grease to the valve stem [1].
4. Place output drive type A on valve stem and turn until it is flush on the valve
flange.
5. Turn output drive type A until alignment of the fixing holes.
6. Screw in fastening screws [5], however do not completely tighten.
7. Fit multi-turn actuator on the valve stem so that the stem nut dogs engage into
the output drive sleeve.
➥ The flanges are flush with each other if properly engaged.
8. Adjust multi-turn actuator until alignment of the fixing holes.
9. Fasten multi-turn actuator with screws [3].
10. Fasten screws [3] crosswise with a torque according to table.
11. Turn multi-turn actuator with handwheel in direction OPEN until valve flange
and output drive A are firmly placed together.
12. Tighten fastening screws [5] between valve and output drive type A crosswise
applying a torque according to table.
14
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Assembly
The mounting position of the local controls is selected according to the order. If, after
mounting the actuator to the valve or the gearbox on site, the local controls are in
an unfavourable position, the mounting position can be changed at a later date. Four
mounting positions are possible.
Figure 9: Mounting positions A and B
15
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Assembly AM 01.1/AM 02.1
Hazardous voltage!
Risk of electric shock.
→ Disconnect device from the mains before opening.
16
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Electrical connection
5. Electrical connection
5.1 Basic information
Wiring diagram/terminal
The pertaining wiring diagram/terminal plan is attached to the device in a
plan weather-proof bag, together with these operation instructions. It can also be obtained
from AUMA (state commission no., refer to name plate) or downloaded directly from
the Internet (www.auma.com).
Protection on site
For short-circuit protection and for disconnecting the actuator from the mains, fuses
and disconnect switches have to be provided by the customer.
The current values for respective sizing is derived from the current consumption of
the motor (refer to electrical data sheet) plus the current consumption of the controls.
If controls are mounted separately from actuator (controls on wall bracket): Consider
length and cross section of connecting cable when defining the protection required.
Power supply for the
If the controls (electronics) are supplied externally with 24 V DC, the power supply
controls (electronics) is smoothed via an internal 1,000 µF capacitor). When selecting a power supply,
care must be taken to consider the capacitor inrush current upon powering the unit
up.
Safety standards All externally connected devices shall comply with the relevant safety standards.
Cable installation in ac-
Signal and bus cables are susceptible to interference.
cordance with EMC
Motor cables are interference sources.
● Lay cables being susceptible to interference or sources of interference at the
highest possible distance from each other.
● The interference immunity of signal and bus cables increases if the cables are
laid close to the earth potential.
● If possible, avoid laying long cables and make sure that they are installed in
areas being subject to low interference.
17
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Electrical connection AM 01.1/AM 02.1
● Avoid long parallel paths with cables being either susceptible to interference or
interference sources.
● For the connection of remote position transmitters, screened cables must be
used.
Type of current, mains Type of current, mains voltage and mains frequency must match the data on the
voltage and mains fre- motor name plate.
quency
Figure 11: Motor name plate (example)
● Power terminals (U1, V1, W1, U2, V2, W2): max. 6 mm² flexible/10 mm² solid
●
PE connection : max. 6 mm² flexible/10 mm² solid
● Control contacts (1 to 50): max. 2.5 mm²
18
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Electrical connection
[1] Cover
[2] Screws for cover
[3] O-ring
[4] Screws for socket carrier
[5] Socket carrier
[6] Cable entry
[7] Blanking plug
[8] Cable gland (not included in delivery)
Hazardous voltage!
Risk of electric shock.
→ Disconnect device from the mains before opening.
4. Seal unused cable entries [6] with suitable blanking plugs [7].
5. Insert the cables into the cable glands [8].
5.2.2 Cable connection
19
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Electrical connection AM 01.1/AM 02.1
Information Some actuators are equipped with an additional motor heater. The motor heater
minimises condensation within the motor and improves the start-up behaviour for
extremely low temperatures.
20
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Electrical connection
[1] Cover
[2] Screws for cover
[3] O-ring
[4] Screws for socket carrier
[5] Socket carrier
[6] Cable entry
[7] Blanking plug
[8] Cable gland (not included in delivery)
1. Insert the socket carrier [5] into the cover [1] and fasten with screws [4].
2. Clean sealing faces of cover [1] and housing.
3. Check whether O-ring [3] is in good condition, replace if damaged.
4. Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
5. Fit cover [1] and fasten screws [2] evenly crosswise.
6. Fasten cable glands [8] applying the specified torque to ensure the required
enclosure protection.
5.3 Accessories for electrical connection
— Option —
5.3.1 Controls mounted to wall bracket
The wall bracket allows separate mounting of controls and actuator.
Application ● If the actuator cannot be accessed safely.
● If the actuator is subjected to high temperatures.
● In case of heavy vibration of the valve.
21
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Electrical connection AM 01.1/AM 02.1
22
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Electrical connection
The open terminal compartment can be closed using a protective cover (not
illustrated).
5.3.4 Earth connection, external
As an option, the housing is equipped with an external earth connection (U-bracket)
to connect the device to the equipotential earth bonding.
Figure 18: Earth connection
23
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Operation AM 01.1/AM 02.1
6. Operation
✔ Perform all commissioning settings and the test run prior to motor operation.
24
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Operation
➥ The actuator can now be operated using the push buttons [1 – 3]:
- Run actuator in direction OPEN: Press push button [1] .
- Stop actuator: Press push button [2] Stop.
- Run actuator in direction CLOSE: Press push button [3] .
Information The OPEN - CLOSE operation commands can be given either in push-to-run opera-
tion mode or in self-retaining mode. In self-retaining mode, the actuator runs to the
defined end position after pressing the button, unless another command has been
received beforehand.
➥ Now, it is possible to operate the actuator via remote control, via operation
commands (OPEN, STOP, CLOSE) or analogue setpoints (e.g. 0 – 20 mA).
25
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Operation AM 01.1/AM 02.1
Information For actuators equipped with positioner, it is possible to optionally select between
open-close duty (REMOTE OPEN-CLOSE) and modulating duty (REMOTE
SETPOINT). Selection is made via REMOTE MANUAL input, e.g. based on a 24 V
DC signal (refer to wiring diagram).
26
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Indications
7. Indications
7.1 Indication lights
The colours of the 3 indication lights on the local controls and the assignment of the
signals are specified in the order.
Figure 24: Local controls with indication lights (default signalling)
Collective fault signal The collective fault signal (red indication light) will be activated if one of the following
events occurs (default configuration):
● Torque fault: The set torque was exceeded before reaching an end position.
(This signal can be activated/deactivated via a switch in the controls.)
● Thermal fault: Motor protection has tripped, i.e. the motor is overheated.
● Phase failure: One phase is missing (3-ph AC motors only).
● PTC tripping device: Test complete
Running indication If the actuator is equipped with a blinker transmitter (wiring diagram designation:
S5), indication lights [1] and [3] can be used as running indication. The running
indication can be activated/deactivated via a switch in the controls. If the running
indication is active, the respective indication light blinks during operation.
7.2 Mechanical position indicator/running indication
— Option —
Mechanical position indicator:
● Continuously indicates the valve position
(For complete travel from OPEN to CLOSED or vice versa, the indicator disc
[2] rotates by approximately 180° to 230°.)
● Indicates whether the actuator is running (running indication)
● Indicates that the end positions are reached (via indicator mark [3])
27
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Indications AM 01.1/AM 02.1
[1] Cover
[2] Indicator disc
[3] Mark
[4] Symbol for position OPEN
[5] Symbol for position CLOSED
28
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Signals
8. Signals
8.1 Feedback signals via output contacts (binary)
The output contacts can be used to indicate operation modes of the actuator or the
controls as binary signals.
The signals are assigned according to the order. Example:
Output contact open = end position CLOSED not reached
Output contact closed = end position CLOSED reached
29
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Commissioning (basic settings) AM 01.1/AM 02.1
The switch compartment must be opened to perform the following settings (options).
30
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Commissioning (basic settings)
1. Loosen screws [2] and remove cover [1] from the switch compartment.
Figure 28:
31
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Commissioning (basic settings) AM 01.1/AM 02.1
Black section:
[1] Setting spindle: End position CLOSED
[2] Pointer: End position CLOSED
[3] Mark: End position CLOSED is set
White section:
[4] Setting spindle: End position OPEN
[5] Pointer: End position OPEN
[6] Mark: End position OPEN is set
32
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Commissioning (basic settings)
Black section:
[1] Setting spindle: Running direction CLOSE
[2] Pointer: Running direction CLOSE
[3] Mark: Intermediate position CLOSED is set
White section:
[4] Setting spindle: Running direction OPEN
[5] Pointer: Running direction OPEN
[6] Mark: Intermediate position OPEN is set
33
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Commissioning (basic settings) AM 01.1/AM 02.1
Information After 177 turns (control unit for 1 – 500 turns/stroke) or 1,769 turns (control unit for
1 – 5,000 turns/stroke), the intermediate switches release the contact.
9.5.1 Running direction CLOSE (black section): set
34
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Commissioning (basic settings)
35
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Commissioning (basic settings) AM 01.1/AM 02.1
➥ If the PTC tripping device is working properly, the tripping of the motor protection
is signalled via the red indication light "collective fault signal" on the local con-
trols.
2. Turn selector switch to position Reset.
Information Due to the ratio of the reduction gearing the complete resistance range/stroke is not
always passed. Therefore, external adjustment (setting potentiometer) must be pro-
vided.
[1] Potentiometer
36
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Commissioning (basic settings)
37
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Commissioning (basic settings) AM 01.1/AM 02.1
Information If the maximum value cannot be reached, the selection of the reduction gearing must
be checked. (The max. possible turns/stroke are indicated on the order-related
technical data sheet for the actuator.)
38
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Commissioning (basic settings)
3. Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
39
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Commissioning – controls settings AM 01.1/AM 02.1
Hazardous voltage!
Risk of electric shock.
→ Disconnect device from the mains before opening.
The type of seating can be set via two DIP switches on the logic board.
Limit seating
The limit switching is set in such a way that the actuator switches off at the desired
switching points. The torque switching acts as overload protection for the valve.
Torque seating
The torque switching is set to the desired tripping torque. After reaching the tripping
torque, the actuator is turned off.
40
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Commissioning – controls settings
The limit seating is used to signal that the limit switching will trip shortly before
reaching the set tripping torque. If this is not the case, either the indication light on
the local controls or the alarm contact K9 (collective fault signal) will signal a fault.
→ Set type of seating for end positions via DIP switches [S1] and [S3].
Figure 45: DIP switches on logic board
41
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Commissioning – controls settings AM 01.1/AM 02.1
Information If the controls are equipped with a positioner, switches 1 and 2 (operation commands
from remote) must be in position OFF (push-to-run operation).
➥ Switch 6 in lower position (position ON): The signal "Torque fault in collective
fault signal" is activated.
➥ Switch 6 in upper position (position OFF): The signal "Torque fault in collective
fault signal" is deactivated.
10.6 Positioner
— (Option) —
42
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Commissioning – controls settings
→ Prior to positioner setting, set limit and torque switching as well as potentiometer
or electronic position transmitter.
10.6.1 Input ranges (signal type) for setpoint and actual value
The input range (signal type) for setpoint E1 and actuator value E2 is set in the
factory and marked with a label on the cover plate of the positioner.
The type of signal can be modified at a later date exclusively for versions with setpoint
E1 ≠ 0/4 – 20 mA and split-range version. For these versions, the positioner board
is equipped with an additional contact.
Figure 49: Version with additional switch on the positioner board
0–5V
0 – 10 V
0 – 5 V2)
Information When changing the setting, a new label [5] indicating the set signal type must be
provided. Furthermore, the wiring diagram indicated on the name plate of the actuator
controls also changes.
10.6.2 Behaviour on loss of signal (actuator reaction)
In case of a loss of signal of setpoint E1 or actual value E2, the reaction of the actuator
can be programmed via switch [S2-7]. The complete selection range, however, is
only available for signals 4 – 20 mA.
43
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Commissioning – controls settings AM 01.1/AM 02.1
Fail close
Fail open
0 – 20 mA 4 – 20 mA
0 – 20 mA 0 – 20 mA
0–5V 0–5V
0 – 10 V
Fail close 0 – 20 mA 4 – 20 mA
0–5V
Fail as is 0 – 20 mA 4 – 20 mA
0 – 10 V
Fail open 4 – 20 mA 0 – 20 mA
0–5V
44
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Commissioning – controls settings
End position CLOSED 1. Set selector switch to position Local control (LOCAL).
2. Move valve to end position CLOSED.
3. Connect lower setpoint to customer connection XK (terminals 2/3). The lower
setpoint (0 V, 0 mA or 4 mA) is indicated on the label [5].
4. If the red LED [V10] E1/E2 <4 mA is illuminated:
4.1 Verify polarity of setpoint E1.
4.2 Check whether external load is connected to customer connection XK
(terminals 23/24) (observe max. load RB), or
4.3 Connect terminals 23/24 across customer connection XK (terminals 23/24).
5. Measure setpoint E1: Connect measuring device for 0 – 5 V to measuring points
[MP3/MP4].
➥ For a setpoint E1 of 0 V or 0 mA, the voltmeter shows 0 V.
➥ For a setpoint E1 of 4 mA, the voltmeter shows 1 V.
6. If measured value is not correct: Correct setpoint E1.
7. Measure actual value E2: Connect measuring device for 0 – 5 V to measuring
points [MP1/MP2].
➥ For an actual value E2 of 0 mA, the voltmeter shows 0 V.
➥ For an actual value E2 of 4 mA, the voltmeter shows 1 V.
8. If measured value is not correct: Re-set potentiometer or electronic position
transmitter and perform adjustment once again, starting from step 1.
45
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Commissioning – controls settings AM 01.1/AM 02.1
[P3] Potentiometer 0
[P4] Potentiometer max
[V27] Yellow LED: End position CLOSED reached
[V28] Green LED: End position OPEN reached
➥ The setting is correct if the yellow LED [V27] is switched on when reaching end
position CLOSED.
End position OPEN 10. Move valve to end position OPEN.
11. Measure actual value E2 (measuring points [MP1/MP2]):
➥ For an actual value E2 of 20 mA, the voltmeter shows 5 V.
12. If measured value is not correct: Re-set potentiometer or electronic position
transmitter and perform adjustment once again, starting from step 1.
13. Set maximum setpoint E1 (5 V or 20 mA, refer to label [5]).
14. Measure setpoint E1 (measuring points [MP3/MP4]):
➥ For a setpoint E1 of 5 V or 20 mA, the voltmeter shows 5 V.
15. If measured value is not correct: Verify setpoint E1.
16. Adjust positioner using potentiometer max [P4].
16.1 If both LEDs are OFF or the yellow LED [V27] is illuminated: Turn poten-
tiometer max [P4] slightly counterclockwise until the green LED [V28] is
illuminated.
16.2 If the green LED [V28] is illuminated: Turn potentiometer max [P4] clock-
wise until the green LED [V28] goes out. Then turn potentiometer 0 [P3]
slightly counterclockwise until the green LED [V28] is illuminated again.
➥ The setting is correct if the green LED [V28] is switched on when
reaching end position OPEN.
Dead band The dead band determines the sensitivity between switch-on point and switch-off
point. The smaller the dead band, the higher the sensitivity of the positioner.
46
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Commissioning – controls settings
Dead time The dead time prevents the operation to a new setpoint within a pre-determined time
(0.5 to 10 seconds). The number of starts can be reduced by setting the dead time
to a sufficiently high value.
Figure 53: Sensitivity setting
Dead band setting 1. Set selector switch to position Remote control (REMOTE).
2. Connect setpoint E1 to customer connection XK (terminals 2/3).
3. Set dead band using potentiometer Δ E [P9]:
→ Reduce dead band (increase sensitivity): Turn potentiometer counter-
clockwise.
→ Increase dead band (reduce sensitivity): Turn potentiometer clockwise.
Fine tuning Information: Fine tuning is only useful for output speeds <16 rpm. For 1-phase
AC motors, fine tuning is not possible.
4. Reduce dead band further by up to 0.25 % (increase sensitivity): Turn potentio-
meter sens [P7] counterclockwise.
Dead time setting 5. Set dead time using potentiometer t-off [P10]:
→ Reduce dead time: Turn potentiometer t-off [P10] counterclockwise.
→ Increase dead time: Turn potentiometer t-off [P10] clockwise.
10.7 EMERGENCY command (EMERGENCY - OPEN/EMERGENCY - CLOSE)
— (Option) —
The EMERGENCY input (refer to wiring diagram) has to be connected to the control
voltage using an NC contact (closed circuit principle). In the event of an EMERGENCY
command (removal of the signal = NC contact is operated), the actuator runs to the
preset end position:
● EMERGENCY - CLOSE input: Actuator runs to end position CLOSED.
● EMERGENCY - OPEN input: Actuator runs to end position OPEN.
The EMERGENCY command is effective in all three selector switch positions (LOCAL,
OFF, REMOTE).
47
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Commissioning – controls settings AM 01.1/AM 02.1
Disable EMERGENCY Figure 54:Interface board for available option EMERGENCY - OPEN/EMERGENCY
command - CLOSE
48
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Corrective action
Switch check
The red test buttons [1] and [2] are used for manual operation of the switches:
1. Turn test button [1] in direction of the TSC arrow: Torque switch CLOSED trips.
The red indication light (fault) on the local controls is illuminated.
2. Press push button OPEN to reset the fault (indication light) by operating the
device in the opposite direction.
3. Turn test button [2] in direction of the TSO arrow: Torque switch OPEN trips.
4. Press push button CLOSE to reset the fault (indication light) by operating the
device in the opposite direction.
If the actuator is equipped with a DUO limit switching (option), the intermediate
position switches (LSA and LSB) will be operated at the same time as the torque
switches.
1. Turn test button [1] in direction of the LSC arrow: Limit switch CLOSED trips.
2. Turn test button [2] in direction of the LSO arrow: Limit switch OPEN trips.
11.2 Fuses
Hazardous voltage!
Risk of electric shock.
→ Disconnect device from the mains before opening.
49
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Corrective action AM 01.1/AM 02.1
F3 Internal 24 V DC supply
Information Only replace fuses with fuses of the same type and value.
50
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Corrective action
The actuator can be controlled again once the motor has cooled down (red indication
light goes out).
Version with thermoswitch and additional thermal overload relay within the
controls (option)
The operation may only be resumed once the fault signal (red indication light) has
been reset. The fault signal is reset via the overload relay integrated in the actuator
controls. Therefore the controls have to be opened at the cover and the relay held
down. The relay is located on the contactors.
Version with PTC thermistor (option)
The operation may only be resumed once the fault signal (red indication light) has
been reset. The fault signal is reset via selector switch position Reset of the local
controls.
Figure 58: Selector switch on local controls
51
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Servicing and maintenance AM 01.1/AM 02.1
Service
AUMA offers extensive service such as servicing and maintenance as well as
customer product training. For the relevant contact addresses, please refer to
<Addresses> in this document or to the Internet (www.auma.com) .
52
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Servicing and maintenance
53
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Technical data AM 01.1/AM 02.1
54
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Technical data
55
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Technical data AM 01.1/AM 02.1
Power supply, mains frequency For mains voltage and mains frequency, refer to name plates at the controls and the motor
Permissible variation of the mains voltage: ±10 %
Permissible variation of the mains frequency: ±5 %
Option: Permissible variation of the mains voltage: –10 %
Current consumption Motor current consumption: Refer to motor name plate
Current consumption of the controls depending on the mains voltage:
100 to 120 V AC = max. 575 mA
208 to 240 V AC = max. 275 mA
380 to 500 V AC = max. 160 mA
External supply of the electro- 24 V DC +20 % / –15 %
nics (option) Current consumption: Basic version approx. 200 mA, with options up to 500 mA
Rated power The controls are conceived for the rated motor power, refer to motor name plate
Overvoltage category Category III according to IEC 60364-4–443
Switchgear 1) 2) Standard:
Reversing contactors (mechanically and electrically interlocked) for motor power up to power
class A1
Options:
● Reversing contactors (mechanically and electrically interlocked) for motor power up to
power classes A2 or A3
● Thyristor unit for mains voltage up to 500 V AC (recommended for modulating actuators)
for AUMA power classes B1, B2 and B3
Auxiliary voltage output Standard:
24 V DC ±5 %, max. 50 mA for supply of the control inputs, galvanically isolated from internal
voltage supply
Option:
115 V AC ±10 %, max. 30 mA for supply of the control inputs3), galvanically isolated from
internal voltage supply
Control Standard:
Control inputs 24 V DC, OPEN - STOP - CLOSE (via opto-isolator, one common), current
consumption: approx. 10 mA per input, observe minimum pulse duration for modulating ac-
tuators
Option:
Control inputs 115 V AC, OPEN - STOP - CLOSE - EMERGENCY (via opto-isolator, one
common), current consumption: approx. 15 mA input
Additional enable inputs for directions OPEN and CLOSE
Status signals Standard:
5 output contacts with gold-plated contacts:
● 4 potential-free NO contacts with one common, max. 250 V AC, 0.5 A (resistive load)
- Default configuration: End position OPEN, end position CLOSED, selector switch
REMOTE, selector switch LOCAL
● 1 potential-free change-over contacts, max. 250 V AC, 0.5 A (resistive load)
- Default configuration: Collective fault signal (torque fault, phase failure, motor protec-
tion tripped)
Options:
● Signals in combination with positioner:
- End position OPEN, end position CLOSED (requires tandem switch within actuator),
selector switch REMOTE, selector switch REMOTE, selector switch LOCAL via 2nd
level selector switch
● 1 potential-free change-over contact, max. 250 V AC, 0.5 A (resistive load)
- Default configuration: Collective fault signal (torque fault, phase failure, motor protec-
tion tripped)
Position feedback signal (option) Galvanically isolated analogue output E2 = 0/4 – 20 mA (load max. 300 Ω)
Local controls Standard:
● Selector switch LOCAL - OFF - REMOTE (lockable in all three positions)
● Push buttons OPEN, STOP, CLOSE
● 3 indication lights:
- End position CLOSED (yellow), collective fault signal (red), end position OPEN (green)
Options:
● Special colours for the 3 indication lights
● Protection cover, lockable
● Protection cover with indicator glass, lockable
56
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Technical data
Functions Standard:
● Switch-off mode adjustable
- Limit or torque seating for end position OPEN and end position CLOSED
● Overload protection against excessive torques over the whole travel
● Excessive torque (torque fault) can be excluded from collective fault signal.
● Phase failure monitoring with automatic phase correction
● Push-to-run operation or self-retaining in REMOTE
● Push-to-run operation or self-retaining in LOCAL
● Running indication via blinker transmitter signal of actuator (option) can be activated or
deactivated
Options:
● Positioner
- Position setpoint via analogue input E1 = 0/4 – 20 mA
- Galvanic isolation for position setpoint (0/4 – 20 mA) and position feedback (0/4 – 20
mA)
- Adjustable behaviour on loss of signal
- Adjustable sensitivity (dead band) and pause time
● Positioner for Split Range operation
Motor protection evaluation Standard:
Monitoring of the motor temperature in combination with thermoswitches in the actuator
motor
Options:
● Additional thermal overload relay in the controls in combination with thermoswitches within
the actuator
● PTC tripping device in combination with PTC thermistors in the actuator motor
Electrical connection Standard:
AUMA plug/socket connector (S) with screw-type connection and M-threads
Options:
● Pg-threads, NPT-threads, G-threads, special threads
● Gold-plated control contacts (pins and sockets)
● Parking frame for wall mounting of the disconnected plug
● Protection cover for plug compartment (when plug is removed)
Wiring diagram Refer to name plate
1) The reversing contactors are designed for a lifetime of 2 million starts.
2) For the assignment of AUMA power classes, please refer to electrical data on actuator.
3) Not possible in combination with PTC tripping device
57
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Technical data AM 01.1/AM 02.1
58
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Spare parts
59
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Spare parts AM 01.1/AM 02.1
Information: Please state type and commission no. of the device (see name plate) when ordering spare parts.
Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts
AUMA from any liability. Delivered spare parts may slightly vary from the representation.
No. Designation Type No. Designation Type
001.0 Housing Sub-assembly 553.0 Mechanical position indicator Sub-assembly
002.0 Bearing flange Sub-assembly 554.0 Socket carrier with motor cable har- Sub-assembly
ness
003.0 Hollow shaft with worm wheel Sub-assembly 556.0 Potentiometer for position transmitter Sub-assembly
005.0 Drive shaft Sub-assembly 556.1 Potentiometer without slip clutch Sub-assembly
005.1 Motor coupling on output drive shaft 557.0 Heater Sub-assembly
005.3 Manual drive coupling 558.0 Blinker transmitter including pins at Sub-assembly
wires (without impulse disc and insula-
tion plate)
009.0 Planetary gear for manual drive Sub-assembly 559.0–1 Control unit without torque switching Sub-assembly
heads and switches
017.0 Torque lever Sub-assembly 559.0–2 Control unit with magnetic limit and Sub-assembly
torque transmitter (MWG) for Non-
intrusive version in combination with
AUMATIC integral controls
018.0 Gear segment 560.0–1 Switch stack for direction OPEN Sub-assembly
019.0 Crown wheel 560.0–2 Switch stack for direction CLOSE Sub-assembly
022.0 Drive pinion II for torque switching Sub-assembly 560.1 Switch for limit/torque switching Sub-assembly
023.0 Output drive wheel for limit switching Sub-assembly 560.2 Switch case
024.0 Drive wheel for limit switching Sub-assembly 566.0 Position transmitter RWG Sub-assembly
025.0 Locking plate Sub-assembly 566.1 Potentiometer for RWG without slip Sub-assembly
clutch
058.0 Wire for protective earth (pin) Sub-assembly 566.2 Electronic board RWG Sub-assembly
070.0 Motor (VD motor incl. no. 079.0) Sub-assembly 566.3 Wire harness for RWG Sub-assembly
079.0 Planetary gear for motor drive Sub-assembly 567.1 Slip clutch for potentiometer/RWG Sub-assembly
(SA/SAR 07.2 — 16.2 for VD motor)
155.0 Reduction gearing Sub-assembly 568.1 Stem protection tube (without cap)
500.0 Cover for switch compartment Sub-assembly 568.2 Cap for stem protection tube
501.0 Socket carrier (complete with sockets) Sub-assembly 568.3 V-seal
502.0 Pin carrier without pins Sub-assembly 574.1 Radial seal output drive A for ISO
flange
503.0 Socket for controls Sub-assembly 575.1 Stem nut type A
504.0 Socket for motor Sub-assembly 583.0 Motor coupling on motor shaft Sub-assembly
505.0 Pin for controls Sub-assembly 583.1 Pin for motor coupling
506.0 Pin for motor Sub-assembly 584.0 Retaining spring for motor coupling Sub-assembly
507.0 Plug cover Sub-assembly S1 Seal kit, small Set
511.0 Screw plug Sub-assembly S2 Seal kit, large Set
514.0 Output drive form A (without stem nut) Sub-assembly
514.1 Axial needle roller bearing Sub-assembly
516.0 Output drive D Sub-assembly
535.1 Snap ring
539.0 Screw plug Sub-assembly
542.0 Handwheel with ball handle Sub-assembly
549.0 Output drive B1/B3/B4/C Sub-assembly
549.1 Output drive sleeve B1/B3/B4/C
551.1 Parallel key
60
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Spare parts
61
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Spare parts AM 01.1/AM 02.1
Information: Please state type and commission no. of the device (see name plate) when ordering spare parts.
Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts
AUMA from any liability. Delivered spare parts may slightly vary from the representation.
No. Designation Type
001.0 Housing
002.0 Local controls Sub-assembly
002.5 Selector switch Sub-assembly
003.0 Local controls board Sub-assembly
003.1 Primary fuse
003.2 Fuse cover
004.0 Carrier for contactors
006.0 Power supply including mounting plate Sub-assembly
006.1 Secondary fuse F3
006.2 Secondary fuse F4
008.0 Interface board Sub-assembly
008.1 Interface board
008.2 Cover plate for interface board
009.0 Logic board Sub-assembly
013.0 Adapter board
500.0 Cover Sub-assembly
501.0 Socket carrier (complete with sockets) Sub-assembly
502.0 Pin carrier without pins Sub-assembly
503.0 Socket for controls Sub-assembly
504.0 Socket for motor Sub-assembly
505.0 Pin for controls Sub-assembly
506.0 Pin for motor Sub-assembly
507.0 Plug cover Sub-assembly
508.0 Switchgear Sub-assembly
509.1 Padlock
S Seal kit Set
62
Part-turn actuators
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
with actuator controls
AUMA MATIC AM 01.1
Reference documents:
Reference documents can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA
(refer to <Addresses>).
2
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Table of contents
6. Operation................................................................................................................................ 23
6.1. Manual operation 23
6.1.1. Manual operation: engage 23
6.1.2. Manual operation: disengage 23
6.2. Motor operation 23
6.2.1. Local operation 23
6.2.2. Actuator operation from remote 24
7. Indications.............................................................................................................................. 26
7.1. Indication lights 26
7.2. Mechanical position indicator/running indication 26
8. Signals..................................................................................................................................... 28
8.1. Feedback signals via output contacts (binary) 28
8.2. Feedback signals (analogue) 28
9. Commissioning (basic settings)........................................................................................... 29
9.1. Heat-up time for low temperature version 29
9.2. End stops in part-turn actuator 29
9.2.1. End stop CLOSED: set 30
9.2.2. End stop OPEN: set 31
9.3. Switch compartment: open 31
9.4. Torque switching: set 32
9.5. Limit switching: set 33
9.5.1. End position CLOSED (black section): set 33
9.5.2. End position OPEN (white section): set 33
9.6. Intermediate positions: set 34
9.6.1. Running direction CLOSE (black section): set 34
9.6.2. Running direction OPEN (white section): set 35
9.7. Test run 35
9.7.1. Direction of rotation: check 35
9.7.2. Limit switching: check 36
9.7.3. PTC tripping device (option): test 36
9.8. Electronic position transmitter EWG 01.1 36
9.8.1. Measuring range: set 37
9.8.2. Current values: adjust 38
9.8.3. LED end position signalling: switch on/off 38
9.9. Potentiometer 39
9.9.1. Potentiometer setting 39
9.10. Electronic position transmitter RWG 39
9.10.1. Measuring range: set 40
9.11. Mechanical position indicator: set 41
9.12. Switch compartment: close 41
10. Commissioning – controls settings..................................................................................... 43
10.1. Controls: open 43
10.2. Type of seating: set 43
10.3. Push-to-run operation or self-retaining: set 44
10.4. Running indication (blinker transmitter): activate/deactivate 45
10.5. Torque fault in collective fault signal: activate/deactivate 45
10.6. Positioner 45
10.6.1. Input ranges (signal type) for setpoint and actual value 46
10.6.2. Behaviour on loss of signal (actuator reaction) 46
3
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Table of contents AM 01.1
4
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Safety instructions
1. Safety instructions
1.1. Basic information on safety
Standards/directives AUMA products are designed and manufactured in compliance with recognised
standards and directives. This is certified in a Declaration of Incorporation and an
EC Declaration of Conformity.
The end user or the contractor must ensure that all legal requirements, directives,
guidelines, national regulations and recommendations with respect to assembly,
electrical connection, commissioning and operation are met at the place of installation.
Safety instructions/warn- All personnel working with this device must be familiar with the safety and warning
ings instructions in this manual and observe the instructions given. Safety instructions
and warning signs on the device must be observed to avoid personal injury or property
damage.
Qualification of staff Assembly, electrical connection, commissioning, operation, and maintenance must
be carried out exclusively by suitably qualified personnel having been authorised by
the end user or contractor of the plant only.
Prior to working on this product, the staff must have thoroughly read and understood
these instructions and, furthermore, know and observe officially recognised rules
regarding occupational health and safety.
Commissioning Prior to commissioning, it is important to check that all settings meet the requirements
of the application. Incorrect settings might present a danger to the application, e.g.
cause damage to the valve or the installation. The manufacturer will not be held
liable for any consequential damage. Such risk lies entirely with the user.
Maintenance To ensure safe device operation, the maintenance instructions included in this manual
must be observed.
Any device modification requires prior consent of the manufacturer.
1.2. Range of application
AUMA part-turn actuators are designed for the operation of industrial valves, e.g.
butterfly valves and ball valves.
Other applications require explicit (written) confirmation by the manufacturer.
5
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Safety instructions AM 01.1
● Escalators
● Continuous duty
● Buried service
● Permanent submersion (observe enclosure protection)
● Potentially explosive areas, with the exception of zone 22
● Radiation exposed areas in nuclear power plants
No liability can be assumed for inappropriate or unintended use.
Observance of these operation instructions is considered as part of the device's
designated use.
Information These operation instructions are only valid for the "clockwise closing" standard
version, i.e. driven shaft turns clockwise to close the valve.
1.3. Applications in Ex zone 22 (option)
Actuators of the indicated series basically meet the requirements for applications in
dust hazardous locations of ZONE 22 in compliance with the ATEX directive 94/9/EC.
The actuators are designed to meet enclosure protection IP68 and fulfil the
requirements of EN 50281-1-1:1998 section 6 - Electrical apparatus for use in
presence of combustible dust, requirements for category 3 electrical equipment -
protected by enclosures.
To comply with all requirements of EN 50281-1-1:1998, it is imperative that the
following points are observed:
● In compliance with the ATEX directive 94/9/EC, the actuators must be equipped
with an additional identification – II3D IP6X T150 °C.
● The maximum surface temperature of the actuators, based on an ambient
temperature of +40 °C in accordance with EN 50281-1-1 section 10.4, is +150
°C. In accordance with section 10.4, an increased dust deposit on the equipment
was not considered for the determination of the maximum surface temperature.
● The correct connection of the thermoswitches or the PTC thermistors as well
as fulfilling the requirements of the duty type and the technical data are pre-
requisites for compliance with the maximum surface temperature of devices.
● The connection plug may only be plugged in or pulled out when device is dis-
connected from the mains.
● The cable glands used also have to meet the requirements of category II3 D
and must at least comply with enclosure protection IP68.
● The actuators must be connected by means of an external ground connection
(accessory part) to the potential compensation or integrated into an earthed
piping system.
● As a general rule, the requirements of EN 50281-1-1 must be respected in dust
hazardous locations. During commissioning, service, and maintenance, special
care as well as qualified and trained personnel are required for the safe operation
of actuators.
1.4. Warnings and notes
6
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Safety instructions
Information The term Information preceding the text indicates important notes and information.
7
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Identification AM 01.1
2. Identification
2.1. Name plate
Each device component (actuator, controls, motor) is equipped with a name plate.
Figure 1: Arrangement of name plates
8
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Identification
Descriptions
Type designation Figure 4: Type designation (example)
Order number The product can be identified using this number and the technical data as well as
order-related data pertaining to the device can be compiled.
Please always state this number for any product inquiries.
On the Internet at http://www.auma.com, we offer a service allowing authorised
users to download order-related documents such as wiring diagrams and technical
data (both in German and English), inspection certificates and the operation
instructions when entering the order number.
9
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Identification AM 01.1
AUMA power class for The switchgear used in the actuator controls (reversing contactors/thyristors) are
switchgear classified according to AUMA power classes (e.g. A1, B1, ....). The power class
defines the max. permissible rated power (of the motor) the switchgear has been
designed for. The rated power (nominal power) of the actuator motor is indicated in
kW on the motor name plate. For the assignment of the AUMA power classes to the
nominal power of the motor types, refer to the separate electrical data sheets.
For switchgear without assignment to any power classes, the actuator controls name
plate does not indicate the power class but the max. rated power in kW.
Data Matrix code When registered as authorised user, you may use the AUMA Support App to scan
the Data Matrix code and directly access the order-related product documents without
having to enter order number of serial number.
Figure 5: Link to the App store:
Control
Table 2: Control example (data on actuator controls name plate)
Input signal Description
24 V DC Control voltage 24 V DC for OPEN-CLOSE control via digital inputs
(OPEN, STOP, CLOSE)
115 V AC Control voltage 115 V AC for OPEN-CLOSE control via digital inputs
(OPEN, STOP, CLOSE)
0/4 – 20 mA Input current for setpoint control via analog input
10
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Transport, storage and packaging
Hovering load!
Risk of death or serious injury.
→ Do NOT stand below hovering load.
→ Attach ropes or hooks for the purpose of lifting by hoist only to housing and NOT
to handwheel.
→ Actuators mounted on valves: Attach ropes or hooks for the purpose of lifting
by hoist to valve and NOT to actuator.
→ Actuators mounted to gearboxes: Attach ropes or hooks for the purpose of lifting
by hoist only to the gearbox using eyebolts and NOT to the actuator.
→ Actuators mounted to controls: Attach ropes or hooks for the purpose of lifting
by hoist only to the actuator and NOT to the controls.
3.2. Storage
Long-term storage If the device must be stored for a long period (more than 6 months) the following
points must be observed in addition:
1. Prior to storage:
Protect uncoated surfaces, in particular the output drive parts and mounting
surface, with long-term corrosion protection agent.
2. At an interval of approx. 6 months:
Check for corrosion. If first signs of corrosion show, apply new corrosion protec-
tion.
3.3. Packaging
Our products are protected by special packaging for transport when leaving the
factory. The packaging consists of environmentally friendly materials which can easily
be separated and recycled. We use the following packaging materials: wood,
cardboard, paper, and PE foil. For the disposal of the packaging material, we
recommend recycling and collection centres.
11
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Assembly AM 01.1
4. Assembly
AUMA actuators and actuator controls can be operated without restriction in any
mounting position.
[1] Spacer
[2] Input shaft
[3] Handwheel
[4] Circlip
The actuator is mounted to the valve using a coupling (standard) or via lever. Separate
instructions are available for actuator mounting to the valve when equipped with
base and lever.
12
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Assembly
[1] Coupling
[2] Valve shaft
[3] Grub screw
[4] Screw
Assembly Information: Mount valve and actuator in the same end position.
- For butterfly valves: Recommended mounting position is end position
CLOSED.
- For ball valves: Recommended mounting position is end position OPEN.
1. Thoroughly degrease mounting faces of output mounting flanges.
2. Apply a small quantity of grease to the valve shaft [2].
3. Use handwheel to run actuator to mechanical end stop.
4. Place coupling [1] onto valve shaft [2] and secure against axial slipping by using
a grub screw, a circlip or a screw. Thereby, ensure that dimensions X, Y or Z
are observed (refer to figure and table <Coupling fitting dimensions>).
5. Apply non-acidic grease at splines of coupling.
6. Fit actuator.
Information: Ensure that the spigot (if provided) fits uniformly in the recess
and that the flanges are in complete contact.
7. If flange bores do not match thread:
7.1 Slightly rotate handwheel until bores line up.
7.2 If required, shift actuator position by one tooth on the coupling.
13
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Assembly AM 01.1
The mounting position of the local controls is selected according to the order. If, after
mounting the actuator to the valve or the gearbox on site, the local controls are in
an unfavourable position, the mounting position can be changed at a later date. Four
mounting positions are possible.
Figure 8: Mounting positions A and B
Hazardous voltage!
Risk of electric shock.
→ Disconnect device from the mains before opening.
14
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Assembly
2. Loosen 3 screws of the board, turn board to the new position and fasten the
screws.
3. Check whether O-ring is in good condition, correctly insert O-ring.
4. Turn local controls into new position and re-place.
15
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Electrical connection AM 01.1
5. Electrical connection
5.1. Basic information
Wiring diagram/terminal
The pertaining wiring diagram/terminal plan (both in German and English) is attached
plan to the device in a weather-proof bag, together with these operation instructions. It
can also be requested from AUMA (state order number, refer to name plate) or
downloaded directly from the Internet (http://www.auma.com).
Protection on site
For short-circuit protection and for disconnecting the actuator from the mains, fuses
and disconnect switches have to be provided by the customer.
The current values for respective sizing is derived from the current consumption of
the motor (refer to electrical data sheet) plus the current consumption of the controls.
If controls are mounted separately from actuator (controls on wall bracket): Consider
length and cross section of connecting cable when defining the protection required.
Power supply for the
If the controls (electronics) are supplied externally with 24 V DC, the power supply
controls (electronics) is smoothed via an internal 1,000 µF capacitor). When selecting a power supply,
care must be taken to consider the capacitor inrush current upon powering the unit
up.
Safety standards All externally connected devices shall comply with the relevant safety standards.
Cable installation in ac-
Signal and bus cables are susceptible to interference.
cordance with EMC
Motor cables are interference sources.
● Lay cables being susceptible to interference or sources of interference at the
highest possible distance from each other.
● The interference immunity of signal and bus cables increases if the cables are
laid close to the earth potential.
● If possible, avoid laying long cables and make sure that they are installed in
areas being subject to low interference.
● Avoid long parallel paths with cables being either susceptible to interference or
interference sources.
● For the connection of remote position transmitters, screened cables must be
used.
16
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Electrical connection
Type of current, mains Type of current, mains voltage and mains frequency must match the data on the
voltage and mains fre- motor name plate.
quency Figure 10: Motor name plate (example)
● Power terminals (U1, V1, W1, U2, V2, W2): max. 6 mm² flexible/10 mm² solid
●
PE connection : max. 6 mm² flexible/10 mm² solid
● Control contacts (1 to 50): max. 2.5 mm²
5.2.1. Terminal compartment: open
[1] Cover
[2] Screws for cover
[3] O-ring
[4] Screws for socket carrier
[5] Socket carrier
[6] Cable entry
[7] Blanking plug
[8] Cable gland (not included in delivery)
17
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Electrical connection AM 01.1
Hazardous voltage!
Risk of electric shock.
→ Disconnect device from the mains before opening.
4. Seal unused cable entries [6] with suitable blanking plugs [7].
5. Insert the cables into the cable glands [8].
5.2.2. Cable connection
18
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Electrical connection
Information Some actuators are equipped with an additional motor heater. The motor heater
minimises condensation within the motor.
19
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Electrical connection AM 01.1
[1] Cover
[2] Screws for cover
[3] O-ring
[4] Screws for socket carrier
[5] Socket carrier
[6] Cable entry
[7] Blanking plug
[8] Cable gland (not included in delivery)
1. Insert the socket carrier [5] into the cover [1] and fasten with screws [4].
2. Clean sealing faces of cover [1] and housing.
3. Check whether O-ring [3] is in good condition, replace if damaged.
4. Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
5. Fit cover [1] and fasten screws [2] evenly crosswise.
6. Fasten cable glands [8] applying the specified torque to ensure the required
enclosure protection.
5.3. Accessories for electrical connection
— Option —
5.3.1. Controls mounted to wall bracket
The wall bracket allows separate mounting of controls and actuator.
Application ● When mounted in confined spaces.
● If the actuator is subjected to high temperatures.
● In case of heavy vibration of the valve.
20
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Electrical connection
21
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Electrical connection AM 01.1
The open terminal compartment can be closed using a protective cover (not
illustrated).
5.3.4. Double sealed intermediate frame
When removing the electrical connection or due to leaky cable glands, ingress of
dust and water into the housing may occur. This is prevented effectively by inserting
the double sealed intermediate frame [2] between the plug/socket connector [1] and
the housing of the device. The enclosure protection of the device (IP68) will not be
affected, even if the electrical connection [1] is removed.
Figure 17: Electrical connection with double sealed intermediate frame
22
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Operation
6. Operation
✔ Perform all commissioning settings and the test run prior to motor operation.
23
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Operation AM 01.1
➥ The actuator can now be operated using the push buttons [1 – 3]:
- Run actuator in direction OPEN: Press push button [1] .
- Stop actuator: Press push button [2] Stop.
- Run actuator in direction CLOSE: Press push button [3] .
Information The OPEN - CLOSE operation commands can be given either in push-to-run operation
mode or in self-retaining mode. In self-retaining mode, the actuator runs to the defined
end position after pressing the button, unless another command has been received
beforehand.
➥ Now, it is possible to operate the actuator via remote control, via operation
commands (OPEN, STOP, CLOSE) or analogue setpoints (e.g. 0 – 20 mA).
24
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Operation
Information For actuators equipped with positioner, it is possible to optionally select between
open-close duty (REMOTE OPEN-CLOSE) and modulating duty (REMOTE
SETPOINT). Selection is made via REMOTE MANUAL input, e.g. based on a 24 V
DC signal (refer to wiring diagram).
25
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Indications AM 01.1
7. Indications
7.1. Indication lights
Figure 20: Local controls with indication lights
Information The three indication lights can be provided in different colours (deviating from the
standard).
Collective fault signal The collective fault signal [2] appears if one of the following events occurs (default
configuration):
● Torque fault: The set torque was exceeded before reaching an end position.
(This signal can be activated/deactivated via a switch in the controls.)
● Thermal fault: Motor protection has tripped, i.e. the motor is overheated.
● Phase failure: One phase is missing (3-ph AC motors only).
● PTC tripping device: Test complete
Running indication If the actuator is equipped with a blinker transmitter (wiring diagram designation:
S5), indication lights [1] and [3] can be used as running indication. The running
indication can be activated/deactivated via a switch in the controls. If the running
indication is active, the respective indication light blinks during operation.
7.2. Mechanical position indicator/running indication
Mechanical position indicator:
● Continuously indicates the valve position
(For a swing angle of 90°, the indicator disc [2] rotates by approximately 180°.)
● Indicates whether the actuator is running (running indication)
● Indicates that the end positions are reached (via indicator mark [3])
26
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Indications
[1] Cover
[2] Indicator disc
[3] Mark
[4] Symbol for position OPEN
[5] Symbol for position CLOSED
27
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Signals AM 01.1
8. Signals
8.1. Feedback signals via output contacts (binary)
The output contacts can be used to indicate operation modes of the actuator or the
controls as binary signals.
The signals are assigned according to the order. Example:
Output contact open = end position CLOSED not reached
Output contact closed = end position CLOSED reached
28
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Commissioning (basic settings)
29
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Commissioning (basic settings) AM 01.1
Information ● The swing angle set in the factory is indicated on the name plate:
30
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Commissioning (basic settings)
Information In general, the end stop OPEN does not have to be set.
1. Remove screw plug [1].
2. Move valve to end position OPEN with handwheel.
3. If the valve end position is not reached:
→ Slightly turn setting screw [2] counterclockwise until valve end position
OPEN can be safely set.
➥ Turning the setting screw [2] clockwise results in a smaller swing angle.
➥ Turning the setting screw [2] counterclockwise results in a larger swing
angle.
The switch compartment must be opened to perform the following settings (options).
31
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Commissioning (basic settings) AM 01.1
1. Loosen screws [2] and remove cover [1] from the switch compartment.
32
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Commissioning (basic settings)
2. Turn torque dial [4] to set the required torque (1 da Nm = 10 Nm). Example:
- Black torque switching head set to approx. 25 da Nm ≙ 250 Nm for direction
CLOSE
- White torque switching head set to approx. 20 da Nm ≙ 200 Nm for direction
OPEN
3. Fasten lock screws [3] again.
Information: Maximum tightening torque: 0.3 – 0.4 Nm
➥ The torque switch setting is complete.
Black section:
[1] Setting spindle: End position CLOSED
[2] Pointer: End position CLOSED
[3] Mark: End position CLOSED is set
White section:
[4] Setting spindle: End position OPEN
[5] Pointer: End position OPEN
[6] Mark: End position OPEN is set
33
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Commissioning (basic settings) AM 01.1
3. Press down and turn setting spindle [4] with screw driver in direction of the
arrow and observe the pointer [5]: While a ratchet click is felt and heard, the
pointer [5] moves 90° every time.
4. If the pointer [5] is 90° from mark [6]: Continue turning slowly.
5. If the pointer [5] moves to mark [6]: Stop turning and release setting spindle.
➥ The end position OPEN setting is complete.
6. If you override the tripping point inadvertently (ratchet click is heard after the
pointer has snapped): Continue turning the setting spindle in the same direction
and repeat setting process.
9.6. Intermediate positions: set
— Option —
Actuators equipped with DUO limit switching contain two intermediate position
switches. One intermediate position may be set for each running direction.
Figure 26: Setting elements for limit switching
Black section:
[1] Setting spindle: Running direction CLOSE
[2] Pointer: Running direction CLOSE
[3] Mark: Intermediate position CLOSED is set
White section:
[4] Setting spindle: Running direction OPEN
[5] Pointer: Running direction OPEN
[6] Mark: Intermediate position OPEN is set
34
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Commissioning (basic settings)
35
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Commissioning (basic settings) AM 01.1
➥ If the PTC tripping device is working properly, the tripping of the motor protection
is signalled via the red indication light "collective fault signal" on the local con-
trols.
2. Turn selector switch to position Reset.
36
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Commissioning (basic settings)
Setting elements The EWG is housed in the actuator switch compartment. The switch compartment
must be opened to perform any settings. ➔ Refer to <Switch compartment: open>.
All settings are made via the two push buttons [S1] and [S2].
Figure 27: View on control unit when switch compartment is open
For measuring range setting, voltage must be applied at the position transmitter.
Information ● Both measuring ranges 0/4 – 20 mA and 20 – 0/4 mA (inverse operation) can
be set.
During setting process, the measuring range (normal or inverse operation) is
assigned to the end positions by push button S1/S2 assignment.
● Setting mode activating clears the setting in both end positions and sets the
output current to a value of 3.5 mA. After activation, both end values (0/4 mA
and 20 mA) need to be reset.
● In case of inadvertent incorrect adjustment, the settings can always be reset
by renewed activation of the setting mode (simultaneous pressing of [S1] and
[S2]).
37
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Commissioning (basic settings) AM 01.1
Activate setting mode 1. Press both push buttons [S1] and [S2] and hold down for 5 seconds:
➥ By pulsing double flashes, the LED indicates that the setting mode is correctly
activated:
➥ For any other LED flash sequence (single/triple flashing): ➔ Refer to <Faults
during commissioning>.
Set measuring range 2. Operate valve in one of the end positions (OPEN/CLOSED).
3. Set desired output current (0/4 mA or 20 mA):
→ for 4 mA: Hold down push button [S1] for approx. 3 seconds,
until LED is slowly blinking .
→ for 0 mA: Hold down push button [S1] for approx. 6 seconds,
until LED is blinking fast .
→ for 20 mA: Hold down push button [S2] for approx. 3 seconds,
until LED is illuminated .
4. Operate valve into opposite end position.
➥ The value set in end position (0/4 mA or 20 mA) does not change during travel
in setting mode.
5. Perform setting in the second end position following the same steps.
6. Approach both end positions again to check the setting.
→ If the measuring range cannot be set:
Refer to <Faults during commissioning>.
→ If the current values (0/4/20 mA) are incorrect:
Refer to <Current values: adjust>.
→ If the current value fluctuates (e.g. between 4.0 – 4.2 mA):
<LED end position signalling: switch on/off>.
9.8.2. Current values: adjust
The current values (0/4/20 mA) set in end positions can be adjusted at any time.
Conventional values are e.g. 0.1 mA (instead of 0 mA) or 4.1 mA (instead 4 mA).
Information If the current value fluctuates (e.g. between 4.0 – 4.2 mA), the <LED end position
signalling> must be switched on for current adjustment.
→ Operate valve in desired end position (OPEN/CLOSED).
→ Reduce current value: Press push button [S1]
(the current is reduced by 0.02 mA every time the push button is
pressed)
→ Increase current value Press push button [S2]
(the current is increased by 0.02 mA every time the push button is
pressed)
9.8.3. LED end position signalling: switch on/off
The LED behaviour for end position reached can be set as follows: blinking/continuous
illumination or no illumination. During setting mode, end positions signalling is
switched on.
Switching on and off 1. Operate valve in one of the end positions (OPEN/CLOSED).
38
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Commissioning (basic settings)
9.9. Potentiometer
— Option —
The potentiometer is used as travel sensor and records the valve position.
Information This setting is only required if the potentiometer is directly wired to the customer
connection XK (refer to wiring diagram).
Setting elements The potentiometer is housed in the actuator switch compartment. The switch
compartment must be opened to perform any settings. ➔ Refer to <Switch
compartment: open>.
Setting is made via potentiometer [1].
Figure 28: View on control unit
[1] Potentiometer
Information Due to the ratio of the reduction gearing, the complete resistance range/stroke is not
always covered. Therefore, external adjustment (setting potentiometer) must be
provided.
1. Move valve to end position CLOSED.
2. Turn potentiometer [1] clockwise to the stop.
➥ End position CLOSED corresponds to 0 %
➥ End position OPEN corresponds to 100 %
3. Turn potentiometer [1] slightly in opposite direction.
4. Perform fine-tuning of the zero point at external setting potentiometer (for remote
indication).
9.10. Electronic position transmitter RWG
— Option —
The electronic position transmitter RWG records the valve position. On the basis of
the actual position value measured by the potentiometer (travel sensor), it generates
a current signal between 0 – 20 mA or 4 – 20 mA.
39
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Commissioning (basic settings) AM 01.1
Technical data
Table 10: RWG 4020
Data 3-wire or 4-wire system 2-wire system
Output current Ia 0 – 20 mA, 4 – 20 mA 4 – 20 mA
Power supply UV 1) 24 V DC (18 – 32 V) 14 V DC + (I x RB), max. 30 V
Max. current consumption 24 mA at 20 mA output current 20 mA
Max. load RB 600 Ω (UV – 14 V)/20 mA
Impact of power supply 0.1 %/V 0.1 %/V
Load influence 0.1 %/(0 – 600 Ω) 0.1 %/100 Ω
Temperature impact < 0.3 ‰/K
Ambient temperature2) –60 °C to +80 °C
Transmitter potentiometer 5 kΩ
1) Power supply possible via: AC, AM controls or external power supply
2) Depending on temperature range of the actuator: Refer to name plate
Setting elements The RWG is housed in the actuator switch compartment. The switch compartment
must be opened to perform any settings. Refer to <Switch compartment: open>.
Setting is made via three potentiometers [1], [2] and [3].
Figure 29: View on control unit when switch compartment is open
For measuring range setting, voltage must be applied at the position transmitter.
40
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Commissioning (basic settings)
9. Approach end position CLOSED again and check minimum value (0.1 mA or
4.1 mA). If necessary, correct the setting.
9.11. Mechanical position indicator: set
41
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Commissioning (basic settings) AM 01.1
42
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Commissioning – controls settings
Hazardous voltage!
Risk of electric shock.
→ Disconnect device from the mains before opening.
The type of seating can be set via two DIP switches on the logic board.
Limit seating
The limit switching is set in such a way that the actuator switches off at the desired
switching points. The torque switching acts as overload protection for the valve.
Torque seating
The torque switching is set to the desired tripping torque. After reaching the tripping
torque, the actuator is turned off.
43
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Commissioning – controls settings AM 01.1
The limit seating is used to signal that the limit switching will trip shortly before
reaching the set tripping torque. If this is not the case, either the indication light on
the local controls or the alarm contact K9 (collective fault signal) will signal a fault.
→ Set type of seating for end positions via DIP switches [S1] and [S3].
Figure 30: DIP switches on logic board
44
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Commissioning – controls settings
Information If the controls are equipped with a positioner, switches 1 and 2 (operation commands
from remote) must be in position OFF (push-to-run operation).
➥ Switch 6 in lower position (position ON): The signal "Torque fault in collective
fault signal" is activated.
➥ Switch 6 in upper position (position OFF): The signal "Torque fault in collective
fault signal" is deactivated.
10.6. Positioner
— (Option) —
45
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Commissioning – controls settings AM 01.1
→ Prior to positioner setting, set limit and torque switching as well as potentiometer
or electronic position transmitter.
10.6.1. Input ranges (signal type) for setpoint and actual value
The input range (signal type) for setpoint E1 and actual value E2 is set in the factory
and marked with a label on the cover plate of the positioner.
The type of signal can be modified at a later date exclusively for versions with setpoint
E1 ≠ 0/4 – 20 mA and split-range version. For these versions, the positioner board
is equipped with an additional contact.
Figure 34: Version with additional switch on the positioner board
0–5V
0 – 10 V
0 – 5 V2)
Information When changing the setting, a new label [5] indicating the set signal type must be
provided. Furthermore, the wiring diagram indicated on the name plate of the actuator
controls also changes.
10.6.2. Behaviour on loss of signal (actuator reaction)
In case of a loss of signal of setpoint E1 or actual value E2, the reaction of the actuator
can be programmed via switch [S2-7]. The complete selection range, however, is
only available for signals 4 – 20 mA.
46
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Commissioning – controls settings
Fail close
Fail open
0 – 20 mA 4 – 20 mA
0 – 20 mA 0 – 20 mA
0–5V 0–5V
0 – 10 V
Fail close 0 – 20 mA 4 – 20 mA
0–5V
Fail as is 0 – 20 mA 4 – 20 mA
0 – 10 V
Fail open 4 – 20 mA 0 – 20 mA
0–5V
47
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Commissioning – controls settings AM 01.1
End position CLOSED 1. Set selector switch to position Local control (LOCAL).
2. Move valve to end position CLOSED.
3. Connect lower setpoint to customer connection XK (terminals 2/3). The lower
setpoint (0 V, 0 mA or 4 mA) is indicated on the label [5].
4. If the red LED [V10] E1/E2 <4 mA is illuminated:
4.1 Verify polarity of setpoint E1.
4.2 Check whether external load is connected to customer connection XK
(terminals 23/24) (observe max. load RB), or
4.3 Connect terminals 23/24 across customer connection XK (terminals 23/24).
5. Measure setpoint E1: Connect measuring device for 0 – 5 V to measuring points
[MP3/MP4].
➥ For a setpoint E1 of 0 V or 0 mA, the voltmeter shows 0 V.
➥ For a setpoint E1 of 4 mA, the voltmeter shows 1 V.
6. If measured value is not correct: Correct setpoint E1.
7. Measure actual value E2: Connect measuring device for 0 – 5 V to measuring
points [MP1/MP2].
➥ For an actual value E2 of 0 mA, the voltmeter shows 0 V.
➥ For an actual value E2 of 4 mA, the voltmeter shows 1 V.
8. If measured value is not correct: Re-set potentiometer or electronic position
transmitter and perform adjustment once again, starting from step 1.
48
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Commissioning – controls settings
[P3] Potentiometer 0
[P4] Potentiometer max
[V27] Yellow LED: End position CLOSED reached
[V28] Green LED: End position OPEN reached
➥ The setting is correct if the yellow LED [V27] is switched on when reaching end
position CLOSED.
End position OPEN 10. Move valve to end position OPEN.
11. Measure actual value E2 (measuring points [MP1/MP2]):
➥ For an actual value E2 of 20 mA, the voltmeter shows 5 V.
12. If measured value is not correct: Re-set potentiometer or electronic position
transmitter and perform adjustment once again, starting from step 1.
13. Set maximum setpoint E1 (5 V or 20 mA, refer to label [5]).
14. Measure setpoint E1 (measuring points [MP3/MP4]):
➥ For a setpoint E1 of 5 V or 20 mA, the voltmeter shows 5 V.
15. If measured value is not correct: Verify setpoint E1.
16. Adjust positioner using potentiometer max [P4].
16.1 If both LEDs are OFF or the yellow LED [V27] is illuminated: Turn poten-
tiometer max [P4] slightly counterclockwise until the green LED [V28] is
illuminated.
16.2 If the green LED [V28] is illuminated: Turn potentiometer max [P4] clock-
wise until the green LED [V28] goes out. Then turn potentiometer 0 [P3]
slightly counterclockwise until the green LED [V28] is illuminated again.
➥ The setting is correct if the green LED [V28] is switched on when reaching
end position OPEN.
Dead band The dead band determines the sensitivity between switch-on point and switch-off
point. The smaller the dead band, the higher the sensitivity of the positioner.
49
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Commissioning – controls settings AM 01.1
Dead time The dead time prevents the operation to a new setpoint within a pre-determined time
(0.5 to 10 seconds). The number of starts can be reduced by setting the dead time
to a sufficiently high value.
Figure 38: Sensitivity setting
Dead band setting 1. Set selector switch to position Remote control (REMOTE).
2. Connect setpoint E1 to customer connection XK (terminals 2/3).
3. Set dead band using potentiometer Δ E [P9]:
→ Reduce dead band (increase sensitivity): Turn potentiometer counter-
clockwise.
→ Increase dead band (reduce sensitivity): Turn potentiometer clockwise.
Fine tuning Information: Fine tuning is only useful for output speeds <16 rpm. For 1-phase
AC motors, fine tuning is not possible.
4. Reduce dead band further by up to 0.25 % (increase sensitivity): Turn poten-
tiometer sens [P7] counterclockwise.
Dead time setting 5. Set dead time using potentiometer t-off [P10]:
→ Reduce dead time: Turn potentiometer t-off [P10] counterclockwise.
→ Increase dead time: Turn potentiometer t-off [P10] clockwise.
10.7. EMERGENCY command (EMERGENCY - OPEN/EMERGENCY - CLOSE)
— (Option) —
The EMERGENCY input (refer to wiring diagram) has to be connected to the control
voltage using an NC contact (closed circuit principle). In the event of an EMERGENCY
command (removal of the signal = NC contact is operated), the actuator runs to the
preset end position:
● EMERGENCY - CLOSE input: Actuator runs to end position CLOSED.
● EMERGENCY - OPEN input: Actuator runs to end position OPEN.
The EMERGENCY command is effective in all three selector switch positions (LOCAL,
OFF, REMOTE).
50
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Commissioning – controls settings
Disable EMERGENCY Figure 39: Interface board for available option EMERGENCY - OPEN/EMERGENCY
command - CLOSE
51
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Corrective action AM 01.1
Switch check
The red test buttons [1] and [2] are used for manual operation of the switches:
1. Turn test button [1] in direction of the TSC arrow: Torque switch CLOSED trips.
The red indication light (fault) on the local controls is illuminated.
2. Press push button OPEN to reset the fault (indication light) by operating the
device in the opposite direction.
3. Turn test button [2] in direction of the TSO arrow: Torque switch OPEN trips.
4. Press push button CLOSE to reset the fault (indication light) by operating the
device in the opposite direction.
If the actuator is equipped with a DUO limit switching (option), the intermediate
position switches (LSA and LSB) will be operated at the same time as the torque
switches.
1. Turn test button [1] in direction of the LSC arrow: Limit switch CLOSED trips.
2. Turn test button [2] in direction of the LSO arrow: Limit switch OPEN trips.
52
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Corrective action
11.2. Fuses
11.2.1. Fuses within the actuator controls
Hazardous voltage!
Risk of electric shock.
→ Disconnect device from the mains before opening.
F3 Internal 24 V DC supply
Information Only replace fuses with fuses of the same type and value.
53
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Corrective action AM 01.1
The actuator can be controlled again once the motor has cooled down ("collective
fault" indication light goes out).
Version with thermoswitch and additional thermal overload relay within the
controls (option)
The operation may only be resumed once the fault signal ("collective fault" indication
light) has been reset. The fault signal is reset via the overload relay integrated in the
actuator controls. Therefore the controls have to be opened at the cover and the
relay held down. The relay is located on the contactors.
Version with PTC thermistor (option)
The operation may only be resumed once the fault signal ("collective fault" indication
light) has been reset. The fault signal is reset via selector switch position Reset of
the local controls.
Figure 41: Selector switch on local controls
54
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Servicing and maintenance
AUMA
AUMA offer extensive service such as servicing and maintenance as well as customer
Service & Support product training. For the relevant contact addresses, please refer to <Addresses>
in this document or to the Internet (www.auma.com).
55
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Servicing and maintenance AM 01.1
56
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Technical data
57
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Technical data AM 01.1
58
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Technical data
Service conditions
Use Indoor and outdoor use permissible
Mounting position Any position
Installation altitude ≤ 2,000 m above sea level
> 2,000 m above sea level, please contact AUMA
Ambient temperature Standard: –40 °C to +80 °C (part-turn actuators for open-close duty with 3-phase AC mo-
tors)
–40 °C to +70 °C (part-turn actuators for open-close duty with 1-phase AC mo-
tors)
–40 °C to +60 °C (part-turn actuators for modulating duty)
Options: –60 °C to +60 °C
0 °C to +120 °C (part-turn actuators for open-close duty with 3-phase AC motors)
For actual version, refer to actuator name plate.
Enclosure protection according Standard: IP68 with AUMA 3-phase AC motor/1-phase AC motor
to EN 60529 For special motors differing enclosure protection: refer to name plate.
Option: DS Terminal compartment additionally sealed against interior (double sealed)
According to AUMA definition, enclosure protection IP68 meets the following requirements:
● Depth of water: maximum 8 m head of water
● Duration of continuous immersion in water: Max. 96 hours
● Up to 10 operations during continuous immersion
Modulating duty is not possible during continuous immersion.
For actual version, refer to actuator name plate.
Pollution degree Pollution degree 4 (when closed) according to EN 50178
Vibration resistance according 2 g, from 10 to 200 Hz
to IEC 60068-2-6 Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength
may not be derived from this. Valid for part-turn actuators in version AUMA NORM (with
AUMA plug/socket connector, without actuator controls). Not valid in combination with
gearboxes.
Corrosion protection Standard: KS: Suitable for installation in industrial units, in water or power plants with a
low pollutant concentration as well as for installation in occasionally or perman-
ently aggressive atmosphere with a moderate pollutant concentration (e.g.
wastewater treatments plants, chemical industry)
Option: KX: Suitable for installation in extremely aggressive atmospheres with high hu-
midity and high pollutant concentration
KX-G : same as KX, however aluminium-free version (outer parts)
Finish coating Powder coating
Colour Standard: AUMA silver-grey (similar to RAL 7037)
Option: Other colours are possible on request.
Lifetime AUMA part-turn actuators meet or even exceed the lifetime requirements of EN 15714-2.
Detailed information can be provided on request.
Further information
EU Directives Electromagnetic Compatibility (EMC): (2004/108/EC)
Low Voltage Directive: (2006/95/EC)
Machinery Directive: (2006/42/EC)
59
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Technical data AM 01.1
60
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Technical data
Service conditions
Use Indoor and outdoor use permissible
Mounting position Any position
Installation altitude ≤ 2 000 m above sea level
> 2,000 m above sea level, please contact AUMA
Ambient temperature Standard: –40 °C to +70 °C
Options: -60 °C to +60 °C, extreme low temperature version incl. heating system
Low temperature versions incl. heating system for connection to external power
supply 230 V AC or 115 V AC.
For actual version, refer to actuator controls name plate.
Enclosure protection according Standard: IP68 with AUMA 3-phase AC motor/1-phase AC motor
to EN 60529 For special motors differing enclosure protection: refer to name plate.
Option: DS Terminal compartment additionally sealed against interior (double sealed)
According to AUMA definition, enclosure protection IP68 meets the following requirements:
● Depth of water: maximum 8 m head of water
● Duration of continuous immersion in water: Max. 96 hours
● Up to 10 operations during continuous immersion
Modulating duty is not possible during continuous immersion.
For actual version, refer to actuator controls name plate.
Pollution degree Pollution degree 4 (when closed) according to EN 50178
Vibration resistance according 2 g, from 10 to 200 Hz
to IEC 60068-2-6 Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength
may not be derived from this. Valid for multi-turn actuators in version AUMA NORM (with
AUMA plug/socket connector, without actuator controls). Not valid in combination with
gearboxes.
61
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Technical data AM 01.1
Service conditions
Corrosion protection Standard: KS: Suitable for installation in industrial units, in water or power plants with a
low pollutant concentration as well as for installation in occasionally or perman-
ently aggressive atmosphere with a moderate pollutant concentration (e.g.
wastewater treatments plants, chemical industry)
Option: KX: Suitable for installation in extremely aggressive atmospheres with high hu-
midity and high pollutant concentration
Finish coating Powder coating
Two-component iron-mica combination
Colour Standard: AUMA silver-grey (similar to RAL 7037)
Option: Other colours are possible on request.
Wall bracket AM mounted separately from the actuator, including plug/socket connector. Connecting cable
on request. Recommended for high ambient temperatures, difficult access, or in case of
heavy vibration during service.
Cable length between actuator and AM max. 100 m. Not suitable for version with potentiometer
in the actuator. Instead of the potentiometer, the actuator has to be provided with EWG.
Further information
Weight Approx. 7 kg (with AUMA plug/socket connector)
EU Directives Electromagnetic Compatibility (EMC): (2004/108/EC)
Low Voltage Directive: (2006/95/EC)
Machinery Directive: (2006/42/EC)
62
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Spare parts
63
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Spare parts AM 01.1
Information: Please state device type and our order number (see name plate) when ordering spare parts. Only
original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts
AUMA from any liability. Delivered spare parts may slightly vary from the representation in these instructions.
Ref. Designation Type Ref. Designation Type
no. no.
001.0 Housing Sub-assembly 539.0 Screw plug Sub-assembly
005.0 Drive shaft Sub-assembly 542.0 Handwheel with ball handle
005.1 Motor coupling Sub-assembly 553.0 Mechanical position indicator Sub-assembly
005.3 Manual drive coupling 554.0 Socket carrier for motor plug/socket Sub-assembly
connector with cable harness
006.0 Worm wheel Sub-assembly 556.0 Potentiometer for position transmitter Sub-assembly
009.0 Planetary gearing for manual drive Sub-assembly 556.1 Potentiometer without slip clutch Sub-assembly
017.0 Torque lever 557.0 Heater Sub-assembly
018.0 Gear segment Sub-assembly 558.0 Blinker transmitter including pins at Sub-assembly
wires (without impulse disc and insula-
tion plate)
019.0 Crown wheel 559.0 Control unit with torque switching Sub-assembly
heads and switches
022.0 Drive pinion II for torque switching Sub-assembly 559.0 Control unit with magnetic limit and Sub-assembly
torque transmitter (MWG) for Non-in-
trusive version in combination with
AUMATIC integral controls
023.0 Output drive wheel for limit switching Sub-assembly 560.0–1 Switch stack for direction OPEN Sub-assembly
024.0 Drive wheel for limit switching Sub-assembly 560.0–2 Switch stack for direction CLOSE Sub-assembly
025.0 Locking plate Sub-assembly 560.1 Switch for limit/torque Sub-assembly
058.0 Wire for protective earth Sub-assembly 560.2 Switch case
070.0 Motor (VD motor incl. ref. no. 079.0) Sub-assembly 566.0 Position transmitter EWG/RWG Sub-assembly
079.0 Planetary gearing for motor drive Sub-assembly 566.1 Potentiometer for RWG without slip Sub-assembly
(SQ/SQR 05.2 – SQ SQR 14.2 for VD clutch
motor)
155.0 Reduction gearing Sub-assembly 566.2 Position transmitter board for RWG Sub-assembly
500.0 Cover Sub-assembly 566.3 Wire harness for RWG Sub-assembly
501.0 Socket carrier (complete with sockets) Sub-assembly 567.1 Slip clutch for potentiometer Sub-assembly
502.0 Pin carrier without pins Sub-assembly 583.0 Motor coupling on motor shaft Sub-assembly
503.0 Socket for control Sub-assembly 583.1 Pin for motor coupling Sub-assembly
504.0 Socket for motor 584.0 Retaining spring for motor coupling
505.0 Pin for controls Sub-assembly 596.0 Output drive flange with end stop Sub-assembly
506.0 Pin for motor Sub-assembly 612.0 Screw plug for end stop Sub-assembly
507.0 Cover for electrical connection Sub-assembly S1 Seal kit, small Set
525.0 Coupling Sub-assembly S2 Seal kit, large Set
64
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Spare parts
65
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Spare parts AM 01.1
Information: Please state device type and our order number (see name plate) when ordering spare parts. Only
original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts
AUMA from any liability. Delivered spare parts may slightly vary from the representation in these instructions.
Ref. Designation Type
no.
001.0 Housing
002.0 Local controls Sub-assembly
002.5 Selector switch Sub-assembly
003.0 Signal and control board Sub-assembly
003.1 Primary fuse F1/F2
003.2 Fuse cover
004.0 Carrier for contactors
006.0 Power supply unit Sub-assembly
006.1 Secondary fuse F3
006.2 Secondary fuse F4
008.0 Interface board Sub-assembly
008.1 Interface board
008.2 Cover plate for interface board
009.0 Logic board Sub-assembly
013.0 Adapter board Sub-assembly
500.0 Cover Sub-assembly
501.0 Socket carrier (complete with sockets) Sub-assembly
502.0 Pin carrier without pins Sub-assembly
503.0 Socket for controls Sub-assembly
504.0 Socket for motor Sub-assembly
505.0 Pin for controls Sub-assembly
506.0 Pin for motor Sub-assembly
507.0 Cover for electrical connection Sub-assembly
508.0 Switchgear Sub-assembly
509.1 Padlock
S Seal kit Set
66
OPERATING MANUAL
Cartex®
applies to all mechanical seals of the same series
PLEASE READ this manual carefully and OBSERVE the information contained as to:
If there are any unclear points please contact BURGMANN by all means.
Any person being involved in assembly, Mechanical seals are often used for sealing
disassembly, start up, operation and maintenance hazardous substances. The valid regulations
of the BURGMANN Mechanical Seal must have for handling hazardous substances have to be
read and understood this Operating Manual and observed by all means.
in particular the safety notes. We recommend the
user to have this confirmed. Medium and/or supply medium may splash out
if the seal fails. Personal injury may be
BURGMANN Mechanical Seals are prevented by the user providing for splash
manufactured on a high quality level (quality protection and wearing safety goggles. Care has
management EN ISO 9001: 2000) and they keep to be taken by the user for proper disposal of the
a high working reliability. Yet, if they are not leakage.
operated within their intended purpose or
handled inexpertly by untrained personnel they The user has to check what effects a failure of
may cause risks. the mechanical seal might have and what safety
measures have to be taken to prevent personal
The machine has to be put up in such a way that injury or damage to the environment.
seal leakage can be led off and disposed properly
and that any personal injury caused by spurting
product in the event of a seal failure is avoided.
TRANSPORT
Any operation mode that affects the operational
safety of the mechanical seal is not permitted. If not specified differently by contract the BURGMANN
standard packing is used which is suitable for dry transport
Unauthorised modifications or alterations which by truck, train or plane. The warning signs and notes on the
affect the operational safety of the mechanical packing must be observed.
seal are not permitted.
Notes for income inspection:
BURGMANN mechanical seals must be operated, • Check packaging for visible damages.
maintained or repaired by authorised, trained • Open packaging carefully. Do not damage or lose parts
supplied separately.
and instructed personnel only.
• Check if consignment is complete (delivery note). Inform
the supplier immediately in writing if parts are damaged
The responsibilities for the respective jobs to be or missing.
done have to be determined clearly and observed
in order to prevent unclear competencies from the Especially inboard side of the mechanical seal has to be
point of safety. protected from damage during transport and storage. The
transport case in which the seal is supplied is well suited for
Any work to be done on the mechanical seal is this purpose and should be kept for a possible return
only permitted when the seal is neither transport.
operating nor pressurised.
For the stock keeping of elastomers special conditions are Check in case of a preservation of complete plants with
required. For all rubber-elastic parts the rules of ISO 2230- mechanical seals installed:
1973 (E) are valid. For reasons of safety BURGMANN • the compatibility of the chosen preservation agent with
recommend to replace the stock in store after 3 years at the the seal materials and with the elastomers
latest. • no impairment of the seal’s axial movability by
conglutination or by gumming
Sliding materials and elastomers are subject to material-
specific and time-based alterations (distortion, ageing) which
might reduce the full efficiency of the seals. Yet, this may be
avoided by observing the storage instructions. PRODUCT INFORMATION
IMPORTANT! Store the seal in the original packing The CARTEX® mechanical seal concept has been specially
lying on a flat surface. developed for machines and applications in refineries and
petrochemicals plants. At the heart of the CARTEX® are tried
Conveniences for storing of mechanical seals and tested elements, such as the rotating seat, which have
• dustfree been in successful service for years. Be it for retrofits, initial
• moderately ventilated equipping or the conversion of machines previously equipped
• constantly tempered with stuffing box packings, the CARTEX® is ideal for
relative air humidity below 65 %, standardisation projects due to the wide range of applications
temperature between 15 °C and 25 °C. for which it can be used.
Operation under several limit values simultaneously should We can only guarantee the safe and efficient functioning of
be avoided as higher loads (pressure, temperature, speed) can mechanical seals in individual cases if we have been
increase wear or lead to damage of sliding faces or comprehensively informed of the operating conditions to
elastomers. This could result in a shorter service life and in which they will be subject, and if this has been confirmed in a
the risk of a sudden seal failure endangering men and separate agreement. In case of doubt BURGMANN has to be
environment. consulted before start up.
Product pressure and sliding speed We reserve the right to carry out modifications, even if
they have not yet been considered in this manual.
Cartex®-SNO /-SN /-QN Cartex®-DN
Cartex®-ASPN+ABPN Cartex®-ASDN+ABDN
Cartex®-ASTN+ABTN
DESIGNATED USE
This mechanical seal is exclusively designed for the use in
the specified application. A different utilisation or a
utilisation going beyond the specification is considered
contrary to its designated use and excludes a liability by the
manufacturer.
The data given are for the seal. The machine data have to be
observed in addition by all means. MATERIALS
The operating data for the respective application, such as Designation acc. to EN 12756
medium to be sealed, operating pressure, operating
temperature, speed, etc. can be taken from the corresponding seal face, Q1 silicon carbide
machine data sheets. stationary B1 carbon graphite
seat, rotating Q1 silicon carbide
Connections construction G CrNiMo- steel, 1.4571
elements
Connections springs M Hastelloy®-C4, 2.4610
d1 < 38 mm (< 1.500") 1/4 NPT- thread o-rings V FPM
d1 ≥ 38 mm (≥ 1.500") 3/8 NPT- thread E EPDM
K perfluorocarbon rubber
Cartex®-SN / ASPN / ABPN U1 perfluorocarbon
Circulation (flushing) "IN" at connection » A « rubber/PTFE
rotary shaft seal P NBR
Cartex®-QN / ASTN / ABTN T3 PTFE, carbon reinforced
Circulation (flushing) "IN" at connection » A « gasket Buratherm® Buratherm
Supply medium (quench) "IN/OUT" at connections T2 PTFE, glass fibre reinforced
»B« throttle ring T12 PTFE, carbon-graphite
reinforced
Cartex®-DN /ASDN / ABDN
Supply medium "IN/OUT" at connections » C «
Cartex®-DN If this is not the case or if there are other malfunctions the
Cartex®-ASDN / ABDN mechanical seal has to be shut down, removed and checked
Operation with barrier pressure (pressurised supply for reasons of safety.
fluid)
When operating as a double seal a barrier fluid system Leakage of mechanical seal at outboard side has to be
(API, Plan 53 / 54) is required (where both seals are drained and disposed properly.
pressurised).
Forced fluid circulation by means of a pumping device IMPORTANT! Components which may get in contact with
in the seal when the shaft rotates. the leakage have to be corrosion-resistant or have to be
adequately protected.
External fluid reservoir,
pressurised. Thermosiphon or WARNING If the medium to be sealed and/or the
forced circulation, if required. barrier/buffer/quench liquid is subject to the Hazardous
1 if specified Substances Regulation (GefStoffV), the instructions for
(PS = pressure switch) handling dangerous substances (safety data sheets to EU
(PI = pressure indicator) Directive 91/155/EEC) and the accident prevention
(FI = flow indicator) regulations must be observed.
external pressure source
normally open
fill port Cartex®-DN
level indicator Cartex®-ASDN / ABDN
reservoir Operation with barrier pressure (pressurised supply
if specified fluid)
drain valve
ATTENTION! If the barrier pressure falls below the
Operation with pressureless supply fluid pressure in the machine the medium to be sealed may
penetrate through the seal gap, contaminating the barrier
When working in tandem, the reservoir liquid is used as a fluid. A regular control of the barrier pressure and change of
"dead-end quench" (API, Plan 51) or a circulating buffer the barrier fluid is recommended.
fluid (API, Plan 52) (with the seal on the production side
pressurised externally) depending on operating conditions. Operation with pressureless supply fluid
Forced fluid circulation by means of a pumping device
in the seal when the shaft rotates. ATTENTION! Due to the overpressure in the stuffing box
the medium to be sealed will penetrate through the sealing
External fluid reservoir, gap of the inboard seal into the buffer fluid which will
pressure less. Thermosiphon consequently be contaminated. For plan 52 BURGMANN
or forced circulation, if recommend a regular control and exchange of the buffer
required. fluid.
1 if specified
(PS = pressure switch)
(PI = pressure indicator)
(FI = flow indicator) UTILITIES & TOOLS
normally open
fill port ethyl alcohol
level indicator cellulose-tissue (no rag, no cloth!)
reservoir suitable lubricant for elastomer-sealing rings: e.g.
if specified "TURMOPOLGREASE SH 2 D", make Lubricant
drain valve Consult (LUBCON)
Elastomers made of EP-rubber must never come
into contact with lubricants on the base of mineral oil
(swelling, decomposition).
EMISSIONS liquid screw retention, e.g. "LOCTITE® No. 243" ,
make LOCTITE Corporation
A mechanical seal is a dynamic seal that cannot be free of set of hexagon keys (Allen keys)
leakage due to physical and technical reasons. Seal design, set of open end or ring spanners
manufacture tolerances, operating conditions, running quality torque wrench
of the machine, etc. mainly define the leakage value. In fact,
compared to other sealing systems (e.g. packings) there is
few leakage.
PRELIMINARIES INSTALLATION
ATTENTION! To prevent damage to the seal, do not The mechanical seal is supplied as a precisely set cartridge
remove it from its packaging until all the work described unit, premounted at works, and does not require any
below has been completed. adjustment during installation.
Check the parts of the machine for: For installation the assembly drawing of mechanical seal has
to be on hand.
PROCESS AGENTS
Supply fluid according to operating requirements.
For supply fluid preferably such media should be used
only which are compatible with the product medium and
may leak out to atmosphere at outboard side of seal
without risk for staff and environment.
ATTENTION! Supply fluids may not form residues on For reasons of safety the temperature of buffer fluid should
the seal faces. not exceed 60 ºC (at higher temperatures consultation
with BURGMANN) and should be at least 40 ºC below the
Supply fluids e. g.: boiling point at normal pressure measured at the outlet line
light oil without high pressure additives from the mechanical seal. Regulation of the temperature by
water/ethylene glycol mixture without anti-corrosion cooling the barrier fluid inside the barrier system.
additives
steam-condensate; demineralised water Operation with barrier pressure (pressurised supply
fluid)
The efficiency of the integrated pumping device depends on
different parameters e.g.: The barrier pressure must exceed the pressure to be sealed
the viscosity of supply medium during every state of operation.
the shaft speed
ATTENTION! If the barrier pressure falls below the
A clarification with BURGMANN is recommended. pressure in the machine the medium to be sealed may
penetrate through the seal gap, contaminating the barrier
fluid. A regular control of the barrier pressure and change of
the barrier fluid is recommended.
SAFE OPERATION
Operation with pressureless supply fluid
The mechanical seal at inboard has to be constantly wetted
by the product in its liquid form, in particular when the ATTENTION! Due to the overpressure in the stuffing box
machine is started or stopped. The machine design has to be the medium to be sealed will penetrate through the sealing
such as to take this necessity into consideration. gap of the inboard seal into the buffer fluid which will
consequently be contaminated. For plan 52 BURGMANN
Damages due to dry-running are excluded from the warranty. recommend a regular control and exchange of the buffer
fluid.
If the medium to be pumped builds deposits or tends to
solidify during cooling down or standstill of the machine the
stuffing box has to be flushed with suitable clean liquid. Flow
and liquid to be determined by the user. TEST RUN
If the operation limit values and the instructions given in this Safety checks before start up
manual are observed a trouble-free operation of the • Seal assembly fixtures removed
mechanical seal can be expected. • Torque transmission (set screws) between mechanical
seal and shaft duly installed
particularly for: • Supply connections tightened pressure-sealed
Cartex®-SNO • Disposal connections installed environmentally safe
Cartex®-SN
Cartex®-ASPN / ABPN The mechanical seal must never turn dry. The seal cartridge
For a single mechanical seal the pressure in the seal must be filled with liquid to avoid the risk of a dry-run and
chamber (stuffing box pressure) should always be higher consequently a damage of the sliding faces.
than the ambient pressure at the machine. Otherwise the When the shaft turns the filled-in liquid warms up due to
machine will suck in air via the sliding faces, which will frictional heat produced by the sliding faces. An
result in dry-running and consequent failure of the unpermitted pressure increase due to this temperature rise
mechanical seal. must be avoided.
particularly for: Damages due to dry-running are excluded from the warranty.
Cartex®-QN
Cartex®-ASTN / ABTN particularly for:
As for Cartex®-SNO / SN, Cartex®-ASPN / ABPN: but in Cartex®-DN
addition: Cartex®-ASDN / ABDN
Quench medium should flow through the mechanical • Connections must be assigned according to direction of
seal. shaft rotation (see instruction
"INTEGRAL CIRCULATION DEVICE" on the
particularly for: drawing)
Cartex®-DN
Cartex®-ASDN / ABDN ATTENTION! Circulation of the buffer fluid is only
ATTENTION! Circulation of the buffer fluid is only assured when the shaft rotates. At standstill the seal cannot
assured when the shaft rotates. At standstill the seal cannot be cooled because the fluid does not circulate. This can result
be cooled because the fluid does not circulate. This can result in damages caused by excessive heating!
in damages caused by excessive heating!
ATTENTION! Set screws with cup point must be used
only once. Repeated fastening endangers the safety of force
transmission.
Safety checks before start up When working in tandem, the reservoir liquid is used as a
• Seal assembly fixtures removed "dead-end quench" (API, Plan 51) or a circulating buffer
• Torque transmission (set screws) between mechanical fluid (API, Plan 52) (with the seal on the production side
seal and shaft duly installed pressurised externally) depending on operating conditions.
• Supply connections tightened pressure-sealed
• Disposal connections installed environmentally safe API, Plan 52:
• Connections must be assigned according to direction of
shaft rotation (see instruction • Fill supply circuit and mechanical seal with fluid and
"INTEGRAL CIRCULATION DEVICE" on the vent thoroughly.
drawing)
IMPORTANT! To avoid dry run at the sliding faces the
When operating as a double seal a barrier fluid system supply circuit has to be thoroughly vented a few times before
(API, Plan 53 / 54) is required (where both seals are start up.
pressurised).
In case of vertical arrangement:
• Flood mechanical seal and barrier circuit with clean • To ensure a complete venting of the M.S. carefully push
liquid (particles size ≤ 50 µm) and vent thoroughly. down the outboard seal face with a suitable tool through
the hole in cover.
IMPORTANT! To avoid dry run at the sliding faces the
barrier circuit has to be thoroughly vented a few times before • Make sure that the buffer fluid may circulate unimpeded.
start up. Forced fluid circulation by means of a pumping device
in the seal when the shaft rotates.
In case of vertical arrangement:
• To ensure a complete venting of the M.S. carefully push • Flood machine and seal area with medium.
down the outboard seal face with a suitable tool through • Thoroughly vent seal and circulation system.
the hole in cover. • After a short start up period repeat the venting procedure
several times with the machine being at standstill.
• Make sure that the barrier fluid may circulate unimpeded.
Forced fluid circulation by means of a pumping device
in the seal when the shaft rotates.
A duly operation includes a regular check of the following If, for compelling reasons, a repair has to be carried out
parameters: on site (e.g. no. spare seal on stock, long transport, problems
• Barrier pressure
with customs) the seal may be repaired in a clean room by
• Barrier fluid temperature
trained personnel of the operating company under the
• Barrier fluid quantity
instruction of BURGMANN maintenance personnel.
• Tightness of the supply circuit
• Leakage of mechanical seal
In the event of excessive leakage, note changes in the IMPORTANT! When removing, please observe:
amount and switch the machine off if necessary. current accident prevention regulations
If a constant amount is leaking in a steady flow, the
regulations for handling hazardous substances
mechanical seal is damaged.
In the event of a prohibited temperature rise, the WARNING! Seals that have been used with hazardous
machine must be stopped for safety reasons. substances must be properly cleaned so that there is no
possible danger to people or to the environment.
If there is a malfunction which you cannot correct on your
own, or if the cause of malfunction is not clearly recognisable IMPORTANT! The packaging used to transport the seal
please immediately contact the nearest BURGMANN must
agency, a BURGMANN service centre or the BURGMANN be identified with the relevant hazard symbol and
headquarters. include the safety data sheet for the product and/or
barrier/buffer/quench medium
• Drain the mechanical seal. Collect the drained liquid and DISPOSAL
dispose it properly.
Usually, the BURGMANN mechanical seals can be easily
IMPORTANT! Insert all assembly fixtures into the groove disposed after a thorough cleaning.
in the cover and fix them. Metal parts (steels, stainless steels, non-ferrous heavy
metals) divided into the different groups belong to scrap
• Screw out the cup pointed set screws and dispose. metal waste.
Ceramic materials (synthetic carbons, ceramics, carbides)
ATTENTION! Set screws with cup point must be used belong to waste products. They can be separated from
only once. Repeated fastening endangers the safety of force their housing materials, as are physiologically recognised
transmission. as safe.
Synthetic materials/plastics (elastomers, PTFE) belong to
• Loosen all screw connections between seal cartridge and special waste.
the respective machine parts. CAUTION! Material containing fluorine must not be
burnt.
• Remove the seal in the reverse sequence as described for IMPORTANT! Some of the synthetic materials, divided
assembly (set up). into the different groups can be recycled.
www.regalbeloit.com
GES 4.0 / R10
TerraMAX Motor Installation, Operation and Maintenance
Product line: SCA / TCA / QCA / TCN / TCT / TCE
The TerraMAX series motors are designed • Shaft locking clamps, where supplied,
and manufactured to be robust and reliable are fitted securely
with minimal maintenance. The following • Remove shaft locking clamps and turn
items should be taken into consideration to rotor by one full rotation at least once
ensure a trouble free installation and a fortnight and replace shaft locking
reliable operation throughout the motor clamps
life. • Anti-condensation heaters, where fitted,
should be energized if the environment
Inspection is likely to be damp
TerraMAX motors are delivered through
safe and reliable transport in appropriate Installation
packing to avoid damage during transit. The following items should be considered
On receipt of the motor thoroughly inspect on installation to ensure reliable operation
the unit for any transit damage, if needed of the motor:
be in the presence of an insurance agent.
Any equipment damage or shortfall should Surroundings
be immediately advised to the nearest • Ensure that the motor is properly
Regal regional office. protected against ingress of oil, water or
dust especially if construction work is in
Check the following: progress around the motor,
• Rating plate details and enclosure are as • Ensure air intake is not obstructed. Refer
ordered to dimension BL in the catalogue,
• Shaft turns freely (in absence of shaft • When installing hazardous location
locking clamp) motors, make sure that the zone and
• Condensation drain holes are in the gas group or dust and temperature
correct position for the motor mounting classification on motor nameplate are
application (they should be located at complied with.
the lowest point of the motor when it is in
Mounting
its operating position)
• Bed plates or slide rails should be
• If the winding is Insulation Resistance
firmly fixed to a solid, level foundation
(IR) tested to earth, ensure that the
to ensure the motor remains rigid and
thermal protectors are not inadvertently
vibration free
damaged. (The thermistor leads should
• Shims or packers (if required) must be
be shorted together whilst IR testing
of adequate size and placed adjacent to
takes place)
and between base fixing screws
• Protective transport coatings on shafts
Storage and/or flanges must be removed prior to
When the motor is not for immediate use connection to the driven load
store as follows: • A light coating of grease to shafts and/
• Clean and dry location or flanges will inhibit corrosion during
• Free from vibration (vibration can service and assist removal of pulleys or
damage bearings) couplings
`
As a general rule the midpoint of the applied Where higher than recommended axial loads
force should be at the midpoint of the shaft are necessary different bearing types will be
and it is good engineering practice to mount required. (Refer to Regal regional location).
the motor pulley with hub and locking screw
at the shaft end.
`
Hazardous location motors
Product line: TCN / TCT / TCE
Standard motors in the range of frame sizes 80 to 355 with appropriate modifications are
certified for use in hazardous areas as below.
Ex nA, Zone 2, Group II, Temperature class T3, TAmb -20°C TO +50°C,
Ex tc, Zone 22, Group II, Temperature class T135, TAmb -20°C TO +50°C,
Ex ec, Zone 2, Group II, Temperature class T3, TAmb -20°C TO +50°C,
Ex tb, Zone 21, Group II, Temperature class T135, TAmb -20°C TO +50°C,
Ex eb, Zone 1, Group II, Temperature Class T3, TAmb -20°C TO +50°C,
LUBRICATION PROCEDURE:
NOTE: Frames 80 through 180 use
sealed bearings and are not
re-greaseable.
Frames 200 through 355 use open
re-greaseable bearings.
Bearing Grease
Bearing 3000 r/min 1500 r/min 1000 r/min 750 r/min
bore Qty
number (2)
[mm] [g] Ball Roller Ball Roller Ball Roller Ball Roller
6312/NU312 60 22 3000 1500 9000 4500 12000 6000 12000 6000
6313/NU313 65 24 2000 1000 8000 4000 10000 5000 10000 5000
6314/NU314 70 26 1500 750 4000 2000 7000 3500 7000 3500
6316/NU316 80 38 1000 500 - - - - - -
6317/NU317 85 38 1000 500 4000 2000 7000 3500 7000 3500
6319/NU319 90 45 - - 3000 1500 5000 2500 5000 2500
6322/NU322 95 60 - - 3000 1500 5000 2500 5000 2500
1) 2)
Based on maximum grease service life of 20,000 hours Refer to Nameplate / Motor to confirm bearing size.
The graph below shows the TerraMAX motor’s loadability with a frequency converter.
IM 01C25B01-01E
15th Edition
<7. Operation> 7-1
7. Operation
7.1 Preparation for Starting Venting Gas from the Transmitter Pressure-
detector Section
Operation
This section describes the operation procedure for
is constructed to be self-venting, no venting
the EJ 110 , EJ 120 and EJ 130 as shown
make the piping self-venting, refer to subsection
pressure connection: right side) when measuring
430 , EJ 440 and
open even after venting gas.
EJ 310
(b) Turn ON power and connect the communicator.
pressure.
Open the terminal box cover, and connect
the communicator to the SUPPLY + and
NOTE – terminals.
Check that the process pressure tap valves,
drain valves, and 3-valve manifold stop valves transmitter is operating properly. Check
on both the low pressure and high pressure parameter values or change the setpoints as
sides are closed, and that the 3-valve manifold necessary.
See IM 01C25T03-01E (BRAIN
communication) or IM 01C25T01-06EN (HART
(a) Follow the procedures below to introduce communication) for communicator operation.
process pressure into the impulse piping and
transmitter.
that the transmitter is operating properly.
Orifice
1) Open the low pressure and high pressure tap Tap valve
(high pressure)
Tap valve
(low pressure)
Stop valve
5) Close the low pressure stop valve. (low pressure)
3-valve manifold
6) Gradually open the high pressure stop valve. At
Equalizing valve
and high pressure sides of the transmitter.
Stop valve
(high pressure)
impulse piping, 3-valve manifold, transmitter, or
other components. Drain valve
(high pressure)
F0701.ai
detector section.
IM 01C25B01-01E
<7. Operation> 7-2
PARAM
C60:SELF CHECK
ERROR
Vent plug (Fill plug)
communication error
blank.
Properly
Self-diagnostic error on the integral indicator
Using the BT200 (Faulty transmitter) F0704.ai
error’ appears on the display. Other parameters like following are shipped with the
default setting.
ERROR’ appears on the display.
06EN or 01C25T03-01E.
IM 01C25B01-01E
<7. Operation> 7-3
7.2 Zero Point Adjustment The zero-adjustment screw is located inside the
cover.
After completing preparations for operating the Use a slotted screwdriver to turn the zero-
transmitter, adjust the zero point.
Zero point adjustment can be done by turning the turn the screw clockwise to increase the output or
transmitter’s zero-adjustment screw or by using counterclockwise to decrease the output. The zero
the communicator. This section describes the point adjustment can be made with a resolution
procedure for the zero-adjustment screw. For the of 0.01% of the setting range. The degree of zero
communicator procedure, see the communication adjustments varies with the screw turning speed;
manual.
7.2.1 Adjusting Zero Point for Differential to the transmitter is only the head of the seal
Pressure Transmitters
3) Adjust the zero point at this status.
Before adjusting zero point, make sure that the
gradually open the tap valve.
Use a slotted screwdriver to turn the zero-
adjustment screw. Turn the screw clockwise
to increase the output or counterclockwise to
decrease the output. The zero point adjustment can
be made with a resolution of 0.01% of the setting
Zero-adjustment range. Since the degree of the zero adjustment
screw cover
F0705.ai
varies with the screw turning speed, turn the screw
IM 01C25B01-01E
<7. Operation> 7-4
2) Gradually open the low pressure stop valve. 7.4 Shutting Down the
This places the transmitter in an operational
condition. Transmitter
Shut down the transmitter as follows.
NOTE
IM 01C25B01-01E
<7. Operation> 7-5
7.5 Venting or Draining 7.5.2 Venting Gas
Transmitter Pressure- 1) Gradually open the vent screw to vent gas from
the transmitter pressure-detector section. (See
detector Section
Since this transmitter is designed to be self- 2) When the transmitter is completely vented,
draining and self-venting with vertical impulse close the vent screw.
piping connections, neither draining nor venting
gas disturbs the pressure measurement, this should Figure 7.6 Venting the Transmitter
not be done when the loop is in operation.
removed, close the drain screw or drain plug. immediately after performing parameter
setting. Powering off within 30 seconds of
performing this procedure will return the
parameter to its previous setting.
IM 01C25B01-01E
<7. Operation> 7-6
7.6.1 Local Parameter Setting (LPS)
Overview
External adjustment
screw cover
Push-button
F0708.ai F0709.ai
screw
Process
Measurement Zero adjustment
Display push
Activate LPS mode
push
*
1. Tag Number Edit Tag number Save/Cancel the value
*
2. Press Unit Select Press unit Save/Cancel the value
push *
3. Press LRV Edit Press LRV Save/Cancel the value
*
4. Press URV Edit Press URV Save/Cancel the value
push *
5. Damping Time Edit Damping time Save/Cancel the value
*
6. Output Mode Select Output mode Save/Cancel the value
push *
7. Display Out1 Edit Display Out1 Save/Cancel the value
push
9. URV-Apply Press Set URV Save/Cancel the value
Process
Measurement
Display F0710.ai
button.
Tag number, Unit, LRV, URV, Damping,Output
Process
Measurement
Display
push
push
push
push
push
push
push
push
push Process
Measurement
Display
F0711.ai
IM 01C25B01-01E
<7. Operation> 7-8
Save ?/
Cancel ?
Blinking Blinking
Set all other
characters in the
Go to the next Character same way
Change the first Character
screw
push
F0712.ai
Save ?/
Cancel ?
Blinking Blinking
[Available pressure units]
Select by the push button
kPa bar inH2O@4degC(39.2degF)
Torr mbar inH2O@20degC(68degF)
atm g/cm2 inHg
MPa kg/cm2 ftH2O@4degC(39.2degF)
screw hPa Pa ftH2O@20degC(68degF)
push mmHg mmH2O@4degC(39.2degF)
psi mmH2O@20degC(68degF)
In addition to the above units, mmAq@4degC,
mmAq@20degC, mmWG@4degC and mmWG@20degC
are available for BRAIN communication type.
F0713.ai
numerical value.
When the setting is out of the limit, an alarm will be
generated.
IM 01C25B01-01E
<7. Operation> 7-9
7.6.7 Damping Time Constant
Save ?/
Cancel ?
push
F0714.ai
IM 01C25B01-01E
<7. Operation> 7-10
appropriate measure in reference to , “Errors and
Countermeasures” in each communication manual.
Note 3 : Changing the lower range value (LRV) also
automatically changes the upper range value (URV),
keeping the span constant. New URV=previous hold down the button for over 2 seconds and select
URV+(new LRV–previous LRV) “Save” or “Cancel”.
7.6.11 Save or Cancel
At the end of each parameter setting, select “Save”
or “Cancel” by the external adjustment screw
and press the push button to save or cancel the
Tag editing Return to
(3rd Character) parameter review window
2. Press Unit
HART BRAIN
3. Press LRV Up to 8 Up to 16
Tag Number characters can characters can
be set be set
4. Press URV
Hold down the button “TRNS.FC” “OUT.MOD”
Output Mode
for over 2 seconds shown on the shown on the
Jump to the normal mode
6. Output Mode
speed of turning the adjustment screw. Turn the
7. Display Out1
8. LRV-Apply Press
9. URV-Apply Press
Proccess Value
F0717.ai
IM 01C25B01-01E
<8. Maintenance> 8-1
8. Maintenance
8.1 Overview
Use the procedure below to check instrument
WARNING operation and accuracy during periodic
maintenance or troubleshooting.
should be done in a shop that has all the 2) Apply reference pressures of 0%, 50%,
necessary tools. and 100% of the measurement range to the
transmitter. Calculate the errors (differences
that can be damaged by static electricity. between digital voltmeter readings and
Take precautions such as using a grounded reference pressures) as the pressure is
wrist strap when handling electronic parts or increased from 0% to 100% and is decreased
touching the board circuit patterns. Also be
sure to place the removed CPU assembly
into a bag with an antistatic coating.
Selection
Table 8.1 lists the instruments that can be used
to calibrate a transmitter. When selecting an
IM 01C25B01-01E
<8. Maintenance> 8-2
Name
Power supply Model SDBT or SDBS distributor 4 to 20 mA DC signal
Load resistor
F0801.ai
IM 01C25B01-01E
<8. Maintenance> 8-3
8.4.1 Replacing the Integral Indicator
CAUTION
This section describes procedures for disassembly
and reassembly for maintenance and component Cautions for Flameproof Type Transmitters
replacement. Users are prohibited by law from modifying the
Always turn OFF power and shut off and release
pressures before disassembly. Use proper tools for This would invalidate the agency approval for the
use of the transmitter in a rated area.
It follows that the user is prohibited from using
Shrouding Bolt
F0803.ai
Shrouding Bolt F0802.ai Figure 8.3 Removing and Attaching LCD Board
Figure 8.2 Shrouding Bolts
IM 01C25B01-01E
<8. Maintenance> 8-4
NOTE
This subsection describes the procedure for
between the CPU assembly and the capsule. capsule assembly is a critical element in
2) Connect the output terminal cable (with brown
connector). must be checked to verify that it is free of
dents, scratches, and other defects.
NOTE
securely tighten the setscrews that fasten
Make certain that the cables do not get pinched the transmitter section and pressure-detector
between the case and the edge of the CPU section together.
assembly.
IM 01C25B01-01E
<8. Maintenance> 8-5
3) After the pressure-detector section has been
reassembled, a leak test must be performed to
IMPORTANT verify that there are no pressure leaks.
4) Reattach the transmitter section to the
Exercise care as follows when cleaning the pressure-detector section.
capsule assembly. Reattach the stopper with the hexagon-head
screw.
be especially careful not to damage or distort 5) Tighten the two setscrews. (Tighten the screws
the diaphragms that contact the process
6) Install the CPU assembly according to
subsection 8.4.2.
cleaning. 7) After completing reassembly, adjust the zero
point and recheck the parameters.
cleaning.
Transmitter section
1) Remove the CPU assembly as shown in
subsection 8.4.2.
2) Remove the two setscrews that connect the
transmitter section and pressure-detector
section.
Setscrew
3) Remove the hexagon-head screw and the
stopper.
4) Separate the transmitter section and pressure- Nut
detector section.
Capsule gasket
6) While supporting the capsule assembly with
Flange bolt
Pressure-detector section
bolts, paying close attention to the relative Cover flange
F0804.ai
positions of the H (high pressure side) and
Figure 8.4 Removing and Mounting the Pressure-
L (low pressure side) marks on the capsule detector Section
assembly.
Replace the two capsule gaskets with new
gaskets. IMPORTANT
If you remove the vent/drain plugs when
disassembling EJ 130 and EJ 440
transmitters, install the plugs again before
EJ 110 , EJ 310 , EJ 430
Model Wetted parts material code EJ 120 assmbly.
S H,M,T,A,D,B
17* 40 40
EJ 130 EJ 440
Model Bolts & nuts material code
G, C J G, C J
90 110 70 100
IM 01C25B01-01E
<8. Maintenance> 8-6
8.4.4 Replacing the Process Connector
First determine whether the process variable
This subsection describes process connector is actually abnormal or a problem exists in the
measurement system.
(a) Loosen the two bolts, and remove the process If the problem is in the measurement system,
connectors. isolate the problem and decide what corrective
(b) Replace the process connector gaskets. action to take.
(c) Remount the process connectors. Tighten the
function which will be useful in troubleshooting,
below, and verify that there are no pressure
leaks.
indicator will show an alarm code as a result of self-
EJ 110 EJ 440 diagnosis.
EJ 120 See subsection 8.5.3 for the list of alarms.
Model EJ 130
EJ 310 C capsule D capsule See also each communication manual.
EJ 430
: Areas where self-diagnostic offers support
39 to 49 49 to 59
Abnormalities appear in measurement.
Bolt
Isolate problem in
measurement system.
F0805.ai
YES Does problem exist in
Figure 8.5 Removing and Mounting the Process receiving instrument?
Connector
NO
Inspect receiver.
If any abnormality appears in the measured values, Environmental conditions Transmitter itself
IM 01C25B01-01E
<8. Maintenance> 8-7
Is power supply
polarity correct?
Are valves opened or NO
closed correctly?
YES Refer to Section 6.3 to check/correct
polarity at each terminal from power
supply to the terminal box. YES Fully close equalizing valve, and fully
open high pressure and low pressure
valves.
Are power
supply voltage and load
resistance correct?
YES
Is there any pressure leak?
YES Refer to Section 6.6 for rated voltage
and load resistance.
NO
Fix pressure leaks, paying particular
attention to connections for impulse
piping, pressure-detector section, etc.
Is there
continuity through the Contact Yokogawa service personnel.
transmitter loop wiring? F0808.ai
Do the loop numbers
match?
IM 01C25B01-01E
<8. Maintenance> 8-8
Is impulse piping NO
connected correctly?
Is transmitter
installed where there is YES
marked variation in
temperature?
Were appropriate NO
instruments used for
calibration?
NO
Is output adjusted correctly?
IM 01C25B01-01E
<8. Maintenance> 8-9
8.5.3 Alarms and Countermeasures
Output Operation
Indicator Cause Countermeasure
during Error
None
AL. 01 Sensor problem. Outputs the signal (Hold, High, or Replace capsule when error
CAP. ERR Capsule temperature sensor Low) set with parameter. keeps appearing even after
problem. restart.
Capsule EEPROM problem.
AL. 02 Outputs the signal (Hold, High, or
AMP. ERR problem. Low) set with parameter.
AL. 10 Input is outside measurement Outputs high range limit value or Check input or replace capsule
PRESS range limit of capsule. low range limit value. when necessary.
AL. 11 Static pressure exceeds limit. Continues to operate and output.
ST. PRSS
AL. 12 Capsule temperature is outside Use heat insulation or make
CAP. TMP range (–50 to 130°C). lagging to keep temperature
AL. 13 within range.
AMP. TMP range (–50 to 95°C)
AL. 30 Output is outside upper or lower Outputs high range limit value or Check input and range setting,
RANGE range limit value. low range limit value. and change them as needed.
AL. 31 Continues to operate and
SP. RNG range. output.
AL. 35 *1 Check input.
P. HI threshold.
AL. 36 *1
P. LO
AL. 37 *1 Input static pressure exceeds
SP. HI
AL. 38 *1
SP. LO
AL. 39 *1 Detected temperature exceeds
TMP. HI
AL. 40 *1
TMP. LO
AL. 50 Holds output immediately before Check setting and change them
P. LRV range. error occurred. as needed.
AL. 51
P. URV
AL. 52
P. SPN
AL. 53 Continues to operate and output. Check input.
P. ADJ
AL. 54 Continues to operate and output Check setting and change them
SP. RNG holding static pressure in %. as needed.
AL. 55 Continues to operate and output. Check input.
SP. ADJ
AL. 60 Check setting and change
SC. CFG them as needed.
do not satisfy the condition.
AL. 79 Displayed value exceeds limit.
OV. DISP
*1: These alarms may appear only when process alarm function is activated.
IM 01C25B01-01E
CLEANING BALLS
Cleaning Balls are used for preventing formation of deposits and scales inside the Condenser tubes.
The composition of balls is based on a natural rubber mixture containing fillers and chemicals.
APPLICATIONS
RB Cleaning Balls are used for Stainless Steel and Titanium Tubes to remove biofouled layers. Though
the titanium and high-performance stainless steels are having excellent corrosion resistance, they are
more susceptible to biofouled layers than copper-base alloys. In copper-base alloys, toxic effect of
copper-ions hampers the formation of biofouled layers. Generally, RB Scouring balls with 10 to 12
balls passes per tube per hour are recommended for continuous cleaning.
BRIEF DESCRIPTION
The bio fouled layers are soft in nature and readily removed by normal sponge balls. However, in Sea
Water applications, a gradual build-up of inorganic layer, resistant to normal sponge balls can occur.
It can be identified in any one of the following indications :
In such case, a basic charge of ring coated with fine granulated balls (Type RG) may be circulated for
removing the inorganic layers because RG Balls are having more aggressive scouring effect. RG Balls
are effective only till the coating is prevailed but uncoated balls are effective as long as they are in
oversize. Extensive depreciation of Ring Coating of RG Balls after 30 minutes of operation with one
basic charge is the indication of rough surface or fouling of the condenser tubes. In such case, one or
more basic charge can be circulated. One basic charge of RG Balls is recommended at least once a
year for this project. However, the frequency may be increased depends upon any one of the above
indications is likely to appear. Usage of RG Balls can be stopped immediately once the system is free
from the above indications.
The choice of optimum ball hardness is dictated by the need to be able to collect the balls on screens,
recirculate them and good ball life (the soft balls with the optimum permitted oversize for a given
pressure drop are longer life).
From a practical point of view, ball hardness does not affect the cleaning properties of the ball.
DES/OMM/CB Sheet 1
LIFE
Ball life strongly depends on Water Quality, Cleaning frequency and surface condition of the condenser
tubes. Scaled and corroded surfaces are having a detrimental effect on ball life.
STORAGE
Storage temperature is to be maintained at 24 ± 3 ºC. Store the cleaning balls in packed cartons to
prevent deformation. Do not store the cleaning balls near the ozone releasing equipment. Do not stack
more than two cartons in a row. Use cleaning balls on first in first out basis. If the balls are removed
from the carton, they should be stored loosely. Cleaning balls should be stored in a place free from oil
and grease. Used but effective balls should always be kept in the water.
For every fresh charge of cleaning balls in the Ball Collector, squeezing in water is mandatory to
release the air to avoid floating of balls on top of the condenser and uniform ball circulation.
BALL OVERSIZE
Ball oversize is the difference between the actual ball diameter and the internal diameter of the tube.
Basically, a cleaning ball has to be larger than the internal diameter of the tube to be cleaned. The
cleaning ball gets squeezed when it enters the tube, thereby pressing itself against the surface of the
tube. The pressure drop between the inlet and outlet ends of the tube transport the ball through the
tube. Cleaning is only fully effective so long as the ball is oversize.
ORDERING
When ordering Cleaning Balls, please specify ball type (e.g. Type RB), nominal ball diameter in mm
and grade of hardness. Refer Catalogue Section for more details.
DES/OMM/CB Sheet 2
CLEANING BALLS
www.website.com
Schmitz Cleaning Balls
Schmitz (An Affiliate Company of GEA BGR) cleaning balls plays a crucial
role in maintaining the condenser and Heat Exchanger Tubes clean and
free from Fouling & Scaling.
Schmitz Cleaning balls are manufactured with high-quality standards CLEANING BALLS
and are eco-friendly in nature. The Cleaning balls we provide are proven
and accepted by several reputed customers across the world.
Soft Deposits
In all cooling water applications, fouled layers, such as slime, mud or silt,
from on the inner surfaces of condenser tubes even at velocities of
2m/s.These deposits are typically soft and easily removed by SCHMITZ
Cleaning Balls without an abrasive layer.
SCHMITZ recommend Type RS open pore structure sponge ball for
continuous cleaning with 8 to 12 ball passes per tube per hour.
Hard Deposits
In cooling towers and other open evaporative cooling water systems the
water becomes highly concentrated with certain chemicals. The solubility
limit is thereby exceeeded and hard crystalline deposits, such as calcium
carbonate, form on the tube surface.
SCHMITZ ring coated Abrasive Balls Type RA are first used to clean the
fouled tubes,typically for a period of a few weeks. Continuous cleaning
with Schmitz Balls without an abrasive layer then hinders growth of
nuclei. In very hard waters, regualr use of abrasive ball is recommended,
i.e. 1 or more ball charges every 1 to 3 months.
Lower
Sinking
Velocity
RS 15 RSL 10 RT 35
RA 15 RAT 15 RTAT 35
Removal of Hard Scales Ca Co, Removal of Soft Scales Removal of Soft Scales Mg (OH)2
Copper and Brass Tubes Mg (OH)2 Fe SO4 Cupronickel & SS Tubes
Welded Copper and Brass Tubes
Lower
Sinking
Velocity
RB 20 RG 20 RTL 30
RB Scouring balls for removal of RG Scouring balls for removal of Removal of Soft Deposits
Biofoulded layers Aderent Biofoulded layers Cupronickel & SS Tubes
Stainless Steel, Titanium Tubes Stainless Steel, Titanium Tubes
RBR 20 RSR 15
(LONG LIFE) (LONG LIFE) RTA 35
Removal of Soft Deposits Removal of Soft Deposits Removal of Hard Scales Ca Co,
Stainless Steel, Titanium Tubes Copper & Brass Tubes Cupronickel & SS Tubes
Nominal Dia : Ball size from 8 - 51 mm dia in 1 mm steps. For Ring Coated Balls Coating of 1- 2 mm will be additional to nominal dia
20 - Blue - 0
SS Tubes
Storage
Ball Distribution
It is important that cleaning balls be stored in a cool, dry
place,away from direct sunlight. Do not stack more than 2 Distribution of balls in the condenser / heat exchanger is
boxes and the balls are to be used in First in First out basis. influenced by factors such as ball injection in c.w. inlet, the
With proper storage, the shelf life of cleaning balls can be c.w. flow conditions in the waterbox Schmitz cleaning balls
two years from manufacturing. are chosen also for optimising the ball distribution by
mixing ball types of different sinking velocities.
Ball Life
Advisory Service
Ball life is strongly dependent on the cleaning frequency
and the surface condition of the tubes to be cleaned. It is Our Specialists will gladly answer your queries regarding the
typically about 4 weeks, but can be much longer selection and use of schmitz clenaing balls. Contact us
depending on local conditions and frequency of cleaning. directly or via your local agent.
Scaled and corroded surface have a particularly detrimental
effect on ball life. The use of other types of balls e.g., abrasive
balls, to polish roughened surfaces should be considered in
case of excessive ball wear.
CONTENTS
1 PURPOSE ................................................................................................................................................. 3
2 DESIGN ................................................................................................................................................... 3
3 PARTS & FUNCTIONS ........................................................................................................................ 3
4 PRINCIPLE OF OPERATION ............................................................................................................. 4
5 INSTALLATION .................................................................................................................................... 4
6 PRE-COMMISSIONING CONDITIONS ......................................................................................... 5
7 PRE-REQUEST........................................................................................................................................ 5
8 START-UP ............................................................................................................................................... 5
9 CALIBRATION ...................................................................................................................................... 6
9.1 SETTINGS ...................................................................................................................................................... 6
10 OPERATION ....................................................................................................................................... 7
11 BRM MEASURING COUNTER...................................................................................................... 8
11.1 SALIENT FEATURES ................................................................................................................................... 8
11.2 DIP SWITCH SETTING ............................................................................................................................... 9
12 PHOTO ELECTRIC SENSOR ........................................................................................................ 10
12.1 SALIENT FEATURES ................................................................................................................................. 10
12.2 SENSOR PARTS & FUNCTIONS ............................................................................................................ 11
12.3 GUIDE LINES FOR SENSOR ALIGNMENT ........................................................................................ 11
12.4 GUIDELINE FOR SENSITIVITY ADJUSTMENT PROCEDURE ..................................................... 12
13 SAFETY AND GENERAL NOTES................................................................................................ 13
13.1 SENSORS ...................................................................................................................................................... 13
13.2 BRM FIELD UNIT ....................................................................................................................................... 13
13.3 MEASURING COUNTER ......................................................................................................................... 13
14 STORAGE .......................................................................................................................................... 14
15 PREVENTIVE MAINTENANCE SCHEDULE ........................................................................... 14
16 SHUTDOWN PROCEDURES ....................................................................................................... 14
17 TROUBLESHOOTING ................................................................................................................... 15
18 SPARE PARTS .................................................................................................................................. 16
19 BRM GENERAL ARRANGEMENT ............................................................................................. 17
20 BRM – 2K WIRING DIAGRAM ................................................................................................... 18
DES/OMM/BRM Sheet 2
OPERATION & MAINTENANCE MANUAL
FOR BALL RECIRCULATING MONITOR
1 PURPOSE
The GEA-BGR Condenser On Load Tube Cleaning System (COLTCS) maintains the condenser tube
cleanliness and constant heat transfer & corrosion-free operation by engaging sufficient number of
oversize sponge cleaning balls in the system.
GEA-BGR ball recirculating monitor (BRM2K) is stand-alone in operation and a user friendly
instrument. This continuously monitors the sufficient number of cleaning balls in circulation in the
condenser. BRM initiates an alarm when the number of circulating balls falls below the set value
while the preset measuring time elapses.
2 DESIGN
BRM comprises a compact non-metallic field assembly unit with internal configuration
corresponding to the nominal diameter of the ball transport pipe.
Ball counting is made free from any mechanical contact with use of light barrier sensor. These
sensors are mounted diametrically opposite in the housing. BRM is an easy and maintenance-free
instrument as no moving parts are involved.
Ball monitor counter is mounted on the control panel mimic facial for easy operation, which
receives the signals from the field sensor unit and displays the status.
The sensor emits strong infrared light beam from its light-emitting transmitter, which is received at
the receiver end. Thrubeam type photo sensor is used to measure the change in light quantity caused
by the ball crossing the optical axis.
The photoelectric sensor employs the pulse light emission method, which ensures stable operation
even in strong external light and measures in extremely turbid cooling water flow.
Objects, which are bigger than Dia 10mm are identified as a cleaning object.
DES/OMM/BRM Sheet 3
OPERATION & MAINTENANCE MANUAL
FOR BALL RECIRCULATING MONITOR
Salient feature of BRM2K is capable of handling both Sponge and Abrasive Balls without affecting
the Sensor Assembly, which is protected by toughened glasses. Hence, the sensor need not be
removed while Abrasive balls are in use.
4 PRINCIPLE OF OPERATION
After sponge cleaning balls are circulated in the condenser tubes, balls are retrieved from the main
cooling water outlet stream through Ball Strainer. And this will be recirculated in the ball transport
line using Ball recirculation Pump. Ball recirculating monitor is fixed in the ball transport pipe line.
The balls will be passing through Ball recirculation monitor.
As the sensor is mounted at the middle of housing, all the balls passing through BRM will not be
counted. The balls which interrupts the sensor only will be counted. As the BRM is working on
statistical analysis principle, this sample counting is adequate for satisfactory results.
During commissioning stage GEA BGR engineer will establish the set value by counting the number
of cleaning balls passing the sensor for a duration of 10 minutes. And the set value will be arrived
by various trials and averaging the counts. And this value will be set in the Ball Counter which is
mounted in the control panel.
Ball recirculation Monitor is designed such that whenever the operator switches ‘ON’ the BRM
sensor will ON and continue to count the balls for the duration of 10 minutes and comes to OFF
condition after 10 minutes automatically.
At any point of time during the ball circulation, if the operator wants to ensure the availability of
sufficient quantity of balls in the system, he has to switch ON the BRM MANUALLY. Now BRM
continues to count the balls for the duration of 10 minutes and comes to OFF condition. If the actual
count in the Ball counter meets the set value, it is considered that there is sufficient quantity of
cleaning balls in the system. If it is not met there will be alarm which indicates there is no sufficient
number of balls in the system. Then operator has to intervene and find the root cause for less number
of balls and to replenish with good balls.
5 INSTALLATION
Installation Instructions
General Precautions
Avoid the contact of ferrite material or tools with stainless steel to prevent corrosion
Lubricate the O-rings with silicon-based grease
Apply thin layer of grease/molly coat to all external bolts and nuts before assembly
Apply Loctite 2701 to all the internal bolts and nuts for assembly
Strictly observe required tightening torque of different bolts/nuts
DES/OMM/BRM Sheet 4
OPERATION & MAINTENANCE MANUAL
FOR BALL RECIRCULATING MONITOR
Mechanical
Generally, BRM will be a part of the Ball Recirculating Skid. Otherwise, BRM field unit to be
installed as per installation drawing.
BRM field unit is normally installed before Ball Vessel.
BRM field unit counter flanges to be uniformly tightened crosswise to avoid leak and damage.
Electrical
6 PRE-COMMISSIONING CONDITIONS
7 PRE-REQUEST
Check the Isolation Valves in open position
Check the System watered and vented
Check the Control Panel is energized
Check the screen in operating position
Check measuring time in HMI as 10 mins
Check for basic charge fill-in
8 START-UP
DES/OMM/BRM Sheet 5
OPERATION & MAINTENANCE MANUAL
FOR BALL RECIRCULATING MONITOR
Balls are injected into the system as the ball vessel outlet valve is fully opened
Start BRM manually after 10 minutes of interval to ensure good ball distribution on the tube
sheets and uniform ball circulation in the system.
9 CALIBRATION
BRM has to be calibrated during initial start-up. Further calibration can be made whenever the new
operating condition changes.
9.1 SETTINGS
Fill the ball vessel with required basic charge of cleaning balls.
Put the system in AUTO ON condition.
Wait for 30 minutes to have the uniform ball circulation in the condenser.
Switch ON the BRM. Now, the counter will start counting the cleaning balls.
BRM will come to OFF condition automatically after 10 minutes (BRM is preprogrammed to
switch off after 10 minutes of operation).
Note down the counter reading and enter in the table.
Repeat this exercise ten times and enter the counter readings.
Arrive the average of 10 readings.
Set the counter value to 80% of the average value arrived by calibration.
DES/OMM/BRM Sheet 6
OPERATION & MAINTENANCE MANUAL
FOR BALL RECIRCULATING MONITOR
10 OPERATION
After setting the counter value, BRM can be operated during Normal Operation. Whenever we want
to count the number of balls following sequences has to be followed.
a) Press the BRM ON push button in the Mimic on the panel manually during Normal
operation of the system. BRM on indication will be illuminated in the panel.
b) Previous set value in the counter will be rested on by pressing the BRM ON pushbutton.
c) BRM Counting timer will be started (Adjustable internal PLC timer – 10 Minutes).
d) BRM Counter will start receiving the count input from the field sensor and counting of balls
started which can be viewed on the BRM counter.
e) After the elapse of counting time, BRM ON indication will go off and BRM OFF indication
will be ON.
f) Counting of balls will be stopped since 12-24V DC supply to sensor is stopped.
g) During 10 Minutes of operation, if healthy feedback is received from counter (i.e., the set
value in the counter is met), the system is considered to be operating with sufficient number
of balls.
h) During 10 Minutes of operation, if healthy feedback is not received from counter (i.e., the set
value in counter is not met), the system is considered to be operating with insufficient
number of balls. Then, BRM fail indication will glow. Operator has to press reset pushbutton
in the panel to switch off the BRM fail indication. The operator has to stop the system to
replenish the required no. of balls and start the system again.
Note : The BRM can be operated and monitored only from BRM Local Panel.
DES/OMM/BRM Sheet 7
OPERATION & MAINTENANCE MANUAL
FOR BALL RECIRCULATING MONITOR
Bright backlight negative LCD display enables higher visibility under both dark & bright lighting
conditions.
Programmable PV color indication change in output status are visually indicated by switching
the PV display color from red to green or vice versa, enable to check the output status from a
distance.
Ergonomic up-down rocker keys enable to change setting values. (6-digits) & DIP switch.
NPN switchable input.
Six – language programme instruction.
Weather protection IP66 / NEMA4 for front panel.
DES/OMM/BRM Sheet 8
OPERATION & MAINTENANCE MANUAL
FOR BALL RECIRCULATING MONITOR
Setting Functions can be either in DIP switch mode or internal function settings. If the internal
function setting is opted, the DIP Switch Pin 1 should be in disabled (OFF) mode. It is
generally recommended to perform the settings with the operation keys.
DES/OMM/BRM Sheet 9
OPERATION & MAINTENANCE MANUAL
FOR BALL RECIRCULATING MONITOR
How to Mount
1. Insert the controller through the panel cutout.
2. Insert the mounting bracket into the mounting groove at the top and bottom of the controller
and push the mounting bracket forward until the bracket stops at panel wall.
3. Insert and tighten screws on bracket to secure the controller in place.
Parameters Setting
A photoelectric sensor emits a light beam either visible or infrared from its light-emitting
transmitter. These photoelectric sensors employ the pulse light beam emission method with use of
infra red LED. Thrubeam type is used to measure the change in light quantity caused by the ball
crossing the optical axis.
Compact in size
Long-detecting distance
Stable detecting position
Powerful beam
Opaque objects detectable regardless of shape, color or material.
DES/OMM/BRM Sheet 10
OPERATION & MAINTENANCE MANUAL
FOR BALL RECIRCULATING MONITOR
Caution ! Do not hit the Sensor with hard materials such as hammer.
This may downgrade the degree of protection.
The sensors are waterproof (IP 67). However this does not mean the
detection is possible under water or in rain.
The photoelectric sensors employ the pulse light emission method, which ensures stable operation
even when external light is strong and also harsh environment. The sensor emits infrared light beam
from its light-emitting transmitter, through beam type photo sensor is used to measure the change
in light quantity cause by the target crossing the optical axis.
Set the operation mode switch to the Light-ON mode position (L side).
Placing the emitter and the receiver face to face along a straight line. Move the emitter up, down,
left and right to determine where light is received with the help of the receiver’s operation
indicator (orange). Set the emitter in the middle of this area.
Adjust the angle of the emitter by twisting it up, down, left and right.
In a similar manner, adjust the angle of the receiver.
Check that the stability indicator (green) lights up.
Choose the desired operation mode, Light-ON or Dark-ON, with the operation mode switch.
DES/OMM/BRM Sheet 11
OPERATION & MAINTENANCE MANUAL
FOR BALL RECIRCULATING MONITOR
This procedure assumes that “Light-ON” is set for the operation mode.
If “Dark-ON” is the operation mode, the output will behave the other way around!
Sensitivity
Step Description
adjuster
In the “dark” condition, turn the sensitivity adjuster clockwise until the
sensor output turns ON.*1
3 Turn it back slowly to confirm point B, where the sensor output just turns
OFF.*1 If the sensor output does not turn ON even when the sensitivity
adjuster is turned fully clockwise, point B is the position at MAX.
DES/OMM/BRM Sheet 12
OPERATION & MAINTENANCE MANUAL
FOR BALL RECIRCULATING MONITOR
Caution : Do not turn the receiver sensitivity adjuster beyond the specified range (0-
240º). If may so it cause mal function in sensitive adjustment. Do not use
metallic screwdrivers for adjusting the trimmer. Use only plastic
screwdrivers.
13.1 SENSORS
Handle the sensor carefully when mounting. Strong impact to the sensor head may damage the
sensor’s waterproof capability.
The sensors enclosure are weatherproof, this does not mean the detection is possible under water
or in moist condition.
Do not use voltage in excess of the operation voltage range (24V DC). It may result in internal
elements fail or burn of the sensors.
Isolate the sensor wiring from power lines and high voltage lines; otherwise, the sensor may
malfunction due to noise interference.
Use the attached mounting bracket to install and fix the sensor.
Mount the sensor and fasten the screws at a tightening torque of 0.5nm (Max.)
To ensure safety, be sure to observe the following :
Avoid installing the BRM field unit in locations where there is a possibility of direct contact
with water, oil, corrosive gas or chemical splash
Avoid exposure to strong magnetic or electric fields
Avoid location with high humidity and a possibility of condensation
Avoid location subject to vibration or shock
DES/OMM/BRM Sheet 13
OPERATION & MAINTENANCE MANUAL
FOR BALL RECIRCULATING MONITOR
Caution ! Be sure to turn OFF the BRM power before replacing any component.
It is recommended to take substantial safety measures to avoid any damage
in the event a problem occurs.
14 STORAGE
FREQUENCY PERSONS
S.NO. COMPONENTS INSPECTION
OF CHECK RESPONSIBLE
Check LCD Visible Display and
Weekly Electrician
confirm the correct set value
01 Counter Overall visual inspection Weekly Electrician
Check counter cable connection
Yearly Electrician
& TB
Overall visual inspection Weekly Electrician
Housing external damage, sign
Yearly Mechanic
of corrosion
Check wear and Tear of Inlet,
outlet spool piece ‘O’ Rings, bolt
Yearly Mechanic
BRM Field sensor & nut check and replace if
02
assembly unit require.
Inspect general condition of
Yearly Mechanic
polymer block & fasteners.
16 SHUTDOWN PROCEDURES
DES/OMM/BRM Sheet 14
OPERATION & MAINTENANCE MANUAL
FOR BALL RECIRCULATING MONITOR
17 TROUBLESHOOTING
DES/OMM/BRM Sheet 15
OPERATION & MAINTENANCE MANUAL
FOR BALL RECIRCULATING MONITOR
18 SPARE PARTS
Quantity
S. No. Description
per BRM
1 Sensor 1 Set
DES/OMM/BRM Sheet 16
OPERATION & MAINTENANCE MANUAL
FOR BALL RECIRCULATING MONITOR
DES/OMM/BRM Sheet 17
OPERATION & MAINTENANCE MANUAL
FOR BALL RECIRCULATING MONITOR
DES/OMM/BRM XXI
DES/OMM/BRM Sheet 18