DS8870 Code Load Instructions v4.71

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

IBM DS8870

242X Model 961

CDA Microcode Update Instructions

87.0.x.x – 87.51.x.x

Transformation
• HMC Rebuild to upgrade the base Operating System
Preload
• Acquire code from source (media or network), distribute to components (staging for use later)

HMC Update / SFI Activate


• This step is to be completed in one day
• Please expect communication errors from monitoring or diagnostic tools until the CCL completes

After the CDA Preload is started the following steps will be performed automatically:
- Acquire of the release bundle
- Prepare the HMC with any code update specific fixes
- Distribute the code updates to the LPAR and install them to an alternate BOS
- Perform scheduled CDA Preverify scans until the distributed code is ready to be activated by the user for up to 11 days.
Media list for use with these instructions
Required Media for HMC Rebuild (87.5x.x.x Base) – Appendix C

ICS UPG_R7.5-MCP8.1-SAVE-UPGRADE-DATA_v1.1.iso

ICS PFE_Console_Hard_Drive_Test_v1.1.iso

Recovery Set Disk 1 APO9_1411A_0314_0218.1.Recovery.iso

Recovery Set Disk 2 mmhmc-b25.75.0-20150211.1.iso

Recovery Set Disk 3 DS8000StorageManager_HMC_5.7.50.1195.iso

v4.71 – Page 1
Media for Standard Code Load

ICS CSE_CallHomeCertificates_v1.0

ICS CVE_1Q2020_v1.x - Customer permission required. Install at 87.52.xx.xx and higher


Security Bulletin:
https://www.ibm.com/support/pages/node/3517185?myns=s028&mynp=OCST8NCA&mynp=OCST5GL
J&mync=E&cm_sp=s028-_-OCST8NCA-OCST5GLJ-_-E

You may experience a timeout issue where the ICS takes over 8 minutes to install. If encountered,
disconnect (do not log out) from the GUI and log back in and you should see the install completed.
ICS CVE_1Q2019_v1.2 - Install at bundles up to 87.52.28.0, unless customer requests CVE_1Q2020
Security Bulletin: https://www.ibm.com/support/pages/node/882400
ICS PFE_FixAOS_Consolidated – install the latest version

ICS CSE_FixAosPerms

ICS CSE_PatchJavaLink_v1.x

Power Code Power Firmware should be installed on any machines running a code level below the following:
Use Power Firmware Update instructions in Tip 01350
ICS DS8k DDM SSD FW Update – use the latest version on Fix Central

v4.71 – Page 2
Informational Notices
Please see Customer Information Document in TIP 01350

v4.71 – Page 3
Prerequisites to start a Code Load

What is the current code and the target code level?

Step 1 – Appendix Appendix


HMC Current Level Target Level
Preload B C

87.x.x.x – 87.50.70.0 87.51.x.x Start Here

87.50.71.0 or higher 87.51.x.x Start Here

Is the HMC hostname valid?


Host Name Rules
● “localhost” is not valid
● The first character must be an alpha character
● The last character must not be a minus sign
● Single character names are not allowed
Does this HMC manage only one Storage facility?
1X2 or 2x2 multiple Storage Facility configurations are NOT supported with Preload installation method. Please use the
non-preload instructions for all other configurations.

v4.71 – Page 4
STEP A - Before starting Preload – Check HMC hard drive is good – ICS Image

Note: If you just came from APP C, no need to install this one again – Continue to STEP 1

Install PFE_Console_Hard_Drive_Test_v1.1 ICS Disk:

ICS Disk Installation


Select: HMC Management
Select: Install Corrective services
Insert ICS Disk into HMC DVD drive.
Select: Next to confirm Current HMC Driver Information
Select: Removable Media and Next
Select: CD-ROM or DVD and Next
Select: Media Image and Next (no image description is standard)
Select: Finish to confirm -- Install Corrective Service install will take less than 15 minutes ---
The CD will run and display results of the process
Click OK then No (Reboot HMC not required)
Repeat on HMCB, if applicable
Continue to Step 1

STEP 1 Starting CDA Preload


If you were directed to STEP 1 from Appendix B, please understand you are starting Preload. Appendix B was standard
Acquire only to the HMC.

There are two ways to begin a Preload.

Media Acquire:

Insert the release bundle DVD into the primary HMC1 drive. You do not need to be logged in, but you can be.

The HMC will automatically begin acquiring the release bundle from the DVD. The welcome screen will state that the
HMC is “Importing media”. If a user is logged in, a progress panel will automatically pop up. After the acquire is complete,
the welcome screen and progress window will be updated to let the user know the acquire is complete and media can be
ejected. Preload will automatically continue with code distribution. ~ 45 minutes
Media should be removed from HMC drive.

For machines with Dual HMC, the bundle DVD removed from HMC1 should NOT be inserted into the HMC2 drive. The
bundle will automatically be acquired from HMC1 via internal network.
When complete the welcome screen and progress window will be updated to let the user know the acquire is complete.
No other actions will be automatically performed on HMC2.

Network Acquire:

Log in to HMC1
Select: Updates
Select: Radio button on the HMC line
Select: Acquire Code Images

a) CDA4TP (Please follow CDA4TP acquire instructions – located on the Tips db or Wiki)

A progress panel will automatically pop up stating that acquire is complete. Preload distribute will automatically continue
from HMC1.

For Dual HMC, acquire code bundle from network on HMC2. Code will only acquire on HMC2

v4.71 – Page 5
STEP 2 Automatic Distribution

NOTE: Do not run CDA Preverify manually, the code load process will execute it automatically.

CDA will continue to run regular CDA Preverify checks in the background and open serviceable events for any issues
found. Anytime the user logs in during this time frame, the preload activation panel will come up which also shows the
last CDA Preverify scan time. If the user chooses to cancel the automatically opened panel, it will not be shown again
until the next login.

After the distribute completes, the user will have 11 days to activate the preloaded code. During this time the machine
can be used normally, including making logical configuration changes and repairing any issues.

Note: If cancel is selected, the preload status panel will be closed. To return to this panel go to the Updates menu, select
the Storage Facility from the target list and choose the “Display Preload Status” utility.

When the code distribution is complete, SRC BEFCDA01 will be created and called home.

STEP 3 HMC Code Activation


Note: If there are no HMC updates, the automated process will go directly to STEP 4, Storage Facility update.

Check on both HMCs if AOS is running:

Select: HMC Management


Select: Manage AOS

If Status is running, the AOS service needs to be restarted after the HMC Code Activation

Log in to the HMC and remove any Microcode media from the drive.
If already logged in and the preload status panel has been closed, go to the
Updates menu, select the Storage Facility from the target list, choose the “Display Preload Status” utility

Bundle 87.xx.xxx.x has been successfully preloaded on SFI xxxx-961*xxxxxxx.


However, before this preload can be activated, an HMC update to this bundle is
required. Do you want to update the HMC to this level now?
* xxxx-961*xxxxxxx passed CDA Preverify less than an hour ago

Yes | No

Do NOT continue if the Preload has EXPIRED – you MUST restart the Preload (STEP 1) and then continue.

Do not continue until passed CDA Preverify is displayed.


CDA Preverify must automatically run one time successfully before selecting Yes.

- If a window is shown with a list of serviceable events, open the serviceable event management task and repair each of
the issues.

If all conditions above are met, and you are ready to Start the HMC update:
Select: Yes, to start the HMC update

Proceeding with update will take the HMC offline. Do you want to continue?

Yes | No

Select: Yes to take the HMC offline

v4.71 – Page 6
Continued on next page...

The update of HMC1 will continue...... ~20 minutes


Update successful. Press OK to complete the update and reboot.

OK

Select: OK to reboot ~13 minutes

**If the HMC hangs at initialize screen for more that 5 minutes, reboot again by selecting the Alt Ctrl and F1 keys, then
Alt Ctrl Del keys. Use Alt and Ctrl keys on the left side of keyboard.

Start AOS service if it was running prior the HMC Code Activation.

If this is a single HMC configuration continue to the section: Storage Facility code activation

For Dual HMC configurations:

Update HMC2 from HMC1


Log into HMC1 after the reboot and receive message that HMC2 needs to be updated.
Select: Yes (this will update the secondary HMC from the primary)
Follow the on-screen prompts to complete the update of HMC2

Start AOS service if it was running prior the HMC Code Activation.

Continue with the next section: Storage Facility code activation

Step 4 Storage Facility code activation


NOTE: Do not run EOC or CDAPreverify until SFI activation complete

Log in to HMC1 - The following screen will display:


Please stop and follow Step 4a before continuing

Bundle 87.xx.xxx.x has been successfully preloaded on SFI xxxx-961*xxxxxxx


Do you want to activate this code now? (Note: Activation expires in x days.)
xxxx-961*xxxxxxx passed CDA Preverify ...............................

By continuing with the activation, you acknowledge that the system is within
the scheduled maintenance window and the customer is prepared for the code
load.

OK | Cancel | Help

Continued on next page...

v4.71 – Page 7
Step 4a Code Check Point
Option 1. If your current “come from” level of code is 87.10.x.x or higher, place a check in the box
Select: OK
Continue to Step 5
Option 2. If your current “come from” level of code is 87.05.x.x or lower
Select: Cancel

Install ICS Disk ICS_disableETmigration using Install Corrective Service CD

Note: The installation of these ICS disks (ICS disableETmigration_v1.x -or- ICS_enableETmigration_v1.x) will cause a
single Warmstart to occur in order to complete the installation.

After the ICS installation completes, please continue...

Select: Updates
Select: The radio button on the Storage Facility line
Select the Storage Facility radio button and choose “Display Preload Status”.
The following panel will be displayed:

Bundle 87.xx.xxx.x has been successfully preloaded on SFI xxxx-961*xxxxxxx


Do you want to activate this code now? (Note: Activation expires in x days. )
xxxx-961*xxxxxxx passed CDA Preverify ...............................

By continuing with the activation, you acknowledge that the system is within
the scheduled maintenance window and the customer is prepared for the code
load.

OK | Cancel | Help

*If all conditions are met, place a check in the box


Select: OK

Note: If Cancel is selected the preload status panel will be closed. To return to this panel go to Updates,
select the Storage Facility radio button and choose “Display Preload Status”.

Note: To restart CCL to an LPAR after a suspend where you are in Dual Cluster Mode and repair was completed to
resolve the reason for the suspend, do the following:
Updates → SFI radio button → Update Storage Facility Code and select: Resume the CCL

v4.71 – Page 8
STEP 5 Run Final Checks

Reset Advanced Configurations to Default


Select: Updates
Select: The radio button on the Storage Facility line
Expand: Recovery Utilities
Select: Advanced Configuration
Select: Reset to default

Reset No-rsStart
Expand: Storage Facility Management and below
Select: SF Image (from left panel)
Select: LPAR radio button (from right panel)
Expand: Service Utilities
Select: Reset No-rsStart
Repeat this step for all LPARs
This is just a precaution to ensure no remaining norsStart files exist

Run end of call


Select: Storage Facility Management
Select: The radio button on the Storage Facility line.
Expand: Service Utilities
Select: View Storage Facility State
All sections should report with “PASSED” in the status column.
Failed status can be viewed by highlighting the System Check Type and then select Details.
Select: Cancel to close the screen.

Verify all Code levels are installed Except DDM firmware


Select: Updates
Select: The radio button on the Storage Facility line.
Select: Verify Bundle Installed
The action panel will display all code levels now installed. Ensure all code levels have successfully
been installed. Any downlevel code will be displayed in red and will need to be updated.

Note: Some DDM types are not updated when using the “Concurrent DDM FW Update”, such as
H5Dx drives. DDM levels that match these scenarios can be ignored.
Select: OK to close screen

Enable/Re-enable HMC Heartbeat


Select: HMC management
From Storage Server HMC tasks,
Select: View/Change Heartbeat configuration
Select: Set “Send heartbeat to IBM once in every” to “disable”
Select: Schedule Heartbeat
Select: Yes, to continue, then click OK
Select: Set “Send heartbeat to IBM once in every” to “7 days”
Select: Schedule Heartbeat
Select: Yes, to continue
Select: OK, then Close

Continued on next page...

v4.71 – Page 9
Turn on or cycle MRPD settings.
Select: Service Management
Select: Transmit Service Information
Under Transmit Tab, Hardware service information (VPD) transmission

If the "Enable” box is checked it must be cycled off and on:

Uncheck "Enable” box and click OK


Select: OK at “Successfully updated settings”
Select: Transmit Service Information
Check "Enable" box, set Interval (days) to 14 and click OK
Select: OK at “Successfully updated settings”

If "Enable" is not checked it must be cycled on, off and on again.

Check "Enable" box and click OK


Select: OK at “Successfully updated settings”
Select: Transmit Service Information
Uncheck "Enable" box and click OK
Select: OK at “Successfully updated settings”
Select: Transmit Service Information
Check "Enable" box, set Interval (days) to 14 and click OK
Select: OK at “Successfully updated settings”

Enabling and Configuring AOS


Select: HMC management
From Storage Server HMC tasks,
Select: Manage AOS
Select AOS Groups from the right panel and add to the list on the left.

Ensure the following groups are added at a minimum:


IBM/BLUE/STG/DS8k US and AP SME access
IBM/BLUE/STG/Storage SSR, SE, and RCL access
IBM/BLUE/GTS/EMEA/STORAGE/DS8000 EMEA SME access

Once selections are completed: Click "Start" at the top and "OK" at the bottom to save the work.

Continued on next page…

v4.71 – Page 10
For embedded AOS version 3.3 on DS8870 version 7.1 (licensed machine code level 87.0.102.0) through
version 7.4 , allow encrypted SSL to the following servers :

GEO Host name IP address Ports

Americas aos.us.ihost.com 72.15.208.234 8200 or 80

Americas aosback.us.ihost.com 72.15.223.61 8200 or 80 or 443

Americas aosrelay1.us.ihost.com 72.15.223.60 8200 or 80 or 443

For embedded AOS version 4.0 on DS8870 version 7.5 and later, allow encrypted SSL to the following servers:

GEO Host name IP address Ports

Americas https://aos.uk.ihost.com 195.171.173.165 443

Americas https://aoshats.us.ihost.com 72.15.223.62 443

Perform backup critical data to the Storage Facility Hard drive (LPAR)
Select: HMC management
From Storage Server HMC tasks,
Select: Backup Critical data (time less than 10 minutes) Click OK.
***Automatic Critical backups will occur at 11:00 PM on Thursdays.

v4.71 – Page 11
STEP 6 Install Corrective Service Disks

Image Name Instructions and Restrictions HMC Reboot


(1, 2 or Both) (Y or N)
CSE_CallHomeCertificates_v1.0 Install this ICS image ONLY at 87.51.110.0 and lower B N

CSE_WHRepair-57C3_v1.2 Install this ICS image only at the following versions: 1 N


• 87.51.23.4
• 87.51.23.5
• 87.51.38.0
• 87.51.38.1
CVE_1Q2020_v1.x Customer permission required. B Y
Install at 87.52.xx.xx and higher.

You may experience a timeout issue where the ICS takes over
8 minutes to install. If encountered, disconnect (do not log out)
from the GUI and log back in and you should see the install
completed.
CVE_1Q2019_v1.2 Install at bundles up to 87.52.28.0, unless customer requests B Y
Use the highest available version CVE_1Q2020

enableETmigration_v1.x Install this ICS image only if Step 4a Option 2 was completed 1 N
Note: if you performed Step 4a Option 2 – Easy Tier migration
is disabled and you must re-enable it here otherwise, Easy Tier
migration will remain OFF.
CSE_FixAosPerms Install this ICS image only if going to 87.51.38.0 B N
PFE_FixAOS_Consolidated Install this ICS image if (DNS) Name Servers are not 1 N
configured – compatible with any DS8000 using AOS
DDM_SSD_FW_Update – use the DS8k DDM & SSD Firmware Update Instructions B N
latest version on Fix Central

Verify Installed ICS images


Select: Updates (from left menu)
Select: HMC (from top menu)
Select: Display Installed HMC Code Levels

Look for ICS entries with Mode: ICS


Installed on local HMC

Mode: ICS

ICS Disk Installation


Select: HMC Management
Select: Install Corrective services
Insert: ICS Disk into HMC DVD drive.
Select: Next to confirm Current HMC Driver Information
Select: Removable Media and Next
Select: CD-ROM or DVD and Next
Select: Media Image and Next (no image description is standard)
Select: Finish to confirm -- Install Corrective Service install will take less than 15 minutes ---
The CD will run and display results of the process
Click OK then Yes (Reboot HMC(s) once after all ICS images in this step are installed)

In single- or dual-HMC environment:


Install ICS Disk(s) on HMC A, then reboot.
Wait 15 minutes.
Install ICS Disk(s) on HMC B, then reboot

- End of Code Load -


v4.71 – Page 12
Appendix A
Description of host adapter settings for update during concurrent code load.
The preferred for code load that will be faster with no manual intervention are:
FICON Fastload enabled (default on) CDA setting
CUIR set during machine install. Recommended setting (true)
Interactive host adapter update (default off) CDA setting

Host adapter settings and support


Fiber card Fiber card (FICON)

Fastload Yes Yes

FICON Fastload off Still uses Fastload Will use CUIR if enabled

CUIR N/A Yes, if FICON Fastload is off

CUIR off N/A If FICON Fastload is off, SRN created for manual dummy
replacement

Interactive Update Yes Yes

Mixing topologies on fiber cards and turning FICON Fastload off will result in the card being skipped and an SRN
generated for manual dummy replacement of the card.

Instructions for checking / changing CUIR options


Select: Storage Facility Management
Select: Select the Storage Facility
Select: The Storage Facility Image (e.g. SF Image #1)
Expand: Service Utilities
Select: Enable/Disable Control Switches
Observe the setting for CUIR and, if needed, change the setting and select Set
Select: Cancel to close the screen.

Instructions for disabling FICON Fastload, when required


Select: Updates
Select: The radio button on the Storage Facility line.
Expand: Recovery Utilities
Select: Advanced Configuration
Select the configuration option from the list
Highlight "FICON Fastload Disable" and select “Save Selected Configuration”
Confirm Selection and select Continue

The CDA Concurrent Code Load process will prompt that the default configuration is not set and ask that you confirm the
settings. Validate that only the Desired options are set at that time and select continue or cancel as appropriate.
(Note: to select 2 options at once the use the CTRL key)

After completing the Concurrent Code Update, restore the default Advanced Configuration options.
Instructions for enabling interactive Host Adapter update, when required
Select: Updates
Select: The radio button on the Storage Facility line.
Expand: Recovery Utilities
Select: Advanced Configuration
Select the configuration option from the list
Highlight "Interactive HA" and press “Save Selected Configuration”
Confirm Selection and select Continue

The CDA Concurrent Code Load process will prompt that the default configuration is not set and ask that you confirm the
settings. Validate that only the desired options are set at that time and select continue or cancel as appropriate.
After completing the Concurrent Code Update, restore the default Advanced Configuration options.
v4.71 – Page 13
Appendix B
Appendix B manually updates HMC code only, this requires a manual acquire and update by disabling preload distribute.

Section 1 Acquire Release Bundle


Select: Updates
Select: The radio button on the Storage Facility line
Expand: Recovery Utilities
Select: Advanced Configuration
Hold the Ctrl (Control key) while selecting both options below
Select: Disable HMC Update checking
Select: Disable Preload Distribute
Select: Save Selected Configuration
Select: Continue (Disable HMC Update Checking and Disable Preload Distribute should be displayed in the window)

Select: Updates
Select: The radio button on the HMC line
Select: Acquire Code Images
a) If you are using physical media to acquire code, continue with this step.
If you are using the network, go to step b)
Removable Media (CDROM) radio button is selected
Select Go
Insert the Target Release Bundle DVD as called for by screens
A pop-up will indicate the acquisition is complete
--->>> Remove media and continue to the next section –

b) CDA4TP (Please follow CDA4TP acquire instructions – located on the Tips db or Wiki)

Section 2 Update the HMC to the Latest Bundle


Select: Updates
Select: The radio button on the HMC line.
Select: Update HMC Code from the tasks screen.
Highlight the desired code level
Select: OK
At “Proceeding with the update will take the HMC offline”
Select: Yes
A series of screens will indicate which component is being updated.
At "An HMC reboot is necessary. Press OK to reboot?"
Select: OK
HMC will reboot.
Once the HMC has rebooted the HMC update is complete
Log in to HMC
Select: Updates
Select: The radio button on the Storage Facility line.
Expand: Recovery Utilities
Select: Advanced Configuration
Select: Reset to default
**If the HMC hangs at initialize screen for more that 5 minutes, reboot again by selecting the Alt Ctrl and F1 keys, then Alt Ctrl Del
keys. Use Alt and Ctrl keys on the left side of keyboard.

For Dual HMC configurations, return to the top of Appendix B and acquire and update HMC2

Navigate to Step A – Before starting Preload and follow the instructions from beginning to end normally.

v4.71 – Page 14
Appendix C
Appendix C Upgrades HMC Base Code only to a new 790 level using a Recovery Set.

Required Media for HMC Rebuild (87.5x.x.x Base)

ICS UPG_R7.5-MCP8.1-SAVE-UPGRADE-DATA_v1.x.iso

ICS PFE_Console_Hard_Drive_Test_v1.1.iso

Recovery Set Disk 1 APO9_1411A_0314_0218.1.Recovery.iso

Recovery Set Disk 2 mmhmc-b25.75.0-20150211.1.iso

Recovery Set Disk 3 DS8000StorageManager_HMC_5.7.50.1195.iso

Note HMC recovery set for T510, T520, T530, T540, mini-pc, and XServer HMCs

Required Media for the HMC Rebuild can be downloaded (two options)
CDA4TP (version 4.5) Select->Download->ICS->961_HMC_BASE_790
Fix Central https://www.ibm.com/support/fixcentral/ac/options
Please select “Include Preview Options”

ICS Disk Installation


Select: HMC Management
Select: Install Corrective services
Insert: ICS Disk PFE_Console_Hard_Drive_Test_v1.1 into HMC DVD drive.
Select: Next to confirm Current HMC Driver Information
Select: Removable Media and Next
Select: CD-ROM or DVD and Next
Select: Media Image and Next (no image description is standard)
Select: Finish to confirm -- Install Corrective Service install will take less than 15 minutes ---
The CD will run and display results of the process
If test fails, order and replace the HMC HDD.
If test OK, click OK then No (no reboot required)
Repeat on HMCB, if applicable

ICS Disk Installation


Select: HMC Management
Select: Install Corrective services
Insert UPG_R75-MCP8.1-SAVE-UPGRADE-DATA_v1.1 into HMC DVD drive.
Select: Next to confirm Current HMC Driver Information
Select: Removable Media and Next
Select: CD-ROM or DVD and Next
Select: Media Image and Next (no image description is standard)
Select: Finish to confirm -- Install Corrective Service install will take less than 15 minutes ---
The CD will run and display results of the process
Click OK then Yes (reboot required)

Perform Save Upgrade Data


Log into the HMC after 15 minutes
Select: HMC Management
Select: Save Upgrade Data - Leave the default media as Hard drive
Select: Next
Select: Finish to save the upgrade data
Select: OK to acknowledge completion

Optional: In addition to saving to the HMC HDD, perform the Save Upgrade Data to an external CD/DVD
which can be used to restore the HMC if a failure occurs.

Continued on next page...


v4.71 – Page 15
Perform HMC Rebuild
Insert: HMC Recovery Disk1 APO9_1411A_0314_0218.1.Recovery.iso
Select: HMC Management
Select: Shutdown/Restart
Select: Restart HMC

NOTE: The HMC must only be rebooted with the recovery set after the Save Upgrade Data completes. If the HMC is
rebooted without starting the upgrade, then the Save Upgrade Data MUST be run again before starting the upgrade.
After HMC reboots with Disk1 the Install/Backup/Restore Wizard is started
Select: Upgrade
Select: Next

NOTE: The Upgrade option MUST be selected to recover the saved upgrade data, if Install is selected then the HMC's Save
Upgrade Data will be lost.
Select: OK to acknowledge the Upgrade Warning
Leave default option “Upgrade from media”
Select: Next
Select: Finish to begin the HMC Upgrade - The base installation will take 20-25 minutes to complete
Once the base HMC install is complete a prompt will be displayed to reboot the HMC
Remove Recovery Set Disk 1 from the HMC
Press any key to reboot the HMC

The HMC will boot to an install prompt


Select: Option 1 install additional software
Insert: HMC Recovery Disk 2 mmhmc-b25.75.0-20150211.1.iso from the HMC Recovery Set

Note: Ensure that Disk 2 is inserted, and the LED on the DVD drive is no longer blinking before continuing.

Select: Enter to start the MM Extensions install - This will take about 5-10 minutes to complete.
Once the MM Extensions install is complete another install prompt will be displayed
Select: Option 1 install additional software
Insert: HMC Recovery Disk 3 DS8000StorageManager_HMC_5.7.50.1195.iso from the HMC Recovery Set

Note: Ensure that Disk 3 is inserted, and the LED on the DVD drive is no longer blinking before continuing.

Select: Enter to acknowledge the disk is inserted


Select: Enter to start the ICAT install - This will take 5-10 minutes to complete.

Note: Once the ICAT installation is complete the HMC will automatically reboot and restore the upgrade data. At this point the HMC
Upgrade is complete

Navigate to Appendix B and follow the instructions from beginning to end normally.

v4.71 – Page 16