Characteristic of Trip curves of MCCB tell about the trip current rating of MCCB.
MCB will trip instantaneously according to their Tripping Characteristic at 0.1 sec.
There are various type of MCCB
Type B MCCB
Type C MCCB
Type D MCCB
Type K MCCB
Type Z MCCB
Type B MCCB:
Operating Current: This type of MCB trips between 3 and 5 times rated current (In).
Operating Time:04 To 13 Sec
For example a 10A device will trip at 30-50A.
Application: Domestic applications or light commercial applications where connected loads are primarily lighting fixtures,
domestic appliances with mainly restive elements.
Suitable for: Restive Load application (Lighting , Small Motor)
Surge Current: The surge current level is relatively low.
Installation at: At Sub feeder of Distribution Board.
Type C MCCB:
Operating Current: This type of MCB trips between 5 and 10 times full load current.
Operating Time:04 To 5 Sec
Application: commercial or industrial type of applications, fluorescent lighting, motors etc where there could be chances of
higher values of short circuit currents in the circuit.
https://electricalnotes.wordpress.com/2016/11/02/how-to-select-mcb-mccb-part2/ 1/6
12/28/2020 How to select MCB / MCCB (Part:2) | Electrical Notes & Articles
Suitable for: Inductive Load application (Pumps, Motor, fluorescent lighting.)
Surge Current: The surge current level is relatively moderate level.
Installation at: At incoming / Outgoing of Distribution Board.
Type D MCCB:
Operating Current: This type of MCB trips between 10 and 20 times full load current.
Operating Time:04 To 3 Sec
Application: specialty industrial / commercial uses (Transformers or X-ray machines, large winding motors, discharge lighting,
large ba ery charging). Where current inrush can be very high.
Suitable for: Inductive- Capacitive Load application (Pumps, Motor)
Surge Current: The surge current level is relatively High
Installation at: At incoming of Distribution Board / Panels.
Type K MCCB:
Operating Current: This type of MCB trips between 8 and 12 times full load current.
Operating Time:04 To 5 Sec
Application: Suitable for inductive and motor loads with high inrush currents.
Surge Current: The surge current level is relatively High
Installation at: At incoming of Distribution Board / Panels.
Type Z MCCB:
Operating Current: This type of MCB trips between 2 and 3 times full load current.
Operating Time:04 To 5 Sec
Application: These types of MCBs are highly sensitive to short circuit and are used for protection of highly sensitive devices such
as semiconductor devices.
Surge Current: The surge current level is relatively too low
Installation at: At Sub feeder of Distribution Board for IT equipment.
(D) Accessories:
https://electricalnotes.wordpress.com/2016/11/02/how-to-select-mcb-mccb-part2/ 2/6
12/28/2020 How to select MCB / MCCB (Part:2) | Electrical Notes & Articles
It used to trip MCCB in under voltage condition (70 to 35% of rated Voltage).
https://electricalnotes.wordpress.com/2016/11/02/how-to-select-mcb-mccb-part2/ 3/6
12/28/2020 How to select MCB / MCCB (Part:2) | Electrical Notes & Articles
MCCB may have provision for Auto /Manual operation.
An “auto/manual” switch in front of Panel.
When set to the “Manual” position, lock out electrical control and when set to “auto”, lock out the manual control; remote
indication
MCCB may have option for manual operation or with a motor mechanism for electrically controlled
[email protected] says:
November 2, 2016 at 12:52 pm
Hi parmar,
MD is 1650 KVA and what are procedures I have to follow in u ar Pradesh Electricity board.
Reply
kush says:
November 2, 2016 at 1:15 pm
Sir can you provide me your email id?
Reply
billa madhu says:
November 2, 2016 at 2:19 pm
Hi sir thanks for information. And I want all safe values of electrical apparatus for example cable insulation values, transformer
insulation values,earthing values, motor insulation values, insulators, continuity values,IE rules, with numbers. This information
I require, thank you sir, with regards On 02-Nov-2016 6:18 PM, “Electrical Notes & Articles” wrote:
> Jignesh.Parmar posted: “(C) Application Type: (9) Utilization category / > Characteristic (B, C, D, K, Z curve): Characteristic of
Trip curves of MCCB > tell about the trip current rating of MCCB. MCB will trip instantaneously > according to their Tripping
Characteristic at 0.1 sec” >
Reply
kannanshrikanth says:
November 2, 2016 at 2:27 pm
ThanksPlease categorize the difference and their application of RCCBThanksRegardsSrikanth
Reply
Srikanth kannan says:
November 2, 2016 at 2:35 pm
https://electricalnotes.wordpress.com/2016/11/02/how-to-select-mcb-mccb-part2/ 4/6
12/28/2020 How to select MCB / MCCB (Part:2) | Electrical Notes & Articles
Please categorize RCCB and their applications
Thanks
Regards
Srikanth
Reply
Ashoke Ghosh says:
November 2, 2016 at 5:14 pm
Great solution….
Reply
Tony Zonneveld says:
November 2, 2016 at 8:15 pm
Jignesh.Parmar
thanks for this info
(I use your site quite for all sorts of info that is not readily available elsewhere
so please keep up the good work
Regards
Reply
syed618 says:
November 3, 2016 at 5:24 am
GOOD VERY USEFUL
On Wed, Nov 2, 2016 at 6:17 PM, Electrical Notes & Articles wrote:
> Jignesh.Parmar posted: “(C) Application Type: (9) Utilization category / > Characteristic (B, C, D, K, Z curve): Characteristic of
Trip curves of MCCB > tell about the trip current rating of MCCB. MCB will trip instantaneously > according to their Tripping
Characteristic at 0.1 sec” >
Reply
shamin says:
November 3, 2016 at 10:15 am
sir,how we conduct generator testing?
Reply
shamin says:
November 3, 2016 at 10:16 am
sir,how we conduct generator testing
Reply
Raju says:
November 4, 2016 at 2:20 pm
Thank you sir.
Reply
billa madhu says:
November 5, 2016 at 5:41 pm
Hi sir please clear me one doubt, how the fuel consumption calculated, on dg set
Reply
Muhammad Isah says:
November 12, 2016 at 1:42 pm
very educative
Reply
Haeseb says:
November 15, 2016 at 6:09 am
Describe the precautions necessary to deal with each of the following issues when carrying out an oil change on an 11 kv/400 v
transformer.
Reply
Madhav Bamne says:
https://electricalnotes.wordpress.com/2016/11/02/how-to-select-mcb-mccb-part2/ 5/6
12/28/2020 How to select MCB / MCCB (Part:2) | Electrical Notes & Articles
November 21, 2016 at 8:56 am
Dear sir,
those articles are very helpful for all electrical professional specially freshers .
Reply
Rommel says:
November 30, 2016 at 1:50 am
Thank you. It’s very helpful for us.
Reply
Ibrahin says:
May 1, 2019 at 1:13 am
G’ day,
I am working on designing protection devices for my research work and I am struggling to model the thermal part for the low
voltage circuit breakers based on IEC standards.
Based on the standards, the time current curve for types B, C and D are as mentioned on the a ached figure. I could not find the
proper formula which represents the thermal characteristic for these types. Please, assist on this ma er.
Reply
This site uses Akismet to reduce spam. Learn how your comment data is processed.
https://electricalnotes.wordpress.com/2016/11/02/how-to-select-mcb-mccb-part2/ 6/6