Beam Column Slab Calculation
Beam Column Slab Calculation
Beam Column Slab Calculation
Beam No : FTB1,FTB2,FTB3
Group No : G1
Analysis Reference(Member) 1.2 m : 37,38,39
Breadth : 250 mm
Depth : 400 mm
Concrete Grade : C24 N/sqmm
Grade Of Steel (Main) : Fy275 N/sqmm
Grade Of Steel (Shear) : Fy230 N/sqmm
Top/Bottom Clear Cover : 20 mm
Side Clear Cover : 20 mm
Design Code : NSCP C101 - 2015
Beam Type : Ductile Beam
Flexure Design
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Mu (kNm) 35.36 13.14 35.28 38.49 17.94 38.76
PtClc (%) 0.509 0.233 0.509 0.527 0.53 0.53
AstCalc (sqmm) 445.45 335.08 445.45 460.74 463.98 463.98
Ast Prv (sqmm) 603.18 402.12 603.18 603.18 603.18 603.18
Reinforcement 3-⌀16mm 2-⌀16mm 3-⌀16mm 3-⌀16mm 3-⌀16mm 3-⌀16mm
SFR : 3-#10EF
Beam No : FTB4,FTB6
Group No : G4
Analysis Reference(Member) 1.2 m : 34,36
Breadth : 250 mm
Depth : 400 mm
Concrete Grade : C24 N/sqmm
Grade Of Steel (Main) : Fy275 N/sqmm
Grade Of Steel (Shear) : Fy230 N/sqmm
Top/Bottom Clear Cover : 20 mm
Side Clear Cover : 20 mm
Design Code : NSCP C101 - 2015
Beam Type : Ductile Beam
Flexure Design
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Mu (kNm) 25.06 10.1 22.62 28.53 13.61 24.91
PtClc (%) 0.45 0.179 0.405 0.509 0.509 0.447
AstCalc (sqmm) 393.79 438.5 354.61 445.46 445.46 391.26
Ast Prv (sqmm) 565.5 565.5 565.5 603.18 603.18 603.18
Reinforcement 3-⌀12mm 3-⌀12mm 3-⌀12mm 3-⌀16mm 3-⌀16mm 3-⌀16mm
2-⌀12mm 2-⌀12mm 2-⌀12mm
Beam No : FTB5,FTB7
Group No : G4
Analysis Reference(Member) 1.2 m : 33,35
Breadth : 250 mm
Depth : 400 mm
Concrete Grade : C24 N/sqmm
Grade Of Steel (Main) : Fy275 N/sqmm
Grade Of Steel (Shear) : Fy230 N/sqmm
Top/Bottom Clear Cover : 20 mm
Side Clear Cover : 20 mm
Design Code : NSCP C101 - 2015
Beam Type : Ductile Beam
Flexure Design
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Mu (kNm) 22.49 10.26 25.22 25.25 13.52 28.11
PtClc (%) 0.403 0.182 0.453 0.454 0.506 0.506
AstCalc (sqmm) 352.53 444.28 396.27 396.84 442.99 442.99
Ast Prv (sqmm) 565.5 565.5 565.5 603.18 603.18 603.18
Reinforcement 3-⌀12mm 3-⌀12mm 3-⌀12mm 3-⌀16mm 3-⌀16mm 3-⌀16mm
2-⌀12mm 2-⌀12mm 2-⌀12mm
SFR : 3-#10EF
BEAM DESIGN SUMMARY
Project Name : Proposed Two Storey Transformer Room
Client Name : Subic Grain
Engineer Name : Marcley Bataoil
Design File : ...\Users\Engr.Marcley Bataoil\Desktop\Project in Subic
Grain\PROPOSED TWO STROREY ELECTRICAL
ROOM\DESIGN\Design Revise\Revise v2\With ftb and cantilever
slab\Two Storey Transformer Room-Beam-1-4.2 m.rcdx
Analysis File : C:\Users\Engr.Marcley Bataoil\Desktop\Project in Subic
Grain\PROPOSED TWO STROREY ELECTRICAL
ROOM\DESIGN\Design Revise\Revise v2\With ftb and cantilever
slab\Two Storey Transformer Room.STD
Analysis Last Modified : 12/1/2023 10:52:26 AM
Level Designed : 4.2 m
Beam No : B1,B2,B3
Group No : G1
Analysis Reference(Member) 4.2 m : 11,12,13
Breadth : 250 mm
Depth : 400 mm
Concrete Grade : C24 N/sqmm
Grade Of Steel (Main) : Fy275 N/sqmm
Grade Of Steel (Shear) : Fy230 N/sqmm
Top/Bottom Clear Cover : 20 mm
Side Clear Cover : 20 mm
Design Code : NSCP C101 - 2015
Beam Type : Ductile Beam
Flexure Design
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Mu (kNm) 27.58 18.49 27.43 48.89 15.66 49.31
PtClc (%) 0.496 0.33 0.494 0.676 0.682 0.682
AstCalc (sqmm) 434.39 552.67 432.01 591.37 596.61 596.61
Ast Prv (sqmm) 565.5 565.5 565.5 603.18 603.18 603.18
Reinforcement 3-#12 3-#12 3-#12 3-#16 3-#16 3-#16
2-#12 2-#12 2-#12
SFR : 3-#10EF
Beam No : B4,B6
Group No : G4
Analysis Reference(Member) 4.2 m : 8,10
Breadth : 250 mm
Depth : 400 mm
Concrete Grade : C24 N/sqmm
Grade Of Steel (Main) : Fy275 N/sqmm
Grade Of Steel (Shear) : Fy230 N/sqmm
Top/Bottom Clear Cover : 20 mm
Side Clear Cover : 20 mm
Design Code : NSCP C101 - 2015
Beam Type : Ductile Beam
Flexure Design
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Mu (kNm) 19.32 14.7 17.58 37.33 10.15 38.78
PtClc (%) 0.345 0.261 0.314 0.51 0.531 0.531
AstCalc (sqmm) 301.84 483.4 282.75 446.34 464.33 464.33
Ast Prv (sqmm) 339.3 565.5 339.3 603.18 603.18 603.18
Reinforcement 3-#12 3-#12 3-#12 3-#16 3-#16 3-#16
2-#12
SFR : 3-#10EF
Beam No : B5,B7
Group No : G4
Analysis Reference(Member) 4.2 m : 7,9
Breadth : 250 mm
Depth : 400 mm
Concrete Grade : C24 N/sqmm
Grade Of Steel (Main) : Fy275 N/sqmm
Grade Of Steel (Shear) : Fy230 N/sqmm
Top/Bottom Clear Cover : 20 mm
Side Clear Cover : 20 mm
Design Code : NSCP C101 - 2015
Beam Type : Ductile Beam
Flexure Design
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Mu (kNm) 16.68 16 20.16 41.12 10.84 35.12
PtClc (%) 0.297 0.285 0.36 0.564 0.564 0.509
AstCalc (sqmm) 282.75 540.62 315.33 493.48 493.48 445.46
Ast Prv (sqmm) 339.3 565.5 339.3 603.18 603.18 603.18
Reinforcement 3-#12 3-#12 3-#12 3-#16 3-#16 3-#16
2-#12
SFR : 3-#10EF
BEAM DESIGN SUMMARY
Project Name : Proposed Two Storey Transformer Room
Client Name : Subic Grain
Engineer Name : MPB
Design File : ...\Users\Engr.Marcley Bataoil\Desktop\Project in Subic
Grain\PROPOSED TWO STROREY ELECTRICAL
ROOM\DESIGN\Design Revise\Revise v2\With ftb and cantilever
slab\Two Storey Transformer Room-Beam-1-7.2 m.rcdx
Analysis File : C:\Users\Engr.Marcley Bataoil\Desktop\Project in Subic
Grain\PROPOSED TWO STROREY ELECTRICAL
ROOM\DESIGN\Design Revise\Revise v2\With ftb and cantilever
slab\Two Storey Transformer Room.STD
Analysis Last Modified : 12/1/2023 10:52:26 AM
Level Designed : 7.2 m
Beam No : RB1,RB2,RB3
Group No : G1
Analysis Reference(Member) 7.2 m : 24,25,26
Breadth : 250 mm
Depth : 300 mm
Concrete Grade : C24 N/sqmm
Grade Of Steel (Main) : Fy275 N/sqmm
Grade Of Steel (Shear) : Fy230 N/sqmm
Top/Bottom Clear Cover : 20 mm
Side Clear Cover : 20 mm
Design Code : NSCP C101 - 2015
Beam Type : Ductile Beam
Flexure Design
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Mu (kNm) 8.28 7.58 8.2 18.64 5.01 18.75
PtClc (%) 0.247 0.226 0.245 0.509 0.509 0.509
AstCalc (sqmm) 201.06 313.01 201.06 343.64 343.64 343.64
Ast Prv (sqmm) 339.3 339.3 339.3 402.12 402.12 402.12
Reinforcement 3-⌀12mm 3-⌀12mm 3-⌀12mm 2-⌀16mm 2-⌀16mm 2-⌀16mm
SFR : 2-#10EF
Beam No : RB4
Group No : G4
Analysis Reference(Member) 7.2 m : 42
Breadth : 250 mm
Depth : 300 mm
Concrete Grade : C24 N/sqmm
Grade Of Steel (Main) : Fy275 N/sqmm
Grade Of Steel (Shear) : Fy230 N/sqmm
Top/Bottom Clear Cover : 20 mm
Side Clear Cover : 20 mm
Design Code : NSCP C101 - 2015
Beam Type : Cantilever Beam
Flexure Design
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Mu (kNm) 6.36 7.88 6.17 5.49 0.18 5.77
PtClc (%) 0.189 0.235 0.184 0.163 0.13 0.172
AstCalc (sqmm) 127.77 158.76 124.02 110.19 87.75 115.81
Ast Prv (sqmm) 235.62 235.62 235.62 235.62 235.62 235.62
Reinforcement 3-⌀10mm 3-⌀10mm 3-⌀10mm 3-⌀10mm 3-⌀10mm 3-⌀10mm
Shear Design
Left Mid Right
Vu (kN) 13.39 8.11 13.56
Asv Torsion (sqmm/m) 0 0 0
Asv Reqd (sqmm/m) 380.44 380.44 380.44
Asv Prv (sqmm/m) 1309 1309 1309
Reinforcement 2L-⌀10mm @ 120 2L-⌀10mm @ 120 2L-⌀10mm @ 120
SFR : -
Beam No : RB5,RB8
Group No : G5
Analysis Reference(Member) 7.2 m : 41,40
Breadth : 250 mm
Depth : 300 mm
Concrete Grade : C24 N/sqmm
Grade Of Steel (Main) : Fy275 N/sqmm
Grade Of Steel (Shear) : Fy230 N/sqmm
Top/Bottom Clear Cover : 20 mm
Side Clear Cover : 20 mm
Design Code : NSCP C101 - 2015
Beam Type : Cantilever Beam
Flexure Design
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Mu (kNm) 1.81 0 0 3.37 14.72 21.16
PtClc (%) 0.221 0.13 0.13 0.268 0.509 0.599
AstCalc (sqmm) 158.57 87.75 87.75 189.87 343.64 391.99
Ast Prv (sqmm) 235.62 235.62 235.62 402.12 402.12 402.12
Reinforcement 3-⌀10mm 3-⌀10mm 3-⌀10mm 2-⌀16mm 2-⌀16mm 2-⌀16mm
Shear Design
Left Mid Right
Vu (kN) 15.28 15.97 17.69
Asv Torsion (sqmm/m) 693.99 693.99 693.99
Asv Reqd (sqmm/m) 1022.02 1036.8 1073.78
Asv Prv (sqmm/m) 1309 1309 1309
Reinforcement 2L-⌀10mm @ 120 2L-⌀10mm @ 120 2L-⌀10mm @ 120
SFR : 2-#10EF
Beam No : RB6,RB9
Group No : G5
Analysis Reference(Member) 7.2 m : 21,23
Breadth : 250 mm
Depth : 300 mm
Concrete Grade : C24 N/sqmm
Grade Of Steel (Main) : Fy275 N/sqmm
Grade Of Steel (Shear) : Fy230 N/sqmm
Top/Bottom Clear Cover : 20 mm
Side Clear Cover : 20 mm
Design Code : NSCP C101 - 2015
Beam Type : Ductile Beam
Flexure Design
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Mu (kNm) 4.93 5.13 7.89 17.62 6.88 3.07
PtClc (%) 0.146 0.153 0.236 0.509 0.509 0.13
AstCalc (sqmm) 201.06 257.27 261.38 343.64 343.64 250.72
Ast Prv (sqmm) 339.3 339.3 339.3 402.12 402.12 402.12
Reinforcement 3-⌀12mm 3-⌀12mm 3-⌀12mm 2-⌀16mm 2-⌀16mm 2-⌀16mm
SFR : 2-#10EF
Beam No : RB7,RB10
Group No : G5
Analysis Reference(Member) 7.2 m : 20,22
Breadth : 250 mm
Depth : 300 mm
Concrete Grade : C24 N/sqmm
Grade Of Steel (Main) : Fy275 N/sqmm
Grade Of Steel (Shear) : Fy230 N/sqmm
Top/Bottom Clear Cover : 20 mm
Side Clear Cover : 20 mm
Design Code : NSCP C101 - 2015
Beam Type : Ductile Beam
Flexure Design
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Mu (kNm) 5.62 5.4 7.74 4.8 3.56 3.56
PtClc (%) 0.167 0.16 0.231 0.143 0.458 0.13
AstCalc (sqmm) 201.06 296.37 231.22 308.9 309.19 309.19
Ast Prv (sqmm) 339.3 339.3 339.3 402.12 402.12 402.12
Reinforcement 3-⌀12mm 3-⌀12mm 3-⌀12mm 2-⌀16mm 2-⌀16mm 2-⌀16mm
SFR : 2-#10EF
BEAM DESIGN CALCULATION
Project Name : Proposed Two Storey Transformer Room
Client Name : Subic Grain
Engineer Name : MPB
Design File : ...\Users\Engr.Marcley Bataoil\Desktop\Project in Subic
Grain\PROPOSED TWO STROREY ELECTRICAL
ROOM\DESIGN\Design Revise\Revise v2\With ftb and cantilever
slab\Two Storey Transformer Room-Beam-1-1.2 m.rcdx
Analysis File : C:\Users\Engr.Marcley Bataoil\Desktop\Project in Subic
Grain\PROPOSED TWO STROREY ELECTRICAL
ROOM\DESIGN\Design Revise\Revise v2\With ftb and cantilever
slab\Two Storey Transformer Room.STD
Analysis Last Modified : 12/1/2023 10:52:26 AM
Level Designed : 1.2 m
All Forces are in 'kN', 'kNm', Stress in 'N/sqmm' & Dimension are in 'mm'.
Code References
Sr.No. Item Clause / Table
407.3.3.1, 408.3.3.1,
1. Ptmax :
409.3.3.1
2. As,min (flex) (B) : 409.6.1.1, 409.6.1.2
3. As,min : 409.6.1.3
4. Vc : 422.5
5. Asv : 422.5.10.5 & 422.6.7
6. Min Shear Reinf : 409.6.3.1
Max Stirrup
7. : 409.7.62
Spacing
Shear Reinf -
8. : 422.7.3.1
Torsion
Side Face
9. : 409.7.2.3
Reinforcement
10. Tcr : 409.5.4.1
11. fs,perm : 424.3.2.1
12. fc,perm : A.3.1 (ACI 318-99)
Eq 1-2 ( ACI 224R-
13. Wcr :
01)
14. Ptmin : 418.6.3.1
15. Asmin : 418.6.3.1
16. Sclc : 418.6.4.1 & 418.6.4.4
Strength Reduction
17. factor for tension : 21.2.2
controlled section
Group : G1
Beam No : FTB1,FTB2,FTB3
Analysis Reference
: 37,38,39 (1.2 m)
(Member)
Beam Length : 2900 mm
Breadth (B) : 250 mm
Depth (D) : 400 mm
Effective Depth (d) : 350 mm
Design Code : NSCP C101 - 2015
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (f'c) : C24 N/sqmm
Grade Of Steel (Main) : Fy275 N/sqmm
Grade Of Steel (Shear) : Fy230 N/sqmm
Grade Of Steel - Flexural
: Fy275 N/sqmm
Design
Grade Of Steel - Shear
: Fy230 N/sqmm
Design
Grade Of Steel - Torsion
: Fy230 N/sqmm
Design
Top/Bottom Clear Cover
: 20 mm
(Cmin)
Side Clear Cover : 20 mm
Es : 2x10^5 N/sqmm
Mubal : 150.66 kNm
As,min (flex) (B) : 445.45 sqmm
As,nominal (Bn) : 113.75 sqmm
As,min(user input)(B') : 113.75 sqmm
Maximum percentage steel
:4 %
(User Defined)
Maximum percentage steel
: 2.365 %
(Tension Controlled section)
Maximum percentage steel Min (4 ,
:
(Special Frame) 2.5 ,2.365)
: 2.365 %
Strength Reduction Factor φ
: 0.6
(Shear)
Ast = Max {B, C+D, A+D} (for Mu > 0 and C x 1.33 > B)
Ast = Max{B', C x 1.33 + D, A+D} (for Mu > 0 and C x 1.33 < B)
Ast = Bn (for Mu = 0)
Where,
Compression reinforcement required for
A = Asc (flex) =
bending moment
B = As,min (flex) = Min area of flexural reinforcement
Bn = As,nominal = Nominal area of reinforcement
Total area of longitudinal reinforcement
C = As (flex) =
calculated at a given section
Distributed longitudinal torsional
D = Al (Dist) =
reinforcement at section considered
A s,reqd Crack Area of reinforcement required for Crack
E = =
Width
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
Slenderness Check
Slenderness Check is not
considered along D and B
Basic
0.33 Sqrt(f'c)Bd = 141.46 kN
Left Mid Right
Vs (kN) 50.36 44.75 50.66
Vs <= 0.33 Vs <= 0.33 Vs <= 0.33
Check
Sqrt(f'c)Bd Sqrt(f'c)Bd Sqrt(f'c)Bd
Spc1 (mm) d/2=175 d/2=175 d/2=175
Spc2 (mm) 600 600 600
For Torsion
(X1 = 220, Y1 = 370)
Spc3 = 300 mm
Spc4=(X1+Y1)/4 = 148 mm
= 96 mm
Spc5 = 6 x Small Longitudinal Dia
Spc6 = d / 4 = 88 mm
Spc7 = 150 mm
Provided Spacing = 85 mm
Mid Section
Provided Spacing = 175 mm
Skin reinforcement
Spacing Criteria
Group : G4
Beam No : FTB4,FTB6
34,36 (1.2
Analysis Reference (Member) :
m)
Beam Length : 2625 mm
Breadth (B) : 250 mm
Depth (D) : 400 mm
Effective Depth (d) : 350 mm
Design Code : NSCP C101 - 2015
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (f'c) : C24 N/sqmm
Grade Of Steel (Main) : Fy275 N/sqmm
Grade Of Steel (Shear) : Fy230 N/sqmm
Grade Of Steel - Flexural
: Fy275 N/sqmm
Design
Grade Of Steel - Shear Design : Fy230 N/sqmm
Grade Of Steel - Torsion
: Fy230 N/sqmm
Design
Top/Bottom Clear Cover
: 20 mm
(Cmin)
Side Clear Cover : 20 mm
Es : 2x10^5 N/sqmm
Mubal : 150.66 kNm
As,min (flex) (B) : 445.45 sqmm
As,nominal (Bn) : 113.75 sqmm
As,min(user input)(B') : 113.75 sqmm
Maximum percentage steel
: 4 %
(User Defined)
Maximum percentage steel
: 2.365 %
(Tension Controlled section)
Maximum percentage steel Min (4 ,
:
(Special Frame) 2.5 ,2.365)
: 2.365 %
Strength Reduction Factor φ
: 0.6
(Shear)
Ast = Max {B, C+D, A+D} (for Mu > 0 and C x 1.33 > B)
Ast = Max{B', C x 1.33 + D, A+D} (for Mu > 0 and C x 1.33 < B)
Ast = Bn (for Mu = 0)
Where,
Compression reinforcement required for
A = Asc (flex) =
bending moment
B = As,min (flex) = Min area of flexural reinforcement
Bn = As,nominal = Nominal area of reinforcement
Total area of longitudinal reinforcement
C = As (flex) =
calculated at a given section
Distributed longitudinal torsional
D = Al (Dist) =
reinforcement at section considered
A s,reqd Crack Area of reinforcement required for Crack
E = =
Width
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
Slenderness Check
Slenderness Check is not
considered along D and B
+ 6- + 6- + 6-
⌀10mm ⌀10mm ⌀10mm
Load Angle (deg) 180.1 180.09 0.1
-1
Tan (Muy/Mux)
MRes (kNm) 25.06 17.55 24.91
φ Mcap (kNm) 60.36 60.36 65.96
Capacity Ratio 0.42 0.29 0.38
MRes/ MCap
Where,
A = Moments directly from analysis
B = Moment due to slenderness effect
C = Final design Moment = Max(A,B)
Basic
0.33 Sqrt(f'c)Bd = 141.46 kN
Left Mid Right
Vs (kN) 39.89 34.54 38.71
Vs <= 0.33 Vs <= 0.33 Vs <= 0.33
Check
Sqrt(f'c)Bd Sqrt(f'c)Bd Sqrt(f'c)Bd
Spc1 (mm) d/2=175 d/2=175 d/2=175
Spc2 (mm) 600 600 600
For Torsion
(X1 = 220, Y1 = 370)
Spc3 = 300 mm
Spc4=(X1+Y1)/4 = 148 mm
= 72 mm
Spc5 = 6 x Small Longitudinal Dia
Spc6 = d / 4 = 88 mm
Spc7 = 150 mm
Provided Spacing = 70 mm
Mid Section
Provided Spacing = 175 mm
Skin reinforcement
Spacing Criteria
Group : G4
Beam No : FTB5,FTB7
33,35 (1.2
Analysis Reference (Member) :
m)
Beam Length : 2625 mm
Breadth (B) : 250 mm
Depth (D) : 400 mm
Effective Depth (d) : 350 mm
Design Code : NSCP C101 - 2015
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (f'c) : C24 N/sqmm
Grade Of Steel (Main) : Fy275 N/sqmm
Grade Of Steel (Shear) : Fy230 N/sqmm
Grade Of Steel - Flexural
: Fy275 N/sqmm
Design
Grade Of Steel - Shear Design : Fy230 N/sqmm
Grade Of Steel - Torsion
: Fy230 N/sqmm
Design
Top/Bottom Clear Cover
: 20 mm
(Cmin)
Side Clear Cover : 20 mm
Es : 2x10^5 N/sqmm
Mubal : 150.66 kNm
As,min (flex) (B) : 445.45 sqmm
As,nominal (Bn) : 113.75 sqmm
As,min(user input)(B') : 113.75 sqmm
Maximum percentage steel
: 4 %
(User Defined)
Maximum percentage steel
: 2.365 %
(Tension Controlled section)
Maximum percentage steel Min (4 ,
:
(Special Frame) 2.5 ,2.365)
: 2.365 %
Strength Reduction Factor φ
: 0.6
(Shear)
Ast = Max {B, C+D, A+D} (for Mu > 0 and C x 1.33 > B)
Ast = Max{B', C x 1.33 + D, A+D} (for Mu > 0 and C x 1.33 < B)
Ast = Bn (for Mu = 0)
Where,
Compression reinforcement required for
A = Asc (flex) =
bending moment
B = As,min (flex) = Min area of flexural reinforcement
Bn = As,nominal = Nominal area of reinforcement
Total area of longitudinal reinforcement
C = As (flex) =
calculated at a given section
Distributed longitudinal torsional
D = Al (Dist) =
reinforcement at section considered
A s,reqd Crack Area of reinforcement required for Crack
E = =
Width
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
Slenderness Check
Slenderness Check is not
considered along D and B
+ 6- + 6- + 6-
⌀10mm ⌀10mm ⌀10mm
Load Angle (deg) 0.11 180.09 180.1
Tan-1 (Muy/Mux)
MRes (kNm) 25.25 17.66 25.22
φ Mcap (kNm) 65.88 60.33 60.33
Capacity Ratio 0.38 0.29 0.42
MRes/ MCap
Where,
A = Moments directly from analysis
B = Moment due to slenderness effect
C = Final design Moment = Max(A,B)
Basic
0.33 Sqrt(f'c)Bd = 141.46 kN
Left Mid Right
Vs (kN) 39.19 34.05 39.41
Vs <= 0.33 Vs <= 0.33 Vs <= 0.33
Check
Sqrt(f'c)Bd Sqrt(f'c)Bd Sqrt(f'c)Bd
Spc1 (mm) d/2=175 d/2=175 d/2=175
Spc2 (mm) 600 600 600
For Torsion
(X1 = 220, Y1 = 370)
Spc3 = 300 mm
Spc4=(X1+Y1)/4 = 148 mm
= 72 mm
Spc5 = 6 x Small Longitudinal Dia
Spc6 = d / 4 = 88 mm
Spc7 = 150 mm
Provided Spacing = 70 mm
Mid Section
Provided Spacing = 175 mm
Skin reinforcement
Spacing Criteria
All Forces are in 'kN', 'kNm', Stress in 'N/sqmm' & Dimension are in 'mm'.
Code References
Sr.No. Item Clause / Table
407.3.3.1, 408.3.3.1,
1. Ptmax :
409.3.3.1
2. As,min (flex) (B) : 409.6.1.1, 409.6.1.2
3. As,min : 409.6.1.3
4. Vc : 422.5
5. Asv : 422.5.10.5 & 422.6.7
6. Min Shear Reinf : 409.6.3.1
Max Stirrup
7. : 409.7.62
Spacing
Shear Reinf -
8. : 422.7.3.1
Torsion
Side Face
9. : 409.7.2.3
Reinforcement
10. Tcr : 409.5.4.1
11. fs,perm : 424.3.2.1
12. fc,perm : A.3.1 (ACI 318-99)
Eq 1-2 ( ACI 224R-
13. Wcr :
01)
14. Ptmin : 418.6.3.1
15. Asmin : 418.6.3.1
16. Sclc : 418.6.4.1 & 418.6.4.4
Strength Reduction
17. factor for tension : 21.2.2
controlled section
Group : G1
Beam No : B1,B2,B3
11,12,13
Analysis Reference (Member) :
(4.2 m)
Beam Length : 2900 mm
Breadth (B) : 250 mm
Depth (D) : 400 mm
Effective Depth (d) : 350 mm
Design Code : NSCP C101 - 2015
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (f'c) : C24 N/sqmm
Grade Of Steel (Main) : Fy275 N/sqmm
Grade Of Steel (Shear) : Fy230 N/sqmm
Grade Of Steel - Flexural
: Fy275 N/sqmm
Design
Grade Of Steel - Shear Design : Fy230 N/sqmm
Grade Of Steel - Torsion
: Fy230 N/sqmm
Design
Top/Bottom Clear Cover
: 20 mm
(Cmin)
Side Clear Cover : 20 mm
Es : 2x10^5 N/sqmm
Mubal : 150.66 kNm
As,min (flex) (B) : 445.45 sqmm
As,nominal (Bn) : 113.75 sqmm
As,min(user input)(B') : 113.75 sqmm
Maximum percentage steel
: 4 %
(User Defined)
Maximum percentage steel
: 2.365 %
(Tension Controlled section)
Maximum percentage steel Min (4 ,
:
(Special Frame) 2.5 ,2.365)
: 2.365 %
Strength Reduction Factor φ
: 0.6
(Shear)
Ast = Max {B, C+D, A+D} (for Mu > 0 and C x 1.33 > B)
Ast = Max{B', C x 1.33 + D, A+D} (for Mu > 0 and C x 1.33 < B)
Ast = Bn (for Mu = 0)
Where,
Compression reinforcement required for
A = Asc (flex) =
bending moment
B = As,min (flex) = Min area of flexural reinforcement
Bn = As,nominal = Nominal area of reinforcement
Total area of longitudinal reinforcement
C = As (flex) =
calculated at a given section
Distributed longitudinal torsional
D = Al (Dist) =
reinforcement at section considered
A s,reqd Crack Area of reinforcement required for Crack
E = =
Width
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
Slenderness Check
Slenderness Check is not
considered along D and B
Where,
A = Moments directly from analysis
B = Moment due to slenderness effect
C = Final design Moment = Max(A,B)
Basic
0.33 Sqrt(f'c)Bd = 141.46 kN
Left Mid Right
Vs (kN) 98.21 61.68 95.52
Vs <= 0.33 Vs <= 0.33 Vs <= 0.33
Check
Sqrt(f'c)Bd Sqrt(f'c)Bd Sqrt(f'c)Bd
Spc1 (mm) d/2=175 d/2=175 d/2=175
Spc2 (mm) 600 600 600
For Torsion
(X1 = 220, Y1 = 370)
Spc3 = 300 mm
Spc4=(X1+Y1)/4 = 148 mm
= 72 mm
Spc5 = 6 x Small Longitudinal Dia
Spc6 = d / 4 = 88 mm
Spc7 = 150 mm
Provided Spacing = 70 mm
Mid Section
Provided Spacing = 175 mm
Skin reinforcement
Spacing Criteria
Ast = Max {B, C+D, A+D} (for Mu > 0 and C x 1.33 > B)
Ast = Max{B', C x 1.33 + D, A+D} (for Mu > 0 and C x 1.33 < B)
Ast = Bn (for Mu = 0)
Where,
Compression reinforcement required for
A = Asc (flex) =
bending moment
B = As,min (flex) = Min area of flexural reinforcement
Bn = As,nominal = Nominal area of reinforcement
Total area of longitudinal reinforcement
C = As (flex) =
calculated at a given section
Distributed longitudinal torsional
D = Al (Dist) =
reinforcement at section considered
A s,reqd Crack Area of reinforcement required for Crack
E = =
Width
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
Slenderness Check
Slenderness Check is not
considered along D and B
Where,
A = Moments directly from analysis
B = Moment due to slenderness effect
C = Final design Moment = Max(A,B)
Basic
0.33 Sqrt(f'c)Bd = 141.46 kN
Left Mid Right
Vs (kN) 83.34 52.66 89.48
Vs <= 0.33 Vs <= 0.33 Vs <= 0.33
Check
Sqrt(f'c)Bd Sqrt(f'c)Bd Sqrt(f'c)Bd
Spc1 (mm) d/2=175 d/2=175 d/2=175
Spc2 (mm) 600 600 600
For Torsion
(X1 = 220, Y1 = 370)
Spc3 = 300 mm
Spc4=(X1+Y1)/4 = 148 mm
= 72 mm
Spc5 = 6 x Small Longitudinal Dia
Spc6 = d / 4 = 88 mm
Spc7 = 150 mm
Provided Spacing = 70 mm
Mid Section
Provided Spacing = 175 mm
Skin reinforcement
Spacing Criteria
Group : G4
Beam No : B5,B7
Analysis Reference (Member) : 7,9 (4.2 m)
Beam Length : 2625 mm
Breadth (B) : 250 mm
Depth (D) : 400 mm
Effective Depth (d) : 350 mm
Design Code : NSCP C101 - 2015
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (f'c) : C24 N/sqmm
Grade Of Steel (Main) : Fy275 N/sqmm
Grade Of Steel (Shear) : Fy230 N/sqmm
Grade Of Steel - Flexural
: Fy275 N/sqmm
Design
Grade Of Steel - Shear Design : Fy230 N/sqmm
Grade Of Steel - Torsion
: Fy230 N/sqmm
Design
Top/Bottom Clear Cover
: 20 mm
(Cmin)
Side Clear Cover : 20 mm
Es : 2x10^5 N/sqmm
Mubal : 150.66 kNm
As,min (flex) (B) : 445.45 sqmm
As,nominal (Bn) : 113.75 sqmm
As,min(user input)(B') : 113.75 sqmm
Maximum percentage steel
: 4 %
(User Defined)
Maximum percentage steel
: 2.365 %
(Tension Controlled section)
Maximum percentage steel Min (4 ,
:
(Special Frame) 2.5 ,2.365)
: 2.365 %
Strength Reduction Factor φ
: 0.6
(Shear)
Ast = Max {B, C+D, A+D} (for Mu > 0 and C x 1.33 > B)
Ast = Max{B', C x 1.33 + D, A+D} (for Mu > 0 and C x 1.33 < B)
Ast = Bn (for Mu = 0)
Where,
Compression reinforcement required for
A = Asc (flex) =
bending moment
B = As,min (flex) = Min area of flexural reinforcement
Bn = As,nominal = Nominal area of reinforcement
Total area of longitudinal reinforcement
C = As (flex) =
calculated at a given section
Distributed longitudinal torsional
D = Al (Dist) =
reinforcement at section considered
A s,reqd Crack Area of reinforcement required for Crack
E = =
Width
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
Slenderness Check
Slenderness Check is not
considered along D and B
Where,
A = Moments directly from analysis
B = Moment due to slenderness effect
C = Final design Moment = Max(A,B)
Basic
0.33 Sqrt(f'c)Bd = 141.46 kN
Left Mid Right
Vs (kN) 89.48 56.48 83.31
Vs <= 0.33 Vs <= 0.33 Vs <= 0.33
Check
Sqrt(f'c)Bd Sqrt(f'c)Bd Sqrt(f'c)Bd
Spc1 (mm) d/2=175 d/2=175 d/2=175
Spc2 (mm) 600 600 600
For Torsion
(X1 = 220, Y1 = 370)
Spc3 = 300 mm
Spc4=(X1+Y1)/4 = 148 mm
= 72 mm
Spc5 = 6 x Small Longitudinal Dia
Spc6 = d / 4 = 88 mm
Spc7 = 150 mm
Provided Spacing = 70 mm
Mid Section
Provided Spacing = 175 mm
Skin reinforcement
Spacing Criteria
Beam No : RB1,RB2,RB3
Group No : G1
Analysis Reference(Member) 7.2 m : 24,25,26
Breadth : 250 mm
Depth : 300 mm
Concrete Grade : C24 N/sqmm
Grade Of Steel (Main) : Fy275 N/sqmm
Grade Of Steel (Shear) : Fy230 N/sqmm
Top/Bottom Clear Cover : 20 mm
Side Clear Cover : 20 mm
Design Code : NSCP C101 - 2015
Beam Type : Ductile Beam
Flexure Design
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Mu (kNm) 8.28 7.58 8.2 18.64 5.01 18.75
PtClc (%) 0.247 0.226 0.245 0.509 0.509 0.509
AstCalc (sqmm) 201.06 313.01 201.06 343.64 343.64 343.64
Ast Prv (sqmm) 339.3 339.3 339.3 402.12 402.12 402.12
Reinforcement 3-⌀12mm 3-⌀12mm 3-⌀12mm 2-⌀16mm 2-⌀16mm 2-⌀16mm
SFR : 2-#10EF
Beam No : RB4
Group No : G4
Analysis Reference(Member) 7.2 m : 42
Breadth : 250 mm
Depth : 300 mm
Concrete Grade : C24 N/sqmm
Grade Of Steel (Main) : Fy275 N/sqmm
Grade Of Steel (Shear) : Fy230 N/sqmm
Top/Bottom Clear Cover : 20 mm
Side Clear Cover : 20 mm
Design Code : NSCP C101 - 2015
Beam Type : Cantilever Beam
Flexure Design
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Mu (kNm) 6.36 7.88 6.17 5.49 0.18 5.77
PtClc (%) 0.189 0.235 0.184 0.163 0.13 0.172
AstCalc (sqmm) 127.77 158.76 124.02 110.19 87.75 115.81
Ast Prv (sqmm) 235.62 235.62 235.62 235.62 235.62 235.62
Reinforcement 3-⌀10mm 3-⌀10mm 3-⌀10mm 3-⌀10mm 3-⌀10mm 3-⌀10mm
Shear Design
Left Mid Right
Vu (kN) 13.39 8.11 13.56
Asv Torsion (sqmm/m) 0 0 0
Asv Reqd (sqmm/m) 380.44 380.44 380.44
Asv Prv (sqmm/m) 1309 1309 1309
Reinforcement 2L-⌀10mm @ 120 2L-⌀10mm @ 120 2L-⌀10mm @ 120
SFR : -
Beam No : RB5,RB8
Group No : G5
Analysis Reference(Member) 7.2 m : 41,40
Breadth : 250 mm
Depth : 300 mm
Concrete Grade : C24 N/sqmm
Grade Of Steel (Main) : Fy275 N/sqmm
Grade Of Steel (Shear) : Fy230 N/sqmm
Top/Bottom Clear Cover : 20 mm
Side Clear Cover : 20 mm
Design Code : NSCP C101 - 2015
Beam Type : Cantilever Beam
Flexure Design
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Mu (kNm) 1.81 0 0 3.37 14.72 21.16
PtClc (%) 0.221 0.13 0.13 0.268 0.509 0.599
AstCalc (sqmm) 158.57 87.75 87.75 189.87 343.64 391.99
Ast Prv (sqmm) 235.62 235.62 235.62 402.12 402.12 402.12
Reinforcement 3-⌀10mm 3-⌀10mm 3-⌀10mm 2-⌀16mm 2-⌀16mm 2-⌀16mm
Shear Design
Left Mid Right
Vu (kN) 15.28 15.97 17.69
Asv Torsion (sqmm/m) 693.99 693.99 693.99
Asv Reqd (sqmm/m) 1022.02 1036.8 1073.78
Asv Prv (sqmm/m) 1309 1309 1309
Reinforcement 2L-⌀10mm @ 120 2L-⌀10mm @ 120 2L-⌀10mm @ 120
SFR : 2-#10EF
Beam No : RB6,RB9
Group No : G5
Analysis Reference(Member) 7.2 m : 21,23
Breadth : 250 mm
Depth : 300 mm
Concrete Grade : C24 N/sqmm
Grade Of Steel (Main) : Fy275 N/sqmm
Grade Of Steel (Shear) : Fy230 N/sqmm
Top/Bottom Clear Cover : 20 mm
Side Clear Cover : 20 mm
Design Code : NSCP C101 - 2015
Beam Type : Ductile Beam
Flexure Design
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Mu (kNm) 4.93 5.13 7.89 17.62 6.88 3.07
PtClc (%) 0.146 0.153 0.236 0.509 0.509 0.13
AstCalc (sqmm) 201.06 257.27 261.38 343.64 343.64 250.72
Ast Prv (sqmm) 339.3 339.3 339.3 402.12 402.12 402.12
Reinforcement 3-⌀12mm 3-⌀12mm 3-⌀12mm 2-⌀16mm 2-⌀16mm 2-⌀16mm
SFR : 2-#10EF
Beam No : RB7,RB10
Group No : G5
Analysis Reference(Member) 7.2 m : 20,22
Breadth : 250 mm
Depth : 300 mm
Concrete Grade : C24 N/sqmm
Grade Of Steel (Main) : Fy275 N/sqmm
Grade Of Steel (Shear) : Fy230 N/sqmm
Top/Bottom Clear Cover : 20 mm
Side Clear Cover : 20 mm
Design Code : NSCP C101 - 2015
Beam Type : Ductile Beam
Flexure Design
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Mu (kNm) 5.62 5.4 7.74 4.8 3.56 3.56
PtClc (%) 0.167 0.16 0.231 0.143 0.458 0.13
AstCalc (sqmm) 201.06 296.37 231.22 308.9 309.19 309.19
Ast Prv (sqmm) 339.3 339.3 339.3 402.12 402.12 402.12
Reinforcement 3-⌀12mm 3-⌀12mm 3-⌀12mm 2-⌀16mm 2-⌀16mm 2-⌀16mm
SFR : 2-#10EF
COLUMN DESIGN SUMMARY
Project Name : Proposed Two Storey Transformer Room
Client Name : Subic Grain
Engineer Name : MPB
Design File : C:\Users\Engr.Marcley Bataoil\Desktop\Project in Subic
Grain\PROPOSED TWO STROREY ELECTRICAL
ROOM\DESIGN\Design Revise\Revise v2\With ftb and cantilever
slab\Two Storey Transformer Room-Column-1.rcdx
Analysis File : C:\Users\Engr.Marcley Bataoil\Desktop\Project in Subic
Grain\PROPOSED TWO STROREY ELECTRICAL
ROOM\DESIGN\Design Revise\Revise v2\With ftb and cantilever
slab\Two Storey Transformer Room.STD
Analysis Last Modified : 12/1/2023 10:52:26 AM
Note:
Some Of the checks For vertical And horizontal reinforcement are updated In latest version Of
RCDC, Thus If the RCDC file created Using older version (older than V11 Update 1), Is opened In
latest version And calculation reports are directly generated, Then, some Of the values printed In the
report may Not match the design. For such files created Using older version, it Is recommended To
unlock the old design And re-perform the same
Levels : 1. FOUNDATION
2. 1.2 m
3. 4.2 m
4. 7.2 m
Column/Wall : C1
FrameType : Lateral
Level Size Material LC Analysis P Mx My Pt Interaction Main Links
(mm) LC No (kN) (kNm) (kNm) (%) Ratio Reinforcement
C24 :
1 TO 350 X #10 @ 50 +
Fy275 : 41 223 -4.68 19.59 -0.41 1.03 0.43 4-#16 + 4-#12
2 350 #10 @ 175
Fy230
C24 :
2 TO 350 X #10 @ 50 +
Fy275 : 41 223 11.51 31.6 -1.23 1.03 0.66 4-#16 + 4-#12
3 350 #10 @ 175
Fy230
C24 :
3 TO 350 X #10 @ 50 +
Fy275 : 26 208 24.1 15.83 2.17 1.03 0.32 4-#16 + 4-#12
4 350 #10 @ 175
Fy230
Column/Wall : C2
FrameType : Lateral
Level Size Material LC Analysis P Mx My Pt Interaction Main Links
(mm) LC No (kN) (kNm) (kNm) (%) Ratio Reinforcement
C24 :
1 TO 350 X #10 @ 50 +
Fy275 : 42 224 -5.55 -19.58 -0.41 1.03 0.43 4-#16 + 4-#12
2 350 #10 @ 175
Fy230
C24 :
2 TO 350 X #10 @ 50 +
Fy275 : 42 224 10.59 -31.48 -1.23 1.03 0.66 4-#16 + 4-#12
3 350 #10 @ 175
Fy230
C24 :
3 TO 350 X #10 @ 50 +
Fy275 : 25 207 23.05 -15.85 2.19 1.03 0.32 4-#16 + 4-#12
4 350 #10 @ 175
Fy230
Column/Wall : C3
FrameType : Lateral
Level Size Material LC Analysis P Mx My Pt Interaction Main Links
(mm) LC No (kN) (kNm) (kNm) (%) Ratio Reinforcement
C24 :
1 TO 350 X #10 @ 75 +
Fy275 : 41 223 11.73 19.14 -0.24 1.31 0.32 8-#16
2 350 #10 @ 150
Fy230
C24 :
2 TO 350 X #10 @ 75 +
Fy275 : 44 226 52.07 -0.5 34.86 1.31 0.54 8-#16
3 350 #10 @ 150
Fy230
C24 :
3 TO 350 X #10 @ 75 +
Fy275 : 26 208 37.87 17.62 -0.8 1.31 0.28 8-#16
4 350 #10 @ 175
Fy230
Column/Wall : C4
FrameType : Lateral
Level Size Material LC Analysis P Mx My Pt Interaction Main Links
(mm) LC No (kN) (kNm) (kNm) (%) Ratio Reinforcement
C24 :
1 TO 350 X #10 @ 75 +
Fy275 : 42 224 9.68 -19.12 -0.24 1.31 0.32 8-#16
2 350 #10 @ 150
Fy230
C24 :
2 TO 350 X #10 @ 75 +
Fy275 : 45 227 49.93 0.58 34.39 1.31 0.54 8-#16
3 350 #10 @ 150
Fy230
C24 :
3 TO 350 X #10 @ 75 +
Fy275 : 25 207 35.45 -17.17 -0.8 1.31 0.28 8-#16
4 350 #10 @ 175
Fy230
Column/Wall : C5
FrameType : Lateral
Level Size Material LC Analysis P Mx My Pt Interaction Main Links
(mm) LC No (kN) (kNm) (kNm) (%) Ratio Reinforcement
C24 :
1 TO 350 X #10 @ 50 +
Fy275 : 40 222 -0.38 22.39 2.08 1.03 0.48 4-#16 + 4-#12
2 350 #10 @ 175
Fy230
C24 :
2 TO 350 X #10 @ 50 +
Fy275 : 40 222 17.03 36.29 4.31 1.03 0.74 4-#16 + 4-#12
3 350 #10 @ 175
Fy230
C24 :
3 TO 350 X #10 @ 50 +
Fy275 : 27 209 52.19 23.08 8.71 1.03 0.43 4-#16 + 4-#12
4 350 #10 @ 175
Fy230
Column/Wall : C6
FrameType : Lateral
Level Size Material LC Analysis P Mx My Pt Interaction Main Links
(mm) LC No (kN) (kNm) (kNm) (%) Ratio Reinforcement
C24 :
1 TO 350 X #10 @ 50 +
Fy275 : 43 225 -1.66 -22.37 2.08 1.03 0.48 4-#16 + 4-#12
2 350 #10 @ 175
Fy230
C24 :
2 TO 350 X #10 @ 50 +
Fy275 : 43 225 15.7 -36.17 4.32 1.03 0.74 4-#16 + 4-#12
3 350 #10 @ 175
Fy230
C24 :
3 TO 350 X #10 @ 50 +
Fy275 : 24 206 50.02 -23.04 8.77 1.03 0.43 4-#16 + 4-#12
4 350 #10 @ 175
Fy230
COLUMN DESIGN CALCULATIONS
Project Name : Proposed Two Storey Transformer Room
Client Name : Subic Grain
Engineer Name : MPB
Design File : C:\Users\Engr.Marcley Bataoil\Desktop\Project in Subic
Grain\PROPOSED TWO STROREY ELECTRICAL
ROOM\DESIGN\Design Revise\Revise v2\With ftb and cantilever
slab\Two Storey Transformer Room-Column-1.rcdx
Analysis File : C:\Users\Engr.Marcley Bataoil\Desktop\Project in Subic
Grain\PROPOSED TWO STROREY ELECTRICAL
ROOM\DESIGN\Design Revise\Revise v2\With ftb and cantilever
slab\Two Storey Transformer Room.STD
Analysis Last Modified : 12/1/2023 10:52:26 AM
Definitions Of Terms:
All forces in units 'kN' and 'm'
All reinforcement details like area, spacing in 'mm'
Neutral axis angle for resultant design moment is with respect to local major axis.
Ratio to account for reduction of stiffness of columns
1 βdns =
due to sustained axial loads
Moment magnification factor for frames not braced
2 δns =
against sidesway
First-order relative deflection between the top and
3 Δo =
bottom of the story due to Vu in 'kN'
4 ∑Pu = Total factored vertical load in 'kN'. (Clause 406.6.4.4)
5 δu = Design displacement in 'mm'
Modification factor reflecting the reduced mechanical
6 λ =
properties Of concrete
Coefficient defining the relative contribution Of
7 ac =
concrete strength To nominal wall shear strength
Cross-sectional area of a structural member measured
8 Ach = to the outside edges of transverse reinforcement in
'sqmm'
Gross area of concrete section bounded by web
9 Acv = thickness And length of section in the direction Of
shear force considered in 'sqmm'
Effective cross-sectional area within a joint In a plane
10 Aj = parallel To plane Of reinforcement generating shear
In the joint in 'sqmm'
Area Of non-prestressed longitudinal tension
11 As =
reinforcement in 'sqmm'
Minimum area Of shear reinforcement within spacing
12 Avmin =
's' in 'sqmm'
13 B = Width of column/ wall in 'mm'
14 beff = Effective Width of column/ wall in 'mm'
Code References:
NSCP C101 - 2015
Sr.No Element Clause / table
Minimum area of longitudinal reinforcement
1 : 418.7.4
for column
Maximum area of longitudinal
2 : 418.7.4
reinforcement for column
Minimum longitudinal and transverse
3 : 418.10.2.1
reinforcement for wall
4 Minimum diameter of transverse ties : 425.7.2
5 Minimum spacing of transverse ties : 425.7.2
Maximum spacing of longitudinal and
6 : 418.10.2.1
transverse reinforcement for wall
7 Applicability of boundary element : 418.10.6
Area and spacing of special confining
8 : 418.7.5
reinforcement
9 Slenderness Moments : 406.2.5
Shear Strength provided by concrete for
10 : 422.5.5
column
11 Design of shear for non-ductile wall : 411.5.4
12 Design of shear for ductile wall : 418.10.4.1
13 Minimum Flexural Strength of Columns : 418.7.3
14 Shear Check at Column Joint : 418.8.4.1
15 Shear Strength of Column : 418.3.3, 418.4 & 418.6.5
16 fs,perm : 424.3.2.1
17 fc,perm : A.3.1 (ACI 318-99)
18 Wcr : Eq 1-2 ( ACI 224R-01)
Sway Calculation (Stability Index)
For Global-X Direction
Level Load Storey Gravity Relative Storey Stability Sway
Combination Height Load P Displacements Shear Index (Q) Condition
Analysis (m) (kN) (mm) (kN)
B x C / (A x
A B C D
D)
0 m to 1.2
206 1.2 870.44 0.47 112.46 0.003 Non Sway
m
1.2 m to
206 3 718.91 4.93 108.08 0.011 Non Sway
4.2 m
4.2 m to
206 3 175.33 5.16 44.57 0.007 Non Sway
7.2 m
General Data
Column No. : C1
Level : 0 m To 1.2 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C24 N/sqmm
Grade Of Steel (Main) = Fy275 N/sqmm
Grade Of Steel (Shear) = Fy230 N/sqmm
Grade Of Steel - Flexural Design = Fy275 N/sqmm
Grade Of Steel - Shear Design = Fy230 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 800 mm
Clear Floor Height @ luy = 800 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.003
0.003< 0.05, Column shall be designed as non-sway frame
(Braced)
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = -4.68 kN
Mux = 19.59 kNm
Muy = -0.41 kNm
Shear Calculation
Along D Along B
(Analysis Forces)
Lu (mm) 800 800
Pu Top (kN) 174.64 174.64
Mnt (kNm) 78.78 78.78
Pu Bottom (kN) 180.04 180.04
Mnb (kNm) 79.45 79.45
Vu1 (kN) 197.79 197.79
Shear from Beam Capacity at Joint
Moment Mnt (kNm) MAX((left,Bot + Right,Top), (left,Top +
Right,Bot))
38.79 39.12
Moment Mnb (kNm) MAX((Left,Top + Right,Bot), (Right,Top +
Left,Bot))
0 0
Lu (mm) 800 800
Vu2 (kN) 48.48 48.9
Critical Analysis Load 223 226
Combination
Critical Load [41] : 0.57 (LOAD 9: [44] : 0.57 (LOAD 9:
Combination DL) +(LOAD 2: EQ +X DL) +(LOAD 5: EQ +Z
-E) +E)
Nu (kN) -6.69 3.82
Mu (kNm) 3.23 16.63
Vu3 (kN) 19.02 -16.66
Vu' (kN) Minimum(Vu1, Vu2)
48.48 48.9
Design Shear, Vu (kN) Maximum(Vu', Vu3)
48.48 48.9
λ 1 1
φ 0.75 0.75
Deff (mm) 302 302
ρw (50% of As 0.006 0.006
provided)
Mm (kNm) 4.14 16.11
φVc (kN) 64.98 69.48
Check Vu < φVc Vu < φVc
Link For Shear Design Not Required Not Required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 170.88 kN
Vs
Check <=0.33*Sqrt
(f'c)*B*d
b/2 = 151 mm
600 = 600 mm
Provided spacing = 175 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 462.21 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 532.61 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 532.61 sqmm/m
Criterion for spacing of Ductile
links:
Min. Longitudinal Bar dia x 6 = 72 mm
B/4 = 87.5 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 50 mm
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.85
r = 101.04 mm
Kluy /r = 21.87
M1 = -21.29 kNm
M2 = 31.6 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.87 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.85
r = 101.04 mm
Klux /r = 21.87
M1 = -1.23 kNm
M2 = 2.44 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.87 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Shear Calculation
Along D Along B
(Analysis Forces)
Lu (mm) 2600 2600
Pu Top (kN) 129.07 129.07
Mnt (kNm) 73.11 73.11
Pu Bottom (kN) 142.57 142.57
Mnb (kNm) 74.79 74.79
Vu1 (kN) 56.88 56.88
Shear from Beam Capacity at Joint
Moment Mnt (kNm) MAX((left,Bot + Right,Top), (left,Top +
Right,Bot))
51.01 39.03
Moment Mnb (kNm) MAX((Left,Top + Right,Bot), (Right,Top +
Left,Bot))
38.79 39.12
Lu (mm) 2600 2600
Vu2 (kN) 34.54 30.06
Critical Analysis Load 208 213
Combination
Critical Load [26] : 1.53 (LOAD 9: [31] : 1.53 (LOAD 9:
Combination DL) +0.5 (LOAD 10: DL) +0.5 (LOAD 10:
LL) +(LOAD 3: EQ -X LL) +(LOAD 8: EQ -Z
+E) -E)
Nu (kN) 142.57 138.41
Mu (kNm) 34.76 32.35
Vu3 (kN) -20.94 20.33
Vu' (kN) Minimum(Vu1, Vu2)
34.54 30.06
Design Shear, Vu (kN) Maximum(Vu', Vu3)
34.54 30.06
λ 1 1
φ 0.75 0.75
Deff (mm) 302 302
ρw (50% of As 0.006 0.006
provided)
Mm (kNm) 15.19 13.35
φVc (kN) 67.64 67.59
Check Vu < φVc Vu < φVc
Link For Shear Design Not Required Not Required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 170.88 kN
Vs
<=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 151 mm
600 = 600 mm
Provided spacing = 175 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 462.21 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 532.61 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 532.61 sqmm/m
Criterion for spacing of Ductile
links:
Min. Longitudinal Bar dia x 6 = 72 mm
B/4 = 87.5 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 50 mm
General Data
Column No. : C1
Level : 4.2 m To 7.2 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C24 N/sqmm
Grade Of Steel (Main) = Fy275 N/sqmm
Grade Of Steel (Shear) = Fy230 N/sqmm
Grade Of Steel - Flexural Design = Fy275 N/sqmm
Grade Of Steel - Shear Design = Fy230 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2700 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.006
0.006< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.85
r = 101.04 mm
Kluy /r = 22.71
M1 = -14.74 kNm
M2 = 15.83 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.71 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.84
r = 101.04 mm
Klux /r = 22.45
M1 = 2.17 kNm
M2 = -2.39 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.45 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Shear Calculation
Along D Along B
(Analysis Forces)
Lu (mm) 2700 2700
Pu Top (kN) 24.1 24.1
Mnt (kNm) 59.59 59.59
Pu Bottom (kN) 37.6 37.6
Mnb (kNm) 61.37 61.37
Vu1 (kN) 44.8 44.8
Shear from Beam Capacity at Joint
Moment Mnt (kNm) MAX((left,Bot + Right,Top), (left,Top +
Right,Bot))
19.96 20.13
Moment Mnb (kNm) MAX((Left,Top + Right,Bot), (Right,Top +
Left,Bot))
51.01 39.03
Lu (mm) 2700 2700
Vu2 (kN) 26.29 21.91
Critical Analysis Load 208 213
Combination
Critical Load [26] : 1.53 (LOAD 9: [31] : 1.53 (LOAD 9:
Combination DL) +0.5 (LOAD 10: DL) +0.5 (LOAD 10:
LL) +(LOAD 3: EQ -X LL) +(LOAD 8: EQ -Z
+E) -E)
Nu (kN) 24.1 22.98
Mu (kNm) 15.83 13.17
Vu3 (kN) -10.19 8.14
Vu' (kN) Minimum(Vu1, Vu2)
26.29 21.91
Design Shear, Vu (kN) Maximum(Vu', Vu3)
26.29 21.91
λ 1 1
φ 0.75 0.75
Deff (mm) 302 302
ρw (50% of As 0.006 0.006
provided)
Mm (kNm) 12.52 10.02
φVc (kN) 67.22 67.43
Check Vu < φVc Vu < φVc
Link For Shear Design Not Required Not Required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 170.88 kN
Vs
<=0.33*Sqrt
Check
(f'c)*B*d
b/2 = 151 mm
600 = 600 mm
Provided spacing = 175 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 462.21 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 532.61 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 532.61 sqmm/m
Criterion for spacing of Ductile
links:
Min. Longitudinal Bar dia x 6 = 72 mm
B/4 = 87.5 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 50 mm
General Data
Column No. : C2
Level : 0 m To 1.2 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C24 N/sqmm
Grade Of Steel (Main) = Fy275 N/sqmm
Grade Of Steel (Shear) = Fy230 N/sqmm
Grade Of Steel - Flexural Design = Fy275 N/sqmm
Grade Of Steel - Shear Design = Fy230 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 800 mm
Clear Floor Height @ luy = 800 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.003
0.003< 0.05, Column shall be designed as non-sway frame
(Braced)
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Shear Calculation
Along D Along B
(Analysis Forces)
Lu (mm) 800 800
Pu Top (kN) 172.1 172.1
Mnt (kNm) 78.47 78.47
Pu Bottom (kN) 177.5 177.5
Mnb (kNm) 79.14 79.14
Vu1 (kN) 197 197
Shear from Beam Capacity at Joint
Moment Mnt (kNm) MAX((left,Bot + Right,Top), (left,Top +
Right,Bot))
38.79 39.12
Moment Mnb (kNm) MAX((Left,Top + Right,Bot), (Right,Top +
Left,Bot))
0 0
Lu (mm) 800 800
Vu2 (kN) 48.48 48.9
Critical Analysis Load 224 226
Combination
Critical Load [42] : 0.57 (LOAD 9: [44] : 0.57 (LOAD 9:
Combination DL) +(LOAD 3: EQ -X DL) +(LOAD 5: EQ +Z
+E) +E)
Nu (kN) -7.56 -1.18
Mu (kNm) 3.25 2.89
Vu3 (kN) -19.03 -15.21
Vu' (kN) Minimum(Vu1, Vu2)
48.48 48.9
Design Shear, Vu (kN) Maximum(Vu', Vu3)
48.48 48.9
λ 1 1
φ 0.75 0.75
Deff (mm) 302 302
ρw (50% of As 0.006 0.006
provided)
Mm (kNm) 4.29 3.05
φVc (kN) 64.84 65.84
Check Vu < φVc Vu < φVc
Link For Shear Design Not Required Not Required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 170.88 kN
Vs
Check <=0.33*Sqrt
(f'c)*B*d
b/2 = 151 mm
600 = 600 mm
Provided spacing = 175 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 462.21 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 532.61 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 532.61 sqmm/m
Criterion for spacing of Ductile
links:
Min. Longitudinal Bar dia x 6 = 72 mm
B/4 = 87.5 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 50 mm
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.85
r = 101.04 mm
Kluy /r = 21.87
M1 = 21.37 kNm
M2 = -31.48 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.87 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.85
r = 101.04 mm
Klux /r = 21.87
M1 = -1.23 kNm
M2 = 2.44 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.87 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Shear Calculation
Along D Along B
(Analysis Forces)
Lu (mm) 2600 2600
Pu Top (kN) 126.38 126.38
Mnt (kNm) 72.77 72.77
Pu Bottom (kN) 139.88 139.88
Mnb (kNm) 74.45 74.45
Vu1 (kN) 56.62 56.62
Shear from Beam Capacity at Joint
Moment Mnt (kNm) MAX((left,Bot + Right,Top), (left,Top +
Right,Bot))
51.01 39.03
Moment Mnb (kNm) MAX((Left,Top + Right,Bot), (Right,Top +
Left,Bot))
38.79 39.12
Lu (mm) 2600 2600
Vu2 (kN) 34.54 30.06
Critical Analysis Load 207 212
Combination
Critical Load [25] : 1.53 (LOAD 9: [30] : 1.53 (LOAD 9:
Combination DL) +0.5 (LOAD 10: DL) +0.5 (LOAD 10:
LL) +(LOAD 2: EQ +X LL) +(LOAD 7: EQ -Z
-E) +E)
Nu (kN) 139.88 135.96
Mu (kNm) 35.11 31.92
Vu3 (kN) 20.98 20.08
Vu' (kN) Minimum(Vu1, Vu2)
34.54 30.06
Design Shear, Vu (kN) Maximum(Vu', Vu3)
34.54 30.06
λ 1 1
φ 0.75 0.75
Deff (mm) 302 302
ρw (50% of As 0.006 0.006
provided)
Mm (kNm) 15.91 13.26
φVc (kN) 67.39 67.62
Check Vu < φVc Vu < φVc
Link For Shear Design Not Required Not Required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 170.88 kN
Vs
Check <=0.33*Sqrt
(f'c)*B*d
b/2 = 151 mm
600 = 600 mm
Provided spacing = 175 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 462.21 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 532.61 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 532.61 sqmm/m
Criterion for spacing of Ductile
links:
Min. Longitudinal Bar dia x 6 = 72 mm
B/4 = 87.5 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 50 mm
Along B
Q = 0.006
0.006< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.85
r = 101.04 mm
Kluy /r = 22.71
M1 = 15.05 kNm
M2 = -15.85 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.71 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.84
r = 101.04 mm
Klux /r = 22.45
M1 = 2.19 kNm
M2 = -2.41 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.45 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Shear Calculation
Along D Along B
(Analysis Forces)
Lu (mm) 2700 2700
Pu Top (kN) 23.05 23.05
Mnt (kNm) 59.46 59.46
Pu Bottom (kN) 36.55 36.55
Mnb (kNm) 61.24 61.24
Vu1 (kN) 44.7 44.7
Shear from Beam Capacity at Joint
Moment Mnt (kNm) MAX((left,Bot + Right,Top), (left,Top +
Right,Bot))
24.73 20.17
Moment Mnb (kNm) MAX((Left,Top + Right,Bot), (Right,Top +
Left,Bot))
51.01 39.03
Lu (mm) 2700 2700
Vu2 (kN) 28.05 21.93
Critical Analysis Load 207 212
Combination
Critical Load [25] : 1.53 (LOAD 9: [30] : 1.53 (LOAD 9:
Combination DL) +0.5 (LOAD 10: DL) +0.5 (LOAD 10:
LL) +(LOAD 2: EQ +X LL) +(LOAD 7: EQ -Z
-E) +E)
Nu (kN) 23.05 22
Mu (kNm) 15.85 12.98
Vu3 (kN) 10.3 8.02
Vu' (kN) Minimum(Vu1, Vu2)
28.05 21.93
Design Shear, Vu (kN) Maximum(Vu', Vu3)
28.05 21.93
λ 1 1
φ 0.75 0.75
Deff (mm) 302 302
ρw (50% of As 0.006 0.006
provided)
Mm (kNm) 12.68 9.96
φVc (kN) 67.49 67.46
Check Vu < φVc Vu < φVc
Link For Shear Design Not Required Not Required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 170.88 kN
Vs
Check <=0.33*Sqrt
(f'c)*B*d
b/2 = 151 mm
600 = 600 mm
Provided spacing = 175 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 462.21 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 532.61 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 532.61 sqmm/m
Criterion for spacing of Ductile
links:
Min. Longitudinal Bar dia x 6 = 72 mm
B/4 = 87.5 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 50 mm
Along B
Q = 0.003
0.003< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.82
r = 101.04 mm
Kluy /r = 6.49
M1 = -3.01 kNm
M2 = 19.14 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.89
6.49 < 35.89, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.79
r = 101.04 mm
Klux /r = 6.26
M1 = 0.19 kNm
M2 = -0.24 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
6.26 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Shear Calculation
Along D Along B
(Analysis Forces)
Lu (mm) 800 800
Pu Top (kN) 217.3 217.3
Mnt (kNm) 97.07 97.07
Pu Bottom (kN) 222.7 222.7
Mnb (kNm) 97.68 97.68
Vu1 (kN) 243.44 243.44
Shear from Beam Capacity at Joint
Moment Mnt (kNm) MAX((left,Bot + Right,Top), (left,Top +
Right,Bot))
38.79 71.28
Moment Mnb (kNm) MAX((Left,Top + Right,Bot), (Right,Top +
Left,Bot))
0 0
Lu (mm) 800 800
Vu2 (kN) 48.48 89.1
Critical Analysis Load 223 226
Combination
Critical Load [41] : 0.57 (LOAD 9: [44] : 0.57 (LOAD 9:
Combination DL) +(LOAD 2: EQ +X DL) +(LOAD 5: EQ +Z
-E) +E)
Nu (kN) 11.73 59.56
Mu (kNm) 19.14 19.74
Vu3 (kN) 18.46 -25.11
Vu' (kN) Minimum(Vu1, Vu2)
48.48 89.1
Design Shear, Vu (kN) Maximum(Vu', Vu3)
48.48 89.1
λ 1 1
φ 0.75 0.75
Deff (mm) 302 302
ρw (50% of As 0.008 0.008
provided)
Mm (kNm) 17.53 11.57
φVc (kN) 70.7 86
Check Vu < φVc Vu > φVc
Link For Shear Design Not Required Required
Shear Links Design
Vs (kN) (Vu - φVc) / φVc
- 4.14
Vs Permissible (kN) 0.66 x sqrt(f'c) x b x deff
- 341.76
Vs Permissible Check - Vs < Vs permissible;
Hence, OK
Check for Minimum -
Shear Reinforcement
0.5 x φVc (kN) - 43
Minimum Shear - Vu > 0.5 x φVc;
Reinforcement Check Hence , Minimum
Shear reinforcement
required
Av/s minimum - 532.61
(sqmm/m)
Av/s shear (sqmm/m) - 59.6
Av/s required max (Av/s minimum , Av/s shear)
(sqmm/m)
- 532.61
Link Rebar Number - 10
Diameter of link (mm) - 10
Numbers of legs - 3
provided
Spacing of Link - 150
Provided (mm)
Av/s provided - 1570.8
(sqmm/m )
Av/s provided check - Av/s required < Av/s
provided; Hence, OK
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 4.14 kN
0.33*Sqrt (f'c)*Aeff = 170.88 kN
Vs
Check <=0.33*Sqrt
(f'c)*B*d
b/2 = 151 mm
600 = 600 mm
Provided spacing = 150 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 462.21 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 532.61 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 532.61 sqmm/m
Criterion for spacing of Ductile
links:
Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 87.5 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 75 mm
General Data
Column No. : C3
Level : 1.2 m To 4.2 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C24 N/sqmm
Grade Of Steel (Main) = Fy275 N/sqmm
Grade Of Steel (Shear) = Fy230 N/sqmm
Grade Of Steel - Flexural Design = Fy275 N/sqmm
Grade Of Steel - Shear Design = Fy230 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.85
r = 101.04 mm
Kluy /r = 21.87
M1 = -0.5 kNm
M2 = 1 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.93
21.87 < 39.93, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.78
r = 101.04 mm
Klux /r = 20.07
M1 = -27.66 kNm
M2 = 34.86 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
20.07 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Shear Calculation
Along D Along B
(Analysis Forces)
Lu (mm) 2600 2600
Pu Top (kN) 167.99 167.99
Mnt (kNm) 91.44 91.44
Pu Bottom (kN) 181.49 181.49
Mnb (kNm) 92.98 92.98
Vu1 (kN) 70.93 70.93
Shear from Beam Capacity at Joint
Moment Mnt (kNm) MAX((left,Bot + Right,Top), (left,Top +
Right,Bot))
44.93 77.45
Moment Mnb (kNm) MAX((Left,Top + Right,Bot), (Right,Top +
Left,Bot))
38.79 71.28
Lu (mm) 2600 2600
Vu2 (kN) 32.2 57.2
Critical Analysis Load 225 229
Combination
Critical Load [43] : 0.57 (LOAD 9: [47] : 0.57 (LOAD 9:
Combination DL) +(LOAD 4: EQ -X DL) +(LOAD 8: EQ -Z
-E) -E)
Nu (kN) 78.35 52
Mu (kNm) 32.4 34.62
Vu3 (kN) -18.57 20.89
Vu' (kN) Minimum(Vu1, Vu2)
32.2 57.2
Design Shear, Vu (kN) Maximum(Vu', Vu3)
32.2 57.2
λ 1 1
φ 0.75 0.75
Deff (mm) 302 302
ρw (50% of As 0.008 0.008
provided)
Mm (kNm) 21.65 27.48
φVc (kN) 66.75 68.58
Check Vu < φVc Vu < φVc
Link For Shear Design Not Required Not Required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 170.88 kN
Vs
Check <=0.33*Sqrt
(f'c)*B*d
b/2 = 151 mm
600 = 600 mm
Provided spacing = 150 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 462.21 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 532.61 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 532.61 sqmm/m
Criterion for spacing of Ductile
links:
Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 87.5 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 75 mm
General Data
Column No. : C3
Level : 4.2 m To 7.2 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C24 N/sqmm
Grade Of Steel (Main) = Fy275 N/sqmm
Grade Of Steel (Shear) = Fy230 N/sqmm
Grade Of Steel - Flexural Design = Fy275 N/sqmm
Grade Of Steel - Shear Design = Fy230 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2700 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.006
0.006< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.85
r = 101.04 mm
Kluy /r = 22.71
M1 = -14.38 kNm
M2 = 17.62 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.71 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.76
r = 101.04 mm
Klux /r = 20.31
M1 = -0.8 kNm
M2 = 2.98 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.24
20.31 < 37.24, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Shear Calculation
Along D Along B
(Analysis Forces)
Lu (mm) 2700 2700
Pu Top (kN) 37.87 37.87
Mnt (kNm) 75.29 75.29
Pu Bottom (kN) 51.37 51.37
Mnb (kNm) 76.97 76.97
Vu1 (kN) 56.39 56.39
Shear from Beam Capacity at Joint
Moment Mnt (kNm) MAX((left,Bot + Right,Top), (left,Top +
Right,Bot))
24.73 39.91
Moment Mnb (kNm) MAX((Left,Top + Right,Bot), (Right,Top +
Left,Bot))
44.93 77.45
Lu (mm) 2700 2700
Vu2 (kN) 25.8 43.47
Critical Analysis Load 208 210
Combination
Critical Load [26] : 1.53 (LOAD 9: [28] : 1.53 (LOAD 9:
Combination DL) +0.5 (LOAD 10: DL) +0.5 (LOAD 10:
LL) +(LOAD 3: EQ -X LL) +(LOAD 5: EQ +Z
+E) +E)
Nu (kN) 37.87 31.04
Mu (kNm) 17.62 16.73
Vu3 (kN) -10.67 -11.35
Vu' (kN) Minimum(Vu1, Vu2)
25.8 43.47
Design Shear, Vu (kN) Maximum(Vu', Vu3)
25.8 43.47
λ 1 1
φ 0.75 0.75
Deff (mm) 302 302
ρw (50% of As 0.008 0.008
provided)
Mm (kNm) 12.43 12.47
φVc (kN) 68.57 72.93
Check Vu < φVc Vu < φVc
Link For Shear Design Not Required Not Required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Vs <=
0.33*Sqrt (f'c)
Check
*B*d
d/2 = 151 mm
600 = 600 mm
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 170.88 kN
Vs
Check <=0.33*Sqrt
(f'c)*B*d
b/2 = 151 mm
600 = 600 mm
Provided spacing = 175 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 462.21 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 532.61 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 532.61 sqmm/m
Criterion for spacing of Ductile
links:
Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 87.5 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 75 mm
General Data
Column No. : C4
Level : 0 m To 1.2 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C24 N/sqmm
Grade Of Steel (Main) = Fy275 N/sqmm
Grade Of Steel (Shear) = Fy230 N/sqmm
Grade Of Steel - Flexural Design = Fy275 N/sqmm
Grade Of Steel - Shear Design = Fy230 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 800 mm
Clear Floor Height @ luy = 800 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.003
0.003< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.82
r = 101.04 mm
Kluy /r = 6.49
M1 = 3.01 kNm
M2 = -19.12 kNm
Min (40, 34 - 12 x (M1/M2)) = 35.89
6.49 < 35.89, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.79
r = 101.04 mm
Klux /r = 6.26
M1 = 0.19 kNm
M2 = -0.24 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
6.26 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Shear Calculation
Along D Along B
(Analysis Forces)
Lu (mm) 800 800
Pu Top (kN) 211.31 211.31
Mnt (kNm) 96.38 96.38
Pu Bottom (kN) 216.71 216.71
Mnb (kNm) 97 97
Vu1 (kN) 241.73 241.73
Shear from Beam Capacity at Joint
Moment Mnt (kNm) MAX((left,Bot + Right,Top), (left,Top +
Right,Bot))
38.79 71.28
Moment Mnb (kNm) MAX((Left,Top + Right,Bot), (Right,Top +
Left,Bot))
0 0
Lu (mm) 800 800
Vu2 (kN) 48.48 89.1
Critical Analysis Load 224 227
Combination
Critical Load [42] : 0.57 (LOAD 9: [45] : 0.57 (LOAD 9:
Combination DL) +(LOAD 3: EQ -X DL) +(LOAD 6: EQ +Z
+E) -E)
Nu (kN) 9.68 57.48
Mu (kNm) 19.12 19.45
Vu3 (kN) -18.44 -24.73
Vu' (kN) Minimum(Vu1, Vu2)
48.48 89.1
Design Shear, Vu (kN) Maximum(Vu', Vu3)
48.48 89.1
λ 1 1
φ 0.75 0.75
Deff (mm) 302 302
ρw (50% of As 0.008 0.008
provided)
Mm (kNm) 17.79 11.56
φVc (kN) 70.58 86
Check Vu < φVc Vu > φVc
Link For Shear Design Not Required Required
Shear Links Design
Vs (kN) (Vu - φVc) / φVc
- 4.14
Vs Permissible (kN) 0.66 x sqrt(f'c) x b x deff
- 341.76
Vs Permissible Check - Vs < Vs permissible;
Hence, OK
Check for Minimum -
Shear Reinforcement
0.5 x φVc (kN) - 43
Minimum Shear - Vu > 0.5 x φVc;
Reinforcement Check Hence , Minimum
Shear reinforcement
required
Av/s minimum - 532.61
(sqmm/m)
Av/s shear (sqmm/m) - 59.54
Av/s required max (Av/s minimum , Av/s shear)
(sqmm/m)
- 532.61
Link Rebar Number - 10
Diameter of link (mm) - 10
Numbers of legs - 3
provided
Spacing of Link - 150
Provided (mm)
Av/s provided - 1570.8
(sqmm/m )
Av/s provided check - Av/s required < Av/s
provided; Hence, OK
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 4.14 kN
0.33*Sqrt (f'c)*Aeff = 170.88 kN
Vs
Check <=0.33*Sqrt
(f'c)*B*d
b/2 = 151 mm
600 = 600 mm
Provided spacing = 150 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 462.21 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 532.61 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 532.61 sqmm/m
Criterion for spacing of Ductile
links:
Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 87.5 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 75 mm
General Data
Column No. : C4
Level : 1.2 m To 4.2 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C24 N/sqmm
Grade Of Steel (Main) = Fy275 N/sqmm
Grade Of Steel (Shear) = Fy230 N/sqmm
Grade Of Steel - Flexural Design = Fy275 N/sqmm
Grade Of Steel - Shear Design = Fy230 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.85
r = 101.04 mm
Kluy /r = 21.87
M1 = 0.58 kNm
M2 = -0.84 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.87 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.78
r = 101.04 mm
Klux /r = 20.07
M1 = -27.27 kNm
M2 = 34.39 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
20.07 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Shear Calculation
Along D Along B
(Analysis Forces)
Lu (mm) 2600 2600
Pu Top (kN) 161.81 161.81
Mnt (kNm) 90.73 90.73
Pu Bottom (kN) 175.31 175.31
Mnb (kNm) 92.28 92.28
Vu1 (kN) 70.39 70.39
Shear from Beam Capacity at Joint
Moment Mnt (kNm) MAX((left,Bot + Right,Top), (left,Top +
Right,Bot))
44.93 77.45
Moment Mnb (kNm) MAX((Left,Top + Right,Bot), (Right,Top +
Left,Bot))
38.79 71.28
Lu (mm) 2600 2600
Vu2 (kN) 32.2 57.2
Critical Analysis Load 222 228
Combination
Critical Load [40] : 0.57 (LOAD 9: [46] : 0.57 (LOAD 9:
Combination DL) +(LOAD 1: EQ +X DL) +(LOAD 7: EQ -Z
+E) +E)
Nu (kN) 76.23 49.89
Mu (kNm) 32.48 34.14
Vu3 (kN) 18.55 20.6
Vu' (kN) Minimum(Vu1, Vu2)
32.2 57.2
Design Shear, Vu (kN) Maximum(Vu', Vu3)
32.2 57.2
λ 1 1
φ 0.75 0.75
Deff (mm) 302 302
ρw (50% of As 0.008 0.008
provided)
Mm (kNm) 22.02 27.3
φVc (kN) 66.67 68.63
Check Vu < φVc Vu < φVc
Link For Shear Design Not Required Not Required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 170.88 kN
Vs
Check <=0.33*Sqrt
(f'c)*B*d
b/2 = 151 mm
600 = 600 mm
Provided spacing = 150 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 462.21 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 532.61 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 532.61 sqmm/m
Criterion for spacing of Ductile
links:
Min. Longitudinal Bar dia x 6 = 96 mm
B/4 = 87.5 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 75 mm
General Data
Column No. : C4
Level : 4.2 m To 7.2 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C24 N/sqmm
Grade Of Steel (Main) = Fy275 N/sqmm
Grade Of Steel (Shear) = Fy230 N/sqmm
Grade Of Steel - Flexural Design = Fy275 N/sqmm
Grade Of Steel - Shear Design = Fy230 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2700 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.006
0.006< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.85
r = 101.04 mm
Kluy /r = 22.71
M1 = 14.25 kNm
M2 = -17.17 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.71 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.76
r = 101.04 mm
Klux /r = 20.31
M1 = -0.8 kNm
M2 = 2.97 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.21
20.31 < 37.21, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Shear Calculation
Along D Along B
(Analysis Forces)
Lu (mm) 2700 2700
Pu Top (kN) 35.45 35.45
Mnt (kNm) 74.99 74.99
Pu Bottom (kN) 48.95 48.95
Mnb (kNm) 76.67 76.67
Vu1 (kN) 56.17 56.17
Shear from Beam Capacity at Joint
Moment Mnt (kNm) MAX((left,Bot + Right,Top), (left,Top +
Right,Bot))
24.73 39.91
Moment Mnb (kNm) MAX((Left,Top + Right,Bot), (Right,Top +
Left,Bot))
44.93 77.45
Lu (mm) 2700 2700
Vu2 (kN) 25.8 43.47
Critical Analysis Load 207 211
Combination
Critical Load [25] : 1.53 (LOAD 9: [29] : 1.53 (LOAD 9:
Combination DL) +0.5 (LOAD 10: DL) +0.5 (LOAD 10:
LL) +(LOAD 2: EQ +X LL) +(LOAD 6: EQ +Z
-E) -E)
Nu (kN) 35.45 28.6
Mu (kNm) 17.17 16.45
Vu3 (kN) 10.48 -11.18
Vu' (kN) Minimum(Vu1, Vu2)
25.8 43.47
Design Shear, Vu (kN) Maximum(Vu', Vu3)
25.8 43.47
λ 1 1
φ 0.75 0.75
Deff (mm) 302 302
ρw (50% of As 0.008 0.008
provided)
Mm (kNm) 12.31 12.53
φVc (kN) 68.63 72.88
Check Vu < φVc Vu < φVc
Link For Shear Design Not Required Not Required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 170.88 kN
Vs
Check <=0.33*Sqrt
(f'c)*B*d
b/2 = 151 mm
600 = 600 mm
Provided spacing = 175 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 462.21 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 532.61 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 532.61 sqmm/m
General Data
Column No. : C5
Level : 0 m To 1.2 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C24 N/sqmm
Grade Of Steel (Main) = Fy275 N/sqmm
Grade Of Steel (Shear) = Fy230 N/sqmm
Grade Of Steel - Flexural Design = Fy275 N/sqmm
Grade Of Steel - Shear Design = Fy230 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 800 mm
Clear Floor Height @ luy = 800 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.003
0.003< 0.05, Column shall be designed as non-sway frame
(Braced)
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Shear Calculation
Along D Along B
(Analysis Forces)
Lu (mm) 800 800
Pu Top (kN) 199.92 199.92
Mnt (kNm) 81.93 81.93
Pu Bottom (kN) 205.32 205.32
Mnb (kNm) 82.6 82.6
Vu1 (kN) 205.67 205.67
Shear from Beam Capacity at Joint
Moment Mnt (kNm) MAX((left,Bot + Right,Top), (left,Top +
Right,Bot))
38.79 39.12
Moment Mnb (kNm) MAX((Left,Top + Right,Bot), (Right,Top +
Left,Bot))
0 0
Lu (mm) 800 800
Vu2 (kN) 48.48 48.9
Critical Analysis Load 222 229
Combination
Critical Load [40] : 0.57 (LOAD 9: [47] : 0.57 (LOAD 9:
Combination DL) +(LOAD 1: EQ +X DL) +(LOAD 8: EQ -Z
+E) -E)
Nu (kN) -2.39 13.54
Mu (kNm) 3.85 16.59
Vu3 (kN) 21.87 16.69
Vu' (kN) Minimum(Vu1, Vu2)
48.48 48.9
Design Shear, Vu (kN) Maximum(Vu', Vu3)
48.48 48.9
λ 1 1
φ 0.75 0.75
Deff (mm) 302 302
ρw (50% of As 0.006 0.006
provided)
Mm (kNm) 4.17 14.73
φVc (kN) 65.65 70.17
Check Vu < φVc Vu < φVc
Link For Shear Design Not Required Not Required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 170.88 kN
Vs
Check <=0.33*Sqrt
(f'c)*B*d
b/2 = 151 mm
600 = 600 mm
Provided spacing = 175 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 462.21 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 532.61 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 532.61 sqmm/m
Criterion for spacing of Ductile
links:
Min. Longitudinal Bar dia x 6 = 72 mm
B/4 = 87.5 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 50 mm
General Data
Column No. : C5
Level : 1.2 m To 4.2 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C24 N/sqmm
Grade Of Steel (Main) = Fy275 N/sqmm
Grade Of Steel (Shear) = Fy230 N/sqmm
Grade Of Steel - Flexural Design = Fy275 N/sqmm
Grade Of Steel - Shear Design = Fy230 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.85
r = 101.04 mm
Kluy /r = 21.87
M1 = -24.22 kNm
M2 = 36.29 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.87 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.85
r = 101.04 mm
Klux /r = 21.87
M1 = -4.13 kNm
M2 = 4.31 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.87 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 17.03 kN
Mux = 36.29 kNm
Muy = 4.31 kNm
Shear Calculation
Along D Along B
(Analysis Forces)
Lu (mm) 2600 2600
Pu Top (kN) 152.74 152.74
Mnt (kNm) 76.05 76.05
Pu Bottom (kN) 166.24 166.24
Mnb (kNm) 77.74 77.74
Vu1 (kN) 59.15 59.15
Shear from Beam Capacity at Joint
Moment Mnt (kNm) MAX((left,Bot + Right,Top), (left,Top +
Right,Bot))
51.01 39.09
Moment Mnb (kNm) MAX((Left,Top + Right,Bot), (Right,Top +
Left,Bot))
38.79 39.12
Lu (mm) 2600 2600
Vu2 (kN) 34.54 30.08
Critical Analysis Load 209 210
Combination
Critical Load [27] : 1.53 (LOAD 9: [28] : 1.53 (LOAD 9:
Combination DL) +0.5 (LOAD 10: DL) +0.5 (LOAD 10:
LL) +(LOAD 4: EQ -X LL) +(LOAD 5: EQ +Z
-E) +E)
Nu (kN) 166.24 157.97
Mu (kNm) 38.97 33.11
Vu3 (kN) -22.96 -20.38
Vu' (kN) Minimum(Vu1, Vu2)
34.54 30.08
Design Shear, Vu (kN) Maximum(Vu', Vu3)
34.54 30.08
λ 1 1
φ 0.75 0.75
Deff (mm) 302 302
ρw (50% of As 0.006 0.006
provided)
Mm (kNm) 16.15 11.43
φVc (kN) 67.31 68.51
Check Vu < φVc Vu < φVc
Link For Shear Design Not Required Not Required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 170.88 kN
Vs
Check <=0.33*Sqrt
(f'c)*B*d
b/2 = 151 mm
600 = 600 mm
Provided spacing = 175 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 462.21 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 532.61 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 532.61 sqmm/m
Criterion for spacing of Ductile
links:
Min. Longitudinal Bar dia x 6 = 72 mm
B/4 = 87.5 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 50 mm
General Data
Column No. : C5
Level : 4.2 m To 7.2 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C24 N/sqmm
Grade Of Steel (Main) = Fy275 N/sqmm
Grade Of Steel (Shear) = Fy230 N/sqmm
Grade Of Steel - Flexural Design = Fy275 N/sqmm
Grade Of Steel - Shear Design = Fy230 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2700 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.006
0.006< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.85
r = 101.04 mm
Kluy /r = 22.71
M1 = -18.56 kNm
M2 = 23.08 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.71 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.77
r = 101.04 mm
Klux /r = 20.58
M1 = 2.18 kNm
M2 = 8.71 kNm
Min (40, 34 - 12 x (M1/M2)) = 31
20.58 < 31, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 52.19 kN
Mux = 23.08 kNm
Muy = 8.71 kNm
Shear Calculation
Along D Along B
(Analysis Forces)
Lu (mm) 2700 2700
Pu Top (kN) 52.19 52.19
Mnt (kNm) 63.3 63.3
Pu Bottom (kN) 65.69 65.69
Mnb (kNm) 65.08 65.08
Vu1 (kN) 47.55 47.55
Shear from Beam Capacity at Joint
Moment Mnt (kNm) MAX((left,Bot + Right,Top), (left,Top +
Right,Bot))
24.73 49.6
Moment Mnb (kNm) MAX((Left,Top + Right,Bot), (Right,Top +
Left,Bot))
51.01 39.09
Lu (mm) 2700 2700
Vu2 (kN) 28.05 32.85
Critical Analysis Load 209 221
Combination
Critical Load [27] : 1.53 (LOAD 9: [39] : 1.23 (LOAD 9:
Combination DL) +0.5 (LOAD 10: DL) +(LOAD 8: EQ -Z
LL) +(LOAD 4: EQ -X -E)
-E)
Nu (kN) 52.19 28.19
Mu (kNm) 23.08 15.43
Vu3 (kN) -13.89 7.11
Vu' (kN) Minimum(Vu1, Vu2)
28.05 32.85
Design Shear, Vu (kN) Maximum(Vu', Vu3)
28.05 32.85
λ 1 1
φ 0.75 0.75
Deff (mm) 302 302
ρw (50% of As 0.006 0.006
provided)
Mm (kNm) 15.92 11.56
φVc (kN) 66.4 69.01
Check Vu < φVc Vu < φVc
Link For Shear Design Not Required Not Required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 170.88 kN
Vs
Check <=0.33*Sqrt
(f'c)*B*d
b/2 = 151 mm
600 = 600 mm
Provided spacing = 175 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 462.21 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 532.61 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 532.61 sqmm/m
Criterion for spacing of Ductile
links:
Min. Longitudinal Bar dia x 6 = 72 mm
B/4 = 87.5 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 50 mm
General Data
Column No. : C6
Level : 0 m To 1.2 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C24 N/sqmm
Grade Of Steel (Main) = Fy275 N/sqmm
Grade Of Steel (Shear) = Fy230 N/sqmm
Grade Of Steel - Flexural Design = Fy275 N/sqmm
Grade Of Steel - Shear Design = Fy230 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 800 mm
Clear Floor Height @ luy = 800 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.003
0.003< 0.05, Column shall be designed as non-sway frame
(Braced)
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 170.88 kN
Vs
Check <=0.33*Sqrt
(f'c)*B*d
b/2 = 151 mm
600 = 600 mm
Provided spacing = 175 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 462.21 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 532.61 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 532.61 sqmm/m
Criterion for spacing of Ductile
links:
Min. Longitudinal Bar dia x 6 = 72 mm
B/4 = 87.5 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 50 mm
General Data
Column No. : C6
Level : 1.2 m To 4.2 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C24 N/sqmm
Grade Of Steel (Main) = Fy275 N/sqmm
Grade Of Steel (Shear) = Fy230 N/sqmm
Grade Of Steel - Flexural Design = Fy275 N/sqmm
Grade Of Steel - Shear Design = Fy230 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Flexural Design (Analysis Forces)
Analysis Reference No. = 32
Critical Analysis Load Combination : 225
Load Combination = [43] : 0.57 (LOAD 9: DL) +(LOAD 4: EQ -X -E)
Critical Location = Bottom Joint
Put = 10.67 kN
Muxt = 24.3 kNm
Muyt = -4.14 kNm
Vuxt = -2.82 kN
Vuyt = -20.16 kN
Pub = 15.7 kN
Muxb = -36.17 kNm
Muyb = 4.32 kNm
Vuxb = -2.82 kN
Vuyb = -20.16 kN
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.85
r = 101.04 mm
Kluy /r = 21.87
M1 = 24.3 kNm
M2 = -36.17 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.87 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.85
r = 101.04 mm
Klux /r = 21.87
M1 = -4.14 kNm
M2 = 4.32 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.87 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Shear Calculation
Along D Along B
(Analysis Forces)
Lu (mm) 2600 2600
Pu Top (kN) 148.93 148.93
Mnt (kNm) 75.58 75.58
Pu Bottom (kN) 162.43 162.43
Mnb (kNm) 77.26 77.26
Vu1 (kN) 58.78 58.78
Shear from Beam Capacity at Joint
Moment Mnt (kNm) MAX((left,Bot + Right,Top), (left,Top +
Right,Bot))
51.01 39.09
Moment Mnb (kNm) MAX((Left,Top + Right,Bot), (Right,Top +
Left,Bot))
38.79 39.12
Lu (mm) 2600 2600
Vu2 (kN) 34.54 30.08
Critical Analysis Load 206 211
Combination
Critical Load [24] : 1.53 (LOAD 9: [29] : 1.53 (LOAD 9:
Combination DL) +0.5 (LOAD 10: DL) +0.5 (LOAD 10:
LL) +(LOAD 1: EQ +X LL) +(LOAD 6: EQ +Z
+E) -E)
Nu (kN) 162.43 154.43
Mu (kNm) 39.33 32.7
Vu3 (kN) 23 -20.15
Vu' (kN) Minimum(Vu1, Vu2)
34.54 30.08
Design Shear, Vu (kN) Maximum(Vu', Vu3)
34.54 30.08
λ 1 1
φ 0.75 0.75
Deff (mm) 302 302
ρw (50% of As 0.006 0.006
provided)
Mm (kNm) 17.03 11.5
φVc (kN) 67.04 68.47
Check Vu < φVc Vu < φVc
Link For Shear Design Not Required Not Required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 170.88 kN
Vs
Check <=0.33*Sqrt
(f'c)*B*d
b/2 = 151 mm
600 = 600 mm
Provided spacing = 175 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 462.21 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 532.61 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 532.61 sqmm/m
Criterion for spacing of Ductile
links:
Min. Longitudinal Bar dia x 6 = 72 mm
B/4 = 87.5 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 50 mm
General Data
Column No. : C6
Level : 4.2 m To 7.2 m
Frame Type = Lateral
Response Modification Coefficient = 3
Design Code = NSCP C101 - 2015
Grade Of Concrete (f'c) = C24 N/sqmm
Grade Of Steel (Main) = Fy275 N/sqmm
Grade Of Steel (Shear) = Fy230 N/sqmm
Grade Of Steel - Flexural Design = Fy275 N/sqmm
Grade Of Steel - Shear Design = Fy230 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 350 mm
Column D = 350 mm
Clear Cover, Cc = 40 mm
Clear Floor Height @ lux = 2700 mm
Clear Floor Height @ luy = 2700 mm
No Of Floors = 1
No Of Columns In Group = 1
Strength Reduction Factor φ (Shear) = 0.75
Along B
Q = 0.006
0.006< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
k = 0.85
r = 101.04 mm
Kluy /r = 22.71
M1 = 18.86 kNm
M2 = -23.04 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.71 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
k = 0.77
r = 101.04 mm
Klux /r = 20.58
M1 = 2.16 kNm
M2 = 8.77 kNm
Min (40, 34 - 12 x (M1/M2)) = 31.04
20.58 < 31.04, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Final Critical Design Forces
Critical Case - Axial Load & BiAxial Bending
Pu = 50.02 kN
Mux = -23.04 kNm
Muy = 8.77 kNm
Shear Calculation
Along D Along B
(Analysis Forces)
Lu (mm) 2700 2700
Pu Top (kN) 50.02 50.02
Mnt (kNm) 63.01 63.01
Pu Bottom (kN) 63.52 63.52
Mnb (kNm) 64.79 64.79
Vu1 (kN) 47.34 47.34
Shear from Beam Capacity at Joint
Moment Mnt (kNm) MAX((left,Bot + Right,Top), (left,Top +
Right,Bot))
24.73 49.6
Moment Mnb (kNm) MAX((Left,Top + Right,Bot), (Right,Top +
Left,Bot))
51.01 39.09
Lu (mm) 2700 2700
Vu2 (kN) 28.05 32.85
Critical Analysis Load 206 220
Combination
Critical Load [24] : 1.53 (LOAD 9: [38] : 1.23 (LOAD 9:
Combination DL) +0.5 (LOAD 10: DL) +(LOAD 7: EQ -Z
LL) +(LOAD 1: EQ +X +E)
+E)
Nu (kN) 50.02 26.34
Mu (kNm) 23.04 15.21
Vu3 (kN) 13.97 6.98
Vu' (kN) Minimum(Vu1, Vu2)
28.05 32.85
Design Shear, Vu (kN) Maximum(Vu', Vu3)
28.05 32.85
λ 1 1
φ 0.75 0.75
Deff (mm) 302 302
ρw (50% of As 0.006 0.006
provided)
Mm (kNm) 16.18 11.6
φVc (kN) 66.33 68.99
Check Vu < φVc Vu < φVc
Link For Shear Design Not Required Not Required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Along B
Vs = 0 kN
0.33*Sqrt (f'c)*Aeff = 170.88 kN
Vs
Check <=0.33*Sqrt
(f'c)*B*d
b/2 = 151 mm
600 = 600 mm
Provided spacing = 175 mm
Along B
Av/s min-1 = 0.062 x Sqrt(f'c) x D x 1000 / fyt
= 462.21 sqmm/m
Av/s min-2 0.35 x B x 1000 / fyt
= 532.61 sqmm/m
Av/s min = Max ( Av/s min-1, Av/s min-2)
= 532.61 sqmm/m
Criterion for spacing of Ductile
links:
Min. Longitudinal Bar dia x 6 = 72 mm
B/4 = 87.5 mm
So = 150 mm
Max 150 mm = 150 mm
Provided Spacing = 50 mm
Panel Types:
One Way Slab: 1. Simply Supported
2. End Span
3. Span Next to End Span
4. Interior Span
Level: 3m
Slab No. : S1
Ly = 3.35 m Lx = 3.03 m
Live Load = 1.9 kN/sqm Imposed Load = 1 kN/sqm
Thickness = 150 mm Span Type = 2-Way Panel Type = 7
Design Code = NSCP
Grade of Concrete = C21 Grade of Steel = Fy275
C101 - 2015
Panel Types:
One Way Slab: 1. Simply Supported
2. End Span
3. Span Next to End Span
4. Interior Span
Level: 7.2 m
Slab No. : S4
Ly = 3.35 m Lx = 3.03 m
Live Load = 1 kN/sqm Imposed Load = 1 kN/sqm
Thickness = 100 mm Span Type = 2-Way Panel Type = 7
Design Code = NSCP
Grade of Concrete = C21 Grade of Steel = Fy275
C101 - 2015
Slab No. : S6
Ly = 3.35 m Lx = 1.5 m
Live Load = 1 kN/sqm Imposed Load = 1 kN/sqm
Thickness = 100 mm Span Type = 1-Way Panel Type = 1
Design Code = NSCP
Grade of Concrete = C21 Grade of Steel = Fy275
C101 - 2015
NOTES:
1. Density of concrete assumed as 25 kN/cum.
Definitions Of Terms: :
Ratio of flexural stiffness of beam section to flexural
1. αf =
stiffness of slab.
Ratio of torsional stiffness of edge beam section to
2. βt =
flexural stiffness of slab.
3. Φt = Strength reduction factor.
4. As = Area of Tension reinforcement required in 'sqmm'.
5. As,min = Min area of flexural reinforcement in 'sqmm'.
Area of longitudinal reinforcement provided at given
6. AstPrv =
section in 'sqmm'.
Total area of longitudinal reinforcement calculated at a
7. Ast =
given section in 'sqmm'.
8. b = Width of the Slab in 'mm'.
9. B1 to B4 = Width of beams around slab in 'mm'.
10. Cc = Effective Cover to tension reinforcement in 'mm'.
cross-sectional constant to define torsional properties
11. CA and CB =
of slab and beam.
12. deff = Effective depth of slab in 'mm'.
13. D1 to D4 = Depth of beams around slab.
14. Icr = Moment of Inertia of concrete crack section.
Length of clear span in direction that moment are
15. Ln =
being determined in 'mm'.
16. L2 = Length of adjacent span of Ln in 'mm'.
17. lb1 to lb2 = Moment of inertia of beams around slab in 'mm4'.
18. Mcr = Cracking Moment.
19. Mu = Factored Bending Moment at a section in 'kNm'.
20. Ptmin = Minimum percentage steel as per chapter 8.
21. PtPrv = Provided percentage steel.
22. Vc = Nominal shear strength provided by concrete in 'kN'.
23. Vu = Factored Shear Force at a section in 'kN'.
24. Vud = Design Shear Force in 'kN'.
25. y = Neutral axis depth.
Code References :
NSCP C101 - 2015
Slab No. : S1
Level = 3m
Design Code = NSCP C101 - 2015
Grade Of Concrete = C21
Grade Of Steel = Fy275
Clear Cover = 20.000 mm
Long Span, Ly = 3.350 m
Short Span, Lx = 3.030 m
Imposed Load = 1.000 kN/sqm
Live Load, Qk = 1.900 kN/sqm
Slab Thickness = 150.000 mm
Effective Depth Along LX, Deffx = 125.000 mm
Effective Depth Along LY, Deffy = 115.000 mm
Self Weight = 3.750 kN/sqm
Total Load, TL (ultimate) = 8.740 kN/sqm
Span = 2-Way
Load Combination = 1.2 DL + 1.6 LL
Design Moments:
Short Span Positive Moment At Midspan -
M1 = 2.440 kNm
M1 (per m) = M1/Effective
Width
= 2.910 kNm/m
Area Of Reinforcement = 270.000 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 290 C/C
= 271.000 sqmm/m
Short Span Negative Moment At Continuous Support -
M2 = 3.000 kNm
M2/Effective
M2 (per m) =
Width
= 3.580 kNm/m
Area Of Reinforcement = 270.000 sqmm/m
Required (BM)
Additional Area Of
= 135.000 sqmm/m
Reinforcement Required
Reinforcement Provided = #10 @ 300 C/C
= 262.000 sqmm/m
Long Span Positive Moment At Midspan -
M3 = 3.200 kNm
M3/Effective
M3 (per m) =
Width
= 4.230 kNm/m
Area Of Reinforcement = 270.000 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 290 C/C
= 271.000 sqmm/m
Long Span Negative Moment At Continuous Support -
M4 = N.A. kNm
Area Of Reinforcement = N.A. sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 290 C/C
= 271.000 sqmm/m
Distribution Reinforcement @ 0.18% -
Area Of Reinforcement = 270.000 sqmm/m
Required
Reinforcement Provided = #10 @ 290 C/C
= 271.000 sqmm/m
Shear Check :
Along Short Span
Vsx (TL(ultimate) x Lx / 4) = 6.620 kN
Nominal Shear, ΦVc = 72.480 kN
> 6.620 Slab Is Safe In Shear
Along Long Span
Vsy (TL(ultimate) x Lx / 2 x = 7.250 kN
(1 - (Lx / (2 x Ly))))
Nominal Shear, ΦVc = 66.680 kN
> 7.250 Slab Is Safe In Shear
Slab No. : S2
Level = 3m
Design Code = NSCP C101 - 2015
Grade Of Concrete = C21
Grade Of Steel = Fy275
Clear Cover = 20.000 mm
Long Span, Ly = 3.350 m
Short Span, Lx = 3.030 m
Imposed Load = 1.000 kN/sqm
Live Load, Qk = 1.900 kN/sqm
Slab Thickness = 150.000 mm
Effective Depth Along LX, Deffx = 125.000 mm
Effective Depth Along LY, Deffy = 115.000 mm
Self Weight = 3.750 kN/sqm
Total Load, TL (ultimate) = 8.740 kN/sqm
Span = 2-Way
Load Combination = 1.2 DL + 1.6 LL
Design Moments:
Short Span Positive Moment At Midspan -
M1 = 2.440 kNm
M1 (per m) = M1/Effective
Width
= 2.910 kNm/m
Area Of Reinforcement = 270.000 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 290 C/C
= 271.000 sqmm/m
Short Span Negative Moment At Continuous Support -
M2 = 3.000 kNm
M2/Effective
M2 (per m) =
Width
= 3.580 kNm/m
Area Of Reinforcement = 270.000 sqmm/m
Required (BM)
Additional Area Of
= 135.000 sqmm/m
Reinforcement Required
Reinforcement Provided = #10 @ 300 C/C
= 262.000 sqmm/m
Long Span Positive Moment At Midspan -
M3 = 3.200 kNm
M3/Effective
M3 (per m) =
Width
= 4.230 kNm/m
Area Of Reinforcement = 270.000 sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 290 C/C
= 271.000 sqmm/m
Long Span Negative Moment At Continuous Support -
M4 = N.A. kNm
Area Of Reinforcement = N.A. sqmm/m
Required (BM)
Reinforcement Provided = #10 @ 290 C/C
= 271.000 sqmm/m
Distribution Reinforcement @ 0.18% -
Area Of Reinforcement = 270.000 sqmm/m
Required
Reinforcement Provided = #10 @ 290 C/C
= 271.000 sqmm/m
Shear Check :
Along Short Span
Vsx (TL(ultimate) x Lx / 4) = 6.620 kN
Nominal Shear, ΦVc = 72.480 kN
> 6.620 Slab Is Safe In Shear
Along Long Span
Vsy (TL(ultimate) x Lx / 2 x = 7.250 kN
(1 - (Lx / (2 x Ly))))
Nominal Shear, ΦVc = 66.680 kN
> 7.250 Slab Is Safe In Shear
SLAB DESIGN CALCULATIONS
Project Name : Proposed Two Storey Transformer Room
Client Name : Subic Grain
Engineer Name : MPB
Design File : ...\Users\Engr.Marcley Bataoil\Desktop\Project in Subic
Grain\PROPOSED TWO STROREY ELECTRICAL
ROOM\DESIGN\Design Revise\Revise v2\With ftb and cantilever
slab\Two Storey Transformer Room-Slab-1-7.2 m.rcdx
Analysis File : C:\Users\Engr.Marcley Bataoil\Desktop\Project in Subic
Grain\PROPOSED TWO STROREY ELECTRICAL
ROOM\DESIGN\Design Revise\Revise v2\With ftb and cantilever
slab\Two Storey Transformer Room.STD
Analysis Last Modified : 12/1/2023 10:52:26 AM
NOTES:
1. Density of concrete assumed as 25 kN/cum.
Definitions Of Terms: :
Ratio of flexural stiffness of beam section to flexural
1. αf =
stiffness of slab.
Ratio of torsional stiffness of edge beam section to
2. βt =
flexural stiffness of slab.
3. Φt = Strength reduction factor.
4. As = Area of Tension reinforcement required in 'sqmm'.
5. As,min = Min area of flexural reinforcement in 'sqmm'.
Area of longitudinal reinforcement provided at given
6. AstPrv =
section in 'sqmm'.
Total area of longitudinal reinforcement calculated at a
7. Ast =
given section in 'sqmm'.
8. b = Width of the Slab in 'mm'.
9. B1 to B4 = Width of beams around slab in 'mm'.
10. Cc = Effective Cover to tension reinforcement in 'mm'.
cross-sectional constant to define torsional properties
11. CA and CB =
of slab and beam.
12. deff = Effective depth of slab in 'mm'.
13. D1 to D4 = Depth of beams around slab.
14. Icr = Moment of Inertia of concrete crack section.
Length of clear span in direction that moment are
15. Ln =
being determined in 'mm'.
16. L2 = Length of adjacent span of Ln in 'mm'.
17. lb1 to lb2 = Moment of inertia of beams around slab in 'mm4'.
18. Mcr = Cracking Moment.
19. Mu = Factored Bending Moment at a section in 'kNm'.
20. Ptmin = Minimum percentage steel as per chapter 8.
21. PtPrv = Provided percentage steel.
22. Vc = Nominal shear strength provided by concrete in 'kN'.
23. Vu = Factored Shear Force at a section in 'kN'.
24. Vud = Design Shear Force in 'kN'.
25. y = Neutral axis depth.
Code References :
NSCP C101 - 2015
Slab No. : S4
Level = 7.2 m
Design Code = NSCP C101 - 2015
Grade Of Concrete = C21
Grade Of Steel = Fy275
Clear Cover = 20.000 mm
Long Span, Ly = 3.350 m
Short Span, Lx = 3.030 m
Imposed Load = 1.000 kN/sqm
Live Load, Qk = 1.000 kN/sqm
Slab Thickness = 100.000 mm
Effective Depth Along LX, Deffx = 75.000 mm
Effective Depth Along LY, Deffy = 65.000 mm
Self Weight = 2.500 kN/sqm
Total Load, TL (ultimate) = 5.800 kN/sqm
Span = 2-Way
Load Combination = 1.2 DL + 1.6 LL
Design Moments:
Short Span Positive Moment At Midspan -
M1 = 1.620 kNm
M1 (per m) = M1/Effective
Width
= 1.930 kNm/m
Area Of Reinforcement = 180.000 sqmm/m
Required (BM)
Reinforcement Provided = ⌀10mm @ 200 C/C
= 393.000 sqmm/m
Short Span Negative Moment At Continuous Support -
M2 = 1.990 kNm
M2/Effective
M2 (per m) =
Width
= 2.370 kNm/m
Area Of Reinforcement = 180.000 sqmm/m
Required (BM)
Additional Area Of
= 90.000 sqmm/m
Reinforcement Required
Reinforcement Provided = ⌀10mm @ 200 C/C
= 393.000 sqmm/m
Long Span Positive Moment At Midspan -
M3 = 2.120 kNm
M3/Effective
M3 (per m) =
Width
= 2.800 kNm/m
Area Of Reinforcement = 180.000 sqmm/m
Required (BM)
Reinforcement Provided = ⌀10mm @ 200 C/C
= 393.000 sqmm/m
Long Span Negative Moment At Continuous Support -
M4 = N.A. kNm
Area Of Reinforcement = N.A. sqmm/m
Required (BM)
Reinforcement Provided = ⌀10mm @ 300 C/C
= 262.000 sqmm/m
Distribution Reinforcement @ 0.18% -
Area Of Reinforcement = 180.000 sqmm/m
Required
Reinforcement Provided = ⌀10mm @ 300 C/C
= 262.000 sqmm/m
Shear Check :
Along Short Span
Vsx (TL(ultimate) x Lx / 4) = 4.390 kN
Nominal Shear, ΦVc = 43.490 kN
> 4.390 Slab Is Safe In Shear
Along Long Span
Vsy (TL(ultimate) x Lx / 2 x = 4.810 kN
(1 - (Lx / (2 x Ly))))
Nominal Shear, ΦVc = 37.690 kN
> 4.810 Slab Is Safe In Shear
Slab No. : S5
Level = 7.2 m
Design Code = NSCP C101 - 2015
Grade Of Concrete = C21
Grade Of Steel = Fy275
Clear Cover = 20.000 mm
Long Span, Ly = 3.350 m
Short Span, Lx = 3.030 m
Imposed Load = 1.000 kN/sqm
Live Load, Qk = 1.000 kN/sqm
Slab Thickness = 100.000 mm
Effective Depth Along LX, Deffx = 75.000 mm
Effective Depth Along LY, Deffy = 65.000 mm
Self Weight = 2.500 kN/sqm
Total Load, TL (ultimate) = 5.800 kN/sqm
Span = 2-Way
Load Combination = 1.2 DL + 1.6 LL
Design Moments:
Short Span Positive Moment At Midspan -
M1 = 0.990 kNm
M1 (per m) = M1/Effective
Width
= 1.190 kNm/m
Area Of Reinforcement = 180.000 sqmm/m
Required (BM)
Reinforcement Provided = ⌀10mm @ 200 C/C
= 393.000 sqmm/m
Short Span Negative Moment At Continuous Support -
M2 = 1.850 kNm
M2/Effective
M2 (per m) =
Width
= 2.200 kNm/m
Area Of Reinforcement = 180.000 sqmm/m
Required (BM)
Additional Area Of
= 90.000 sqmm/m
Reinforcement Required
Reinforcement Provided = ⌀10mm @ 200 C/C
= 393.000 sqmm/m
Long Span Positive Moment At Midspan -
M3 = 2.120 kNm
M3/Effective
M3 (per m) =
Width
= 2.800 kNm/m
Area Of Reinforcement = 180.000 sqmm/m
Required (BM)
Reinforcement Provided = ⌀10mm @ 200 C/C
= 393.000 sqmm/m
Long Span Negative Moment At Continuous Support -
M4 = N.A. kNm
Area Of Reinforcement = N.A. sqmm/m
Required (BM)
Reinforcement Provided = ⌀10mm @ 300 C/C
= 262.000 sqmm/m
Distribution Reinforcement @ 0.18% -
Area Of Reinforcement = 180.000 sqmm/m
Required
Reinforcement Provided = ⌀10mm @ 300 C/C
= 262.000 sqmm/m
Shear Check :
Along Short Span
Vsx (TL(ultimate) x Lx / 4) = 4.390 kN
Nominal Shear, ΦVc = 43.490 kN
> 4.390 Slab Is Safe In Shear
Along Long Span
Vsy (TL(ultimate) x Lx / 2 x = 4.810 kN
(1 - (Lx / (2 x Ly))))
Nominal Shear, ΦVc = 37.690 kN
> 4.810 Slab Is Safe In Shear
Slab No. : S6
Level = 7.2 m
Design Code = NSCP C101 - 2015
Grade Of Concrete = C21
Grade Of Steel = Fy275
Clear Cover = 20.000 mm
Long Span, Ly = 3.350 m
Short Span, Lx = 1.500 m
Imposed Load, Qk = 1.000 kN/sqm
Live Load = 1.000 kN/sqm
Slab Thickness = 100.000 mm
Effective Depth Along LX, Deffx = 75.000 mm
Self Weight = 2.500 kN/sqm
Total Load, TL(ultimate) = 5.800 kN/sqm
Span = 1-Way
End Conditions = Simply Supported
Load Combination = 1.2 DL + 1.6 LL
Design Moments:
Short Span Positive Moment at Mid Span -
Moment Coefficient, M1 = 0.1250
Mu (M1 x TL(ultimate) x Lx x = 1.630 kNm
Lx)
Area Of Reinforcement = 180.000 sqmm/m
Required (BM)
Reinforcement Provided = ⌀10mm @ 200 C/C
= 393.000 sqmm/m
All Other Sections provide Minimum Steel @ 0.18% -
Area Of Reinforcement = 180.000 sqmm/m
Required
Reinforcement Provided = ⌀10mm @ 300 C/C
= 262.000 sqmm/m
Shear Check :
Shear Coefficient, SF1 = 0.500
Vsx (SF1 x TL(ultimate) x Lx) = 4.350 kN
Nominal Shear, ΦVc = 43.490 kN
> 4.350 Slab Is Safe In Shear