CPS SCH275KTL DO US 800 User Manual Rev 1.2 815 - 759 - 792 Models 1

Download as pdf or txt
Download as pdf or txt
You are on page 1of 98

USER MANUAL

SCH275KTL-DO/US-800 Grid-Tied PV Inverter


(1.0101.0815/1.0101.0759/1.0101.0792 Models)

CHINT POWER SYSTEMS AMERICA CO., LTD.


Rev 1.2 June 2023
Table of Contents

Table of Contents
0 Preface .......................................................................................... 4
1 IMPORTANT SAFETY INSTRUCTIONS ....................................... 5
Warnings and Symbols in this Document............................................................ 5
Markings on the Product ..................................................................................... 6
Safety Instructions of Operating the PV Inverter ................................................. 8
2 Product Introduction .................................................................. 11
Inverter for Grid-tied PV Systems ..................................................................... 11
Product Appearance and Dimensions ............................................................... 11
Product Features .............................................................................................. 12
Schematic Diagram and Circuit Design ............................................................ 14
Product Protection Functions ............................................................................ 15
Smart Inverter Functions and Default Activation ............................................... 15
Anti-islanding Detection .................................................................................... 15
DC Ground Fault Protection .............................................................................. 16
Surge Suppression ........................................................................................... 16
3 Mechanical Installation .............................................................. 17
Unpacking for Inspection .................................................................................. 17
Pre-Installation Checklist .................................................................................. 18
Installation Requirements ................................................................................. 21
3.1.1 Installation Methods ......................................................................... 21
3.1.2 Installation Environment................................................................... 21
3.1.3 Space Requirements ....................................................................... 22
Installation Procedures ..................................................................................... 23
3.1.4 Install the Inverter ............................................................................ 23
4 Electrical Connection ................................................................ 26
Cable Specifications ......................................................................................... 26
Tools Required and Torque Values ................................................................... 26
Connect Interfaces and Connection Points ....................................................... 27
4.1.1 Connection Interfaces ...................................................................... 27
4.1.2 Internal Connection Points ............................................................... 28
Electrical Cable Connection .............................................................................. 29
4.1.3 Grounding ........................................................................................ 30
4.1.4 AC Wiring......................................................................................... 32
4.1.5 DC Wiring ........................................................................................ 34
Communication Cable Connection.................................................................... 38
4.1.6 Communication Board ..................................................................... 38
4.1.7 Communication Connection ............................................................. 39
Install the LINKIT Module .................................................................................. 42
Cable Connection Notices for Joints and Seals ................................................ 43

2 / 98
Table of Contents

5 Commissioning .......................................................................... 45
Pre-commissioning Checks............................................................................... 45
5.1.1 Mechanical Installation..................................................................... 45
5.1.2 Cable Connections .......................................................................... 45
5.1.3 Electrical Check ............................................................................... 45
Commissioning Steps ....................................................................................... 46
6 APP Interface and Setting ......................................................... 47
APP Download .................................................................................................. 47
APP Setting....................................................................................................... 47
Structure Tree of App Interface ......................................................................... 51
Main Menu ........................................................................................................ 51
6.1.1 Chart .............................................................................................. 53
6.1.2 Setting.............................................................................................. 53
6.1.3 Event .............................................................................................. 76
6.1.4 More .............................................................................................. 78
7 Troubleshooting ......................................................................... 79
LED Indicator Troubleshooting .......................................................................... 79
Common Fault and Troubleshooting ................................................................. 80
8 Maintenance ............................................................................... 87
Check Electrical Connections ........................................................................... 87
Clean the Air Vent Filter .................................................................................... 87
Replace the Cooling Fans ................................................................................. 87
Replace the Inverter .......................................................................................... 89
9 Technical Data ............................................................................ 90
Datasheet ......................................................................................................... 90
Measurement Tolerance.................................................................................... 95
10 Limited Warranty ........................................................................ 96
11 Recycling .................................................................................... 97

3 / 98
Preface

0 Preface
Thank you for choosing a CPS Grid-tied PV Inverter (hereinafter referred to as “PV
Inverter”) developed by CHINT POWER SYSTEMS AMERICA CO., LTD (hereinafter
referred to as "CPS").
This PV Inverter is a high performance and highly reliable product specially designed
for the North American Solar market.

IMPORTANT!
Please read this manual carefully and make sure that you have
understood all the contents thoroughly before you start any
operation.

Main Contents
This Installation and Operation manual contains important information, safety
guidelines, detailed planning and setup information for installation, as well as
information about configuration, operation and troubleshooting. Be sure to read this
manual carefully before using.

Target Readers
Plant owner
Project Engineer
Installation engineer
Maintenance engineer
Installation, commissioning, troubleshooting, and maintenance of the inverter must
be done only by qualified personnel. If you encounter any problems during installation
or operation of this unit, please check the user manual carefully before contacting
CPS Customer Service.
Manual Management
Please keep this user manual on hand for quick reference.
Copyrights
CPS reserves all rights in this manual. Any reproduction, disclosure or copy in whole
or in part is forbidden without prior written authorization. CPS doesn’t accept any
responsibility whatsoever for potential errors or possible lack of information in this
document.
Version
This manual is subject to change or modification without prior notice. The latest
version of this manual can be acquired via the website at:
www.chintpowersystems.com.
4 / 98
IMPORTANT SAFETY INSTRUCTIONS

1 IMPORTANT SAFETY INSTRUCTIONS


(SAVE THESE INSTRUCTIONS)
Please read this user manual carefully before the installation and operation of
this PV Inverter. CPS reserves the right to refuse warranty claims for
equipment damage if users fail to install the equipment according to the
instructions in this manual.
Failure to follow these instructions and other relevant safety procedures may
result in voiding of the warranty and/or damage to the inverter or other
property.
Warnings and Symbols in this Document
Symbols Meanings
DANGER!
DANGER indicates a hazardous situation with high level of risk which,
if not avoided, will result in death or serious injury.
DANGER!
DANGER indique une situation dangereuse avec un niveau de risque
élevé qui, si elle n'est pas évitée, entraînera la mort ou des blessures
graves.
WARNING!
WARNING indicates a hazardous situation with medium level of risk
which, if not avoided, could result in death or serious injury.
ATTENTION!
AVERTISSEMENT indique une situation dangereuse avec un niveau
de risque moyen qui, si elle n'est pas évitée, pourrait entraîner la mort
ou des blessures graves.
CAUTION!
CAUTION indicates a hazardous situation with low level of risk which,
if not avoided, could result in minor or moderate injury.
AVERTIR!
ATTENTION indique une situation dangereuse avec un faible niveau
de risque qui, si elle n'est pas évitée, pourrait entraîner des blessures
mineures ou modérées.
NOTICE!
NOTICE indicates a hazardous situation which, if not avoided, could
result in equipment working abnormally or property loss.
AVIS!

5 / 98
IMPORTANT SAFETY INSTRUCTIONS
indique une situation dangereuse qui, si elle n'est pas évitée, pourrait
entraîner un fonctionnement anormal de l'équipement ou la perte de
biens.
IMPORTANT!
INSTRUCTION indicates important supplementary information or
provides skills or tips that can be used to help you solve a problem or
save you time.
IMPORTANT!
indique des informations supplémentaires importantes ou fournit des
compétences ou des conseils qui peuvent être utilisés pour vous aider
à résoudre un problème ou vous faire gagner du temps.
Table 1-1 Warnings and Symbols in this Document
Markings on the Product
Symbols Meanings
WARNING:
Risk of Electric Shock.
ATTENTION:
Risque de choc electrique.
CAUTION:
Risk of electric shock from energy stored in capacitor.
Do not remove cover until 5 minutes after disconnecting all
sources of supply.
ATTENTION:
Risque de choc électrique à partir d´énergie stockée dans les
condensateurs.
Retirer le couvercle du boîtier au moins 5 minutes après avoir
débranché toutes les sources d´approvisionnement.
CAUTION:
Hot surfaces.
To reduce the risk of burns. Do not touch.
ATTENTION:
Surface chaude.
Pour réduire le risqué de brûlures ne pas toucher.
For more details please see the user manual.

Pour plus de détails, veuillez consulter le manuel d'utilisation.

6 / 98
IMPORTANT SAFETY INSTRUCTIONS
WARNING:
For continued protection against risk of fire, replace only with
same type and ratings of fuse. Refer to instruction manual for
details.
ATTENTION:
Pour continuer d'assurer la protection contre les risques
d'incendie, il faut remplacer les fusibles de même type et
courant.
Reportez-vous au manuel d'instructions pour plus de détails.
EARTH GROUND!
This symbol marks the location of a grounding terminal, which
must be securely connected to the earth through the PE
(protective earthing) cable to ensure operational safety.
TERRE TERRE !
Ce symbole marque l'emplacement d'une borne de mise à la
terre, qui doit être solidement connectée à la terre via le câble
PE (mise à la terre de protection) pour assurer la sécurité de
fonctionnement.
RoHS SYMBOL
In accordance with 2011/65/EU regulations, the inverter
imposes restrictions on the use of specific hazardous
substances in electrical and electronic equipment.
SYMBOLE RoHS
Conformément à la réglementation 2011/65/UE, l'onduleur
impose des restrictions sur l'utilisation de substances
dangereuses spécifiques dans les équipements électriques et
électroniques.
TUV Certification
This inverter has passed TUV Certification.
Certification TUV
Cet onduleur a passé la certification TUV.
Phase information of the inverter.

Information de phase de l'onduleur.


Table 1-2 Markings on the Product

7 / 98
IMPORTANT SAFETY INSTRUCTIONS

Safety Instructions of Operating the PV Inverter

DANGER!
Disconnect the inverter from PV modules and the AC grid before
maintaining and operating the equipment. Make sure hazardous high
voltage and energy inside the equipment has been discharged.
Do not operate or maintain the inverter until at least 5 minutes after
disconnecting all sources from DC and AC sides.
The DC conductors of this PV system are normally ungrounded but will
become intermittently grounded without indication when the inverter
measures the PV array isolation.
WARNING!
All the installation and wiring connections should be performed only by
qualified technical personnel. Disconnect the inverter from PV modules
and the AC grid before maintaining and operating the equipment.
Risk of electric shock and fire. Use only with PV modules in
conformance with the maximum system voltage.
Electric shock Hazard. The DC conductors of this photovoltaic system
are normally ungrounded but will become intermittently grounded
without indication when the inverter measures the PV array isolation.
Shock Hazard. The inverter is energized from both AC and DC
sources. Disconnect all sources before servicing.

CAUTION!
The total weight of the inverter is approx.119kg (262.4pounds). Please
ensure the mounting bracket is properly installed before hanging the
inverter and wire-box on the bracket. It is recommended to have at least
3 people mount the inverter due to the weight of the equipment.
This AFCI device automatically resets and may only be used when
allowed by NFPA 70 and CSA C22.1.
NOTICE!
This inverter is designed to connect AC power only to the public grid.
Do not connect the AC output of this equipment directly to any private
AC power equipment. The inverters are to be installed with floating or
ungrounded PV arrays only.

8 / 98
IMPORTANT SAFETY INSTRUCTIONS
IMPORTANT!
Please check with your local electricity supply company before
selecting a Grid Code. If the inverter is operated with an incorrect grid
standard, the electric utility supply company may cancel the
interconnection agreement.
Placing the inverter into operation before the overall system complies
with the national rules and safety regulations of the application is not
permitted.
WARNING!

WARNING: The DC Switch is rated to break loads under normal operating


conditions. However, a DC short circuit could be hazardous, and the
following procedures should be followed before turning OFF the DC
Switch under fault conditions.

If there is a fault and it is safe to access the inverter:


1. Read/record the fault code(s) displayed on the APP interface.
2. Turn OFF the inverter via the APP or Remote access.
3. Turn OFF the AC feed breaker or AC fuse switch disconnect.
4. If possible, read the DC MPPT currents displayed on the APP interface:
a. If the MPPT current is lower than 20A or the irradiation is obviously
low, turn OFF the DC switch.
b. If it is safe to open the front cover, proceed with troubleshooting
procedures. Make sure appropriate safety precautions and PPE
are used.
5. If it is not possible to read the DC MPPT currents through the APP interface,
and no fire, smoke or voltage (AC or DC) to ground is present in the
enclosure:
a. Follow general safety practices including PPE to open the wire-
compartment.
b. Measure the DC current on each string. If zero, open the fuse

9 / 98
IMPORTANT SAFETY INSTRUCTIONS
holder (when applicable) for each string reading approximately
zero amps.
c. If the DC current is higher than 0.25A, do not open the fuse holder
(when applicable).
d. When all possible fuses are open, measure each MPPT current. If
it is lower than 20A, turn OFF the DC switch.
e. If turning OFF the DC switch causes smoke, then (if safe) turn the
DC switch back ON and wait until low irradiation ~30min prior to
sunset to continue troubleshooting.

If there is a fault and it is unsafe to access the inverter:


1. Notify someone else. Initiate emergency mitigation plan if necessary. If
smoke or fire exists, procure a fire extinguisher.
2. If a fire has escaped the inverter enclosure – notify 911 immediately!
3. Turn OFF the AC feed breaker as soon as possible/safe.
4. If safe but conditions are deteriorating, consider:
a. Using the fire extinguisher.
b. Cutting the string conductors – one cable at a time with insulated cutters
(while wearing appropriate PPE).
5. Monitor conditions until low irradiation ~30min prior to sunset. If safe, turn
OFF DC switches on the inverter and AC switches/disconnect external to
the inverter and proceed with normal troubleshooting procedures, refer to
chapter 7 Troubleshooting.

10 / 98
General Introduction

2 Product Introduction
Inverter for Grid-tied PV Systems
CPS 3-Phase String Inverters SCH275KTL-DO/US-800 series are designed for use
with an UNGROUNDED PV array in Commercial and Utility scale PV grid-tied
systems. The system is generally made up of PV modules, PV inverter and AC power
distribution equipment, as shown in Figure 2-1. The inverter converts the available
DC energy from the PV modules to AC power by synchronizing the output current to
the same frequency and phase as the AC grid. All or part of the AC power is supplied
to local loads, and the surplus power is exported to the electric utility grid.

AC power
distribution
Bidirectional
equipment electric meter

Figure 2-1 Grid-tied PV system

Product Appearance and Dimensions

Figure 2-2 Product appearance

11 / 98
General Introduction

Figure 2-3 Product dimensions

IMPORTANT!
SCH275KTL-DO/US-800 inverter has 36 input (fused) and 24 input
(unfused) versions. Both of these versions have similar appearance, similar
dimensions and their mounting procedures are also the same. However,
their DC connection methods and communication methods are different,
hence will be introduced separately in the following contexts.

Product Features

High conversion efficiency: Advanced 3-level conversion technology with


Space-Vector PWM; Max. efficiency: 99%; CEC efficiency: 98.5%.
Grid adaptability: Selectable grid standards: IEEE 1547-2018, CA Rule 21,
ISO-NE, and HECO; Reactive power; PF value: ±0.8, and optional local or
remote Active Power Curtailment.
Flexible communication: Supports standard CPS Modbus RS485, SunSpec
Modbus, Ethernet TCP/IP, and AC-PLC communications to ensure compatibility
with 3rd party monitoring and control systems. The FlexOM gateway card
enables further command/control as well as remote firmware upgrades.
(FlexOM gateway card is an optional accessory. Refer to FlexOM gateway card
manual for further detailed information.)
Wide DC input voltage range: Operating DC Input Voltage Range: 500-
1450Vdc; Max DC input voltage: 1500Vdc.
Long Service Life: Uses thin-film and electrolytic capacitors to extend inverter's
service life.

12 / 98
General Introduction
High protection degree: NEMA Type 4X enclosure meets the demanding
needs of both indoor and outdoor use.
Intelligent Integration: Integrated load break rated DC disconnect switches;
DC switches can be locked out in the OFF position to prevent operation. Up to
36 fused string inputs or 24 unfused inputs eliminate the need for external
combiner boxes, simplifying installation.

13 / 98
General Introduction

Schematic Diagram and Circuit Design

The electrical schematic diagrams of inverter are as shown in Fig. 2-4.


BUS
DC Switch
PV Input MPPT1 DC/AC
PV1+
PV2+
LC Filter
PV1-
PV2- AC Relay AC Output

MPPT2 L1
PV3+
PV4+
PV3- AC L2
PV4- DC RCD EMI
IMD
EMI L3

...
...

...

MPPT12
PV23+
PV24+ AC SPD
PV23-
PV24- PE

PV Sense DC SPD

Figure 2-4a Schematic Diagram of the 24 Input Inverter Model

PV Input BUS
DC Switch
MPPT1 DC/AC
PV1+
PV2+
PV3+ LC Filter
PV1- AC
PV2- AC Relay
PV3- Output
MPPT2 L1
PV4+
PV5+
PV6+
PV4- AC L2
PV5- DC EMI
PV6-
EMI
L3
...

...

...

MPPT12
PV34+
PV35+
PV36+ AC SPD
PV34-
PV35- PE
PV36-

DC SPD

Figure 2-4b Schematic Diagram of the 36 Input Inverter Model

14 / 98
General Introduction

Product Protection Functions


AC and DC short circuit protection
AC output voltage and frequency monitoring
Leakage current to ground monitoring
DC Input and AC output over-current protection
DC input insulation ground fault monitoring
DC injection of AC output
Anti-islanding protection with bi-directional frequency perturbation
DC Input and AC output over-voltage protection
External environmental temperature monitoring
IGBT power module temperature monitoring

Smart Inverter Functions and Default Activation


The CPS SCH275KTL-DO/US-800 3-Phase String Inverters employ Smart Inverter
(Grid Support) functions in compliance with UL 1741-SA8-SA18 and UL1741-SB
standards. The default activation status is indicated below.

Smart Inverter Function IEEE1547-2018 Rule 21 ISO-NE


Anti-islanding Enabled Enabled Enabled
Low/High Voltage Ride-through Enabled Enabled Enabled
Low/High Frequency Ride-through Enabled Enabled Enabled
Dynamic Volt/VAR Operation Enabled Enabled Enabled
Ramp Rate Enabled Enabled Enabled
Fixed Power Factor Disabled Disabled Disabled
Reconnect by “Soft-Start” Enabled Enabled Enabled
Frequency-Watt Enabled Enabled Enabled
Volt/Watt Enabled Enabled Enabled
Table 2-1 Smart inverter functions and default activation

Anti-islanding Detection
The inverter includes Anti-Islanding detection as required by UL1741/IEEE1547. The
inverter will continuously make bi-directional perturbations to the frequency of the
output current by injecting a small amount of reactive power in order to detect a
possible islanding condition. If the grid is stable, these small perturbations will have
negligible effects on the system voltage frequency. However, in an islanded condition
the changes in reactive power will force the frequency of the system voltage to deviate

15 / 98
General Introduction
significantly, which will trigger the inverter to cease operation and disconnect from the
grid.

DC Ground Fault Protection


The inverters include residual current detection GFCI as part of the DC ground fault
detection method required by UL 1741. If there is a ground fault in the PV array, the
ground fault detection circuitry will detect leakage current, trigger an alarm, and the
inverter will cease operation. See Chapter 6 for further information regarding GFCI
Static and Dynamic trip thresholds and operation.

Surge Suppression
Standard Waveform Peak Values
Surge Category Ring Wave Combination Wave
B 6kV/0.5kA 6kV/3kA
Table 2-2 Standard Waveform Peak Values
Notes:
• “Standard 0.5μs - 100 kHz Ring Wave”
• “Standard1.2/50μs - 8/20μs Combination Wave”

16 / 98
Mechanical Installation

3 Mechanical Installation
Unpacking for Inspection
All the delivery items are shipped in one package, which includes the inverter,
mounting bracket, four PE accessory bags and one ziploc bag.
Before performing installation, check the product for any obvious damages or if the
items on the delivery list are complete. Contact your supplier if any problem is found.
The delivery list is as below:

Figure 3-1 Delivery list items

No. Item QTY Note


1 Inverter 1
1 Bracket upon which the PV inverter is hung
2 Mounting bracket
and mounted
3 Accessory bag 1 Includes accessories A-D
4 Accessory bag 1 Includes accessories E-K
5 Accessory bag 1 Includes accessories I-N
6 Accessory bag 1 Includes accessory O
7 Quick Guide 1 Quick Guide
M10x50 Hex.
A 6 For mounting bracket
combination bolt

17 / 98
Mechanical Installation
M6x90 Hex.comb. For fastening the inverter onto the
B 2
bolt mounting bracket
C M6x16 Comb. bolt 2 For external ground connection
D M10 Lifting eyebolt 2 For lifting inverter
E M10 nut 6 For mounting bracket
F M10 flat gasket 6 For mounting bracket
G M10 spring washer 6 For mounting bracket
H M12 nut 6 For AC terminal block
I M12 flat gasket 6 For AC terminal block
J M12 spring washer 6 For AC terminal block
K M12 big flat gasket 6 For AC terminal
M6x18 bolt with
L 1 Spare for front cover
plastic flat washer
M Handle 2 For lifting the inverter
N 6-pin connector plug 1 For RS485 communication
For mobile app interface via CPS Connect
O LINKIT 1
Pro app
Table 3-1 Accessory list

IMPORTANT!
Additional accessories for the CPS SCH275KTL-DO/US-800 inverters are
available and can be purchased separately.

Pre-Installation Checklist
Check that the product environmental specifications (protection degree,
operating temperature range, humidity and altitude, etc.) meet the requirements
of the specific project location.
Make sure that the power grid voltage is within the normal range of the Grid
Code chosen.
Ensure that you have been authorized by the local electricity supply authority to
connect to the grid.
Installation personnel must be qualified electricians or those who have received
professional training.
Wear and use proper PPE (personal protective equipment) during installation.
Sufficient space must be provided to allow the inverter cooling system to operate
normally.
Install the inverter away from flammable and explosive substances.

18 / 98
Mechanical Installation
Make sure the installation condition doesn’t exceed the temperature limits
specified for the inverter, to prevent undesirable power loss.
Do not install the inverter near an electromagnetic source which can
compromise the normal operation of electronic equipment.
The PV Array is not grounded (floating).
The conduits entries meet the following:
ALL Conduit Entries must use water-tight fittings.
ALL Conduit Entries should use sealant around wires inside wire-compartment to
prevent moisture ingress.
Metal Conduit Fittings are recommended to prevent propagation.
For detailed specification ranges and limits, see Chapter 9.

NOTICE: The allowable ambient temperature ranges for the CPS


SCH275KTL-DO/US-800 3-Phase String Inverters are defined based
on the following conditions:

Condition 1: -40°C to 70°C, Inverter not installed, and in storage (in


packaging or unpackaged).
Condition 2: -30°C to 60°C, Inverter installed, connected to electric
utility grid and operating during daylight hours.
Condition 3: No low temp limit to 70°C, Inverter installed, connected to
electric utility grid but non-operating (daylight or nighttime hours).

NOTICE:

Outdoor Installations for Extended Periods without Power

CPS advises against leaving inverters mounted


outdoors for an extended period of time (more than 90
days) and/or allowing inverters exposed to cycles of
freezing temperature without both DC and AC power
connected to the inverters under normal operation.

The CPS inverter enclosures are designed to conform


to NEMA4 (or IP65), however there exists the
possibility of water condensation inside the inverter

19 / 98
Mechanical Installation
enclosure when it is left exposed to an outdoor
environment without power to operate for an extended
period of time. Moisture in the air could enter the
inverter during the time that the cover is opened for
wiring purposes. When the inverter is exposed to
temperature swings, especially in cold weather,
moisture inside the inverter could condense over the
aluminum heatsink area where inverter
semiconductors are mounted. Water droplets on the
heatsink may cause a short-circuit to live
semiconductor devices. When the PV source is
applied to the inverter, this PV power source could
cause the inverter to fail and result in a short-circuit
across the PV array.

If such a situation in which the inverter is mounted


outdoors without operating power occurs, CPS
recommends that the inverter be inspected for water
condensation before any DC or AC power can be
applied to inverter. Without inspection, customers will
run the risk of having inverter electronic circuit damage
when power is applied to inverter during startup. It is
advised that customers contact CPS for further advice
and to arrange schedule for CPS service personnel to
perform inspection of inverter on site.

CPS hotline: 855-584-7168

20 / 98
Mechanical Installation

Installation Requirements

3.1.1 Installation Methods


The inverter shall be installed as follows:
If the location permits, install the inverter vertically.
If the inverter cannot be mounted vertically, it may be tilted backward
0 to15 degrees from vertical.
Do not mount the inverter leaning forward.
Do not mount the inverter upside down.
Do not mount the inverter horizontally.

Figure 3-2 Inverter Mounting Options

NOTICE!
Make sure that the mounting structure (bearing wall, rack, etc.) is rated to
bear the weight of the inverter.

3.1.2 Installation Environment


If the installation environment allows, avoiding direct sunlight, rain and snow can
reduce power derating and extend the life of the inverter. It is recommended that the
inverter is installed under a roof or sunshade. However, installation outdoors with
direct sunlight, rain and snow does not impact the warranty.

Figure 3-3 Inverter Mounting Suggestion


21 / 98
Mechanical Installation

3.1.3 Space Requirements


The distances between the inverters or the surrounding objects should meet the
following conditions:

Figure 3-4 Space Requirements

A: Keep a proper distance between the inverter and the shelter to ensure good
ventilation.
B: The inverter can be installed at an angle of 75° ~90° and its back shall not be
blocked to ensure good ventilation.
C: Two inverters can be installed back to back, and proper distance shall be kept to
ensure good ventilation.
D: The inverter can be installed under the PV module, while its back and top shall not
be blocked to ensure good ventilation.
E: The inverter can be installed on a single column holding rod and shall be checked
to confirm a secure installation.

22 / 98
Mechanical Installation

Installation Procedures
3.1.4 Install the Inverter
1. Mark hole-positions on the installation structure (shelter, steel rack, etc.)
according to the size of the mounting brackets.

Figure 3-5 Hole positions of mounting bracket

23 / 98
Mechanical Installation
2. Drill holes with a Ф12mm drill at the marked position, and then fasten the
mounting bracket ① on the installation structure with six M10x50
hexagon combination screws ② included in the PE accessory bag.
Tools required: 16mm hex socket wrench, torque: 12.5N.m,110 in-lbs.

Figure 3-6 Fasten the mounting bracket

3. Hang the inverter onto the mounting brackets by either:


A. Hoist mounting: screw two M10 lifting eyebolts to the studs at the top
of the inverter. Use sling rope or bar (inserted through both lifting
eyebolts) to lift the inverter onto the mounting bracket. The minimum
angle between the two sling ropes should be less than 90 degrees,
as shown in Figure 3-7 left.
B. Manual mounting: Four people are needed to properly lift the inverter
by the two handles and supporting positions marked by the arrows in
Figure 3-7 right, and mount the inverter onto the mounting bracket.

24 / 98
Mechanical Installation

A – Hoist Mounting B – Manual Mounting


Figure 3-7 Inverter Mounting Methods

CAUTION!
The total weight of the inverter is approx. 119 kg (262.4 pounds).
Ensure the mounting bracket is properly installed before hanging the
inverter on the bracket. It is recommended to have at least 4 people to
mount the inverter due to the weight of the equipment.

4. Use two M6X90 screws to fasten inverter on mounting bracket.


Tools required: #3 Philips head screwdriver, torque: 6 N.m, 53 in-lbs.

Figure 3-8 Fasten the inverter

25 / 98
Commissioning

4 Electrical Connection
Cable Specifications
Cable Type Acceptable wire range

• 36 fused input: screw clamp fuse holder


(wire range: #14 - #8 AWG CU).
• 24 non-fused input: screw clamp terminal
Use 90℃ Copper (wire range: #14 - #8 and #6 - #4 AWG
DC
wire only CU). One threaded hole per MPPT for
connecting #6 - #4 AWG CU.
• Terminals are 90C rated.
Outdoor copper core
GND Phase wire diameter/2
wire
• L1, L2, L3: either 4/0AWG~750kcmil
copper wire or 250kcmil~750kcmil
aluminum wire.
AC Use 90°C Cu/Al wire
• PE: Phase wire diameter/2
• Terminals are 90C rated.

Comm. Communication cable UTP CAT-5e or Belden 3106A or equivalent.

Table 4-1 Cable Specifications

Tools Required and Torque Values


No. Tools Usage Torque value

No.2 Phillips head


1 DC Cable 3 N.m, 26 in-lbs
screwdriver
18mm hex socket
2 AC terminal block L1-L3 31 N.m, 275 in-lbs
wrench
10mm hex socket
3 External grounding 6 N.m, 53 in-lbs
wrench
DC internal grounding bar 3 N.m, 26 in-lbs
4 5mm flat screwdriver
AC internal grounding bar 5 N.m, 45 in-lbs
5 1.5mm flat screwdriver RS485 comm. terminal 0.2 N.m, 1.8 in-lbs

26 / 98
Commissioning

6 Diagonal pliers Cut cable -

7 Wire stripping pliers Remove jacket -

8 Crimping pliers Crimp terminal -

Table 4-2 Tools required and torque values

Connect Interfaces and Connection Points


In the following section, you will find the connect interfaces, internal connection points,
as well as their names, positions etc.

4.1.1 Connection Interfaces


The connection interfaces of inverter are as shown in figure 4-1.

Figure 4-1 Connection interfaces

No. Item name


1 Four Knockouts for DC inputs (2 inch Trade Size)
2 LINKIT interface
3 Two Knockouts for communication (3/4 inch Trade Size)
4 One Knockout for AC output (3 inch Trade Size)
5 External GND connection point
Table 4-3 Connection interfaces

27 / 98
Commissioning

4.1.2 Internal Connection Points


The internal connection points of inverter are as shown in figure 4-2.

Figure 4-2a Internal connection points of 36 input inverter

① ① ①
Figure 4-2b Internal connection points of 24 input inverter

28 / 98
Commissioning

No. Item name


1 DC input fuse holder/terminal (Non-fused inputs for 24 input inverter)
2 DC Ground
3 AC output terminal block
4 AC Ground
5 Communication board
Table 4-4 Names of Internal connection points

Electrical Cable Connection


CAUTION!
The cables shall be connected in accordance with the National
Electrical Code NFPA 70, CSA C22.1 and all other applicable local
codes or jurisdictions.

WARNING!
This unit is not provided with a GFDI device for AC ground fault
protection. External AC ground fault protection is required by code
NEC 2017/2020 Section 250.21 when CPS inverters are connected
to Wye Floating or Delta Floating transformer windings. The inverter
will provide DC ground Fault detection.

For the 24 input and 36 input inverter models, there is no significant difference in their
Ground terminals and AC terminals wiring methods. The 36 input version is shown
below as an example. There are differences for their DC terminals layout and wiring
methods, so the DC wiring methods separately in following texts.
Use a 5mm socket head screw wrench to remove the four screws on the front cover,
and then lift the cover slightly to remove it.

29 / 98
Commissioning

Figure 4-3 Remove the front cover

IMPORTANT!
It is important to use hand tools (e.g. socket wrench) instead of power
drivers or other types of screw drivers.

4.1.3 Grounding

IMPORTANT!
The following wiring diagrams will take the 36 string input inverter as an
example since there are no obvious differences in ground wiring terminals.

There are two kinds of grounding methods for this inverter. You can choose one of
the following:
a) Connect two internal DC grounding terminals (in the middle) and one AC
grounding terminal (on the right side) as shown in Figure 4-4, or
b) Connect the external grounding point as shown in Figure 4-5 using the M6x16
Comb. bolt.

30 / 98
Commissioning

Figure 4-4 Internal DC and AC Ground Terminals

Figure 4-5 External Ground Cable Connection

IMPORTANT!
There are no differences on Internal DC and AC Ground Terminals,
External Ground Cable Connections, and AC wiring terminals between 24
input inverter and 36 input inverter versions. Therefore, the 36 input
inverter is shown as an example in the following section.

31 / 98
Commissioning

4.1.4 AC Wiring
1. Remove the watertight plug from the AC output of the wiring box to install
3 inch Trade Size conduit and conduit fittings into the hole. Then route the
cables through the conduit inside the wiring box.
2. A Circuit Ground should run with the AC Power cables and connected to
the internal ground bus.
3. A separate Ground wire should bond the Inverter to the local ground
connection for personnel safety. By bonding at this location, it is easy for
the operator to determine the inverter is safely grounded.
4. Connect the AC (L1, L2, L3) cables to the copper bus bar and connect the
ground cable to the internal grounding terminal block.

Figure 4-6 AC wiring terminals

When the output of the inverter is connected to the grid, an external AC circuit breaker
or fused disconnect device is required to be installed to safely disconnect the inverter
32 / 98
Commissioning

from the grid should an overcurrent event occur. The minimum size breaker is
determined by NEC calculations. The internal temperature of the AC Panel must be
considered and appropriate thermal derating applied to prevent nuisance tripping.

Inverter model Min AC OCPD Max AC OCPD


CPS SCH275KTL-DO/US-800 250A 300A
Table 4-5 Specification of AC OCPD

The inverter operates at 800VAC output. If another voltage/configuration is required,


a transformer may be necessary.

Figure 4-7 Acceptable Transformer Winding Configurations

IMPORTANT!
The CPS SCH275KTL-DO/US-800 inverter is only compatible with Wye
Floating and Delta Floating transformer winding configurations.
External AC Ground Fault detection is required by code NEC 2017/2020
Section 250.21 when CPS inverters are connected to Wye Floating or Delta
Floating transformer windings. The inverter will provide DC Ground Fault
detection

NOTES:

• Transformer short-circuit impedance (Z%) should be less than 6%.


• The transformer VA rating should be at least 100% of the sum of the
connected inverter VA ratings.
• CPS recommends the transformer VA rating be selected based on IEEE
C57.159-2016 Guide on Transformers for application in Distributed
Photovoltaic (DPV) Power Generation Systems. It is the responsibility of the
system designer to determine and take into account the reliability of the

33 / 98
Commissioning

transformer and other system parameters.


• The transformer does not require a static shield.
• Up to 20 inverters may be connected in parallel for use with a single
transformer.
• The recommended maximum voltage-drop on the Inverter to Point of
Common Coupling (to the grid) is 2% at full load – including conductor
temperature considerations. Voltage drop greater than 2% may require
changing the transformer tap or as last resort adjusting the GridMaxVolt trip
point settings.

4.1.5 DC Wiring
DC fuse configuration
The 36 input inverter version includes touch safe fuse holders and preinstalled 20A
DC fuses. Customers must verify that the appropriate fuses are installed depending
on the configuration of PV array and by performing PV fuse sizing calculations for
each string.
Each MPPT DC input from the PV that has more than 2 strings requires fuse
protection.
The rated voltage of the fuse should be 1500VDC. ADLER series 1500VDC fuse
are recommended.
The ampere rating of the fuse is generally selected as 1.56 × module Isc of the
PV string. Refer to NEC 690.8 for Circuit Sizing and Current requirements.
The following table lists the names, types and specifications of ADLER series fuses,
which are within the rated voltage of PV modules.

Names 20A fuses 25A fuses 30A fuses


Types A74 (36 input) A74 (36 input) A74 (36 input)
Spec. 20A/1500V 25A/1500V 30A/1500V
Table 4-6 DC Fuse selection
WARNING!
Replace only with the same ratings and type of fuses.
Different fuses or incorrectly sized fuses could result in equipment
damage or unsafe working conditions.
Any damage resulting from incompatible fuses is not covered by
warranty.

34 / 98
Commissioning

CAUTION!
Disconnect all power sources before replacing fuses.

DC Cable Connection
To ensure the optimum performance of the inverter, please read the following
guidelines before performing any DC connections:

Confirm the DC configuration and ensure that the maximum open circuit voltage
of the PV modules is lower than 1500VDC under any conditions.
Confirm that the PV modules for each MPPT within the inverter are of the same
type and specification before connection.
Ensure correct polarity of the PV strings before terminating the DC cables
according to the following steps, as shown in figure 4-8:
i. Use a multi-meter to measure the PV strings’ cable ends and check
the polarity.
ii. The positive (+) terminal of cable should match the positive (+)
terminal of inverter’s DC input.
iii. The negative (-) terminal of cable should match the negative (-)
terminal of inverter’s DC input.

Figure 4-8 Polarity Check

NOTICE!
It is important to use a multi-meter to check the polarity of the DC input
cables to avoid any risk of reverse polarity.

35 / 98
Commissioning

WARNING!
A reversed string is extremely hazardous and will result in a blown fuse
when the irradiation is high.
The voltage across the blown fuse can be as much as two times Voc and
could prevent proper fuse operation resulting in a fire.

Perform cable connection as per the following steps:


1. Remove the liquid-tight hole plugs from the DC input of the wiring box and
install 2 inch Trade Size conduit and conduit fittings into the holes. If the
use of smaller conduit is desired, proper weather-tight reducing bushings
may be installed. Confirm all fittings are NEMA 4X rated, properly
tightened, and route the cables through the conduit into the wiring
compartment.
2. Connect the DC cables to the fuse holders of 36 input inverter as shown
in Figure 4-9a; or connect to the DC terminals of 24 input inverter as
shown in Figure 4-9b, and then tighten the screws.
3.

Figure 4-9a Connect the DC cable to fuse holder

36 / 98
Commissioning

Figure 4-9b Connect the DC cable to DC terminal

NOTICE!
To maximize production, reduce clipping losses, and optimize thermal
performance, the DC input power should be distributed across all 12
MPPTs as evenly as possible (e.g. difference in number of strings per
MPPT not larger than 1.)

NOTICE!
The use of ferrules is recommended for all stranded wire connections.

37 / 98
Commissioning

Communication Cable Connection


4.1.6 Communication Board

Figure 4-10 Communication Board

No. Item names Picture Configuration


6 - RS485_GND (Common)
5 - RS485_B
RS485 port 4 - RS485_A
1
6-pin connector plug 3 - RS485_GND (Common)
2 - RS485_B
1 - RS485_A
S2 Selector switch OFF - Disable terminal resistor
2
(set terminal resistor) ON - Enable terminal resistor

Table 4-7 Communication board Interfaces

38 / 98
Commissioning

4.1.7 Communication Connection


The inverter supports industry standard Modbus RS485, Ethernet, and AC-PLC
communication modes. AC-PLC communication requires connection of the CPS AC-
PLC Kit accessory.

RS485 Communication Schematic Diagram


Connect RS485 communication cables with the help of 6-pin terminal to 485
communication module, referring to figure 4-11 (1) for a single inverter RS485
communication connection and figure 4-11 (2) for network configuration. (Wiring
methods of new and old communication boards are the same, here we take the new
one for instance as below).

Figure 4-11 RS485 communication cable connection

It is recommended that industrial grade shielded twisted pair RS485 cable be used in
lieu of unshielded twisted pair. Communication cable such as (CAT5e) or Belden
3106A cable for RS485 6-pin connector is preferred.

39 / 98
Commissioning

RS485 Network Connection


When the inverters are monitored via the RS485 communication, a unique RS485
address for each inverter can be set up through the APP interface. Up to 32 inverters
can be connected in a serial fashion in the RS485 communication network. Therefore,
the daisy-chain topology (see Figure 4-12) is recommended for the RS485 network
connection, which can minimize the noise and bus reflections. Other communication
topologies, such as the star networks, are not recommended.

Figure 4-12 RS485 Network Connection

If there are multiple inverters in the RS485 network and the last inverter is more than
200 m distant from data logger, the selector switch S2 of the last inverter in the daisy-
chain should be in ON position, to enable the 120ohm terminal resistor. The selector
switch S2 of all other inverters should be in the OFF position to disable the terminal
resistor.
It is important to daisy chain the inverter RS485 connections to minimize noise and
bus collisions. All RS485 connections must be terminated in a serial fashion and not
to exceed 32 in total. Daisy Chain configuration is recommended.

DANGER!
Make sure all DC and AC power has been disconnected before opening
the wire box and ensure that hazardous high voltage and power has been
discharged to avoid risk of electric shock.
Wait at least 5 minutes after disconnecting from the DC and AC sources
before servicing or maintaining the inverter.

40 / 98
Commissioning

Communication Wiring
The detailed steps to perform the communication wiring for a single inverter or a
network of inverters are as follows:
1. Open the inverter wire box.
2. Insert the communication cables into the wire box through the knockout
holes at the bottom. Conduit and knockouts must be sealed and water-
tight to maintain the NEMA 4X rating.
3. Connect the RS485 wires to their corresponding connectors, ensuring
correct polarity and using a shielded twisted pair cable.
4. (a). If the inverter is the last Modbus device in the daisy chain and it’s
more than 200m distant from data logger, make sure the Modbus
termination switch S2/ LEFT S150 is in the ON position to enable Modbus
termination; while all other switches shall be in the OFF position.
(b). If there is only one inverter and it’s more than 200m distant from data
logger, the Modbus termination switch should also be set to ON, otherwise,
it can be set as OFF.
5. The shield of the individual cables must be open (not connected to ground)
on one end – the other end of the shield must be grounded.
WARNING!
Failure to follow this installation practice will increase lightning surge
damage to the inverter and will void the warranty.

After completing all the wiring steps, reinstall the front cover and press down to lock
it. Finally, fasten the four screws on the front cover as shown in the figure.
Tools required: 5mm socket head screw wrench, torque: 3N.m, 26in-lbs.

Figure 4-13 Re-install the upper cover

41 / 98
Commissioning

IMPORTANT!
• It is important to use hand tools (e.g. socket wrench) instead of power
drivers or other types of screw drivers.
• During installation, it is recommended the cover is in alignment with
balanced force to avoid thread damage.
• Partially engage the screws into the threaded inserts before
tightening.

Install the LINKIT Module


INSTRUCTION
The LINKIT module is required for the commissioning of the inverter. This
step does not need to be completed until commissioning.

1. Remove the two M4x10 fixing screws on the DB9 connector cover, as
shown in Figure 4-14.

Figure 4-14 Expose the connector

2. Rotate the cover to expose the connector and then install the LINKIT
module with the two screws just removed. Pay attention to the control
torque of 1.6 Nm (14 in-lbs), to ensure that the seal watertight.

42 / 98
Commissioning

Figure 4-15 Install LINKIT module

Cable Connection Notices for Joints and Seals


All the electrical cables and communication cables shall be jointed and sealed
properly according to the following requirements to ensure their excellent
performance and good water tightness.
The cable must be vertical to prevent excessive cable stress.

Figure 4-16 Cable must be vertical

After the cable passes through the fastening head, fireproof putties shall be
applied to seal the joint tightly to prevent water vapor from entering.

43 / 98
Commissioning

Figure 4-17 Apply fireproof putties

After tightening the fastening head, watertight sealants shall be applied on its
inner surface and outer surface to avoid loosening or prevent water from
entering.

Figure 4-18 Apply watertight sealants

44 / 98
Commissioning

Before and after tightening the fastening head, check carefully to ensure the
watertight gasket is in good condition, i.e. its surface is uniform and unbroken.

Figure 4-19 Check watertight gasket

5 Commissioning
WARNING!
Please follow the guidelines below before performing any on-grid
operation to eliminate possible danger. Before powering up the PV
system it is important to check the installation for any hazards that may
be present.

Pre-commissioning Checks
5.1.1 Mechanical Installation
Make sure all the mounting brackets are secure.
Make sure all the screws have been tightened to the specified torque values.
Confirm all knockouts are sealed and conduit is securely attached to the inverter,
creating a water-tight seal.
5.1.2 Cable Connections
Make sure all cables are connected to the right terminals and properly labeled.
Ensure appropriate cable management to avoid physical damage.
Check polarity of DC input conductors. The DC Switches should be in the OFF
position.
5.1.3 Electrical Check
Make sure the AC circuit breaker and/or fused switch disconnect is appropriately

45 / 98
Commissioning

sized.
Test and check that the AC voltage is within the normal operating range.
Make sure the DC open circuit voltage of input strings is less than 1500V.
Commissioning Steps
Complete the list above before commissioning the inverter as follows:
1. Turn on the AC circuit breaker or fused switch disconnect.
2. Turn on the DC circuit breaker. (Skip this step if there is no DC circuit
breaker).
3. Switch the Inverter’s DC Switches to the ON position. When the energy
supplied by the PV array is sufficient, the POWER indicator of inverter will
light up. The inverter will then start up and enter the self-check process.
4. Connect to the inverter via the CPS Connect Pro app according to the
procedures introduced in section 6.1 APP Download and section 6.2 APP
Setting to select the inverter parameter settings.

46 / 98
APP Interface and Setting

6 APP Interface and Setting


APP Download
The inverter settings are accessed through the CPS Connect Pro
application.
Users can download iOS version at Apple store or Android version
in Google store or scan the QR code (Support Android 4.1 and
IOS 9.0 or later).

APP Setting
Once powered, the inverter will automatically create a wireless network that can be
visible as an Access Point from the user communication devices (tablet, smartphone,
etc.). Users can perform the following procedures to set the APP easily. First of all,
open your Bluetooth function, and then open CPS Connect Pro APP.

1. Touch Smart Link icon to enter smart link interface and then click Next to
enter the Connect to the adapter interface.
2. Touch the wireless network named CPLK-XXXXXXX (X can be found on
the LINKIT label) shown in the Bluetooth List, or touch the green QR icon
under the list to scan LINKIT car code to connect network; Or you can
choose the WiFi Mode tab in the top right corner to set WiFi and input the
password “Password” (Capital P), to connect network.

47 / 98
APP Interface and Setting

3. Touch OK icon to finish initialization process during the first


commissioning.
4. Set correct inverter parameters, such as Grid Code, PV Link Type, Neutral
line, RS485, then click Next button, it will go to home interface
Grid Connection Rule: Choose the Grid Code according to the requirements of your
local authority. the available Grid Codes include IEEE 1547-2018, CA Rule 21, ISO-
NE, IEEE 1547_2014 and HECO.
PV Input Mode: The working mode of the DC input connection and MPPT can only
be configured as Independent.
Neutral Line Setting: this inverter can only be applied in IT system, the neutral line
connection is not supported.
RS485: Choose the communication data Modbus Address and Baud Rate.
Time Set: Set the system clock.
IMPORTANT!
Please check with your local electricity supply company before selecting
a Grid Code. If the inverter is operated with a wrong Grid Code, the
electricity supply company may cancel the interconnection agreement.
Placing the inverter into operation before the overall system complies with
the national rules and safety regulations of the application is not
permitted.

48 / 98
APP Interface and Setting

5. When the device screen shows the normal operation status and the RUN
light on the LED panel is illuminated, it indicates that the grid connection
and power generation are successful. You can now browse through the
real-time data in the APP now. Sliding the interface left and right can
browse through DC, AC, Other and Version pages. Touch the Setting icon
and input the password “1111”, it will go to Setting interface.
6. You can reset or modify inverter parameters such as Grid Code, PV Link
Type, RS485 or password as required.

49 / 98
APP Interface and Setting

7. If the inverter fails to operate normally, the FAULT light will illuminate and
the fault information will be shown on the interface. Touching Event icon
in the bottom can skip to Event page, you can check the detailed current
and history information here. Troubleshoot related problems and restart.
Contact our after-sale department if necessary.
8. Touch More icon and input password "1111" to power on/off device.

50 / 98
APP Interface and Setting

Structure Tree of App Interface


Choose APP function

Setup the product Activate a site Manage my site

Wifi Setting

Password: Password

Main menu

Chart Setting History Turn ON/OFF

Running Data Password: 1111 Warning Running Status

Inverter Parameters Read/Write Register Upgrade Firmware

Grid Code PV Link Type Neutral Line RS485 Inverter Clock Change password

ActivePower ReactivePower LcdLess Basic


Protect LVRT/HVRT Others Command Derating Derating Parameters

Figure 6-1 Structure tree of App Interface


Main Menu
In the Main interface, you can access the DC, AC, OTHER and VERSION information.

51 / 98
APP Interface and Setting

Figure 6-2 Main information on Main Interface

In addition, you can see four submenus: Chart, Setting, History and Turn ON/OFF.

52 / 98
APP Interface and Setting

6.1.1 Chart
In the chart sub-menu, you can view the power generation situation at different times,
such as Current, Today and Total. These data can also be displayed in Day, Month,
Year, shown as below in Figure 6-3.

Figure 6-3 power generation screen


6.1.2 Setting

Touch the Setting icon and input the password “1111”, you will go to the setting
interface.

53 / 98
APP Interface and Setting

Figure 6-4 Setting interface


It’s possible to access three submenus on the setting interface: Inverter Parameters,
Read/Write Register and Upgrade Firmware.

Inverter Parameters
Touch the Inverter Parameters tab, you can set the following parameters as required.

Figure 6-5 Inverter Parameters

54 / 98
APP Interface and Setting

IMPORTANT!
Check with your local electric supply company before selecting a grid
code. If the inverter operates with a wrong grid code, the electric
supply company may cancel the interconnection agreement.

Read/Write Register
In the Read/Write Register interface, you can find the following sub-menus:
Protect
LVRT/HVRT
Others
Command
ActivePowerDerating
ReactivePowerDerating
LcdLess Basic Parameters

Figure 6-6 Read/Write Register

55 / 98
APP Interface and Setting

IMPORTANT!
The following mobile screenshots show parameters in accordance
with IEEE 1547-2018 Grid Code.

Protect
The Protect interface displays the protect parameters of the AC grid voltage,
frequency and recovery, etc. In addition, you can find and set the protection levels of
over voltage, under voltage, over frequency and under frequency.

56 / 98
APP Interface and Setting

Figure 6-7 Protection Parameters

57 / 98
APP Interface and Setting

In addition, the table listed below can provide detailed parameter information for you.
Grid code Grid code Grid code
Parameter name Description Range Unit
IEEE-1547 RULE-21 ISO-NE
Grid Over Voltage Protection
Threshold Level 1
GridVoltMax1 {100.00%,135.00%} 110.00% 110.00% 110.00% %
Max. grid voltage
Trip Time Level 1
VoltMaxTripT1 {0, 655.35} 13.00 12.50 2 Secs
Max. grid voltage
Level 1 Max. grid
GridVoltMax1En {Disable, Enable} Enable Enable Enable
voltage protection
Threshold Level 2
GridVoltMax2 {100.00%,135.00%} 120.00% 120.00% 120.00% %
Max. grid voltage
Trip Time Level 2
VoltMaxTripT2 {0, 655.35} 0.16 0.16 0.16 Secs
Max. grid trip voltage
Level 2 Max. grid
GridVoltMax2En {Disable, Enable} Enable Enable Enable
voltage protection
Threshold Level 3
GridVoltMax3 {100.00%,135.00%} 120.00% 120.00% 120.00% %
Max. grid voltage
Trip Time Level 3
VoltMaxTripT3 {0, 655.35} 0.16 0.16 0.16 Secs
Max. grid trip voltage
Level 3 Max. grid
GridVoltMax3En {Disable, Enable} Disable Disable Disable
voltage protection
Grid Under Voltage Protection
Threshold Level 1
GridVoltMin1 {0.00%,100.00} 88.00% 88.00% 88.00% %
Min. grid voltage
Trip Time Level 1
VoltMinTripT1 {0, 655.35} 21.00 20.50 2 Secs
Min. grid trip voltage
Level 1 Min. grid
GridVoltMin1En {Disable, Enable } Enable Enable Enable
voltage protection
Threshold Level 2
GridVoltMin2 {20.00%,100.00%} 50.00% 70.00% 50.00% %
Min. grid voltage
Trip Time Level 2
VoltMinTripT2 {0, 655.35} 2.00 10.50 1.1 Secs
Min. grid trip voltage
Level 2 Min. grid
GridVoltMin2En {Disable, Enable } Enable Enable Enable
voltage protection
Threshold Level 3
GridVoltMin3 {20.00%,100.00%} 45.00% 50.00% 50.00% %
Min. grid voltage
Trip Time Level 3
VoltMinTripT3 {0, 655.35} 0.16 1.50 1.1 Secs
Min. grid trip voltage
Level 3 Min. grid
GridVoltMin3En {Disable, Enable } Disable Enable Disable
voltage protection
Grid Over Frequency Protection
Threshold Level 1
GridFrqMax1 {60, 72} 61.19 60.49 61.19 Hz
Max. grid frequency
Trip time of Level 1
FrqMaxTripT1 {0, 1310} 300.00 599.00 599.00 Secs
Max. grid frequency
Level 1 Max. grid
GridFrqMax1En {Disable, Enable} Enable Enable Enable
frequency protection
Threshold Level 2
GridFrqMax2 {60, 72} 61.99 61.99 61.99 Hz
Max. grid frequency
Trip time of Level 2
FrqMaxTripT2 {0, 1310}} 0.16 0.32 0.32 Secs
Max. grid frequency
Level 2 Max. grid
GridFrqMax2En {Disable, Enable} Enable Enable Enable
frequency protection

58 / 98
APP Interface and Setting
Threshold Level 3
GridF.Max3 {60, 66} 61.99 61.99 61.99 Hz
Max. grid frequency
Trip time of Level 3
FrqMaxTripT3 {0, 1310} 0.16 0.32 0.32 Secs
Max. grid frequency
Level 3 Max. grid
GridFrqMax3En {Disable, Enable} Disable Disable Disable
frequency protection
Grid Under Frequency Protection
Threshold Level 1
GridFrqMin1 {48, 60} 58.49 58.49 58.49 Hz
Min. grid frequency
Trip time of Level 1
FrqMinTripT1 {0, 1310} 300.00 599.00 599.00 Secs
Min. grid frequency
Level 1 Min. grid
GridFrqMin1 En {Disable, Enable} Enable Enable Enable
frequency protection
Threshold Level 2
GridFrqMin2 {48, 60} 56.49 57 56.5 Hz
Min. grid frequency
Trip time of Level 2
FrqMinTripT2 {0, 1310} 0.16 0.32 0.16 Secs
Min. grid frequency
Level 2 Min. grid
GridFrqMin2 En {Disable, Enable} Enable Enable Enable
frequency protection
Threshold Level 3
GridFrqMin3 {48, 60} 56.49 57.00 56.50 Hz
Min. grid frequency
Trip time of Level 3
FrqMinTripT3 {0, 1310} 0.16 0.32 0.32 Secs
Min. grid frequency
Level 3 Min. grid
GridFrqMin3 En {Disable, Enable} Disable Disable Disable
frequency protection
Voltage and Frequency Protection Recovery
Recovery Max
VoltMaxRecovery threshold grid voltage {80.00%, 135.00%} 105.00% 108.00% 108.00% %
protection
Recovery Min
VoltMinRecovery threshold. grid {20.00%,100.00%} 91.70% 90.00% 90.00% %
voltage protection
Recovery time of grid
VolRecoveryT {0, 655.35} 300.00 300.00 300 Secs
voltage protection
Recovery Max
FrqMaxRecovery threshold grid {54, 72} 60.09 60.40 61.00 Hz
Frequency protection
Recovery Min
FrqMinRecovery threshold. grid {48, 60} 59.49 58.60 58.80 Hz
Frequency protection
Recovery time of grid
FrqRecoveryT {0, 655.35} 300 600 600 Secs
frequency protection
Moving Average Parameters
Threshold max
VoltMaxMovAvg Voltage move {100.00%,135.00%} 110.00% 110.00% 110.00% %
average
Trip time of max.
MaxTripVMovAvg
voltage move {0, 655.35} 600 600 600 Secs
T
average
VoltMaxMovAvgE max voltage move
{Disable, Enable} Disable Disable Disable
n average enable
Threshold min
VoltMinMovAvg voltage move {80.00%, 100.00%} 88.00% 87.99% 88.00% %
average

59 / 98
APP Interface and Setting
Trip time of min
MinTripVMovAvg
voltage move {0, 655.35} 600 600 600 Secs
T
average
VoltMinMovAvgE min voltage move
{Disable, Enable} Disable Disable Disable
n average enable
Voltage Unbalance
GridVoltUnbalanc Threshold grid
{0.01%, 50%} 10% 10% 10% %
e voltage unbalance
GridVoltUnbalanc grid voltage
{Disable, Enable} Enable Enable Enable
eEn unbalance enable
PhaseLose and Phase-PE parameters
Phase lose protection
PhaseLoseCoeff {0.5%,30.0%} 3.0% 3.0% 3.0% %
trigger value
PhaseLoseRcvCo Phase lose protection
{0.5%,30.0%} 2.0% 2.0% 2.0% %
eff recovery value
PhaseLoseVUnba PhaseLose Voltage
{0.1%,10.0%} 10.0% 10.0% 10.0% %
lance Unbalance
PhasLoseCoeffEn
Phase lose protection {Disable, Enable} Disable Disable Disable
able
Phase-PE Trip
Phase-PETripVolt {0.01,100.00} 45% 45% 45% %
Voltage
Phase-PE grid
Phase-PERcvVolt {0.01,100.00} 35% 35% 35% %
recovery
Enable Phase-PE
Phase-PEEnable {Disable, Enable} Disable Disable Disable
protection

Table 6-1 Protection Parameters (IEEE1547 2018, Rule21 and ISO-NE)

60 / 98
APP Interface and Setting

LVRT/HVRT
The LVRT/HVRT interface is used to set the LVRT (Low voltage ride through) and
HVRT (High voltage ride through) parameters as shown in the following interfaces:

Figure 6-8 LVRT/HVRT interface

61 / 98
APP Interface and Setting

You can also see the LVRT Curve in figure 6-9 and HVRT Curve in figure 6-10.

PRC-024 LVRT PRC-024 HVRT CPS LVRT CPS HVRT


1.40
1.35
1.30
1.25
1.20
1.15
1.10
1.05
1.00
PRC-024
0.95 No Trip Zone
0.90
0.85
0.80
0.75
CPS Inverter No Trip
0.70 Zone
0.65
0.60
0.55
0.50
0.45
0.40
0.35
0.30
0.25
0.20
0.15
0.10
0.05
0.00
0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 9.00 10.00 11.00 12.00 13.00 14.00 15.00 16.00 17.00 18.00 19.00 20.00 21.00 22.00 23.00 24.00 25.00

Figure 6-9 LVRT Curve

Figure 6-10 HVRT Curve

62 / 98
APP Interface and Setting

In addition, the table listed below can provide detailed parameter information for you.
Grid code Grid code Grid code
Parameter name Description Range Unit
IEEE-1547 RULE-21 ISO-NE
LVRT
Threshold LVRT {0%, 100%} 0% 0% 0%
LVRTVolt (1,2) %
(1st or 2nd point) {0%, 100%} 0% 0% 49%
Time of LVRT {0, 655.35} 0 0 0
LVRTTime (1,2) Secs
(1st or 2nd point) {0, 655.35} 1.2 1.2 1.2
Threshold LVRT {0%, 100%} 50% 50% 45%
LVRTVolt (3,4) %
(3rd or 4th point) {0%, 100%} 50% 50% 45%
Time of LVRT {0, 655.35} 1.2 1.2 1.2
LVRTTime (3,4) Secs
(3rd or 4th point) {0, 655.35} 10.5 10.5 10.5
Threshold LVRT {0%, 100%} 70% 70% 65%
LVRTVolt (5,6) %
(5th or 6th point) {0%, 100%} 70% 70% 65%
Time of LVRT {0, 655.35} 10.50 10.50 10.50
LVRTTime (5,6) Secs
(5th or 6th point) {0, 655.35} 20.50 20.50 20.50
Threshold of LVRT {0%, 100%} 88% 88% 83%
LVRTVolt (7,8) %
(7th or 8th point) {0%, 100%} 88% 88% 83%
Time of LVRT {0, 655.35} 20.5 20.5 20.5
LVRTTime (7,8) Secs
(7th or 8th point) {0, 655.35} 20.5 20.5 20.5
HVRT
Threshold of HVRT {100%, 135%} 125% 125% 125%
HVRTVolt (1,2) %
(1st or 2nd point) {100%, 135%} 125% 125% 125%
Time of Level HVRT {0, 655.35} 0 0 0
HVRTTime (1,2) Secs
(1st or 2nd point) {0, 655.35} 0.16 0.11 0.80
Threshold of HVRT {100%, 135%} 120% 120% 124%
HVRTVolt (3,4) %
(3rd or 4th point) {100%, 135%} 120% 120% 124%
Time of Level HVRT {0, 655.35} 0.16 0.11 0.80
HVRTTime (3,4) Secs
(3rd or 4th point) {0, 655.35} 12.50 12.50 12.50
Threshold of HVRT {100%, 135%} 110% 110% 115%
HVRTVolt (5,6) %
(5th or 6th point) {100%, 135%} 110% 110% 115%
Time of Level HVRT {0, 655.35} 12.50 12.50 12.50
HVRTTime (5,6) Secs
(5th or 6th point) {0, 655.35} 13.50 12.50 12.50
Threshold of HVRT {100%, 135%} 110% 110% 115%
HVRTVolt (7,8) %
(7th or 8th point) {100%, 135%} 110% 110% 115%
Time of Level HVRT {0, 655.35} 13.50 12.50 12.50
HVRTTime (7,8) Secs
(7th or 8th point) {0, 655.35} 13.50 12.50 12.50
LVRT Setting
{Disable; Enable
reactive power
Enable, Enable, Enable,
output; Enable no
active active reactive
LVRTModeSetting LVRT mode setting reactive power
power power power
output; Enable,
output output output
active power
output }
Trigger Voltage of 88% 88% 88% %
LVRTTripVolt {70%, 100%}
LVRT
Coefficient of LVRT 150% 150% 150% %
LVRTPstReactivel {0%, 500%}
positive current
Coefficient of LVRT 200% 200% 200% %
LVRTNegReactivel {0%, 500%}
negative current
HVRT Setting

63 / 98
APP Interface and Setting
{Disable; Enable
reactive power
Enable, no Enable, no Enable, no
output; Enable no
reactive reactive reactive
HVRTModeSetting HVRT mode setting reactive power
power power power
output; Enable,
output output output
active power
output }
Trigger Voltage of %
HVRTTripVolt {110%,135%} 110% 110% 110%
HVRT
Coefficient of HVRT %
HVRTReactiveI {0%,500%} 150% 150% 150%
reactive current

Table 6-2 LVRT and HVRT Parameters (IEEE1547 2018, Rule21 and ISO-NE)

64 / 98
APP Interface and Setting

Others
In the others interface, you can find following common parameters shown as below,
such as power on delay, Normal Start Power Rate, PV slow start step, DCI protection,
ISO protection, as well as Min. and Max. Voltage of MPPT optimizer.

65 / 98
APP Interface and Setting

Figure 6-11 Others interface

66 / 98
APP Interface and Setting

In addition, the table listed below can provide detailed parameter information for you.
Grid code Grid code Grid code
Parameter name Description Range Unit
IEEE-1547 RULE-21 ISO-NE
PowerOnDelay Startup delay time {0,1200} 5 5 5 Secs
ReactivePowerStep Reactive Power Step {0.01%,655.35%} 50.00% 50.00% 50.00%
ErrSoftStartP Pwr Ramp after Fault {0.01%,100%} 0.16% 2.00% 0.16% %
NomSoftStopP Normal Stop Pwr Rate {0.01%,100%} 6.00% 10.00% 10.00% %
Normal Stop Pwr Rate
NomSoftStopPEn {Disable, Enable} Enable Enable Enable
Enable
NomSoftStartP Normal Start Pwr Rate {0.01%,100%} 4.00% 100.00% 2.00% %
NomDeratingStep Normal Pwr Derating Step {0.01%,100%} 6.00% 100.00% 6.00% %

PVSlowStartStep PV Slow Start Step {0.01%,10%} 10% 10% 10% %


PVSlowStartPwDelt
PV Slow Start Pwr slope {0.01%,100%} 5.00% 5.00% 5.00% %
a
PVSlowStartSEn PV Slow Start Setting {Disable, Enable} Disable Disable Disable

FaultEnvT Enclosure Fault Temp NA 83.0 83.0 83.0 ℃


Static Threshold Leakage
GFCIStaticValue {0.100,5.000} 2.500 2.500 2.500 A
current
Static Threshold Leakage
GFCIStaticT {0,655.35} 0.20 0.20 0.20 Secs
Time
Enable Static Threshold
GFCIStaticEn {Disable, Enable} Enable Enable Enable
Leakage current

GFCIDynPro Threshold dynamic


coefficient Leakage {0.0%,500%} 100% 100% 100% %
Factor current
Enable Dynamical ground
GFCIDynProEn {Disable, Enable} Disable Disable Disable
fault circuit interrupter
DCIProtection1 Max. DCI value 1 {0.1%,5.00%} 0.50% 0.50% 0.50% %
DCIProtectionT1 Trip time 1 of DCI value {0.00,120.00} 10.00 10.00 60.00 Secs
Enable Maximum DCI
DCIProtection1En {Disable, Enable} Enable Enable Enable
value 1
DCIProtection2 Max. DCI value 2 {5,5000} 950 950 950 mA

DCIProtectionT2 Trip time 2 of DCI value {0.00,120.00} 1.00 1.00 1.00 Secs
DCIProtection2En Enable Max. DCI value 2 {Disable, Enable} Disable Disable Disable

PVStartupVolt PV start-up voltage (500, 700) 550 550 550 V


MPPTScanPeriod MPPT Scan Cycle {300,5400} 3600 3600 3600 Secs

MPPTScanEn Enable MPPT Scan {Disable, Enable} Disable Disable Disable


Minimum insulation
ISOProtection {1, 2000} 50 50 50 kΩ
resistance
ISOProtectionEn Insulation detection {Disable, Enable} Enable Enable Enable
StartUpMinTemp Min Startup Temperature {-35℃, -20℃} -30 -30 -30 ℃

DuplicationControl Duplication Control {0%,100%} 0% 0% 0% %


control parameter setting Article 4 Article 4 Article 4
CtrParaGroup Article 1~5 groups,
of inverter loop groups groups groups
Island Protect anti-Island protection {Disable, Enable} Enable Enable Enable

67 / 98
APP Interface and Setting
Grid code Grid code Grid code
Parameter name Description Range Unit
IEEE-1547 RULE-21 ISO-NE
FANDetectEn fans detection {Disable, Enable} Enable Enable Enable
AC surge protection
ACSPDDetectEnSet {Disable, Enable} Disable Disable Disable
device test
Operation over voltage
OperationOverVol {100%,135%} 120% 120% 120% %
protect value
OperationOverVolD
Over voltage detection {Disable, Enable} Disable Disable Disable
ectEn
Resonance damping
VirtualDamping {0.000, 5.000} 0.000 0.000 0.000 Ω
coefficient
MPPTRangEnable Enable MPPT {Disable, Enable} Disable Disable Disable
RapidShutdownEna
Enable Rapid Shutdown {Disable, Enable} Disable Disable Disable
bBit
FreqLv2PrtEn (CEI) Only for Italian Grid Code {Disable, Enable}
OptiVoltMinMpptxx Minimal voltage of Mppt
{500, 1450} 500 500 500 V
(xx=1..12) optimizer
OptiVoltMaxMpptxx Maximal voltage of Mppt
{500, 1450} 1450 1450 1450 V
(xx=1..12) optimizer

Table 6-3 Other Parameters (IEEE1547 2018, Rule21 and ISO-NE)

Command
In the Command interface, you can access the following information:

Figure 6-12 Commands interface


Force Restart: If a fault shutdown happens, a severe fault may have occurred
inside the inverter. The user can perform a force reboot for one time per Power
On in this menu if the user needs to restart the inverter.

68 / 98
APP Interface and Setting

Factory Defaults: The manufacturer’s parameter default values can be


restored when the inverter is not in operation mode. Otherwise a “Fault
Operated” alarm will be indicated.
AutoTest: Only for Italian Grid Code.
MPPT Scan: This function is used to manually execute the MPPT scan. The
device screen will skip to normal operation interface if the MPPT scanning
succeeds or remain on the interface if the scanning fails.
MPPT scan function is used for multi-MPP tracking, and is useful if the PV
modules are partly shadowed or installed with different angles. The factory
setting of MPPT Scan is Enabled, yet can also be set to Disabled. When the
MPPT scan function is enabled, the scan period is 60 minutes.
The inverter will scan the maximum power point in the MPPT range, according
to the following conditions:
The total input power is lower than 90% of the active power.
Once this MPPT scan function is activated on the device, it will search the
maximum power point at a voltage step of 5V in the MPPT range for full load,
and retrieve the maximum power point.

69 / 98
APP Interface and Setting

ActivePowerDerating
The ActivePower Derating menu is used to set the active power derating parameters,
including Active Power Derating, Over Voltage Derating, Over Frequency Derating,
etc.

Figure 6-16 ActivePower Derating interface

You can see the Curve of over voltage derating in figure 6-17 and Curve of over
frequency derating in figure 6-18.

Power
Present

0.0%~100.0%
Settable

0
100.00%~135.00% GridV.Max1 Grid voltage
Settable

Figure 6-17 Curve of over voltage derating

70 / 98
APP Interface and Setting

Power
Present

0.0%~100.0%
Settable

0
60.00~72.00Hz GridF.Max1 Grid Frequency
Settable

Figure 6-18 Curve of over frequency derating


In addition, the table listed below can provide detailed parameter information for you.
Grid code Grid code Grid code
Parameter name Description Range Unit
IEEE-1547 RULE-21 ISO-NE
Over-Voltage Derate
Grid Volt of VwCurve
VwCurveV1 {100.00%, 110%} 106.00% 106.00% 106.00% %
point V1
Power of VwCurve point
VwCurveP1 {0%,110%} 100% 100% 100% %
P1
Grid Volt of VwCurve
VwCurveV2 {100%,115%} 110.00% 110.00% 110.00% %
point V2
Power of VwCurve point
VwCurveP2 {0%,110%} 0.0% 0.0% 0.0% %
P2
OpenLoopRespT Open loop response time {0.5, 90.0} 10.0 10.0 10.0 Secs
Over voltage derating
OvrVoltDerEn { Disable, Enable} Enable Enable Disable
enable
The dead zone of
FreqDroop_DbOf overfrequency active {0.001, 2.000} 0.036 0.036 0.036 Hz
power regulation
The dead zone of
FreqDroop_DbUf underfrequency active {0.001, 2.000} 0.036 0.036 0.036 Hz
power regulation
Coefficient of {0.01, 0.10}
FreqDroop_KOf overfrequency active 0.05 0.05 0.05 NA
power regulation
Coefficient of {0.01, 0.10}
FreqDroop_KUf underfrequency active 0.05 0.05 0.05 NA
power regulation
Response time of
FreqDroop_RspT
frequency active {0.1, 900.0} 5.0 5.0 5.0 Secs
ms
regulation
Over-Frequency Derate
The trigger frequency of
OvrFrqMin {60, 72} 60.03 60.03 60.49 Hz
over frequency derating
The end frequency of
OvrFrqMax {60, 72} 62.51 62.03 61.39 Hz
over frequency derating
The rate of over
OvrFrqSlop {0.01, 100} 30% 30% 0.16% %
frequency derating

71 / 98
APP Interface and Setting
The recovery frequency of
RecoveryFrq {58.8, 66} 59.95 59.96 60.00 Hz
over frequency derating
The recovery time of over
OvrFrqRecoveryT {0,1200} 60 60 60 Secs
frequency derating
OvrFrqDerating Over frequency derating
{Disable, Enable} Enable Enable Disable
Mode mode
under frequency derating
UFDerEn {Disable, Enable} Disable Disable Disable
enable
{ Disable dispatch
Disable Disable Disable
Active power control mode, Remote
CtrModeActivePw dispatch dispatch dispatch
mode dispatch mode,
mode mode mode
Local control}
Local Active power
PSetPercentLocal {0%,110%} 100% 100% 100% %
derating percent
ActPwrLowConfig 250kW active power
{Disable, Enable} Disable Disable Disable
Enab mode

Table 6-4 ActivePower Derating para. (IEEE1547 2018, Rule21 and ISO-NE)

ReactivePowerDerating
The ReactivePowerDerating interface is used to set the Grid reactive power derating
parameters, including PF parameters and Qu parameters, etc.

Figure 6-19 The ReactivePowerDerating interface


Note: The PF and Q value can be adjusted by remote software if the “Remote” is
selected.
PF Set: Set the PF value. Note: Change the reactive power by adjusting the

72 / 98
APP Interface and Setting

power factor.
PF(P) Curve:PF curve mode. Note: The power factor changes according to the
power change, as shown in Figure 6-20.
PF

(PFCurveP1,PFCurvePF1)
Inductive

1
(P%)

-1

Capacitive

(PFCurveP2,PFCurvePF2)

Figure 6-20 PF(P) Curve Mode


Q(u) Curve:Q(u) curve mode.
Note: The reactive compensation changes according to the grid voltage change, as
shown in Figure 6-21.
Q(%)

(QuCurveU2i,QuCurveQ2i)
Inductive

+ (QuCurveU1,
QuCurveQ1)

_ (QuCurveU1i, U(V)
QuCurveQ1i)

Capacitive

(QuCurveU2,QuCurveQ2)

Figure 6-21 Q(u) Curve Mode

In addition, the table listed below can provide detailed parameter information for you.

73 / 98
APP Interface and Setting
Grid code Grid code Grid code
Parameter name Description Range Unit
IEEE-1547 RULE-21 ISO-NE
PF(P) Power Factor Vs. Power

PFpCurveP1 Power of PF(P) point 1 {0,110%} 50% 50% 50% %

PFpCurvePF1 PF of PF(P) point 1 {-1,1} 1 1 1 NA

PFpCurveP2 Power of PF(P) point 2 {0,110%} 100% 100% 100% %

PFpCurvePF2 PF of PF(P) point 2 {-1,1} -0.9 -0.9 -0.9 NA

Trigger voltage of
PFpCurveTriVolt {100%,110%} 100% 100% 100% %
PF(P)
PFpCurveUndoVo The undo voltage
{90%,100%} 90% 90% 90% %
lt of PF(P)
Q(u) Dynamic Var Support

QuCurveU1 Voltage of Q(u) point 1 {100%, 110%} 102.00% 103.30% 107.99% %

Reactive power of Q(u)


QuCurveQ1 {-66%, 66%} 0% 0% 0% %
point 1

QuCurveU2 Voltage of Q(u) point 2 {100%,110%} 108% 107% 110% %

Reactive power of Q(u)


QuCurveQ2 {-66%, 66%} -44% -30% -50% %
point 2

QuCurveU1i Voltage of Q(u) point 1i {90% ,100%} 98.00% 96.70% 92.01% %

Reactive power of Q(u)


QuCurveQ1i {-66%, 66%} 0% 0% 0% %
point 1i

QuCurveU2i Voltage of Q(u) point 2i {80%, 100%} 92% 92% 90% %

Reactive power of Q(u)


QuCurveQ2i {-66%, 66%} 44% 30% 50% %
point 2i
The trigger power of
QuCurveTriPower {5%, 100%} 20% 20% 20% %
Q(u)
QuCurveUndoPo The undo power of
{5%, 100%} 5% 5% 5% %
wer Q(u)
Adjustment of rated
QuCrvVoltAdjustE
reference voltage of {Disable, Enable} Disable Disable Disable
nab
Q(U) curve
The rated reference
QuCurveVref {80.00, 110.00} 100.00% 100.00% 100.00% %
voltage of Q(U) curve
Adjust time of rated
QuCrvVrefAdjstT reference voltage of {0, 6553.5} 30.0 30.0 30.0 Secs
Q(U) curve
QuCrvOpenLoop Open Loop Time of
{0.1, 900.0} 5.0 5.0 5.0 Secs
T Q(U) curve
Qp Dynamic Var Support
Active power of Q(p)
QpCurveP1 {0,110%} 20.0% 20.0% 20.0% %
point P1

74 / 98
APP Interface and Setting
Grid code Grid code Grid code
Parameter name Description Range Unit
IEEE-1547 RULE-21 ISO-NE
Reactive power of Q(p)
QpCurveQ1 {-66%, 66%} 0.0% 0.0% 0.0% %
point Q1
Active power of Q(p)
QpCurveP2 {0,110%} 50.0% 50.0% 50.0% %
point P2
Reactive power of Q(p)
QPCurveQ2 {-66%, 66%} 0.0% 0.0% 0.0% %
point Q2
Active power of Q(p)
QpCurveP3 {0,110%} 100.0% 100.0% 100.0% %
point P3
Reactive power of Q(p)
QpCurveQ3 {-66%, 66%} -44% -44% -44% %
point Q3
QpCurveOpenLo Open loop response
{0.0, 900.0} 10.0 10 10 Secs
opRespTime time
Mode Setting
{Disable,
CtrModeReactive Reactive power control
Remote,Q,PF,PF Q(U) curve Q(U) curve Q(u) curve
Pw mode
(P),Q(u), Q(p)}
QSetPercentLoca Local Reactive power
{-66%,66%} 0.0% 0.0% 0.0% %
l derating percent

PFSetValue PF setting value {-1,-0.8},{0.8,1} 1.000 -0.950 1 NA

ReactivePowerOv Reactive power over


NA Disable Disable Enable
er matching

Table 6-5 ReactivePowerDerating Para. (IEEE1547 2018, Rule21 and ISO-NE)

75 / 98
APP Interface and Setting

LcdLess Basic Parameters


The LcdLess Basic Parameters interface is used to set the parameters as below.

500V

Figure 6-22 LcdLess Basic Parameters interface


The last three registers are configured as standard, i.e. the inverter supports IV curve
function, Automatic MdbsAdr assignment function and the Fault recording function.
However, almost all these parameters are read-only, that means you cannot change
them randomly. More information, please contact the after-sale service personnel.

Firmware Upgrade
As to the detailed procedures for firmware upgrade, Refer to specific instructions or
consult our after-sale support personnel.

6.1.3 Event
Touch the Event icon, it will go to the Event interface.
There are 2 submenus in the Event menu: “Current” and “History”.

76 / 98
APP Interface and Setting

Figure 6-23 Event interface

77 / 98
APP Interface and Setting

6.1.4 More

Figure 6-24 Turn ON/OFF interface

Manual Turn ON/OFF: Manual Power ON/OFF is required after Grid Code
setting or manual (fault) shut-down. Touch to submenu “More”. Then move the
cursor to “Turn ON” to start the inverter, the inverter will start up and operate
normally if the start-up condition is met. Otherwise, the inverter will go to stand-
by mode.
Normally, it is not necessary to Turn OFF the inverter, but it can be shut down
manually if Grid Code setting or maintenance is required.
Move the cursor to submenu “More”. Move the cursor to “Turn OFF” and ensure,
then the inverter will be shut down.
Automatic Turn ON/OFF: The inverter will start up automatically when the
output voltage and power of PV arrays meet the set value, AC power grid is
normal, and the ambient temperature is within allowable operating range.
The inverter will be shut down automatically when the output voltage and power
of PV modules are lower than the set value, or AC power grid fails; or the
ambient temperature exceeds the normal range.

78 / 98
Troubleshooting

7 Troubleshooting
LED Indicator Troubleshooting
LED display of the inverter is shown as follows:

Figure 7-1 LED display of the inverter


Indicators and their indications are shown in Table 7-1.
LED Icon Name Status Indication
PV Energized (control panel starts to
Working ON
POWER work)
power light
OFF No Power working
ON In grid-tied power generation state
Grid-tied Derated running status (light up 0.5s,
RUN operation Flash
light off 1.5s)
indication light In other operation status or power
OFF
supply not working
ON Grid is normal
Grid status
GRID Flash Grid fault (light up 0.5s, light off 1.5s)
indication light
OFF Power supply not working
ON Indicates a Fault
Slow Indicates Alarm (light up 0.5s, light off
Fault status flash 2s)
FAULT
indication light Protective action (light up 0.5s, light off
Fast flash
0.5s)
OFF No fault or power supply not working
ALL Upgrade
flash LCD or DSP upgrading
status
Table 7-1 LED Indicators and their meanings

79 / 98
Troubleshooting
If the LED light indicates any faults, please perform troubleshooting according to the
Table 7-2.

LED status Solutions


Neither the Power LED nor Turn off the external AC breaker.
the LCD screen lights up. Switch the DC switch to OFF position.
Check the PV input voltage and polarity.
The GRID LED is blinking. Turn off the external AC breaker.
Switch the DC switch to OFF position.
Check if the grid voltage is normal.
Check if the cable connection of AC side is
correct and secure.
The RUN LED lights off or Refer to Table 7-3 for troubleshooting.
FAULT LED lights up.
Table 7-2 Troubleshooting based on LED Lights
Common Fault and Troubleshooting
The inverter will be shut down automatically if the PV power generation system fails,
such as output short circuit, grid overvoltage/under voltage, grid over frequency/under
frequency, high environmental temperature or internal malfunction of the machine.
The fault information will be displayed on the APP interface.
The issue can be identified and resolved based on the definitions, possible causes
and recommended solutions listed in the following table. There are generally 3 types
of faults: warning, protection and hardware fault, see the detailed information in table
7-3. Proper analysis is recommended before contacting after-sales service.

Types Fault Codes Solutions


Definition:
Communication inside inverter fails
Possible causes:
Terminal block connecters of internal communication
wires have poor contact
Recommended solutions:
CommErr
Warning Observe for 5 minutes and see whether the alarm will be
Faults eliminated automatically;
Switch off 3-phase working power supply and then reboot
the system;
Contact after-sales service personnel.
Definition:
ExtFanErr
Cooling fan failure by visual check

80 / 98
Troubleshooting
Possible causes:
Fan is blocked;
Fan service life has expired;
Fan socket connecter has poor contact.
Recommended solutions:
Observe for 5 minutes and see whether the alarm will be
eliminated automatically;
Check for foreign objects on fan blades;
Switch off 3-phase work power supply and then reboot the
system;
Contact after-sales service personnel.
Recommended solutions:
Observe for 5 minutes and see whether the alarm will be
eliminated automatically;
Check for foreign objects on fan blades;
IntFanErr
Switch off 3-phase work power supply and then reboot the
system;
Contact after-sales service personnel.
Definition:
Internal alarm
Recommended solutions:
Warn0030
(EepromErr) Observe for 5 minutes and see whether the alarm will be
eliminated automatically;
Contact after-sales service personnel.
Recommended solutions:
Warn0040
The alarm is reserved now. The alarms in field can be
(DC SPD fault)
ignored.
Recommended solutions:
Observe temperature display;
Warn0050 Switch off 3-phase working power supply and then reboot
(TempSensorErr) the system;

Contact after-sales service personnel.


Recommended solutions:
Warn0100
The alarm is reserved now. The alarms in field can be
(AC SPD fault)
ignored.
Protect0090 Restart inverter by recycle both AC and DC switches.

81 / 98
Troubleshooting
(Bus over voltage) Wait for 1 minute between OFF and ON for all energy to
discharge.
If inverter cannot clear fault, replace inverter.
Raise limit of IDCmax (for example, 400mA) to allow
inverter more room to adjust in transient condition to cope
Protect0070 with imbalance of impedance and voltage between Grid
(Bus imbalance) phases
If after adjustment, alarm still occurs, replace inverter
Restart inverter by recycle both AC and DC switches.
Protect0030 Wait for 1 minute between OFF and ON for all energy to
(Inverter over discharge.
Current)
If inverter cannot clear fault, replace inverter.
Make sure the grid connection is good.
GridV.OutLim
Restart the inverter again.
Check the AC wires connection and AC frequency is in
range;
GridF.OutLim
Check the measurement value in LCD, if the grid
Protection
frequency is in limit, restart the inverter.
Faults
Restart inverter by recycle both AC and DC switches.

Protect0020 Wait for 1 minute between OFF and ON for all energy to
(Grid relay error) discharge.
If inverter cannot clear fault, replace inverter.
Confirm that external ambient temperature is within the
specified range of operating temperature;
Check whether air inlet is blocked;
Check whether fan is blocked;
TempOver
(Over-temperature Check whether the location of installation is appropriate or
protection) not;
Observe for 30 minutes and see whether the alarm will be
eliminated automatically;
Contact after-sales service personnel.
If the inverter can start up, then recalibrate.
Protect0180
(Sampling offset of If the inverter always report this alarm and cannot start up,
DCI) then replace inverter.

82 / 98
Troubleshooting
Raise limit of DCImax (for example, 400mA) to allow
inverter more room to adjust in transient condition to cope
with imbalance of impedance and voltage between Grid
Protect0170
phases
(High DCI)
After raising limit, if inverter cannot clear fault, replace
inverter.
Check wires of PV and ground:
Turn OFF AC switch to disconnect inverter from Grid.
Open fuse drawers to de-couple PV strings from each
other. Test strings with string test set.
Add one PV string at a time, and start up inverter to see if
alarm occurs.
IsolationErr
If there is no alarm, turn OFF AC switches to disconnect
(Low insulation
from Grid and add in the next string. Startup inverter
resistance)
again.
Continue until you can find the string that triggers the
alarm. Trace wirings of faulted string to find any leakage
to Earth Ground.
The parameter ISOResist in hidden menu can be
adjusted a bit.
Check wires of PV and ground:
Turn OFF AC switch to disconnect inverter from Grid.
Open fuse drawers to de-couple PV strings from each
other. Test strings with string test set.
Add one PV string at a time, and startup inverter to see if
GFCIErr alarm occurs.
(High leakage
current) If there is no alarm, turn OFF AC switches to disconnect
from Grid and add in the next string. Startup inverter
again.
Continue until you can find the string that triggers the
alarm. Trace wirings of faulted string to find any leakage
to Earth Ground.
Restart inverter by recycle both AC and DC switches.

Protect0150 Wait for 1 minute between OFF and ON for all energy to
(Mini MCU Fault) discharge.
If inverter cannot clear fault, replace inverter.

Protect0110 Restart inverter by recycle both AC and DC switches.

83 / 98
Troubleshooting
(BUS over voltage Wait for 1 minute between OFF and ON for all energy to
(firmware)) discharge.
If inverter cannot clear fault, replace inverter.
Restart inverter by recycle both AC and DC switches.
Protect0100 Wait for 1 minute between OFF and ON for all energy to
(Sensor fault of discharge.
leakage current)
If inverter cannot clear fault, replace Filt board or inverter.
Turn DC Switch OFF
Open Fuse holder to isolate PV strings
Reverse PVx
electrode Use meter to find out which PV string is connected in
(x=1,2…36/24/18) reverse polarity.
Correct PV string connection.
Contact after-sales service personnel.
Restart inverter by recycle both AC and DC switches.
High PVx Input Wait for 1 minute between OFF and ON for all energy to
current discharge.
(x=1,2…36/24/18)
Contact after-sales service personnel.
Check if its input voltage is within 1100V;
Restart inverter by recycle both AC and DC switches.
High PVx Input
voltage Wait for 1 minute between OFF and ON for all energy to
(x=1,2…36/24/18) discharge.
Contact after-sales service personnel.
Measure voltage at DC terminals in wiring box and
compare with reading in Measurement menu. PV
voltage must be less than 1000V in open circuit condition.

PVVoltOver If display reading is not within 2% of meter reading,


replace inverter.
If display reading is within 2% of meter reading, adjust
number of panel in the string.
Restart inverter by recycle both AC and DC switches.
Protect0230 Wait for 1 minute between OFF and ON for all energy to
(Inverter open- discharge.
loop self-test fault)
If inverter cannot clear fault, replace inverter.

84 / 98
Troubleshooting
Restart inverter by recycle both AC and DC switches.
Fault0130 Wait for 1 minute between OFF and ON for all energy to
(Bus over total discharge.
voltage)
If inverter cannot clear fault, replace inverter.
Raise limit of IDCmax (for example, 400mA) to allow
inverter more room to adjust in transient condition to cope
Fault0110 with imbalance of impedance and voltage between Grid
(Bus imbalance) phases
If after adjustment, alarm still occurs, replace inverter.
Restart inverter by recycle both AC and DC switches.

Fault0100 Wait for 1 minute between OFF and ON for all energy to
(Grid relay fault) discharge.
If inverter cannot clear fault, replace inverter.
Check wires of PV and ground:
Turn OFF AC switch to disconnect inverter from Grid.
Open fuse drawers to de-couple PV strings from each
other. Test strings with string test set
Hardware
Faults Add one PV string at a time, and startup inverter to see if
Fault0090 alarm occurs.
(High static
leakage current) If there is no alarm, turn OFF AC switches to disconnect
from Grid and add in the next string. Startup inverter
again.
Continue until you can find the string that triggers the
alarm. Trace wirings of faulted string to find any leakage
to Earth Ground.
Restart inverter by recycle both AC and DC switches.
Wait for 1 minute between OFF and ON for all energy to
Fault0060 discharge.
(CPLD Fault)
If inverter cannot clear fault, replace Control Board or
inverter.
Restart inverter by recycle both AC and DC switches.
Fault0020 Wait for 1 minute between OFF and ON for all energy to
(Bus over volt discharge.
Hardware)
If inverter cannot clear fault, replace inverter.

Fault0150 Restart inverter by recycle both AC and DC switches.

85 / 98
Troubleshooting
(Open-loop self- Wait for 1 minute between OFF and ON for all energy to
check failure) discharge.
If inverter cannot clear fault, replace inverter.

Table 7-3 Troubleshooting list

DANGER!
Please disconnect the inverter from AC grid and PV modules before
opening the equipment. Make sure hazardous high voltage and energy
inside the equipment has been discharged.
Do not operate or maintain the inverter until at least 5 minutes after
disconnecting all sources of DC and AC.

86 / 98
Maintenance

8 Maintenance
DANGER!
Before starting any product maintenance, the inverter should be stopped
running, the AC circuit breaker connected to the grid and the PV input on
the DC side shall be all disconnected, and then wait at least 5 minutes
before starting any operation.
These servicing instructions are for use by qualified personnel only.
To reduce the risk of electrical shock, do not perform other servicing other
than those specified in the operation instructions unless you are qualified
to do so.

Check Electrical Connections


Check all the cable connections as a regular maintenance inspection every 6
months or once a year.
Check the cable connections. If loose, please tighten all the cables acc. to
section 4.5 Electrical Cable Connection.
Check for cable damage, especially whether the cable surface is scratched or
smooth. Repair or replace the cables if necessary.
Clean the Air Vent Filter
The inverter can become hot during normal operation. Inverter uses built-in cooling
fans to provide sufficient air flow to help with heat dissipation.
In order to ensure good ventilation and heat dissipation of the inverter, it is necessary
to check the air inlet and outlet regularly.
Ensure that air inlets and outlets are not blocked and clean the vent with soft brush
or vacuum cleaner if necessary.
Replace the Cooling Fans
If the internal temperature of the inverter is too high or abnormal noise is heard
assuming the air vent is not blocked and is clean, it may be necessary to replace the
external fans.

IMPORTANT!
Please disconnect the AC & DC power before replacing the fans.

Refer to Figure 8-1 for replacing the cooling fans.


1. Use a No.2 Phillips head screwdriver to remove the 8 screws fixing the
fan tray.

87 / 98
Maintenance

Figure 8-1 Remove the fan tray and fan


2. Disconnect the watertight cable connector from cooling fan, as shown in
Figure 8-2.

Figure 8-2 Disconnect the watertight cable connector


3. Use a No.2 Phillips head screwdriver to remove the 4 screws fixing every
fan. (Figure 8-3)

88 / 98
Maintenance

Figure 8-3 Replace cooling fans


4. Place the new cooling fans on the fan tray, and fasten the cable on the fan
tray with cable ties. Tools required: No.2 Phillips head screwdriver, torque
value: 14~18kgf.cm
5. Reinstall the assembled fans onto the inverter. Tools required: No.2
Phillips head screwdriver, torque value: 16kgf.cm.
Replace the Inverter
IMPORTANT!
Make sure the AC breaker and DC switch of inverter are turned off.

Replace the inverter in reverse order relative to the installation steps in section 3.4
Install the Inverter:
1. Use a #3 Philips head screwdriver to remove the two M6X90 screws.
2. Remove the inverter from its mounting bracket with the coordination of 3
people.
3. Replace the new inverter on the mounting bracket and fasten it.

89 / 98
Technical Data

9 Technical Data
Datasheet
Model No. CPS SCH275KTL-DO/US-800
DC Input
Nominal input power 285 kW/260 kW
Max input voltage 1500Vdc
MPPT full load operating input
900-1300Vdc
voltage range (1)
MPPT voltage range @
500-1450Vdc
PF>0.99
Turn on voltage/Power 550V/500W
Nominal input voltage 1190 Vdc
Number of DC input channels 2 x 12/ 3 x 12
36 Fused Inputs, 3 per MPPT or 24 Non-Fused
No. of DC input
Inputs, 2 per MPPT (determined by SKU)
Max input current 26A x 12
Max input short-circuit current 50A x 12
DC Disconnection Type Load-rated DC switches
AC Output
Nominal AC output power(2) 275kW/250kW
Maximum AC output power 275kVA
Nominal AC voltage(2) 800Vac
Output voltage range 704-880Vac
Grid connection form 3Φ (Three phase)/ PE
Maximum AC output current
198.5A
@800Vac
Nominal power frequency 60Hz
Output frequency range 57- 63Hz
Power factor >0.99 (±0.8 adjustable)
Current harmonic distortion <3%
AC disconnect type -
Max. output fault current and
910A @11.6 ms
duration
Max. output overcurrent
300A
protection

90 / 98
Technical Data

System parameters
Topology Transformerless
Maximum efficiency 99.0%
China efficiency 98.5%
Standby/Night loss <5W

Environmental parameters
Protection level NEMA TYPE 4X
Cooling method Variable speed cooling fans
Operating temperature(3) -22°F to +140°F / -30°C to +60°C (derating from
+107°F / +42°C)
Operating humidity 0-100%, No condensation
Operating altitude(4) 2500m,No derating
Display and communication
Display LED indicators, WiFi + APP
Communication Modbus RS485/Ethernet TCP/IP/PLC
Structural parameters
Dimensions (WxHxD) (mm) 1050x690x400
Weight (kg) 119
Fused String Inputs(5) 20A fuses provided (Fuse values up to 30A
acceptable)
Safety
UL1741_2018; CSA-22.2 NO.107.1-16; FCC
Safety and EMC standards
CFR 47 part15.
IEEE1547_2003; IEEE1547_2014;
Grid-connected specification
IEEE1547_2018; CA Rule21; ISO-NE.
Table 9-1 Datasheet of the inverter

Notes:
1. When the DC input voltage is lower than 900V or higher than 1300V, the
inverter begins derating. Once the input voltage is between 900-1300V,
the inverter supports full output power. Derating curve of PV input voltage
are as shown in Figure 9-1.

91 / 98
Technical Data

INPUT VOLTAGE DERATING SCH275KTL


42℃ 45℃ 50℃ Vac=800V
280
270
260
250
240
230
220
210
200
190
180
OUTPUT POWER (KVA)

170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200 1250 1300 1350 1400 1450 1500 1550
INPUT VOLTAGE (VDC)

Figure 9-1 Derating curve with DC input voltage

2. When the grid Voltage is within 100%~110% of the rated output voltage,
the inverter output power may reach 100%. When the grid voltage is lower
than 100%, the inverter will limit the AC Output Current and the output
power will begin to derate, as shown in Figure 9-2.
OUTPUT AC VOLTAGE DERATING SCH275KTL
Vdc=1080V
42℃ 45℃ 50℃
280
270
260
250
240
230
220
210
200
190
180
170
160
OUTPUT POWER (KVA)

150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
680 700 720 740 760 780 800 820 840 860 880 900
GRID VOLTAGE (VAC)

Figure 9-2 Derating curve with grid voltage


3. When the ambient temperature is higher than 42°C, the inverter output
power will begin to derate, as shown in Figure 9-3.

92 / 98
Technical Data

Po/Pn

100%

80%

60%

40%

20%

42 45 60
Tamb( )
Figure 9-3 Derating curve with high temperature

4. The highest no-derating working altitude level is 2500m for this inverter,
its derating situation is as shown in Figure 9-4.
ALTITUDE DERATING SCH275KTL
42℃ 45℃ 50℃
280

270

260

250
OUTPUT POWER (W)

240

230

220

210

200
0 500 1000 1500 2000 2500 3000 3500 4000 4500
ALTITUDE (M)

Figure 9-4 Derating curve with working altitude


5. Fused string inputs only applicable to the SCH275KTL 36 input model.

93 / 98
Technical Data

P-Q Capabilities at Nominal Output Voltage


Inverter is capable providing reactive power of ±165kVAR at nominal grid voltage and
rated ambient temperature. Chart below details inverter reactive power capabilities
at various input voltages and various ambient temperature condition.

P-Q CURVE SCH275KTL


50℃ 45℃ 42℃ PF=(0.8) PF=(-0.8)
280
270
260
250
240
230
220
210
200
190
180
170
160
ACTIVE POWER (KW)

150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
-180-170-160-150-140-130-120-110-100 -90 -80 -70 -60 -50 -40 -30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180

Absorbing VAR from Grid REACTIVE POWER (KVAR) Providing VAR to Grid

Figure 9-5 P-Q Capabilities at Nominal Output Voltage

94 / 98
Technical Data

Measurement Tolerance
The data supplied by the inverter may differ from measurements taken by certified
measuring instruments (e.g. output meters, millimeters and grid analyzers). The
inverter is not a measuring instrument and has wider tolerances for the measurement
results it gives.
The general inverter tolerances are as below:
±5% for real-time measurements with output power below 20% nominal power
±3% for real-time measurements with output power above 20% nominal power
±4% for all statistical data

CPS inverter tolerances are specified as below:


Voltage tolerances: ±1%
Current tolerances: ±2%
Frequency tolerances: ±0.01Hz
Power tolerances: ±5%
Power factor tolerances: ±0.01
Time tolerances: ±1%
Temperature tolerances: ±2degC

95 / 98
Quality Assurance

10 Limited Warranty
The warranty policy of this product is specified in the contract; otherwise, the standard
warranty is 5 years.

For service, Chint Power Systems America will provide technical support. For
warranty terms, please refer to the CPS America standard warranty policy in place at
time of purchase.

96 / 98
Recycling

11 Recycling
Distributors or installers should contact the inverter manufacturer after removing the
inverter from the photovoltaic module and follow the instructions.

The inverter cannot be disposed of as household waste.


When the inverter's service life expires, please dispose of it in accordance with the
electrical waste disposal laws applicable to the installation location.
You can contact the inverter manufacturer or distributor for handling.

97 / 98
CHINT POWER SYSTEMS AMERICA CO., LTD.
Address: 1380 Presidential Drive, Richardson Texas 75081
Service Hotline: 855-584-7168
Email: [email protected]
Website: www.chintpowersystems.com

Shanghai CHINT Power Systems Co., Ltd.


Headquarters: Building 4, No. 3255, Sixian Road,
Songjiang District, Shanghai, China
Tele: +86 -21 -3779 1222 -6300
Fax: +86 -21 -3779 1222 -6001

This manual is subject to change without prior notification. Copyright is reserved.


Duplication of any part of this issue is prohibited without written permission.

98 / 98

You might also like