Power Generation - Handout
Power Generation - Handout
Power Generation - Handout
[email protected], [email protected]
Blog: www.sispowergeneration.blogspot.com
CR4 Forum : http://cr4.globalspec.com/member?u=14927
Mobile phone : ++62 81 311 422270. Jakarta. INDONESIA
Compiled by : Siswanto , March 2008,
Page 1 of 142
Telp : 081311422270, Email: [email protected]
Turbo / Hydro Generator Stator - Rotor Winding Construction
/ Repair / Inspections / Testing / Analyzing Handbook
2008
Preface
This Turbo / Hydro Generator Stator - Rotor Repair / Inspection / Testing /
Analyzing Hand Book is basically used engineer as guidance to selection of
insulation material specification for rewind or reinsulation of Stator - Rotor Turbo /
Hydro generator, with gas cooled or air cooled systems, Inspections and Testing.
This Handbook is compiled by Siswanto based on many literatures and our site
works projects experiences for services and inspections of turbine generators.
This handbook is an effort to provide as much information to our customers as
possible in order to select the best material for the optimal performance of the
generator. To got in complete material information you can found in our Material Specification Based On
NEMA LI-1 Standard Handbook, March 2008.
In practice during to performed our projects in Indonesia ( Rewinding / Reinsulation / Inspections /
Testing / Analyzing of Power generation) is require complex equipments and instruments, to provide that
all equipments and instruments we are collaborate with the independent companies ( Non Manufacture
Company) they support us by their Equipments / Instruments and Engineers.
Evaluation of the actual condition of a generator is a challenging task. Inspection has several limitation:
necessary to disassemble components, many areas cannot be seen even with the best tools including
robots, results are qualitative and highly operator dependent, time consuming. Each of the many tests
also has one or more of several limitations: cannot find local discrete weak areas without risk of insulation
breakdown, gives averaging results only, insensitive to vital deterioration mechanisms, requires
specialized equipment, personnel hazard.
However, the two approaches to generator assessment – inspection and test – are quite complimentary.
The combination of a good testing program and thorough inspection by a skilled and trained individual
can give a good assessment of almost all common forms of generator deterioration. On generators that
are important to system reliability, it is important that both test and inspection be performed, and that
neither be neglected nor superficially done.
In this paper inspection equipment and procedures will be discussed rather comprehensively but in
relatively non-technical terms. The paper will be heavily illustrated to show actual machine conditions on
most all of the known deterioration mechanisms on generators. This information should help those
responsible for inspecting generators to better understand the strengths and weaknesses of generator
inspection procedures, and provide operators of generators a more reliable inspection of the generator. It
should also assist owners of generators in implementing better maintenance practices, and thus reduce
maintenance costs and extend reliable life of the generator.
TABLE OF CONTENTS
TABLE OF CONTENTS PAGES
Cover 1
Preface 2
Table of content 3-7
I STATOR 8 – 26
A High Voltage Insulation system and construction 8 – 20
A.1 Winding in general 8–9
A.2 Winding construction 9 – 20
A.2.1 Coil material 11 – 12
A.2.2 Coil winding construction step by step manufacturing process 12 – 16
1. Copper strip (wire strand) 12 – 12
2. Strand / turn insulation 12 – 12
3. Loop winding 12 – 13
4. Roebbeling 13 – 15
5. Coil spreading 16 – 16
6. Coil shape check 16 – 16
7. Ground wall insulation 16 – 16
a. Insulation tapping system 16 – 18
- Wrapping by discontinuous method 16 – 16
- Wrapping by continuous method 17 – 17
8. Corona protection 18 - 18
9. Coil overhang 18 – 18
10. Coil pressing 19 – 19
11. Coil lead 19 – 19
12. Individual coil testing 19 – 19
13. Post curing 20 – 20
II ROTOR 27 – 43
A Rotor turbo Generator 27 – 40
A.1 Rotor Winding Parts 27 – 29
A.2 Coil Winding Configuration and Material 29 – 39
B Salient Poles 40 – 43
a. Introduction 74 – 74
b. Online Rotor Short Detection 75 – 79
c. The Causes of Shorted Turn 79 – 81
F VISUAL INSPECTION 82 – 118
F.1 STATOR 82 – 99
1. Frame Stator Extension 83 – 83
2. HV Winding & Flexible Bus Connection 83 – 83
3. End Winding, Connection Rings and Support 84 – 84
4. Blocking Condition and Ties 84 – 89
5. Surge Rings Insulation Condition 85 – 85
6. Surge Rings Support Assembly 85 – 85
7. Core Compression Nuts and Bolts 86 – 86
8. Out Going Cable Support 86 – 86
9. Insulation Condition 86 – 87
10. Tape Separation 87 – 87
11. Insulation Galling 87 – 88
12. Insulation Bulging 88 – 88
13. End Winding Blocking Coil and Ties 88 – 88
14. Corona Activity 89 – 89
15. RTD and TC 89 – 89
16. Fan Baffle Support Stud 90 – 90
17. Endwinding Support Hardware 90 – 90
18. Circumferential Bus Insulation 90 – 90
19. Bar Bottomed in Slot 90 – 90
20. Core Inspection 91 – 91
21. Lamination Bent or Broken 91 – 92
22. Wedge Mapping 92 – 98
a. Wedge Function 92 – 93
b. Acceptance criteria 93 – 93
c. New Stator wedge 94 – 95
d. Stator wedge Design 95 – 95
e. Material 96 – 98
23. Core Dampen Bars 98 – 99
F.2 ROTOR INSPECTION 100 - 118
F.2.1 ROTOR TURBO GENERATOR 100 - 110
1. Rotor Cleanliness 100 – 100
2. Rotor Wedge Inspection 100 – 101
3. Retaining Rings Visual Appearance 101 – 102
4. End Winding Blocking 102 – 103
5. Retaining Ring Removal Inspections 104 – 106
6. Rotor Forging NDT Inspection 106 – 107
7. Degaussing 107 – 110
8. Schematic Rotor Area Prone to Damage 111 – 115
F.2.2 ROTOR HYDRO GENERATOR / SALIENT POLES 116 – 118
1. Rotor Cleanliness 116 – 116
2. V Block Rotor inspection 116 – 116
3. Insulation Between Turn 117 – 117
4. Starting Bars (Damper Bars Winding ) 117 – 118
5. Bull Rings Segment and Brazing to Starting Bars 118 – 118
G GENERATOR PROJECT PROFILE 119 – 121
I. STATOR
A. High Voltage Insulation Systems and Constructions
A.1. Winding in general
This paper will focused for the Power Generation High Voltage, in generally has applied for Power Plant,
(Steam / Gas Turbine Generator or Hydro Generator).
Stator Winding for Hydro Generator is typical with Steam or Gas Turbine Generator, but Rotor Hydro
Generator, basically is different design, this paper will discussed both generators (Hydro and Turbine
Generator)
Insulation winding on the rotating electrical machines including generator are classified by thermal class.
Following table is thermal class on for the winding insulations,
The stator winding is made up of insulated copper conductor bars, following are copper conductors are
normally used for electrical machine winding.
Table. A.1 __Enamel Base Wire application
Single Dacron Polyester fused to the conductor and F Salient pole Winding, Magnet coil,
Glass varnished DC field, armature
Double Dacron Polyester fused to the conductor and F Salient pole Winding, Magnet coil,
Glass varnished DC field, armature
Single Fiber Glass Varnished Fiber glass filament F DC field winding
MICA .35mm Mica paper and Polyester Film F A.C Coil 6.6 / 11kV
bonded to conductor
® DUPONT Ref: Westral Insulated Products PTY LTD
Wedge Packing
Stator Core
Groundwall Insulation
Slot Separator
Transposition Filler
Asphalt based insulation systems are prone to develop a number of problems that are very specific to the
thermal class of insulation. A major disadvantage of the asphalt-based insulation is its poor thermal
resilience. When exposed to high temperatures, the asphalt develops a sharp drop in viscosity and thus
tends to migrate along to the coil to areas of less pressure, its can allowed flow out of the coil.
Thermosetting is better voltage breakdown and thermo class than asphalt-based insulation, Both
insulation systems were tapping on the copper bar conductor as many layers, number of layers of tape
depended on the tape thickness and rated voltage of the machine.
Better quality of material will allow increased voltage stresses in the ground wall, and its will resulting
in thinner insulation‟s with better heat dissipation, providing more space for increased copper
content.
Additional stranded covering by Mica Tape on to Enamel Conductor or Bare Conductor for strand / turn
insulation normally for winding with rated voltage ≥ 6 kV
For high voltage machine (11 kV and above) dedicated turn tape is normally applied over the strand
insulation consisting of resin rich mica tapes. Turn tape is then press bonded in special presses to
exclude all voids and ensure a correctly dimensioned wire pack.
3. Loop winding
Placed the copper real tensioners on each reel strands per turn, Loop can be wound with pin centers
Long leads supplied for coil connections to make winding connection easier and quicker for winder and
then dedicated turn tape insulation if required.
4. Roebeling
The currents normally flowing in large turbo generators can be in the order of thousands of amperes. Due
to the very high currents, the conductor bars in a turbo generator have a large cross-sectional area. In
addition they are usually one single turn per bar, as opposed to motors or small generators that have
multiple turn bars or coils. These stator or conductor bars are also very rigid and do not
bend unless significant force is exerted on them. The high current capacities of copper in the stator bars
generate significant heat. The losses due to the flowing currents are called I 2R losses in the winding.
Controlling the losses in the stator winding requires careful design consideration because of the variance
in magnetic field from the stator bore toward the slot bottom. The magnetic field tends to be more intense
toward the top of the slot, and therefore the top bars generally produce more heat than the bottom bars.
Within the bars themselves, there are also “eddy” currents flowing in each bar caused by the localized
leakage magnetic field. To reduce the effect of the eddy currents within each individual stator bar, the
conductors are made up of numerous copper “strands” . This is similar to the reasoning behind the stator
core being made up of laminations rather than a solid mass of steel. However, although the strands are
insulated from one another in the bar, they are eventually connected at each end of the stator bar.
Therefore additional circulating current could flow from top to bottom strands in a single bar. This is due
to the difference in the magnetic field from the top to bottom of the slot. To reduce the effect of the
circulating currents, the strands are “Roebel Transposed” in each bar.
Roebel transposition of the copper strands refers to the re-positioning of each strand in the stator bar
stack such that, it occupies each position in the stack at least once over the full length of the stator bar.
There are 360 and 540 degree Roebel transpositions found by and large. A 360 degree transposition
means that each strand occupies each position once over the length of the bar, and a 540 degree
transposition means that each strand occupies each position one and a half times. The 360 transposition
is generally done in the slot only and the 540 transposition is done out to the very ends of the stator bars,
and in the curved end-winding portion as well.
a b c
5. Coil Spreading
The manufacturing of coils using mica tape can be achieved by the discontinuous method ways: The
main insulation is applied to the un-stretched coil. Both slot section of the coil are wrapped with full width
mica tape and then pressed. The edge of insulation are cleaned , Mica –paper tape are then used to
insulated the end winding using special tape (example FEINMICAGLAS or CALMICA-FLEX – ISOVOLTA
Product) flexible end winding tapes. These tapes should join up flush with the end of main insulation
By using Mica tape ( example by CALMICAGLAS®- Isovalta product) in tape form the straight slot
section and overhang can be taped in a continuous taped sufficient distance around the first slot section
bend, . The conductor stack is taped half-overlapped is then pressed and the end winding cured in oven
if necessary with a varnish. During tapping process uniformly tape thickness and tension around in the
coil section must be maintained to achieve desired void free structure of correct density
The layer number of insulation tape can be calculated with based on to tape thickness after pressed.
Following is example to calculation of layer number for insulation winding (data taken form Insulation
material: CALMICA®, Product: ISOVOLTA
Wrapping of coils and bars with CALMICA® tape can be wrapped with tapping machine and or by hand.
The nominal thickness of CALMICA® is 0.16 mm as supplied and approximately 0.125 mm when
pressed.
The no. of insulation layer materials required can be calculated by referring to the technical data showing
values after pressing.
Table A.3___Table tapping thickness
Un KV ≤4 6 10 12
Example:
Un = 12 kV, the insulation thickness would be 2.8 mm.
Utilize the insulation CALMICA 0.16 mm with approximately 0.125 mm when pressed,
The no of layer required : 2.8 / 0.125 = 22.4 layer app. 23 layers must be applied on to coils winding
8. Corona protection
Corona protection are comprised of conductive tape, which is moulded during finale pressing cycle and
becomes an integral part of the coil side, integrally moulded corona tape systems limits of surface
resistivity are between 0.2 and 20 kΩ / square. On coils 11 kV and above normally applied by silicone
carbide grading paint with voltage dependent resistivity (VDR) from the slot end through the first bend.
9. Coil overhang
Coil overhang, normally are consist of multiple layer of ½ lapped fully cured mica tape and finished with a
resin rich sealing tape, which produces a water tight and smooth protective layer. A special high
molecular weight epoxy resin is applied between all layer of mica tape and is used to bond the basic
insulation materials together and fill many small voids. The resin is not cured during coil manufacturing
and therefore keeps flexibility in the coil overhang making the coil easier and quicker to install. The
complete winding requires final oven cure.
Steel mock stators for large post curing (large hydro), guaranteed
correct shape.
Turn-turn testing
All coils with more than 1 turn are turn to turn tested. This test the integrity of the insulation between
adjacent turn in the coil. Coils are tested with 0.2 µs rise time to the equivalent 1.79 x line voltage with a
minimum of 5 pulses.
The test equipment such as Surge comparison tester
Prototype testing
Some of tender requirements require extra prototype testing to be carried out
Test can include:
- Impulse testing of turn insulation for simulation of lightning strike
- Destruction testing of turn insulation
- Impulse or Power frequency testing of Main insulation
- Destruction testing of main insulation
- Accelerated Voltage endurance testing with or without thermal cycling
- Tan Delta testing at ambient temperature before and after a 900C temperature rise
Insulation Resistance
IEEE 43 - 2000
Standard for coil 6kV or above Standard for coils 5kV to 24kV
(above 11 kV testing to be agreed)
Impulse voltage between coil terminals and Impulse voltage between 2 terminals of same
earth (shield simulating core). coil.
2
Impulse voltage of 5 x (VL [ ] with front
3 Impulse voltage of (4 x VL + 5kV) x 0.65 with
time of 0.2 µs, repeated 5 times. front time of 0.2 µs, repeated 5 times
BS EN ( not
IEEE 1043 : 1996
available)
Coils to be hi-pot test at 110% of endurance voltage for 1 minute and Tan
Delta tested before endurance test.
Test conducted at air.
All conductors connected to constant stable voltage with protection, coil test
sample to be 250 cm or half bar length .
Heater elements 75% length of heater plates. Heater plates to be connected
to earth and clamped to have < 0.2 mm gap with the coil.
Test temperature range 1200C to 2400C. Temperature measured every 15
minutes with a maximum rise of 20C
Supply voltage measured at every 0.1 hr. the timer is stopped if no voltage.
Test completed when retest also fails.
Expected life if insulation statistically calculated.
This test a destructive test on five fully cured coils. This test can run for months.
A set-up of the voltage endurance test station Insulation failure during a voltage endurance test at 280 hours
Thermal cycling tests on stator bars and coils according to IEEE Standard 1310 -1995 and IEC standards
is to test the stator winding under multifactor (electrical, mechanical, and thermal stresses) stress aging
simultaneously to simulate normal service conditions or conditions as required. To assess the insulation
performance under thermal cycling stress as the machine experiences in service, The test insulation
system is heated and cooled at a prescribed rate for a number of cycles (e.g. 500 cycles). A number of
diagnostic tests on stator insulation can be conducted before and after a voltage endurance test.
This can be achieved by warming them to approximately 400C via an electrical welding machine or by
placing them in a covered enclosed heated with an electrical bar heater
Its recommended to stager throw the coils over 2 pitches when installing them, this should be performed
with extreme care so that the corners are not stressed.
Testing
Electrical tests are to be performed in the stated order after lifting each ¼ of the coils and after the coils
have completely fitted and wedges
Insulation Resistance Test ( for windings at 400C)
Apply test between each phase and the frame
The test should be conducted with a 2500 V Megaohmmeter tester or above. The reading is taken after
the test has been applied for 60 second
Minimum Resistance = 100 MΩ
(note : resistance halves with every 100C increased)
II ROTOR
A. ROTOR TURBO GENERATOR
of stopper)
I.7 Length +/- 690 Measured by roll meter
J End Winding blocking 7 variances Material NEMA G-11
J.1 Qty (exciter end) 105
J.2 Qty (turbine end) 106
K Sub Slot Insulation Material NEMA G-11
K.1 Length 5690 mm
K.2 Thickness 3.0 mm
K.3 Wide 34.42-34.8 mm
K.4 Cooling duct length 37.66 – 37.77 mm
K.5 Distance between cooling duct 38.7 – 38.88 mm
K.6 Locking (distance from end of exc end) 885 mm
K.7 Locking diameter 33.05 mm
1 Remarks :
2
3
4
5
6 1. Steel wedge
2. Non ferrous Damper bar
3. Creepage block / Top packer
4. Coil copper bar
5. Turn Insulation NOMEX 410
6. Turn insulation “double side B-
Stage” Nomex 410
7. Slot liner Glass-Nomex
8. Sub slot insulation / Bottom
packer
7
8
- Creepage Blocks
Creepage Blocks are long, thin strips of material that
span the length of the rotor slot.
The primary purpose of Creepage Blocks is to provide
an insulated separation between the conductors and
forging of a generator field during high potential
testing and operation in the field. Though not always
replaced during a field rewind, Creepage Blocks are
normally made from G-10 or G-11 and can be as long
as 18 feet. For creepage. Blocks longer than 8 feet in
length, a step splice can be used.
Using a special production process for homogeneous
Many Creepage Block designs require special
ventilation slots to match the ventilation
pattern of the copper bars and the turn
insulation.
Material Alternatives
The two most common materials for Creepage Blocking are NEMA G-10 and NEMA G-11 glass epoxy
laminates. These two grades are most common due to their very high compressive strength and
excellent overall mechanical strength. NEMA G-10 is a Class B (1300C) material and NEMA G-11 is a
Class F (1550C) material.
Turn insulation is available in slit coils, straight strips, ventilated strips, and J-strips. For
round corner field designs, JStrips or corner pieces that match the radius of the copper. Feathering the
ends of Turn Insulation prevents excessive build up when overlapping adjoining pieces.
Coil Turn Insulation is a thin strip of material used to insulate the copper turns from one another in the
rotor.
Material Alternatives
Description
Material Alternatives
Description
Gas cooled generators are designed to have the coolant
flow through the rotor slots and rotor coils.
Although this design theoretically creates a lower generator
operating temperature, it can also create winding difficulties
for the repair crew that must make sure all ventilation holes
line up properly.
The first layer of insulation in the rotor slot is the slot cell.
In gas cooled generators, the slot cell must have ventilation
holes that match the ventilation holes in the bottom of the
rotor slot.
Because fabricating a pre-formed, rigid slot cell is extremely
difficult, repair crews will utilize the three piece slot cell
system that is shown on the right. The Sub Slot Strip is a
long, thin strip of material with ventilation holes machined to
match the rotor ventilation holes precisely. It overlaps the
Slot Cells to ensure a good dielectric barrier.
Material Alternatives
Material for Sub Slot Strips must have excellent compressive strength and good machining
characteristics. As a result, most repair crews prefer NEMA Grade G-11 or G-10 FR-4. NEMA Grade G-
11 is used in Class F (155oC) insulation systems while NEMA Grade G-10 FR-4 is used in Class B
(130oC) systems
Coil Blocking
Description
Coil Blocking is used at each end of the rotor to insulate and support the coils at the end turns.
Coil Blocking must be extremely strong mechanically to resist the forces of copper growth and coil
shifting during operation.
In machines built prior to the early 1970's, asbestos phenolic was used as Coil Blocking in many designs.
Repair crews are forced to replace any components made of hazardous materials like asbestos phenolic.
Coil Blocking is normally replaced as a complete set.
This helps create proper weight distribution throughout the rotor, which is essential for balancing.
Material Alternatives
To date, the only suitable coil blocking material in the U.S. market is laminated glass epoxy (NEMA
Grade G-10 & G-11). While both G-10 & G-11 have performed well in this application, G-11 is a Class F
material and will retain its electrical and mechanical properties better at high temperatures.
Both materials have performed well as a replacement for asbestos phenolic. For additional information on
NEMA Grade G-10 and G-11, see the data sheets included at the rear of this handbook.
The primary function of Coil Blocking is mechanical - to support and separate the copper coils. In a great
majority of cases,
Coil Blocking will fail mechanically before it fails electrically. Several of OEM / customers are now
requesting G-11 for Coil Blocking because of its Class F (155oC) temperature rating. This often adds 20-
30% to the cost of the replacement components. It is our experience that in generators with an operating
temperature of less than 100oC, G-10 Coil Blocking provides more than adequate protection. G-10 is
rated as a Class B (130oC) material.
Rotor Slot
INSTALLMENT
Damper bars
Creepage block Steel Wedges
Winding Connections
1 2 3 4 5 6 7 8
Bottom connection
1 2 3 4 5 6 7 8
Slipring
Pole B
B. SALIENT POLE
Material Alternatives
Glass Polyester Laminated Sheet- Grade GPO-1 (H-755) and GPO-3 has been used for Pole Collars
for several years. It is generally the most economical material available.
Grade EHC- This special grade of Glass Polyester was developed specifically for use as Pole Collars. It
has a Class F (155° C) temperature rating and excellent compressive strength. As a Glass Polyester
material, it is also relatively economical. Refer to section III for more information.
Glass Epoxy Laminated Sheet- (NEMA Grades G-10 and G-11) For applications that demand
outstanding compressive and mechanical strength, G-10 and G-11 are the best materials available.
The only significant difference between these materials is that G-10 is a Class B material (130° C) and G-
11 is a Class F (155° C). Refer to section III for more information.
D FIELD INSPECTION
R01 Rotor cleanliness [ oil, dust, iron/copper dust ]
R02 Retaining Ring Visual appearance (RR)
R03 Centering visual appearance [RR]
R04 Fan Ring Visual appearance
R05 Fretting / movement at rings fits ?
R06 Fan Blades condition
R07 Bearing journals condition
R08 Balance weights/bolts codition
R09 End wedges [touching end rings, loose ?] RR
R10 Winding wedges [touching end rings, loose ?] RR
R11 Other wedges [overheated, loose, cracks ?] RR
R12 End-Winding condition [RR]
R12 Collector rings condition
R13 Collector insulation condition
R14 Brush spring pressure and condition
R15 Brush rig condition [clean, damaged ? Etc]
R16 Shaft voltage discharge-brush condition
R17 Inner / outer hydrogen seal condition [RR]
R18 Circumferential pole slot condition [RR]
SP : Items to be found only in Salient-pole machines
Thermal cycling may cause stresses and movement of whole bars (complete with groundwall insulation)
axially relative to their slot, or for quick changes in load the forces from differential expansion may cause
internal movement in the bar, between conductors and insulation. The copper windings are the main
heat-source when at high load, so these warm up faster than the surrounding iron and reach a much
higher temperature, besides having different coefficients of thermal expansion. Mechanical stress and/or
movement occurs therefore during changes of load.
There are large forces between conductors even with the currents of normal operation; separate
conductors within a bar, separate bars within a slot, and nearby connections in the end-winding region all
experience forces that alternate at twice the power frequency and that can damage the insulation in
regions where there is looseness that allows movement. During a short circuit the forces can be many
times greater, possibly causing internal damage that initiates longer-term degradation; the bars must be
very firmly held in place particularly in the end-winding regions where they do not have the stator iron and
slot-wedges to constrain them.
Electrical stress can cause electrical treeing, a change in the insulation material along channels in
the field, which may grow enough to cause a breakdown of the insulation.
Partial Discharge activity, although not rapidly damaging to mica insulation when discharges are
small, wears the binding material by the effects of local heating, ultra-violet light and production of
reactive chemicals such as acids and ozone.
The semi-conducting coating of the stator bars may wear out, due to the chafing from vibration in
the slot and from thermal expansion, or due to arcing from lamination short-circuits. The end-
winding stress-grading materials may also become less effective with time, leading to surface PD.
Tape-applied grading is found to be more durable than paints. Stress between windings in the
end-winding region, due to bad design or to movement, can also cause PDs. Conductive dirt on
the surfaces of the end-windings, in the high surface field, may cause PDs that wear the surface.
Different ageing effects respectively ageing mechanism caused by electrical, thermal, mechanical,
chemical or ambient loads change the properties of the electric insulation system and it comes to
an degradation of the material. In the final stage of the ageing the electric insulation breaks down
and the equipment falls out. For this reason different methods and measurements for the
evaluation of the condition are used.
60% is
critical
value
3. Winding DC Resistance
4. PDCA (Polarisation Depolarisation Current Analysis)
5. Tan Delta (Tip-up and Capacitance)
6. Off Line Partial Discharge Test with C – Coupler Sensors
C. 2.2 Rotor Test
1. Insulation Resistance Test
2. Polarization Index
3. Winding DC Resistance
4. RSO (Recurrent Surge Oscillation)
5. AC Impedance
6. PDCA (Polarisation Depolarisation Current Analysis
C. 2.3 Exciter
1. Insulation Resistance Test
2. Polarization Index
3. Winding DC Resistance
4. PDCA (Polarisation Depolarisation Current Analysis)
C. 3 Monitoring Level 3, When Generator Shutdown with partial parts removal ( top half cover
removal)
Inspections Level 2 , plus the following tests
1. Endoscopic Inspections for Endwinding Stator and Rotor underneath retaining rings
2. Endwinding Stator Partial Discharge with Probe
C. 4.2. Stator
1. Visual Inspection with Borrescope camera, incl core loose / tight inspections, compression bolts,
surge rings, support rings, end winding support, etc.
2. Frequency Domain Spectroscopy (FDS) test
3. Natural Frequency Test
4. Coupling Resistance Test
5. Non Linear Analysis Test
6. Stator Wedge Mapping
7. Digital ELCID Test
C. 4.4 Exciter
1. Visual Inspection
2. (for sliprings) Inspection to Collector Ring, Carbon brushes, Springs, Holder, etc
3. (for Rotating diodes), incl insp of Diodes, fuses, surge, etc
D. STATOR TESTING
<1000 500
1000-2500 500-1000
2501-5000 1000-2500
5001-12,000 2500-5000
>12,000 5000-10,000
Minimum Insulation
TEST SPECIMEN
Resistance
Interpretation
What constitutes a „good reading‟ and a „bad reading‟ depends on the nature of the insulation system and
the component (stator or rotor) being tested. Until 2000, the minimum R1 and the acceptable range for PI
was essentially the same for all types of stator winding insulation. However, it has been recognized that
the modern insulation materials in random wound and form wound stators have essentially no conduction
current (as long as there are no cracks or pinholes). Thus it is possible for a clean, dry, form wound
stator winding to have an R1 that is essentially infinite – greater than 100 GW. With an R1 of infinity,
calculations of a realistic PI are dubious. Such high R1‟s are not likely in systems made before the
1970‟s. Consequently, the maintenance person needs to establish the type of insulation used in the
winding, or at least the approximate age of the winding, before interpreting IR and
PI results.
summarizes how to interpret IR and PI results in stator and rotor windings. The distinction between older
and modern insulation systems was set at 1970, although this is somewhat arbitrary. Of note in this table:
1. If R1 is below the indicated minimu m, the implication is that the winding should not be subjected
to a hipot test, or be returned to service, since failure may occur. Of course if historical experience
indicates that a low R1 is always obtained on a particular winding, then the machine can probably
be returned to service with little risk of failure
2. The minimum R1 is the value corrected to 400C.Unfortunately, any more than 10-200C correction
is unlikely to be valid.
3. The minimum acceptable R1 is much lower for old stators than new stators, and it depends on
voltage class. For modern stators, the minimum acceptable R1 only depends on whether it is a
form wound or random wound stator.
4. For modern form wound stators, if a very high R1 is measured (say greater than 5 GΩ), then PI is
not likely to indicate anything about the winding. Thus, one can save time by aborting the test
after the first minute of testing.
5. If the IR or PI is below the minimum in a modern stator winding, it is only an indication that the
winding is contaminated or soaked with water.
6. If a high PI result is obtained on an older stator winding, then there is a possibility the insulation
has suffered thermal deterioration. This occurs because thermal deterioration fundamentally
changes the nature of the insulation, and thus the absorption currents that flow. The insulation
has changed in an asphaltic mica winding if the asphalt has been heated enough to flow out of
the groundwall.
In general, the IR and PI tests are an excellent means of finding windings that are contaminated or
soaked with moisture. Of course the tests are also good at detecting major flaws where the insulation is
cracked or has been cut through. In form wound stators using thermoplastic insulation systems, the tests
can also detect thermal deterioration. Unfortunately, there is no evidence that thermal deterioration or
problems such as loose coils in the slot, can be found in modern windings
Polarization Index [PI ] test is purpose, to evaluate how clean and dry a winding is. The Polarization
Index [PI] is the ratio between the resistance reading at 10 minutes and the reading 1 minute. Winding
with the low PI are usually relate to moisture and / or dirt contamination. The recommended minimum PI
values with refer to EPRI EL – 5036, or IEEE 43 -2000 are:
- Class A insulation : 1.5
- Class B insulation : 2,0
- Class F insulation : 2,0
* EPRI : Electric Power Research Institute
Rt2 (t1 k) When the resistance, Rt2 : of a winding has been determined by test at winding
Rt1 temperature,
(t2 k) t1 : the resistance may be corrected to a specified temperature,
t2 : the temperature test of winding
k : is 234.5 for 100% IACS conductivity copper, or 225 for aluminum, based on a volume conductivity of
62%
The AC hipot is similar to the DC hipot (section IV), with the exception that power frequency (50 or 60 Hz)
voltage is used. Sometimes 0.1 Hz AC is also employed, as described in IEEE 433. Both commissioning
(acceptance) and maintenance AC hipot versions of the test are in use. This test is most commonly
applied to form wound stator windings.
Interpretation
A winding either passes or fails the AC hipot. There is no other diagnostic information provided. If the
winding fails, as determined by the power supply circuit breaker tripping, then repairs, coil or winding
replacement is required.
Test Methods
There are several different methods for performing a DC hipot. Most are reviewed in IEEE Standard 95,
and the 2002 version highlights a new variation of the DC hipot called the DC Ramp test. Some of the
variations reduce the risk of a failure during the test, and some also give information of a diagnostic
nature.
For all types of DC maintenance hipot test methods, the critical decision to be made is the maximum test
voltage. For form wound stator windings, IEEE 95 gives guidance. It suggests that the maintenance hipot
should be 75% of the acceptance hipot level. NEMA MG1 and IEC 60034 stipulate that the DC
acceptance hipot be 1.7 times the AC hipot acceptance level of 2E+1 kV, where E is the rated rms
phase-to-phase voltage of the stator winding. After performing the arithmetic, it works out that the DC
maintenance hipot level should be about 2E. That is, a 4.1 kV winding would be tested at about 8 kV, DC.
This level was originally suggested since it approximates the highest likely over voltage in the motor that
can occur if a phase-to ground fault occurs in the power system. Consequently, a maintenance hipot just
reproduces, in a controlled, off-line fashion, the over-voltage a stator can see in service. The idea here is
that if the winding can survive this hipot, it is unlikely to fail in service due to a voltage surge created by a
power system fault.
Conventional DC HiPot
In the conventional maintenance DC hipot, a suitable high voltage DC power supply (available from many
suppliers) is connected to the winding, either at the switchgear, or at the machine terminals. The DC
voltage is quickly raised to the test voltage and held for either 1 minute or 5 minutes.
After this time, the voltage is quickly lowered, and the winding is grounded. If the insulation is sound,
there will be no high current surge, and the power supply circuit breakers will not trip. If the power supply
breaker trips, then it is likely a puncture has occurred, since the insulation resistance will have
instantaneously dropped to zero, which causes an „infinite‟ current to flow (by Ohm‟s law), and the power
supply can not deliver this „infinite‟ current. Circuit breaker tripping is an indication that the winding has
failed and winding repairs or replacement is required.
Step-Stress Hipot
A variation is to use the same supply as described previously, and gradually increase the voltage in
either equal or unequal steps. For example, the DC voltage can be increased in 1 kV steps, with each
voltage level being held for 1 minute before it is increased again. One then measures the DC current
after the end of each step (since by this time the capacitive current will have dropped to zero), and plots it
on a graph of current versus DC voltage. Ideally, the plot will be a line with a gentle upward curve.
However, sometimes the current increases abruptly above a certain voltage. This may be a warning that
the insulation is close to puncturing.
If the tester acts rapidly, the test can be aborted (voltage turned off) before a complete puncture occurs.
Experience shows that warning is likely if the flaw is in the endwinding, but little or no warning is given if
the flaw is within the slot. By carefully applying this test, a hipot failure may be avoided.
However, if the voltage at which the current instability was detected is below operating voltage, there is a
high risk in returning the winding to service without repairs.
In comparison with a traditional loop (ring flux) test, an EL CID test offers the following
benefits:
• Uses a portable excitation transformer instead of a large excitation transformer in a loop test to
considerably reduce test cost;
• Saves 30% of test time and labor cost of a loop test.
• Conducts low power testing (EL CID uses only 4% of the rated magnetic flux) to avoid further
damage to fault areas;
• Does not have safety concerns to test personnel;
• Records test data by a computer for trending of test results.
• Provides an easy and in-expensive test method to check the quality of a core repair or a re-
wedging operation.
a
b
Theory
Power factor testing of rotating machinery is a non-destructive AC test performed off-line at apparatus
frequency. When a 50 Hz voltage is impressed across generator stator insulation, the total current that
flows is similar to that of any capacitor. The total current has two components: a relatively large
capacitive current (ic) which leads the voltage by 90°; and a smaller resistive current (ir) which is in-
phase with the voltage. The dielectric of this simulated capacitor is the insulation system which is
embedded between two electrodes, the high voltage copper conductors and the stator iron core.
tan ∂ = ir / ic
The power factor is the Cos Ø = ir / it. Power factor is a dimensionless quantity and thus can be
compared amongst different volumes of insulation systems. It is a measure of the dielectric losses of the
insulation and provides valuable information about the insulation quality. Power factor is performed per
phase at incremental voltages starting at a voltage below corona inception and continuing up to the line-
ground voltage rating of the machine and possibly 20% over.
The leakage current IL through the insulation stator winding consist of capacitance current a loss current
as describe on figure.On the other hand capacitance “C” is filled up the gas to make energy loss in
capacitive is negligible.
Power factor Tip-up is defined as the power factor measured at the line-ground voltage minus the low
voltage power factor (typically performed at 100% and 20% of the line-ground voltage). Since all dry type
insulation systems contain voids, the power factor will increase with an increase in test voltage. The
increases in power-factor as a function of voltage are due to the ionization of the gas in the voids of the
insulation system. An insulation system with excessive voids will have a higher power factor tip-
up.Excessive voids may be due to the aging of the paper tape or of the bonding material in the insulation
system. Aging of these materials leads to a reduction of physical strength, and thus the production of
voids. Once excessive voids are present, partial discharge will occur which also damages the bonding
materials. The degradation of the insulation system may occur internally or on the surface of the coil/bar,
due to loose coils within the slot, deterioration of the semicond grading paint and/or inadequate coil
spacing .
12
Tan δ
10
Decreasing
Tan δ
ΔTan δ
Increasing
U / Un
Tan delta4 performed by increasing and decreasing test with 20% increment voltage.
A tape separation is a separation of tape covering the wall insulation of the coil due to axial expansion
and contraction of the conductors and the opposing forces of the slot applied to the wall insulation.
In some cases only the armor tape is separated, in other cases the mica-tape comprising the ground-wall
insulation is also affected , when this occur a few layer may be affected and the whole tape will move
creating “ a neck” in the coil.
PARTIAL DISCHARGE
Corona activity
Corona is define as the ionization of gas when exposed to an intense electric field , the discharge have a
wide range of frequencies [ 40 kHz to 100 MHz ].
Partial Discharge (PD) in the large generator application, is usually associated with the high voltage
stator conductor bars.
Partial discharges are a symptom and sometimes a cause of many types of stator winding insulation
system deterioration mechanisms. Thus it is not surprising that the on-line measurement of partial
discharges has been used to assess the need for maintenance in stator windings since .More
particularly, off line / on line PD measurement has been able to determine if the electrical insulation is
deteriorating due to loose coils in the slots resulting in insulation abrasion; thermal deterioration or load
cycling leading to insulation delamination; and electrical tracking caused by partly conductive
contamination of the endwindings .
Many methods are available to measure the PD activity in operating machines. The electrical techniques
all rely on monitoring the current or voltage pulse that is created whenever a partial discharge occurs.
Test method
PD probe tests performed on the generator to identify the bad bars. The probe scanned each slot to
pinpoint partial discharge locations in each slot. An HV transformer used to apply Un/√3 kV to each
phase of the generator. While one phase was energized with the other two phases grounded, the probe
scanned only these slots in the energized phase.
The PD levels in mA is the representative of corona
activities in the winding normally there is a concern over 20
mA, slot discharge can also develop surface discharge if
the air gap of coil to slot is big enough. Surface discharge
can produce excessive heat to cause further thermal
damages to the semi-conductive coating and the fillers.
Loose wedge also caused movement of the bars in the slots and abraded away the semi-conductive
coating, therefore resulting in slot discharges and surface discharges which can lean to insulation
failures.
Six capacitive couplers, two couplers per phase, installed in the stator generator. One coupler was
installed at the isolated phase bus close to the generator and the other at the isolated phase bus with
some distance from the first one. The two capacitive couplers on each phase work as a pair to eliminate
noise from outside the generator using the “time-of-flight” technique. A partial discharge analyzer (PDA)
can perform PD tests during normal machine operation. PD test results are displayed in the form of pulse
polarity, magnitude, number, and phase position. Subsequent data analysis provides further information,
such as, maximum PD values, normalized quantity number (NQN), historical trending of PD test results,
variation of PD activity with temperature and load, etc. The three-dimension graph the PD magnitude, PD
pulses per second and the PD position against the 50 or 60 Hz sine wave.
The positive and negative pulse distribution has an equal distribution, this indicates that there were partial
discharges within the groundwall insulation. The internal voids within groundwall insulation, created by
poor impregnation during manufacture or by other aging mechanisms during machine operation,
produced groundwall partial discharges under high voltage stress. Groundwall discharges can occur at
delaminations or areas where bonding material is incompletely cured.
Interpretation
The key measurement in a PD test is the peak PDmagnitude Qm, i.e. the magnitude of the highest PD
pulse. This can be measured in several units:
1. picoCoulombs (pC) if a laboratory PD measurement device is used. pC is a measure of the
apparent number of electrons that was involved in each discharge.
2. millivolts (mV), where the PD magnitude is measured with an oscilloscope or electronic pulse
magnitude analyzer (PMA). A PMA counts the number of PD pulses of each magnitude range.
3. milliamps (mA) if the PD pulses are measured with a high frequency (ferrite core) current
transformer and displayed on an oscilloscope.
4. decibels (dBm) if a frequency spectrum analyzer records the pulses.
The detected PD magnitude at the stator terminals of a PD pulse within the winding depends on a large
number of factors:
1. The size of the defect. In general, physics indicates that the larger the volume of the defect, the
larger will be the detected pulse.
2. The capacitance of the winding. If the winding has a large capacitance, the impedance to ground
at high frequencies will be very low. Thus most of the PD pulse current is immediately shorted to
ground, leaving little to be detected at the stator terminals.
3. The inductance between the PD site and the PD detector. The pulse will be attenuated as it
propagates through the winding to the terminal. In general, the further the PD site is from the PD
detector, the lower will be the magnitude detected at the machine terminal
These plus other effects make it difficult to define a „high‟ PD magnitude that indicates that a winding has
serious deterioration [6]. The PD test is thus a comparison test.
One can determine which phase has the highest Qm, and thus which phase has the greatest
deterioration. One can also compare several similar machines to see which has the highest PD. Finally,
one can compare the PD from the same stator over time, i.e. trend the data. In general, if the PD doubles
every 6 months, then the rate of deterioration is increasing.
Direct measurement of the PD pulses also enables one to measure how widespread the PD is. Studies
show that as many as 10,000 PD pulses may occur per second in a stator winding. It seems that a single
defect only produces at most 1 or 2 PD pulses per half ac cycle.
Thus if only a few hundred PD pulses are occurring per second, then there are only a few PD sites in the
winding, and the deterioration is localized. If there are 10,000 PD pulses per second, then there are
thousands of PD sites, and the deterioration is widespread. The pulse count rate can be easily measured
with a pulse magnitude analyzer, which is incorporated into most modern commercial PD analyzers.
If there is one dominant deterioration mechanism in a winding, the PD test can sometimes give the
approximate location of the deterioration within the groundwall.
1. If the positive PD pulses (which by definition occur in approximately the negative half of the AC
cycle) are larger than negative PD pulses, then it is likely the PD is occurring on the surface of the
coil (due to loose coils or defective semiconductive coatings).
2. If the negative PD is predominant, then the PD is most likely occurring at the copper.
3. If there is no polarity predominance or the positive and negative pulse distribution has an
equal distribution, then the PD is likely to be between the groundwall insulation layers. The
internal voids within groundwall insulation, created by poor impregnation during manufacture
or by other aging mechanisms during machine operation, produced groundwall partial
discharges under high voltage stress. Groundwall discharges can occur at delaminations or
areas where bonding material is incompletely cured.
Unfortunately there is no standardized measurement unit. In Europe, there is a tendency to use pC, in
spite of various standards indicating that the pC calibration procedure is not intended for use in inductive
apparatus [6]. In North America, mV and dB are more common
Pulse Discharge Maximum Ref To TOSHIBA TIL No. ECS -990506P (Technical Information Letter For
Preventive Maintenance of 125 and 250 MVA Turbine Generator.
Qmax = 10 000 pC for machine with voltage E ≥ 6.6 KV
Qmax = 4000 pC for machine with voltage E = 3.3 kV
Ref :
Testing of Large Electric Generator for Suitability of Services.Clyde V. Maughan P.E. Maughan
Engineering Consultant. Schenectady, New York
Qmax = 5000 pC, is interpreted as insulation deterioration.
Qmax = 500 mV, is interpreted as insulation deterioration.
IEC 60270, defines the repetition rate for Qm to be 50 or 60 pps
Figure References.
Document references Stator coils burnt out due to corona activities: Our Project Rewinding Stator
Generator ALSTOM 87.5 MVA / 11000 KV.
Stator filler burn-out due to PD activities Overheating on the stator bar due to corona
activities, figure was taken after stator wedge
removal (ALSTOM 87.5 MVA, PT DSS)
Premature winding failure may occur due to excessive end winding vibration. Large turbine generators
and hydro generators are most susceptible. Routine measurement of vibration amplitude and frequency
is important in detecting looseness, which can lead to fatigue and failure of copper conductors and
insulation systems.
Q1 T1 :_Charge storage: The charge storage takes place due to various mechanisms such as
Q2 T2 : Space charge polarization: The alignment of electric dipoles within the insulation on
application of electric field results in accumulation of charges in a region such as slots and in the
endwinding.This is called space charge polarization.
Q3 T3 : Interfacial polarization: The migration and accumulation of charge between two different
dielectrics that have different dielectric constants (such as that between machine insulation and oil
contaminant) gives rise to interfacial polarization.
Q3T3: Interfacial
polarization in
ENDWINDING region
Theory:
Shorted turn in the rotor winding are associated with turn shorts on the copper winding as opposed to
turn to ground faults. Rotor winding shorted turns or inter turn –turn shorts can occur from an electrical
break down of the inter turn insulation , mechanical damaged to the inter turn insulation allowing adjacent
turn to turn contact or contamination in the slot which allows leakage current between turn.
When the shorted turn occur, the total ampere-turns produced by the rotor are reduced, since the
effective number of turns are reduced by the number of turn shorted. The result is an increase in the
required field current in the rotor to maintain the same load point and an increase in rotor winding
temperature.At the location of the short, there is also a high probability of localized heating of the copper
winding and arcing damage to the insulation between the turns. This type of damage can propagate and
worsen the fault such that more turns are affected or the ground-wall insulation becomes damaged and a
rotor winding ground occurs.
Although shorted turn maybe exist in a rotor, in many cases the rotor will still run with out significant
effect on the operation of the generator. In addition short can occur anywhere in the rotor winding, but
they often found In the end winding under the retaining rings
There are number of factors which will influence the seriousness of any particular shorted turn-turn how
they will affect operation of the generator, these tend to show vibration on the rotor.
When a short on one pole of the rotor occurs, a condition of unequal heating in the rotor winding will exist
between poles, the unequal heating will cause bowing of the rotor and hence vibration
130.20
150.50
170.20
190.80
209.00
50.10
70.40
90.40
a. NTRODUCTION
Generator rotor thermal sensitivity is a phenomenon found on the generator rotor causing change in
vibration as the field The most likely problem with operation in the presence of shorted field windings is
excessive vibration.
Vibration in two pole rotors occurs due to uneven heating of the rotor forging. When turn shorts cause an
unequal distribution of active turns between poles, the amount of heat (I2R losses) between poles is also
unequal. This unequal heating will cause the rotor to bow and thereby introduce vibration. The coil
location of turn shorts is the key to determining if the rotor will experience vibration problems. In general,
unequal turn distribution in smaller coils will have a greater effect whereas unequal turn distribution in the
larger coils will have a lesser effect. For instance, one could expect vibration problems with only 5%
shorted turns in the # 1 coil of one pole of a seven coil rotor where no vibration problems would be
expected if the same percentage of turn shorts were present in the # 6 or # 7 coils.
One telltale sign of shorted turn induced vibration is the variation of vibration magnitude on increase in
load. Increased field current increases differential heating on the rotor forging, increasing bowing and
subsequent vibration. Some machines are observed to show the opposite effect. That is, the rotor
vibration decreases with increase in load. When this is the case, it is clearly the effect of compensation
balancing that has been done to offset shorted turn induced vibration levels at load.
In the past two decades, the use of on-line testing of generator rotor windings has surged. The benefit of
on-line testing has been recognized throughout the power generation industry and the installation of
airgap flux probe monitoring equipment has become almost standard procedure for utilities and OEM‟s.
Online testing for field winding shorted turns gives operators positive answers that can be used in trouble
shooting generator operational problems and helps determine whether rotor rewinding is required.
.
Prior to the widespread use of on-line air-gap flux probe testing, balancing programs would be performed
to compensate for shorted turn induced vibrations. If the results of the vibration testing indicated that
static weights were required at the pole centerline, it could be suspected that shorted turns were the
problem. As an example, one recently analyzed rotor was found to have shorts in the #1 coil of one pole
and the #2 coil of the opposite pole. Upon removal, the rotor was found to have two sets of balance
weights in place. One set on each pole had been placed to compensate for the shorted turn induced. The
balancing weights were placed to compensate for rotor bowing at full load, but actually throw the balance
off at lower loads when rotor bowing is not as great.
The new technology uses a simple permanently mounted air-gap flux probe positioned on a stator
wedge. The probe is sensitive to changes in radial flux density magnitudes as the rotor surface passes
by. This waveform is the time rate of change of the radial air-gap flux density waveform. Thus, it greatly
amplifies minute variations in the slopes. Analyses of the flux probe waveforms can detect critical
shorted turn conditions.
How it Works .
Step One
shorted turn detection/analysis system measures flux-density changes in the stator air gap. The flux
density reversals at each rotor slot are recorded at multiple loading conditions for later analysis. The flux
density at each slot, being a function of the number of active turns, is compared with its opposing pole
slot to determine the number of inactive or "shorted" turns.
Figure 1 shows the cross section of a 2-pole rotor and defines the stationary flux probe location. Figure
2 is a digitized waveform from a flux probe recorded during no-load conditions. The nomenclature of the
rotor and the associated waveform are identified.
Fig. 1 Fig. 2
Figure 1 - Field Nomenclature & Stationary Search Coil - 6 coils per pole
Figure 2 - Sample no-load data with field nomenclature - 6 coils per pole
Note that the voltage spikes are directly associated with the field slots. The flux probe (sensitive to radial
flux variations) provides voltage reversals at the centerline of the slots (labeled) and the centerline of the
teeth. These voltage spike magnitudes are a function of the active turns in the slots (slot leakage flux)
plus a distortion factor due to the air-gap flux density waveform. The success of the detection system
requires separating the slot leakage flux data from the distortion factors.
Step two
Figure 3 is test data from another generator taken
while the generator was at no load (open circuit
condition). Note the air-gap flux density waveform
passes through zero at the quadrature axis (90
degrees from the pole axis). The flux density
waveform can be obtained by integrating the flux
probe waveform. In the following displays the flux
density waveform has been inverted to minimize
overriding the pertinent search coil data (slot data
preceding the poles).
Fig 4 – Low Intermediate Load Shorted Figure 5 - High Intermediate Load Shorted
Turns - Pole B Coil # 6 Turns - Pole A Coil #4
Test and analyses of waveforms when the generator is under load, show that the distortion factors,
mentioned above, are minimal where the air-gap flux density crosses through zero (zero crossing). It
has been shown that the zero crossing traverses from the quadrature axis towards the #1 coil slots
leading the poles as load is increased. Figures 4 and 5 show test data from the same unit displayed in
Figure 3. Note that the zero-crossings in Figures 3, 4 and 5 shift from the quadrature axis to near the
6th and 4th coil slots, respectively. This phenomenon is due to power angle shifts with load. Thus, by
taking roughly 5 sets of test data from zero load to full load at unity power factor, excellent shorted-turn
detection sensitivity can be obtained at all the coil slots preceding the poles. This machine suffers
shorted-turns in coil # 6 on one pole and coil #4 on the other pole. As can be seen in the figures, these
shorted turns are defined best at the loads where the air-gap flux density zero-crossing is aligned with
these slots.
Step Three
Using digital data, a computer program can invert the slot voltage spikes "Y" values of one pole and
align them with the data from the other pole for a direct comparison. Figures 6 and 7 are examples of
computer analysis displays of the base data in Figure 4 - Low Intermediate Load. With this data in digital
form, the computer can also calculate voltage spike amplitudes and/or areas for use to estimate the
number of shorted turns in the effected coil. Two turn shorts out of six turns in coil #6 pole B were
identified at this load. Without distortion effects, two turn shorts equate to a 33.3% smaller voltage spike.
The actual test data produced a 26% and 30% reduction using voltage spike amplitudes and area
ratios, respectively. Partial shorted turns can not exist; therefore, engineering judgement suggests that
there are two shorted turns.
Figure 8 - Signature Analysis (25% Load) Figure 9 - Signature Analysis (70% Load)
Figures 8 and 9 are graphs of quantitative voltage spike amplitudes of all the coils for the generator
loads in Figure 4 and Figure 5 respectively. These type graphs for each load are signatures of the
winding condition when the data were taken. New test data, taken at the same loads, can be
compared to this data to improve the overall sensitivity for detecting shorted turns. For example, if
both pole A and B coils #6 had an identical number of shorted turns (2) during a retest, these original
graphs would help identify the condition.
Figure 10 shows an animation of real generator data
collected from no-load to a full load condition. The figure
is displaying overlays of the two poles' leading slots
signal, along with the location of the flux density zero-
crossing. Notice how the shorted-turn in coil #5-pole A is
visible when the flux density zero-crossing is near that
coil, but disappears when the flux density zero-crossing
moves away from the coil. This illustrates the need to
collect a series of load points designed to move the flux
density zero-crossing from the quadrature axis to the #1
leading coil slot in order to pick up potential shorted-turns
in each of the rotor coils.
Diminished Capacity
Excitation systems for generator fields have a certain amount of excess capacity. However, fields with
numerous shorted turns can sometimes require reducing full load values of MW‟s and/or MVAR‟s. In the
cases that we have observed that require load reduction, shorted turn indications are on the order of 5-
10% or greater. Machines in this category are candidates for a rotor rewind at the earliest opportunity.
cycles, the deformed copper can cause cracking in the turn insulation within the body or cause serious
misalignment of the end turns. If end turn misalignment is severe enough, the stacked turns of the
affected coil cannot support its own weight under centrifugal force. Most copper foreshortening problems
are the result
of using
materials
with
insufficient
yield
strengths.
3. Blocking Problems
Although not as
prevalent as other turn
short causes, end-
winding blocking
problems have been
the cause of a number
of shorted rotor
winding conditions that
we have observed over
the years. The purpose
of end-winding
blocking is to maintain
the alignment of the end-windings during operation. The cases missing blocks or blocks that have moved
out of position as shown in Fig. 6. Most blocking arrangements have been developed and/or refined by
manufacturers through experience with past problems. Service organizations should pay close attention
to the manufacturers recommendations for blocking installation during rewinding.
The distance blocks that provide the spacing in the generator field end windings must be spaced and fit
properly. Uneven spacing and/or fitting can cause non-uniform forces to be transmitted into the field
forging through the retaining rings or centering rings and, like all the other possible causes of thermal
sensitivity, make the rotor bow and change dynamic characteristics.
(See Figure.) Uneven distance block fitting will cause reversible vibration
F. VISUAL INSPECTION
F.1. STATOR
Important information on the general condition of the machine may be obtained from a general view of
the bore area and frame.
Inspection to be obtained for instance :
Excessive discoloration of paint of the paint on the casing, frame and bore indicate a probable
case of overheating
Presence of large amount of oil or dust
Excessive amount of iron powder mixed with oil and dust or found alone in the bore area tend to
indicate a loose of core
The end-winding of electric machine are subject to substantial movement during sudden change load,
vibration on normal operation. To minimize of end-winding movement the side coils are tied to a circular
rings are commonly called : “surge-rings or support rings “.
In large machine surge-rings are normally made of steel, and the steel are covered with several layer o
insulation. Te purpose of insulation on surge-rings is to minimize of a ground fault to the rings. The surge
rings insulation can deteriorate due to electrostatic discharge from the coil, is appear as electrical
tracking and/or burnlike marks on the insulation.
Cable support is designed to out going lead cable from generator stator winding to termination, loose on
the clamps support can occur due to vibration during machine in operation, loose support can caused
crack on the termination and lead cable insulation.
Brownish color is indicate overheating and white powder is indicate excessive vibration .
9. Insulation Condition
Thermoplastic, resin / epoxy polyester binder, insulation system when exposed temperature will become
dry and brittle, the exposed temperature may arise from overload condition, poor cooling, damage core
section, negative sequence current due to unbalance, etc.
Overload condition will show-up as an external discoloration of the insulation, brittle winding will show
powder accumulation arising from the movement of the shrunken coil within the slot.
The insulation degradation will be rapid growth-up if partial discharge activity are developed.
Inspection to be obtained for instance :
The sign of discoloration
The sign of greasing
Mechanical Electromagnetic
vibration
Partial Discharge
In some cases only the armor tape is separated, in other cases the mica-tape comprising the ground-wall
insulation is also affected , when this occur a few layer may be affected and the whole tape will move
creating “ a neck” in the coil.
Scarf joint represent a weak mechanical point in the structure of the coil, tending to separate under
thermal stresses .
12. Insulation bulging into Air Duct
Corona is define as the ionization of gas when exposed to an intense electric field the discharge have a
wide range of frequencies [ 40 kHz to 100 MHz ].
Corona activity in the rotating machine :
Corona at end winding ( End-
winding Discharge )
Corona at inside of the insulation
( Internal Discharge )
Corona at ground-wall insulation
( Slot Discharge )
Corona at overhang of winding (
Surface Discharge )
Corona activities on the endwinding
Endoscopic Inspection
Corona activities at endwinding can inpected with naked eyes, but corona at wall insulation caused by
slot discharge only can inspected by measurement and indoscopic method.
Top Bar
Bottom Bar
Partial discharge
Magnetic core
Resistance Temperature Detector ( RTD ) and or Thermocouple ( TC ) are mainly found in the winding,
cooling gas flow path, cooling water paths and bearings.
Winding temperature detector normally of RTD type are located between the coils in inaccessible
area.
However wiring to and from these devices is partially accessible for visual inspection, its should be tight
and secured along its path to the coils, frame and termination casing. If winding temperature detector are
faulty, they can be replaced during a major inspection. the damage of RTD are left in place with their
wires are disconnected or removed and the new RTD are taped and glued to the coils as close to the
damaged of RTD as possible, in generally they will be located in the end-winding.
Inspection to be obtained for instance :
The presence loose, broken for connection, path, cable,
Most of large machine (gas and or air cooled) are provide an baffle to directing of the cooling from and to
the fan. Fan baffle are supported stud is mounted on the tip of the core-compression finger with spaced
studs are placed around the bore
The fan baffle are subjected to continuous of vibration, stud and bolts should be inspected for stresses-
fatigue cracks, if broken during machine in operation they will probably causes extensive damage to the
windings or rotating elements particularly the fan blade.
Inspection to be obtained for instance :
The presence of red oxide
the presence of loose, broken cracks
In large synchronous machine, the end winding connection normally supported by support hardware.
Inspection to be obtained for instance :
The presence of powder deposit causes abrasion
The presence of loose, broken cracks
and broken may causes by rotor removal or inserting foreign material during machine operation.
Core Looseness
Core looseness usually will occur at the inside diameter near the ends of the core. However, it is possible
for looseness to be general and/or exist on the core outside diameter. If looseness is suspected, degree
of looseness can be evaluated by carefully inserting a knife blade between punchings at several
locations. If a 10-mil (1 mil = 0.0254 mm) blade penetrates more than round a quarter of an inch (6mm),
the core may be not sufficiently tight.
EXTREAME CARE SHOULD BE TAKEN NOT TO BREAK THE BLADE, LEAVING A PIECE IN THE
LAMINATIONS !
Looseness may be accompanied by dust generation, punching and spacer movement, or small pieces of
punchings flaking or cracking off.
Wedge inspection will be applied after rewedging its will be upgrade from the original (class B random
glass mat? ) to high pressure laminate glass cloth impregnated with high temperature epoxy resin NEMA
G11, include radial spring and fillers G-11
Measurement wedge
Body wedge
End wedge
b. Acceptance criteria
Following are threshold criteria of unsatisfactory wedge standard reference, Some literature and
manufacturer have a different criteria for unsatisfactory threshold of wedge to decision re-wedge , repair
or continues to operation. taken from IEEE Power Engineering Series and Toshiba Corporation TIL ECS
– 990506P.
Toshiba Corporation TIL ECS – 990506P for Preventive Maintenance of 125 and 250 MVA Turbine
Generator, recommend a threshold criteria as follow:
If there are 2 (two) consecutive looseness wedge in the same slot or if the percentage of
nonconsecutive looseness wedge is less than 30% from total number of wedges in a same slot,
the looseness wedges are applied the epoxy resin by brush between stator core and stator bar
wedge
If there are 3 (three) or more consecutive looseness wedges in a same slot, or if the percentage
of nonconsecutive looseness wedges reached 30% or more of total number of wedges in a same
slot, the all wedges in the slot shall be disassembled and replaced with new ones.
Note: Application of epoxy resin is only temporary countermeasure for the looseness.
Filler slip out on Gen GE 25 MVA Filler slip out and burn mark on the stator winding
MITSUBISHI 125 MVA.
Another indication of loose coils at least radial direction is movement out of the bottom and or top slot
filler .
Normally the filler are driven back (if possible) 0r broken at the end of core. In both cases they are
secured with resin-epoxy or RTV .
As with the movement of end wedge large number of fillers slipping out of core by several inches may
indicate a loose winding condition. However filler movement can also be result of elongation and
contraction of the coils due to thermal cycles, even in tight coils.
Inspection to be obtained for instance :
The presence of loose, slipping out at end portion of core
Top Ripple
Side Ripple
Over the years, the industry has developed several different wedge design variations based on the type
of generator manufactured. We can make a complete line of wedge designs based on our experience
producing wedges for nearly every type and manufacturer of generators. A sampling of common wedge
designs would include the following:
It should be noted that We does not possess nor utilize any OEM drawings in order to produce wedges
for our customers. We reverse engineer wedges and various insulating components based on samples
provided by the customers as well as our years of experience manufacturing these components.
e. Material Alternatives
Low Shrink Black Canvas - Used in the majority of large and medium sized GE generators. Exceed
the requirements of GE Spec. A50A341A. This material is the primary material used by Our Partner
Company in U.S for re-wedges of GE generators.
Post Bake Black Canvas – Used in smaller gas turbine generator designs, but does not meet the
much more demanding specifications for Low Shrink Black Canvas per GE Spec. A50A341A. Note that
Low Shrink Black Canvas and Post Bake Black Canvas are nearly identical in appearance, but Post Back
Black Canvas is dramatically lower in cost and dramatically different in performance.
Glass Epoxy Laminates (NEMA Grades G-10 & G-11) - Used in Westinghouse and ABB
generators. Also used in some GE generators as a replacement for Low Shrink Black Canvas.
Glass Polyester Laminates (NEMA Grades GPO-1,-2,-3) - Used in Allis Chalmers and Electric
Machinery generators as well as several different models of hydro generators.
Description
Top Filler Strips are strips of dielectric material that fit snugly between the stator winding bars and the
stator wedges. Their primary purpose is to fill space between the bar and the wedge and ensure a tight
radial fit. Top Filler Strips must have a slick surface for ease of strip placement and excellent mechanical
strength.
Material Alternatives
There are several materials that meet the requirements of the Top Filler application. The most commonly
ordered materials are NEMA Grades G-10, G-11, CE and LE. Many also use Top Ripple Springs, which
provide added radial pressure on the stator wedge. We stocks each of these materials in the following
thicknesses:
Unless the repair crew is trying to maintain a Class B insulation system, the most cost effective material
for this application is NEMA Grade CE. For Class F insulation systems, NEMA Grade G-11 is a common
choice. Top Ripple Springs are rated Class F and are used in either Class B or Class F insulation
systems.
Description
Side Filler Strips are strips of semi-conductive material that fits between the stator bar and the slot wall.
Material for this application is semi-conductive to ensure a secure contact between the outer corona
protection of the copper bars and the walls of the slot. This material must also be strong mechanically to
provide a tight lateral fit for the copper bar.
Material Alternatives
There are a wide variety of semi-conductive materials on the market. Each of the major U.S. laminate
manufacturers, as well as several European laminate manufacturers, have products to fit this application
for the generator repair industry. We stocks the following materials for this application
Frame vibration is also excited by unbalanced magnetic pull and by any vibration produced in the core.
There are known cases of vibration resonance occurring on the frame as a result of the frame having a
resonant frequency near line or twice line frequency. Resonant frequencies may be corrected by either
adding mass to the frame to bring the natural frequency down, or by stiffening the frame to drive the
natural frequency higher; the object being to move the frame natural frequency away from the exciting
frequencies by at least 10%.
Severe damage to the frame can occur by initiating cracks in the frame welds or in the frame members
themselves. Residual damage from the high vibrations associated with frame vibration is likely to be
transmitted to other components of the generator if the situation becomes severe.
Good core-to-frame coupling is required to ensure that the core and the frame move together. There is
evidence of numerous cases where core frames became “uncoupled” from the core and impacting
damage found at the core to key bar interface. Such vibrations were corrected in past by spring mounting
the core to the frame or installing a damping arrangement to “de-tune” the vibration modes.
Monitoring of frame vibrations can also be done with accelerometers mounted on the key bars, frame
ribs, or casing structure in strategic locations to determine the magnitude and phase of both radial and
tangential vibration modes. (Fig. below).
Tangential frame vibration bars, identify Excessive discoloration of paint of the paint on the
casing, frame and bore indicate a probable case of overheating, crack, bent etc.
1. Rotor Cleanliness
A rotor exhibiting numerous deposits of copper
powder indicate excessive movement of the DC
field coils, the excessive copper dust should alert
the inspector to possibility of the existence or the
development of shorted turn and / or ground fault.
Copper dust, iron dust, or any other telltale material
my concealed in a mixture of oil and dirt, can mask
cracks on the surface of critical components such
as wedges, fan hub and blades, retaining rings, bar
connection, etc. Heavy dust deposit affect to the
flow of the cooling gas or air, in affect de-rating the
machine.
Inspection to be obtained for instance :
The presence deposit copper or/and iron
powder
cracks on the surface of wedges, blade, retaining ring etc
as between the wedges themselves and between wedge to the rotor body, its important to note that any
sign of burning should be carefully investigation.
During systems oscillation or other type of abnormal operation, alternating current are established in the
body of the rotor.
These current tend to flow along to the rotor body (pole and teeth) , along the wedges and in the end
bells (retaining rings).
When bridging high resistance contact area, these current may give rise to very localized pitting of the
metal. These high-resistance area mainly found in the contact surface between the wedge and the slot,
between different wedge, and between wedge and retaining ring.
Pitting sign found on the rotor wedge due to alternating current are established in the body rotor
End wedge
migration to RR
The visual inspection on the retaining ring can be made as nondestructive examination (NDE) of the
several type available such as:
eddy current
acoustic
die penetrant
If the visual inspection of the surface reveals oxidation traces: - pitting, or other warning anomalies,
inspection of the inner side of the retaining rings might be advisable.
The endwinding blocking must support the winding to prevent permanent distortion, yet also allow for
thermal expansion. (See Figure.) The blocking materials that are currently utilized are epoxy glass
laminates. It is important to employ a service-proven blocking pattern that is compatible with the specific
endwinding geometry being used, since it is the blocking pattern which allows for thermal expansion
movement and ventilation. Also, special consideration must be given to the blocking and support of pole-
to-pole, coil-to-coil and terminal connectors. It should be noted that
asbestos was used extensively in older generation distance blocks and rotor insulation; maintenance/
repair processes must take this into account.
Some design features are added when high cyclic duty is anticipated. These include reliefs
in either the copper or body at the end of the coil slots to prevent armor damage, reliefs between the slot
armor ends, and the blocks just outside the body when rigid armors are utilized.
Some times centering is constructed with narrow space , hand touching and conventional camera is
inaccessible to inspect the endwinding blocking and other parts under retaining ring area. endoscopic
camera is require to inspection.
interpolar connection.
Rotor winding inspection by using endoscopic camera when retaining ring in place
RR being removed
NDT Inspection on the rotor, is designed to verify any anomalies on the retaining rings, centering
rings, rotor fans , journal shaft and bearings
Clean-up CRR‟s before NDT inspection before removal NDT inspection after CRR‟s
removal and NDT inspection removal
MPI test entire rotor body, no anomalies was found Steel wedges NDT inspection
7. Degaussing / Demagnetizing
Magnetism in Machinery, account for many machinery failures, in particular the deterioration of bearings,
seals, geras, couplings and journal has been attributed to electrical currents in machinery. Often on
machinery groupings contain no components with electrical windings or intended magnetism, ie. No
motors, generators. Manufacturers of electrical equipment have recognized and protected against the
effects of electrical shaft currents, bearing insulation has been utilized for such purposes.
There are number of ways in which steel machinery parts can become magnetized. Placing a part in a
strong magnetic field can leave substantial residual magnetism. Mechanical shock and high stressing of
some materials can also initiate a residual field.
Another that can creating residual magnetism is the passing of electrical current through the parts,
electrical system faults nearby heavy electrical currents such as rectified supplies and lightning,
electrostatic discharges, which are credited with causing bearing and seal pitting, the use of electrical
welding and heaters on pipes and other parts is common and if not used properly can induce residual
magnetism.
Magnetism in Machinery
Magnetism in machinery accounts for many previously unexplained machinery failures. In particular, the
deterioration of bearings, seals, gears, couplings and journals has been attributed to electrical currents in
machinery. Often, such trains or machinery groupings contain no components with electrical windings or
intended magnetism, i.e., no motors or generators.
Since the turn of the century, manufacturers of electrical equipment have recognized and protected
against the effects of electrical shaft currents. Bearing insulation has customarily been utilized for such
purposes.
Only since the mid-1970's has the need for protective measures on totally mechanical systems been fully
realized. The evolution of turbine and compressor systems towards high speeds and massive frames is
acknowledged as the cause for a new source of trouble from magnetic fields.
An electrical generator converts mechanical power to electrical power through magnetic fields. A
conventional generator rotor is essentially a magnet that is rotated in such a manner that its magnetic
field flux passes through coils of windings. Propitious placement of the coils in slots and other design
features result in the conversion of mechanical energy to electrical energy. This produces electrical
voltage and power in the windings that is then delivered to the electrical load or power system.
A turbine, compressor, or any other rotating machine that is magnetized behaves much the same way.
The magnetic steel parts provide a magnetic circuit, and are also electrically conducting so that voltages
are generated, producing localized eddy currents and circulating currents. These currents will be either
alternating or direct, and can spark or discharge across gaps and interfaces, producing sparking with
frosting, spark tracks, and, in the extreme, welding. They can cause increased temperatures and inflict or
initiate severe damage.
The generator action occurs as a result of relative movement between the magnet and the "conductors."
Hence, either the frame of a machine or the rotor can be magnetized, and the same action exists when
relative motion occurs between the rotating and stationary parts.
The magnetic field density in the air gap of assembled and operating motors and generators is designed
to be in the order of 7,000 to 9,000 gauss. These fields are capable of generating from watts to
megawatts of electrical power, depending upon the speed and size of the generator.
The field levels due to residual magnetism in turbomachinery occur not from design but from
manufacturing, testing, and environmental causes. They have been measured at the surface and in gaps
of disassembled parts of a machine at levels from 2 gauss to thousands of gauss. These increase
significantly in the assembled machine where the magnetic material provides a good closed path for the
magnetism and the air gaps between parts are reduced considerably. This combination can set up
conditions for generation of notable stray voltages and the circulation of damaging currents.
There are a number of ways in which steel machinery parts can become magnetized. Placing a part in a
strong magnetic field can leave substantial residual magnetism. Mechanical shock and high stressing of
some materials can also initiate a residual field.
Another method of creating residual magnetism is the passing of electrical current through the parts. In
increasing order of their effect, following are the known examples: Electric system faults; nearby heavy
electrical currents, such as rectified supplies and chemical processes; and lightning. Electrostatic
discharges, which are credited with causing bearing and seal pitting, can also be insidious sources in
magnetization of shafts.
The use of electrical welders and heaters on pipes and other parts is common and, if not used properly,
will induce residual magnetism.
Items that have been subjected to magnetic particle inspection often retain residual magnetism because
of insufficient or improper demagnetizing following the test.
Components that have come in contact with magnetic chucks and magnetic bases often display multiple
adjacent poles of a residual field.
8. Schematic rotor and the areas most prone to be damaged by the “skin-currents”.
Schematic representation of a turbogenerator‟s rotor and the areas most prone to be damaged by
the “skin-currents” generated during inadvertent energization event.
- Loss of field during operation. If for some reason the field current goes to zero while
the generator is connected to the system, the machine starts acting as an induction generator.
The rotor operates at a speed slightly higher than synchronous speed and slip-frequency currents
are developed.
These penetrate deep into the rotor body because they are of low frequency (this does not
represent the skin effect discussed in case, below). Severe arcing between rotor components and
heavy heating may result. The ends of the stator core also experience heating due to stray fluxes
in the end region, more severely than for operation at underexcited power factor. Protection is
commonly provided to prevent or minimize the duration of this mode of operation, by the so-called
loss-of-field relay.
The maximum of damage occurs while the speed is low and the large currents concentrate in a
thin cross section around the surface of the rotor (due to the skin effect). The temperatures
generated by the large currents, flowing in a relatively small cross section of the rotor, create very
large temperature differentials and large mechanical stresses within the rotor. Areas most prone
to damage are at the ends of the circumferential flex slots. Other areas are the wedges and in
the body-mounted retaining rings, the area where the rings touch the forging and the end wedges
(see Figs. below)
Rotor damaged due to skin effect current resulting by high reverse power attack from GSU 150 kv
Transformer
The initial stator current supplied from the power system will also be very high, but the most vulnerable
part of the generator is the rotor. As the rotor speed rises, stresses increase at the same time that the
temperatures of the stressed regions also increase due to circulating rotor body currents. Generators
have been destroyed from this event, as extreme temperatures reduce the component material strengths.
The internal rotor components are so weakened that they cannot handle the applied loads any longer.
The result can be that the rotor wedges or retaining rings fail. Therefore protection is needed for the
generator, even when it is out of service, to prevent or at least limit motoring from rest.
Overheated ends of the circumferential flex slots can over time develop cracks in the forging,
compromising its integrity. Heating of the ends of the stator core is strongly affected by stray magnetic
flux in the end region. This field is complex and is affected by the magnitudes and angular positions of
the current in the stator and rotor windings.
Temperature rise measured at the end of the rotor body during short-term unbalanced load operation. (I2
given in per unit)
Value of Permissible I2 Current in a Generator
Permissible I2 as % of
Type of Generator
Rated Stator Current
Salient Pole
With connected amortisseur winding 10
Without connected amortisseur winding 5
Cylindrical rotor
Indirect ly cooled 10
Directly cooled up to 950 MVA 8
951 – 1200 MVA 6
1200 – 1500 MVA
All large synchronous machines have (should have) installed protective relays that remove the machine
from operation under excessive negative sequence currents. To properly “set” the protective relays, the
operator should obtain maximum allowable negative sequence I2 values from the machine‟s
manufacturer. The values shown in Table above are contained in ANSI/IEEE C50.13 -1989 [2] as values
for continuous I2 current to be withstood by a generator without injury, while exceeding neither rated
MVA nor 105% of rated voltage. When unbalanced fault currents occur in the vicinity of a generator, the
I2 values of Table 4.2 will probably be exceeded. In order to set the protection relays to remove the
machine from the network before damage is incurred, but avoiding unnecessary relay operation,
manufacturers have developed the so-called (I2)2t values. These values represent the maximum time in
seconds a machine can be subjected to a negative-sequence current. In the (I2)2t expression, the
current is given as per unit of rated stator current. These values should be obtained from the
manufacturer. Table above shows typical values given in the standard .
AMORTISSEUR WINDING
Amortisseur winding for turbo generator Amortisseur winding for salient poles
Most modern rotors employ a damper or amortisseur or damping winding to dampen torsional oscillations
and provide a path for induced currents to flow. The amortisseur winding is essentially a separate
winding installed under the rotor wedges and retaining-rings that is connected similar to the squirrel-cage
of an induction motor. It produces an opposing torque when currents flow in it, and this helps dampen
torsional oscillations and add to the stability of the rotor during system stress events. In some instances,
where full-length aluminum wedges are used in the rotor, these may serve additionally as part of the
damper winding. Also some designs use the retaining-rings as the shorting connection at the end of the
rotor, instead of a dedicated component. Figure 2.46 shows a particular type of amortisseur. Photographs
of other types of amortisseurs can be seen in In addition to the above, the damper winding can help
divert negative-sequence and motoring currents from flowing in the rotor forging and causing overheating
damage. The negative-sequence rating or current-carrying ability of any rotor design is largely dependent
on the arrangement and effectiveness of the Armortisseur winding.
pole . these bars which are short-circuited at the ends, function like as induction machines squirrel cage
during start up operation, allowing machine to start from zero speed and go up nearly to full speed,
without the need variable frequency drives. In addition the bars provide electrical damping to oscillation
during the synchronous operation of the machine.
Starting (amortissuer ) winding is designed in accordance with the chosen mode of starting. For example:
some machine are designed to start at reduced voltage, while order the start at full voltage, operator error
such as higher then designed voltage starting , starting too often, prolonged asynchronous operation and
other abnormal conditions, can result in overstressing of the starting winding.
The shortcircuiting ring on one side of the cage broke loose from the bars, completely destroying the
entire end winding on that side of the stator winding.
Visual inspection is very effective in this case to assess the conditions of the damper bars. Discoloration
and / or deformation at test to abnormal operation. The bars should be checked for the crack or breaks.
In some cases removal of the paint in the region of the junction between the short bars and the short
rings allow for more effective visual inspection. If hairline cracks are suspected, non destructive (NDT)
with penetrating dye ink should be performed.
FIELD PROFILE
MATERIAL REQUIREMENT
A. Theory
Thermal sensitivity Generator rotor: thermal sensitivity is a phenomenon which may occur on the
generator rotor causing the rotor vibration to change as the field current is increased. In most cases, a
thermally sensitive rotor will not prevent a generator from running, but may limit the operation at high field
currents or VAR loads due to excessive rotor vibration.
There are many causes of high vibration on a Generator field. The most common are mechanical
unbalance, thermal sensitivity, misalignment and bearing degradation. Other causes include rubbing,
bent overhangs, rotor stiffness dissymmetry, out-of-round journals and other design deviations caused by
abnormal in service operation. Each of these causes has a predominate frequency and a characteristic
response. The cause of the vibration can be diagnosed by a thorough analysis of the vibration data. For
example, the most frequently observed cause of vibration is mechanical unbalance. This type of vibration
is synchronous; that is, the vibration frequency equals the rotor rotational speed frequency. It does not
respond to changes in operating conditions, such as generator load or field current. In most cases,
unless the unbalance is excessive, mechanical vibration can be corrected by balancing.
The remainder of this paper will only discuss generator field thermal sensitivity because it is generally the
least understood and is relatively common.
As a result, a field winding with this condition will limit load options for the owner since the generator will
not be able to operate over its full electrical capability. Figure below a plot of an irreversible field where
the vibration increased with field current but locked in at the high vibration level when the field current
was removed. through zero and the maximum vibration remains within acceptable limits.
The first part of the test is to apply constant field current to the field and then to vary the megawatt
loading on the generator from 15–60%. Detailed vibration readings as well as other key generator
parameters, such as generator voltage, currents and temperatures, should be monitored throughout all
stages of the testing.
Any significant changes in the generator vibration during any part of the testing should be noted. This first
part of the testing would correspond to moving from point 1 to point 4 on Figure below.
1. Shorted Turns
Shorted turns occur when there is a breakdown in the insulation between turns. They are the most
common cause of thermal sensitivity. Depending on the distribution and number of shorted turns, there
may or may not be an operating problem. Shorted turns in the coils adjacent to the poles are most
significant. When there are shorted turns in a field, the pole of the field that has the higher number of
shorted turns, there may or may not be an operating problem. Shorted turns in the coils adjacent to the
poles are most significant. When there are shorted turns in a field, the pole of the field that has the higher
number of shorts has a lower electrical resistance and, as a result, will be at a slightly lower temperature
than the opposite pole. Therefore, the higher temperature pole will elongate in the axial direction more
than the other pole and, as a result, the field will bow in that direction. (See Figure.) As field current is
increased, the amount of bowing will increase and the field vibration and phase angle will be similarly
affected. Shorted turns result in a reversible thermal sensitivity.
3. Insulation Variation
4. Wedge Fit
Significant forces from the field coils are transmitted into the retaining ring and centering ring as field
current is increased. If these rings are not installed properly, the field can be non-uniformly loaded and
cause the rotor to bow. Also, if the shrink fit is insufficient, these rings can move on their shrink fits and
cause a change in center of mass of the retaining rings. In this case, the field vibration signature will be
variable and the problem cannot be resolved until the light shrink is corrected. It should be noted that
rotors that have spindlemounted retaining rings as compared to those that are body-mounted are much
more susceptible to thermal sensitivity since the retaining rings are mounted on the more flexible spindle
section of the shaft. Because of this, for the same amount of axial force, a spindle-mounted rotor will bow
to a much larger extent. (See Figure above.) Movement of the retaining ring and/or centering ring can
cause reversible and irreversible vibration.
7. Tight Slots
This rare condition will usually occur
if, during a field rewind, the insulation
system is changed and/or the copper
is reused and is no longer flat due to
distortion caused by handling and
operation. It is important that the
required design clearance is
incorporated in a field rewind. Tight
slots will cause the copper to move unevenly in the axial direction as field current is applied and result in
rotor bowing. This condition typically causes the irreversible type of vibration.
D Project Experiences
1. BACKGROUND
Generator data:
Loading Data, :
Field Field
Loading Vibration
Data No Voltage Current
MW MVAR Volts Amperes BB5X BB6X
Data 1 93.4 30.0 204 854 NA NA
Data 2 95 10 183 875 0.108 0.076
3. Rotor Removal
Site finding
Rotor to be repaired with complete copper rotor winding to be removed, following items activities
were done being repairing:
NDT inspection on rotor forging and retaining rings, steel wedges, etc
Degaussing on rotor forging, journal shaft, bearings, turbine HP/LP, etc
a. Dynamic testing.
Generator vibration was monitor by ADRE Data Acquisition 208 Bently Nevada, and DCS
control, vibration was monitor during generator without excitation with air-cooled and H2 cooled,
and excitation with H2 cooled.When the generator has been energized the initial excitation
vibration level at bearing 6X No has no changed, bearing 5X decrease from 60 to 50 µ .
a.1. Testing Step 1. apply constant field current to the field and then to vary the megawatt
loading on the generator from 15–60%.Due to load system is to be set automatically, manual
setting to get a constant field current is difficult, based on this condition the load percentage load
level during test has been set as per operation systems required, however field constant current
setting is chosen as close to test recommendation.
Field constant current has been set by chosen with vary megawatt and megavar loading.
Field current test .
(test point 1 ) : 722 A, MW : 34.3 or 18.5% H2 pressure was increased from 15 PSI to 30 PSI,
the vibration level at bearing 6X was decrease from 106 to 82.2µ.
(test point 2 ) : 770 A, MW : 61 or 33%
(test point 3) : 763 A, MW : 75 or 40.5%
(test point 4) : 732 A, MW : 81.2 or 43.9%
Each step test has been maintained 6 hours until the vibration level reached steady. Maximum
vibration level during this test is 90µ <700 at bearing 6X, with initial vibration level is 82.2µ.˂660
This test is purpose to analyze of vibration change based on the MW load change
a.2. Testing step 2 : is to apply a constant megawatt load to the generator (approximately 60–
80%) and then raise field current to maximum rated field current. Each test point should be held
until steady state is reached. This test should then be reversed; that is, decrease field current
from its maximum value back down to the starting point.
This test to be done after test 1 has been finished, and the maximum MW load at test 1 to be kept
for this test and vary MVAR was set as much as can achieved with cos Φ = 0.8, starting from cos
Φ = 1, and than to be reversed with decreased the MVAR value back downward to the starting
point.
b. Static Testing
Static test was perform during rotor stand still especial for RSG was tested for dynamic when
rotor rotate at 2500 RPM and 3000 RPM.
Rdc at 28 C = 0.20945 Ω
Factory measurement at 1250C = 0.320
Site measurement after correction to 1250 C = 0.31691 Ω
% deviation based to factory measurement = 0.87%
If no discontinuities are present in the winding (due to grounds or shorted-turns), both traces will
be nearly identical and if inverted and summed, a single trace will be displayed as a horizontal
straight line, with a minor blip at the origin and an almost imperceptible ripple. Any significant
discontinuity arising from a fault will be shown as an irregularity on the summed trace. By
estimating the location of the anomaly on the screen, an inference can be made as to the
approximate location of the fault. For instance, large irregularities near the origin of the trace are
attributed to faults close to either end of the winding.
Ground
wire
RSG 220
Vac
Oscilloscope
Field Field
Loading Vibration
Data No Voltage Current
MW MVAR Volts Amperes BB5X BB6X
Data 1 93.4 30.0 204 854 NA NA
Data 2 95 10 183 875 0.108 0.076
Data 3 83 33.5 215 889 0.03 0.11
Vibration Record
0.66 mm
0.62 mm
vibration monitor by ADRE Data Acquisition 208 Bently Nevada, and DCS control
The two individual tests (TEST 1 and TEST 2) confirmed the generator rotor is stable and within an
acceptable standard. The OEM limit of between 2 to 3 MILS (0.50 to 0.75 mm) was not exceeded and
therefore this rotor cannot be considered „thermally sensitive‟.
TEST 2 was solely undertaken to prove to the customer that the generator rotor after the rewound
programme was not thermally sensitive. This test placed the rotor under an extremely high MVAR status
that is not normally experienced during normal operational requirements of the unit. Under a TEST 2
condition, any generator rotor will experience some form of vector change because of the high current
applied to the rotor but providing these vectors do not exceed the acceptable limit of 3 MILS, the rotor
can be classified as acceptable.
After TEST 2 the unit was returned to the customer since there was a need for commercial power. A
compromise was taken with the customer to complete the RotorPro test programme and then to have the
generator made available for commercial service. This compromise saw the unit been placed at 140 MW
and 0 MVARS for the next six hours, thereafter the unit was made available to the customer to meet their
commercial power demands.
Prior to completing this report, the writer was informed that the highest vibration level from the generator
during its commercial service was 0.10 mm. Since the unit meets the vibration specification requested by
the customer for the rewound programme it seems commercially pointless to undertake a further balance
exercise to „offset‟ the acceptable vibration vectors on this rotor. A single balance correction is expected
to take a few days and there is very possibility that more than one weight set correction will be
necessary.
Now that the unit has been in commercial service there is the possibility to complete the RotorPro test
programme, which requires the „over-speed‟ operation. This ‟over-speed‟ is to settle the CRR‟s and the
copper windings after which the vibration levels are re-valuated. Based on the vibration results after the
„over-speed‟ programme further recommendations will be proposed to the customer should this be
necessary.
5. START UP PROCEDURE
This is the recommended step-by-step procedure for the commissioning and balancing (if necessary) of
the generator rotor of the above-mentioned unit.
a. The run to speed (3000 rpm) of the unit is undertaken by the operator. The limitation during the
transient (i.e. run up behavior) event is the maximum shaft vibration level and this is not to exceed
180 micrometers peak to peak (0.18 mm). This run up event is to be undertaken with the
generator rotor in air, if this is possible. During this programme BRG 4, BRG 5 and BRG 6 will be
monitored with the portable analyzer.
b. If generator vibration levels reach 180 micrometers during the run up, the unit is to be run down
and another attempt made to reach full speed. This is to confirm vibration repeatability behavior.
c. If generator rotor requires balancing then a balance procedure will be undertaken. Calibration
weights need to be fitted to the fan balance ring and the unit returned to speed. Based on the
results of this calibration weight, additional weight corrections will be necessary and additional run
to speed of the unit until <180 micrometer pp is achieved. Depending on results, this procedure
may take between 2 to 4 individual runs. After balancing the stator is to be hydrogen filled and
customer to undertake their respective tests to ensure unit is ready to be placed into service.
d. Once the generator rotor achieves full speed with vibration levels (<180 micrometers pp), the rotor
is to remain in the unexcited condition to allow temperatures, pressures etc to stabilize.
Anticipated time will be approximately 2 hours.
e. Generator Load Conditions: Apply full machine voltage and wait for stabilization. Synchronize
unit and maintain the applied load for 6 hours.
f. Generator Load Steps: These steps are at 20% increments and maintain unity. Anticipated
time will be approximately 6 hours per step. Should vibration levels exceed 180 micrometers pp,
the load procedure is to be stopped and the generator rotor re-assessed. This may include a
reverse in the load programme and/or run down/run up event.
g. Generator load to be taken to maximum (185 MW) at unity through the 20% steps.
h. Unit to be handled over to Operations. If „over-speed‟ test (10%) is done then the vibration levels
to be re-assessed once the generator rotor is returned to full speed. Due to this large mass
across the poles, is expecting the copper windings to eventually shift and finally settle (either
during the load programme and/or the „over-speed‟) which will mean that the rotor will need to be
re-balanced.
E. References
This hand out has been compiled referring to the following reference literatures and project
experiences during inspection, repairing, rewinding of generators in Indonesia.
1. Private Project experiences during inspections, repairing, rewinding of power generation with
various capacity from 10 MVA up to 250 MVA, salient poles and cylindrical pole generator in
Indonesia.
2. IEEE 43 – 2000, Recommended Practice for Testing Insulation Resistance of Rotating Machinery
4. ANSI / EASA AR100-2006: Recommended Practice for Repair of Rotating Electrical Apparatus
10. Ronald J. Zawoysky, William M. Genovese. Generator Rotor Thermal Sensitivity -, GE Power
Systems,Schenectady, NY
11. Dean T. Roney, Ronald J. Zawoyski. Generator In Situ Inspection, , GE Power Systems,
Schenectady, NY
12. Ronald J. Zawoysky, Karl C. Tornroos, GE Generator Rotor Design, Operational Issues and
Refurbishment Option, GE Power Systems, Schenectady, NY
13. Dan Huynh and Terry Hill, Hugh Zhu. EXPERIENCE WITH DIAGNOSTIC TESTING TO
EVALUATE THE REMAINING USEFUL LIFE OF A HYDROGEN-COOLED GENERATOR ,
14. Hugh Zhu (Ph. D., P. Eng.), Vern Buchholz (P. Eng.) Insulation Condition Assessment of
Generators and Motors, Powertech Labs Inc, Canada.
15. TOSHIBA CORPORATION, Technical Information Letter For Preventive Maintenance of 125 and
250 MVA Turbine Generator (TIL No. ECS – 990506P)
16. Clyde V, Maughan P.E. Upgrading of Generators to Improve Reliability, Maughan Engineering
Consultants, Schenectady, New York 12306 USA.
17. Advanced Non Destructive Inspection For Turbine Generator Components. TOSHIBA
Corporation, Keihin Product Operation, Yokohama 230-0045, Japan.
18. DR Hassan EL-Kisky, Beant Nendra P.E. The Development And Evaluation Of Anti-Corona
Systems For High Voltage Rotating Machine, National Electric Coil, Inc, Brownsville,
19. Clyde V. Maughan P.E. Testing Of Large Electric Generators For Suitability Of Service, Maughan
Engineering Consultants, Schenectady, New York 12306 USA.
20. R. Albright, David J. Albright and James D. Albright. GENERATOR FIELD WINDING
SHORTED TURN DETECTION TECHNOLOGY, Donald Generatortech, Inc.
21. Bill Moore, P.E Refurbishment Solutions for Various Field Pole Problems,.. National Electric Coil.
800 King Ave. Columbus, OH 43212 614-488-1151
22. G. Klempoer. Rotor Shorted Turns – Detection and Diagnostics” EPRI – International Conference
on Electric Generator Predictive Maintenance and Refurbishment. January 20-21.2003 / Orlando
Florida.. Kinectric Inc.
23. G.C. Stone S. Iris Power Engineering , Cherukupalli B.C. Hydro, “A NEW IEEE STANDARD
FOR VOLTAGE ENDURANCE TESTING of HYDROGENERATOR STATOR COILS”.
24. Wood Group Generator Services, Inc. 1113 Camina Entrada Farmington, New Mexico 87401
MEGA-Pac™:Resin-Rich Windings.
25. ADWEL Corona Probe, Model PPM-97. ...off-line test for precise locating of sources of partial
discharge operation manual.
26. Sumatron. Inc. INSTRUCTION MANUAL GENERATOR ROTOR SHORTED TURN ANALYZER
FOR TURBO-GENERATOR DC-FIELD WINDINGS
27. Rotor Pro Power Generation Services Company Profile, Johannesburg, South Africa.
30. ISOVOLTA AG. A-2355 Wiener Neudorf. E ISOSEAL MF 0611_MF ME 2411 a, Electrical
Insulation and Rigid Lamination.
32. IEEE Std 112-1996 “Standard Test Procedure for Polyphase Induction Motors and Generators.
33. Greg C. Stone. Recent Important Changes in IEEE Motor and Generator Winding Insulation
Diagnostic Testing Standards. Copyright Material IEEE. Paper No. PCIC-2004-XX IEEE Fellow.
Iris Power Engineering. 1 Westside Drive, Unit 2. Toronto, Ontario M9C 1B2. Canada
Siswanto
Specilaist Engineer
Power Generation Services
Mobile phone : +62 81 311422270
Emails : [email protected]
[email protected]
Blog : www.sispowergeneration.blogspot.com
Member of CR4.globalspec.com
http://cr4.globalspec.com/member?u=14927