PD in GIS Webinar - 1
PD in GIS Webinar - 1
PD in GIS Webinar - 1
Switchgear Webinar
Hussain Al Juffairi
Abdulla Jawher
May 2024
1
Outline
Introduction
Testing Methods
Q & A Session
Our History
Introduction
1986 2019
1993 Today
Test laboratories
Repair shops Service Providers
Providing partial discharge solutions based on your purpose and need
Applications Assets
• Quality assurance & quality control (e.g. • Transformer
Factory acceptance test) • Rotating Machine
• On-site offline testing • Cable
• GIS
• On-site online testing • AIS
• Permanent monitoring
• Temporary monitoring
Our product portfolio covers various partial discharge needs
ICMcompact
ICMsystem
ICMmonitor
ICMmonitor Portable
GISmonitor
GISmonitor Portable
ICMflex
AIAcompact
PRPDreplay
HVcontrol
Our partial discharge measurement devices
ICMcompact ICMsystem
purpose
What makes our GISmonitor unique? Reasons for the portable version
• Specialized continuous monitoring device for GIS • Offered as a standardized solution
• Suitable for embedded + external UHF sensors available in • Portable monitoring version for GIS
the market For temporary GIS monitoring
Allows retrofitting of existing GIS • Flexible solution, can be used for several GIS at your
• Real-time monitoring of multiple assets with multichannel site
system • Up to 40 measurement channels in parallel
• Up to 120 measurement channels in parallel
• Available in different versions Recommended: HV testing on single or three phase
encapsulated GIS
Asset
• GIS
ICMflex AIAcompact
Customer groups
• Power utility
Customer groups • Heavy industry
• Repair shops* (on-site) • Service providers
• Service Providers* • Test laboratories
• OEM
• Power utilities Applications
• Heavy industry • On-Site offline test
• Test laboratories • On-site online test
ICMflex AIAcompact
Customer groups
• Power utility
Customer groups • Heavy industry
• Repair shops* (on-site) • Service providers
• Service Providers* • Test laboratories
• OEM
• Power utilities Applications
• Heavy industry • On-Site offline test
• Test laboratories • On-site online test
Introduction
Testing Methods
Q & A Session
Partial Discharge Basics
‘‘A localized electrical discharge that only partially bridges the insulation between conductors and which
can or cannot occur adjacent to a conductor’’ - IEC 60270
Present when voltage stress across the void exceeds the dielectric strength of the insulating material
Physical and chemical changes may happen to the insulator which produce emissions that we can detect
Occurrence of PD
• The local electric field must have reached the critical inception field (E > Ecrit )
• A free electron must be available to start the discharge avalanche
Outline
Introduction
Q & A Session
Partial Discharge Basics
Heat
Detection Methods Limitations
Optical
Introduction
Testing Methods
Q & A Session
Gas Insulated Switchgear
Heat
PD in GIS
PD caused by imperfection
PD in GIS
PD caused by imperfection
UHF Sensors
EFS
UHF Sensors
PRPD-Pattern at Pos 3
Acoustic Transmission of PD signals
Introduction
Testing Methods
Q & A Session
Sensitivity Verification
Sensitivity Verification
• 2 step procedure for acceptance
criteria
• Calibration like procedure
Described in:
• CIGRE TBA 654
• CIGRE TF 15/33.03.05
Downloadable on e-cigre.org
(account required but for free)
Sensitivity Verification
PD caused by imperfection
Sensitivity Verification
Sensitivity Verification
Acceptance criteria
Introduction
Testing Methods
Q & A Session
GIS Defects
Moving Particles
Floating Elements
Protrusion
Voids
Moving particles
Moving Particles
• Mostly enter GIS during assembly
• Can be lifted by electrostatic forces
and jump towards HV conductor
• Breakdown when it gets to close to HV
conductor or through contact with
insulators
Loose and floating elements
Phase B
Protrusions
Protrusion
•Mostly scratches due to insufficient
care during assembly
•Often low PD level
•The sharper the tip, the easier to
detect
•Shape of the tip can change over time
•Significant polarity effect
Voids
Void
PD inception requires a starting
electron
• Voids are difficult to detect
during acceptance testing
• GISmanufacturers have
implemented PD tests under x-
ray to detect voids
Aging effects in insulators
Contact Problem Faulty Insulator Disc Mobile Particles
Gating
Introduction
Testing Methods
Q & A Session
Instruments and Products
Permanent PD Monitoring
GISmonitor
Introduction
Testing Methods
Q & A Session