Quick Guide For Gas Detection System Salwico SW2020

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 2

QUICK REFERENCE GUIDE FOR USING OF GAS SAMPLING SYSTEM

“Salwico SW2020”

WARNING: BEFORE BALLASTING OF BALLAST TANKS, THE


CORRESPONDING SAMPLING-POINTS MUST BE DISCONNECTED
FROM THE SAMPLING SEQUENCE AT THE SW2020 CONTROL UNIT.
THIS WILL AVOID WATER BEING SUCKED INTO THE PIPES AND
DAMAGING THE SYSTEM
IMPORTANT NOTES:
THE PRESSURE AIR TO THE SYSTEM MUST NEVER BE SHUT OFF.
THE MANUAL SHUT-OFF VALVES SHALL DURING NORMAL
OPERATION AND WHEN THERE IS WATER IN THE WATER BALLAST
TANKS REMAIN OPEN. THIS WILL KEEP THE COUNTER-PRESSURE-
AIR FLOW AND AVOID WATER ENTERING THE PIPES.

1. DISCONNECTION
a. SAMPLING POINT LIST
b. CHOOSE A POINT BY ADJUSTING OF ARROW KEY
c. F2 (DISCONNECT)
d. F1 (DISCONNECT COMPLETION)
e. USE HOME KEY FOR RETURN TO THE MEASUREMENT OF ALL
SAMPLING-POINTS CONNECTED TO THE SAMPLING SEQUENCE

WHEN THE BALLAST TANKS ARE EMPTY, THE


CORRESPONDING SAMPLING-POINTS SHALL BE
RECONNECTED
2. RECONNECTION
a. DISCONNECTION LIST
b. CHOOSE A POINT BY ADJUSTING OF ARROW KEY
c. F1 (RECONNECT)
d. F1 (YES) FUNCTION OF PURGE DURING 2 MINUTES BEFORE
RECONNECTON
e. USE HOME KEY FOR RETURN TO THE MEASUREMENT OF ALL
SAMPLING-POINTS CONNECTED TO THE SAMPLING SEQUENCE

3. PURGE
a. SAMPLING POINT LIST
b. CHOOSE A POINT BY ADJUSTING OF ARROW KEY
c. F4 (PURGE)
d. USE F1 KEY OR ESC KEY FOR STOPPING
e. USE HOME KEY FOR RETURN TO THE MEASUREMENT OF ALL
SAMPLING-POINTS CONNECTED TO THE SAMPLING SEQUENCE

4. MEASURE OF SINGLE POINT


a. SAMPLING POINT LIST
b. CHOOSE A POINT BY ADJUSTING OF ARROW KEY
c. F3 (MEASURE) VARIOUS TIME IS ABLE TO BE INPUTTED
BUT 5 MINUTES IS SET AT FIRST
d. F1 (MEASURE)
e. PUSH DOWN ESC KEY TWO TIMES FOR STOPPING
5. CALIBRATION
a. GENERAL SETTING SET UP
b. CHOOSE “CHANGE LEVEL ACCESS” BY ADJUSTING OF ARROW
KEY
c. 3333 -> ENTER
d. CHOOSE SUB MENU (13a) adjust zero BY ADJUSTING OF
ARROW KEY
e. F1(CONTINUE) -> F1(ADJUST)
f. WHEN GET DISPLAY READINGS “ZERO CALIBRATION DONE”
PUSH ESC (EXIT)
g. CHOOSE SUB MENU (12a) calibration span on a gas detector BY
ADJUSTING OF ARROW KEY
h. F1 (CONTINUE)
i. SUB MENU (12b) for entering % of LEL (C3H8) (50 for C3H8) ->
ENTER
j. F1 (CONTINUE)
k. OPEN THE VALVE ON CYLINDER WITH TEST GAS
l. F1 (START)
m. WHEN THE LEVEL OF LEL WILL RICH 50% PUSH
F1(CALIBRATE)
n. WHEN GET DISPLAY READINGS “CALIBRATION DONE” PUSH
F2 (EXIT)
o. SUM MENU 12 (e) CLOSE THE VALVE ON CYLINDER WITH TEST
GAS
p. F1(EXIT)
q. CHOOSE SUBMENU 10 restart the system with saving of current
set up BY ADJUSTING OF ARROW KEY
r. F1 (RESTART)

6. ALARM RESET
a. IN CASE OF SEVERAL POINT ALARMS ARE HAPPENED
1) PUSH THE ALARM MUTE TO STOP BUZZER WHEN
BUZZER IS RINGING FOR ALARM
2) CHECK A ALARM PLACE AFTER PUSHING OF ALARM
LIST
3) PUSH DOWN THE ALARM RESET
b. IN CASE OF ONE POINT ALARM IS HAPPENED
1) PUSH THE ALARM MUTE TO STOP BUZZER WHEN
BUZZER IS RINGING FOR ALARM
2) PUSH DOWN THE ALARM RESET

7. FAULT RESET
a. PUSH DOWN THE MUTE TO STOP A BUZZER DURING BUZZER
IS RINGING DUE TO FAULT
b. PUSH DOWN THE FAULT LIST AND CHECK A KIND OF FAULT
c. PUSH DOWN THE RESET