30RB Catalogue
30RB Catalogue
30RB Catalogue
30RB 182-802
Nominal cooling capacity 175-760 kW
2
Remote management (standard) Remote management (EMM option)
A simple two-wire communication bus between the RS485 - Room temperature: permits set-point reset based on the
port of the Aquasnap and the Carrier Comfort Network building indoor air temperature (with Carrier
offers multiple remote control, monitoring and diagnostic thermostat)
possibilities. Carrier offers a vast choice of control - Set point reset: ensures reset of the cooling set-point
products, specially designed to control, manage and based on a 4-20 mA or 0-5 V signal
supervise the operation of an air conditioning system. - Demand limit: permits limitation of the maximum chiller
Please consult your Carrier representative for more demand based on a 4-20 mA or 0-5 V signal
information on these products. - Demand limit 1 and 2: closing of these contacts limits the
- Start/stop: opening of this contact will shut down the unit maximum chiller capacity to three predefined values
- Dual set-point: closing of this contact activates a second - User safety: this contact can be used for any customer
set-point (example: unoccupied mode) safety loop, closing of the contact generates a specific
- Demand limit: closing of this contact limits the maximum alarm
chiller capacity to a predefined value - Ice storage end: when ice storage has finished, this input
- User safety: this contact is connected in series with the permits return to the second set-point (unoccupied
water flow switch and can be used for any customer mode)
safety loop - Time schedule override: closing of this contact cancels
- Heat reclaim (option): closing of this contact allows heat the time schedule effects
reclaim mode operation - Out of service: this signal indicates that the chiller is
- Water pump 1 and 2 control*: these outputs control the completely out of service
contactors of one or two evaporator water pumps - Chiller capacity: this analogue output (0-10 V) gives an
- Water pump on reversal*: these contacts are used to immediate indication of the chiller capacity
detect a water pump operation fault and automatically - Compressor operation: this contact signals that one or
change over to the other pump several compressors are in operation
- Operation indication: this volt-free contact indicates that
the chiller is operating (cooling load) or that it is ready
to operate (no cooling load)
- Alert indication: this volt-free contact indicates the
presence of a minor fault
- Alarm indication: this volt-free contact indicates the
presence of a major fault that has led to the shut-down
of one or two refrigerant circuits
* contacts already supplied with the hydronic module option
3
30RB 182 - 802
Part load performances Part load performances in accordance with Eurovent
30RB LOAD CAP UNIT EER ESEER
With the rapid increase in energy costs and the care about
% kW kW kW/kW kW/kW
environmental impacts of electricity production, the power
182 100 173.3 59.3 2.92
consumption of air conditioning equipment has become an
75 130 37.6 3.45
important topic. The energy efficiency of a liquid chiller at
50 86.7 23.1 3.75
full load is rarely representative of the actual performance
25 43.3 10.6 4.10 3.71
of the units, as on average a chiller works less than 5% of
202 100 192.8 70.1 2.75
the time at full load.
75 144.6 42.2 3.43
50 96.4 25.2 3.82
The heat load of a building depends on many factors, such
25 48.2 11.5 4.19 3.74
as the outside air temperature, the exposure to the sun and
232 100 227.3 72.8 3.12
its occupation.
75 170.4 45.4 3.76
Consequently it is preferable to use the seasonal energy 50 113.6 25.5 4.45
efficiency, calculated at several operating points that are 25 56.8 11.4 4.98 4.30
representative for the unit utilisation. 262 100 263.4 97.5 2.70
75 197.5 59.8 3.31
ESEER (EUROVENT) 50 131.7 32.6 4.04
The ESEER (European seasonal energy efficiency ratio) 25 65.8 14.7 4.49 3.86
permits evaluation of the average energy efficiency at part 302 100 293.3 104.5 2.81
load, based on four operating conditions defined by 75 220 62.3 3.53
Eurovent. The ESEER is the average value of energy 50 146.6 36.1 4.06
efficiency ratios (EER) at different operating conditions, 25 73.3 16.2 4.54 3.96
weighted by the operating time. 342 100 327.5 120.9 2.71
75 245.6 71.5 3.44
ESEER (European seasonal energy efficiency ratio) 50 163.7 40 4.09
Load Air temperature (°C) Energy Operating 25 81.9 18.1 4.53 3.94
(%) efficiency time, % 372 100 358.5 127.5 2.81
100 35 EER1 3 75 268.9 73.7 3.65
75 30 EER2 33 50 179.3 42.4 4.22
50 25 EER3 41 25 89.6 19.4 4.62 4.08
25 20 EER4 23 402 100 391 146.6 2.67
ESEER = EER1 x 3% + EER2 x 33% + EER3 x 41% + EER4 x 23% 75 293.2 83.9 3.50
Note: Constant leaving water temperature = 7°C 50 195.5 48.3 4.05
25 97.7 21.7 4.50 3.93
432 100 417.6 150.6 2.77
75 313.2 86.7 3.61
50 208.8 51.4 4.06
25 104.4 24.6 4.24 3.92
462 100 446.8 168.5 2.65
75 335.1 93.3 3.59
50 223.4 55.5 4.03
25 111.7 27.2 4.11 3.86
522 100 506.3 191.4 2.65
75 379.7 109.5 3.47
50 253.1 63.7 3.97
25 126.6 31.6 4.01 3.77
602 100 596.2 218.1 2.73
75 447.1 121.9 3.67
50 298.1 70.8 4.21
25 149 31.9 4.66 4.09
672 100 651.8 240.6 2.71
75 488.8 137 3.57
50 325.9 78.8 4.14
25 163 36.1 4.52 4
732 100 704.2 265.1 2.66
75 528.2 148.2 3.56
50 352.1 84.3 4.15
25 176.1 40.6 4.33 3.96
802 100 757.7 288.1 2.63
75 568.3 162.6 3.50
50 378.8 92.4 4.10
25 189.4 43.9 4.31 3.91
Legend
Load % - Unit heat load
Cap kW - Cooling capacity
Unit kW - Unit power input
EER - Cooling capacity kW/unit power input kW
4
Options and accessories
Options No. Description Advantages Use
Condenser with anti-corrosion 2B Coils with copper tubes and aluminium fins with Improved corrosion resistance, recommended for 30RB 182-802
post-treatment Blygold Polual treatment marine, industrial and rural environments
Corrosion protection, traditional 3A Fins made of pre-treated aluminium (polyurethane or Improved corrosion resistance, recommended for 30RB 182-802
coils epoxy) marine, moderate or urban environments
Unit for low leaving water 6 Leaving water temperature from +3°C to -10°C All low-temperature applications: ice storage, 30RB 182-402
temperature cooling and process cooling applications
Unit for indoor installation with 12 Fans with available pressure Ducted condenser air discharge, optimised 30RB 182-802
discharge ducts condensing temperature control, based on the
operating conditions and system characteristics
Low noise level 15 Acoustic compressor enclosure Noise emission reduction 30RB 182-802
Very low noise level 15LS Acoustic compressor enclosure and low-speed fans Noise emission reduction 30RB 182-802
Grilles 23 Metallic grilles on all four unit faces (this option Improved aesthetics 30RB 182-802
includes the supply of enclosure panels)
Enclosure panels (for units with 23A Side panels on each end of the coils Improved aesthetics 30RB 182-802
copper/aluminium coils only)
Electronic starter 25 Electronic starter on each compressor Reduced start-up current 30RB 182-522
Winter operation down to -20°C 28 Fan speed control via frequency converter Stable unit operation when the air temperature is 30RB 182-802
between 0°C and -20°C
Winter operation down to -10°C 28B Twin-speed lead fan for each circuit Stable unit operation when the air temperature is 30RB 182-802
between 0°C and -10°C
Evaporator frost protection 41 Electric heater on the evaporator Evaporator frost protection down to -20°C outside 30RB 182-802
temperature
Evaporator and hydronic module 42A Electric heaters on the evaporator and hydronic Evaporator and hydronic module frost protection 30RB 182-522
frost protection module down to -20°C outside temperature
Partial heat reclaim 49 Partial heat reclaim by desuperheating the Free high-temperature hot-water production 30RB 182-802
compressor discharge gas simultaneously with chilled water production
Total heat reclaim 50 See heat reclaim option. Note: Unit equipped with Free hot water production simultaneously with 30RB 262-522
coils with copper tubes and aluminium fins chilled water production
Twinning 58 Unit equipped with an additional field-installed Optimised operation of two chillers connected in 30RB 182-802
leaving water temperature sensor, allowing master/ parallel with operating time equalisation
slave operation of two chillers connected in parallel
Main disconnect switch without 70 Factory-installed main electric disconnect switch in Ease-of-installation and compliance with local 30RB 302-802
fuse (standard for sizes 182-262) the control box electrical regulations
Main disconnect switch with fuse 70D Factory-installed main electric disconnect switch with Same advantage as main disconnect switch and 30RB 302-802
fuse in the control box reinforced anti-short circuit protection
Evaporator with aluminium jacket 88 Evaporator thermal insulation protection by Improved resistance to climatic aggression 30RB 182-802
aluminium sheets
Evaporator and hydronic module 88A Evaporator and water piping thermal insulation Improved resistance to climatic aggression 30RB 302-522
with aluminium jacket protection by aluminium sheets
Suction valve 92 Shut-off valves on the compressor suction piping Simplified maintenance 30RB 302-802
(discharge valve as standard)
Compressor suction and 92A Shut-off valves on the common compressor suction Simplified maintenance 30RB 182-262
discharge valves and discharge piping
High-pressure single-pump 116B See hydronic module option Easy and fast installation 30RB 182-522
hydronic module
High-pressure dual-pump 116C See hydronic module option Easy and fast installation, operating safety 30RB 182-522
hydronic module
Low-pressure single-pump 116F See hydronic module option Easy and fast installation 30RB 182-522
hydronic module
Low-pressure dual-pump 116G See hydronic module option Easy and fast installation, operating safety 30RB 182-522
hydronic module
Direct-expansion free cooling 118A See free cooling option. Note: Unit equipped with coils Economic chilled-water production at low outside 30RB 232-522
system with copper tubes and aluminium fins temperature
JBus gateway 148B Two-directional communications board, complies with Easy connection by communication bus to a building 30RB 182-802
JBus protocol management system
Bacnet gateway 148C Two-directional communications board, complies with Easy connection by communication bus to a building 30RB 182-802
Bacnet protocol management system
LonTalk gateway 148D Two-directional communications board, complies with Easy connection by communication bus to a building 30RB 182-802
LonTalk protocol management system
Energy Management module 156 See controls manual Easy connection by wired connection to a building 30RB 182-802
EMM management system
Fitted safety valves with sealed 196 Valve with sealed ball upstream of the safety valves Safety valve inspection and replacement facilitated 30RB 182-802
ball valve without refrigerant loss
Conformance with Australian 200 Heat exchanger approved to Australian code - 30RB 182-802
regulations
Storage unit above 48°C 241 Refrigerant charge stored in the condenser. Option Unit transport by container only possible with this 30RB 182-802
not compatible with MCHX coils; Cu/Al coils are option
required to store the charge.
5
Options and accessories
Options Description Advantages Use
Connection sleeve Piping to be welded with Victaulic connection Ease-of-installation 30RB 182-802
Energy Management Module See controls manual Easy connection by wired connection to a building 30RB 182-802
EMM management system
Scrolling Marquee Interface Remotely installed user interface (communication bus) Remote chiller control up to 300 m 30RB 182-802
Power cable connection side Side extension on the power control to allow a reduced Use of thicker power cables 30RB 302-802
extension cable bend radius
Physical data
30RB 182 202 232 262 302 342 372 402 432 462 522 602 672 732 802
Nominal cooling capacity* kW 173 193 227 263 293 328 359 391 418 447 506 596 652 704 758
Seasonal energy efficiency ratio kW/kW 3.71 3.74 4.30 3.86 3.96 3.94 4.08 3.93 3.92 3.86 3.77 4.09 4.00 3.96 3.91
(ESEER)
Operating weight**
Unit with option 15 kg 2082 2172 2202 2370 2990 3186 3234 3370 3922 4062 4240 5480 5658 6370 6550
Standard unit kg 1902 2002 2012 2180 2760 2956 2984 3110 3632 3772 3930 5120 5289 5960 6120
Refrigerant R410A
Circuit A kg 11.4 11.4 14.5 14.5 20 21 21 20.5 26 26.5 26.5 23 23 28 28
Circuit B kg 13.5 13.5 14 14 14 14 21 21.5 22 21.5 27.5 23 22.5 30 30
Circuit C kg - - - - - - - - - - - 24 28 25 33
Compressors Hermetic scroll, 48.3 r/s
Circuit A 1 1 2 2 3 3 3 3 4 4 4 3 3 4 4
Circuit B 2 2 2 2 2 2 3 3 3 3 4 3 3 4 4
Circuit C - - - - - - - - - - - 3 4 3 4
No. of control stages 3 3 4 4 5 5 6 6 7 7 8 9 10 11 12
Minimum capacity % 28 33 25 25 18 20 15 17 13 14 13 11 10 9 8
Control Pro-Dialog Plus
Condensers Grooved copper tubes and aluminium fins
Fans Axial FLYING BIRD IV with rotating shroud
Quantity 4 4 4 4 5 5 6 6 7 7 8 9 10 11 12
Total air flow l/s 18056 18056 18056 18056 22569 22569 27083 27083 31597 31597 36111 40625 45139 49653 54167
Speed r/s 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16
Evaporator Direct expansion, shell-and-tube
Water volume l 120 120 110 110 110 125 125 125 113 113 113 284 284 284 284
Max. water-side operating pressure kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
without hydronic module
Water connections (without Victaulic
hydronic module)
Diameter in 3 3 3 3 4 4 4 4 6 6 6 6 6 6 6
Outside tube diameter mm 88.9 88.9 88.9 88.9 114.3 114.3 114.3 114.3 168.3 168.3 168.3 168.3 168.3 168.3 168.3
* Nominal conditions: evaporator entering/leaving water temperature 12°C/7°C, outside air temperature 35°C, evaporator fouling factor 0.18 x 10-4 (m2 K)/W
** Weights are for guidance only
Sound levels
30RB 182 202 232 262 302 342 372 402 432 462 522 602 672 732 802
Unit with very low noise level option
Sound power level 10-12 W* dB(A) 84 84 85 85 86 86 87 87 88 88 88 89 89 89 90
Sound pressure level at 10 m** dB(A) 52 52 53 53 54 54 55 55 55 55 56 56 57 57 57
Unit with low noise level option
Sound power level 10-12 W* dB(A) 89 89 89 89 90 90 91 91 92 92 92 93 94 93 94
Sound pressure level at 10 m** dB(A) 57 57 57 57 58 58 59 59 60 60 60 61 61 61 62
Standard unit
Sound power level 10-12 W* dB(A) 91 91 91 91 92 92 93 93 94 94 94 95 95 96 96
Sound pressure level at 10 m** dB(A) 59 59 59 59 60 60 61 61 62 62 62 62 63 63 64
* In accordance with ISO 9614-1 and certified by Eurovent
** Average sound pressure level, unit in a free field on a reflective surface
6
Electrical data
30RB (without hydronic module) 182 202 232 262 302 342 372 402 432 462 522 602 672 732 802
Power circuit
Nominal power supply V-ph-Hz 400-3-50
Voltage range V 360-440
Max. connectable power cable section
Circuit A+B mm2 1x240 1x240 1x240 1x240 2x240 2x240 2x240 2x240 3x240 3x240 3x240 2x240 2x240 3x240 3x240
or 2x150 2x150 2x150 2x150
2
Circuit C mm - - - - - - - - - - - 2x185 2x185 2x185 2x185
Control circuit supply 24 V, via internal transformer
Maximum unit power input*
Circuit A+B kW 85 98 102 127 140 159 172 191 204 223 255 191 191 255 255
Circuit C kW - - - - - - - - - - - 96 127 96 127
Nominal unit current draw**
Circuit A+B A 113 129 135 167 185 209 226 251 269 293 334 251 251 334 334
Circuit C A - - - - - - - - - - - 125 167 125 167
Maximum unit current draw***
Circuit A+B A 146 168 175 219 241 274 296 329 351 384 438 329 329 439 438
Circuit C A - - - - - - - - - - - 164 219 164 219
Maximum start-up current, standard unit†
Circuit A+B A 353 375 348 426 448 481 502 535 557 590 645 535 535 645 645
Circuit C A - - - - - - - - - - - 371 426 371 426
Cosine phi, unit at nom. capacity 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84
Max. start-up current, unit with soft starter (UN)†
Circuit A+B A 283 305 277 356 378 411 433 466 489 521 575 - - - -
Circuit C A - - - - - - - - - - - - - - -
Stability for three-phase short circuits (TN system)
Unit with main disconnect without fuse††
Short-time current (1 s) - rms/peak value
Circuit A+B kA/kA 13/26 13/26 13/26 13/26 13/26 13/26 13/26 13/26 15/30 15/30 15/30 13/26 13/26 15/30 15/30
Circuit C kA/kA - - - - - - - - - - - 13/26 13/26 13/26 13/26
Unit with main disconnect with fuse‡
Current value, rms, circuit A+B kA NA NA NA NA 50 50 50 50 50 50 50 50 50 50 50
Current value, rms, circuit C kA - - - - - - - - - - - 50 50 50 50
* Power input of the compressor(s) + fan(s) at maximum unit operating conditions. Values given on the unit name plate.
** Nominal unit current draw at nominal conditions: evaporator entering/leaving water temperature 12°C/7°C, outdoor air temperature 35°C. The current values are given at 400 V nominal voltage.
*** Maximum unit operating current at maximum unit power input and 400 V.
† Maximum instantaneous starting current at 400 V nominal voltage and operating limit values with compressor in across-the-line start (maximum operating current of the smallest compressor(s) +
fan current + locked rotor current of the largest compressor).
†† Standard for 30RB 182 to 262 and option for 30RB 302 to 802
‡ Not available for 30RB 182 to 262 and option for 30RB 302 to 802
Operating limits
Evaporator water flow rate Operating range
30RB Min. water flow (l/s) Max. water flow* (l/s)
182 2.8 28.1
48
202 2.8 28.1
232 3 26.7
262 3.5 26.7
302 3.9 26.7
342 4.4 29.4
Entering air temperature °C
7
Dimensions/clearances
30RB 182-262
Legend:
All dimensions are given in mm.
Water outlet
NOTE:
Drawings are not contractually binding. Before
designing an installation, consult the certified
dimensional drawings, available on request.
8
Dimensions/clearances
30RB 302-522
30RB X Y
302-402 3604 200
432-522 4798 0
9
Dimensions/clearances
30RB 602-802
30RB X
602-672 5992 Legend:
732-802 7186 All dimensions are given in mm.
Water inlet
Water outlet
NOTE:
Drawings are not contractually binding. Before
designing an installation, consult the certified
dimensional drawings, available on request.
10
30RB 182-802
Condenser entering air temperature, °C
25 30 35 40 45
LWT
CAP COMP UNIT COOL COOL CAP COMP UNIT COOL COOL CAP COMP UNIT COOL COOL CAP COMP UNIT COOL COOL CAP COMP UNIT COOL COOL
°C kW kW kW l/s kPa kW kW kW l/s kPa kW kW kW l/s kPa kW kW kW l/s kPa kW kW kW l/s kPa
182 5 180 42 49 9 18 170 47 53 8 16 161 52 58 8 15 150 58 64 7 13 138 64 70 7 11
202 201 51 58 10 22 191 57 63 9 20 180 62 69 9 18 168 69 75 8 16 155 75 82 7 14
232 242 53 60 12 32 230 59 66 11 30 217 66 72 10 27 201 73 79 10 25 184 81 87 9 22
262 278 74 80 13 40 264 81 88 13 37 248 89 95 12 34 231 97 104 11 30 213 107 113 10 27
302 309 78 86 15 46 294 85 94 14 43 276 94 102 13 39 257 104 112 12 35 237 115 123 11 31
342 345 91 99 16 39 327 100 109 16 35 308 110 118 15 32 286 121 129 14 28 264 133 140 13 25
372 376 95 105 18 45 357 105 114 17 41 336 115 125 16 37 312 127 136 15 33 286 139 149 14 28
402 412 111 121 20 52 391 122 132 19 48 368 134 143 18 43 342 147 156 16 38 316 161 171 15 33
432 439 113 124 21 50 418 124 135 20 45 394 136 147 19 41 368 150 161 17 36 339 165 176 16 31
462 468 127 138 22 56 445 140 151 21 51 419 153 164 20 46 391 168 179 19 40 361 184 195 17 35
522 532 144 158 25 71 507 159 172 24 65 477 174 187 23 58 445 191 203 21 51 412 209 222 20 44
Cooling capacities
602 629 165 180 30 41 597 181 196 28 38 562 199 213 27 34 524 218 232 25 30 484 238 253 23 26
672 687 182 198 33 48 653 200 216 31 44 615 220 235 29 39 573 241 256 27 35 531 264 280 25 30
732 743 200 218 35 56 705 220 238 34 51 664 241 258 32 46 619 264 281 29 40 573 289 306 27 35
802 799 218 237 38 64 759 239 258 36 58 714 262 281 34 52 665 286 305 32 46 615 314 332 29 40
182 6 186 43 49 9 19 177 47 54 8 17 167 52 59 8 16 155 58 64 7 14 143 64 71 7 12
202 208 52 59 10 23 197 57 64 9 21 186 63 69 9 19 174 69 76 8 17 160 76 82 8 15
232 248 54 60 12 33 235 60 66 11 31 222 66 72 11 28 207 73 79 10 25 190 81 87 9 23
262 287 75 81 14 41 272 82 89 13 38 256 90 96 12 35 238 99 105 11 32 220 108 114 10 28
302 318 79 87 15 47 302 87 95 14 44 285 95 103 14 41 265 105 113 13 37 245 116 124 12 33
342 356 93 101 17 40 338 102 110 16 37 318 112 120 15 33 296 122 130 14 30 273 134 142 13 26
372 389 96 106 19 47 369 106 116 18 43 347 117 126 17 39 322 128 138 15 34 297 141 150 14 30
402 425 112 122 20 55 403 123 133 19 50 379 135 145 18 45 353 149 158 17 40 327 163 173 16 35
432 449 114 125 21 52 429 125 136 20 47 405 138 149 19 43 379 151 163 18 38 351 167 178 17 33
462 484 129 140 23 59 460 142 153 22 54 434 155 167 21 48 404 170 181 19 43 374 186 197 18 37
522 549 147 160 26 75 523 161 174 25 68 493 177 189 23 61 461 193 206 22 54 427 212 225 20 47
602 649 167 182 31 44 616 184 198 29 40 579 201 216 28 35 540 220 234 26 31 499 241 255 24 27
672 707 184 201 34 51 672 203 219 32 46 633 222 238 30 41 591 243 259 28 36 547 267 283 26 32
732 766 203 221 36 59 727 223 241 35 53 684 244 262 33 48 638 267 285 30 42 590 293 310 28 37
802 823 221 241 39 67 782 243 262 37 61 736 265 284 35 55 686 290 309 33 48 635 318 336 30 42
182 7 194 43 50 9 20 184 48 54 9 19 173 53 59 8 17 161 59 65 8 15 148 65 71 7 13
202 216 53 59 10 25 205 58 64 10 23 193 64 70 9 20 180 70 76 9 18 166 77 83 8 15
232 253 54 61 12 34 241 60 67 11 31 227 66 73 11 29 212 73 80 10 26 195 81 88 9 23
262 295 76 82 14 42 280 83 90 13 39 263 91 98 13 36 245 100 106 12 33 227 109 116 11 29
302 328 80 88 16 49 311 88 96 15 46 293 96 104 14 42 274 106 114 13 38 252 117 125 12 34
342 367 94 102 17 42 348 103 111 17 39 328 113 121 16 35 305 124 132 15 31 282 136 143 13 27
372 402 97 107 19 49 381 107 117 18 45 359 118 128 17 41 333 130 139 16 36 307 142 152 15 31
402 438 114 123 21 57 416 125 135 20 52 391 137 147 19 47 364 150 160 17 42 337 165 174 16 37
432 463 115 126 22 54 442 127 138 21 50 418 139 151 20 45 391 153 164 19 40 362 168 179 17 34
462 499 131 142 24 62 475 144 155 23 57 447 157 169 21 51 417 172 183 20 45 386 189 200 18 39
522 564 149 162 27 78 537 163 176 26 72 506 179 191 24 64 473 196 208 23 57 439 215 227 21 49
602 670 170 185 32 46 635 187 201 30 42 596 204 218 28 37 556 223 237 26 33 514 244 258 25 28
672 728 187 203 35 53 692 205 221 33 49 652 225 241 31 43 608 246 262 29 38 564 270 286 27 33
732 790 207 224 38 62 749 227 244 36 56 704 248 265 34 50 657 271 288 31 44 608 296 314 29 38
802 850 224 244 41 71 806 246 266 38 64 758 269 288 36 57 707 294 313 34 51 654 322 341 31 44
11
30RB 182-802
12
Condenser entering air temperature, °C
25 30 35 40 45
LWT
CAP COMP UNIT COOL COOL CAP COMP UNIT COOL COOL CAP COMP UNIT COOL COOL CAP COMP UNIT COOL COOL CAP COMP UNIT COOL COOL
°C kW kW kW l/s kPa kW kW kW l/s kPa kW kW kW l/s kPa kW kW kW l/s kPa kW kW kW l/s kPa
182 8 201 44 50 10 22 191 48 55 9 20 180 53 60 9 18 168 59 65 8 16 154 65 71 7 13
202 224 54 60 11 27 212 59 65 10 24 200 65 71 10 22 186 71 77 9 19 172 78 84 8 16
232 258 55 61 12 35 246 61 67 12 32 232 67 73 11 30 217 74 80 10 27 200 82 88 10 24
262 304 77 84 14 44 288 85 91 14 41 271 92 99 13 37 253 101 107 12 34 234 111 117 11 30
302 339 81 89 16 51 322 89 97 15 48 303 98 106 14 44 282 107 115 13 40 261 118 126 12 35
342 379 96 104 18 44 359 105 113 17 41 338 115 123 16 37 315 125 133 15 32 291 137 145 14 28
372 415 99 108 20 52 394 109 118 19 47 370 119 129 18 43 344 131 140 16 38 317 144 153 15 33
402 452 115 125 22 60 429 127 136 20 55 403 139 148 19 49 375 152 161 18 44 348 167 176 17 39
432 477 116 128 23 57 455 128 140 22 52 430 141 152 21 47 402 155 166 19 42 373 170 181 18 36
462 515 133 144 25 66 489 146 157 23 60 460 160 171 22 53 429 174 186 20 47 398 191 202 19 41
522 581 151 164 28 82 552 165 178 26 75 520 181 194 25 67 486 198 211 23 59 451 217 229 22 52
602 691 173 187 33 48 655 189 204 31 44 615 207 221 29 39 572 226 240 27 34 530 247 261 25 30
672 749 189 206 36 56 712 208 224 34 51 671 228 243 32 46 626 249 265 30 40 581 273 289 28 35
732 816 210 228 39 65 773 230 248 37 59 726 251 269 35 53 676 274 292 32 46 626 300 317 30 40
802 878 228 247 42 75 832 250 269 40 68 780 273 292 37 60 728 298 317 35 53 674 326 345 32 46
182 10 217 45 52 10 25 206 50 56 10 22 194 55 61 9 20 181 60 67 9 18 166 66 72 8 15
202 239 55 62 11 30 227 60 67 11 27 214 66 73 10 24 199 72 79 10 21 184 79 86 9 18
Cooling capacities (cont.)
Hydronic module
Expansion tank volume l 50 50 50 50 80 80 80 80 80 80 80
Maximum operating pressure kPa 400 400 400 400 400 400 400 400 400 400 400
Water filter Screen filter (Victaulic)
Low-pressure pump
Water pump Single or dual monocell centrifugal pump
Pump capacity kW 2 2 2 2 3 3 4 4 4 6 6
Pump power input kW 2.7 2.7 2.7 2.7 3.6 3.6 4.6 4.6 4.6 6.3 6.3
Maximum pump current drawn A 4.7 4.7 4.7 4.7 6.4 6.4 8.2 8.2 8.2 11.2 11.2
High-pressure pump
Water pump Single or dual monocell centrifugal pump
Pump capacity kW 4 4 4 4 6 6 8 8 8 11 11
Pump power input kW 4.7 4.7 4.7 4.7 6.4 6.4 8.5 8.5 8.5 12.2 12.2
Maximum pump current drawn A 8.2 8.2 8.2 8.2 11.2 11.2 15.4 15.4 15.4 21.2 21.2
Water connections (with hydronic module) Victaulic type
Diameter in 3 3 3 3 4 4 4 4 5 5 5
Outside pipe diameter mm 88.9 88.9 88.9 88.9 114.3 114.3 114.3 114.3 139.7 139.7 139.7
* Weights are for guidance only
Legend
8
17 Water temperature sensor
5 5
System components
5
18 Air vent
11 19 Flexible connection
6
20 Shut-down valves
7 16 21 Charge valve
5 14
---- Hydronic module (units with hydronic module)
19 20 9
12
Notes:
21 17 With option 42A the unit hydronic module is protected against frost by electric
heaters.
The unit evaporator must be protected against frost (anti-freeze solution or optional
Typical hydronic circuit diagram electric heater)
13
Available static system pressure
Low-pressure pump (hydronic module option) High-pressure pump (hydronic module option)
Available static pressure, kPa
Legend Legend
1 30RB 232-262 1 30RB 182-202
2 30RB 182-202 2 30RB 232-262
3 30RB 302 3 30RB 302
4 30RB 342 4 30RB 342
5 30RB 372-402 5 30RB 372-402
6 30RB 432 6 30RB 432
7 30RB 462-522 7 30RB 462-522
14
Total heat reclaim (option 50)
Suitable for heating, domestic hot water preparation, Operating principle
agriculture and food industry, industrial processes and If hot water production is required, the compressor
other hot-water requirements. discharge gases are directed towards the heat reclaim
condenser. The refrigerant releases its heat to the hot
With the total heat reclaim option it is possible to reduce water that leaves the condenser at a temperature of up to
the energy consumption bill considerably compared to 55°C. In this way 100% of the heat rejected by the liquid
conventional heating equipment such as fossil fuel boilers chiller can be used to produce hot water. When the
or electric water tanks. demand for heat is satisfied, the hot gas is again directed
towards the air condenser where the heat is rejected to the
outside air by the fans. Hot water temperature control is
ensured by the chiller Pro-Dialog control that
independently controls the reclaim operation of each
refrigerant circuit.
15
DX free cooling system (option 118A)
The DX free cooling option permits significant energy Advantages of the DX free cooling system
savings for all applications that require cooling in winter. ■ Operation without glycol
In the free cooling mode the compressors are stopped and - Unlike traditional hydronic free-cooling systems that
only the fan and cooling micro-pump are running. The require the use of a glycol solution, the Aquasnap DX
changeover from compressor cooling mode to free cooling free cooling chiller works with pure water. The
mode is automatically controlled by the Pro-Dialog evaporator is protected against frost down to -20°C by
control, based on the chiller heat load and the temperature an electric resistance heater (option).
difference between chilled water and ambient air. ■ Low water pressure losses
Important: In order to optimise chiller performances, it is - The Aquasnap DX free cooling chiller does not include a
recommended to use the leaving water set point reset three-way valve nor free cooling coils connected in series
function. with the evaporator. The Aquasnap free cooling chiller
has the same water pressure losses as a standard chiller.
Operating principle ■ Weight and dimensions gain
When the chilled water-air temperature difference exceeds - The DX free cooling option has little impact on the
a threshold value, the Pro-Dialog control carries out a weight of the liquid chiller.
comparison between the instantaneous chiller cooling - The Aquasnap free cooling chiller has the same
capacity and the available free cooling capacity. If the dimensions as a standard chiller.
operating conditions allow free cooling operation, the ■ Increased energy efficiency
compressors are stopped, a three-way valve on the suction - In free cooling mode only the fans and the cooling
piping connects the evaporator with the condenser, micro-pump run. At an air-water temperature difference
allowing the migration of the refrigerant vapours to the of 10 K for example the average chiller energy efficiency
condenser. The refrigerant condenses in the condenser (EER) is 15 (kW/kW).
coils, and the cooling micro-pump transports the liquid to - In the mechanical cooling mode chiller thermal and
the evaporator. The cooling capacity in free cooling mode energy performances are not reduced by the use of a
is controlled by the opening of the electronic expansion water-glycol solution.
valve (EXV). - As the pressure losses of the water circuit are low, the
water pumps use less energy.
Cap Unit EER Cap Unit EER Cap Unit EER Entering water during operation 8.5 25
30RB (°C) kW kW kW/kW kW kW kW/kW kW kW kW/kW Leaving water during operation 5 15
232 10 117 8 14.6 121 8 15.1 121 4 30.2 Condenser air temperature °C Minimum Maximum
262 117 8 14.6 121 8 15.1 121 4 30.2 Standard free cooling unit 0 48
302 145 10 14.5 162 10 16.2 186 8 23.2 With winter operation option (No. 28) -20 48
342 145 10 14.5 162 10 16.2 186 8 23.2
372 173 11 15.7 203 12 16.9 250 12 20.8 30RB - free cooling mode
402 173 11 15.7 203 12 16.9 250 12 20.8 Evaporator water temperature °C Minimum Maximum
432 211 13 16.2 246 13 18.9 277 13 21.3 Entering water at start-up 6.8 40
462 211 13 16.2 246 13 18.9 277 13 21.3 Leaving water during operation 5 26
522 248 15 16.5 275 15 18.3 293 15 19.5 Condenser air temperature °C Minimum Maximum
Legend -25 20
LWT - Leaving water temperature
Cap kW - Cooling capacity
Unit kW - Unit power input (compressors, fans, control)
EER kW/kW - Energy efficiency
16
Units with fans with available pressure for indoor installation
(option 12)
This option applies to 30RB units installed inside the Each refrigerant circuit (A, B and C) must have a separate
building in a plant room. For this type of installation the ducting system to prevent any air recycling between the
hot air leaving the air-cooled condensers is discharged by condensers of the different refrigerant circuits.
the fans to the outside of the building, using a duct system.
In 30RB units with option 12 each fan is equipped with a
30RB units equipped with fans with available pressure are factory-installed connection interface, allowing the
designed to operate with air discharge ducts with connection to the ducting system for the specific circuit (A,
maximum pressure drops of 200 Pa. B and C) for each fan. Please refer to the unit dimensional
drawings for the exact dimensions of the connection
To compensate for these pressure drops 30RB units with interface.
option 12 are equipped with variable-speed fans with a
maximum speed of 19 r/s, instead of 15.8 r/s and fixed- The unit cooling capacity and energy efficiency ratio
speed fans as for the standard units. (EER) varies depending on the duct pressure drops:
- between 0 and 100 Pa the unit cooling capacity is only
All fans in the same refrigerant circuit are controlled by a slightly affected,
single speed variator and therefore all run at the same - between 100 and 200 Pa the unit cooling capacity falls
speed. considerably depending on the operating conditions
(outdoor air temperature and water conditions).
The full-load or part-load speed is controlled by a
patented algorithm that permanently optimises the Please refer to the curves below to evaluate the impact of
condensing temperature to ensure the best unit energy the estimated duct system pressure drop for the
efficiency (EER) whatever the operating conditions and installation and the impact of different full load operating
pressure drops of the system ductwork. conditions on the 30RB unit cooling capacity and EER.
Cooling capacity variations for operating conditions EER variations for operating conditions that differ
that differ from Eurovent conditions from Eurovent conditions
Cooling capacity variation coefficient
Sound power level at the discharge duct outlet for all circuits
30RB 182 202 232 262 302 342 372 402 432 462 522 602 672 732 802
Sound power level 10-12 W dB(A) 93 93 93 93 94 94 95 95 95.5 95.5 96 96.5 97 97.5 98
17
Electrical data notes for 30RB units:
• 30RB 182-522 units have a single power connection point at the main 2. Power supply frequency variation: ± 2 Hz.
disconnect switch; 30RB 602-802 units have two connection points at the 3. The neutral (N) line must not be connected directly to the unit (if necessary
main disconnect switch. use a transformer).
• The control box includes the following standard features: 4. Overcurrent protection of the power supply conductors is not provided with
- Starter and motor protection devices for each compressor and the fan(s) the unit.
- Control devices 5. The factory-installed disconnect switch(es)/circuit breaker(s) is (are) of a
• Field connections: type suitable for power interruption in accordance with EN 60947-3
All connections to the system and the electrical installations must be in full (corresponds to IEC 60947-3).
accordance with all applicable local codes. 6, The units are designed for simplified connection on TN(s) networks (IEC
• The Carrier 30RB units are designed and built to ensure conformance with 60364). For IT networks derived currents may interfere with network
these codes. The recommendations of European standard EN 60 204-1 monitoring elements, and it is recommended to create an IT type divider
(corresponds to IEC 60204-1) (machine safety - electrical machine for the system units that require this and/or a TN type divider for Carrier
components - part 1: general regulations) are specifically taken into account, units. Please consult the appropriate local organisations to define the
when designing the electrical equipment. monitoring and protection elements and carry out the electrical installation.
• Electrical reserves: If short circuit currents above those given in the electrical data table are
Circuit A has disconnect switches and branch sections, designed to supply likely, modifications are required. Please contact your local Carrier
the evaporator pump power input. representative.
IMPORTANT: NOTE:
• Generally the recommendations of IEC 60364 are accepted as compliance If particular aspects of an actual installation do not conform to the
with the requirements of the installation directives. Conformance with conditions described above, or if there are other conditions which
EN 60204 is the best means of ensuring compliance with the Machines should be considered, always contact your local Carrier
Directive § 1.5.1. representative.
• Annex B of EN 60204-1 describes the electrical characteristics used for the
operation of the machines. * The required protection level for this class is IP43B (according to reference
document IEC 60529). All 30RB units are protected to IP44CW and fulfil
1. The operating environment for the 30RB units is specified below: this protection condition.
a. Environment* - Environment as classified in EN 60721 (corresponds to
IEC 60721) :
- outdoor installation*
- ambient temperature range: -20°C to +48°C, class 4K3*
- altitude: ≤ 2000 m
- presence of hard solids, class 4S2 (no significant dust present)
- presence of corrosive and polluting substances, class 4C2 (negligible)
- vibration and shock, class 4M2
b. Competence of personnel, class BA4* (trained personnel - IEC 60364)
18
Carrier is participating in the Eurovent Certification Programme for
liquid chilling packages. Products are as listed in the Eurovent
Directory of Certified Products or on the Internet site
www.eurovent-certification.com.
Order No.: 13438-20.12.2008. Supersedes order No. 13438-20, 05.2008. Manufactured by: Carrier SCS, Montluel, France.
Manufacturer reserves the right to change any product specifications without notice. Printed in the Netherlands.