Flexible Cables For Reeling Applications - HeaVY Duty ... - Conductix

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

GPM-RF

Flexible cables for reeling applications - HEAVY duty operations - 0.6 / 1 kv

All the very stringent characteristics of the insulating cover


2
and the sheath make the cable suitable for use with reeling
systems such as power supply of moving machines.
In addition to its excellent mechanical characteristics, the polyurethane
sheath has a good resistance to wear combined with a high flexibility over
3 a large range of temperatures, a good resistance to weathering agents, and
an excellent stability against oils, greases, and against a lot of solvents.

1
Design
1 Polyurethane double sheath, green coloured RAL 6032
2 Plain copper cores
3 Insulation:
• 3 phase cores black - brown - grey
• 3 earth cores green / yellow

Marking
“CONDUCTIX WAMPFLER / GPM-RF 3×__+3G__ - 0.6/1kV”

Standards Conditions of use Voltage


• NF EN CEI 60228 class 5 • Suitable for all spool types in • 0.6 / 1 kV - Low Voltage
for the copper cores adequacy with the minimum
• NF C 32-013 - VDE 0295 - bending radius. Linear reeling speed
BSI 6360 for the copper cores • Not suitable for level • 90 m/min max.
• CEI 60502-1: voltage test wind applications.
• Flame resistance: class C3 • Installation with a deflection Ambient temperature
(not tested) pulley: contact us. • From -25 to +60°C (see table of
• Halogen free de-rating factors next page).
Cables GPM-RF Technical Data
Number of Cores 3×25 3×35 3×50 3×70 3×95 3×120 3×150 3×185 3×240
and + + + + + + + + +
Nominal C.S.A. (mm²) 3G6 3G6 3G10 3G16 3G16 3G25 3G25 3G35 3G50
Mechanical Data
Min. outer diameter (mm) 24.3 27.2 31.0 35.9 40.7 45.6 50.4 56.3 64.0
Max. outer diameter (mm) 25.8 28.8 33.0 38.1 43.3 48.4 53.6 59.7 68.0
Unsheathed cable diameter (mm) 20.5 23.0 26.5 31.0 35.0 39.5 45.0 47.5 55.5
Linear weight (kg/m) 1.20 1.55 2.16 3.10 3.84 4.98 6.03 7.51 9.93
Min. bending radius (mm):
Anchor drum Max. cable outer diameter × 4
Spool Max. cable outer diameter × 6
Guiding device Max. cable outer diameter × 9
Pulley Not recommended - Contact us
Max. tensile load (daN):
Direct 150 210 300 420 570 720 900 1 110 1 440
With guiding device 110 160 240 340 440 580 700 880 1 160
With pulley Not recommended - Contact us
Electrical Data
Current carrying capacity (A) (a) 127 158 192 246 298 346 395 450 538
Voltage drop (V/A/km) (b) 1.46 1.00 0.75 0.55 0.44 0.36 0.30 0.26 0.22
Max. resistance (Ω/km) (c) 0.780 0.554 0.386 0.272 0.206 0.161 0.129 0.106 0.080
Dynamic short circuit current (A/s) 2.49 3.49 4.99 6.98 9.47 11.96 14.96 18.45 23.96

Oblique grey tint: cable not referenced, contact us. (b): cos = 0.8 / temperature of cores = +90°C
(a): Cable laid on the ground @+30°C (c): DC resistance of a core @ +20°C

Recommendations Installation
• Amperage de-rating factor for • Minimum distance between two guiding devices: L min = 20 × cable O.D.
reeling applications: 0.85
in
Lm
• De-rating factors in relation to the
ambient temperature above 30°C:

30°C up to 40°C 0.90


L min

40°C up to 50°C 0.80


50°C up to 55°C 0.74
55°C up to 60°C 0.65
• Deflection angle (if Ør < bending radius) = 15° max for laying on rollers
• Recommended voltage drop limits:

Usual 5% Ør
15°

Lighting 3%
E-GPMRF-0609

Frequency inverter 2.5%


15°