Analysis and Design of Stay Cable Anchorage For Deck For Cable Stay Rob, Ranchi
Analysis and Design of Stay Cable Anchorage For Deck For Cable Stay Rob, Ranchi
Analysis and Design of Stay Cable Anchorage For Deck For Cable Stay Rob, Ranchi
REVISIONS
DESIGN CONSUTANT:
EPC CONTRACTOR:
Executive Engineer,
IIT BOMBAY,
Ranchi Road Construction
Department (RCD), MUMBAI
Government of Jharkhand
This document is the property of L&T Construction, TI IC, and must not be passed on
to any third person or firm not authorized by us, nor be copied/made use of in full or
part by such person or firm without our prior permission in writing.
DATE : 10-Oct-23 NOTE NO.: O22051-C-RP-FL-DC-
2028
STUP Consultants P.Ltd. 3 .
BY : MDE SHEET NO.:
INDEX
Sr. No. Content
1 Introduction
5 Bursting Reinforcement
6 Calculation of bearing stress behind Anchorage as per IRC SP 105 (pg no.160)
DATE : 10-Oct-23 NOTE NO.: O22051-C-RP-FL-DC-
2028
STUP Consultants P.Ltd. 4 .
BY : MDE SHEET NO.:
1 Introduction
This design note presents the design of stay cable blister block at concrete deck level for ROB.
1. General Considerations
Grade of concrete 50 Mpa
Grade of steel (fy) 500 Mpa
Ultimate tensile stress of prestressing steel 1860 Mpa
Maximum no of strands 55 nos
Area of strands 150 mm2
UTS of each strand (F) 279 kN
Friction factor for monolithic construction m 1.4
Max Design
Expected Force=0.95*1860*150*str
No of and
strands kN
37 9807
55 14578
Design Force = Max (Jacking Force, Max design force) * 1.1* cos q
Expected Provided
Min Design Dia of Req No Ast
No of Ast Req Leg No of CHECK
q Force Bar of Bars
Bars provided
strands
55 28.066 14150 23234 20 6 14 16* 30159.3 OK
55 32.567 13514 22191 20 6 12 14* 26389.4 OK
55 38.966 12468 20473 20 6 12 14* 26389.4 OK
37 48.505 7147 11736 20 6 8 8* 15079.6 OK
37 62.771 4936 8105 20 6 6 6* 11309.7 OK
37 62.771 4936 8105 20 6 6 6* 11309.7 OK
37 48.505 7147 11736 20 6 8 8* 15079.6 OK
55 38.966 12468 20473 20 6 12 14* 26389.4 OK
55 32.567 13514 22191 20 6 12 14* 26389.4 OK
55 28.066 14150 23234 20 6 14 16* 30159.3 OK
* Bar mark 1 & 2 Taking min no. (provided bar is always more)
DATE : 10-Oct-23 NOTE NO.: O22051-C-RP-FL-DC-
2028
STUP Consultants P.Ltd. 5 .
BY : MDE SHEET NO.:
kN mm2
5894 530
Mu
At =
f * Fe * 0.8D
Where,
D = Total Length of Blister
d = Effective depth = 0.8 D
Fe= 500 Mpa
F = 0.87
Cover = 45 mm
q = Cable angle with horizontal
Pmax = Max (Jacking, ULS Force) * 1.1 * cos q
Mu = Pmax * e
Expected Dia of
Pmax e Mu No of
q No of D d Ast req Bar Bars
Cable Strands kN m kN-m m m mm2 mm
C1 28.07 55 14150 0.396 5603 1.895 1.806 7132 32 10
C2 32.57 55 13514 0.378 5108 1.657 1.568 7489 32 10
C3 38.97 55 12468 0.348 4339 1.419 1.330 7499 32 10
C4 48.51 37 7147 0.296 2116 1.194 1.105 4401 32 6
C5 62.77 37 4936 0.202 997 1.006 0.917 2500 32 4
C16 62.77 37 4936 0.202 997 1.006 0.917 2500 32 4
C17 48.51 37 7147 0.296 2116 1.194 1.105 4401 32 6
C18 38.97 55 12468 0.348 4339 1.419 1.330 7499 32 10
C19 32.57 55 13514 0.378 5108 1.657 1.568 7489 32 10
C20 28.07 55 14150 0.396 5603 1.895 1.806 7132 32 10
Refer Bar mark 12 Max 10
5 Bursting Reinforcement
The Bursting reinforcement will be provided in the form of sprial reinforcement as per manufacture
manual.
6 Calculation of bearing stress behind Anchorage as per IRC SP 105 (pg no.160)
Expected
P max C C'
No of Pmax/CC' 0.6*Fck CHECK
strand kN mm mm Mpa Mpa
55 5894 1000 900 6.55 19.2 OK