Poz. 4 - F27HC 85 E 6

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Date 12/2/2024

For the attention of:


Reference
Operator

COMMERCIAL UNIT COOLER:CUBIC


Type: F27HC 85 E 6
N. units: 1
Inlet air temp. (room) [°C] 2,0
Room relative humidity [%] 85
Refrigerant R449A
Altitude [m] 0
Residual static pressure [Pa] 0
DT1 needed for unit cooler (Dew) [K] 9,5
Connection 230V-1PH-50Hz
Actual capacity [W] 8.000
Air flow [m3/h] 2.850,0
Air throw [m] 14
Outlet air temperature [°C] -4,2
Evaporating temp (Dew) [°C] -8,5
DT superheating (Dew) [K] 5,0
Temp. before expansion valve [°C] 30,0
DT1 (Dew) [K] 10,5
DTmlg [K] 6,9
Fluid pressure drop [K] 0,8
RC factor (Sensible capacity/Total capacity) [%] 71,4
Energy efficiency class D (2014 thresholds)
Fan motor consumpt. [W] 255
Power draw [A] 1,8
Max fan absorbed current* [A] 1,83
Fan speed [1/min] 1450
Sound pressure level (5 m) 5 [dB(A)@5m] 42
Sound Power Level [dB(A)] 67
Electric defrost (230 V) [W] 3.080
N° Fans [mm] 3 x 275 Weight [kg] 27
Poles [n] 4 Connections in [n] x [mm] 1 x 12
Fin spacing [mm] 6 Connections out [n] x [mm] 1 x 28
Internal volume [dm3] 3,3 Drain tray connection [''] 3/4
Surface [m2] 16,8 Overall dimensions [mm] 1.418 x 330 x 415
Max Working pressure [bar] 24,0
Casing material Powder coated galvanized steel RAL 9003 Fin material Al
Header material Cu Tube material Cu
* Refer to LU-VE S.p.A. instruction manuals for details, data and standards. Noise level in 5m free field. The current may increase according to temperature
frost quantity, external static pressure. The weight and dimensions are not valid for all possible configurations. All fans are ErP 2015-compliant (Directive
2009/125/EC Energy-related products). LU-VE S.p.A. reserves the right to modify and correct at any time, with or without notice, the specifications and prices
listed in the Refriger software.
EUROVENT – CERTIFY ALL! Eurovent certification guarantees thermal performance, sound specifications, electrical power consumption, air volume flows. The
certified performances and conditions in this software are in line with performances and conditions published on EUROVENT website.
LU-VE Group participates in the ECP programme for HE. Check ongoing validity of certificate and performance on www.eurovent-certification.com. The
EUROVENT certification refers to the unit in standard configuration, additional options may impact on declared reference performance.

LUVE S.p.A Headquarters Uboldo ITALY via Caduti della Liberazione, 53


Tel +39 02 967161 Fax +39 02 96780560 mail [email protected] web www.luvegroup.com