Multilin: 8 Series 889
Multilin: 8 Series 889
Multilin: 8 Series 889
Multilin
8 Series 889
Technical Manual
Generator Protection System
Hardware Version: C
Firmware Version: 4.10
Publication Reference: 1601-0320-C410-1
Copyright statement
Copyright © 2023 GE Vernova. All rights reserved.
EnerVista, EnerVista Launchpad, and EnerVista D&I Setup software are registered trademarks of GE Vernova.
The contents of this manual are the property of GE Vernova. This documentation is furnished on license and may
not be reproduced in whole or in part without the permission of GE Vernova. The content of this manual is for
informational use only and is subject to change without notice.
Disclaimer
It is the responsibility of the user to verify and validate the suitability of all GE Grid Automation products. This
equipment must be used within its design limits. The proper application including the configuration and setting of
this product to suit the power system assets is the responsibility of the user, who is also required to ensure that all
local or regional safety guidelines are adhered to. Incorrect application of this product could risk damage to
property/the environment, personal injuries or fatalities and shall be the sole responsibility of the person/entity
applying and qualifying the product for use.
The content of this document has been developed to provide guidance to properly install, configure and maintain
this product for its intended applications. This guidance is not intended to cover every possible contingency that
may arise during commissioning, operation, service, or maintenance activities. Should you encounter any
circumstances not clearly addressed in this document, please contact your local GE service site.
The information contained in this document is subject to change without notice.
It is the sole responsibility of the user to secure their network and associated devices against cybersecurity
intrusions or attacks. GE Vernova and its affiliates are not liable for any damages or losses arising from or
related to such security intrusion or attacks.
Contents
Chapter 1 Introduction 1
1.1 Chapter Overview 3
1.2 Foreword 4
1.2.1 Target Audience 4
1.2.2 Typographical conventions 4
1.2.3 Nomenclature 5
1.3 Product overview 6
1.4 General description of the 8 Series 7
1.5 Functions and features 9
1.6 Security Overview 14
1.7 Order Codes 16
1.8 Cautions, warnings and notes 19
1.8.1 Safety words and definitions 19
1.8.2 General Cautions and Warnings 19
1.9 Must-read Information 22
1.9.1 Storage 22
1.10 For Further Assistance 23
1.10.1 Repairs 23
Chapter 2 Installation 25
2.1 Chapter Overview 27
2.2 Product Identification 28
2.3 Dimensions 29
2.4 Mounting 30
2.4.1 Standard Panel Mount 30
2.5 Draw-out Unit Withdrawal and Insertion 35
2.6 Removable Power Supply 37
2.7 Removable Magnetic Module 38
2.8 Remote Module I/O (RMIO) 41
2.9 IP20 Back Cover 43
2.10 Arc Flash Sensor 44
2.11 Physical considerations of wiring 47
2.11.1 Terminal Strip Types 48
2.11.2 Wire Size 49
2.12 Terminal connections 50
2.12.1 General connections 51
2.13 Terminal Identification 53
2.14 RMIO Module Installation 55
2.15 Phase Sequence and Transformer Polarity 57
2.16 Zero-Sequence CT Installation 61
2.17 Voltage Inputs 62
2.18 Control Power 63
2.19 Contact Inputs 64
2.20 Output Relays 66
2.21 Serial Communications 69
2.22 IRIG-B 71
2.23 Typical Wiring Diagrams 72
Contents
Chapter 3 Interfaces 75
3.1 Chapter Overview 77
3.2 First access 78
3.3 Front panel options 79
3.3.1 Graphical Display Pages 80
3.3.1.1 Menu hierarchy 81
3.3.1.2 Working with Graphical Display Pages 82
3.3.1.3 Single Line Diagram 85
3.3.2 Three-pushbutton front panel LEDs 88
3.3.3 Ten-pushbutton front panel LEDs 89
3.3.4 Home screen icons 92
3.3.5 Relay Messages 93
3.3.5.1 Target Messages 93
3.3.5.2 Self-test errors 93
3.3.5.3 Out of Service 98
3.3.5.4 Flash Messages 98
3.3.6 Label Removal 98
3.4 Software Interface 100
3.4.1 EnerVista D&I Setup software 100
3.4.1.1 Hardware & Software Requirements 100
3.4.1.2 Installing EnerVista D&I Setup software 100
3.4.1.3 Upgrading EnerVista D&I Setup software 101
3.4.2 Connecting EnerVista D&I Setup software to the relay 101
3.4.2.1 Using the Quick Connect Feature 101
3.4.2.2 Configuring Ethernet Communications 101
3.4.2.3 Connecting to the Relay 102
3.4.2.4 Configuring USB Address 102
3.4.3 Working with Setpoints 104
3.4.3.1 Entering Setpoints 104
3.4.3.2 Using Setpoint Files 106
3.4.3.3 Downloading and saving Setpoint files 107
3.4.3.4 Adding Setpoint files to the environment 107
3.4.3.5 Creating a new Setpoints file 107
3.4.3.6 Upgrading Setpoint files to a new revision 108
3.4.3.7 Printing Setpoints 108
3.4.3.8 Printing values from a connected device 109
3.4.3.9 Loading Setpoints from a File 109
3.4.3.10 Uninstalling files and clearing data 109
3.4.4 Quick Setup 109
3.4.5 Upgrading relay firmware 110
3.4.5.1 Loading new relay firmware 110
3.4.6 SLD Configurator 111
3.4.6.1 Control Objects 113
3.4.6.2 Status Objects 115
3.4.6.3 Metering Objects 116
3.4.6.4 Device Status Object 116
3.4.6.5 Static Objects 116
3.4.6.6 Front Panel Interaction 116
3.4.7 FlexCurve Editor 119
3.4.8 Transient Recorder (Waveform Capture) 120
3.4.9 Protection Summary 123
3.4.10 FlexLogic Favourites 124
3.4.11 Offline Settings File Conversion 124
ii 1601-0320
Contents
1601-0320 iii
Contents
iv 1601-0320
Contents
1601-0320 v
Contents
vi 1601-0320
Contents
1601-0320 vii
Contents
viii 1601-0320
Contents
1601-0320 ix
Contents
x 1601-0320
CHAPTER 1
INTRODUCTION
Chapter 1 - Introduction
2 1601-0320
Chapter 1 - Introduction
1601-0320 3
Chapter 1 - Introduction
1.2 FOREWORD
This technical manual provides a functional and technical description of the relay, as well as a comprehensive set of
instructions for using it. The level at which this manual is written assumes that you are already familiar with
protection engineering and have experience in this discipline. The description of principles and theory is limited to
that which is necessary to understand the product. For further details on general protection engineering theory, we
refer you to the publication, Protection and Automation Application Guide, which is available online.
We have attempted to make this manual as accurate, comprehensive and user-friendly as possible. However we
cannot guarantee that it is free from errors. Nor can we state that it cannot be improved. We would therefore be
very pleased to hear from you if you discover any errors, or have any suggestions for improvement. Our policy is to
provide the information necessary to help you safely specify, engineer, install, commission, maintain, and eventually
dispose of this product. We consider that this manual provides the necessary information, but if you consider that
more details are needed, please contact us.
4 1601-0320
Chapter 1 - Introduction
● Setting values are written with the courier font and are italicized
For example: Enabled
● Multilin products, use Flexlogic operands. Flexlogic operands are written in light blue uppercase courier font
For example: PUSHBUTTON 1 ON
● Notes are written in italic and are surrounded by a by a blue border.
For example:
Note:
This is a note
1.2.3 NOMENCLATURE
Due to the technical nature of this manual, many special terms, abbreviations and acronyms are used throughout
the manual. Some of these terms are well-known industry-specific terms while others may be special product-
specific terms used by GE Grid Solutions. The first instance of any acronym or term used in a particular chapter is
explained. In addition, a separate glossary is available on the GE Grid Solutions website.
We would like to highlight the following changes of nomenclature however:
● The word relay and IED (Intelligent Electronic Device) are both used to describe the protection device. The
term IED is associated with the IEC61850 standard, whereas the term relay is the long-used traditional term.
It may also be referred to simply as the device' or the product.
● American English and spelling is used throughout this manual.
● The term 'Earth' and American term 'Ground' are equivalent. You may find either used in the manual.
1601-0320 5
Chapter 1 - Introduction
6 1601-0320
Chapter 1 - Introduction
CPU
Relay functions are controlled by two processors: a Freescale MPC5125 32-bit microprocessor that measures all
analog signals and digital inputs and controls all output relays, and a Freescale MPC8358 32-bit microprocessor
that controls all the advanced Ethernet communication protocols.
Frequency
Frequency measurement is accomplished by measuring the time between zero crossings of the composite signal of
three-phase bus voltages, line voltage or three-phase currents. The signals are passed through a low pass filter to
prevent false zero crossings. Frequency tracking utilizes the measured frequency to set the sampling rate for
current and voltage which results in better accuracy for the Discrete Fourier Transform (DFT) algorithm for off-
nominal frequencies.
The main frequency tracking source uses three-phase bus voltages. The frequency tracking is switched
automatically by an algorithm to the alternative reference source, i.e., three-phase currents signal or line voltage for
the configuration of tie-breaker, if the frequency detected from the three-phase voltage inputs is declared invalid.
The switching will not be performed if the frequency from the alternative reference signal is detected invalid. Upon
detecting valid frequency on the main source, the tracking will be switched back to the main source. If a stable
frequency signal is not available from all sources, then the tracking frequency defaults to the nominal system
frequency.
1601-0320 7
Chapter 1 - Introduction
Protection Elements
All voltage, current and frequency protection elements are processed eight times every cycle to determine if a
pickup has occurred or a timer has expired. The voltage and current protection elements use RMS current/voltage,
or the magnitude of the phasor.
8 1601-0320
Chapter 1 - Introduction
Cl
!"!#$%&# '#&%!(%)&" *+,%!-
p 5
mquqw
4 P 59P hj_2 59N 1O 1U 1R 1 4
S./3 :H < => ?@AB
Z[\ hx_2
{ 49
6 hx
L
50P 50N
Metering
Transient Recorder
{9
L Event Recorder
S./3 F; < => ?@AB G 50P 50N 50
S./3 : <IJ/KAL
7 D 50G 51G 6G
Y
64TN
8
¡ ¢¡¢¡
1601-0320 9
Chapter 1 - Introduction
10 1601-0320
Chapter 1 - Introduction
1601-0320 11
Chapter 1 - Introduction
12 1601-0320
Chapter 1 - Introduction
7!89
!" 0&$4
:*,*$
#$%&'%$(
¬6,-%(
§&(, $6/ &,&
$- 3&(
)*+,&-, .+/0,(
10,/0, 2%3&4(
56$,0&3 .+/0,(
56$,0&3 10,/0,(
3%¦ ,&,%(
¡¢£¤¡ ¥
.+*$&,6*+
%6-% ,&,0(
)3*-'
,&,0(
1601-0320 13
Chapter 1 - Introduction
BASIC SECURITY
The basic security feature is present in the default offering of the relay. The relay introduces the notion of roles for
different levels of authority. Roles are used as login names with associated passwords stored on the device. The
following roles are available at present: Administrator, Engineer, Operator, Factory and Viewer, with a fixed
permission structure for each one. Note that the Factory role is not available for users, but strictly used in the
manufacturing process.
The relay can still use the SETPOINT ACCESS switch feature, but enabling the feature can be done only by an
Administrator. Setpoint access is controlled by a keyed switch to offer some minimal notion of security.
CYBERSENTRY
The CyberSentry Embedded Security feature is a software option that provides advanced security services. When
the software option is purchased, the Basic Security is automatically disabled.
CyberSentry provides security through the following features:
● An Authentication, Authorization, Accounting (AAA) Remote Authentication Dial-In User Service (RADIUS)
client that is centrally managed, enables user attribution, and uses secure standards based strong
cryptography for authentication and credential protection.
● A Role-Based Access Control (RBAC) system that provides a permission model that allows access to device
operations and configurations based on specific roles and individual user accounts configured on the AAA
server. At present the defined roles are: Administrator, Engineer, Operator and Viewer.
● Strong encryption of all access and configuration network messages between the EnerVista software and
devices using the Secure Shell (SSH) protocol, the Advanced Encryption Standard (AES), and 128-bit keys in
Galois Counter Mode (GCM) as specified in the U.S. National Security Agency Suite B extension for SSH
and approved by the National Institute of Standards and Technology (NIST) FIPS-140-2 standards for
cryptographic systems.
● Security event reporting through the Syslog protocol for supporting Security Information Event Management
(SIEM) systems for centralized cyber security monitoring.
There are two types of authentication supported by CyberSentry that can be used to access the device:
● Device Authentication – in which case the authentication is performed on the device itself, using the
predefined roles as users (No RADIUS involvement).
○ Device authentication using local roles may be done either from the front panel or through EnerVista.
● Server Authentication - in which case the authentication is done on a RADIUS server, using individual user
accounts defined on the server. When the user accounts are created, they are assigned to one of the
predefined roles recognized by the relay.
○ Device authentication using RADIUS server may be done only through EnerVista.
Note:
USB does not currently support CyberSentry security.
EnerVista Viewpoint Monitor does not currently support CyberSentry security.
With the CyberSentry security option, many communication settings cannot be changed remotely. All communication settings
can still be changed through the relay front panel.
14 1601-0320
Chapter 1 - Introduction
When both device and server authentication are enabled, the relay automatically directs authentication requests to
the device or the respective RADIUS server, based on user names. If the user ID credential does not match one of
the device local accounts, the relay automatically forwards the request to a RADIUS server when one is provided. If
a RADIUS server is provided, but is unreachable over the network, server authentication requests are denied. In
this situation, use local device accounts to gain access to the system.
USER ROLES
User Access Levels are used to grant varying permissions to specific user roles. User roles are used by both Basic
Security and CyberSentry.
The following user roles are supported:
● Administrator: The Administrator role has complete read and write access to all settings and commands.
The role does not allow concurrent access. The Administrator role also has an operand to indicate when it is
logged on.
● Engineer: This role has similar rights to the Administrator role, except that some commands, the security
settings modification and firmware upload are not allowed.
● Operator: The Operator role is present to facilitate operational actions that may be programmed and
assigned to buttons on the front panel. The Operator has read/write access to all settings under the
command menu/section. The Operator can also use the Virtual Input command under the control menu/
section. The Operator can view settings from EnerVista or the front panel but does not have the ability to
change any settings. This role is not a concurrent role.
● Viewer: The Viewer role has read-only access to all 8 Series 889 settings. This role allows concurrent
access. The Viewer is the default role if no authentication has been done to the device. This role can
download settings files and records from the device.
● Factory: This is an internal non-user accessible role used for manufacturing diagnostics. The ability to enable
or disable this role is a security setting that the Administrator controls.
1601-0320 15
Chapter 1 - Introduction
E Standard
POWER SUPPLY:
L 24 to 48 VDC
SLOT B:
N None
SLOT C:
N None
SLOT F:
A 2 Form A (Vmon) Relays, 2 Form C Relays, 1 Critical Failure Relay, 7 Digital Inputs (Int/Ext Supply)
M 4 SSR (High-Speed, High-Break), 1 Critical Failure Relay, 7 Digital Inputs (Int/Ext Supply)
SLOT G:
N None
16 1601-0320
Chapter 1 - Introduction
SLOT H:
N None
FACEPLATE:
CURRENT PROTECTION:
M Standard: 38 (RTD) (1), 39 (AnIp) (1), 46 (Gen. Unbl.) (1), 50/27 (1), 50OFL (1), 50OL (1), 50P (2/CT
bank), 50N (1/CT bank), 50G (2), 50SG (1), 50_2 (1/CT bank), 51V (2), 51N (2), 51G (2), 51SG (1),
67N (1), 67G (1), 67SG (1), 76 (AnIp) (1), 87G (1)
A Advanced: Standard, 67P (1), 67_2 (1), 87GD (RGF) (1), 87O, Load Encroachment
S Standard: 24 (2), 25 (1), 27TN (1), 27P (2), 27X (2), 32 (2), 40Q (1), 40 (1), 47 (1), 59X (2), 81O (2),
81U (4)
P Advanced: Standard, 21P, 55, 59P (2), 59N (1), 59_2 (1), 64TN (100% stator ground) (1), 78 (1),
81R (2),
CONTROL
F Standard: Setpoint Group Control, Virtual Inputs Control, Trip Bus, FlexLogic, VTFF (1), 50BF (1),
Sequential Shutdown, Field Breaker Discrepancy, Breaker Control, Digital Elements
T Advanced HMI: Standard, Tab Pushbuttons, Annunciator Panel, Configurable SLDs with Bay Control
MONITORING
B Basic: Breaker Coil and Arcing Monitoring, Demand, Digital Counters, Running Hours
COMMUNICATIONS:
S E Standard: Front USB, 1x Rear RS485 (Modbus RTU/TCP, DNP 3.0, IEC 60870-5-103), 1x Ethernet
RJ45 port (Modbus TCP, DNP).
1 E Advanced: Standard + IEC 60870-5-104, 1588, SNTP, OPC-UA
N None, no additional communication ports. RJ45 Port 1 Enabled, RJ45 Port 2 disabled
S ST, Multi-mode 1310nm - With 1E to 3E, the user gets 2x Fiber ST Ports with Redundancy, RJ45
ports 1 and 2 are disabled. With 4E user gets 2x Fiber ST ports and 2xRJ45 Ports with Redundancy
selectable on 2 ports
C RJ45, Copper 10/100M - With 1E to 3E, the user gets 2x RJ45 ports with Redundancy, RJ45 ports 1
and 2 are disabled. With 4E user gets 4x RJ45 Ports with Redundancy selectable on 2 ports.
T 1x additional RS485 Port and 1x additional RJ45 Copper 10/100M port, Redundancy not available
with Communications option SE.
1601-0320 17
Chapter 1 - Introduction
WIRELESS COMMUNICATION:
N None
W WiFi 802.11
SECURITY
B Basic
FW OPTION
4 FW version 4.xx
RMIO1 * G G * *
Power Supply L | | | | 24 - 48 V DC
H | | | | 110 - 250 V DC / 110 - 230 V AC
I/O Module 1 G | | | Remote Module I/O (3 - 100 Ohm Platinum RTDs)
I/O Module 2 G | | Remote Module I/O (3 - 100 Ohm Platinum RTDs)
I/O Module 32 G | Remote Module I/O (3 - 100 Ohm Platinum RTDs)
X | None
I/O Module 4 G Remote Module I/O (3 - 100 Ohm Platinum RTDs)
X None
1. RMIO requires firmware version 2.00 and later and hardware version B. Check the hardware
version under Status > Information > Main CPU. If RMIO support is required for relays with earlier
hardware versions, contact the factory.
2. RMIO comes standard with 6 RTDs (Modules 1 and 2).
892800RMIO-A1.fm
Other Accessories
● 18J0-0030 8 Series Depth Reducing Collar - 1 3/8”
● 18J0-0029 8 Series Depth Reducing Collar - 3”
● 8 Series Retrofit Kit, 750/760 to 850
● 8 Series Retrofit Kit, 735 to 850
18 1601-0320
Chapter 1 - Introduction
Caution:
Refer to equipment documentation. Failure to do so could result in damage to the
equipment
Warning:
Risk of electric shock
Warning:
Risk of damage to eyesight
Note:
Indicates practices not related to personal injury.
Caution:
Before attempting to use the equipment, it is important that all danger and caution
indicators are reviewed.
If the equipment is used in a manner not specified by the manufacturer or functions
abnormally, proceed with caution. Otherwise, the protection provided by the
equipment may be impaired and can result in impaired operation and injury.
Warning:
Hazardous voltages can cause shock, burns or death.
Caution:
Installation/service personnel must be familiar with general device test practices,
electrical awareness and safety precautions must be followed.
Before performing visual inspections, tests, or periodic maintenance on this device
or associated circuits, isolate or disconnect all hazardous live circuits and sources
of electric power.
1601-0320 19
Chapter 1 - Introduction
Warning:
Failure to shut equipment off prior to removing the power connections could
expose you to dangerous voltages causing injury or death.
Ensure that all connections to the product are correct so as to avoid accidental risk
of shock and/or fire, for example from high voltage connected to low voltage
terminals.
Caution:
Follow the requirements of this manual, including adequate wiring size and type,
terminal torque settings, voltage, current magnitudes applied, and adequate
isolation/clearance in external wiring from high to low voltage circuits.
Use the device only for its intended purpose and application.
Ensure that all ground paths are un-compromised for safety purposes during
device operation and service.
All recommended equipment that should be grounded and must have a reliable and
un-compromised grounding path for safety purposes, protection against
electromagnetic interference and proper device operation.
Equipment grounds should be bonded together and connected to the facility’s
main ground system for primary power.
Keep all ground leads as short as possible.
In addition to the safety precautions mentioned all electrical connections made
must respect the applicable local jurisdiction electrical code.
It is recommended that a field external switch, circuit breaker be connected near
the equipment as a means of power disconnect. The external switch or circuit
breaker is selected in accordance with the power rating.
This product itself is not Personal Protective Equipment (PPE). However, it can be
used in the computation of site specific Arc Flash analysis when the arc flash
option is ordered. If a new appropriate Hazard Reduction Category code for the
installation is determined, user should follow the cautions mentioned in the arc
flash installation section.
The critical failure relay must be connected to annunciate the status of the device
for all applications and in particular when the arc flash option is ordered.
Ensure that the control power applied to the device, the AC current, and voltage
input match the ratings specified on the relay nameplate. Do not apply current or
voltage in excess of the specified limits.
Only qualified personnel are to operate the device. Such personnel must be
thoroughly familiar with all safety cautions and warnings in this manual and with
applicable country, regional, utility, and plant safety regulations.
Warning:
Hazardous voltages can exist in the power supply and at the device connection to
current transformers, voltage transformers, control, and test circuit terminals. Make
sure all sources of such voltages are isolated prior to attempting work on the
device.
Hazardous voltages can exist when opening the secondary circuits of live current
transformers. Make sure that current transformer secondary circuits are shorted
out before making or removing any connection to the current transformer (CT)
input terminals of the device.
20 1601-0320
Chapter 1 - Introduction
Caution:
For tests with secondary test equipment, ensure that no other sources of voltages
or currents are connected to such equipment and that trip and close commands to
the circuit breakers or other switching apparatus are isolated, unless this is
required by the test procedure and is specified by appropriate utility/plant
procedure.
When the device is used to control primary equipment, such as circuit breakers,
isolators, and other switching apparatus, all control circuits from the device to the
primary equipment must be isolated while personnel are working on or around this
primary equipment to prevent any inadvertent command from this device.
Use an external disconnect to isolate the mains voltage supply.
Warning:
LED transmitters are classified as IEC 60825-1 Accessible Emission Limit (AEL)
Class 1M. Class 1M devices are considered safe to the unaided eye. Do not view
directly with optical instruments.
Note:
To ensure the settings file inside the relay is updated, wait 30 seconds after a setpoint change before cycling power.
This product is rated to Class A emissions levels and is to be used in Utility, Substation Industrial environments. Not
to be used near electronic devices rated for Class B levels.
1601-0320 21
Chapter 1 - Introduction
1.9.1 STORAGE
Store the unit indoors in a cool, dry place. If possible, store in the original packaging. Follow the storage
temperature range outlined in the Specifications.
If applicable, use the factory-provided dust caps on all Arc Flash sensor fiber and connectors when not in use, to
avoid dust contamination in the transceiver and sensor plugs.
22 1601-0320
Chapter 1 - Introduction
1.10.1 REPAIRS
The firmware and software can be upgraded without return of the device to the factory.
For issues not solved by troubleshooting, the process to return the device to the factory for repair is as follows:
● Contact a GE Grid Solutions Technical Support Center. Contact information is found in the first chapter.
● Obtain a Return Materials Authorization (RMA) number from the Technical Support Center.
● Verify that the RMA and Commercial Invoice received have the correct information.
● Tightly pack the unit in a box with bubble wrap, foam material, or styrofoam inserts or packaging peanuts to
cushion the item(s). You may also use double boxing whereby you place the box in a larger box that contains
at least 5 cm of cushioning material.
● Ship the unit by courier or freight forwarder, along with the Commercial Invoice and RMA, to the factory.
● Customers are responsible for shipping costs to the factory, regardless of whether the unit is under warranty.
● Fax a copy of the shipping information to the GE Grid Solutions service department.
Use the detailed return procedure outlined at
https://www.gegridsolutions.com/multilin/support/ret_proc.htm
The current warranty and return information are outlined at
https://www.gegridsolutions.com/multilin/warranty.htm
1601-0320 23
Chapter 1 - Introduction
24 1601-0320
CHAPTER 2
INSTALLATION
Chapter 2 - Installation
26 1601-0320
Chapter 2 - Installation
1601-0320 27
Chapter 2 - Installation
Note:
This example label is specific to a particular order code of the 850 and may not represent your model.
28 1601-0320
Chapter 2 - Installation
2.3 DIMENSIONS
The relay dimensions are shown below. Additional dimensions for mounting, and panel cutouts, are shown in the
following sections.
1601-0320 29
Chapter 2 - Installation
2.4 MOUNTING
The relay can be mounted two ways: standard panel mount or optional tab mounting, if required.
● Standard panel mounting: From the front of the panel, slide the empty case into the cutout. From the rear of
the panel, screw the case into the panel at the 8 screw positions.
● Optional tab mounting: The V tabs are located on the sides of the case and appear as shown in the
following figure. Use needle nose pliers to bend the retaining V tabs outward to about 90°. Use caution and
do not bend and distort the wall of the enclosure adjacent to the tabs. The relay can now be inserted and can
be panel wired.
Caution:
To avoid the potential for personal injury due to fire hazards, ensure the unit is
mounted in a safe location and/or within an appropriate enclosure.
30 1601-0320
Chapter 2 - Installation
1601-0320 31
Chapter 2 - Installation
Note:
The drill hole locations are different when a depth reducing collar is used. See the Depth reducing collar panel cutout figure
below.
32 1601-0320
Chapter 2 - Installation
1601-0320 33
Chapter 2 - Installation
7+6/*-'6.MNH
To mount an 8 Series relay with a depth reducing collar, follow these steps:
1. Drill mounting holes as shown on the Depth reducing collar panel cutout figure above.
2. Mount the collar on the captive unit using eight screws.
3. Mount the combined unit and collar on the panel using eight screws.
34 1601-0320
Chapter 2 - Installation
Caution:
Turn off control power before drawing out or re-inserting the relay to prevent mal-operation.
Follow the steps outlined in the diagrams below to insert and withdraw.
1601-0320 35
Chapter 2 - Installation
STEP 1
SCALE 0.400
HANDLE TO BE LIFTED TO 90
POSITION WHILE SLIDING
DRAW-OUT UNIT INTO
CAPTIVE UNIT
STEP 3
STEP 2
36 1601-0320
Chapter 2 - Installation
1601-0320 37
Chapter 2 - Installation
Warning:
You must follow all preparation steps before removing the CT/VT magnetic module.
Warning:
You must identify all current and voltage sources connected to the relay before
starting the removal process.
Warning:
Only suitably-qualified personnel may remove the magnetic module from an
installed relay.
Warning:
Appropriate PPE is required based on the arc flash calculations.
Caution:
LOTO (Lockout Tag Out) of the system is required prior to module removal/
replacement.
Follow the procedures outlined below to remove or replace the CT/VT magnetic module.
PREPARATION
1. Shut down and de-energize all systems connected to the relay.
2. Review all cautions and warnings in the introduction.
Warning:
A relay, with the magnetic module removed, does NOT have an internal automatic
CT shorting mechanism.
Warning:
Hazardous voltages may exist when opening the secondary circuits of live current
transformers.
Warning:
Make sure that in-field current transformer secondary circuits are shorted out
before making or removing any connection to the current transformer (CT) input
terminals.
38 1601-0320
Chapter 2 - Installation
REMOVAL
Caution:
LOTO (Lockout Tag Out) of the system is required prior to module removal/
replacement.
1. Remove the draw-out unit from the chassis. Carefully set aside.
2. Within the captive chassis, unscrew the mounting screw (as indicated in the following figure).
3. Insert the magnetic module extractor tool as shown in the following figure, without engaging the pins.
4. Slide the tool to the left, engaging the pins fully (see arrow in figure).
5. Pull the tool handle towards the operator to disengage the module, and carefully remove the module from the
chassis.
6. Remove the tool from the module, and save for future use.
REPLACEMENT
Caution:
LOTO (Lockout Tag Out) of the system is required prior to module removal/
replacement.
Ensure the replacement CT /VT module is the same type as the removed module.
Alternate models and configurations may be unsafe for use.
1. Insert the extractor tool into the front of the module, then slide the tool to the left to engage the tool pins.
2. Place the module/tool at the front of the chassis so that it is flush with the left and bottom sides.
3. Slide the module/tool into the back of the chassis as far as it will go, making sure the connectors mate while
keeping the module flush to the left and bottom sides of the chassis.
4. Tighten the captive mounting screw using a torque of 6 in-lbs.
5. Remove the tool from the magnetics module and save for future use.
6. Insert the draw-out unit.
7. Re-energize the relay system.
1601-0320 39
Chapter 2 - Installation
40 1601-0320
Chapter 2 - Installation
Figure 16: RMIO - DIN rail mounting - Base & Expansion units
1601-0320 41
Chapter 2 - Installation
42 1601-0320
Chapter 2 - Installation
1601-0320 43
Chapter 2 - Installation
Caution:
If the Arc Flash Protection is used, operands for Arc Flash sensor failures must be
assigned to an auxiliary output relay. This must be connected to the control logic of
the breaker equipment to ensure safe operations when the output relay is asserted.
In the event of this assertion, the Hazard Reduction Category code cannot be
maintained unless backup protection is continuing to maintain it.
Caution:
Arc Flash sensor fiber is pressure sensitive and must be handled carefully to avoid
damage. Read the following guidelines fully before proceeding.
44 1601-0320
Chapter 2 - Installation
Installlation
Figure 21: AF Sensor - dimensions of sensor tip
Note:
The sensor fiber should be secured loosely for the best long-term performance. Avoid over-tightening ties which may deform
or break the sensor fiber.
Before installing the AF sensor unit, ensure that all other drilling and installation is complete to minimize possible
damage to the sensitive unit.
1601-0320 45
Chapter 2 - Installation
To install the AF sensor and route the sensor fiber, follow these steps:
1. Choose a location for the sensor clear of any obstructions that could shield the sensor from arc flash light.
2. Mount the sensor securely, using the mounting screw holes.
3. Once the sensor is securely mounted, carefully route the sensor fiber from the AFS sensor to the base unit,
minimizing loops and curves for the strongest possible signal.
4. Secure all sensor fibers (loosely but securely) away from any moving parts.
Note:
Both the AF sensor connections (CH 1 through CH 4) and the sensor cables are shipped with dust caps in place to avoid dust
contamination. The small rubber dust caps must be removed before operation.
46 1601-0320
Chapter 2 - Installation
S W
WAS
1 2 3
LO
T L
T L
BLO
D D
1601-0320 47
Chapter 2 - Installation
48 1601-0320
Chapter 2 - Installation
1601-0320 49
Chapter 2 - Installation
Note:
Make sure that the first letter on the terminal strip corresponds to the slot location identified on the chassis silkscreen.
Due to the possible number of applications, it is not possible to present typical connections for all possible schemes.
The information in this section covers the main aspects of interconnectivity, in the general areas of inputs, outputs,
communications and grounding. The figure below shows the rear terminal layout of the 8 Series platform.
50 1601-0320
Chapter 2 - Installation
1601-0320 51
Chapter 2 - Installation
Power Supply
H - HV Power Supply L - LV Power Supply
Terminal Description Terminal Description
(DC Voltage input polarity)
1 Line 1 +ve (positive)
2 Neutral 2 -ve (negative)
3 Ground 3 Ground
Communications
SE - Comms - Basic Ethernet 1E/1P/3E/3A - Comms - Advanced Ethernet
Terminal Description Terminal Description
1 IRIG-B (+) 1 IRIG-B (+)
2 IRIG-B (-) 2 IRIG-B (-)
3 RS485_1 (+) 3 RS485_1 (+)
4 RS485_1 (-) 4 RS485_1 (-)
5 RS485_1 COM 5 RS485_1 COM
6 RESERVED 6 RESERVED
7 RESERVED 7 RESERVED
8 optional RMIO COM 8 optional RMIO COM
9 optional RMIO + 9 optional RMIO +
10 optional RMIO - 10 optional RMIO -
RJ45 ETHERNET RJ45 NOT USED
52 1601-0320
Chapter 2 - Installation
! " " #
"! $% &' (
)* ! " " # "! $% &' +
,&,+ -' " ' %. '!/ ! #! "
0'! 01'/
2 *%" ' " % 3!1 ( ) / 43()5
$% " - &' ( '/
22 3!- & "' "'!" 67 % 3' ! )*
1601-0320 53
Chapter 2 - Installation
AC Analog
AC Inputs - 1 X 3-Phase 1/5A CT, 4 AC Inputs - 1 X 3-Phase 1/5A CT, 4 AC Inputs -2 X 3 - Phase 1/5A CT, 4
VT (Slot J) VT (Slot K-P1/P5) VT (Slot K - R1/R5)
Terminal Description Terminal Description Terminal Description
54 1601-0320
Chapter 2 - Installation
1 1 1 1
L
S N
G
T 9 9 9 9
R 8 8 8 8
7 7 7 7
6 6 6 6
ot + B 5 5 5 5
1 1 1 1
- B
B
C
Figure 30: RMIO terminal identification with 4 IO_G modules
1601-0320 55
Chapter 2 - Installation
w !"#g$%&
g&u'5 bu
56 1601-0320
Chapter 2 - Installation
Caution:
Verify that the relay’s nominal input current of 1 A or 5 A matches the secondary
rating of the connected CTs. Unmatched CTs may result in equipment damage or
inadequate protection.
Caution:
IMPORTANT: The phase and ground current inputs correctly measure up to 46
times the current input’s nominal rating. Time overcurrent curves become
horizontal lines for currents above 20 × PKP.
The ground input (Terminals J7 and J8) is used in conjunction with a Zero Sequence CT as source, or in the neutral
of wye-connected source CTs. The ground current input can be used to polarize both the neutral and sensitive
ground directional elements. When using the residual connection, set the GROUND CT PRIMARY setpoint to a
value equal to the PHASE CT PRIMARY setpoint. The sensitive ground current input is intended for use either with
a CT in a source neutral of a high-impedance grounded system, or on ungrounded systems. On ungrounded
systems it is connected residually with the phase current inputs. In this case, the SENSTV GND CT PRIMARY
setpoint should be programmed to a value equal to the PHASE CT PRIMARY setpoint. The sensitive ground
current input can be connected to a Zero Sequence CT for increased sensitivity and accuracy when physically
possible in the system.
1601-0320 57
Chapter 2 - Installation
Figure 32: Ground inputs
58 1601-0320
Chapter 2 - Installation
Alternatively, the 50:0.025 ground CT input has been designed for sensitive ground current detection on high
resistance grounded systems where the GE Digital Energy 50:0.025 corebalance CT is to be used.
For example, in mining applications where earth leakage current must be measured for personnel safety, primary
ground current as low as 0.5 A primary may be detected with the GE Digital Energy 50:0.025 CT. Only one ground
CT input tap must be used on a given unit.
Note that when this CT input is selected for the Ground Fault function, fixed ratio of 50:0.025 A is used by the relay.
1601-0320 59
Chapter 2 - Installation
34 56768695
:;<=>?@A@B:= CD
!
60 1601-0320
Chapter 2 - Installation
G o
o
T& '(&)*+,
-)./ 01 &*
LOA
l&2+ .3+1
99 !"#
LOA
1601-0320 61
Chapter 2 - Installation
!"#$ &
!"#$ '
789:;9<
62 1601-0320
Chapter 2 - Installation
Caution:
Control power supplied to the relay must match the installed power supply range. If
the applied voltage does not match, damage to the unit may occur. All grounds
MUST be connected for normal operation regardless of control power supply type.
Caution:
The relay should be connected directly to the ground bus, using the shortest
practical path. A tinned copper, braided, shielding and bonding cable should be
used. As a minimum, 96 strands of number 34 AWG should be used. Belden catalog
number 8660 is suitable.
1601-0320 63
Chapter 2 - Installation
Note:
The same type of input signal must be connected to all contact inputs on the same contact input card.
64 1601-0320
Chapter 2 - Installation
I
SI
SI
(
I
SI
SI
( Y
E
D
SY
1601-0320 65
Chapter 2 - Installation
66 1601-0320
Chapter 2 - Installation
13 Digital In_1 Analog In_4 ARC FLASH 13 Digital In_1 Analog In_4 Digital In_8
Sensor 1 Sensor
14 Digital In_2 Return 2 Sensor 3 14 Digital In_2 Return Digital In_9
Sensor 4
15 Digital In_3 Shield 15 Digital In_3 Shield Digital In_10
1601-0320 67
Chapter 2 - Installation
13 Digital In_1 Digital In_8 ARC FLASH 13 Digital In_1 ARC FLASH
Sensor 1 Sensor 1 Sensor
14 Digital In_2 Digital In_9 Sensor 2 14 Digital In_2 2 Sensor 3
Sensor 3 Sensor 4
15 Digital In_3 Digital In_10 15 Digital In_3
Sensor 4
16 Digital In_4 Digital In_11 16 Digital In_4
68 1601-0320
Chapter 2 - Installation
F 4;9 E
% 5'G H
5 5'G (
G
/
II J
'( )*+), J
5'G H
4;9 / 5'G (
47<=+>?@@< 1&2 AB3, ?CD 1 C09
:
!"#$
Caution:
To ensure that all devices in a daisy-chain are at the same potential, it is imperative
that the common terminals of each RS485 port are tied together and grounded at
the master end. Failure to do so may result in intermittent or failed
communications.
The source computer/PLC/SCADA system should have similar transient protection devices installed, either
internally or externally. Ground the shield at one point only, as shown in the figure above, to avoid ground loops.
Correct polarity is also essential. The relays must be wired with all the positive (+) terminals connected together and
all the negative (–) terminals connected together. Each relay must be daisy-chained to the next one. Avoid star or
stub connected configurations. The last device at each end of the daisy-chain should be terminated with a 120 ohm
¼ watt resistor in series with a 1 nF capacitor across the positive and negative terminals. Some systems allow the
1601-0320 69
Chapter 2 - Installation
shield (drain wire) to be used as a common wire and to connect directly to the COM terminal; others function
correctly only if the common wire is connected to the COM terminal, but insulated from the shield. Observing these
guidelines ensure a reliable communication system immune to system transients.
70 1601-0320
Chapter 2 - Installation
2.22 IRIG-B
IRIG-B is a standard time code format that allows time stamping of events to be synchronized among connected
devices within 1 millisecond. The IRIG-B time code formats are serial, width-modulated codes which can be either
DC level shift or amplitude modulated (AM) form. The type of form is auto-detected by the relay. Third party
equipment is available for generating the IRIG-B signal; this equipment may use a GPS satellite system to obtain
the time reference so that devices at different geographic locations can also be synchronized.
! "#
$%& '())*'+,()
(%+,()-.
<=<>?@
A<BC DEFC
>CGC=HAE= 3 01 /
IJK LMNOP QR
STUVNPWJX TQJWVSPXJ 4 02
LNYZSV KSZ [X WLXJ\
56275189:;0
Figure 40: IRIG-B connection
1601-0320 71
Chapter 2 - Installation
72 1601-0320
Chapter 2 - Installation
6
R S ¡ ÷ ø ùú û ü ÷ 8
TU V W TXY TZ VwY Tx Ty Tz { { ¢£Y¤¥¦§¤¥¨ ¤©ª«¬ ¤¥Y ¤ ® «¥¯ «° ±² ¤X ³ ýþ ¤ÿ ¤ ¤ T ¥ ¥¥ W UX ¥Z T T C D EF
{ {
[\ ]^ _ ]|}~ { ´µ e¶ · ¸¹ º »¼ ½ ½ ¾ ¿À ]| ^ | ] G HJI
{ L NK M
PQ R O T UVWWX YZ[
` ` ` ` { ÁÂ ÃÄ Å Æ Ç Æ Ç { Æ Æ Æ Æ ] ^
S \
` b
abcd e fg f| Ⱦ Éd Ê ¾ É È !"# _
hijkl { { ËÌ Í Î { c d Ò ef a
ghhhhhhh
{ { { { nopq
r stuvwx wyzux{w|s ijklm
i}k~ ijklm o
wv vv
I Í 3 ¡ Ý
Í ¢£ ¦ 3¦§ Þè èÞ
ÇF
¤¥ ÔÕÖ ßèZ Y
× ØÙ4ÚB à Ý[pè
# á
¨ © ª«¬ Íw ÊZ ËÌ Í W Ç ÜÝÞ Û
ß ¦3¦à ±
®¥z I ª ͯ ° ÈÉ á
±²³ '''´ µ Î
¶·¸ I Í Í y
®¹º » ¼½¾¿À Å
Æ ÇÒ
ÏÐÍÑ
®¹¥ I ÁÂÃÄ Ó
åæ
Ç£ è# # Zé
âãããããããããããããããããããããããããããããããããã ä ç
êë ö ~èÒ Ò ~ è
÷
è Z èÒ
nì¥X I ÍíîÍ¥ { { Ç¥¥
å
UW
ÇWW
ï𥯠I ÍÍíñ Íò Í Ë
ó¥y I Ííô Íw õ øùúû üý þÿú Ç W Ê
nì¥z I Ííîͯ
ï ¸ ÍÍ Íy
ï h ¿ ¾ ~
¥ ï I ÁÂÃÄ YVWX
ST£ U Y W
!!!!!!"!!!!"!!!!!!!!!!!!!!!!!!#$ YVWY
% I Í Í & '
¹ I ÍÍí( )
X I ÍÍ* í+ X UZ [\ YVW
, I ÍÍ Í - ]
w I Ííô Íw 2 Å YVW
. I Ííîͯ 3 \
#U¥
y I ÍÍ Íy 4 å_ YV^£
z I Í/ Íz
01 I ªÍ ͸ ÷
# UW
¥º I Í Í `a
U¥ » ¿ ¾~ Y W
V ¥W
¹ Á¹ÃÄ i}kl 5 k6 78 9:k;< =k>?@kAjB
¼C ®D EÍ~ GÚ 4 H IJ4K Ú Ù L AHB2 ÚÙ4 M NÚ AO PQRKÙ U¯
F åb YcWW
d eDf¹ g øùúûhi 9júkl múnl@úojB
¼X pqrÍ~X t hhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhhh u
¼Ã pvw rÍ~à s xyyyyyyyyyy yyyyyyyyyyy yyyyyyyyy yyy yyyyyyy yyy z
{yyyyyyyyyyyyyyyyyyyyyyyyyyyyyy| } ¿ DC
KKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK ¥ w
¿ E w X
y
¼¹ ¼½
)
wò ¯
³ ¶ Dº °
¾ 3±
¼X E
¿
yz ³
² ´ µ ·¸¹D¯»¼½¿
z X ÀÁÁÂÀÃ
¼w ¼½ ¼¿ Äy
¼. ¿ ÅÃ E Æ
£
ÍEg w Ç
¼z E ¸ Cº ¿ DÈÉ
Ê Ã˵µÌÍÎ
¼¸ Ír ¼¿ D¥
º Ï ÐµÑ ÒÓ ÕÖ×)
¥ ¼¿ ¥º
ÔwXØ
¼¹ ¿ ijk? ¡ k6 ¢£ 9:kk6 k6 ¤jkki¥ =k>?¦kAjB Ù Ú wÃ
¥¥
¥X ¼¿ . ˵µÌÍÜ
wÛ
ò E~ ¥¥ ¹ § Ú¨¡¡13 ©ª 4H« ¬1¡¡B3 3 Ú ABÙ® ¿ w.
âã Z Þ äåæ * ¥¹
Írî wç
Zß # è ¼¥ ¯ ¼ r E Är Dz
B H B3 ê B
ë Írî ì íííííííííííííííííííííííííííííí
é z E rÄE î
ïðñò ódôdõ ö÷ øùú û ¼üüüüüüüü ýüüüüüüüüü ýüüüüüüüüüüüüþ
ããããã ããããããããããããããããããããã
§Úÿ úúû üýþýÿ ÿ ÿ ý þ ý
rî ñ
Í ! "
# $% &'()*+, {
1 2 Í 3456
{
-./0 h }
789:
>?@A ;<= B
i}k ? 5 9:kkj =k>l kAjB
C h
vv ¡¢£ ¤ ¥¥¥ ¦ § ¨©ª¨« ¬ ®¯°±²³ ¬´ µ¶ ·¸ ¬¹º»©¼ ½ ( ) * + , - . / (0 ¥( (1 (* ( (, (- ( (9 (: ); 1¥ <== )* ?@
¨ Ã ¨
2 3 > K L
ÁÂà ÄÅÆÇÈÉÊË Ì¾¿ÍÎ À ëâ ã
ÏÐÑÒÒÓÔÕÖ×ÒØ 4 5 6 ãóéã #ã MN O P
ÚÛÜÜÜÜÜÜÝÙÞßÜà Í
Í
á âáã äWã å âã æè#çã è î ÷ Í
éáêáèëé#dã ãç èçì í
ï
Í
Í U«£ VWQRST
¥XY«¥CZ¤ [CX «¥
\ ] ] ] ]^_ ] ]^_ ] ]`ab
¹ ò
ð
ñ
òëã ä#ã 7
è óã ãã
èæ é ëãã õ
ô çìë8 ä#8 è
ëããã æé ëãã
è#é# ä
è
çé#ä cdefdghijklm
ö øù
1601-0320 73
Chapter 2 - Installation
74 1601-0320
CHAPTER 3
INTERFACES
Chapter 3 - Interfaces
76 1601-0320
Chapter 3 - Interfaces
1601-0320 77
Chapter 3 - Interfaces
Basic Security
If the relay is in the commissioning phase and you want to bypass authentication, switch the SETPOINT ACCESS
setting on or assign it to a contact input. Once the setting is on, you have complete administrator access from the
front panel. If a contact input is chosen, the access is also conditional on the activation of the respective contact
input.
For more information on setpoint access and other security features available with basic security, refer to Basic
Security.
CyberSentry
If logging in through EnerVista D&I Setup software, choose Device authentication and login as Administrator.
Note:
If the relay is in the commissioning phase, to bypass authentication use the setpoint access feature to gain administrative
access to the front panel in the same way as with basic security.
78 1601-0320
Chapter 3 - Interfaces
Note:
These figures are representative only. They may not reflect the exact model that this manual describes.
1601-0320 79
Chapter 3 - Interfaces
80 1601-0320
Chapter 3 - Interfaces
1601-0320 81
Chapter 3 - Interfaces
894319A1
82 1601-0320
Chapter 3 - Interfaces
894319A1
1601-0320 83
Chapter 3 - Interfaces
The tab pushbuttons are used to enter the menu corresponding to the label on the tabs. If more than 5 tabs exist,
the first and the last tab are labeled with arrows to allow you to scroll to the other tabs.
84 1601-0320
Chapter 3 - Interfaces
● The Up, Down, Left and Right pushbuttons on the membrane faceplate are used to move the yellow
highlight. These pushbuttons are also used on special screens to navigate to multiple objects.
● The Escape pushbutton is used to display the previous menu. This pushbutton can also be used to cancel a
setpoint change.
● The Reset pushbutton clears all latched LED indications, target messages, and latched output relays,
providing the conditions causing these events are not present.
1601-0320 85
Chapter 3 - Interfaces
Figure 49: Single Line Diagram example, see order code (3-P1/P5) for slot K
Setpoints > Device > Front Panel > Default Screen (3-R1/R5)
Figure 50: Single Line Diagram example, see order code (3-R1/R5) for slot K
The breaker status icon changes state according to the breaker status input and the color of the icon changes in
accordance with the color scheme setting (Setpoints > Device > Front Panel > Display Properties > Color
Scheme). The breaker and generator status color is based on the following logic.
86 1601-0320
Chapter 3 - Interfaces
Note:
The Unknown status has a white background with black text.
When breaker detection Connected/Disconnected (Racked-In/Racked-Out) is configured, the symbols change with
respect to the Connected/Disconnected state of the breaker. The following table further illustrates this with an
example of the switching device Close state when the color scheme is set to Green (Open).
*8 Series 889 considers the breaker state Connected when detection of the Connected/Disconnected state of the
breaker is not configured. Connected/Disconnected detection is not configured when setpoint Connected (under
Setpoints > System > Breaker) is set to Off.
The parameters displayed in the Front panel screen example are as follows.
Parameter Input for the value
Load Cur Metering\ Generator\ General\ Load Current
Unbln Metering\ Generator\ General\ Unbalance Current
Volt (L-L) Metering\ Ph VT Bnk1-J2\ J2 V AVG L-L
Freq Metering\ Frequency 1-J\ J2-3VT Frequency
V/ Hz Metering\ Volts per Hertz\ Volts Per Hertz 1
S: Metering\ Power 1\ Pwr1 Apparent
P: Metering\ Power 1\ Pwr1 Real
Q: Metering\ Power 1\ Pwr1 Reactive
PF Metering\ Power 1\Pwr1 PF
1601-0320 87
Chapter 3 - Interfaces
Note:
The rugged front panel is is not available for all models. See the order codes for details
Figure 51: LED numbering
Some status indicators are common while some are feature specific which depend on the availability in the order
code. The common status indicators in the first column are described below.
88 1601-0320
Chapter 3 - Interfaces
Breaker status indication is based on the breaker’s 52a and 52b contacts. With both contacts wired to the relay and
configured, closed breaker status is determined by closed 52a contact and opened 52b contact. Vice-versa the
open breaker status is determined by opened 52a contact and closed 52b contact. If both 52a and 52b contacts are
open, due to a breaker being racked out from the switchgear, both the Breaker Open and Breaker Closed LED
Indicators will be off.
The Event Cause indicators in the first column are described as follows:
Events Cause LEDs are turned On or Off by protection elements that have their respective target settings selected
as either Self-Reset or Latched. If a protection element target setting has Self-Reset selected, then the
corresponding Event Cause LEDs remain On as long as the operate operand associated with the element remains
asserted. If a protection element target setting is Latched, then the corresponding Event Cause LEDs turn On
when the operate operand associated with the element is asserted and will remain On until the RESET button on
the front panel is pressed after the operand is reset.
Default labels are shipped in the package of every product, together with custom templates. A custom LED template
is available for editing and printing. You can download the document GET-20035 from the website. The default
labels can be replaced by user-printed labels. Customization of LED operation is of maximum benefit in installations
where languages other than English are used to communicate with operators.
Note:
The Ten-pushbutton front panel is only available for the 850. See the order codes for details.
1601-0320 89
Chapter 3 - Interfaces
triggered by either a selection of FlexLogic operand assigned in their own menu, or by the operation of any
protection, control or monitoring element with function selected as Trip, Alarm, or Latched Alarm.
The RESET key is used to reset any latched LED indicator or Target Message once the condition has been cleared
(latched conditions can also be reset via the RESETTING menu).
90 1601-0320
Chapter 3 - Interfaces
Some status indicators are common while some are feature specific which is dependent upon the order code. The
common status indicators in the first column are described below.
Status Indicator Description
IN SERVICE This LED indicates that control power is present, all monitored inputs, outputs, and
internal systems are OK, and that the device is programmed.
TRIP This LED indicates that the FlexLogic operand serving as a trip switch has operated. This
indicator always latches so a reset command must be initiated to allow the latch to be
reset.
ALARM This LED indicates that the FlexLogic operand serving as an alarm switch has operated.
Latching of the indicator depends on the selected protection function. The Reset
command must be initiated to allow the latch to be reset.
PICKUP This LED indicates that at least one element is picked up. This indicator is never latched.
TEST MODE This LED indicates that the relay has been set into Test Mode.
MESSAGE This LED indicates the presence of Target Messages detected by the relay.
PHASE A FAULT This LED indicates that phase A of the Phase Time Overcurrent 1 function has operated.
PHASE B FAULT This LED indicates that phase B of the Phase Time Overcurrent 1 function has operated.
PHASE C FAULT This LED indicates that phase C of the Phase Time Overcurrent 1 function has operated.
GROUND FAULT This LED indicates that the Ground Time Overcurrent 1 function has operated.
50P INST OC This LED indicates that the Phase Instantaneous Overcurrent 1 function has operated.
1601-0320 91
Chapter 3 - Interfaces
27 PHASE UV This LED indicates that the Phase Undervoltage 1 function has operated.
(Order Code without Autoreclose)
LOCKOUT This LED indicates that the Autoreclose function has reached the lockout stage.
(Order Code with Autoreclose)
Note:
The security icon only represents the security access level through the front panel.
Do not remove power from the relay whenever the Settings Save icon is ON. When power is removed the data being saved
can also be lost.
92 1601-0320
Chapter 3 - Interfaces
MESSAGE TIMEOUT
The timeout applies to every screen apart from the default screen. Examples include viewing, metering, or
navigating to a screen with setting, etc. If no further navigation is performed, no pushbutton is touched, and/or no
target is initiated for the time specified in the message timeout setpoint, the display goes back to the default screen
(the metering summary screen).
The target message overrides the message timeout. The message timeout starts timing after each target message,
and if no more activity is recorded for the specified time, the display goes back to the default screen.
Pressing a programmable pushbutton activates a new screen with a Target Message corresponding to the
programmed pushbutton action. The pushbutton Target Message is displayed for 10 seconds then defaults to the
screen that was displayed before pressing the pushbutton. The pushbutton Target Message is recorded in the list
with other generated Target Messages.
Target Messages can be cleared either by pressing the pushbutton corresponding to the CLEAR tab, or by initiating
a RESET command. The CLEAR command clears only the Target Messages, while initiating a RESET clears not
only the Target Messages, but also any latched LEDs and output relays.
Caution:
Self-Test Warnings may indicate a serious problem with the relay hardware!
1601-0320 93
Chapter 3 - Interfaces
94 1601-0320
Chapter 3 - Interfaces
1601-0320 95
Chapter 3 - Interfaces
96 1601-0320
Chapter 3 - Interfaces
1601-0320 97
Chapter 3 - Interfaces
Note:
When a total loss of power is present, the Critical Failure Relay (Output Relay 8) is de-energized.
98 1601-0320
Chapter 3 - Interfaces
The following procedures describes how to use the label removal tool.
1. Bend the tabs of the tool upwards as shown in the image.
2. Slide the label removal tool under the LED label as shown in the next image. Make sure the bent tabs are
pointing away from the relay. Move the tool inside until the tabs enter the pocket.
1601-0320 99
Chapter 3 - Interfaces
100 1601-0320
Chapter 3 - Interfaces
6. Select the complete path, including the new directory name, where the software is to be installed.
7. Click on Next to begin the installation. The files are installed in the directory indicated, the USB driver is
loaded into the computer, and the installation program automatically creates icons and adds the EnerVista
D&I Setup software to the Windows start menu.
8. The required device is added to the list of installed IEDs in the EnerVista D&I Setup software Launchpad IED
Setup window.
If you are going to communicate from your computer to the relay using the USB port:
1. Connect the USB cable from your computer to the relay's USB port.
2. Launch EnerVista D&I Setup software from the LaunchPad. Then in EnerVista D&I Setup software 8 Series
setup software > Device Setup, select USB as the Interface type.
3. Select the Read Order Code button.
Note:
The relay supports a maximum of 3 TCP/IP sessions.
1. Install and start the latest version of the software (available from the GE Multilin Website). See the previous
section for the installation procedure.
2. Click on the Device Setup button to open the Device Setup window and click the Add Site button to define a
new site.
3. Enter the desired site name in the Site Name field. If desired, a short description of the site can also be
entered. In this example, we will use Substation 1 as the site name.
4. The new site appears in the upper-left list.
5. Click the Add Device button to define the new device.
1601-0320 101
Chapter 3 - Interfaces
6. Enter the desired name in the Device Name field, and a description (optional).
7. Select Ethernet from the Interface drop-down list. This displays a number of interface parameters that must
be entered for proper Ethernet functionality.
8. Enter the IP address, slave address, and Modbus port values assigned to the relay (from the Setpoints >
Device > Communications menu).
9. Click the Read Order Code button to connect to the relay and upload the order code. If a communications
error occurs, ensure that the Ethernet communication values correspond to the relay setting values.
10. Click OK when the relay order code has been received. The new device will be added to the Site List window
(or Online window) located in the top left corner of the main EnerVista D&I Setup software window.
The Site Device has now been configured for Ethernet communications.
102 1601-0320
Chapter 3 - Interfaces
the relay settings, and the EnerVista D&I Setup software settings in order to connect to the relay through the USB
port.
1. Open the Windows Control Panel and select Network and Internet > Network Sharing. The exact path may
vary depending on the version of Windows.
3. Find the GE RNDIS Device (or GE RNDIS Device #2) and right-click the network it is on to open the
Properties window.
4. Select Internet Protocol Version 4 (TCP/IPv4) and click Properties.
5. In the Internet Protocol Version 4 (TCP/IPv4) Properties window, ensure that Use the following IP Address
is selected, and enter an appropriate IP address.
1601-0320 103
Chapter 3 - Interfaces
104 1601-0320
Chapter 3 - Interfaces
3. Select the Aux. VT Secondary setpoint by clicking anywhere in the parameter box. This displays three
arrows: two to increment/decrement the value and another to launch the numerical keypad.
4. Clicking the arrow at the end of the box displays a numerical keypad interface used to enter values within the
setpoint range displayed near the top of the keypad: Click = to exit from the keypad and keep the new value.
Click on X to exit from the keypad and retain the old value.
1601-0320 105
Chapter 3 - Interfaces
5. For setpoints requiring non-numerical pre-set values (e.g. Phase VT Connection below), clicking anywhere
within the setpoint value box displays a drop-down selection menu arrow. Select the desired value from this
list.
6. In the Setpoints > System Setup > Voltage Sensing dialog box, click on Save to save the values into the
relay. Click YES to accept any changes and exit the window. Click Restore to retain previous values. Click
Default to restore Default values.
7. For setpoints requiring an alphanumeric text string (e.g. relay name), the value may be entered directly within
the setpoint value box.
Note:
When using Setpoint Groups, an element from one group can be dragged and dropped on the same element in another
group, copying all settings.
106 1601-0320
Chapter 3 - Interfaces
● Monitoring
● FlexLogic
● Quick setup
● Protection summary
● IEC 61850 configurator
● Modbus user map
Factory default values are supplied and can be restored after any changes.
The relay displays relay setpoints with the same hierarchy as the front panel display.
1601-0320 107
Chapter 3 - Interfaces
4. To select a file name and path for the new file, click the button beside the File Name box.
5. Select the file name and path to store the file, or select any displayed file name to replace an existing file. All
setpoint files should have the extension .CID.
6. Click OK to complete the process. Once this step is completed, the new file, with a complete path, is added
to the software environment.
Note:
Offline settings files can be created for invalid order codes in order to support file conversion from different products,
upgrades, and special orders. To validate an order code, visit the GE Multilin online store.
Filenames for setting files cannot have a period character (.) other than the one that is added in front of CID.
108 1601-0320
Chapter 3 - Interfaces
Note:
An error message occurs when attempting to upload a setpoint file with a revision number that does not match the relay
firmware.
The following procedure illustrates how to load setpoints from a file. Before loading a setpoints file, it must first be
added to the software environment.
1. Select the previously saved setpoints file from the File pane of the main window.
2. Select the Offline > Edit Settings File Properties menu item and verify that the corresponding file is fully
compatible with the hardware and firmware version of the target relay.
3. Right-click on the selected file and select the Write Settings File to Device item.
4. Select the target relay from the list of devices shown and click Send. If there is an incompatibility, an
Incompatible device order codes, versions or Serial Locks error will occur.
If there are no incompatibilities between the target device and the settings file, the data is transferred to the relay.
An indication of the percentage completed is shown in the bottom of the main window.
1601-0320 109
Chapter 3 - Interfaces
Quick Setup is designed for quick and easy user programming. Power system parameters, and settings for some
simple overcurrent elements are easily set. The Quick Setup screen works as follows:
● Settings names and units can be viewed at this screen. To view the range of the settings, hover the cursor
over the setpoint value field.
● Configure and save the settings as required.
● The Save, Restore and Default buttons function the same as in the individual setting setup screens.
● Attempting to enter and save a setting value which exceeds the range gives a warning dialog box. Correct the
setting value and save to proceed.
Note:
In Quick Setup, the value is not replaced with the maximum value of the setting.
For example, the Phase CT Primary setting has a range of 1 to 12000, but the user enters 12001 and tries to
save it. Quick Setup displays a warning dialog. Pressing OK leaves the setting value at 12001, but not 12000
(max. value) as is the case with other views.
Note:
EnerVista D&I Setup software prevents incompatible firmware from being loaded into a relay.
Uploading firmware on a WiFi interface is not allowed.
Before upgrading firmware, it is very important to save the current settings to a file on your PC. After the firmware has been
upgraded, it will be necessary to load this file back into the relay.
110 1601-0320
Chapter 3 - Interfaces
5. A screen appears confirming the firmware versions of the target device and the selected .SFD. Click YES to
proceed with the firmware loading process.
6. EnerVista D&I Setup software will prompt the user to reboot the relay after both the Boot 1 and Boot 2
uploads.
Note:
The relay should be rebooted BEFORE pressing OK.
Note:
Wait for the relay to boot up, then cycle power to the relay to complete the firmware update process.
After successfully updating the firmware, the relay is not in service and requires setpoint programming. To
communicate with the relay, the communication settings may have to be manually reprogrammed.
When communication is established, you must reload the saved setpoints back into the relay.
Modbus addresses assigned to features, settings, and corresponding data items (i.e. default values, min/max
values, data type, and item size) may change slightly from version to version of firmware. The addresses are
rearranged when new features are added or existing features are enhanced or modified.
1601-0320 111
Chapter 3 - Interfaces
For optimum use, the first SLD page can be used for the overall SLD and the subsequent pages can be used for
breaker/switch specific CT/VT placement, metering and status. Once the configurable SLDs are programmed, they
are saved within the relay settings file. The SLD pages can also be saved individually as local XML files. The locally
stored XML files can then be reloaded to generate another diagram. SLDs represent objects using GE symbols
(similar to ANSI).
The following figure shows the objects that are available for design in the SLD Configurator and their maximum
usage limits [X]. The maximum limit reflects the maximum possible order code.
112 1601-0320
Chapter 3 - Interfaces
Note:
The displayed breaker name is configured in the setpoint Setpoints > System > Breakers > Breaker[X] > Name. This
setpoint has a 13-character limit. The name should be kept to a minimum so that it appears properly on the SLD.
1601-0320 113
Chapter 3 - Interfaces
Note:
GE symbols are color-coded ANSI symbols.
The control objects status follows the color scheme from the Setpoints > Device > Front Panel > Display
Properties > Color Scheme setting. By default, this setting is set to Green (open). If set to Red (open), the
status colors are reversed.
If the setting is used, the breaker symbols automatically change to the Truck CB symbols. The SLD assumes that if
the Breaker Racked-In/Racked-Out input is used (anything other than Off), the appropriate Truck CB symbol will
be used.
The following figure shows the orientation available for the control objects. The default position for the control
objects is 0 degrees. Orientation in multiple directions allows for configuration of the single line diagram according
to the existing drawings and ensure the correct side for the fixed/moving contacts.
114 1601-0320
Chapter 3 - Interfaces
In addition, Remote Breaker status objects are added for GE and IEC style. Remote breaker status allows
monitoring of three distant breakers. These objects are not controllable and hence cannot be used for selection and
operation.
1601-0320 115
Chapter 3 - Interfaces
3.4.6.6.1 NAVIGATION
The SLD can be accessed in two ways from the front panel of the relay. The original location for the SLD pages is
under Status > Summary > Single Line Diagram > SLD [X]. However, a more convenient way to access an SLD
116 1601-0320
Chapter 3 - Interfaces
page is by setting it as a default home screen at Setpoints > Device > Front Panel > Home Screens > Home
Screen1. Pressing the home button more than once rotates through the configured home screens. If the desired
SLD is set to Home Screen 2 through Home Screen 10, it can be activated by pressing home button until it
appears on the screen. If no home screen is configured, the default screens become active. If the default screens
are disabled, Status > Summary > Values screen is shown.
While browsing through switches/breakers the active element is shown with a blue colored border around it. To
select a breaker/switch, the browsing indicator border must be around the desired breaker or switch. The breaker or
switch can then be selected by pressing the Enter key. As the breaker or switch is being selected, a flash message
appears indicating that the breaker or switch has been selected as shown in the following figure. Once the element
is selected for operation, the SLD control pushbuttons appear and the color of the highlighter will change to maroon
indicating that the breaker or switch is selected. By default, the control pushbuttons are programmed for Tag,
Block, and Bypass. For each control action, a flash message is displayed.
1601-0320 117
Chapter 3 - Interfaces
Browsing and selection is allowed only when the relay is in Local Mode and the user has security access of at least
operator level. To check if the relay is in local mode, look for an LM symbol on the task pane at the top of the
screen. Pressing navigation keys on SLD pages while in remote mode does nothing.
Control pushbuttons appearing on the SLD page are only active while a control object is selected.
The control object is deselected if you navigate to any screen other than the SLD or by pressing the Escape key. If
no action is taken after selection, the object is automatically deselected after the Bkr/Sw Select timeout setting
(Setpoints > Control > Control Mode > Bkr/Sw Select Timeout). Once deselected, the control pushbutton labels
return to the SLD page navigation labels and the color of the box around the object changes back to blue for
browsing. Pressing Escape once more removes the browsing highlight around the objects. If inactive during
browsing for the timeout setting (Setpoints > Device > Front Panel > Message Timeout), the browsing highlight
around the object disappears. If an object is selected, Home button operation is prohibited. The object must be de-
selected by pressing Escape in order for the Home button to function.
After upgrading from firmware versions 1.3x to 1.7x, the breaker/contactor starting/stopping operations from the
front panel now follow a select-before-operate mechanism. The breaker/contactor must be first selected by
browsing and pressing the Enter key for selection. Once selected, the function can be started or stopped with the
front panel’s pushbuttons.
Note:
Remote operations are allowed for opening, closing, blocking, and bypassing. Tagging must be done locally.
It is recommended that tagging is only used for maintenance purposes. When a breaker or a switch is tagged, it cannot be
bypassed although the letters By may appear below the element on SLD.
If breaker is selected and relay status is changed to Out-of-Service, the breaker control actions, such as tag, blocked, bypass
and open/close are blocked. The breaker may remain in the selected state, but no action can be executed.
118 1601-0320
Chapter 3 - Interfaces
Once the selected breaker or switch is tagged, a letter T appears below the associated element. Similarly, for
blocking, letter B appears and for bypassing, letters By appear below the associated breaker or switch as shown in
the last column of the following figure. The blocking and bypassing letters also appear if the breakers/switches are
blocked or bypassed remotely. These are linked to their respective breaker/switch in the SLD Configurator window
so that when that breaker/switch is deleted, the letters also get deleted.
Permitted breaker/switch operations are described in the following figure when various letter indications are present
under the control element.
1601-0320 119
Chapter 3 - Interfaces
● The Operate Curves are displayed, which can be edited by dragging the tips of the curves
● A Base curve can be plotted for reference, to customize the operating curve. The blue colored curve in the
picture is a reference curve. It can be Extremely Inverse, Definite Time, etc.
● The Trip (Reset and Operate) Times in the tables and curves work interactively i.e., changing the table value
affects the curve shape and vice versa.
● Save Configured Trip Times.
● Export Configured Trip Times to a CSV file
● Load Trip Times from a CSV File
● The screen above shows the model for viewing FlexCurves. Select Initialize to copy the trip times from the
selected curve to the FlexCurve.
120 1601-0320
Chapter 3 - Interfaces
Note:
The COMTRADE Version used on 8 Series relays is C37.111-1999.
● With EnerVista D&I Setup software running and communications established, select the Records >
Transients > Transient Records menu item to open the Transient Recorder Viewer window.
● Click on Trigger to trigger a waveform capture.
● To view the captured waveforms, click on the Launch Viewer button. A detailed Waveform Capture window
appears as shown below.
● Click on the Save button to save the selected waveform to the local PC. A new window appears, requesting
the file name and path. One file is saved as a COMTRADE file, with the extension CFG. The other file is a
DAT file, required by the COMTRADE file for proper display of waveforms.
● To view a previously saved COMTRADE file, click the Open button and select the corresponding
COMTRADE file.
1601-0320 121
Chapter 3 - Interfaces
122 1601-0320
Chapter 3 - Interfaces
● From the window main menu bar, press the Preference button
to open the COMTRADE Setup page, in order to change the graph attributes. Change the color of each
graph as desired and select other options as required by checking the appropriate boxes. Click OK to store
these graph attributes and to close the window. The Waveform Capture window reappears based on the
selected graph attributes.
● To view a vector graph of the quantities contained in the waveform capture, press the View Phasors button
to display the following window:
1601-0320 123
Chapter 3 - Interfaces
With EnerVista D&I Setup software running and communications established, select the Setpoints > Protection
Summary menu item to open the Protection Summary window.
124 1601-0320
Chapter 3 - Interfaces
5. To select the SR settings file used for initialization, check the box to the left of Initialize Settings from SR
Settings File.
6. To locate and select the file to convert, click the ellipsis button beside the Initialize Settings from SR Settings
File box.
7. Click OK to begin the conversion and complete the process. Once this step is completed, the new file, with a
complete path, is added to the EnerVista D&I Setup software software environment.
Note:
If there are settings that are not applicable to the later model, they are ignored and will not appear in the settings list.
Note:
Print the Settings Conversion Report immediately following conversion for future reference in case the report is removed or
the settings are modified from the EnerVista D&I Setup software.
Note:
All other settings available (not shown in the conversion report) in the file are set to default and must be verified before putting
the relay into service.
Settings in the results window are linked to setting screens. Click in the results window to navigate to the corresponding
settings window.
Status Icons
The status icons show the conversion results:
Successful conversion
1601-0320 125
Chapter 3 - Interfaces
Print Report
If desired, the conversion summary report can be printed using the File/Print command in the taskbar or it can be
printed from the GUI print button.
Note:
Even if the report shows that a conversion has been successful (green checkbox icon), all settings must still be verified before
putting the relay in service.
126 1601-0320
CHAPTER 4
ABOUT SETPOINTS
Chapter 4 - About Setpoints
128 1601-0320
Chapter 4 - About Setpoints
1601-0320 129
Chapter 4 - About Setpoints
Note:
Use the path provided to access the menus from the front panel and from the EnerVista D&I Setup software software.
Certain named settings allow custom names. Do not create 13-character long names using the largest width characters (i.e.
WWWWWWWWWWWWW). Doing so can cause the last 3 characters to overlap the setting name when viewed from the HMI
or the EnerVista D&I Setup software software.
130 1601-0320
Chapter 4 - About Setpoints
1601-0320 131
Chapter 4 - About Setpoints
FUNCTION
The <ELEMENT_NAME> FUNCTION setpoint determines the operational characteristic of each feature. The range
for this setpoint is: Disabled, Trip, Latched Trip, Alarm, Latched Alarm and Configurable.
If the FUNCTION setpoint is selected as Disabled, then the feature is not operational.
If FUNCTION is selected as Trip or Latched Trip, then the feature is operational. When the Trip or Latched
Trip function is selected and the feature operates, the output relay #1 Trip operates (when selected as Trip
Relay), and the TRIP LED is lit.
When the Latched Trip function is selected and the feature operates, the TRIP LED and trip output operands will
remain latched. The Latched Trip can be reset by issuing the reset command.
If FUNCTION is selected as Alarm or Latched Alarm, then the feature is operational. When this function is
selected and the feature operates, the ALARM LED is lit and any assigned auxiliary output relays operate. The Trip
output relay does not operate, and the TRIP LED is not lit.
When FUNCTION is selected as Latched Alarm, operation of the Latched Alarm function depends on the
selection of the setting LATCH ALARM OPERATION, configured under Path: Setpoints > Device > Installation.
When the setting LATCH ALARM OPERATION is set to Self-Reset while an element is set to Latched Alarm,
only the Alarm LED will remain latched. When setting LATCH ALARM OPERATION to Latched, both Alarm LED
and element will remain latched.
When Alarm is selected and the feature operates, the ALARM LED flashes, and it self-resets when the operating
conditions are cleared.
If FUNCTION is selected as Configurable, the feature is fully operational but outputs are not driving any action,
such as output relay #1, ALARM LED or anything else. Operands from this element must be programmed to the
required action which may be as simple as the auxiliary output relay from the list of available relays in the element
itself; FlexLogic, Trip Bus etc.
Note:
The FlexLogic operands generated by the operation of each feature are active, and available to assign to outputs, or use in
FlexLogic equations, regardless of the selected function, except when the function is set to Disabled.
PICKUP
The setpoint selects the threshold equal to or above (for over elements) or equal to or below (for under elements)
which the measured parameter causes an output from the measuring element.
PICKUP DELAY
The setpoint selects a fixed time interval to delay an input signal from appearing as an output.
DROPOUT DELAY
The setpoint selects a fixed time interval to delay dropping out the output signal after being generated.
132 1601-0320
Chapter 4 - About Setpoints
TDM
The setting provides a selection for Time Dial Multiplier which modifies the operating times per the selected inverse
curve. For example, if an IEEE Extremely Inverse curve is selected with TDM=2, and the fault current is 5 times
bigger than the pickup level, operation of the element can not occur until 2.59 s after pickup.
OUTPUT RELAYS
The <ELEMENT_NAME> RELAYS setpoint selects the relays required to operate when the feature generates an
output. The range is Operate or Do Not Operate, and can be applied to any combination of the auxiliary output
relays. The default setting is Do Not Operate.
The available auxiliary relays vary depending on the order code.
DIRECTION
The <ELEMENT_NAME> DIRECTION setpoint is available for overcurrent features which are subject to control
from a directional element. The range is Disabled, Forward, and Reverse. If set to Disabled, the element is
allowed to operate for current flow in any direction. There is no supervision from the directional element. If set to
Forward, the OC element is allowed to operate when the fault is detected by the directional element in forward
direction. In this mode, the OC element does not operate for fault in reverse direction. If set to Reverse, the OC
element is allowed to operate when the fault is detected in reverse direction, and does not operate in forward
direction.
RESET
Selection of an Instantaneous or a Timed reset is provided by this setting. If Instantaneous is selected, the
element resets instantaneously providing the quantity drops below 97 to 98% of the pickup level before the time for
operation is reached. If Timed is selected, the time to reset is calculated based on the reset equation for the
selected inverse curve.
BLOCK
The <ELEMENT_NAME> BLOCK setpoint selects an operand from the list of FlexLogic operands, which when
active, blocks the feature from running. When set to On the feature is always blocked; when set to Off, block is
disabled.
EVENTS
The <ELEMENT_NAME> EVENTS setpoint can be set to Enabled, or Disabled. If set to Enabled, the events
associated with the pickup, operation, or other conditions of the feature are recorded in the Event Recorder.
TARGETS
The <ELEMENT_NAME> TARGETS setpoint can be set to Disabled, Self-Reset, or Latched. If set to Self-
Reset, or Latched, the targets associated with the pickup, operation, or another condition of the feature are
displayed on the screen of the 8 Series 889 relay. The targets disappear from the screen when Self-Reset is
selected, and the conditions are cleared. The targets stay on the screen, when Latched is selected, and the
conditions are cleared.
1601-0320 133
Chapter 4 - About Setpoints
Note:
The targets of status, control and pickup conditions are always self-reset type, regardless of the Self-Reset, or Latched
configuration of setpoint <ELEMENT_NAME> TARGETS.
To ensure the settings file inside the relay is updated, wait 30 seconds after a setpoint change before cycling power.
When IP addresses are changed and sent as a Settings file, the unit reboots twice.
134 1601-0320
Chapter 4 - About Setpoints
1601-0320 135
Chapter 4 - About Setpoints
136 1601-0320
CHAPTER 5
DEVICE SETPOINTS
Chapter 5 - Device Setpoints
138 1601-0320
Chapter 5 - Device Setpoints
1601-0320 139
Chapter 5 - Device Setpoints
@ AbG P
Ral Tm Cl ck
485
cury UB
C mmuca W-F
Set point s v !
Eh
"# $%& Tra Rc rdr
G =
? @ AbG D £
;:x<.2 !
alla
D> P
D >G
D >G
140 1601-0320
Chapter 5 - Device Setpoints
Configuration Mode
The 8-series platform, supports a multitude of functions and features including:
● Protection and Control (P&C)
● Asset Monitoring
● Flexible Logic Engine (FlexLogic)
● Records and Reporting
● Time Synchronization
● Testing/Simulation
Taking into consideration user experience, configuration mode controls how the Setpoints are presented by only
displaying settings that are typically used, or settings that are important to configure.
Two configuration modes are supported:
● Simplified - In this mode, some of the functions, features and settings are hidden or made read-only (grayed
out). All the settings made in Regular configuration mode are still applied during simplified mode (they are
either hidden or read-only), so simplified configuration mode can also be seen as a way of locking advanced
setpoints.
● Regular - In this mode, all function/features and setpoints of the device are editable and nothing is hidden or
grayed out.
Configuration mode is applicable to the Setpoints items only and does not control view/presentation to other main
menu items, such as Device Definition, Status, Metering, Records, Commands and Maintenance. The configuration
mode setting is available to be changed by the Administrator role. The configuration mode control is applicable to
device HMI and setup software, as well as online and offline setting files.
Note:
Configuration mode does not disable the device functionality or settings. It only controls the view or presentation on the HMI
and setup software screens. Therefore, settings which are hidden or Read-only are preserved and applied within the device.
The home icon on the home page changes color according to the configuration mode. When in Simplified
configuration mode, the home icon color is green. When in regular mode the home icon color is blue.
Note:
All setpoints under Regular mode are still applied and used by the device. For example the Input is hidden but configured as
Phasor during Regular mode, therefore Phase TOC 1 still applies Phasor as an input. Similarly, Reset is read-only, and
Phase TOC 1 still applies Instantaneous for resetting. The read-only settings are greyed out.
1601-0320 141
Chapter 5 - Device Setpoints
r Simplified
..\Current\Phase TOC 1 ..\Current\Phase TOC 1
Item Name Value Unit Item Name Value Unit
Function Disabled Function Disabled
Signal Input CT Bank 1 -J1 Signal Input CT Bank 1 -J1
Input Phasor
Pickup 1.000 x CT
Pickup 1.000 x CT
Curve IEEE Mod Inverse
Curve IEEE Mod Inverse
TDM 1.00
TDM 1.00
Reset Instantaneous
Reset Instantaneous
Direction Disabled Direction Disabled
Voltage Restraint Disabled Voltage Restraint Disabled
Volt Lower Limit 0.1 p.u. Relays Do Not Operate
Block Off PTOC 1
Relays Do Not Operate
Events Enabled
Targets Self-Reset
PTOC 1
Figure 67: Comparison of the setpoints for Regular and Simplified mode
r Simplified
..\Setpoints\Inputs ..\Setpoints\Inputs
Item Name Item Name
Contact Inputs Contact Inputs
Virtual Inputs Analog Inputs
Analog Inputs
Remote Inputs
Inputs MA In
Figure 68: Comparison of the Inputs screens for Regular and Simplified mode
142 1601-0320
Chapter 5 - Device Setpoints
CONFIG MODE
Path: Setpoints > Device > Config Mode
Range: Simplified, Regular
Default: Regular
This setting allows selection of the configuration mode while the device is accessed by the Administrator role. In
Regular configuration mode, all values in settings/functions can be edited. In Simplified configuration mode,
selected settings/functions are hidden or the values are read-only to enhance user experience with minimum
setpoint changes.
1601-0320 143
Chapter 5 - Device Setpoints
Time Sources
Time Source Priority
PTP (IEEE1588) 1*
IRIG-B 2*
SNTP 3
Internal Clock 4
* The priority of IRIG-B and PTP can be swapped.
Note:
Synchronization by IEC103, DNP, Modbus and IEC104 is not going to be issued if there is a sync source from IRIG-B, SNTP
or PTP.
144 1601-0320
Chapter 5 - Device Setpoints
network switching that dynamically changes the amount of uncompensated delay, there is no setting that always
completely corrects for uncompensated delay. A setting can be chosen that reduces worst-case error to half of
the range between minimum and maximum uncompensated delay if these values are known.
1601-0320 145
Chapter 5 - Device Setpoints
PTP VLAN ID
Range: 0 to 4095
Default: 0
The setting selects the value of the ID field in the 802.1Q VLAN tag in request messages issued by the relay’s
peer delay mechanism. It is provided in compliance with PP (Power Profile). As these messages have a
destination address that indicates they are not to be bridged, their VLAN ID serves no function, and so may be
left at its default value.
Depending on the characteristics of the device to which the relay is directly linked, VLAN ID may have no effect.
The setting applies to all of the relay’s PTP-capable ports.
PTP PRIORITY
Range: 1, 2
Default: 1
The setting sets the priority of PTP time for the relay. If set to 1 and IRIG-B is available, the relay syncs the
relay’s time reference to the PTP time. If set to 2 and IRIG-B is available, the relay syncs its reference to IRIG-B
time.
5.4.2 CLOCK
Path:Setpoints > Device > Real Time Clock > Clock
DATE
Format: Month/Day/Year
Range: Month: 1 to 12; Day: 1 to 31; Year: 2008 to 2094
Default: 01/01/2008
TIME
Range: 0 to 23: 0 to 59:0 to 59
Default: 00:00:00
IRIG-B
Range: Disabled, Enabled
146 1601-0320
Chapter 5 - Device Setpoints
Default: Disabled
Note:
IRIG-B is available in all relays. A failure on IRIG-B triggers an event and a target message.
IRIG-B is auto-detected. The signal type is detected in the hardware, so there are no configurable options.
1601-0320 147
Chapter 5 - Device Setpoints
Note:
8 Series relays only support SNTP unicast. It may take 2-3 minutes for the relay to synchronize with the SNTP server.
Path: Setpoints > Device > Real Time Clock > SNTP
SNTP FUNCTION
Range: Disabled, Enabled
Default: Disabled
Note:
The SNTP and PTP settings take effect after rebooting the relay.
148 1601-0320
Chapter 5 - Device Setpoints
5.5 SECURITY
OVERVIEW
The Multilin delivers full cyber security data classification with the use of security levels that help the user to comply
with security standards and guidelines. For Cyber Security, there is a choice of two order code options - Basic or
Advanced Security (CyberSentry):
● Basic Security – The basic security feature is the default offering of the product. It supports role based
access control (RBAC), encrypted communication between the IED and EnerVista configuration software,
with other functionalities such as security events storage on the IED, Inactivity Timeout and Lockout based on
authentication failure.
● CyberSentry – This feature refers to the advanced security options available as a software option. When this
option is purchased, it is automatically enabled and Basic Security is disabled. It supports the same
functionality as a Basic Security IED, but additionally it supports user management with non-shared accounts,
centralized authentication and logging of security events in syslog format to the configured syslog server. It
also supports the configuration of two US servers and two syslog servers to ensure redundancy and
availability.
PASSWORD COMPLEXITY
The password complexity is available on both Basic Security and Advanced Security.
If password complexity is enabled, a user account requires an alpha-numeric password that meets the following
requirements:
● Passwords cannot contain the user account name or parts of the user's full name that exceed two
consecutive characters
● Passwords must be 8 to 20 characters in length
● Passwords must contain characters from the following four categories: - English uppercase characters (A
through Z) - English lowercase characters (a through z) - Base 10 digits (0 through 9) - Non-alphanumeric
characters (e.g. ~, !, @, #, $,%,&)
1601-0320 149
Chapter 5 - Device Setpoints
Note:
Even a Viewer may execute this operation.
The current limitation for the maximum number of Viewer sessions from EnerVista is three when the
Communications card is present.
When the communications card is not present, a maximum of two Viewer sessions may be initiated through
EnerVista. If two Viewers are connected, a third connection is only allowed for an Administrator. No Operator has
access. However, if an Operator is connected, before any other user, only one Viewer is allowed so that an
Administrator can connect. This is because the maximum number of TCP connections from EnerVista, when the
Communications card is not present, is only three. (With a Communications card, the maximum number of TCP
connections is five.)
SECURE TUNNELING
The following items are supported in the feature:
● Under the CyberSentry option, the Multilin supports SSH secure tunneling of MODBUS communications
between itself and EnerVista setup software.
● SSH secure tunneling is supported on Ethernet only.
● If bypass security is set (through setpoint access), the communications over Ethernet is not encrypted.
150 1601-0320
Chapter 5 - Device Setpoints
FlexLogic RW RW R R
Factory Settings No No No No
Commands
Date/Time Change RW RW No No
BKR Related RW RW RW No
Clear Records RW No No No
Restore Defaults RW No No No
Reset W W W No
File Operations
Actual Values
Status R R R R
Metering R R R R
Reports
Events R R R R
Waveforms R R R R
Security Audit Log R R No No
1601-0320 151
Chapter 5 - Device Setpoints
Maintenance
Upload Firmware W No No No
Modbus Analyzer R R R R
Note:
Commands may be issued freely through protocols other than Modbus (e.g. DNP and IEC 61850) without user-authentication
or encryption of data taking place, even if the relay has the advanced security feature enabled.
LOGIN
The setting allows a user to login with a specific role.
1. Whenever a new role is logged in, the user is prompted to enter a password.
2. If the wrong password is entered, an Authentication Failed! message is displayed
3. If the maximum failed authentications occur an Account Blocked! message is displayed.
4. The Viewer is the default choice and it does not require a password.
LOGOUT
This setting logs out the current user and logs in as Viewer. If the user is already an Viewer, this setting does not
apply. When logging out, a switch to Viewer role is performed.
CHANGE PASSWORDS
1. The Change local passwords menu is shown on the front panel and EnerVista on a successful login of
Administrator role.
2. If password complexity is enabled, the rules as defined in Security must be obeyed. If password complexity is
disabled this setting accepts 1 to 20 alphanumeric characters. See Path: Setpoints > Device > Security >
Change Local Passwords.
3. The default password is 0, which is programmed from the factory.
4. The login setting in this menu is similar to that in the parent security settings.
5. The Viewer does not have password associated with it, so it is not shown in this setting.
ACCESS LOCKOUT
Access lockout is the number of failed authentications (the default is 3 and the maximum is 99) before the device
blocks subsequent authentication attempts for the lockout period. A value of 0 means Access Lockout is disabled.
152 1601-0320
Chapter 5 - Device Setpoints
ACCESS TIMEOUT
Access timeout is the time of idleness before a logged in user is automatically logged out. This timeout applies to all
users, independent of the communication channel (serial, Ethernet or direct access).
PASSWORD COMPLEXITY
This setting is available so that the option of selecting between simple passwords and complex ones is provided.
● The setting is only available to Administrator.
● By default Password Complexity is Disabled.
● When Password Complexity is Enabled, it follows the rules defined in Security.
BYPASS ACCESS
This feature allows security authentication to be bypassed. Once this setting is anything other than Disabled, the
user gets Administrator access rights on the configured interface for the period of time when the SETPOINT
ACCESS setting is On. For example, if user configures BYPASS ACCESS as Local, then no user authentication is
needed to access the device over USB or HMI when SETPOINT ACCESS is On. Another option is to configure
BYPASS ACCESS as HMI only - enabling the user to view and modify all settings, view actual values or execute
commands. The use of this feature should be restricted only in commissioning phase or when it is considered safe.
SETPOINT ACCESS
This setting is only available to Administrator. It is used for the purpose of bypassing security. It can be either
switched on or assigned to a digital input. If assigned to a digital input, the digital input needs to be activated
through a physical key.
Note:
If the maximum number of Viewer roles already logged in on the relay has been reached, you must log in on the Security
screen within one minute of making the connection otherwise your session is terminated.
1601-0320 153
Chapter 5 - Device Setpoints
5.5.2 CYBERSENTRY
The following features are supported in the CyberSentry feature:
● CyberSentry provides secure tunneling of MODBUS communications between itself and the EnerVista setup
software, using SSH.
● All the roles supported in the Basic Security are supported.
● Server authentication using RADIUS is added.
154 1601-0320
Chapter 5 - Device Setpoints
HB A ((B>
)*+,-. /012,2345+465
' '( 7+338650
'@ A ((B>
HB A ((B>
)*+,-. 9:.5+465
7+338650
'@ A ((B>
SECURITY SETTINGS
AUTHENTICATION METHOD
Range: Device, Server/Device, Device/Server
Default: Device/Server
The AUTHENTICATION METHOD setting allows user to configure the priority for authentication method for each
authentication attempt. If user selects Device Authentication, then only Local authentication will be utilized. The
relay will not communicate with RADIUS server for authentication. When user selects Server/Device
Authentication then the relay will first connect with remote RADIUS server for authentication but if that is not
reachable then it will authenticate user based on local database of credentials. If Device/Server
authentication is selected, then priority for authentication will be given to device credentials database driven. If
that fails, then the relay will try to connect to remote RADIUS server for authentication.
1601-0320 155
Chapter 5 - Device Setpoints
LOGIN
Range: Administrator, Engineer, Operator, Viewer
Default: Viewer
The setting allows a user to login with a specific role.
Whenever a new role is logged in, the user is prompted to enter a password. If the wrong password is entered,
an Authentication Failed! message is displayed. If the maximum failed authentications occur, the Account
Blocked! message is displayed. Viewer is the default and it does not require a password.
LOGOUT
Range: Yes, No
Default: No
This setting logs out the current user. When logging out from the panel, a switch to the Viewer role is performed.
DEVICE AUTHENTICATION
Range: Yes, No
Default: Yes
Device authentication setting offers the option to disable or enable this type of authentication. By default device
authentication is on, but the option to turn it off is provided and may be chosen when a RADIUS server is
accessible and will be used exclusively.
Only an Administrator role may change this setting. If an Administrator disables it, the role remains logged in, but
it is not allowed to write any other settings. In Enervista, a popup window warns that such changes are not going
to be saved.
If device authentication is disabled, Enervista still displays both radio buttons for choosing between device and
server authentication. See the EnerVista Setup section below. However the drop down menu, when local is
selected, has only the Administrator option. Once logged in, this role is only able to switch on device
authentication. After switching on the device authentication, the Administrator gains write access to all the other
settings without the need to logout and login again.
ACCESS LOCKOUT
Range: 0-99
Default: 3
This is the set number of failed authentications before the device blocks subsequent authentication attempts for
the lockout period. A value of 0 means that Access Lockout is disabled.
156 1601-0320
Chapter 5 - Device Setpoints
Default: 3 minutes
This is the set period of time in minutes of a lockout. A value of 0 means that there is no lockout period.
Note:
The lockout period is measured from the moment the maximum number of failed authentications has been reached.
Additional attempts to login during the lockout period do not extend this time.
ACCESS TIMEOUT
Range: 2-999 minutes
Default: 5 minutes
This is the time of idleness before a logged in user is automatically logged out. The Access Timeout setting
applies to all users, independent of the communication channel (serial, Ethernet or direct access).
SETPOINT ACCESS
Range: Off, On, Digital Input
Default: Off
This setting is only available to the Administrator role. Setpoint Access may be assigned to a digital input.
When the digital input is activated, the user has Administrator access to the front panel.
1601-0320 157
Chapter 5 - Device Setpoints
Note:
The factory role password cannot be altered.
ENERVISTA SETUP
For the software setup the following applies:
● Some security settings (such as Radius configuration) are only accessible and configurable through the
Enervista program.
● The Enervista software only allows for changes that are permitted by the user’s logged in role. For example,
the Observer role cannot write to any settings, but can only view.
158 1601-0320
Chapter 5 - Device Setpoints
● If the settings file is modified off line, the relay checks for the role of the user and allows the download only if
the role is Administrator (see table below). If the role is different, Enervista notifies the user via a pop-up
window that this operation is allowed only for Administrators.
● The Enervista Login Screen has two radio buttons to choose between device and server authentication.
○ If server authentication is chosen, the screen provides User Name: and Password: fields
○ If device authentication is chosen the User Name: field changes to a drop down menu. If device
authentication is enabled internally, the drop down menu contains all predefined roles. If device
authentication is disabled, the drop down menu has only the Administrator option. This is to allow for
switching on the device authentication. Once logged in, the Administrator is only able to turn on the
device authentication, but once the device authentication is enabled, access to all the other settings is
granted.
● A file download may be performed only from the relay.
Role
File Access Administrator Engineer Operator Viewer
Read (Download from 8 Series All files Yes Yes Yes Yes
889)
Write (Upload to 8 Series 889) Settings file Yes No No No
Firmware Yes No No No
Note:
In special cases security settings, such as RADIUS IP address and port, if modified offline, can result in interruption of service
when applied online, if the user is not aware of the change having been made. For this reason, if these settings have been
modified, offline, they will not be written during the file write operation.
RADIUS SETTINGS
The following are settings that need to be configured through Enervista in order to set up communication with two
RADIUS servers. For configuring the RADIUS server itself, consult the RADIUS documentation. An example is
provided, see Communications Guide.
Setting Name Description Range Default Units Minimum
Permissions
Primary Radius IP IP address of primary Radius 0.0.0.0 to 0.0.0.0 - Administrator
Address server. Default value indicates no 223.255.255.254
Primary Radius server is
configured, and so Radius is
disabled.
Secondary Radius IP address of primary Radius 0.0.0.0 to 0.0.0.0 - Administrator
IP Address server. Default value indicates no 223.255.255.254
Secondary Radius server is
configured, and so Radius is
disabled.
Primary Radius authentication port 1 to 65535 1812 - Administrator
Authentication Port
Vendor ID An identifier that specifies Radius 1 to 65535 Value that - Administrator
vendor specific attributes used represents General
with the protocol. Electric (2910)
1601-0320 159
Chapter 5 - Device Setpoints
SECURITY EVENTS
The event recorder records the events described in the following table.
Event Record Level Description
FAILED_AUTH, ORIGIN, TIMESTAMP Warning (4) A failed authentication with time stamp in UTC time
when it occurred.
USER_LOCKOUT, ORIGIN, TIMESTAMP: Error (3) The user lockout has occurred because of too many
failed authentication attempts.
SETTING_CHG, ORIGIN, TIMESTAMP: Notice (5) An event to indicate setting change(s).
LOGIN, ORIGIN, TIMESTAMP: Warning (4) An event to indicate when a certain role logged in.
MANUAL_LOGOUT, ORIGIN, TIMESTAMP: Warning (4) An event to indicate when a certain role logged out or
timed out. Origin: Username and IP:MAC
TIMED_LOGOUT, ORIGIN, TIMESTAMP: Warning (4) An event to indicate when a certain role logged out or
timed out. Origin: Username and IP:MAC
PRIM_RADIUS_UNREACH, ORIGIN, TIMESTAMP: Critical (2) RADIUS server is unreachable. Origin: RADIUS server
IP address and port number.
SEC_RADIUS_UNREACH, ORIGIN, TIMESTAMP: Critical (2) RADIUS server is unreachable. Origin: RADIUS server
IP address and port number.
CLEAR_EVENT_RECORDS, ORIGIN, TIMESTAMP: Warning (4) Clear event records command was issued.
CLEAR_TRANSIENT_RECORDS, ORIGIN, Notice (5) Clear transient records command was issued.
TIMESTAMP:
BYPASS ACCESS ACTIVATED Critical (1) Bypass access has been activated.
BYPASS ACCESS DEACTIVATED Critical (1) Bypass access has been deactivated.
PRIM_SYSLOG_UNREACHABLE Critical (2) SYSLOG server is unreachable. Origin: SYSLOG
server IP address and port number
SEC_SYSLOG_UNREACHABLE Critical (2) SYSLOG server is unreachable. Origin: SYSLOG
server IP address and port number
MODBUS TCP Enabled Warning (4) Port 502 has been opened for Read/Write
MODBUS TCP Disabled Warning (4) Port 502 Closed
MODBUS TCP ReadOnly Warning (4) Port 502 has been opened for Read Only operations.
160 1601-0320
Chapter 5 - Device Setpoints
Firmware Upload Successful Notice (5) [IEEE 1686] requires audit logging for firmware related
aspects. A software is generic that includes also
firmware.
FLEXLOGIC OPERANDS
The following operands are added for CyberSentry.
CyberSentry FlexLogic Operand Description
AUTHENTICATION FAIL Operand set for Failed Authentication self test and alarm
UNAUTH SETTING CHANGE ATTEMPT Operand set for unauthorized setting change action
RADIUS SRV UNAVAILABLE Operand set for RADIUS servers unavailable self test
1601-0320 161
Chapter 5 - Device Setpoints
5.6 COMMUNICATIONS
8-series relays relays have a two-stage communications capability. The base CPU supports the Modbus protocol
through the Ethernet, USB and serial ports. In addition, the base CPU also supports the IEC 103, DNP serial, DNP
TCP/IP, Ethernet and TFTP protocol. Once the communications module option is added to the base, the
communications module supports IEC 61850 Ed.2. The communications CPU also supports Modbus TCP, DNP
TCP, TFTP, SFTP, and SNTP protocol.
Note:
The below settings are applied only to devices with IEC 61850 order codes.
MULTI-LEVEL CONTROL
Range: Disabled, Enabled
Default: Disabled
When set to Enabled, control authority from multiple levels (Bay, Station and Remote) are allowed
simultaneously, based on Local/Remote status and status authority status. Otherwise only one level has the
authority to control, based on Local/Remote status and status authority status.
162 1601-0320
Chapter 5 - Device Setpoints
COMPATIBILITY
Range: Disabled, SR489, FlexMap
Default: Disabled
Compatibility mode changes the Modbus actual value registers to emulate an SR489 relay. The emulation
supports typical actual value data for common data items.
Starting in version 2.90, choose FlexMap for SR489 support to include support for additional SR489 registers
See the 8 Series Protective Relay Communications guide for the list.
1601-0320 163
Chapter 5 - Device Setpoints
Note:
When in compatibility mode the rear RS485 port and the rear Ethernet ports are not accessible via EnerVista D&I Setup
software so it is not possible to change any settings, view actual values or retrieve records. When in compatibility mode the
actual values supported can be read via the rear RS485 or rear Ethernet Ports using Modbus Master e.g. PLC or DCS. The
front USB port should be used for connection and EnerVista D&I Setup software activities.
FLEXMAP FILE
Range: Up to 13 alphanumeric characters
Default: SR489XAFlexMap.000
The Flexmap File describes the translation from the Modbus memory map to the target Modbus memory map.
Note:
This setting applies only to the RS485 connection.
When this setting is changed to Function Code 03h, retrieving configuration settings through the RS485 port is not possible.
5.6.4 RS485
On the rear, the relay is equipped with two RS485 serial communication ports. The RS485 port has settings for
baud rate and parity. It is important that these parameters agree with the settings used on the computer or other
164 1601-0320
Chapter 5 - Device Setpoints
equipment connected to this port. A maximum of 32 relays can be daisy-chained and connected to a DCS, PLC or a
PC using the RS485 port.
Path: Setpoints > Device > Communications > RS485
BAUD RATE
Range: 2400, 4800, 9600, 1200, 19200, 38400, 57600, 115200
Default: 115200
PARITY
Range: None, Odd, Even
Default: None
PORT PROTOCOL
Range: Modbus, DNP 3.0, IEC 60870-5-103
Default: Modbus
5.6.5 USB
The USB parameters are as follows:
IP Address: 172.16.0.2
IP Subnet Mask: 255.255.255.0
IP GWY IP Address: 172.16.0.1
Note:
Whenever the device is rebooted, the USB cable needs to be unplugged and plugged in again for proper communication to be
established over USB.
Connecting multiple relays over USB to a single PC is not possible because in the case of USB, the IP address of
the device 172.16.0.2 is constant.
Base Offering
● 2x Copper (RJ45) Ports
● Modes: 10/100 Mbps
● Protocols: Modbus TCP, DNP 3.0, IEC 61850 GOOSE, SNTP, IEC 62439-3 clause 4 (PRP)
Advanced Offering
● 4x Copper (RJ45) Ports or 2x Fiber
● Modes: 10/100 Mbps (copper)
● 100Mbps (Fiber)
● Protocols: Modbus TCP, DNP 3.0, IEC 61850 GOOSE, SNTP, IEC 62439-3 clause 4 (PRP)
1601-0320 165
Chapter 5 - Device Setpoints
Note:
Use the softkeys and Down/Up key to enter an IP address. When entering an IP address you must press the BACK key first
to switch between softkey mode and the Down/Up key mode.
NETWORK 1, 2, 4, 5
Range: Standard IPV4 Address format
Default: 192.168.11.11 (Port 1)
Default: 192.168.11.12 (Port 2)
Default: 192.168.11.13 (Port 4)
Default: 192.168.11.14 (Port 5)
The setting sets the port’s IPV4 address in standard IPV4 format.
Note:
The setting is valid on Port 2(5) if Prt1(4) is set to Independent
Note:
The setting is valid on Port 2 if Prt1 Operation is set to Independent.
Note:
172.17.X.X/16 and 172.18.X.X/16 are reserved IPs.
PRT1 OPERATION
Range: Independent, LLA, PRP
Default: Independent
This setting determines the mode of operation for ports 1 and 2: Independent, LLA or PRP.
Independent operation: Ports 1, 2, 4 and 5 operate independently with their own MAC and IP address.
166 1601-0320
Chapter 5 - Device Setpoints
LLA operation: Ports 1, 2, 4 and 5 use port 1’s MAC and IP address settings while port 2 is in standby mode in
that it does not actively communicate on the Ethernet network but monitors its link. If port 1 is active and the link
loss problem is detected, communications is switched to port 2 immediately. Port 2 is, in effect, acting as a
redundant or backup link to the network for port 1.
LLA (Link Loss Alert): is a proprietary feature supported by the fiber optic ports. When enabled, this feature is
able to detect a failure of the fiber link. If Prt1 Operation is set to LLA, the detection of a link failure by this
feature triggers the transfer of communications. If LLA is enabled on a port with a non-fiber SFP, the target
message LLA not supported by Prt (1 or 2) is displayed on the keypad and an event is logged.
Note:
LLA is not available on port 4,5 copper (RJ45). When the port operation is selected, the relay requires a reboot for the setting
to be applied.
Parallel Redundancy Protocol (PRP) operation: Ports 1 and 2 use the same MAC address and combine
information at the link layer. It is intended to only be used if the two ports are connected to separate parallel
LAN’s. In this mode of operation, both ports cannot be connected to the same LAN. The receiving devices (8
Series 889) process the first frame received and discard the duplicate through a link redundancy entity (LRE) or
similar service that operates below layer 2. Aside from LRE, PRP uses conventional Ethernet hardware but both
ports must know they are in PRP. Ports of PRP devices operating with the same Internet Protocol (IP) addresses
for traffic that uses IP Management protocols such as Address Resolution Protocol (ARP) must operate
correctly.
Duplicate Discard mode: This is the normal setting for PRP operation and once set it allows the sender LRE to
append a six-octet field that contains a sequence number, the Redundancy Control Trailer (RCT) to both frames
it sends. The receiver LRE uses the sequence number of the RCT and the source MAC address to detect
duplicates. It forwards only the first frame of a pair to its upper layers.
Note:
NOTE: redundancy operations work in pairs Port1/2 and Port4/5 only. It is not interchangeable between all ports.
5.6.7 ROUTING
When the configuration card is present, a default route and a maximum number of 6 static routes can be configured.
The default route is used as the last choice, if no other route towards a given destination is found.
Path: Setpoints > Device > Communications > Routing > Default Route
GATEWAY ADDRESS
Range: Standard IPV4 unicast address format (0.0.0.1 to 223.255.255.254)
Default: 127.0.0.1
This setting sets the gateway of the default route to be used by IP traffic sent from the relay, if no other route
towards a given IP destination is found.
This setting is available only if the communications card is present.
Path: Setpoints > Device > Communications > Routing > Static RT1 (2 to 6)
1601-0320 167
Chapter 5 - Device Setpoints
Default: 127.0.0.1
This setting sets the destination IPv4 route. This setting is available only if the communications card is present.
Note:
Host routes are not supported at present.
The route mask has IPv4 mask format. In binary this is a set of contiguous bits of 1 from left to right, followed by one or more
contiguous bits of 0.
The route destination and mask must match. This can be verified by checking that RtDestination & RtMask == RtDestination
This is an example of a good configuration: RtDestination= 10.1.1.0; Rt Mask= 255.255.255.0
This is an example of a bad configuration: RtDestination = 10.1.1.1; Rt Mask= 255.255.255.0
The route destination must not be a connected network.
The route gateway must be on a connected network. This rule applies to the gateway address of the default route as well.
This can be verified by checking that: RtGwy & Prt4Mask) == (Prt4IP & Prt4Mask) || (RtGwy & Prt5Mask) == (Prt5IP &
Prt5Mask)
TARGETS
Wrong Route Config
Description: A route with mismatched destination and mask has been configured.
Message: Wrong route configuration.
168 1601-0320
Chapter 5 - Device Setpoints
TOPOLOGY
In the topology example above, the Multilin device is connected through the two Ethernet ports available on the
communications card.
Port1 (IP address 10.1.1.2) connects to LAN 10.1.1.0/24 and to the Internet through Router1. Router 1 has an
interface on 10.1.1.0/24 and the IP address of this interface is 10.1.1.1.
Port2 (IP address 10.1.2.2) connects to LAN 10.1.2.0/24 and to EnerVista D&I Setup software through Router 2.
Router 2 has an interface on 10.1.2.0/24 and the IP address of this interface is 10.1.2.1.
Configuration
Network addresses:
PRT21IP ADDRESS = 10.1.1.2PRT1 SUBNET IP MASK = 255.255.255.0PRT2 IP ADDRESS = 10.1.2.2PRT2
SUBNET IP MASK = 255.255.255.0
Routing Settings:
IPV4 DEFAULT ROUTE: GATEWAY ADDRESS = 10.1.1.1
STATIC NETWORK ROUTE 1: RT1 DESTINATION = 10.1.3.0/24RT1 NET MASK = 255.255.255.0RT1
GATEWAY = 10.1.2.1
Behavior:
One static network route was added to the destination 10.1.3.0/24, where a laptop running Enervista is located.
This static route uses a different gateway (10.1.2.1) than the default route. This gateway is the address of Router
2, which is aware of destination 10.1.3.0 and is able to route packets coming from the device and destined to
Enervista.
1601-0320 169
Chapter 5 - Device Setpoints
DNP Address
Range: 0 to 65519 in steps of 1
Default: 65519
The DNP address sets the DNP slave address. This number identifies the device on a DNP communications
link. Each DNP slave must be assigned a unique address.
Note:
DNP Channel 1 Port will take the DNP TCP/UDP Port 1 and DNP Client Address 1 to allow/reject connections. The same
relation is used by channel 2.
170 1601-0320
Chapter 5 - Device Setpoints
Sets the number of times the device retransmits an unsolicited response without receiving confirmation from the
master; a value of 255 allows infinite re-tries.
Note:
If the requirement for synchronization is more than a couple of seconds, consider synchronization via other means such as
IRIG-B or 1588. Given network asymmetry, the consistency of the network latency, clock drift, and additional delays due to
routers located between the client and the device all contribute error.
1601-0320 171
Chapter 5 - Device Setpoints
This setting specifies a time delay for the detection of dead network TCP connections. If there is no data traffic
on a DNP TCP connection for greater than the time specified by this setting, the connection will be aborted.. This
frees up the connection to be re-used by a client.
The menu path for the DNP/IEC104 point lists is shown below.
Path: Setpoints > Device > Communications > DNP/IEC104 Point Lists
Binary Input/MSP Points
Analog Input/MME Points
Binary Outp/CSC/CDC Pnts
Note:
A scale factor of / 0.1 is equivalent to a multiplier of 10.
172 1601-0320
Chapter 5 - Device Setpoints
Default: 30000
The setting is the threshold value to define the condition to trigger unsolicited responses containing analog input
data. Each setting represents the default deadband value for the associated analog input. For example, to
trigger unsolicited responses from the relay when phase A current changes by 15 A, the DNP Current Deadband
for Phase A current should be set to 15. Note that these settings are the deadband default values. DNP object
34 points can be used to change deadband values from the default for each individual DNP analog input point.
Whenever power is removed and re-applied, the new deadbands are in effect.
Note:
The DNP/IEC 60870-5-104 point lists always begin with point 0 and end at the first Off value. Since DNP / IEC 60870-5-104
point lists must be in one continuous block, any points assigned after the first Off point are ignored.
1601-0320 173
Chapter 5 - Device Setpoints
BINARY COUNTERS
● Static (Steady-State) Object Number: 20
● Change Event Object Number: 22
● Request Function Codes supported: 1 (read), 7 (freeze), 8 (freeze noack), 9 (freeze and clear), 10 (freeze
and clear, noack), 22 (assign class)
● Static Variation reported when variation 0 requested: 1 (32-Bit Binary Counter with Flag)
● Change Event Variation reported when variation 0 requested: 1 (32-Bit Counter Change Event without
time)
● Change Event Buffer Size: 10
● Default Class for all points: 3
FROZEN COUNTERS
● Static (Steady-State) Object Number: 21
● Change Event Object Number: 23
● Request Function Codes supported: 1 (read)
● Static Variation reported when variation 0 requested: 1 (32-Bit Frozen Counter with Flag)
● Change Event Variation reported when variation 0 requested: 1 (32-Bit Counter Change Event without
time)
● Change Event Buffer Size: 10
● Default Class for all points: 3
ANALOG INPUTS
It is important to note that 16-bit and 32-bit variations of analog inputs are transmitted through DNP as signed
numbers. Even for analog input points that are not valid as negative values, the maximum positive representation is
32767 for 16-bit values and 2147483647 for 32-bit values. This is a DNP requirement. The deadbands for all Analog
174 1601-0320
Chapter 5 - Device Setpoints
Input points are in the same units as the Analog Input quantity. For example, an Analog Input quantity measured in
volts has a corresponding deadband in units of volts. Relay settings are available to set default deadband values
according to data type. Deadbands for individual Analog Input Points can be set using DNP Object 34.
1. A default variation refers to the variation response when variation 0 is requested and/or in class 0, 1, 2, or 3
scans. The default variations for object types 1, 2, 20, 21, 22, 23, 30, and 32 are selected via relay settings.
This optimizes the class 0 poll data size.
2. For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with
qualifiers 17 or 28, respectively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08,
are responded with qualifiers 00 or 01. For change event objects, qualifiers 17 or 28 are always responded.
Cold restarts are implemented the same as warm restarts – the relay is not restarted, but the DNP process is
restarted.
5.6.9 IEC60870-5-104
The IEC 60870-5-104 communications protocol is supported on Ethernet ports 4 and 5 only. Setting changes
become active after rebooting.
Note:
Both DNP and IEC104 protocol can work at the same time, but consider that there is only one point map. So, the two
protocols use the same data mapping, i.e., same point index and same point source.
The relay supports up to two IEC104 client connections simultaneously.
1601-0320 175
Chapter 5 - Device Setpoints
Note:
IEC104 CHANNEL 1 PORT takes the Port Number 1 and Client Address 1 to allow or reject connections. The same
method is used by channel 2.
GROUPS OF DATA
The data is organized into groups in order to provide values when the controlling station requests them by a general
or group interrogation.
Group 1 is set by the 96 Single Points (M_SP).
Group 2 is set by the 32 Measured values (M_ME).
Group 3 is set by the 32 Measured thresholds (P_ME).
These 96 Single Points and 32 Measured Values are also sent as a response to a General Interrogation.
The Integrated Totals (M_IT) has its own Counter Group 1, and it is sent as a response to a General Request
Counter.
5.6.10 IEC60870-5-103
The point map for the 103 is different from the one shared by the IEC104 and DNP protocols. IEC 60870-5-103
serial communications protocol is supported on the rear RS485 port only.
The DNP, IEC 103 and Modbus cannot be enabled simultaneously. Only one instance of DNP 3.0, IEC 103 or
Modbus can run on the RS485 serial port.
Path: SETPOINTS > DEVICE > COMMUNICATIONS > IEC 60870-5-103 PROTOCOL
176 1601-0320
Chapter 5 - Device Setpoints
Note:
Pay attention when configuring the function type and information number of the different points, because they must be unique.
There is no mechanism in the EnerVista D&I Setup software or the front panel HMI to detect duplication of the information
index.
The IEC 60870-5-103 point lists always begin with point 0 and end at the first Off value. Since IEC 60870-5-103 point lists
must be in one continuous block, any points assigned after the first Off point are ignored.
1601-0320 177
Chapter 5 - Device Setpoints
○ Launch the online IEC 61850 configurator screen, by double-clicking on IEC61850 Configurator.
○ Select the required settings from the different tab displays (in the configurator screen) to complete the
IEC 61850 configuration.
2. Online right-click option
○ Select any online relay and right click on the selected item. More options become available for
selection, as described below.
ADDITIONAL OPTIONS
Generate ICD file: The menu option generates a default ICD file with the respective order code option and saves
the file to the path selected previously.
Read Device Settings: The menu option reads all the settings from the relay by TFTP and creates a file with
extension *.CID. The created *.CID file consists of two sections. A private section where all non IEC 61850 settings
are available, and a public section in which IEC 61850 related settings are implemented.
178 1601-0320
Chapter 5 - Device Setpoints
When creating a CID file using a 3rd party ICT/SCL tool, ensure the following:
● The order code in the CID file must match the device order code if writing the CID file directly into the relay.
The Desc value in communication settings of the CID file must match the relay’s order code.
● The maximum allowed services must be equal or below the specified limits as in ICD/CID.
● Configure Datasets only in LLN0 logical node.
● Creating new LD, LN, and communication-AP settings is not recommended.
Note:
When the IEC 61850 configuration is saved while online, the DEVICE IN SERVICE state (Setpoints > Device > Installation)
switches to Not Ready for the duration of the upload. This ensures that all new settings are applied before the device is
operational.
1601-0320 179
Chapter 5 - Device Setpoints
● Reports
● GOOSE Reception
● GOOSE Transmission
180 1601-0320
Chapter 5 - Device Setpoints
NUMBER OF RECORDS
Range: 1 to 16 in steps of 1
Default: 5
The selection from the range defines the desired number of records.
TRIGGER MODE
Range: Overwrite, Protected
Default: Overwrite
When Overwrite setting is selected, the new records overwrite the old ones, meaning the relay will always
keep the newest records as per the selected number of records. In Protected mode, the relay will keep the
number of records corresponding to the selected number of records, without saving further records that are
beyond the selected number of records.
TRIGGER POSITION
Range: 0 to 100% in steps of 1%
Default: 20%
This setting indicates the location of the trigger with respect to the selected length of record. For example at 20%
selected trigger position, the length of each record will be split on 20% pre-trigger data, and 80% post-trigger
data.
TRIGGER SOURCE:
Range: Off, Any FlexLogic operand
Default: Off
The trigger source can be any digital input: an operand from the list of FlexLogic operands, a contact input, a
contact output, a virtual input or output, or a remote input or output.
1601-0320 181
Chapter 5 - Device Setpoints
TRIGGER ON TRIP
Range: On, Off
Default: Off
Selecting the On setting enables triggering of the recorder when any of the protection elements configured as a
Trip function operates, or the state of the operand assigned to operate the #1 Trip output relay changes to
High.
TRIGGER ON ALARM
Range: On, Off
Default: Off
Selecting On setting enables triggering of the recorder when any of the protection elements configured as
Alarm, or Latched Alarm function operates, or the state of the operand assigned to trigger the Alarm LED
changes to High.
DIGITAL INPUT 1 to 64
Range: Off, Any FlexLogic operand
Default: Off
ANALOG INPUT 1 to 16
Range: Off, Any FlexLogic analog parameter
Default: Off
Note:
A consecutive transient record cannot be triggered until the first record has been completed.
182 1601-0320
Chapter 5 - Device Setpoints
Note:
If data is not available for the entire duration of pre-trigger, the trigger position will be based on available pre-trigger.
FUNCTION
Range: Disabled, Continuous, Triggered
Default: Continuous
This setting configures the mode in which the data logger operates. When set to Continuous, the data logger
actively records any configured channels at the rate defined in the Data Logger Rate setting. The data logger is
idle in this mode if no channels are configured. When set to Triggered, the data logger begins to record any
configured channels at the instance of the rising edge of the trigger (FlexLogic operand). The data logger
ignores all subsequent triggers and continues to record data until the active record is full. Once the data logger is
full, capturing of data stops until it is cleared.
Clear Data Logger
Once the data logger is full, a Clear Data Logger command is required to clear the data logger record, before a
new record can be started. Performing the Clear Data Logger command also stops the current record and resets
the data logger to be ready for the next trigger. The Clear Data Logger command is located at Setpoints >
Records > Clear Records. The Data Logger Storage Capacity table below shows an example of the
dependency of the data logger storage capacity with respect to the selected number of channels, and the
selected rate (time interval) at which the logged values are taken. The Data Logger buffer space can be
monitored to produce an alarm when the logged data occupies 80% of the data logger storage space. Target
message, and operand Data Logger ALRM is generated at this time.
TRIGGER
Range: Off, Any FlexLogic operand
Default: Off
This setting selects the signal used to trigger the start of a new data logger record. Any FlexLogic operand can
be used as a trigger source. The Triggered setting only applies when the Data Logger Function is set to
“Triggered”.
1601-0320 183
Chapter 5 - Device Setpoints
TRIGGER POSITION
Range: 0 to 50% steps of 1%
Default: 20%
This setpoint defines the percentage of buffer space that is used for recording pre-trigger samples.
RATE
Range: 1 cycle, 1 second, 30 seconds, 1 minute, 15 minutes, 30 minutes, 1 hour, 6 hours, 8 hours, 12 hours, 24
hours
Default: 1 minute
This setting selects the time interval at which the actual value is recorded.
184 1601-0320
Chapter 5 - Device Setpoints
1601-0320 185
Chapter 5 - Device Setpoints
FUNCTION
Range: Disabled, Enabled
Default: Disabled
186 1601-0320
Chapter 5 - Device Setpoints
PRE-FAULT TRIGGER
Range: Off, Any FlexLogic operand
Default: Off
This setpoint specifies the FlexLogic operand to capture the pre-fault data. The rising edge of this operand
stores one cycle-old data for subsequent reporting. The element waits for the fault trigger to actually create a
record as long as the operand selected as Pre-Fault Trigger is On. If the operand remains Off for 1 second, the
element resets and no record is created.
FAULT TRIGGER
Range: Off, Any FlexLogic operand
Default: Off
This setpoint specifies the FlexLogic operand to capture the fault data. The rising edge of this operand stores the
data as fault data and results in a new report. The trigger (not the pre-fault trigger) controls the date and time of
the report. The distance to fault calculations are initiated by this signal.
ANALOG CHANNELS 1 to 32
These settings specify an actual value such as voltage or current magnitude, true RMS, phase angle, frequency,
temperature, etc., to be stored should the report be created. Up to 32 analog channels can be configured.
1601-0320 187
Chapter 5 - Device Setpoints
PARAMETER 1 to 64
Range: Off, any FlexAnalog Parameter
Default: Off
188 1601-0320
Chapter 5 - Device Setpoints
1601-0320 189
Chapter 5 - Device Setpoints
Note:
The USB port on the Front Panel is intended for connection to a portable PC.
LED “TRIP”
Range: Off, Any FlexLogic operand
Default: Any Trip
The setpoint requires a FlexLogic operand to be assigned in order to turn on the TRIP LED, when triggered. This
indicator always latches, and a reset command must be initiated to allow the latch to be reset.
The LED can be also triggered by the operation of a protection, control, or monitoring element with its function
selected as Trip.
LED “ALARM”
Range: Off, Any FlexLogic operand
Default: Any Alarm
The setpoint requires a FlexLogic operand to be assigned in order to turn on the ALARM LED, when triggered.
The indicator is a self-reset indicator, unless it is initiated from a protection, control, or monitoring element whose
function is selected as Latched Alarm. Resetting the Latched Alarm LED is performed by initiating a Reset
command.
LED “PICKUP”
Range: Off, Any FlexLogic operand
Default: Any Pickup
190 1601-0320
Chapter 5 - Device Setpoints
The setpoint requires a FlexLogic operand to be assigned in order to turn on the PICKUP LED , when triggered.
The indicator is a self-rest indicator and will turn off if the condition evolves into a fault or the measured
parameter drops below the pickup level.
LED x NAME
Range: Up to 13 alphanumeric characters
Default: LED 5
The setpoint is used to select the LED name by choosing up to 13 alphanumeric characters.
LED x COLOR
Range: Off, Red, Green, Orange
Default: Orange
The setpoint selects the color of the LED. Three colors are available for selection: Red, Green, and Orange.
Note:
This setting is not available for LEDs 18 to 24.
LED x TRIGGER
Range: Off, Any FlexLogic operands
Default: Testing On
This setpoint requires the assigning of a FlexLogic operand to trigger the selected LED upon operation.
LED x TYPE
Range: Self-reset, Latched
Default: Testing On
The setpoint defines the type of LED indication as either Self-Reset (the LED resets after the FlexLogic
operand drops out), or Latched (the LED stays latched upon dropping out of the FlexLogic operand).
1601-0320 191
Chapter 5 - Device Setpoints
192 1601-0320
Chapter 5 - Device Setpoints
Note:
The 10 pushbutton panel is available only for the 850 for hardware versions A and B, and for all models from hardware
version C.
The user-programmable pushbuttons provide an easy and error-free method of entering digital state (on, off)
information. Depending on the faceplate three to ten pushbuttons are available for programming.
The digital state of the pushbuttons can be entered only locally (by directly pressing the front panel pushbutton).
Typical applications include breaker control, autorecloser blocking and settings groups changes. The user-
programmable pushbuttons are under the control level of password protection.
1601-0320 193
Chapter 5 - Device Setpoints
Each pushbutton asserts its own on and off FlexLogic operands (for example, PUSHBUTTON 1 ON and
PUSHBUTTON 1 OFF). These operands are available for each pushbutton and are used to program specific
actions. Each pushbutton has an associated LED indicator. By default, this indicator displays the present status of
the corresponding pushbutton; ON or OFF. This can be changed by programming the LED Trigger setting in the
Programmable LED settings menu.
The activation and deactivation of user-programmable pushbuttons is dependent on whether latched or self-reset
mode is programmed.
LATCHED MODE
In Latched Mode, a pushbutton can be set (activated) by directly pressing the associated front panel pushbutton.
The pushbutton maintains the set state until deactivated by a Reset command or after a user-specified time delay.
The state of each pushbutton is stored in non-volatile memory and maintained through loss of control power.
194 1601-0320
Chapter 5 - Device Setpoints
The pushbutton is Reset (deactivated) in Latched Mode by directly pressing the associated active front panel
pushbutton. It can also be programmed to Reset automatically through the PB 1 AUTORESET and PB 1
AUTORESET DELAY settings. These settings enable the auto-reset timer and specify the associated time delay.
The auto-reset timer can be used in select-before-operate (SBO) switching device control applications, where the
command type (CLOSE/OPEN) must be selected prior to command execution. The selection must Reset
automatically if control is not executed within a specified time period.
SELF-RESET MODE
In Self-reset mode, a pushbutton remains active for the time it is pressed (the pulse duration) plus the Dropout time
specified in the PUSHBTN 1 DROPOUT TIME setting. The pushbutton is Reset (deactivated) in Self-reset mode
when the dropout delay specified in the PUSHBTN 1 DROPOUT TIME setting expires.The pulse duration of the
pushbutton must be at least 50 ms to operate the pushbutton. This allows the user-programmable pushbuttons to
properly operate during power cycling events and various system disturbances that may cause transient assertion
of the operating signals.
The operation of each user-programmable pushbutton can be inhibited through the PUSHBTN 1 LOCK setting. If
locking is applied, the pushbutton ignores the commands executed through the front panel pushbuttons. The locking
functions are not applied to the auto-reset feature. In this case, the inhibit function can be used in SBO control
operations to prevent the pushbutton function from being activated and ensuring “one-at-a-time” select operation.
The locking functions can also be used to prevent accidental pressing of the front panel pushbuttons.
Pushbutton states can be logged by the Event Recorder and displayed as Target Messages. In latched mode, user-
defined messages can also be associated with each pushbutton and displayed when the pushbutton is ON or
changing to OFF.
Path:Setpoints > Device > Programmable PBs > Pushbutton 1(X)
FUNCTION
Range: Self-reset, Latched, Disabled
Default: Self-reset
This setting selects the characteristic of the pushbutton. If set to Disabled the pushbutton is not active and the
corresponding FlexLogic operands (both ON and OFF) are de-asserted. If set to Self-reset the control logic is
activated by the pulse (longer than 100 ms) issued when the pushbutton is being physically pressed.
When in Self-reset mode and activated locally, the pushbutton control logic asserts the ON corresponding
FlexLogic operand as long as the pushbutton is being physically pressed, and after being released the
deactivation of the operand is delayed by the PUSHBTN 1 DROPOUT TIME setting. The OFF operand is
asserted when the pushbutton element is deactivated.
If set to Latched, the control logic alternates the state of the corresponding FlexLogic operand between ON and
OFF on each button press or by virtually activating the pushbutton (assigning Set and Reset operands). When in
Latched mode, the states of the FlexLogic operands are stored in a non-volatile memory. Should the power
supply be lost, the correct state of the pushbutton is retained upon subsequent power-up of the relay.
ID TEXT
Range: Up to 13 alphanumeric characters
Default: Open (PB1), Close (PB2), F1 (PB3), Gnd Trip Enabled (PB4), SCADA Enabled (PB5), Hot Line Tag
(PB6), Demand Reset (PB7), Alt Settings (PB8), Target Reset (PB9), PB Block (PB10)
Default: Start (PB1), Stop (PB2), F1 (PB3), Gnd Trip Enabled (PB4), SCADA Enabled (PB5), Hot Line Tag
(PB6), Demand Reset (PB7), Alt Settings (PB8), Target Reset (PB9), PB Block (PB10)
1601-0320 195
Chapter 5 - Device Setpoints
This setting specifies the 13-character line of the user-programmable message and is intended to provide the ID
information of the pushbutton.
ON TEXT
Range: Up to 13 alphanumeric characters
Default: PB1 On (or PB[X] On)
This setting specifies the 13-character line of the user-programmable message and is displayed when the
pushbutton is in the ON position.
OFF TEXT
Range: Up to 13 alphanumeric characters
Default: PB1 Off (or PB[X] On)
This setting specifies the 13-character line of the user-programmable message and is displayed when the
pushbutton is activated from the ON to the OFF position and the PUSHBUTTON 1 FUNCTION is Latched. This
message is not displayed when the PUSHBUTTON 1 FUNCTION is Self-reset as the pushbutton operand
status is implied to be “OFF” upon its release. The length of the “OFF” message is configured with the
PRODUCT SETUP/DISPLAY PROPERTIES/FLASH MESSAGE TIME setting.
The message programmed in the PUSHBTN 1 ID and PUSHBTN 1 ON TEXT settings will be displayed as long
as Pushbutton 1 On operand is asserted, but not longer than the time period specified by the FLASH MESSAGE
TIME setting. After the flash time has expired, the default message or other active target message is displayed.
The instantaneous Reset of the flash message will be executed if any relay front panel button is pressed or if
any new target or message becomes active.
The PUSHBTN 1 OFF TEXT setting is linked to Pushbutton 1 Off operand and will be displayed in conjunction
with PUSHBTN 1 ID only if the pushbutton element is in Latched mode.
HOLD PRESSED
Range: 0.0 to 10.0 s in steps of 0.1 s
Default: 0.1 s
This setting specifies the time required for a pushbutton to be pressed before it is deemed active.
The timer is Reset upon release of the pushbutton. Note that any pushbutton operation will require the
pushbutton to be pressed a minimum of 60 ms. This minimum time is required prior to activating the pushbutton
hold timer.
AUTORESET
Range: Disabled, Enabled
Default: Disabled
This setting enables the user-programmable pushbutton Autoreset feature. The setting is applicable only if the
pushbutton is in Latched mode.
AUTORESET DELAY
Range: 0.2 to 600.0 s in steps of 0.1 s
Default: 1.0 s
This setting specifies the time delay for automatic Reset of the pushbutton when in the Latched mode.
196 1601-0320
Chapter 5 - Device Setpoints
LOCK
Range: Off, Any FlexLogic operand
Default: Off
This setting assigns a FlexLogic operand serving to inhibit pushbutton operation from the front panel
pushbuttons. This locking functionality is not applicable to pushbutton autoreset.
DROPOUT TIME
Range: 0.0 to 600.0 s in steps of 0.1 s
Default: 0.0 s
This setting applies only to Self-reset mode and specifies the duration of the pushbutton “active” status after
the pushbutton has been released. The length of time the operand remains on has no effect on the pulse
duration.
The setting is required to set the duration of the pushbutton operating pulse.
EVENTS
Range: Disabled, Enabled
Default: Enabled
1601-0320 197
Chapter 5 - Device Setpoints
>A
i h#
^ lk h# === " ===
B? bbim " == ==
i B == ==
lkk
ij g === g ===
>A
^ blkb
i h == h# ==
B II B W #" == " ==
A@ H A@ H ?B imi == ==
L" abc) G G kkl B == ==
FE
) FE
) ji
g ==
g ==
"f ? D) ? D)
& > >
" = 8< = 8<
^ DC4 DC4
-
!& bca
L" )
f"&
Y "^
r -
qp &!
MNO o
n
Y
MNO MNO
Z[
87
)6
5 U
/;0
)6 STR
EX0 5 bca
S S. )
FE V. %
W 3 L"
)/ `$
4/ -
9/ Z[ B%
1230
78) /.
65 e9
8/7
)6 MNO
5 MNO
Y Z[ MNO
"
LK -
KKJ " !&d"
L - - B
""
`@ **+
4
@ ] @
4
] A )
^ -\
^ --
_
Z[ MNO MNO
B B W
B II - A@ A@
A@ H ( !', V
H
G
G '%&
sTX
FE
FE )
? )) /)4 $" ?
>
?
> D)< "
9/ /90
> D< /90 9/ / "#! V3. 0< <6
**+ = = 8 "%
= 8
<6 87 312
2 D4 A
F6 ;4
D4
C ;4
:
)6
5
0/
.
) Ws C V :
Q
P
198 1601-0320
Chapter 5 - Device Setpoints
1601-0320 199
Chapter 5 - Device Setpoints
The digital state of the Tab Pushbuttons can be entered locally (by directly pressing the front panel pushbutton) or
through Modbus by specifying the correct COMMAND sequence. Typical applications include breaker control,
autorecloser blocking, and settings groups changes. The Tab Pushbuttons are under the control level of password
protection. Only one pushbutton can be pressed at a time. If multiple pushbuttons are pressed simultaneously, the
button pressed first takes the priority.
The Tab Pushbutton settings can be accessed from Setpoints > Device > Front Panel > Tab Pushbuttons > Tab
PB1. The Tab Pushbutton control can be executed by navigating to Status > Summary > Tab Pushbuttons. By
default, the summary page is shown to quickly glance at the active tab pushbuttons. The individual pages can then
be accessed from the summary page. Each Tab Pushbutton asserts its own OFF and ON FlexLogic operands (for
example, TAB PB 1 ON and TAB PB 1 OFF). These operands are available for each pushbutton and can be used to
program specific actions. Each pushbutton has an associated “LED” indicator. By default, this indicator displays the
present status of the corresponding pushbutton ON state.
The activation and deactivation of Tab Pushbuttons is dependent on whether latched or self-reset mode is
programmed.
SELF-RESET MODE: In Self-reset mode, a Tab Pushbutton remains active for the time it is pressed (the pulse
duration) plus the Dropout time specified in the settings. The pushbutton is deactivated in Self-reset mode when the
dropout delay specified in the Dropout Time setting expires. The pulse duration of the pushbutton must be at least
100ms to operate the pushbutton.
LATCHED MODE: In Latched Mode, a pushbutton can be set (activated) by directly pressing the associated tab
pushbutton. The pushbutton maintains the set state until deactivated by another press of the same button. The state
of each pushbutton is stored in non-volatile memory and maintained through the loss of control power.
Path: Setpoints > Device > Front Panel > Tab PBs > Tab PB1(X)
FUNCTION
Range: Self-reset, Latched, Disabled
Default: Self-reset (up to 3.xx)
Default: Disabled (from 4.10)
This setting selects the characteristic of the pushbutton. If disabled, the pushbutton is not active and the
corresponding FlexLogic operands (both ON and OFF) are de-asserted. If set to Self-reset the control logic is
activated by the pulse issued when the pushbutton is being physically pressed.
When in Self-Reset mode and activated locally, the pushbutton control logic asserts the Tab PB [X] ON
FlexLogic operand as long as the pushbutton is being physically pressed, and after being released the
deactivation of the operand is delayed by the Dropout Time setting. The OFF operand is asserted when the
pushbutton element is deactivated.
If set to Latched, the control logic alternates the state of the corresponding FlexLogic operand between ON and
OFF on each button press. When in Latched mode, the states of the FlexLogic operands are stored in a non-
volatile memory. Should the power supply be lost, the correct state of the pushbutton is retained upon
subsequent power-up of the relay. When the pushbutton operand is in the ON state, the operand appears on the
target message until the pushbutton is pressed again to change it to the OFF state.
ID TEXT
Range: Up to 13 alphanumeric characters
Default: Tab PB 1 (or Tab PB[X])
This setting specifies the 13-character line of the user-programmable message and is intended to provide the ID
information of the pushbutton. This text is used to describe the pushbutton in the FlexLogic operands.
200 1601-0320
Chapter 5 - Device Setpoints
LINE 1 TEXT
Range: 2 lines of alphanumeric characters
Default: [blank]
This setting specifies the text that is displayed on Line 1 of the button when in the normal view.
LINE 2 TEXT
Range: 2 lines of alphanumeric characters
Default: [blank]
This setting specifies the text that is displayed on Line 2 of the button when in the normal view.
BUTTON COLOR
Range: Black, Red, Yellow, Blue, Green, Teal, Purple, White
Default: Black
This setting specifies the background color of the Tab Pushbutton. If the button is disabled, the button color by
default is shown as gray.
TEXT COLOR
Range: Black, Red, Yellow, Blue, Green, Teal, Purple, White
Default: White
This setting specifies the text color of the Tab Pushbutton.
INDICATOR COLOR
Range: Black, Red, Yellow, Blue, Green, Teal, Purple, White
Default: Yellow
This setting specifies the color of the “LED” indicator for the Tab Pushbutton.
INDICATOR TRIGGER
Range: TAB PB 1 ON, Any FlexLogic operand
Default: TAB PB 1 ON
1601-0320 201
Chapter 5 - Device Setpoints
This setting assigns a FlexLogic operand to trigger the Indicator to change color from the default color (white) to
the selected color.
HOLD PRESSED
Range: 0.1 to 10.0 s in steps of 0.1 s
Default: 0.1 s
This setting specifies the time required for a pushbutton to be pressed before it is deemed active.
The timer is Reset upon release of the pushbutton. Note that any pushbutton operation will require the
pushbutton to be pressed a minimum of 100ms.
AUTORESET
Range: Disabled, Enabled
Default: Disabled
This setting enables the Tab Pushbutton Autoreset feature. The setting is applicable only if the pushbutton is in
“Latched” mode.
AUTORESET DELAY
Range: 0.2 to 600.0 s in steps of 0.1 s
Default: 1.0 s
This setting specifies the time delay for automatic Reset of the pushbutton when in the “Latched” mode.
LOCK
Range: Any FlexLogic operand
Default: Off
This setting assigns a FlexLogic operand to inhibit pushbutton operation from the front panel pushbuttons. This
locking functionality is not applicable to pushbutton autoreset.
DROPOUT TIME
Range: 0.0 s to 600.0 s in steps of 0.1 s
Default: 0.0 s
This setting applies only to “Self-reset” mode and specifies the duration of the pushbutton “active” status after
the pushbutton has been released. The length of time the operand remains on has no effect on the pulse
duration.
The setting is required to set the duration of the pushbutton operating pulse.
EVENTS
Range: Disabled, Enabled
Default: Enabled
202 1601-0320
Chapter 5 - Device Setpoints
5.12.4 ANNUNCIATOR
The graphical annunciator panel provides an emulation of a conventional physical annunciator panel with backlit
indicators each inscribed with a description of the alarm condition that lights the indicator. The annunciator has 36
user-configurable (programmable) indicators. The indicators can be arranged in pages of 3x3 or 2x2 grids. Each
indicator can have up to 3 lines of configurable text. When the indicators are not active (i.e. a configured
FlexOperand for the annunciator is not triggered), the background is black and the foreground text color is gray.
When the associated FlexOperand becomes active, the background and the foreground turns brighter in color per
the color configuration. When disabled, the indicators are grayed out with no text.
Layout
If the grid layout is selected to be 3x3, the annunciator has 4 pages. If the grid layout is 2x2, the annunciator has 9
pages. The numbering of the indicators is shown as follows.
33 3
3 3
Navigation
The annunciator panel can be displayed in two ways. By default, the annunciator panel is programmed as one of
the homescreens. This means that when on the home page, pressing the home button multiple times rotates
through all the homescreens. Alternatively, the annunciator can be accessed by navigating to Status\Summary
\Annunciator\Page1. Individual annunciator pages can also be assigned as a homepage. If the auto navigation
setting is enabled in the setup, the screen automatically jumps from home to the annunciator page with the first
active alarm. Pages with active alarms will have a maroon flashing tab pushbutton label. If other pages have active
alarms, the >> button will show a flashing label.
Path:Setpoints > Device > Front Panel > Annunciator > Annunciator Setup
RESET ANNUNCIATOR
Range: Off, any FlexLogic operand
Default: Off
1601-0320 203
Chapter 5 - Device Setpoints
This setting designates a FlexLogic operand that, when activated, acknowledges/resets all annunciator windows
in the graphical front panel. This setting is the same as that defined under Setpoints > Device > Resetting >
Reset Annunciator.
The Reset Annunctr OP (OPRD) FlexLogic operand is activated by the two sources of RESET command,
operand source and manual source. Each individual source of a RESET ANNUNCIATOR command also
activates its individual operand Reset Annunctr OP (OPRD) or Reset Annunctr OP (MNUL) to identify the source
of the command. Both of these operands generate an event in the event record when activated. The Reset
Annunciator setting selects the operand that activates the Reset Annunctr OP (OPRD) operand. The RESET
pushbutton in the front panel or the reset command from the EnerVista D&I Setup software 8 Series Setup
software activates the Reset Annunctr OP (MNUL) operand.
PAGE LAYOUT
Range: 3x3, 2x2
Default: 3x3
This setting selects the grid layout of the annunciator pages. The default 3x3 grid layout provides 4 annunciator
pages and 2x2 provides 9 pages.
AUTO NAVIGATION
Range: Disabled, Enabled
Default: Enabled
This setting when enabled, automatically navigates to the annunciator panel page from where the indication was
triggered. While in the annunciator panel, if no action is taken, the screen returns back to the home page after
the timeout setting.
FOCUSED NAVIGATION
Range: Disabled, Enabled
Default: Disabled
When this setting is enabled at the same time as the AUTO NAVIGATION setting, the page that has the active
indicator will come into focus. The focus will change to the newest indicator as soon as that becomes active.
Target Messages and Default Screens both have a lower priority than the FOCUSED NAVIGATION setting of
the Annunciator Panel.
Path:Setpoints > Device > Front Panel > Annunciator > Indicator 1(36)
ALARM INPUT
Range: Off, any FlexLogic Operand
Default: Off
This setting specifies the input operand used to activate the corresponding indicator.
ALARM TYPE
Range: Off, Self-Reset, Latched
Default: Off
This setting specifies the alarm type. Self-Reset alarms track the state of the corresponding input operand.
Latched alarms can be reset using Reset pushbutton or through Acknowledgment via graphical front panel.
204 1601-0320
Chapter 5 - Device Setpoints
The alarm type of each annunciator indicator may be configured as Off, Self-Reset, or Latched. The default
mode is Off. In this mode, the indicator is grayed out without any text. In self-reset mode, the indicator’s inactive
state is by default in black background with dark gray color text. When the associated operand becomes active
(i.e. the assigned FlexOperand is triggered), the configured background color and foreground text color appears.
In latched mode, the configured operand causes the background to flash when it becomes active. If the alarm is
then acknowledged or reset, the background stops flashing. If the operand becomes inactive, the indicator
returns to its default colors. The behavior of these modes conforms to ISA-18.1-1979 (R2004) standard - A-4-5-6
(self-reset), and M-6 (latched).
Note:
If the Annunciator Alarm was initiated by another element that is of a Latched type (e.g. Trip Bus), you must navigate out of
the Annunciator and then reset the latched element. This action will reset the latched element, the Annunciator Alarm and
also the Trip LED if applicable.
State rma
Vsa F F
O
p
d R B
O Acwlg
N
State bnrma
Vsa
State: orma
Vsa : F F
Opd O N
State: arm
R B
R B
Ac wld g Vsa : FastF as
Ac wld g
AND
AND
Opd O
Op d O N
R B
Ac wld g
AND
Opd O N
State: bnorma
Vsa :
When any annunciator page is displayed with an alarm condition, the navigation keys can be used to select an
indicator. Once selected, the alarm condition can be acknowledged by pressing the reset pushbutton or by pressing
the enter key. A confirmation message is displayed for acknowledging the alarm. Pressing the Reset or Enter key
again acknowledges the alarm and pressing the Escape button discards the message. When the alarms are active
under latched mode, a power loss retains the previous state of the alarm as the alarm states are stored in non-
volatile memory.
1601-0320 205
Chapter 5 - Device Setpoints
These settings specify the displayed text on the corresponding line in the alarm indicator. Three lines can be
displayed with each line allowing up to 15 alphanumeric characters.
TEXT COLOR
Range: Black, Red, Yellow, Blue, Green, Teal, Purple, White
Default: White
This setting specifies the color of the alarm indicator text.
BACK COLOR
Range: Black, Red, Yellow, Blue, Green, Teal, Purple, White
Default: Red
This setting specifies the color of the alarm indicator background. When the indicator becomes active, the
background changes color from the default Black to the programmed alarm back color.
COLOR SCHEME
Range: Green (open), Red (open)
Default: Green (open)
This setting defines the color scheme for the breaker status. If it is programmed Green (open), the breaker open
status is shown in the color green on the single line diagram and on the device status.
SCREEN TIMEOUT
Range: 10 to 900 s in steps of 1 s
Default: 120 s
If no pushbutton has been pressed for certain period of time, the relay automatically reverts to its default screen.
If the Default Screens are Enabled, Default Screens will become active after the Screen Timeout expires. If the
Default Screens are Disabled, The Actuals\Summary page is displayed after the Screen Timeout expires.
DISPLAY INTENSITY
Range: 10%-100%
206 1601-0320
Chapter 5 - Device Setpoints
Default: 100%
The backlight can be reduced be make the screen easier to view under higher atmosphere lighting.
Note:
Only available on Membrane and 10 Pushbutton front panel
INACTIVITY TIMEOUT
Range: 10 to 900 s in steps of 1 s
Default: 300 s
When the Inactivity Timeout expires, the screen will dim to Inactivity Intensity.
If the Default Screens are Disabled, the Screen Saver images will become active when the Inactivity Timeout
expires. If the Defaults Screens are Enabled, the Default Screens will be displayed at the Inactivity Intensity
when the Inactivity Timeout expires.
If a new Target occurs and the Target Auto Navigation is enabled, the Target Screen will become active. If the
system is in an inactive state, the system will switch to an active state. The intensity will return to Display
Intensity. If targets are present, the Default Screens will still become operational after the Inactivity Timeout.
INACTIVITY INTENSITY
Range: 10% - 100%
Default: 50%
The inactivity intensity can be varied so that backlight is on at a low intensity instead of being fully shut off.
The Active target Icon shown above, will be the only indication of active target messages.
LANGUAGE
Range: English, French, German, Polish, Russian, Ukrainian,
Default: English
This setting selects the language used to display the settings, metering, status, and targets. The range is
dependent on the order code of the relay.
1601-0320 207
Chapter 5 - Device Setpoints
5.12.6 SCRATCHPAD
You can enter up to ten lines of information under the message scratchpad screen. This information could be
installation notes, or any other information which may be useful, such as reminding operators to perform certain
tasks. You can enter these messages using the EnerVista D&I Setup software setup software or the front panel
keypad.
Messages can be displayed in the following ways:
● On the front panel, all ten scratchpad message lines are displayed under the path: Setpoints\Device\Front
Panel\Scratchpad
● On the front panel, this scratchpad screen can also be displayed as a default screen when the Scratchpad
option is selected under the path: Setpoints\Device\Front Panel\Default Screen. The display disappears
after the message time-out period specified by the path: Setpoints\Device\Front Panel\Display Properties
\Message Timeout.
● On the front panel, this scratchpad screen can also be displayed as a FlexScreen when the relevant
FlexLogic operand is asserted. this can be set under the path: Setpoints\Device\Front Panel\FlexScreens
\FlexScreen [X] Operate, if Scratchpad is selected for the corresponding setpoint at the path: Setpoints
\Device\Front Panel\FlexScreens\FlexScreen [X].
Path: Setpoints\Device\Front Panel\Scratchpad
Line 1(10)
Range: up to 26 alphanumeric characters
Default: Text 1(10)
This menu is used to enter user-defined text. 10 lines are available, and each line supports up to 26 characters.
This user-defined text can be entered from the front panel keypad or the EnerVista D&I Setup software.
208 1601-0320
Chapter 5 - Device Setpoints
FUNCTION
Range: Disabled, Enabled
Default: Enabled
This setpoint enables the feature. Displaying of the screen starts 30 s after setting the feature to “Enabled”,
providing no targets have been issued, nor a PB has been pressed.
DISPLAY TIME
Range: 5 to 900 s in steps of 1 s
Default: 10 s
The display time is the amount of time that each of the three screens are displayed within the display sequence.
DEFAULT SCREEN X
Range: varieties of screens for selection
Default: SLD (for Default Screen 1 only), Off (for others)
This setpoint enables the user to input the default screens. FW versions up to 3.xx offer 3 default screens. FW
versions 4.10 and onward offer 5 default screens.
1601-0320 209
Chapter 5 - Device Setpoints
Note:
When on any single line diagram page, if an object is selected, the home button will not function. The selected object must
first be de-selected by pressing the escape button to be able to use the home button functionality again.
Path: Setpoints > Device > Front Panel > Home Screens
HOME SCREEN 1
Range: All available pages
Default: SLD1
HOME SCREEN 2
Range: All available pages
Default: Tab PB Summary
HOME SCREEN 3
Range: All available pages
Default: Annunciator Pg 1
HOME SCREEN 4
Range: All available pages
Default: Values
HOME SCREEN 5 to 10
Range: All available pages
Default: Off
5.12.9 FLEXSCREENS
The FlexScreens allow you to select a page to appear on the display based on the results of an OPERATE setting.
Up to five FlexScreens can be configured. When the OPERATE setting evaluates to a TRUE, the FlexScreen
configured will be displayed.
Path: Setpoints > Device > Front Panel > FlexScreens
FLEXSCREEN 1
Range: All available pages
Default: Off
FLEXSCREEN 1 OPERATE
Range: Off, Any FlexLogic operand
Default: Off
This setpoint requires the assignment of a FlexLogic operand to turn on FlexScreen 1.
210 1601-0320
Chapter 5 - Device Setpoints
FLEXSCREEN 2
Range: All available pages
Default: Off
FLEXSCREEN 2 OPERATE
Range: Off, Any FlexLogic operand
Default: Off
This setpoint requires the assignment of a FlexLogic operand to turn on FlexScreen 2.
FLEXSCREEN 3
Range: All available pages
Default: Off
FLEXSCREEN 3 OPERATE
Range: Off, Any FlexLogic operand
Default: Off
This setpoint requires the assignment of a FlexLogic operand to turn on FlexScreen 3.
FLEXSCREEN 4
Range: All available pages
Default: Off
FLEXSCREEN 4 OPERATE
Range: Off, Any FlexLogic operand
Default: Off
This setpoint requires the assignment of a FlexLogic operand to turn on FlexScreen 4.
FLEXSCREEN 5
Range: All available pages
Default: Off
FLEXSCREEN 5 OPERATE
Range: Off, Any FlexLogic operand
Default: Off
This setpoint requires the assignment of a FlexLogic operand to turn on FlexScreen 5.
1601-0320 211
Chapter 5 - Device Setpoints
5.13 RESETTING
Some events can be programmed to latch the faceplate LED event indicators and target message on the display.
Depending on the application some auxiliary output relays can be programmed to latch after the triggering event is
cleared. Once set, the latching mechanism holds all the latched indicators, messages, and auxiliary output relays in
the set state, after the initiating condition has cleared, until a RESET command is received to return these latches
(except the FlexLogic latches) to the reset state.
The RESET command can be sent from the faceplate Reset pushbutton, a remote device via a communication
channel, or any programmed FlexLogic operand. Executing the RESET command from either source creates a
general FlexLogic operand RESET OP. Each individual source of a RESET command also creates its individual
operand RESET OP (PB), RESET (COMMS), and RESET OP (OPERAND) to identify the source of the command.
212 1601-0320
Chapter 5 - Device Setpoints
5.14 INSTALLATION
Path:Setpoints > Device > Installation
DEVICE NAME
Range: Up to 13 alphanumeric characters
An alphanumeric name may be assigned to the device.
DEVICE IN SERVICE
Default: Not Ready
Range: Not Ready, Ready
The relay is defaulted to the “Not Ready” state when it leaves the factory. This safeguards against the installation
of a relay whose settings have not been entered. When powered up successfully, the “IN SERVICE” LED
becomes red. The relay in the “Not Ready” state blocks signaling of any output relay. These conditions remain
until the relay is explicitly put in the “Ready” state.
SERVICE COMMAND
Range: 0 to 65535
Default: 0
TEMPERATURE DISPLAY
Range: Celsius, Fahrenheit
Default: Celsius
Selects engineering unit of temperature display.
CURRENT CUTOFF
Range: 0.000 to 1.000 p.u. in steps of 0.001 p.u.
Default: 0.020 p.u.
VOLTAGE CUTOFF
Range: 0.0 to 300.0 in steps of 0.1 V
1601-0320 213
Chapter 5 - Device Setpoints
Default: 1.0 V
Note:
Lower the Voltage Cutoff and Current Cutoff levels with care as the relay accepts lower signals as valid measurements.
Unless dictated otherwise by a specific application, the default settings of “0.020 pu” for current and “1.0 V” for voltage are
recommended.
BKR 1 STATUS
Range: Enabled, Disabled
Default: Enabled
Target Message for the breaker status is shown when the set to ‘Enabled’. When ‘Disabled’, all target messages
related to breaker status will be blocked.
BKR 3 STATUS
Range: Enabled, Disabled
Default: Enabled
214 1601-0320
Chapter 5 - Device Setpoints
Caution:
Self-Test Warnings may indicate a serious problem with the relay hardware!
1601-0320 215
Chapter 5 - Device Setpoints
216 1601-0320
Chapter 5 - Device Setpoints
1601-0320 217
Chapter 5 - Device Setpoints
218 1601-0320
Chapter 5 - Device Setpoints
Note:
When a total loss of power is present, the Critical Failure Relay (Output Relay 8) is de-energized.
1601-0320 219
Chapter 5 - Device Setpoints
Note:
The Clear Records command is also available from Records> Clear Records, where the allowable settings also include
FlexLogic operands.
220 1601-0320
CHAPTER 6
SYSTEM SETPOINTS
Chapter 6 - System Setpoints
222 1601-0320
Chapter 6 - System Setpoints
1601-0320 223
Chapter 6 - System Setpoints
224 1601-0320
Chapter 6 - System Setpoints
CT BANK NAME
Range: Any combination of 13 alphanumeric characters
Default: CT Bank 1-J1
PHASE CT PRIMARY
Range: 1 A to 12000 A in steps of 1A (up to FW 3.xx)
Range: 1 A to 50000 A in steps of 1A (from FW 4.10)
Default: 500 A
Enter the phase CT primary current for current sensing bank J1.
GROUND CT PRIMARY
Range: 1 A to 12000 A (up to FW 3.xx)
Range: 1 A to 50000 A in steps of 1A (from FW 4.10)
Default: 500 A
Enter the rated Ground CT primary current for the ground current input for the selected Current 1 bank.
Path:Setpoints > System > Current Sensing > Current Bank 2-K1
CT BANK NAME
Range: Any combination of 13 alphanumeric characters
Default: CT Bank 2-K1
PHASE CT PRIMARY
Range: 1 A to 12000 A in steps of 1A (up to FW 3.xx)
Range: 1 A to 50000 A in steps of 1A (from FW 4.10)
Default: 500 A
Enter the phase CT primary current for current sensing bank K1.
GROUND CT PRIMARY
Range: 1 A to 12000 A (up to FW 3.xx)
Range: 1 A to 50000 A in steps of 1A (from FW 4.10)
Default: 500 A
Enter the rated Ground CT primary current for the ground current input for the selected Current 2 bank.
1601-0320 225
Chapter 6 - System Setpoints
Note:
The Setpoints > System > Current Sensing > CT Bank 3-K2 option is available in 889 with order code option R1/R5 for
Phase Current Slot K.
Note:
Sensitive Ground CT in the K1 slot is order code dependent.
226 1601-0320
Chapter 6 - System Setpoints
PHASE VT CONNECTION
Range: Wye, Delta, Single
Default: Wye
Select the type of phase VT connection to match the VTs (PTs) connected to the relay.
PHASE VT SECONDARY
Range: 10.0 to 240.0 V in steps of 0.1 V
Default: 120.0 V
Select the output secondary voltage for phase VTs connected to the J2 bank.
PHASE VT RATIO
Range: 1.00 to 5000.00 in steps of 0.01
Default: 1.00
Select the phase VT ratio to match the ratio of the VTs connected to the J2 bank.
AUX. VT NAME
Range: Any combination of 13 alphanumeric characters
Default: Ax VT Bnk1-J2
Enter the name of the auxiliary voltage from bank J2.
AUX. VT CONNECTION
Range: Van, Vbn, Vcn, Vab, Vbc, Vca, Vn
Default: Van
Select the voltage type corresponding to the one applied to the Aux VT relay terminals from bank J2. Select Vn
(neutral voltage), if the neutral voltage is applied to the relay auxiliary VT.
AUX. VT SECONDARY
Range: 10.0 to 240.0 V in steps of 0.1 V
Default: 120.0 V
Select the output secondary voltage of the aux. VT connected to the aux. VT input from bank J2.
1601-0320 227
Chapter 6 - System Setpoints
AUX. VT RATIO
Range: 1.00 to 5000.00 in steps of 0.01
Default: 1.00
Select the aux. VT ratio to match the ratio of the VT connected to the aux. VT input from bank J2.
Note:
The nominal PHASE VT SECONDARY and the AUX VT SECONDARY voltage settings are the voltages across the phase VT
terminals and the auxiliary VT terminals correspondingly when nominal voltage is applied.
Note:
For example, on a system of 13.8kV nominal primary voltage, and a 14400:120 volt VT in a Delta connection, the secondary
voltage would be 115V, i.e. (13800/14400)*120. For a Wye connection, the voltage value entered must be the phase to
neutral voltage which would be 115/√3 = 66.4 V.
Note:
On a 14.4 kV system with a Delta connection and a VT primary to secondary turns ratio of 14400:120, the voltage value
entered would be 120 V, i.e. 14400/120.
228 1601-0320
Chapter 6 - System Setpoints
Note:
The setpoint for inversion of the power metering will be useful to avoid the physical inversion of the CT connections on the
relay. As the power metering will affect the power directional elements, the user must determine the correct forward and
reverse direction of the power, before setup.
1601-0320 229
Chapter 6 - System Setpoints
NOMINAL FREQUENCY
Range: 60 Hz, 50 Hz
Default: 60 Hz
The power system NOMINAL FREQUENCY is used as a default to set the digital sampling rate if the system
frequency cannot be measured from available AC signals. This may happen if the signals selected for frequency
tracking are not present, or a valid frequency is not detected. Before reverting to the nominal frequency, the
frequency tracking algorithm holds the last valid frequency measurement for a safe period of time while waiting
for the signals to reappear or for the distortions to decay.
PHASE ROTATION
Range: ABC, ACB
Default: ABC
The selection of the PHASE ROTATION setting must match the power system phase rotation. The phase
sequence setting is required to properly calculate sequence components and power parameters. Note that this
setting informs the relay of the actual system phase sequence, either ABC or ACB. CT and VT inputs on the
relay labeled as a, b, and c, must be connected to system phases A, B, and C for correct operation.
FREQUENCY TRACKING
Range: Disabled, Enabled
Default: Enabled
Frequency measurement is accomplished by measuring the time between zero crossings of the composite
signal of three-phase bus voltages, line voltage or three-phase currents. The signals are passed through a low
pass filter to prevent false zero crossings. FREQUENCY TRACKING utilizes the measured frequency to set the
sampling rate for current and voltage which results in better accuracy for the Discrete Fourier Transform (DFT)
algorithm for off-nominal frequencies.
The main frequency tracking source uses three-phase voltages. The frequency tracking is switched
automatically to the alternative reference source, i.e., three-phase currents signal, if the frequency detected from
the three-phase voltage inputs is declared invalid. The switching will not be performed if the frequency from the
alternative reference signal is detected invalid. Upon detecting valid frequency on the main source, the tracking
will be switched back to the main source. If a stable frequency signal is not available from any source, then the
tracking frequency defaults to the nominal system frequency.
230 1601-0320
Chapter 6 - System Setpoints
1601-0320 231
Chapter 6 - System Setpoints
Rated MVAR (Reactive power) of the generator (obtained by arc/inverse cosine function of rated power
factor, and then its sine function)
RATED MVA
Range: 0.001 to 2000.000 MVA in steps of 0.001 MVA
Default: 50.000 MVA
Enter the generator rated power rating in MVA. Typically this value is obtained from the generator nameplate or
design datasheet. The rated MVA of the generator is used to derive other rated values such as rated MW,
MVAR, etc.
232 1601-0320
Chapter 6 - System Setpoints
Default: 15 min
This setting adjusts the period of time over which average values for generator records are calculated, such as
the generator average load.
1601-0320 233
Chapter 6 - System Setpoints
6.9 TRANSFORMER
Note:
The Transformer setup is only available for the 889 with Overall Differential Protection order code. Two-winding Transformer
setup is used to compensate for transformer winding connection in overall differential protection.
Note:
An 889 unit ordered with the overall differential protection utilizes a two-winding transformer setup for GSU winding
compensation.
Percent differential protection is the main protection for power transformers with regards to detecting all types of
transformer internal fault. This protection is based on Kirchoff’s law, where the sum of all currents flowing in and out
of the protected equipment equals zero. However, when applying this law to the overall differential protection, one
must keep in mind that the direct summation of the measured currents per-phase, does not automatically result into
zero differential current. This is because:
1. The transformer voltage ratio defines different winding nominal currents
2. The winding CTs are not rated to the exact match of the winding nominal currents
3. Physically, the transformer windings are connected in Delta, Wye or Zig-Zag configuration, and they introduce
a phase shift.
4. The transformer voltage ratio defines different winding nominal currents
5. The winding CTs are not rated to the exact match of the winding nominal currents
6. Physically, the transformer windings are connected in Delta or Wye configuration, and they introduce a phase
shift.
For the correct performance of the overall percent differential protection, it is necessary to correct the magnitude
and phase relationships of the CT secondary currents for each winding, in order to obtain near zero differential
currents under normal transformer operating conditions. Traditionally, the phase shift between the currents from the
transformer windings has been corrected by connecting the CTs from the Wye winding in Delta connection, and the
CTs from the Delta winding in Wye connection. In the past, the magnitude correction has been accomplished using
interposing CTs, or tapped relay windings. This however is not required any more when installing the relay.
The relay simplifies the process by performing the magnitude and phase shift compensations automatically
(internally). Upon entering settings for the protected transformer and winding CT ratings, the relay automatically
calculates and applies the correct magnitude scaling to the winding currents as well as applying the correct phase
shift in order to prepare the currents for summation. To perform the correct currents compensation, all winding CTs
need to be connected in Wye (polarity markings pointing away from the transformer).
234 1601-0320
Chapter 6 - System Setpoints
6.10 BREAKERS
The status of each winding breaker is detected by monitoring the state of either one, or two contact inputs. We
recommend you monitor the status of the breaker using both breaker auxiliary contacts 52a, and 52b. However
using only one of them is also acceptable.
The breaker connection/disconnection to/from the power system is provided by monitoring the contact input BKR
CONNECTED. If the contact input is asserted, the breaker is considered to be connected to the primary system.
When the breaker is determined to be disconnected, the breaker state is shown to be neither open, nor closed. The
trolley is integrated with a circuit breaker (CB), which works as a Disconnect Switch. CB Trolley status based on the
contact input selected under the CONNECTED and BKR TROLLEY setpoints.
Path: Setpoints > System > Breakers
NAME
Range: Up to 13 alphanumeric characters
Default: BKRX
CONNECTED
Range: Off, Any FlexLogic operand
Default: Off
Select a contact input to show whether the breaker is connected (Racked-in, or disconnect switches switched-
on), or disconnected (racked-out, or disconnect switches switched-off) from the system.
BKR TROLLEY
Range: Off, Any FlexLogic operand
Default: Off
Select a contact input to show whether the Breaker Trolley is connected or disconnected from the system.
1601-0320 235
Chapter 6 - System Setpoints
This setting is typically available for two or more breaker applications. For single breaker applications, the setting
is hidden and trip relay selection is defaulted to Relay 1.Any output relay from the list of available output relays
can be programmed for breaker tripping action.
Open Closed
236 1601-0320
Chapter 6 - System Setpoints
^][ p SS^[
S
@
N
D
PB &IJK B6IL4I6 M&QTIJ
@
N
D WY ZY[\ ]^_S
C
R
`cd 1 e!
S
5b A
@
N
F a !=1, OO = 0 D
"#$%&'()* '+$-./2
3B46 79> :;.;?:<
&IJK L&L6V
WY ZY[\ ]^_S
X
C EG mH
@ R `cd 1 f gh ijaj
N
D
8
1601-0320 237
Chapter 6 - System Setpoints
6.11 SWITCHES
The Single Line Diagram (SLD) relays can be configured with up to 9 disconnect switches. The disconnect switch
detection is performed by monitoring the state/states of either one or preferably two contact inputs 89a and 89b.
Monitoring the status of the switch using both auxiliary contacts 89a, and 89b is recommended, however using only
one of them is also possible.When both contacts are programmed, the switch can be monitored for state
discrepancy, i.e. both auxiliary contacts OFF, or both auxiliary contacts ON during operation. Discrepancy Alarm
Delay can be programmed to reflect the transition of the switch during operation from Closed to Opened, and
Opened to Closed. If no auxiliary contact discrepancy is detected after the time delay expires, the switch will be in
one of its normal states, i.e. Opened or Closed. However, if contact inputs discrepancy is detected after the time
delay expires, the relay will issue a SW1(9) Discrepancy target message and illuminate the ALARM LED. The
switch discrepancy condition can be reset by the operand assigned under Reset Alarm setpoint, providing both
contact inputs 89a and 89b show normal states on the relay.
Path: Setpoints > System > Switches > Switch 1(9)
NAME
Range: 13 alphanumeric characters
Default: SW 1
Assign a user-defined name to the disconnect switch. This name is used in the SLD, flash messages related to
disconnect switch 1, and the event recorder.
ALARM DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 2.000 s
This setting specifies the required time interval to overcome transient disagreement between the 89a and 89b
auxiliary contacts during disconnect switch operation. If transient disagreement still exists after this time has
expired, SW1(9) Discrepancy FlexLogic operand is asserted for alarm and/or blocking purposes.
RESET ALARM
Range: Off, Any FlexLogic operand
Default: Off
238 1601-0320
Chapter 6 - System Setpoints
Select an operand from the list of FlexLogic operands, which when asserted resets the Switch Discrepancy
state. Please note that resetting the discrepancy alarm will work only after no discrepancy condition exists
between the switch aux contacts 89a and 89b.
Note:
The selection of Output Relay for Open Relay Select and Close Relay Select has higher priority than other settings as follows:
If an Output Relay is first set to Operate"under a protection element for example, and then this same Output Relay is
selected under either Open Relay Select or Close Relay Select, this Output Relay is automatically reverted to Do Not
Operate and hidden from the menu of the protection element. Deselecting the Output Relay from Open Relay Select or
Close Relay Select unhides the output in the menu of the protection element showing the setting value Do Not Operate.
EVENTS
Range: Disabled, Enabled
Default: Enabled
This setting disables or enables the disconnect switch operation events.
TARGETS
Range: Disabled, Self-Reset, Latched
Default: Enabled
This setting disables or enables the disconnect switch operation Targets.
The logic for Switch configuration and the Open, and Close status is shown in the following tables.
Open Closed
1601-0320 239
Chapter 6 - System Setpoints
Open Closed
240 1601-0320
Chapter 6 - System Setpoints
R
Q X
P
V opmn
jl
O T kh
N C ji
hg
L
M
BW
U
LK
BS
I
H
G&
GF
ED
&
R R R
J
Q Q Q
P P P
T
U U B C W
O O T O [
N BT N N CT
LM LM VT bc`a` cf >? LM
^_ de W
L L ] LK
K BS K BS BS
X [
R U T C
C
T U
Q Z [ @A
P
WY C @ BT T
\ C
O
N
L >?
M >?
LK
BS
=>?
>?
:;<
R
R
/. 8 Q /. 8 Q
P P
- 7$
,$ -7 -, $-7
+ 6 +$' 76
' -5
)*( 4 O * 95
)( 4 O
3 N N
&'% 2 LM &'% 32 LM
#$ 01 #$ 01
" LK " LK
! !
1601-0320 241
Chapter 6 - System Setpoints
6.12 FLEXCURVES
The relay incorporates four programmable FlexCurves - FlexCurve A, B, C and D. The points for these curves are
defined in the EnerVista D&I Setup software. User-defined curves can be used for Time Overcurrent protection in
the same way as IEEE, IAC, ANSI, and IEC curves. Each of the four FlexCurves has 120-point settings for entering
times to reset and operate, 40 points for reset (from 0 to 0.98 times the Pickup value) and 80 for operate (from 1.03
to 20 times the Pickup). This data is converted into two continuous curves by linear interpolation between data
points.
Path: Setpoints > System > FlexCurves
Note:
Use EnerVista D&I Setup software to select, design or modify any of the FlexCurves.
The following table for FlexCurves A, B, C, and D details the 120 points as well as the characteristic for each of
them, and a blank cell to write the time value when the operation (for I > Ipickup) or the reset (for I < Ipickup) is
required.
RESET TIME ms RESET TIME ms OPERATE TIME OPERATE TIME OPERATE TIME OPERATE TIME
ms ms ms ms
0.00 0.68 1.03 2.9 4.9 10.5
242 1601-0320
Chapter 6 - System Setpoints
The first two columns (40 points) correspond to the RESET curve. The other 4 columns, with 80 points in total,
correspond to the OPERATE curve. The reset characteristic values are between 0 and 0.98xPKP, and the operation
values are between 1.03 and 20xPKP.
The final curve is created by means of a linear interpolation from the defined points. This is a separate process for
the RESET and the OPERATE curve.
The definition of these points is performed in a separate module from the relay, using a configuration program
included in EnerVista D&I Setup software, which incorporates a graphical environment for viewing the curve, thus
making it easy to create.
Note:
The relay using a given FlexCurve applies linear approximation for times lying between the user-entered points. Therefore,
special care must be taken when setting the points close to a Pickup multiple of 1; that is, 0.97*Ipickup and 0.98*Ipickup
should be set to a similar value as 1.03*Ipickup. Otherwise, the thermal model may incorrectly estimate the TCU% level
resulting in undesired behavior.
1601-0320 243
Chapter 6 - System Setpoints
EnerVista D&I Setup software allows for easy configuration and management of FlexCurves and their associated
data points. Prospective FlexCurves can be configured from a selection of standard curves to provide the best
approximate fit, then specific data points can be edited afterwards. Alternately, curve data can be imported from a
specified file (.csv format) by selecting the Import Data From setting.
Curves and data can be exported, viewed, and cleared by clicking the appropriate buttons. FlexCurves A, B, C, and
D are customized by editing the operating time (ms) values at pre-defined per-unit current multiples. Note that the
pickup multiples start at zero (implying the “reset time”), operating time below Pickup, and operating time above
Pickup.
244 1601-0320
CHAPTER 7
246 1601-0320
Chapter 7 - Input and Output Setpoints
1601-0320 247
Chapter 7 - Input and Output Setpoints
7.2 INPUTS
Setpoints Device
System
Contact Inputs
Inputs
Data
VirtualCapture
Inputs
Outputs
Analog Inputs * Not for F/W 4.0 or later
Protection
Remote Inputs*
Control
FlexLogic
Testing
894331A1
248 1601-0320
Chapter 7 - Input and Output Setpoints
operand reflecting the debounced state of the contact is updated at the protection pass following the debounce
(marked no. 2 on the figure below). The update is performed at the beginning of the protection pass so all protection
and control functions, as well as FlexLogic equations, are fed with the updated states of the Contact Inputs.
The FlexLogic operand response time to the Contact Input change is related to the debounce time setting plus up to
one protection pass (variable and depending on system frequency if frequency tracking enabled). For example, 8
protection passes per cycle on a 60 Hz system correspond to a protection pass every 2.1 ms. With a contact
debounce time setting of 3.0 ms, the FlexLogic™ operand-assert time limits are: 4.2 + 0.0 = 4.2 ms and 4.2 + 2.1 =
6.3 ms. The 4.2 ms is the minimum protection pass period that contains a debounce time, 3.0 ms.
Regardless of the contact debounce time setting, the Contact Input event is time-stamped with 1 protection pass
accuracy using the time of the first scan corresponding to the new state (mark no. 1 below). Therefore, the time
stamp reflects a change in the DC voltage across the Contact Input terminals that was not accidental as it was
subsequently validated using the debounce timer. The debounce algorithm is symmetrical: the same procedure and
debounce time are used to filter the LOW-HIGH (marks no.1 and 2 in the figure below) and HIGH-LOW (marks no.
3 and 4 below) transitions.
Figure 84: Contact Input Debouncing Mechanism and Time-stamping Sample Timing
NAME
Range: Up to 13 alphanumeric characters
Default: CI 1
1601-0320 249
Chapter 7 - Input and Output Setpoints
An alphanumeric name may be assigned to a Contact Input for diagnostic, setting, and event recording
purposes. The CI X ON (Logic 1) FlexLogic operand corresponds to Contact Input X being closed, while CI X
OFF corresponds to Contact Input X being open. The default names of the contact inputs are matched to the
functions of the inputs (differential, speed, emergency restart, remote reset and spare). However, in addition to
their default settings they can also be programmed for use as generic inputs to set up trips and alarms or for
monitoring purposes based on external contact inputs
DEBOUNCE TIME
Range: 0.0 to 16.0 ms in steps of 0.5 ms
Default: 10.0 ms
The Debounce Time defines the time required for the contact to overcome ‘contact bouncing’ conditions. As this
time differs for different contact types and manufacturers, set it as a maximum contact debounce time (per
manufacturer specifications) plus some margin to ensure proper operation.
EVENTS
Range: Enabled, Disabled
Default: Enabled
For example, to use Contact Input F1 as a status input from the breaker 52b contact, to seal-in the trip relay and
record it in the Event Records menu, make the following settings changes:
CONTACT INPUT 1 NAME: 52b
CONTACT INPUT 1 EVENTS: Enabled
Note:
The 52b contact is closed when the breaker is open and open when the breaker is closed.
FUNCTION
Range: Disabled, Enabled
Default: Disabled
If this setting is disabled, the input is OFF (logic 0) regardless of any attempt to alter the input. If enabled, the
input operates as shown on the logic diagram below, and generates output FlexLogic operands in response to
received input signals and the applied settings.
250 1601-0320
Chapter 7 - Input and Output Setpoints
NAME
Range: Up to 13 Alphanumeric Characters
Default: VI 1
An alphanumeric name may be assigned to a Virtual Input for diagnostic, setting, and event recording purposes.
TYPE
Range: Latched, Self-reset
Default: Latched
There are two types of operation: self-reset and latched. If VIRTUAL INPUT x TYPE is “Self-Reset,” when the
input signal transits from OFF to ON the output operand will be set to ON for only one evaluation of the
FlexLogic equations, then return to OFF. If set to “Latched,” the virtual input sets the state of the output operand
to the same state as the most recent received input.
The self-reset operating mode generates the output operand for a single evaluation of the FlexLogic equations
(i.e., a pulse of one protection pass). If the operand is to be used anywhere other than internally in a FlexLogic
equation, it will likely have to be lengthened in time. A FlexLogic timer with a delayed reset time can perform this
function.
EVENTS
Range: Enabled, Disabled
Default: Enabled
S S
VT I T 1
FI T I :
D=0
E=1 A
ViL L 1 Lt I=1 T
!"#$%&'() *#+,./2
L- O
ViL L 1 Lt FF =0 A Dt L 3 V 1 I
S S
VT I T 1
T E: A
L
845679;<>?@B
-L
1601-0320 251
Chapter 7 - Input and Output Setpoints
NAME
Range: Up to 13 Alphanumeric Characters
Default: VI 1
An alphanumeric name may be assigned to a Remote Input for diagnostic, setting, and event recording
purposes.
EVENTS
Range: Enabled, Disabled
Default: Enabled
This setting enables event generation whenever Remote Input Status is updated.
252 1601-0320
Chapter 7 - Input and Output Setpoints
7.3 OUTPUTS
./01/0 23456 7 897:;2<=
n opqrsotuvwxy
1601-0320 253
Chapter 7 - Input and Output Setpoints
Depending on how an Aux. Relay is assigned, one of the following logic diagrams apply:
● If any of the auxiliary output relays are programmed under the Breaker or Contactor menu for tripping, the
operation of the output follows the Trip logic outlined in the logic diagram (Relay 1 TRIP Selected for Breaker
1 logic diagram) below.
● If any of the auxiliary output relays are programmed under Breaker or Contactor menu for closing, the
operation of the output follows the Close logic diagram (Close Selected for Breaker 1 logic diagram).
● If the auxiliary output is not programmed for tripping or closing a breaker, the operation of the output follows
the generic relay logic from logic diagram (Auxiliary relays general logic).
The Trip and Close selected auxiliary relays will follow the respective Trip and Close logic, meaning they will have
fixed operating characteristics as they depend on switching device feedback for resetting.
Any auxiliary output relay, when selected for switching device tripping or closing, is excluded from the list for
selection from the menu of all elements.
The operation of output relays selected for breaker Trip and breaker Close are breaker-controlled relays designed to
be controlled by the state of the breaker as monitored by a 52a contact, 52b contact, or both.
If the selection for TYPE setpoint is Dropoff, Trip and Close relay operation follows the logic outlined below:
● The Trip and Close relays reset after breaker is detected in a state corresponding to the command. When a
command is sent to one of these special relays, it remains operated until the requested change of the breaker
state is confirmed and the initiating condition has reset.
● If the command resets without a change of the breaker state, the output relay is reset after a default interval
of 2 seconds.
● If neither of the breaker auxiliary contacts 52a nor 52b is programmed to a logic input, the Trip Relay resets
after a default interval of 100 ms after the initiating input resets. The Close Relay is reset after 200 ms.
● The Dropoff Time setpoint is available only when the output relay is selected as Dropoff. In all other cases
the Dropoff Time setpoint is hidden and deactivated. The default setting for the Dropoff time is 100 ms.
If the selection is Latched, the relay is energized by any trip or open command and remains energized upon
element dropout. Latched auxiliary outputs can be reset with a reset command.
If Self-Reset type is selected, the output relay is energized when the corresponding element operates and it
stays energized until the element drops out.
DWELL TIMER
When the input energizing quantity is true, output is also activated at the same time instance. If the input energizing
quantity stays activated for a time period shorter than the predefined amount of time “pickup value” output stays
activated for “pickup value” time (even if the input energizing quantity is activated again in between.
If the input energizing quantity stays activated for a time period longer than the predefined amount of time “pickup
value”, output is deactivated when the input energizing quantity is deactivated.
NAME
Range: Up to 13 alphanumeric characters
Default: Trip
The setpoint is used to name the Trip relay by selecting up to 13 alphanumeric characters.
254 1601-0320
Chapter 7 - Input and Output Setpoints
BLOCK
Range: Disabled, Any FlexLogic operand
Default: Disabled
This setting defines a Block to the Trip output relay. When the selected input is asserted, the Trip output relay is
blocked.
OPERATE
Range: Off, On, Any FlexLogic operand
Default: Off
This setpoint provides a selection of any operand from the list of FlexLogic or communications, which can be
used to energize the Trip output relay.
When set to On, the output relay is constantly asserted (On=1).
When set to Off and no FlexLogic operand is selected, the output relay operates as set in individual protection
elements.
Note:
Setting OPERATE to On supersedes individual protection function settings.
TYPE
Range: Pickup, Dropoff, Dwell, Pulse, Pickup/Dropoff, Self-Reset, Latched
Default: Pickup
This setting defines the sequence type of the Trip output relay. The functionality is described in the Outputs
section.
OPERATION
Range: Non-Failsafe, Failsafe
Default: Non-Failsafe
Failsafe operation causes the output relay to be energized when the Trip condition signal is low and de-
energized when the same signal is high. A failsafe relay also changes state (if not already activated by an
operand driving this output relay) when control power is removed. Conversely a non-failsafe relay is de-
energized in its normal non-activated state and will not change state when control power is removed (if not
already activated by a protection element).
EVENTS
Range: Disabled, Enabled
1601-0320 255
Chapter 7 - Input and Output Setpoints
Default: Enabled
Note:
When the setpoint Function in the protection element menu is set to "Trip", the output relays selected under the Breaker menu
for breaker tripping need to be re-selected from the protection element menu. These output relays will not be operational even
if selected to operate from the protection element menu, if the function is set to "Alarm", "Latched Alarm", or “Configurable”.
256 1601-0320
7.3.1.2
1601-0320
Breaker Open
(from Breaker Detection)
At least one
contact programmed
(from Breaker Detection)
For 859
OR
AND
SETTING SETPOINT Operate Output
Relay ( Ready = 1) Relay 1 TRIP
BLOCK Dropoff Value
AND For 845, and 889(two breakers)
Off = 0 t
AND
Operate the selected
Upon dropout of the trip signal and no Aux Relay programmed
This timer starts on the falling edge of breaker open status detected, this timer for BKR trip
a pulse, and issues a positive pulse will start on the raising edge of a pulse
upon time expiry issued from either of the two timers, and TRIP
will produce positive pulse upon time
OR
expiry.
FLEXLOGIC OPERAND 100 ms When breaker open status is detected,
and no trip is present, the output relay
AND
Relay ( Ready = 1)
OPERATE
FL Operand, Off = 0
TRIP
Trip without
OR
BKR 1 Local Open configured
breaker contact FLEXLOGIC OPERAND
OR
Aux Relay
Relay X
( Ready
ON = 1)
BKR 1 Remotel Open RESET (command)
SETPOINT
Trip request
For 859 only
TYPE:
NOTE: Relay 1(Trip) is programmed by the
AND
UVR UV Trip OP
Dropoff
manufacturer for breaker tripping on 850,
Self-Reset
OR
869 and 889(single breaker option) relays.
For 850 only Latched
Additional output relays can be selected to
OPEN ( from Transfer Scheme) Pickup
OR
Timers
OR
869 Only: When Contactor is selected as a Switching
RESET (command) Device, all the inputs associated with Contactor are
AND
used by the Trip logic
892826C1.vsd
Close relay or an Auxiliary relay. This selection is made at Setpoints > System > Breakers (Contactor) >
Breakers 1 (Contactor 1) > Close Relay Select. If the selected value of the CLOSE RELAY SELECT setting is
Output Relay 2 (F4) is labeled CLOSE/AUX on the wiring diagram. As suggested by that name, it can be used as a
257
Chapter 7 - Input and Output Setpoints
Chapter 7 - Input and Output Setpoints
Off, Output Relay 2 functions as an Auxiliary relay. If the selected value is Relay 2, Output Relay 2 functions as a
Close relay.
The default value is Off. The description below applies to Relay 2 Close functionality. For the Relay 2 auxiliary
functionality; see the Auxiliary Relays generic logic figure.
Path: Setpoints > Outputs > Output Relays > Aux Relay 2 (Close)
Note:
The output relays selected under the Breaker menu for breaker closing are excluded from the list of outputs for selection
under the menus of all elements providing such output relay selection.
Note:
For If Aux Relay 2 is selected for Breaker Close or Contactor Close, the relay name from the Output Relays menu changes to
Close If Aux Relay 2 is not selected, the name reverts to Aux Relay 2.
Breaker Close
(from Breaker Detection)
At least one
contact programmed
(from Breaker Detection)
AND
BKR 1 Local Close CLOSE
expiry.
Relay ( Ready = 1) AND
OR
OR
BKR 1 Remotel Close Block Close
( from Transfer scheme)
For 859 only
Autorestart Close Attempt For 850 only FLEXLOGIC
OR CLOSE
OPERAND
OR
UVR Close
AuxRelay
Relay X ON
( Ready = 1)
For 850 only
AND RESET (command)
OR Close without NOTE: Relay 2
CLOSE (from Transfer Scheme) SETPOINT Trip Relay (Close) is set for
configured contact
TYPE: AND breaker close by
CLOSE (from UV restoration) Dropoff default for 850,
Self-Reset and 869 relays
CLOSE ( from UF restoration) Latched
Pickup
OR
Breaker Failure
892827C1.vsd
NAME
Range: Up to 13 alphanumeric characters
Default: Aux Rly #
258 1601-0320
Chapter 7 - Input and Output Setpoints
The setpoint is used to name the auxiliary output relay by selecting up to 13 alphanumeric characters.
BLOCK
Range: Disabled, Any FlexLogic operand
Default: Disabled
This setting defines a block to the Auxiliary output relay. When the selected input is asserted, the Aux relay is
blocked.
OPERATE
Range: Off, On, Any FlexLogic operand
Default: Off
This setpoint provides a selection of any operand from the list of FlexLogic or communications, which can be
used to energize the auxiliary output relay.
When set to On, the output relay is constantly asserted (On=1).
When set to Off and no FlexLogic operand is selected, the output relay operates as set in individual protection
elements.
Note:
Setting OPERATE to On supersedes individual protection function settings.
TYPE
Range: Self-Reset, Latched, Pulsed
Default: Pulsed
If Self-Reset is selected, the output relay is energized as long as the element is in operating mode, and
resets when the element drops out. If Latched is selected, the output relay stays energized upon element
dropout. The latched auxiliary outputs can be reset by issuing a reset command. For Pulse selection, see SEAL-
IN TIME (displayed only if Type = Pulsed).
1601-0320 259
Chapter 7 - Input and Output Setpoints
OPERATION
Range: Non-Failsafe, Failsafe
Default: Non-Failsafe
Failsafe operation causes the output relay to be energized when the operand assigned to the OPERATE AUX
RLY # setting is low and de-energized when the same operand is high. A failsafe relay also changes state (if not
already activated by an operand driving this output relay) when control power is removed. Conversely, a non-
failsafe relay is de-energized in its normal non-activated state and will not change state when control power is
removed from the(if not already activated by a protection element).
EVENTS
Range: Disabled, Enabled
Default: Enabled
260 1601-0320
7.3.2
1601-0320
AND
RESET (Command)
VIRTUAL OUTPUTS
Latched
Opearte Aux
Self- Reset
AND Output Relay
Dropoff AND
OR Relay
This setpoint is displayed only (Ready = 1)
upon Pulsed output type selection
SETPOINT
OPERATE SETPOINT
Off = 0 AND Dropoff Value
FLEXLOGIC
Operation (from Protection, OR t
OPERAND
Control, or Monitoring Elements) AuxRelay
Relay( Ready
X ON=
1)
SETTING
AND
Relay ( Ready = 1)
BLOCK
Off = 0
SETPOINT SETPOINT
TYPE: Pickup Value
Pickup Dropoff Value
Pickup/Dropoff RUN
Dwell
Pulse Timers
The relay is equipped with 96 virtual outputs that may be assigned for use via FlexLogic. Virtual outputs not
261
Chapter 7 - Input and Output Setpoints
Chapter 7 - Input and Output Setpoints
A name can be assigned to each virtual output. Any change of state to a virtual output can be logged as an event if
programmed to do so. Virtual outputs are resolved in each protection pass via the evaluation of FlexLogic
equations.
For example, if Virtual Output 1 is the trip signal from FlexLogic and the trip relay is used to signal events, the
settings would be programmed as follows:
VIRTUAL OUTPUT 1 NAME: Trip
VIRTUAL OUTPUT 1 EVENTS: Enabled
Path: Setpoints > Outputs > Virtual Outputs > Virtual Outputs 1 (32)
NAME
Range: up to 13 alphanumeric characters
Default: VO 1
An alphanumeric name may be assigned to a virtual output for diagnostic, setting, and event recording
purposes.
EVENTS
Range: Disabled, Enabled
Default: Disabled
Path: Setpoints > Outputs > Analog Outputs > Analog Output 1(X)
262 1601-0320
Chapter 7 - Input and Output Setpoints
FUNCTION
Range: Disabled, Enabled
Default: Disabled
RANGE
Range: 0 to 1 mA, 0 to 5 mA, 0 to 10 mA, 0 to 20 mA, or 4 to 20 mA
Default: 0 to 1 mA
This setting provides the selection for the analog output range.
PARAMETER
Range: Off, any Flex Analog Parameter
Default: Off
This setting selects the measured parameter to control the Analog Output level.
MIN VALUE
Range: Populates per selection of the analog parameter
Default: 0
This setting defines the minimum value of the analog output quantity. It populates based on the selection of the
analog parameter.
MAX VALUE
Range: Populates per selection of the analog parameter
Default: 0
This setting defines the maximum value of the analog output quantity. It populates based on the selection of the
analog parameter.
Each channel can be programmed to represent a FlexAnalog parameter available in the respective relay. The range
and steps is the same as the range of the FlexAnalog.
PF SCALING TYPE
Range: Flat, Step
Default: Flat
The measured Power Factor values can be transferred to any of the available analogue outputs. There are two
options for scaling power factor: Flat and Step.
Note:
This setting is only available when Analog Output is selected as Power Factor.
1601-0320 263
Chapter 7 - Input and Output Setpoints
Flat scaling is a simple ascending linear function. It covers all selected ranges. The above figure shows the graph
for the 4 to 20 mA output range in Flat Scaling. It covers the entire selected power factor range from the minimum
(-0.99) to the maximum setting (+1.00).
264 1601-0320
Chapter 7 - Input and Output Setpoints
Step scaling is a discontinuous descending linear function with one step-up point. The figure above shows the
related graph for the 4 to 20 mA output range in Step Scaling. It covers all the entire selected power factor range
from the minimum (-0.01) to the maximum setting (+0.00).
1601-0320 265
Chapter 7 - Input and Output Setpoints
266 1601-0320
CHAPTER 8
PROTECTION
Chapter 8 - Protection
268 1601-0320
Chapter 8 - Protection
1601-0320 269
Chapter 8 - Protection
8.2 PROTECTION
The protection elements are organized in six (6) identical setpoint groups: Setpoint Group 1 to Setpoint Group 6.
Setpoints
Device Group 1 Generator
System Group 2 Current
Inputs Group 3 Voltage
Outputs Group 4 Impedance
Protection Group 5 Power
Monitoring Group 6 Frequency
Control
Flexlogic
Testing
Figure 93: Protection Display Hierarchy
Each Setpoint Group has the same protection functions, depending on the relay order code.
270 1601-0320
Chapter 8 - Protection
For internal summation percent differential, we recommend that the terminal side CTs and neutral side CTs have the
same ratios. The maximum allowable ratio mismatch is 10:1. In the case of a mismatch, the relay scales the
currents to the primary of the CT with the higher primary value which is used as the CT reference for the percent
differential element.
Internal summation operates on a per phase basis (phase-segregated). The key variables used in the element are
the Restraining current (Ir) and the Differential current (Id). The way they are calculated depends on the used
differential method as follows:
Internal Summation Method
For internal summation method, differential current Id and restraint current Ir are defined below:
Id = |Its - Ins|
Ir = MAX{|Its|, |Ins|}
Where: Its is the current phasor of the terminal side CTs (J1-CT bank), in per unit normalized to the reference CT
nominal; Ins is the current phasor of the neutral side CTs (K1-CT bank), in per unit normalized to the reference CT
nominal; They are calculated based on the following equations:
Its = (Its_sec_amp)(CTts_pri_rating)/(Cts_sec_rating)(CTref_pri-rating)
Ins = (Ins_sec_amp)(CTns_pri_rating)/(Cns_sec_rating)(CTref_pri-rating)
Where:
● Its_sec_amp = the terminal side CT current phasor in secondary amps
● Ins_sec_amp = the neutral side CT current phasor in secondary amps
● CTts_sec_rating = the terminal side CT secondary current rating
● CTns_sec_rating = the neutral side CT secondary current rating
● CTts_pri_rating = the terminal side CT primary current rating
● CTns_pri_rating = the neutral side CT primary current rating
● CTref_pri_rating = the reference CT primary current rating
● The reference CT is the CT with the maximum primary current rating
The Percent Differential element with the internal summation method selected uses dual slope dual break point
differential/restraint characteristic. The main purpose of the percent-slope characteristic is to prevent misoperation
caused by unbalances between CTs during external faults. CT unbalances arise as a result of the following factors:
● CT accuracy errors
● CT saturation
The characteristic allows for very sensitive settings when fault current is low and less sensitive settings when fault
current is high and CT performance may produce incorrect operate signals. The dual slope characteristic is shown
in the following figure.
1601-0320 271
Chapter 8 - Protection
The horizontal axes value of the percent differential characteristic is the Restraining current (Ir) and the vertical axes
value is the Differential current (Id).
Each pair of measured restraining and differential currents represents a point on the previous figure: Percent
Differential Characteristic. If this point is located above the limit line (area labeled “Operate”), then the differential
flag is set (DIF=1). If the point is located below or on the limit line (area labeled “Block”), then the differential flag is
reset (DIF=0).
Setpoints
Path: Setpoints > Protection > Group 1 > Generator> Percent Differential
FUNCTION
Range: Disabled, Trip, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
272 1601-0320
Chapter 8 - Protection
PICKUP
Range: 0.05 to 1.00 x CT in steps of 0.01
Default: 0.20
This setting defines the minimum differential current required for operation. The setting is based on the amount
of differential current that can be seen under normal operating conditions. A setting of 0.1 to 0.3 pu is generally
recommended. The CT base of the setting is the reference CT nominal (the CT with the maximum primary
current rating).
SLOPE 1
Range: 1 to 100% in steps of 1
Default: 25%
The setting is applicable for restraint currents from zero to BREAK 1, and defines the ratio of differential to
restraint current above which the element operates. The slope is set to ensure sensitivity to internal faults at
normal operating current levels. The criterion for setting this slope is to allow for maximum expected CT
mismatch error when operating at the maximum permitted current. This maximum error is generally in the range
of 5 to 10% of CT rating.
BREAK 1
Range: 0.50 to 2.00 x CT in steps of 0.01
Default: 1.50
The setting defines the end of the Slope 1 region and the start of the transition region. It should be set just above
the maximum normal operating current level of the machine.
BREAK 2
Range: 2.00 to 30.00 x CT in steps of 0.01
Default: 4.00
The setting defines the end of the transition region and the start of the SLOPE 2 region. It must be set to the
level at which any of the protection CTs are expected to begin to saturate. To avoid discontinuity in the cubic
spline calculation, the relay applies a minimum margin of 0.3 CT between BREAK 1 and BREAK 2.
SLOPE 2
Range: 1 to 100% in steps of 1
Default: 95%
The setting is applicable for restraint currents above the BREAK 2 setting. The slope is set to ensure stability
under heavy external fault conditions that could lead to high differential currents as a result of CT saturation. A
setting of 80 to 100% is recommended. The transition region (as shown on the percent differential characteristic)
is a cubic spline, automatically calculated by the relay to result in a smooth transition between SLOPE 1 and
SLOPE 2 with no discontinuities.
PICKUP DELAY
Range: 0.000 to 10.000 in steps of 0.001
Default: 0.000
This setting defines the pickup time delay of the percent differential element.
1601-0320 273
Chapter 8 - Protection
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Latched
Note:
The values of the setpoints for minimum pickup, Break 1 and Break 2 are expressed in terms of CT reference. Please see the
definition of CT reference which is described in the second paragraph of this section.
DC Saturation Detection:
D.C. components of both J1-CT and K1-CT bank currents, in phases A, B and C must be first calculated.
In other words, the d.c. component is an absolute value of the average of current samples over one last cycle of
data.
DCph = (Idcts > D1 x |Its|) AND (|Its| > PFP)
Operation 2 (Eq. 6) is performed three times for each phase separately.
DCns = (Idcns > D1 x |Ins|) AND (|Ins| > PFP)
D1 is a factory constant of 1/2. A new component of the saturation condition is derived as in the figure below:
274 1601-0320
Chapter 8 - Protection
Saturation Detection
External faults near rotating machines typically result in very large time constants of DC components in the fault
currents. Also, when energizing a step-up transformer, the inrush current being limited only by the machine
impedance can be significant and can last for a very long time. In order to provide additional security against
misoperations during these events, the relay incorporates saturation detection logic. When saturation is detected
the element makes an additional check on the angle between the terminal side CT and differential CT currents. If
this angle indicates an internal fault then tripping is permitted. The latter applies only when the Internal summation
method is used.
The saturation detector is implemented as a state machine (see next figure). "NORMAL" is the initial state of the
machine. When in "NORMAL" state, the saturation flag is not set (SAT = 0). The algorithm calculates the saturation
condition, SC. If SC = 1 while the state machine is "NORMAL", the saturation detector goes into the "EXTERNAL
FAULT" state and sets the saturation flag (SAT = 1). The algorithm returns to the "NORMAL" state if the differential
current is below the first slope, S1, for more than 200 ms. When in the "EXTERNAL FAULT" state, the algorithm
goes into the "EXTERNAL FAULT & CT SATURATION" state if the differential flag is set (DIF = 1). When in the
"EXTERNAL FAULT & CT SATURATION" state, the algorithm keeps the saturation flag set (SAT = 1). The state
machine returns to the "EXTERNAL FAULT" state if the differential flag is reset (DIF = 0) for 100 ms.
1601-0320 275
Chapter 8 - Protection
There are three SAT flags (one per phase). The corresponding FlexLogic operands are:
● Percent Diff Sat A
● Percent Diff Sat B
● Percent Diff Sat C
276 1601-0320
Chapter 8 - Protection
There are three DIR flags (one per phase). The corresponding FlexLogic operands are:
● Percent Diff Dir A
● Percent Diff Dir B
● Percent Diff Dir C
Note:
1601-0320 277
Chapter 8 - Protection
That the above CT saturation (SAT) and phase direction (DIR) checking are applicable to internal summation method only. If
the Core balance method is selected, neither SAT nor DIR check is performed, the fixed values SAT=0 and DIR = 1 are used.
LED: TRIP
AND
OR
Set Dominant
AND
S
LATCH
LED: ALARM
AND
OR
Set Dominant
AND
S
LATCH
SETPOINTS
INSTANTANEOUS DIFF RESET R
FUNCTION:
Command
Disabled = 0
Trip
Latched Trip FlexLogic Operands
OR
OR
Instant Diff OP
RUN
OR
|Ibd| > Pickup
SETPOINT:
RUN OUTPUT RELAY 1(X), upon
|Icd| > Pickup selection
LED: PICKUP
OR
OR
FlexLogic Operands
Ovrl Percent Diff PKP
Ovrl Percent Diff PKP A
Ovrl Percent Diff PKP B
Ovrl Percent Diff PKP C
SETPOINTS
AND
FUNCTION:
Disabled = 0
OR
Set Dominant
Trip SETPOINT
AND
S
OR
Slope 2
Off = 0 RUN
d
Differential Currents
OR
(Ia Diff / SETPOINT
Phase A Diff current (Ia Diff)
OR
Ia Restr) >
FlexLogic Operands Tpkp SETPOINT:
AND
selection
AND
Ovrl Percent Diff Dir A
Restraint Currents
RUN Do Not Operate, Operate
Phase A Rest current (Ia Restr) d
Phase B Rest current (Ib Restr) (Ib Diff / SETPOINT
Ib Restr) >
Phase C Rest current (Ic Restr) Tpkp
FlexLogic Operands
AND
r 0
Ovrl Percent Diff Sat B
OR
AND
AND
Iad>(0.5 x PKP)
10s
OR
Disabled = 0
2nd Harm Block
SETPOINT
OR
Disabled = 0 SETPOINT
278 1601-0320
Chapter 8 - Protection
Note:
An 889 with the specific order code option, K-R1/R5 is required for the Overall Percentage Differential. An 889 with the K-
R1/R5 option supports 3-CT banks, 1 VT bank and an additional second breaker control.
Note:
The K2 CT bank is connected to Winding 1, which is the High-Voltage winding of the GSU connected to the system. In
contrast, the K1 CT bank is connected at the neutral side of the generator, and must be configured as Winding 2 (K1).
1601-0320 279
Chapter 8 - Protection
280 1601-0320
Chapter 8 - Protection
The relay continuously calculates per-phase differential and restraint currents, and compares the ratio between the
two values with a user pre-defined differential/restraint characteristic. The purpose of the characteristic is to define
the zone of differential protection operation and the zone of no operation. The differential characteristic provides
setpoints for sensitivity, dependability, and security for all types of faults, and is programmed by the user to reflect a
variety of transformer differential protection applications.
The differential current is calculated per-phase as a vector sum of the currents from all windings after magnitude
and angle compensation.
The restraint current is calculated as a maximum of the same internally compensated currents:
Note:
Refer to the Transformer Setup chapter for the winding currents magnitude and phase shift compensations performed by the
relay.
d
differential
Operate
Block
Slope 2
Slope 1
Pickup
Break 1
Break 2
restraining r
The above figure shows the differential/restraint characteristic of the main transformer percent differential protection.
The decision for operation or no operation is complemented by detection of CT saturation, followed by currents
directional check. The saturation flag (SAT) can only be initiated during an external fault, providing the magnitude of
any of the restraints is bigger than a threshold average using the Break1 and Break 2 setting programmed in the
menu. While at the same time, the differential/restraint ratio is below a slope average calculated based on Slope 1
and Slope 2 settings. The directional flag is not checked unless the SAT flag is initiated. Normally during internal
faults, the trajectory of the differential/restraint ratio does not cross the average calculated breakpoint threshold, in
which case the directional flag is not checked. The directional flag is checked during external faults (SAT flag
triggered), where due to saturation, the differential/restraint trajectory is able to enter the operating region. Usually
the angle between the currents during external fault and CT saturation remains bigger than 90 degrees, in which
case the percent differential protection does not operate. However, while in the operating region, the protection
1601-0320 281
Chapter 8 - Protection
would operate, on evolving faults (external to internal fault), as the directional flag would be high (angle less than 90
degrees).
Minimum Pickup
This setpoint is expressed in x CT of Winding 1. The minimum pickup defines the minimum differential current
required for operation. The pickup setting must be higher than the amount of differential current that is seen under
282 1601-0320
Chapter 8 - Protection
normal transformer loading conditions, and must be higher than the maximum differential current that is seen during
transformer tap changer operation.
For example, for a 20MVA, 25MVA, or 28MVA power transformer with a 138kV/4.16kV ratio, and class C current
transformers CT(w1) 200:5, and CT(w2) 3000:5, the CT errors and the minimum pickup setting is calculated as
follows:
Winding 1 (138kV) CT – reference. Magnitude factor: M(w1) = 1
Winding 2(4.16kV) CT – non reference. Magnitude factor: M(w2) = 4.16 *3000/138*200 = 0.4521
Based on emergency MVA rating:
Winding 1 rated current = 28MVA/(138kV*sqrt(3)) = 117 Amps
Winding 2 rated current =28MVA/(4.16*sqrt(3)) = 3890 Amps
The accuracy of the Class C current transformer is defined in the IEEE standard C37.110 as not exceeding 10% for
symmetrical current magnitudes of up to 20 times the rating for a standard burden resistance:
117Amps *10% = 11.7 Amps = > 11.7/200 = 0.0585 xCT(w1)
3890 Amps *10% = 389 Amps = > 389/3000*M(w2) = 389/3000*0.4521 =0.0585 xCT (w1)
In the worst case, the errors from the two CTs as expressed in xCT(w1) as a reference can be summed:
Minimum Pickup = 0.0585 + 0.0585 = 0.117 (0.2xCT setting for Pickup is sufficient)
Slope 1
This setting defines the desired differential/restraint ratio for detecting internal faults. The percent Slope 1 setting
must be above the differential/restraint ratio duringexternal faults with non-significant fault current magnitude, but
with long lasting DC component, which is able to cause CT saturation.
The Slope 1 setting can be calculated based on the restraint current during emergency loading of the transformer:
Restraint current Winding 1 = 117 Amps/200 = 0.585 xCT
Restraint current Winding 2 (scaled) = 3890/3000*0.4521 = 0.585 xCT
Differential current = CT error = 0.117 xCT
Slope 1 = (0.117/0.585)*100 = 20%
Adding 5% margin, produces a Slope 1 setting of 25%
Slope 2
The Slope 2 setting ensures stability during heavy through fault conditions, where CT saturation results in high
differential current. Slope 2 must be set high enough to cope with the worst case when the CTs from one winding
saturate but the CTs from the other winding do not saturate during external fault. In such case the ratio of the
differential to restraint current can be as high as 95 to 98%.
Break 1
Break 1 must be set to reflect the through current (restraint current) expressed in times winding 1 CT (w1) below
which CT saturation due to DC components and/or residual magnetism is not expected. The latter may be as high
as 80% of the nominal flux, effectively reducing the CT capabilities by factor of 5.
1601-0320 283
Chapter 8 - Protection
Therefore, this setting must correspond to the end of the linear operation of the CT with the worst characteristic,
counting up to 80% remnant flux in the CT core. To calculate this setting, CTs knee-point voltage and CT secondary
burden are needed.
where:
● The CT burden resistance Rb = 2(Rlead + RCTsec + Rrelay)
● CT secondary resistance = RCTsec,
● Conductor resistance = Rlead and the
● Relay input resistance = Rrelay.
● ICTsec is the CT secondary nominal current.
● Vsat is the CT knee-point voltage.
The Break 1 is calculated per the formula above for each winding CT, and then the smallest per value is entered as
a setting.
Break 2
The Break 2 setting defines the beginning of Slope 2 used to provide stability during heavy through fault conditions,
where CT saturation results in high differential current. Break 2 must be set to the through-fault current which
causes the worst CT to saturate, with saturation free time of at least half power cycle.
To define the degree of CT saturation, the IEEE CT saturation tool can be used:
For example, let
● the CT 3000:5 on winding 2 be the worst one which would saturate first during external faults
● the maximum external fault current be 25kA, with an X/R ratio of 15
The CT voltage kneepoint from the saturation characteristic is 300 V, with winding resistance of 0.5 Ohms, Burden
resistance of 2.19 Ohms, and Burden reactance of 0.01 Ohms.
284 1601-0320
Chapter 8 - Protection
The waveform shows that during this external bolted fault with maximum fault current of 25 kA, the CT (3000:5) will
saturate severely, and produce only a ¼ of a cycle saturation free time. Break 2 must be set to a through fault
current so that the CT (3000:5) produces at least ½ cycle saturation free time. The solution isto change the fault
current to 15000 kA. The waveform now shows a bigger part of the first cycle before saturation.
1601-0320 285
Chapter 8 - Protection
The fault current of 15000 Amps would then be translated as 15000/3000 = 5 times winding 2 CT. Bringing this to
the same scale with respect to winding 1 CT reference , i.e. multiplying by a magnitude of 0.4521, the Break 2
setting would be:
Break 2 = 5 *0.4521 = 2.21 xCT (w1)
286 1601-0320
Chapter 8 - Protection
Path:Setpoints > Protection > Group 1 (6) > Generator > Overall Differential
FUNCTION
Range: Disabled, Trip, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
1601-0320 287
Chapter 8 - Protection
The selection of Trip or Configurable enables the Percent Phase Differential function. The trip output relays
selected to trip each breaker will operate, if the Percent Differential protection operates and these trip outputs
are selected in the Percent Differential menu as Operate.
PICKUP
Range: 0.05 to 1.00 x CT in steps of 0.01
Default: 0.20 x CT
This setting defines the minimum differential current required for operation. The setting is selected based on the
amount of differential current that might be seen under normal conditions. This differential current is a result of
the transformer magnetizing current, CT inaccuracies, and transformer ratio that would change by the
transformer on-load tap changer. When the tap changer feature is set properly, the relay compensates the
transformation ratio which impacts the differential protection automatically.
SLOPE 1
Range: 1 to 100% in steps of 1
Default: 25%
This setting is applicable for restraint currents (through currents) of zero to kneepoint 1, and defines the ratio of
differential/restraint currents, above which the element will operate. This slope is set to ensure sensitivity on
internal faults at normal transformer loading. The value of slope 1 must be above the maximum differential
currents which may be seen for through currents with magnitudes less than break 1 setting. The differential
currents can be caused by winding CT inaccuracies, the constant transformer magnetizing current, and the
leakage current from in-zone grounding transformers. Usually a margin of 2% to 5% is added to this setting.
BREAK 1
Range: 0.50 to 2.00 x CT in steps of 0.01 x CT
Default: 1.50 x CT
The setting defines the limit of linear operation of the magnitude reference CT, accounting for up to 80% residual
flux, that effectively reduces the capability of the CT by a factor of 5. BREAK 1 must be set below the current
that can cause CT saturation due to DC components and/or residual magnetism. Very often the BREAK 1
setting is based on the transformer winding 1 nominal current (100% transformer loading). In such cases, one
must check whether or not this setting complies with the above recommendation regarding the CT linear
performance. This breakpoint marks the end of slope 1, where no CT saturation is expected for restraining
(through) currents smaller than that breakpoint.
BREAK 2
Range: 2.00 to 30.00 x CT in steps of 0.01 x CT
Default: 4.00 x CT
Break 2 must be set below the fault current that is most likely to saturate any of the transformer CTs due to an
AC component alone. The setting is expressed in times CT, where the CT rating is the magnitude reference CT
either user selected, or selected automatically.
SLOPE 2
Range: 1% to 100% in steps of 1%
Default: 95%
288 1601-0320
Chapter 8 - Protection
This setting ensures stability during through fault conditions, resulting in CT saturation and spurious high
differential current. SLOPE 2 must be set high to cater for the worst case scenario, where only CTs from one
winding saturate, but the CTs from the other winding(s) do not saturate. In such cases the differential/restraint
ratio can go as high as 95% to 98%.
Note:
Setting SLOPE 1 higher than SLOPE 2 must be avoided, as it is not practical, even though the ranges for both slopes can
allow for one to do so. Correct programming of the differential-restraint characteristic is achieved when SLOPE 1 is used for
sensitivity of operation during internal fault in the range of 15% to 35%, and SLOPE 2 set usually from 80% to 98%, is used to
provide secure area for the diff./restr. trajectory during external faults and CT saturation.
PICKUP DELAY
Range: 0.000 to 10.000 in steps of 0.001 s
Default: 0.000 s
This setting defines the pickup time delay of the percent differential element.
INRUSH INHIBIT
Range: Disabled, 2nd Harm Block
Default: 2nd Harm Block
This setting enables or disables the inrush inhibit function. None of the settings for inrush inhibit are active, when
the function is set to “Disabled”.
This setting specifies the ratio of the 2nd harmonic differential current to the fundamental frequency differential
current for the selected mode of the 2nd harmonic inhibit. The percent differential protection will be blocked from
operation if the actual ratio of the differential 2nd harmonic current to the fundamental frequency differential
current is above this threshold.
1601-0320 289
Chapter 8 - Protection
If set to 2-out-of-3, the relay estimates the 2nd harmonic differential current per-phase, and blocks the
differential protection for all three phases, if the 2nd harmonic content from any two phases is higher than the
2nd harmonic value entered in the setpoint inrush inhibit level.
If set to 1-out-of-3, the relay estimates the 2nd harmonic differential current per-phase, and blocks the
differential protection for all three phases, if the 2nd harmonic content from any phase is higher than the 2nd
harmonic value entered in the setpoint “inrush inhibit level”. This method is also known as the cross-blocking
method.
OVEREXCITATION INHIBIT
Range: Disabled, 5th Harmonic
Default: 5th Harmonic
This setting provides 5th harmonic differential protection blocking during an over excitation condition resulting
from an increased V/Hz ratio.
An overexcitation condition resulting from an increased V/Hz ratio poses a danger to the protected transformer.
A given transformer can tolerate an overfluxing condition for a limited time, as the danger is associated with
thermal processes in the core. Instantaneous tripping of the transformer from the differential protection is not
desirable.
The relay uses a traditional 5th harmonic ratio for inhibiting the differential function during overexcitation
conditions.
OVEREXCITATION LEVEL
Range: 1.0% to 40.0% in steps of 0.1%
Default: 10.0%
This setting specifies the level of 5th harmonic during overexcitation (overfluxing) transformer conditions. When
the 5th harmonic level exceeds the specified OVEREXCITATION LEVEL setting (5th harmonic ratio) the
differential element is blocked. The overexcitation inhibit works on a per-phase basis.
BLOCK
Range: Any FlexLogic operand
Default: Off
RELAYS
Range: Do Not Operate, Operate
Default: Do Not Operate
Any, or all of the output relays can be selected to operate, upon percent differential operation.
The relay provides one instantaneous differential element per setpoint group.
The Instantaneous differential protection is not biased protection and operates similar to the instantaneous
overcurrent protection. Inputs to this protection are computed by the relay per-phase differential currents.
Operation occurs if any of the computed phase differential current is above the instantaneous differential pickup
290 1601-0320
Chapter 8 - Protection
setting. The instantaneous differential protection is usually set to operate during high fault currents, and if used,
its pickup must be set according to the following criteria:
The○PICKUP setting (xCT) must be selected higher than the maximum inrush current during transformer
energization.
The○PICKUP setting must be set higher than the differential current caused CT saturation during faults
outside the zone of protection.
The○PICKUP setting must be selected lower than the maximum fault current during internal faults.
Note:
The output relays selected under the Breaker menu for breaker trip need to be reselected if the Percent Differential function is
set to Trip. These output relays will not be operational even if selected to operate if the Percent Differential function is set to
Configurable.
EVENTS
Range: Disabled, Enabled
Default: Disabled
TARGETS
Range: Disabled, Self-Reset, Latched
Default: Latched
1601-0320 291
Chapter 8 - Protection
h
y] JRKNIN] i
y
Tz{|P
h
y] JRKNIN] i
y
Tz{|P
SETPOINTS
B B xx
~`` D
x
eppnkl
&(' + ,
$
)Z' $
h FlexLogic Operands
i
(
dkvnkv aqrr c s
)Z' (
dkvnkv aqrr c t
%}# ('
dkvnkv aqrr c e
SETPOINT
SETPOINT B xx
B xx *
FlexLogic Operands
C#$ h
+ ,
i
dkvnkv aqrr c
h
C#$ i
SETPOINT:
!"
C#$
#$% &'(')%
_`ab cdefgc
h
h i
i
FlexLogic Operands
( ' ')
SETPOINTS
x
&(' + , h
y] JRKNIN] i
$
h
SETPOINT y
)Z' $ i
Tz{|P
%}# ('
B(%$'
* 'C ~`` D
SETPOINT
* 'C eppnkl
*
B(%$'
+ ,
DEF
h
Differential Currents i
FlexLogic Operands
SETPOINT
;<6 3455
( ' ')
<6 A10:8=
FlexLogic Operands
( ' ')
h ,
( ' ') B) ( ' ') *
i
( ' ') ( ' ')
h
,&
i
( ' ')
,&
SETPOINT
B *
&(' + ,
*(%C
SETPOINT h
i
( ' ') *(%C'
Differential 2nd Harmonic B *
B * G
DEF
HI JKLL MNO PIQR S TUVUT jkl mnop aqrr s
DEF
jkl mnop aqrr t
HW JKLL MNO PIQR S TUVUT
SETPOINT DEF
jkl mnop aqrr e
G HX JKLL MNO PIQR S TUVUT
*
&(' + , SETPOINT
DEF
Differential 5th Harmonic HI JKLL \]^ PIQR S TUVUT
uvw mnop aqrr s
Y)Z
DEF
¡
292 1601-0320
Chapter 8 - Protection
The inverse time stage operating characteristic is defined by the following equation:
where:
● I2 = negative sequence current
● FLA is the generator rated full load current
● K = negative sequence capability constant from the generator manufacturer depending on size and design
● T = time in seconds when I2 > pickup (minimum 250 ms, maximum defined by setpoint)
Note:
Unusually high negative sequence current levels may be caused by incorrect phase CT wiring.
Path: Setpoints > Protection > Group 1(6) > Generator > Generator Unbalance
SIGNAL INPUT
Range: CT Bank 1-J1, CT Bank 2-K1
Default: CT Bank 1-J1
This setting provides the selection for the 3-Phase CT bank inputs. This setting allows applying this element
either on terminal side or neutral side of the Generator.
TRIP FUNCTION
Range: Disabled, Trip, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
This setting enables the Generator Unbalance Trip functionality. When the Trip function is selected and the
element operates, output relay #1 "Trip" operates but the "ALARM" LED does not turn on.
When the Configurable function is selected, neither the Trip output, nor the ALARM LED turns on automatically.
They must be configured using their own menus and FlexLogicTM operands.
TRIP PICKUP
Range: 0.00 to 100.00 % FLA in steps of 0.01
Default: 8.00 % FLA
This setting defines the pickup value of the trip element. Pickup value is given in negative sequence current as
percentage of generator rated full load current.
Note:
This setting should be greater than the corresponding setting for the alarm stage.
1601-0320 293
Chapter 8 - Protection
CONSTANT K
Range: 0.00 to 100.00 in steps of 0.01
Default: 1.00
This setting is the negative sequence capability constant. This value is normally provided by the generator
manufacturer (see ANSI C50.13) depending on size and design.
MAXIMUM TIME
Range: 0 to 1000 s in steps of 1 s
Default: 600 s
The negative sequence overcurrent Maximum Time setting defines the maximum time that any value of
negative sequence current in excess of the pickup value is allowed to persist before a trip is issued. This setting
can be applied to limit the maximum tripping time for low level unbalances.
Note:
Small power system transients or switching device operation can generate spurious negative sequence current that can result
in the false operation of the Current Unbalance element. In order to prevent false operation of the element, minimum time is
set to a fixed value of 250 ms.
RESET TIME
Range: 0.00 to 1000.00 s in steps of 0.01 s
Default: 227.00 s
This setting defines the linear reset time of the trip element time accumulator. It is the maximum reset time from
the threshold of tripping based on the generator unbalance inverse curve. The reset time has an accumulator/
integrator to represent the thermal memory counter which increments linearly if generator unbalance current is
above threshold, and decrements linearly if it below threshold. The "Unbal DPO" operand is set to high when
thermal memory counter resets to zero.
ALARM FUNCTION
Range: Disabled, Alarm, Latched Alarm
Default: Disabled
This setting enables the generator unbalance Alarm functionality.
When the Alarm function is selected and the element operates, the "ALARM" LED flashes; it self-resets when
the operating conditions are cleared.
When the Latched Alarm function is selected and the element operates, the "ALARM" LED flashes during the
operating condition, and is steadily lit after the conditions are cleared. The "ALARM" LED can be cleared by
294 1601-0320
Chapter 8 - Protection
issuing a Reset command. Output relay #1 "Trip" will not operate if the Alarm or Latched Alarm setting is
selected.
ALARM PICKUP
Range: 0.00 to 100.00 % FLA in steps of 0.01
Default: 3.00 % FLA
This setting specifies a pickup for the alarm function. The definite time overcurrent curve would normally be used
to generate an alarm to prompt an operator to take some corrective action. This element would typically be set at
a safe margin below the trip pickup setting.
ALARM DELAY
Range: 0.00 to 600.00 s in steps of 0.01 s
Default: 0.50 s
This setting specifies a time delay for the alarm function. This is the minimum operate time of the alarm element.
This is set to prevent nuisance alarms during system faults.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
EVENT
Range: Enabled, Disabled
Default: Enabled
TARGET
Range: Self-reset, Latched, DIsabled
Default: Self-reset
1601-0320 295
Chapter 8 - Protection
296 1601-0320
8.2.1.4
1601-0320
LED: Alarm
SETPOINT
AND
Disabled=0
ALARM S
AND
OR
AND
LATCH ALARM LATCH
RESET R
SETPOINT SETPOINT Command
Alarm Pickup SETPOINTS
Block
RUN Alarm Pickup Delay
Off=0 FLEXLOGIC OPERANDS
I2/RATED FLA*100 Alarm tPKP 0
Pickup Unbal Alarm OP
SETPOINT
Unbal Alarm PKP
TRIP FUNCTION:
SETPOINT
AND
Do Not Operate, Operate
Latched Trip
OR
Configurable
SETPOINT FLEXLOGIC OPERANDS
Relay 1(TRIP)
RUN
S
AND
SETTING
t LATCH
SIGNAL INPUT:
I_2
FLEXLOGIC OPERANDS
OR
Unbal OP
SETPOINT
Output Relay
Do Not Operate, Operate
This element provides protection against inadvertent energization also known as accidental energization. The
Inadvertent Energization feature may be armed when all of the phase voltages fall below the undervoltage pickup
level and/or the unit is offline. When the feature is armed, if any one of the phase currents measured at the output
297
Chapter 8 - Protection
Chapter 8 - Protection
Protection can be provided for poor synchronization by using the U/V or Offline arming signal. During normal
synchronization, there should be relatively low current measured. If however, synchronization is attempted when
conditions are not appropriate, a large current that is measured within 250 ms after the generator is placed online
would result in an operate.
Note:
This feature requires 5 s to arm, and 250 ms to disarm.
Path: Setpoints > Protection > Group 1(6) > Generator > Inadvertent Energization
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
ARMING MODE
Range: U/V and Offline, U/V or Offline
Default: U/V and Offline
The element is armed based on the U/V condition and/or Offline status.
O/C PICKUP
Range: 0.050 to 30.00 x CT in steps of 0.01 x CT
Default: 0.30 x CT
This setting is the overcurrent level of any phase currents required to allow the element to operate.
U/V PICKUP
Range: 0.00 to 1.50 x VT in steps of 0.01 x VT
Default: 0.50 x VT
This setting sets the undervoltage level of three-phase voltage required to arm the element. When this setting is
zero and ARMING MODE is set to U/V or Offline, the undervoltage supervision will be bypassed and the
arming mode will check the generator Offline status only.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
Range: Do Not Operate, Operate
Default: Do Not Operate
EVENTs
Range: Enabled, Disabled
298 1601-0320
1601-0320
TARGETs
Default: Enabled
Default: Self-reset
LED: TRIP
AND
FLEXLOGIC OPERAND
OR
Any Trip
AND
SETPOINT
LATCH
FUNCTION:
R LED: ALARM
Range: Self-reset, Latched, DIsabled
Disabled
AND
Trip FLEXLOGIC OPERAND
Latched Trip
OR
Any Alarm
Alarm
OR
S
AND
Latched Alarm SETPOINT
LATCH Output Relay X
Configurable
Command R Do Not Operate, Operate
RESET
SETPOINT
FLEXLOGIC OPERAND
BLOCK:
AND
Inadv Energ OP
OR
Off=0 SETPOINT
O/C PICKUP:
OR
Phase B Current (IB) IB > PICKUP AND
Phase C Current (IC) IC > PICKUP
SETPOINT
J2 Voltage Inputs U/V PICKUP:
WYE DELTA RUN
VA VAB VA (VAB) < PICKUP
VB VBC VB (VBC) < PICKUP
AND
AND
VC VCA VC (VCA) < PICKUP
5s
Inadv Energ Armed
OR
250 ms
FlexLogic Operand
OR
Offline
AND
SETPOINT
ARMING MODE:
U/V and Offline
U/V or Offline 894133C1
299
Chapter 8 - Protection
Chapter 8 - Protection
Loss of excitation protection is achieved using positive sequence impedance measurements (from voltage and
currents), and two inverted offset (Mho) circles, as shown. User configurable Under-Voltage (UV) supervision and
sufficient positive sequence current (>0.05 x CT) are applied for additional protection of this element. Each
individual circle characteristic can be applied independently. In the case where a circle element is enabled and the
measured positive sequence impedance falls within this circle, the element operates with the corresponding time
delay setting. Further, a 20 ms reset delay is applied to the element logic which enhances protection dependability,
especially when measured impedance jitters around a circle boundary.
300 1601-0320
Chapter 8 - Protection
Note:
All impedance (in ohms) settings refer to the relay side impedance quantity, i.e. the CT/VT secondary side when looking into
the machine. Although the setting values are in positive ohms, this protection function is looking in to the generator, and
hence the circle characteristics are shown inverted/reversed.
The following is the guideline used to derive the setting of this element.
Note:
The IEEE C37.102-2006 (IEEE guide for AC Generator Protection) provides typical practices to set this element
The inner circle (Circle 1) diameter is set to machine base impedance (i.e. 1 pu), which considers the loss of field
during full loading to medium loading of the machine. An offset is one half of the direct axis transient reactance (X'd)
- both impedances referring to the relay side. The corresponding time delay for the inner circle needs to be higher
than the worst case power swing scenario, and hence this value is determined from stability studies (typically, this
value may be in the range of 0.2 s to 0.5 s).
On the other hand, the outer circle (e.g. Circle 2) diameter is set to the synchronous reactance of the machine (Xd)
and an offset equal to one half of the direct axis transient reactance (X'd) - both impedances referring to the relay
side. This allows the machine to be protected during light load conditions or with reduced field excitation. The
corresponding time delay for the outer circle should be high enough to prevent mis-operations due to power swings,
and hence this value is determined from stability studies (typically, this value may be in the range of 0.5 s to 2 s).
Path: Setpoints > Protection > Group 1(6) > Generator> Loss of Excitation
1601-0320 301
Chapter 8 - Protection
SIGNAL INPUT
Range: Positive Impedance 1, Positive Impedance 2
Default: Positive Impedance 1
The signal input selection to apply this element at the terminal or neutral side CT. The CT and VT sources used
by Positive impedance 1 and 2 are specified in Metering > Impedance > Pos Seq Impedance. Positive
sequence impedance 1 is calculated using 3-phase J1 currents and 3-phase J2 voltages. With K-slot order code
option, positive sequence impedance 2 is calculated using 3-phase K1 currents and 3-phase J2 voltages.
CIRCLE 1 FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
CIRCLE 1 DIAMETER
Range: 0.1 to 300.0 ohms in steps of 0.1 ohms
Default: 25.0 ohms
This setting is the diameter of the Circle 1 characteristic in ohms, referring to the CT/VT secondary (relay).
CIRCLE 1 OFFSET
Range: 0.1 to 300.0 ohms in steps of 0.1 ohms
Default: 2.5 ohms
This setting is the offset of the Circle 1 characteristic in ohms, referring to the CT/VT secondary (relay).
CIRCLE 1 UV SUPERVISION
Range: Disabled, Enabled
Default: Disabled
Under-voltage supervision of the element can be enabled or disabled. If Enabled for Circle 1, the positive
sequence voltage at the machine terminal should be lower than setting value in “UV Supervision” in order to
execute the Circle 1 impedance element, i.e. LOE Circle 1 is enabled only in case voltage drops below the “UV
supervision” level. This additional check ensures the drop in machine terminal voltage in case of loss of
excitation.
CIRCLE 2 FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
302 1601-0320
Chapter 8 - Protection
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
CIRCLE 2 DIAMETER
Range: 0.1 to 300.0 ohms in steps of 0.1 ohms
Default: 35.0 ohms
This setting is the diameter of the Circle 2 characteristic in ohms, referring to the CT/VT secondary (relay).
CIRCLE 2 OFFSET
Range: 0.1 to 300.0 ohms in steps of 0.1 ohms
Default: 2.5 ohms
This setting is the offset of the Circle 2 characteristic in ohms, referring to the CT/VT secondary (relay).
CIRCLE 2 UV SUPERVISION
Range: Disabled, Enabled
Default: Disabled
Under-voltage supervision of the element can be enabled or disabled. If Enabled for Circle 2, the positive
sequence voltage at the machine terminal should be lower than setting value in “UV Supervision” in order to
execute the Circle 2 impedance element, i.e. LOE Circle 1 is enabled only in case voltage drops below the “UV
supervision” level. This additional check ensures the drop in machine terminal voltage in case of loss of
excitation.
UV SUPERVISION
Range: 0.00 to 1.50 x VT in steps of 0.01 x VT
Default: 0.70 x VT
This setting specifies the pickup value for under-voltage supervision for one or both circles (if enabled).
VTFF SUPERVISION
Range: Disabled, VT Fuse Failure 1, VT Fuse Failure 2
Default: Disabled
A VT fuse failure could cause a maloperation of a distance element unless the element is supervised by the
VTFF element. VTFF Supervision is only available if VT Fuse Failure 1(2) function is enabled, otherwise this
setpoint is hidden.
1601-0320 303
Chapter 8 - Protection
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Latched
SETPOINT
FUNCTION:
Disabled=0 FLEXLOGIC OPERAND
Trip Any Trip
Latched Trip
OR
AND
To operate Output Relay
Latched Alarm 1(TRIP)
Configurable
OR
SETPOINTS
S
AND
BLOCK
AND
LATCH
Off = 0
COMPARATOR R
FLEXLOGIC OPERANDS RUN LED: ALARM
AND
Gen Status Online I1 > 0.05 x CT
FLEXLOGIC OPERAND
OR
SETPOINT Any Alarm
VTFF SUPERVISION:
AND
S
VT Fuse Failure 1
LATCH SETPOINT
VT Fuse Failure 2
AND
OR
VT Fuse Fail 2 OP LOE Circle 1 OP
AND
SETTING
SETTING
AND
UV SUPERVISION
FLEXLOGIC OPERANDS
CIRCLE 1 UV SUPERVISION RUN
IV1| > PKP SETTING LOE Circle 1 PKP
304 1601-0320
Chapter 8 - Protection
SETPOINT
FUNCTION:
Disabled=0 FLEXLOGIC OPERAND
Trip Any Trip
Latched Trip
OR
Alarm LED: TRIP
AND
To operate Output Relay
Latched Alarm 1(TRIP)
Configurable
OR
SETPOINTS
S
AND
BLOCK
AND
LATCH
Off = 0
COMPARATOR R
FLEXLOGIC OPERANDS RUN LED: ALARM
AND
Gen Status Online I1 > 0.05 x CT
FLEXLOGIC OPERAND
OR
SETPOINT Any Alarm
VTFF SUPERVISION:
AND
S
VT Fuse Failure 1
LATCH SETPOINT
VT Fuse Failure 2
AND
OR
VT Fuse Fail 2 OP LOE Circle 2 OP
AND
SETTING
SETTING
AND
UV SUPERVISION
FLEXLOGIC OPERANDS
Circle 2 UV SUPERVISION RUN
IV1| > PKP SETTING LOE Circle 2 PKP
Note:
The setpoint Aux VT Connection (under Setpoints > System > Voltage Sensing > Ph VT Bnk1-J2) must be selected as VN
for this element
Path: Setpoints > Protection > Group 1 > Generator > 3rd Harm Neutral UV
TRIP FUNCTION
Range: Disabled, Trip, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
This setting enables the Third Harmonic Neutral Undervoltage trip functionality.
TRIP PICKUP
Range: 0.10 to 20.00 V in steps of 0.01 V
Default: 1.00 V
This setting specifies the trip pickup level in VT secondary for the magnitude of the 3rd harmonic of the neutral
voltage. The magnitude of the 3rd harmonic voltage at the neutral point can be monitored under Metering >
1601-0320 305
Chapter 8 - Protection
Generator > Stat Gnd 3rd Harm. Measuring the actual value of the operating quantity for a specific machine
under variety of load conditions is helpful when selecting the pickup threshold for this feature.
TRIP RELAY
Range: Do Not Operate, Operate
Default: Do Not Operate
ALARM FUNCTION
Range: Disabled, Alarm, Latched Alarm
Default: Disabled
This setting enables the Third Harmonic Neutral Undervoltage alarm functionality.
ALARM PICKUP
Range: 0.1 to 20.00 V in steps of 0.01 V
Default: 0.50 V
This setting specifies the alarm pickup level for the magnitude of the 3rd harmonic of the neutral voltage.
Note:
Trip and alarm pickup levels are set in secondary voltage.
ALARM RELAY
Range: Do Not Operate, Operate
Default: Operate
306 1601-0320
Chapter 8 - Protection
This setting specifies the minimum real power that inhibits this element. If the measured power is above this
setting but below the Blocking Max Power setting, the element is blocked. This setting applies to three-phase
real power where the rated real generator power is the base unit.
Note:
If the Blocking Min Power is set to “0.000”, then the element does not operate for all power values that are less than the
Blocking Max Power setting.
Note:
The base quantity (Rated) is the rated real power and calculated as:
Note:
Rated Real Power = Rated MVA x Rated Power Factor
Note:
Rated MVA and Rated Power Factor are programmed under Setpoints > System > Generator.
BLOCK
Range: FlexLogic operand
Default: Off
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Latched
1601-0320 307
308
8.2.1.7
Chapter 8 - Protection
FLEXLOGIC OPERANDS
3rd Ntr UV Trp PKP
SETPOINT
Trip Pickup
SETPOINT
RUN
ACTUAL VALUES Trip Pickup Delay
3rd Harm VN in Sec tPKP 0
|3rd Harm VN| < Trip Pickup
Third harmonic volt LED: TRIP
AND
Any Trip
S
AND
LATCH
FLEXLOGIC OPERANDS
SETPOINT RESET R
Command 3rd Ntr UV Trp OP
TRIP FUNCTION:
OR
Disabled=0 SETPOINT
Trip Output Relay X
SETPOINT Do Not Operate, Operate
Latched Trip
OR
Alarm Pickup
Configurable SETPOINT
RUN
Alarm Pickup Delay
tPKP 0
AND
|3rd Harm VN|< Alarm Pickup
SETPOINTS
SETPOINT Blocking Min Power
OR
Off=0 Max > Actual 3 Phase
AND
AND
SETPOINT
SETPOINT
Alarm Output Relay
Alarm Function Do Not Operate, Operate
Disabled
FLEXLOGIC OPERANDS
Alarm
3rd Ntr UV Alm OP
OR
Latched Alarm
3rd Ntr UV Alm PKP
894139C1
This element responds to third harmonic voltage measured at the generator neutral and output terminals. When
used in conjunction with the neutral overvoltage (fundamental frequency) element, it provides 100% ground fault
and machine dependent, the protection method of choice is an adaptive method. The following formula is used to
protection of the stator windings. Since the amount of third harmonic voltage that appears in the neutral is both load
1601-0320
Chapter 8 - Protection
create an adaptive operating quantity based on the amount of third harmonic that appears at the generator
terminals.
Where:
● VN(3rd) is a magnitude of the the 3rd harmonic in the voltage measured at the machine neutral point
measured via an auxiliary channel of the VT bank
● V0(3rd) is a magnitude of the 3rd harmonic in the zero-sequence voltage measured at the machine terminals.
Note:
The setpoint Aux VT Connection (under Setpoints > System > Voltage Sensing > Ph VT Bnk1-J2) must be selected as VN
for this element
Note:
This element requires wye-connected VTs for measurement of the third harmonic in the zero-sequence voltage at the
generator output terminals.
Path: Setpoints > Protection > Group 1 > Generator > 3rd Harm Voltage Difference
TRIP FUNCTION
Range: Disabled, Trip, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
This setting enables the Third Harmonic Voltage Difference trip functionality.
TRIP PICKUP
Range: 0.005 to 0.900 in steps of 0.001
Default: 0.100
This setting specifies a pickup level for the operating quantity. It may be beneficial to measure the operating
quantity under various load conditions for a particular machine in order to optimize this setting. This can be
achieved using the actual values menu..
TRIP SUPV
Range: 0.5 to 30.0 V in steps of 0.1 V
Default: 5.0 V
1601-0320 309
Chapter 8 - Protection
This setting specifies a signal level supervision for the vectorial sum of the third harmonic at the machine neutral
and the zero-sequence terminal voltage. The safe value of this setting can be established after putting a given
machine into service and reading the quantity from the relay under actual values menu (Metering > Generator >
Stat Gnd 3rd Harm).
TRIP RELAY
Range: Do Not Operate, Operate
Default: Do Not Operate
ALARM FUNCTION
Range: Disabled, Alarm, Latched Alarm
Default: Disabled
This setting enables the Third Harmonic Voltage Difference alarm functionality.
ALARM PICKUP
Range: 0.005 to 0.900 V in steps of 0.001
Default: 0.150
ALARM SUPV
Range: 0.5 to 30.0 V in steps of 0.1
Default: 5.0 V
This setting specifies a signal level supervision for the vectorial sum of the third harmonic at the machine neutral
and the zero-sequence terminal voltage. The safe value of this setting can be established after putting a given
machine into service and reading the quantity from the relay under actual values menu (Metering > Generator >
Stat Gnd 3rd Harm).
ALARM RELAY
Range: Do Not Operate, Operate
Default: Operate
BLOCK
Range: FlexLogic operand
Default: Off
EVENTS
Range: Enabled, Disabled
Default: Enabled
310 1601-0320
Chapter 8 - Protection
TARGETS
Range: Self-reset, Latched, Disabled
Default: Latched
*+
#! " ð
# %&'() $
,-././0123
Figure 109: Third Harmonic Voltage Difference Application Example
and the magnitude of the neutral and zero-sequence voltages |VN + V0| as:
1601-0320 311
Chapter 8 - Protection
Therefore, under the normal conditions described above, we set the operating quantities as follows:
In actual practice, the |VN| / |VN + V0| ratio may vary from 0.4 to 0.85 under normal conditions. The pickup and
supervision setpoints are determined by evaluating the operating quantities during a fault condition (refer to
example 2 for details).
Example 2: Operating quantities for a fault at a fraction k from the neutral grounding point.
For analysis, consider the above figure and assume that E3 = 10 V, R = 5Ω, Xc = 5Ω, and k = 0.15.In this case, we
have the magnitude of the neutral voltage at: VN = k x E3 = 0.15 x 10 = 1.5 and the magnitude of the neutral and
zero-sequence voltages |VN + V0| as:
V_0= ((1-k)E_(3 Therefore, for faults at a fraction k = 0.15 from the neutral grounding point, we set the operating
quantities as follows:
312 1601-0320
Chapter 8 - Protection
1601-0320 313
314
quickly.
8.2.1.8
Chapter 8 - Protection
SETPOINT
OR
|VN(3rd)| TRIP PICKUP DELAY:
OR
Pickup
Configurable |VN(3rd)+V0(3rd)| S
AND
AND
tPKP
LATCH
AND
20 ms
R
SETPOINT
|V0(3rd)| RESET
1- Pickup Command
Block
|VN(3rd)+V0(3rd)|
Off SETPOINTS
|VN(3rd)+V0(3rd)| > Supv
TRIP RELAY
ACTUAL VALUES
Disable
FLEXLOGIC OPERANDS
AND
Alarm 3rd V Dif ALM OP
OR
Latch Alarm 3rd V Dif ALM PKP
used, this element may be set to a much higher sensitivity than the differential element in order to detect high
The Offline Overcurrent feature is active only when the generator is in offline mode. In this case, it is easier to
differentiate between system faults and machine faults. When neutral end CT bank measurements (Ia, Ib, Ic) are
1601-0320
impedance phase faults. In the event of a low impedance fault, the differential elements still shutdown the generator
Chapter 8 - Protection
Note:
Since the breaker auxiliary contacts wired to the Breaker Status Input may not operate at exactly the same time as the main
breaker contacts, the time delay should be coordinated with the difference of the operation times.
Path: Setpoints > Protection > Group 1 > Generator > Offline Overcurrent
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
SIGNAL INPUT
Range: CT Bank 1 - J1, CT Bank 2 - K1
Default: CT Bank 1 - J1
Note:
This setting is order code dependent. In the case of two CT cards, it is recommended that the CT wired in the neutral end is
selected as input for this function.
PICKUP
Range: 0.05 to 1.00 x CT in steps of 0.01
Default: 0.05 x CT
Note:
If the unit auxiliary transformer is on the generator side of the breaker, the pickup level must be set greater than the unit
auxiliary load.
PICKUP DELAY
Range: 0.00 to 600.00 s in steps of 0.01 s
Default: 0.08 s
OUTPUT RELAY
Range: Do Not Operate, Operate
Default: Do Not Operate
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
EVENTS:
Range: Enabled, Disabled
1601-0320 315
316
TARGETS:
LED: TRIP
Default: Disabled
AND
FLEXLOGIC OPERAND
Default: Self-reset
Chapter 8 - Protection
OR
Any Trip
S
SETPOINT
AND
LATCH
FUNCTION:
R
Disabled
LED: ALARM
Trip
AND
Latched Trip FLEXLOGIC OPERAND
OR
Any Alarm
Alarm
OR
Latched Alarm S
AND
Configurable LATCH SETPOINT
Range: Self-reset, Latched, Disabled
FLEXLOGIC OPERAND
Offline OC OP
OR
SETPOINTS SETPOINTS
AND
Ia > PICKUP SETPOINTS
FlexLogic Operand
PICKUP DELAY:
OFFLINE
RUN
tPKP
OR
AND
0
FlexLogic Operand
TRIPPED tPKP
OR
Ib > PICKUP
0
tPKP
0
RUN FlexLogic Operands
AND
Offline OC OP A
Ic > PICKUP
Offline OC OP B
Offline OC OP C
SETPOINTS
LED: PICKUP
Signal Input
CT BANK 1-J1
OR
CT BANK 1-K1
Phase A current (Ia) FlexLogic Operands
Phase B current (Ib) Offline OC PKP
Phase C current (Ic)
Offline OC PKP A
Offline OC PKP B
Offline OC PKP C
894131C1
1601-0320
Chapter 8 - Protection
FUNCTION
Range: Disabled, Alarm, Latched Alarm, Configurable
Default: Disabled
PICKUP
Range: 0.50 to 3.00 x FLA in steps of 0.01 x FLA
Default: 0.70 x FLA
PICKUP DELAY
Range: 0.00 to 180.00 s in steps of 0.01 s
Default: 1.00 s
DROPOUT DELAY
Range: 0.00 to 180.00 s in steps of 0.01 s
Default: 1.00 s
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Latched
1601-0320 317
Chapter 8 - Protection
AND
LED:
ALARM
SETPOINT FlexLogic Operands
OR
FUNCTION Any Alarm
Disabled
AND
S
Alarm
LATCH
OR
Latched Alarm
R
Configurable
RESET Set
Dominant
Command
SETPOINT SETPOINT
BLOCK PICKUP SETPOINT
AND
Off = 0 RUN SETPOINTS
PICKUP DELAY:
OUTPUT RELAY X
MOTOR STATUS Iavg > PICKUP DROPOUT DELAY: Do Not Operate, Operate
OR
Running
Overload
tPKP FlexLogic Operands
tDPO
OR
The relay has six setpoint groups with phase, neutral, and ground elements per group. The programming of the
time-current characteristics of these elements is identical in all cases and is only covered in this section. The
required curve is established by programming a Pickup Current, Curve Shape, Curve Multiplier, and Reset Time.
The Curve Shape can be either a standard shape or a user-defined shape programmed with the FlexCurve feature.
318 1601-0320
Chapter 8 - Protection
A time dial multiplier setting allows the selection of a multiple of the base curve shape (where the time dial multiplier
= 1) with the curve shape setting. Unlike the electromechanical time dial equivalent, operate times are directly
proportional to the time multiplier (TD MULTIPLIER) setting value. For example, all times for a multiplier of 10 are
10 times the multiplier 1 or base curve values. Setting the multiplier to zero results in an instantaneous response to
all current levels above Pickup.
Time Overcurrent time calculations are made with an internal energy capacity memory variable. When this variable
indicates that the energy capacity has reached 100%, a Time Overcurrent element will operate. If less than 100%
energy capacity is accumulated in this variable and the current falls below the dropout threshold of 97 to 98% of the
Pickup value, the variable must be reduced.
Two types of this resetting operation are available: DT and Inverse. The Inverse selection can be used where
the relay must coordinate with electromechanical relays. The DT selection is intended for applications with other
relays, such as most static relays, which set the energy capacity directly to zero or some fixed time delay when the
current falls below the reset threshold or when inverse curve coordination is not available.
Note:
In IEEE, ANSI, IAC, I2T, I4T User Curves, multiplier setting TDM value is provided by the Time Dial setting
IEEE CURVES
The IEEE Time Overcurrent curve shapes conform to industry standards and the IEEE C37.112-1996 curve
classifications for extremely, very, and moderately inverse. The IEEE curves are derived from the formula:
1601-0320 319
Chapter 8 - Protection
Where:
● T = operate time (in seconds)
● TDM = Multiplier setting
● I = input current
● Ipickup = Pickup Current setting
● A, B, p = constants
● TRESET = reset time in seconds (assuming energy capacity is 100% and RESET is Timed)
● tr = characteristic constant
320 1601-0320
Chapter 8 - Protection
ANSI CURVES
The ANSI time overcurrent curve shapes conform to industry standards and the ANSI C37.90 curve classifications
for extremely, very, and moderately inverse. The ANSI curves are derived from the following formulae:
Where:
● T = operate time (in seconds)
● TDM = Multiplier setting
● I = input current
● Ipickup = Pickup Current setting
1601-0320 321
Chapter 8 - Protection
● A to E = constants
● TRESET = reset time in seconds (assuming energy capacity is 100% and RESET is Timed)
● tr = characteristic constant
322 1601-0320
Chapter 8 - Protection
IEC CURVES
For European applications, the relay offers three standard curves defined in IEC 255-4 and British standard BS142.
These are defined as IEC Curve A, IEC Curve B, and IEC Curve C. The formula for these curves is:
Where:
● T = operate time (in seconds)
● TDM = Multiplier setting
● I = input current
● Ipickup = Pickup Current setting
● K, E = constants
● tr = characteristic constant
● TRESET = reset time in seconds (assuming energy capacity is 100% and RESET is Timed)
1601-0320 323
Chapter 8 - Protection
Note:
When using Long Time Inverse, Rectifier, IEC Short Time Inverse, BPN EDF curves for the operate characteristic, DT
(Definite Time) is always used for the Reset characteristic
324 1601-0320
Chapter 8 - Protection
0.10 0.306 0.178 0.111 0.088 0.075 0.067 0.062 0.058 0.054 0.052
0.20 0.612 0.356 0.223 0.175 0.150 0.135 0.124 0.115 0.109 0.104
0.40 1.223 0.711 0.445 0.351 0.301 0.269 0.247 0.231 0.218 0.207
0.60 1.835 1.067 0.668 0.526 0.451 0.404 0.371 0.346 0.327 0.311
0.80 2.446 1.423 0.890 0.702 0.602 0.538 0.494 0.461 0.435 0.415
1.00 3.058 1.778 1.113 0.877 0.752 0.673 0.618 0.576 0.544 0.518
Rectifier
0.05 264.241 48.313 4.896 0.976 0.280 0.101 0.042 0.020 0.010 0.006
0.10 528.482 96.626 9.792 1.952 0.559 0.201 0.085 0.040 0.021 0.012
0.20 1056.964 193.251 19.583 3.904 1.119 0.403 0.170 0.080 0.042 0.023
0.40 2113.928 386.502 39.167 7.808 2.237 0.806 0.340 0.161 0.083 0.046
0.60 3170.891 579.754 58.750 11.712 3.356 1.209 0.510 0.241 0.125 0.069
0.80 4227.855 773.005 78.334 15.615 4.474 1.612 0.680 0.322 0.166 0.092
1.00 5284.819 966.256 97.917 19.519 5.593 2.015 0.850 0.402 0.208 0.115
Standard Inverse (1.3s)
0.05 0.373 0.217 0.137 0.108 0.093 0.083 0.076 0.071 0.068 0.064
0.10 0.745 0.435 0.273 0.216 0.186 0.166 0.153 0.143 0.135 0.129
0.20 1.491 0.870 0.546 0.432 0.371 0.333 0.306 0.286 0.270 0.258
0.40 2.982 1.739 1.093 0.864 0.742 0.665 0.612 0.572 0.540 0.515
0.60 4.473 2.609 1.639 1.295 1.113 0.998 0.918 0.858 0.811 0.773
0.80 5.964 3.479 2.186 1.727 1.484 1.331 1.224 1.144 1.081 1.030
1.00 7.455 4.348 2.732 2.159 1.856 1.664 1.530 1.429 1.351 1.288
IAC CURVES
The curves for the General Electric type IAC relay family are derived from the formula:
Where:
● T = operate time (in seconds)
● TDM = Multiplier setting
● I = input current
● Ipickup = Pickup Current setting
1601-0320 325
Chapter 8 - Protection
● A to E = constants
● tr = characteristic constant
● TRESET = reset time in seconds (assuming energy capacity is 100% and RESET is Timed)
326 1601-0320
Chapter 8 - Protection
I2T CURVES
The curves for the I2t are derived from the formula:
Where:
● T = operate time (in seconds)
● TDM = Multiplier setting
● I = input current
● Ipickup = Pickup Current setting
● TRESET = reset time in seconds (assuming energy capacity is 100% and RESET is Timed)
I4T CURVES
The curves for the I4t are derived from the formula:
1601-0320 327
Chapter 8 - Protection
Where:
● T = operate time (in seconds)
● TDM = Multiplier setting
● I = input current
● Ipickup = Pickup Current setting
● TRESET = reset time in seconds (assuming energy capacity is 100% and RESET is Timed)
0.10 1.9753 0.6250 0.1235 0.0391 0.0160 0.0077 0.0042 0.0024 0.0015 0.0010
1.00 19.753 6.250 1.235 0.391 0.160 0.077 0.042 0.024 0.015 0.010
10.00 197.531 62.500 12.346 3.906 1.600 0.772 0.416 0.244 0.152 0.100
100.00 1975.31 625.00 123.46 39.06 16.00 7.72 4.16 2.44 1.52 1.00
600.00 11851.9 3750.0 740.7 234.4 96.00 46.3 25.0 14.65 9.14 6.00
where:
● T is the operating time
● k(RI) is the Time Multiplier setting.
● I = input current,
● Ipickup = Pickup Current setting
Note:
When using RI for the Operate characteristic, DT (Definite Time) is always used for the Reset characteristic.
328 1601-0320
Chapter 8 - Protection
IDG CURVE
The IDG curve is commonly used for time delayed neutral/ground fault protection in the Swedish market. The IDG
curve is represented by the following equation:
T = 5.8 - 1.35 x loge (I/Ipickup)
where:
● T is the operating time
● I = input current,
● Ipickup = Pickup Current setting.
The IDG Is setting is set as a multiple of the Ground/Neutral overcurrent setting Ipickup for the IDG curve. It
determines the actual current threshold at which the element starts.
The IDG Time setting sets the minimum operate time at high levels of fault current for IDG curves.
Note:
When using IDG for the Operate characteristic, DT (Definite Time) with a value of zero is recommended to use for the Reset
characteristic.
1601-0320 329
Chapter 8 - Protection
EPATR B CURVE
The EPATR B curve is commonly used for Sensitive Earth Fault protection. It is based on primary current settings,
employing a SEF CT ratio of 100:1 A. The EPATR_B curve has 3 separate segments defined in terms of the primary
current. It is defined as follows:
Segment Primary Current Range Based on 100A: Current/Time Characteristic
1A CT Ratio
Note:
When using EPATR B curve, DT (Definite Time) is always used for the Reset characteristic.
330 1601-0320
Chapter 8 - Protection
FLEXCURVES
The custom FlexCurves are described in detail in the FlexCurves section of this chapter. The curve shapes for the
FlexCurves are derived from the formulae:
T = TDM x [FlexCurveTime at (I/Ipickup)] when (I/Ipickup) ³ 1.00
TRESET = TDM x [FlexCurveTime at (I/Ipickup)] when (I/Ipickup) £ 0.98
Where:
● T = operate time (in seconds),
● TDM = Multiplier setting,
● I = input current,
● Ipickup = Pickup Current setting,
● TRESET = reset time in seconds (assuming energy capacity is 100% and RESET is timed)
Note:
Flexcurve A/B/C/D is renamed as Def User Curve A/B/C/D
1601-0320 331
Chapter 8 - Protection
Note:
Note: In Definite Time Curves, Multiplier setting value is provided by ‘Time Delay’ setting.
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Latched Trip, Configurable
Default: Disabled
SIGNAL INPUT
Range: Dependent upon the order code
Default: CT Bank 1-J1
This setting provides the selection for the current input bank. The default bank names can be changed in:
Setpoints > System > Current Sensing > [Name] > CT Bank Name.
INPUT
Range: Phasor, RMS
Default: Phasor
332 1601-0320
Chapter 8 - Protection
This selection defines the method of processing of the current signal. It could be Root Mean Square (RMS) or
Fundamental Phasor Magnitude.
PICKUP
Range: 0.020 to 30.000 x CT in steps of 0.001 x CT
Default: 1.000 x CT
CURVE
Range: Definite Time, IEC Curve A, IEC Curve B, IEC Curve C, IEC Short Inverse, Long Time Inverse,
Rectifier,SI(1.3s), BPN EDF, IEEE Mod Inverse, IEEE Very Inverse, IEEE Extr. Inverse, US Inverse, US ST
Inverse, ANSI Extr. Inverse, ANSI Very Inverse, ANSI Norm Inverse, ANSI Mod Inverse, IAC Extr. Inverse, IAC
Very Inverse, IAC Inverse, IAC Short Inverse, I2t, I4t, Rapid Inverse, FlexCurve A, FlexCurve B, FlexCurve C,
FlexCurve D.
Default: IEEE Mod Inverse
This setting sets the shape of the selected over-current inverse curve. If none of the standard curve shapes is
appropriate, a FlexCurve can be created. Refer to the User curve and the FlexCurve setup for more details on
their configurations and usage.
TDM
Range: 0.01 to 28800.00 in steps of 0.01
Default: 1.00
This is the Time Multiplier Setting to adjust the operate time of IEC Curve A/B/C, IEEE M/V/E Inverse, US
Inverse, US Short Time, ANSI E/V/N/M Inverse, IAC E/V/N/S Inverse, I2T and I4T curves. For example, if an
IEEE Extremely Inverse curve is selected with TDM = 2, and the fault current is 5 times bigger than the PKP
level, the operation of the element will not occur before 2.59 s have elapsed after Pickup.
TMS
Range: 0.025 to 1.200 in steps of 0.005
Default: 1.00
This is the Time Multiplier Setting to adjust the operate time of IEC Short Inverse, Long Time Inverse, Rectifier,
Standard Inverse SI(1.3s), and BPN EDF curves.
K (RI)
Range: 0.10 to 10.00 in steps of 0.05
Default: 1.00
This setting defines the Time multiplier constant to adjust the operate time of the Rapid Inverse (RI) curve.
This k(RI) setting can be made visible from setting management, only when the Curve setting is selected as
Rapid Inverse.
TIME DELAY
Range: 0.000 s to 28800.000 s in steps of 0.001 s
Default: 1.000
1601-0320 333
Chapter 8 - Protection
This setting defines the time delay for operation. This Time Delay setting can be made visible from setting
management, only when the Curve setting is selected as Definite Time.
DT ADDER
Range: 0.00 to 100.00 s in steps of 0.01 s
Default: 0.00
This setting adds an additional fixed time delay to the IDMT Operate characteristic.The DT Adder setting will be
visible for when any IDMT curves are selected under the Curve setting.
RESET
Range: DT, Inverse
Default: DT
Selection of a Definite Time (DT) or Inverse reset time is provided using this setting.
If Definite Time (DT) reset is selected, the Phase TOC element will reset after a time delay provided by the
Reset Time setting. If Inverse reset is selected, the time to reset is calculated based on the reset equation for
the selected inverse curve.
Note: When using IEC Short Inverse, Long Time Inverse, BPN EDF, Rectifier, Rapid Inverse curves for the
Operate characteristic, Definite Time is used by default as Reset characteristic.
RESET TIME
Range: 0.000 to 28800.000 in steps of 0.001
Default: 0.000
This setting provides selection for dropout time delay used to delay the dropout of the detection of the
overcurrent condition.
This can be made visible from setting management when the Reset setting is selected as DT or when using
Long Time Inverse, IEC Short Inverse, BPN EDF, Rectifier, and Rapid Inverse curves.
DIRECTION
Range: Disabled, Forward (Ph Dir OCx FWD), Reverse (Ph Dir OCx REV)
Default: Disabled
This setting determines the direction of Phase TOC element.
V DEP OC
Range: Disabled, VCO, VRO
Default: Disabled
V Dep OC (Voltage Dependent Overcurrent) replaces the legacy Voltage Restrained Overcurrent (VRO) function
by adding Voltage Controlled Overcurrent functionality to it. This setting can now select Disabled, VCO or VRO.
When enabled, this feature controls the Pickup value of each individual Phase Time Overcurrent element in a
fixed relationship with its corresponding phase input voltage.
An overcurrent protection scheme is co-ordinated throughout a system such that cascaded operation is
achieved. This means that if for some reason a downstream circuit breaker fails to trip for a fault condition, the
next upstream circuit breaker should trip.
334 1601-0320
Chapter 8 - Protection
If the current seen by a local device for a remote fault condition is below its overcurrent setting, a voltage
dependent element may be used to increase the sensitivity to such faults. As a reduction in system voltage will
occur during overcurrent conditions, this may be used to enhance the sensitivity of the overcurrent protection by
reducing the pick-up level.
If cold load pickup, autoreclosing, or manual close blocking features are controlling the protection, the Phase
TOC Voltage Restraint does not work, even when enabled.
In Voltage Controlled Operation (VCO) mode of operation, the under-voltage detector is used to produce a step
change in the current setting, when the voltage falls below the voltage setting V Dep OC V<1. The operating
characteristic of the current setting when voltage-controlled mode is selected is as follows:
Current
Setting
Current
Setting
VT INPUT
Range: Dependent upon the order code
Default: Ph VT Bank 1-J2
This setting provides the selection for the voltage input bank, when V Dep OC is enabled.
V Dep OC V1
Range: 0.01 to 1.20 x VT in steps of 0.01 x VT
1601-0320 335
Chapter 8 - Protection
Default: 0.72 x VT
This setting sets the voltage V1 threshold at which the current setting of the overcurrent stage becomes reduced.
This is on a per phase basis.
V Dep OC k
Range: 0.10 to 1.00 in steps of 0.05
Default: 0.25
This setting determines the Overcurrent multiplier factor used to reduce the pick-up overcurrent setting.
V Dep OC V2
Range: 0.01 to 1.2 x VT in steps of 0.01 x VT
Default: 0.54 x VT
This setting sets the voltage V2 threshold at which the current setting of the overcurrent stage becomes reduced.
This is on a per phase basis.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Self-reset
336 1601-0320
Chapter 8 - Protection
FLEXLOGIC OPERAND
Any Trip
LED: TRIP To operate Output Relay
AND
1(TRIP)
Configurable in 845 & 859
OR
S
AND
LATCH
R
LED: ALARM
AND
SETPOINT
I>[X] FUNCTION: FLEXLOGIC OPERAND
OR
Any Alarm
Disabled
AND
Trip S
Latched Trip LATCH SETPOINT
SETPOINTS
OR
OR
PTOC I>[X] Trip
SETPOINTS
I>[X] DIRECTION: I>[X] TMS:
Non-Directional
I>[X] TIME DIAL:
Forward
AND
Directional OC element)
I>[X] DT ADDER:
PTOC I>[X] Trip B
AND
SETPOINTS
OR
I>[X] INHIBIT: SETPOINTS
Adjust PKP
Off=0 I>[X] Rly OP[1-11]
RUN Ib > CURRENT SET Do Not Operate, Operate
From Autoreclose
TOC Pickup Raise SETPOINT
PTOC I>[X] Start A
From Manual Close Blocking I>[X] CURRENT SET :
AND
Disable RUN
VCO
VRO
Calculate VCO/VRO
Multiplier
Phase Voltages
Phase A Voltage (Va)
Phase B Voltage (Vb)
Phase C Voltage (Vc)
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
1601-0320 337
Chapter 8 - Protection
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
SIGNAL INPUT
Range: Dependent upon the order code
Default: CT Bank 1-J1 (dependent on order code)
This setting provides the selection for the current input bank. The default bank names can be changed in:
Setpoints > System > Current Sensing > [Name] > CT Bank Name.
INPUT
Default: Phasor (Up to firmware version 3.x)
Default: Phasor (RMS when VFD Function = enabled) (From firmware version 4)
PICKUP
Range (3.xx): 0.020 to 30.000 x CT in steps of 0.001 x CT
Range (4.10): 0.010 to 30.000 x CT in steps of 0.001 x CT
Default: 1.000 x CT
DIRECTION
Range: Disabled, Forward (Ph Dir OCx FWD), Reverse (Ph Dir OCx REV)
Default: Disabled
PICKUP DELAY
Range (3.xx): 0.000 to 6000.000 s in steps of 0.001 s
Range (4.10): 0.000 to 28800.000 s in steps of 0.001 s
Default: 0.000 s
DROPOUT DELAY
Range (3.xx): 0.000 to 6000.000 s in steps of 0.001 s
Range (4.10): 0.000 to 28800.000 s in steps of 0.001 s
Default: 0.000 s
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
338 1601-0320
Chapter 8 - Protection
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Self-reset
FLEXLOGIC OPERAND
Any Trip
LED: TRIP 8S: To operate Output Relay
AND
1(TRIP)
Configurable in 845 & 859
OR
S
AND
SETPOINT LATCH
FUNCTION: R
LED: ALARM
AND
Disabled
FLEXLOGIC OPERAND
Trip
OR
Any Alarm
Latched Trip
AND
S
OR
Alarm
Latched Alarm LATCH SETPOINT
Configurable Command R Output Relay X
RESET Do Not Operate, Operate
FLEXLOGIC OPERAND
SETPOINTS
OR
Phase IOC 1 OP
DIRECTION:
Disabled
SETPOINTS
Forward
AND
Reverse PICKUP:
AND
OR
RUN
SETPOINTS
AND
DROPOUT DELAY:
Ph B Reverse (from Phase Same Logic as for Phase A
Directional OC element)
tPKP
AND
RUN tRST
Ph C Reverse (from Phase
Same Logic as for Phase A
Directional OC element) tPKP
OR
Ib > PICKUP
tRST
SETPOINTS tPKP
BLOCK tRST
AND
1601-0320 339
Chapter 8 - Protection
The element is intended to send a directional signal to an overcurrent element to prevent an operation when current
is flowing in a particular direction. The direction of current flow is determined by measuring the phase angle
between the current from the phase CTs and the line-line voltage from the VTs, based on the 90° or quadrature
connection. To increase security for three phase faults very close to the VTs used to measure the polarizing voltage,
a voltage memory feature is incorporated. This feature remembers the measurement of the polarizing voltage 3
cycles back and uses it to determine direction. The voltage memory remains valid for one second after the voltage
has collapsed.
The main component of the phase directional element is the phase angle comparator with two inputs: the operating
signal (phase current) and the polarizing signal (the line voltage, shifted in the leading direction by the characteristic
angle, ECA).
The following table shows the operating and polarizing signals used for phase directional control:
340 1601-0320
Chapter 8 - Protection
For 850D dual feeder applications, when the signal input is from CT Bank 1 – J1, VT Bank 1-J2 is used as the
polarizing voltage source. Similarly, when the signal input is from CT Bank 2 – K1, VT Bank 2 – K2 is used as the
polarizing voltage source.
Path: Setpoints > Protection > Group1(6) > Current > Phase Dir OC 1(X)
FUNCTION
Range: Disabled, Enabled
Default: Disabled
SIGNAL INPUT
Range: dependent upon the order code
Default: CT Bank 1-J1
This setting provides the selection for the current input bank. The default bank names can be changed in:
Setpoints > System > Current Sensing > [Name] > CT Bank Name.
ECA
Range: 0° to 359° in steps of 1°
Default: 30°
The setting is used to select the element characteristic angle, i.e. the angle by which the polarizing voltage is
shifted in the leading direction to achieve dependable operation.
POLARIZING V THRESHOLD
Range (3.xx): 0.050 to 3.000 x VT in steps of 0.001 x VT (up to FW 3.xx)
Range (4.10): 0.015 to 3.000 x VT in steps of 0.001 x VT (from FW 4.10)
Default: 0.700 x VT
The setting is used to establish the minimum level of voltage for which the phase angle measurement is reliable.
The setting is based on VT accuracy.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
EVENTS
Range: Enabled, Disabled
Default: Enabled
1601-0320 341
Chapter 8 - Protection
TARGETS
Range: Self-reset, Latched, Disabled
Default: Self-reset
Note:
The Phase Directional element responds to the forward load current. In the case of a following reverse fault, the element
needs some time – in the order of 8 ms – to change the directional signal. Some protection elements such as Instantaneous
Overcurrent may respond to reverse faults before the directional signal has changed. A coordination time of at least 10 ms
must therefore be added to all the instantaneous protection elements under the supervision of the Phase Directional element.
If current reversal is a concern, a longer delay – in the order of 20 ms – is needed.
342 1601-0320
Chapter 8 - Protection
}
Jb } } }
Jb Jb Jb
Q% @ (
K S Q% Q% Q%
| K| S
K S K| S
y |
{M ! ] M ! ] ! ] M
Mz xX
x~ ^!
& { y x~ ^!
& M{ y
x~ ^!
& { y
! Mz ! Mz ! Mz
Y ! xX Y ! xX Y ! xX
HI
HI
EFG
-.8 75-
, /0
;: 645
0-.
9
231
0./
-,
?> =,<
@
% <
EFG
hei
b d
a
cb
a ghe
a fe
d
EFG
) l l
U
n n
%OS ^_ ^_ m m
^ ^ l l
DC Q & & k k
$B ^ ^Q _^ j j
$ \ Q `
# Q ^
& q q
A [
S@ QA+ + ^ w w
^ Q v v
)
X R] ^! #A l l
Q Q Q ps ps
us us
m m
ts ts
r r
q q
p p
X
o t
)@ n n
m m
l l
\O k k
j j
( X
@ %W
MLJ
#P %V
!O RQ V
N Q
$ ' JML (
%
#" U
! "#! *
$
K @ T
J
&%
) +# P#! R %QS Y
( O Q Z!
1601-0320 343
Chapter 8 - Protection
FUNCTION
Range: Disabled, Trip, Latched Trip, Alarm, Latched Alarm, Configurable
Default: Disabled
SIGNAL INPUT
Range: dependent upon the order code
Default: CT Bank 1-J1
This setting provides the selection for the current input bank. The default bank names can be changed in:
Setpoints > System > Current Sensing > [Name] > CT Bank Name.
INPUT
Range: Phasor, RMS
Default: Phasor
This selection defines the method of processing of the current signal. It could be Root Mean Square (RMS) or
Fundamental Phasor Magnitude.
PICKUP
Range: 0.010 to 30.000 x CT in steps of 0.001 x CT
Default: 0.200 x CT
CURVE
Range: Range: Definite Time, IEC Curve A, IEC Curve B, IEC Curve C, IEC Short Inverse ,Long Time Inverse,
Rectifier, SI(1.3s), BPN EDF, IEEE Mod Inverse, IEEE Very Inverse, IEEE Extr. Inverse, US Inverse, US ST
Inverse, ANSI Extr. Inverse, ANSI Very Inverse, ANSI Norm Inverse, ANSI Mod Inverse, IAC Extr. Inverse, IAC
Very Inverse, IAC Inverse, IAC Short Inverse, I2t, I4t, Rapid Inverse, IDG, EPATR B, FlexCurve A, FlexCurve B,
FlexCurve C, FlexCurve D.
Default: IEEE Mod Inverse
This setting sets the shape of the selected over-current inverse curve. If none of the standard curve shapes is
appropriate, a FlexCurve can be created. Refer to the User curve and the FlexCurve setup for more details on
their configurations and usage.
344 1601-0320
Chapter 8 - Protection
TDM
Range: 0.01 to 600.00 in steps of 0.01
Default: 1.00
This is the Time Multiplier Setting to adjust the operate time of IEC Curve A/B/C, IEEE M/V/E Inverse, US
Inverse, US Short Time, ANSI E/V/N/M Inverse, IAC E/V/N/S Inverse, I2T and I4T curves.
TMS
Range: 0.025 to 1.200 in steps of 0.005
Default: 1.000
This is the Time Multiplier Setting to adjust the operate time of IEC Short Inverse, Long Time Inverse, Rectifier,
Standard Inverse SI(1.3s), BPN EDF and EPATR B curves.
K (RI)
Range: 0.10 to 10.00 Step: 0.05
Default: 1.00
This setting defines the Time multiplier constant to adjust the operate time of the Rapid Inverse (RI) curve.
This setting can be made visible from setting management, only when Curve setting is selected as Rapid
Inverse.
IDG Is
Range: 1.0 to 4.0 in steps of 0.1
Default: 1.5
This setting is set as a multiple of the ground fault overcurrent setting for the IDG curve.
It determines the actual current threshold at which the element starts.
This setting can be made visible from setting management, only when the Curve setting is selected as IDG.
IDG Time
Range: 1.00 to 2.00 s in steps of 0.01 s
Default: 1.20
This setting sets the minimum operate time at high levels of fault current for IDG curves.
This setting can be made visible from setting management, only when the Curve setting is selected as IDG.
Time Delay
Range: 0.000 s to 200.000 s in steps of 0.001 s
Default: 1.000
This setting defines the time delay for operation.
This setting can be made visible from setting management, only when the Curve setting is selected as DT
(Definite Time).
1601-0320 345
Chapter 8 - Protection
DT Adder
Range: 0.00 to 100.00 s in steps of 0.01 s
Default: 0.00
This setting adds an additional fixed time delay to the IDMT Operate characteristic.
This setting will be visible for when any IDMT curves are selected under the Curve setting.
RESET
Range: DT, Inverse
Default: DT
This setting sets a Definite Time (DT) or Inverse reset time.
If Definite Time (DT) reset is selected, the Neutral TOC element will reset after a time delay provided by the
Reset Time setting. If Inverse reset is selected, the time to reset is calculated based on the reset equation for
the selected inverse curve.
When using Long Time Inverse, BPN EDF, Rectifier, IEC Short Inverse, Rapid Inverse, IDG, EPATR B curves the
reset is always definite time defined by the setpoint Reset Time.
Reset Time
Range: 0.000 to 100.000 s in stepos of 0.001 s
Default: 0.000s
This setting determines the Reset time for the Definite Time Reset characteristic.
This can be made visible from setting management when the Reset setting is selected as DT or when using
Long Time Inverse, IEC Short Inverse, BPN EDF, Rectifier, IDG, EPATR B and Rapid Inverse curves.
DIRECTION
Range: Disabled, Forward (Ntrl Dir OCx FWD), Reverse (Ntrl Dir OCx REV)
Default: Disabled
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
346 1601-0320
8.2.2.6
formula:
1601-0320
Default: Self-reset
FLEXLOGIC OPERAND
Any Trip
SETPOINT
LED: TRIP 8S: To operate Output Relay
FUNCTION:
AND
1(TRIP)
Disabled Configurable in 845 & 859
OR
Trip
Latched Trip S
AND
Alarm
LATCH
OR
Latched Alarm
R
LED: ALARM
Configurable
AND
FLEXLOGIC OPERAND
OR
PICKUP: S
AND
LATCH SETPOINT
CURVE:
Command R Output Relay X
RESET Do Not Operate, Operate
TDM:
FLEXLOGIC OPERAND
RESET: Ntrl TOC 1 OP
OR
SETPOINTS DIRECTION:
AND
Off = 0
From Autoreclose
(per shot settings)
347
Chapter 8 - Protection
Chapter 8 - Protection
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
SIGNAL INPUT
Range: dependent upon the order code
Default: CT Bank 1-J1
This setting provides the selection for the current input bank. The default bank names can be changed in:
Setpoints > System > Current Sensing > [Name] > CT Bank Name.
PICKUP
Range (up to FW 3.xx): 0.050 to 30.000 x CT in steps of 0.001 x CT
Range (from FW 4.10): 0.010 to 30.000 x CT in steps of 0.001 x CT
Default (up to FW 3.xx): 1.00 x CT
Default (from FW 4.10): 0.20 x CT
DIRECTION
Range: Disabled, Forward (Ntrl Dir OCx FWD), Reverse (Ntrl Dir OCx REV)
348 1601-0320
Chapter 8 - Protection
Default: Disabled
PICKUP DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.000 s
DROPOUT DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.000 s
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Self-reset
1601-0320 349
Chapter 8 - Protection
FLEXLOGIC OPERAND
Any Trip
SETPOINT
LED: TRIP 8S: To operate Output Relay
AND
FUNCTION:
1(TRIP)
Disabled Configurable in 845 & 859
OR
Trip
S
AND
Latched Trip
LATCH
OR
Alarm
Latched Alarm
R
LED: ALARM
AND
Configurable
FLEXLOGIC OPERAND
OR
Any Alarm
AND
S
LATCH SETPOINT
Command R Output Relay X
ACTUAL VALUE
RESET Do Not Operate, Operate
SETPOINTS NEUTRAL IOC1 Iop FLEXLOGIC OPERAND
OR
PICKUP: Ntrl IOC1 OP
SETPOINTS
DIRECTION:
SETPOINTS PICKUP DELAY:
AND
RUN
BLOCK:
DROPOUT DELAY:
Off = 0 Iop = 3 * (|I_0| - K * |I_1|)
From Autoreclose
(per shot settings) LED: PICKUP
SETPOINTS
SIGNAL INPUT
Neutral IOC source
Note:
For FW 4.10 onwards, V_X (or VX), is know as V_N (or VN)
The Neutral Directional Overcurrent protection element provides both forward and reverse fault direction indications
shown by the operands Ntrl Dir OC FWD and Ntrl Dir OC REV, respectively. The output operands are asserted if the
magnitude of the operating current is above a Pickup level (overcurrent unit) and the fault direction is seen as
forward or reverse, respectively (directional unit).
The overcurrent unit responds to the magnitude of a fundamental frequency phasor of the neutral current calculated
from the phase currents. There are separate Pickup settings for the forward-looking and reverse-looking functions.
The element applies a positive-sequence restraint for better performance; a small user-programmable portion of the
positive-sequence current magnitude is subtracted from the zero sequence current magnitude when forming the
operating quantity.
Iop = 3 * (|I_0| - K * |I_1|)
The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence
currents resulting from:
● system unbalances under heavy load conditions
● current transformer (CT) transformation errors of during double-line and three-phase faults
● switch-off transients during double-line and three-phase faults.
350 1601-0320
Chapter 8 - Protection
The positive-sequence restraint must be considered when testing for Pickup accuracy and response time (multiple
of Pickup). The operating quantity depends on the way the test currents are injected into the relay (single-phase
injection: Iop = (1 – K) × Iinjected ; three-phase pure zero-sequence injection: Iop = 3 × Iinjected).
The positive-sequence restraint is removed for low currents. If the positive-sequence current is below 0.8 x CT, the
restraint is removed by changing the constant K to zero. This facilitates better response to high-resistance faults
when the unbalance is very small and there is no danger of excessive CT errors as the current is low.
The directional unit uses the zero-sequence current (I_0) for fault direction discrimination and may be configured to
use either zero-sequence voltage (Calculated V0 or Measured VX (known as VN for FW4.10 onwards)),
ground current (Ig), or both for polarizing. The following table defines the neutral directional overcurrent element.
Directional unit Overcurrent unit
Polarizing mode Direction Compared phasors
Voltage Forward -V_0 1_0 x 1ÐECA Iop = 3 x {|I_0| - K x |
I_1|}
Reverse -V_0 -1_0 x 1ÐECA
Current Forward Ig I_0
Reverse Ig -I_0 If |I_1| > 0.8 x CT
Dual Forward -V_0 or I_0 x 1ÐECA or
Iop = 3 x {|I_0|}
Ig I_0
if |I_1| £0.8 x CT
Reverse -V_0 or -I_0 x 1ÐECA or
Ig -I_0
Where:
● V_0 = 1/3 * (Vag + Vbg + Vcg) = zero sequence voltage
● I_0 = 1/3 * In = 1/3 * (Ia + Ib + Ic) = zero sequence current
● ECA = element characteristic angle
● In = neutral current
When POLARIZING VOLTAGE is set to Measured VX, one-third of this voltage is used in place of V0.
The following figure explains the use of the voltage polarized directional unit of the element by showing the voltage-
polarized phase angle comparator characteristics for a phase A to ground fault, with:
● ECA = 90° (element characteristic angle = centerline of operating characteristic)
● FWD LA = 80° (forward limit angle = the ± angular limit with the ECA for operation
● REV LA = 80° (reverse limit angle = the ± angular limit with the ECA for operation).
The element incorporates a current reversal logic: if the reverse direction is indicated for at least 1.25 of a power
system cycle, the prospective forward indication will be delayed by 1.5 of a power system cycle. The element is
designed to emulate an electromechanical directional device. Larger operating and polarizing signals will result in
faster directional discrimination bringing more security to element operation.
The forward-looking function is designed to be more secure as compared to the reverse-looking function, and
should therefore be used for the tripping direction. The reverse-looking function is designed to be faster as
compared to the forward-looking function and should be used for the blocking direction. This allows better protection
coordination.
The above bias should be taken into account when using the Neutral Directional Overcurrent element to
directionalize other protection elements.
1601-0320 351
Chapter 8 - Protection
Note:
For relays ordered without voltage inputs, the polarizing signal for the Neutral Directional OC element is the ground current
(Ig) from the bank selected as Signal Input in the element’s menu. In this case the setpoints POLARIZING MODE, and
POLARIZING VOLTAGE are not displayed.
-V
REV L F L
V G
(
L L
E
E
-E
- L
VG L
VG
REV L F L
V
8 8
Note:
For 850 Dual Feeder Applications: For Signal Input of CT Bank 1 – J1 >> VT Bank 1 -J2 is considered as Polarizing voltage
source. And, For CT Bank 2 – K1 >> VT Bank 2 – K2 is considered as Polarizing Voltage Source
Path: Setpoints > Protection > Group 1(6) > Current > Neutral Directional OC 1(X)
352 1601-0320
Chapter 8 - Protection
FUNCTION
Range: Disabled, Enabled
Default: Disabled
SIGNAL INPUT
Range: dependent upon the order code
Default: CT Bank 1-J1
This setting provides selection of the current input bank. The default bank names can be changed in Setpoints
> System > Current Sensing > [Name] > CT Bank Name.
POLARIZING MODE
Range: Voltage, Current, Dual
Default: Voltage
This setting selects the polarizing mode for the directional unit.
If Voltage
○ polarizing mode is selected, the element uses the zero-sequence voltage angle for polarization.
Select either the zero-sequence voltage V0, calculated from the phase voltages, or the zero-sequence
voltage supplied externally as the auxiliary voltage V_X. The calculated V0 can be used as polarizing voltage
only if the voltage transformers are connected in Wye. The auxiliary voltage can be used as the polarizing
voltage if the auxiliary voltage is connected to a zero-sequence voltage source (such as the open delta
connected secondary of VTs). The zero-sequence (V0) or auxiliary voltage (V_X), accordingly, must be
greater than 0.02 x VT to be validated for use as a polarizing signal. If the polarizing signal is invalid, neither
forward nor reverse indication is given.
If Current
○ polarizing mode is selected, the element uses the angle of the ground current measured on the
ground current input. The ground CT must be connected between the ground and neutral point of an
adequate source of ground current. The ground current must be greater than 0.05 x CT to be validated as a
polarizing signal. If the polarizing signal is not valid, neither forward nor reverse indication is given. For a
choice of current polarizing, it is recommended that the polarizing signal be analyzed to ensure that a known
direction is maintained irrespective of the fault location. For example, if using an autotransformer neutral
current as a polarizing source, it should be ensured that a reversal of the ground current does not occur for a
high-side fault. The low-side system impedance should be assumed minimal when checking for this
condition. A similar situation arises for a wye/delta/wye transformer, where current in one transformer winding
neutral may reverse when faults on both sides of the transformer are considered.
If Dual
○ polarizing mode is selected, the element performs both directional comparisons as described above.
A given direction is confirmed if either voltage or current comparators indicate so. If a conflicting
(simultaneous forward and reverse) indication occurs, the forward direction overrides the reverse direction.
POLARIZING VOLTAGE
Range: Calculated V0, Measured VX (or VN for FW 4.10 onwards)
Default: Calculated V0
Selects the polarizing voltage used by the directional unit when Voltage or Dual polarizing mode is set. The
polarizing voltage can be programmed to be either the zero-sequence voltage calculated from the phase
voltages (Calculated V0) or supplied externally as an auxiliary voltage (Measured VX (or VN))
1601-0320 353
Chapter 8 - Protection
FORWARD ECA
Range: –180° to 180° in steps of 1°
Default: 75°
This setting defines the element characteristic angle (ECA) for the forward direction in “Voltage” polarizing mode.
“Current” polarizing mode uses a fixed ECA of 0°. The ECA in the reverse direction is the angle set for the
forward direction shifted by 180°.
FORWARD PICKUP
Range (3.xx): 0.050 to 30.000 x CT in steps of 0.001 x CT
Range (4.10): 0.010 to 30.000 x CT in steps of 0.001 x CT
Default: 0.050 x CT
This setting defines the Pickup level for the overcurrent unit of the element in the forward direction. When
selecting this setting it must be kept in mind that the design uses a ‘positive-sequence restraint’ technique for the
Calculated 3I0 mode of operation.
REVERSE PICKUP
Range (3.xx): 0.050 to 30.000 x CT in steps of 0.001 x CT
Range (4.10): 0.010 to 30.000 x CT in steps of 0.001 x CT
Default: 0.050 x CT
354 1601-0320
Chapter 8 - Protection
This setting defines the Pickup level for the overcurrent unit of the element in the reverse direction. When
selecting this setting it must be kept in mind that the design uses a ‘positive-sequence restraint’ technique for the
Calculated 3I0 mode of operation.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Self-reset
7+ (# (.,
!"#
* !".
1601-0320 355
Chapter 8 - Protection
FUNCTION
Range: Disabled, Trip, Latched Trip, Alarm, Latched Alarm, Configurable
Default: Disabled
SIGNAL INPUT
Range: Dependent upon the order code
Default: CT Bank 1-J1
This setting provides the selection for the current input bank. The default bank names can be changed in
Setpoints > System > Current Sensing > [Name] > CT Bank Name.
The Signal Input setting is visible only in the 845 and 889. For other products, it is hidden.
INPUT
Range: Phasor, RMS
Default: Phasor
This selection defines the method of processing of the current signal. It could be Root Mean Square (RMS) or
Fundamental Phasor Magnitude.
PICKUP
Range: 0.010 to 30.000 x CT in steps of 0.001 x CT
Default: 0.200 x CT
CURVE
Range: Range: Definite Time, IEC Curve A, IEC Curve B, IEC Curve C, IEC Short Inverse ,Long Time Inverse,
Rectifier, SI(1.3s), BPN EDF, IEEE Mod Inverse, IEEE Very Inverse, IEEE Extr. Inverse, US Inverse, US ST
Inverse, ANSI Extr. Inverse, ANSI Very Inverse, ANSI Norm Inverse, ANSI Mod Inverse, IAC Extr. Inverse, IAC
Very Inverse, IAC Inverse, IAC Short Inverse, I2t, I4t, Rapid Inverse, IDG, EPATR B, FlexCurve A, FlexCurve B,
FlexCurve C, FlexCurve D.
Default: IEEE, Moderately Inverse
TDM
Range: 0.05 to 600.00 in steps of 0.01
Default: 1.00
This is the Time Multiplier Setting to adjust the operate time of IEC Curve A/B/C, IEEE M/V/E Inverse, US
Inverse, US Short Time, ANSI E/V/N/M Inverse, IAC E/V/N/S Inverse, I2T and I4T curves.
356 1601-0320
Chapter 8 - Protection
TMS
Range: 0.025 to 1.200 in steps of 0.005
Default: 1.000
This is the Time Multiplier Setting to adjust the operate time of IEC Short Inverse, Long Time Inverse, Rectifier,
Standard Inverse SI(1.3s), BPN EDF and EPATR B curves.
K (RI)
Range: 0.10 to 10.00 Step: 0.05
Default: 1.00
This setting defines the Time multiplier constant to adjust the operate time of the Rapid Inverse (RI) curve.
This setting can be made visible from setting management, only when Curve setting is selected as Rapid
Inverse.
IDG Is
Range: 1.0 to 4.0 in steps of 0.1
Default: 1.5
This setting is set as a multiple of the ground fault overcurrent setting for the IDG curve.
It determines the actual current threshold at which the element starts.
This setting can be made visible from setting management, only when the Curve setting is selected as IDG.
IDG TIME
Range: 1.00 to 2.00 s in steps of 0.01 s
Default: 1.20
This setting sets the minimum operate time at high levels of fault current for IDG curves.
This setting can be made visible from setting management, only when the Curve setting is selected as IDG.
TIME DELAY
Range: 0.000 s to 1200.000 s in steps of 0.001 s
Default: 1.000
This setting defines the time delay for operation.
This setting can be made visible from setting management, only when the Curve setting is selected as DT
(Definite Time).
DT ADDER
Range: 0.00 to 100.00 s in steps of 0.01 s
Default: 0.00
This setting adds an additional fixed time delay to the IDMT Operate characteristic.
This setting will be visible for when any IDMT curves are selected under the Curve setting.
1601-0320 357
Chapter 8 - Protection
RESET
Range: DT, Inverse
Default: DT
This setting sets a Definite Time (DT) or Inverse reset time.
If Definite Time (DT) reset is selected, the Neutral TOC element will reset after a time delay provided by the
Reset Time setting. If Inverse reset is selected, the time to reset is calculated based on the reset equation for
the selected inverse curve.
When using Long Time Inverse, BPN EDF, Rectifier, IEC Short Inverse, Rapid Inverse, IDG, EPATR B curves the
reset is always definite time defined by the setpoint Reset Time.
RESET TIME
Range: 0.000 to 100.000 s in stepos of 0.001 s
Default: 0.000s
This setting determines the Reset time for the Definite Time Reset characteristic.
This can be made visible from setting management when the Reset setting is selected as DT or when using
Long Time Inverse, IEC Short Inverse, BPN EDF, Rectifier, IDG, EPATR B and Rapid Inverse curves.
DIRECTION
Range: Disabled, Forward, Reverse
Default: Disabled
BLOCK
Range: Off, Any FlexLogic operand
Default: Off or PB 4 OFF (GND TRIP ENABLED), Dependent on order code
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Self-reset
358 1601-0320
8.2.2.9
1601-0320
LED:
In 845 & 859, operate the selected Trip
TRIP
SETPOINT Output Relay
AND
FUNCTION: Operate Output Relay 1 (TRIP)
OR
Disabled
S FLEXLOGIC OPERAND
Trip
AND
LATCH Any Trip
Latched Trip
R LED:
Alarm
OR
ALARM
Latched Alarm
AND
FLEXLOGIC OPERAND
Configurable
OR
Any Alarm
SETPOINTS S
AND
SETPOINTS DIRECTION:
AND
Off = 0
LED: PICKUP
SETPOINTS Adjust PKP
From Autoreclose
(per shot settings)
above the pickup value. The Ground IOC Operate flag is asserted if the element stays picked-up for the time
defined by the Ground IOC PICKUP DELAY setting. If the The Pickup time delay is set to 0.000 seconds. The
The settings of the Ground Instantaneous Overcurrent protection element are applied to the measured Ground
current for producing Pickup and Trip flags. The Ground IOC Pickup flag is asserted when the Ground current is
359
Chapter 8 - Protection
Chapter 8 - Protection
Pickup and Operate flags will be asserted at the same time. The element drops from Pickup without operation if the
Ground current drops below 97 to 98% of the Pickup value.
Path: Setpoints > Protection > Group 1(6) > Current > Ground IOC 1(X)
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
SIGNAL INPUT
Range: dependent upon the order code
Default: CT Bank 1-J1
This setting provides the selection for the current input bank. The default bank names can be changed in
Setpoints > System > Current Sensing > [Name] > CT Bank Name.
PICKUP
Range (up to FW 3.xx): 0.050 to 30.000 x CT in steps of 0.001 x CT
Range (from FW 4.10): 0.010 to 30.000 x CT in steps of 0.001 x CT
Default (up to FW 3.xx): 1.00 x CT
Default (from FW 4.10): 0.200 x CT
DIRECTION
Range: Disabled, Forward, Reverse
Default: Disabled
PICKUP DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.000 s
DROPOUT DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.000 s
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
360 1601-0320
Chapter 8 - Protection
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Self-reset
LED: TRIP
AND
SETPOINT
FLEXLOGIC OPERAND
FUNCTION:
OR
Any Trip
Disabled
S
AND
Trip
LATCH
Latched Trip
R
OR
Alarm
LED: ALARM
AND
Latched Alarm
FLEXLOGIC OPERAND
Configurable
OR
Any Alarm
AND
S
Direction (from Ground Directional LATCH SETPOINT
OC element) SETPOINTS
Command R Output Relay X
PICKUP: SETPOINTS RESET Do Not Operate, Operate
PICKUP DELAY:
FLEXLOGIC OPERAND
SETPOINTS DIRECTION:
OR
Ground IOC1 OP
BLOCK:
AND
From Autoreclose
(per shot settings)
LED: PICKUP
From Manual Close Blocking
FLEXLOGIC OPERANDS
USED ONLY IN 850 Ground IOC1 PKP
SETPOINTS
1601-0320 361
Chapter 8 - Protection
Directional Unit
Overcurrent unit
Polarizing mode Direction Compared phasors
Dual Forward Ipol Ig GROUND CURRENT (Ig)
Dual Reverse -V0 -Ig GROUND CURRENT (Ig)
Dual Reverse Ipol -Ig GROUND CURRENT (Ig)
Where:
V0 = 1/3 * (Vag + Vbg + Vcg) = zero sequence voltage
When POLARIZING VOLTAGE is set to Measured VX, one-third of this voltage is used in place of V0. The
following figure explains the usage of the voltage polarized directional unit of the element by showing the voltage-
polarized phase angle comparator characteristics for a phase A to ground fault, with:
● ECA = 90° (element characteristic angle = centerline of operating characteristic)
● FWD LA = 80° (forward limit angle = the ± angular limit with the ECA for operation)
● REV LA = 80° (reverse limit angle = the ± angular limit with the ECA for operation).
The element incorporates a current reversal logic: if the reverse direction is indicated for at least 1.25 of a power
system cycle, the prospective forward indication will be delayed by 1.5 of a power system cycle. The element is
designed to emulate an electromechanical directional device. Larger operating and polarizing signals will result in
faster directional discrimination bringing more security to element operation.
The forward-looking function is designed to be more secure as compared to the reverse-looking function, and
should therefore be used for the tripping direction. The reverse-looking function is designed to be faster as
compared to the forward-looking function and should be used for the blocking direction. This allows better protection
coordination.
The above bias should be taken into account when using the Ground Directional Overcurrent element to
directionalize other protection elements.
For Dual Feeder Applications, for Signal Input of CT Bank 1 – J1 >> VT Bank 1 -J2 is considered as Polarizing
voltage source. And, For CT Bank 2 – K1 >> VT Bank 2 – K2 is considered as Polarizing Voltage Source.
362 1601-0320
Chapter 8 - Protection
-V
REV L F L
V G
(
L L
E
E
-E
- L
VG L
VG
REV L F L
V
8 8
Path: Setpoints > Protection > Group 1(6) > Current > Ground Directional OC 1(X)
FUNCTION
Range: Disabled, Enabled
Default: Disabled
SIGNAL INPUT
Range: dependent upon the order code
Default: CT Bank 1-J1
This setting provides the selection for the current input bank. The default bank names can be changed in:
Setpoints > System > Current Sensing > [Name] > CT Bank Name.
The signal Input setting is visible only in the 845 and 889. For other products, it is hidden.
1601-0320 363
Chapter 8 - Protection
POLARIZING MODE
Range: Voltage, Current, Dual
Default: Voltage
This setting selects the polarizing mode for the directional unit.
If Voltage
○ polarizing mode is selected, the element uses the zero-sequence voltage angle for polarization.
Select either the zero-sequence voltage V0, calculated from the phase voltages, or the zero-sequence
voltage supplied externally as the auxiliary voltage V_X. The calculated V0 can be used as polarizing voltage
only if the voltage transformers are connected in Wye. The auxiliary voltage can be used as the polarizing
voltage if the auxiliary voltage is connected to a zero-sequence voltage source (such as the open delta
connected secondary of VTs). The zero-sequence (V0) or auxiliary voltage (Vx), accordingly, must be greater
than the voltage set under Polarizing Volt Supv to be validated for use as a polarizing signal. If the
polarizing signal is invalid, neither forward nor reverse indication is given.
If Current
○ polarizing mode is selected, the element uses the angle of the polarizing current measured on the
ground current input K1-CT (if available). The polarizing current must be greater than 0.05 x CT to be
validated as a polarizing signal. If the polarizing signal is not valid, neither forward nor reverse indication is
given. For a choice of current polarizing, it is recommended that the polarizing signal be analyzed to ensure
that a known direction is maintained irrespective of the fault location.
If Dual
○ polarizing mode is selected, the element performs both directional comparisons as described above. A
given direction is confirmed if either voltage or current comparators indicate so. If a conflicting (simultaneous
forward and reverse) indication occurs, the forward direction overrides the reverse direction.
POLARIZING VOLTAGE
Range: Calculated V0, Measured VX(VN)
Default: Calculated V0
Selects the polarizing voltage used by the directional unit when "Voltage" or "Dual" polarizing mode is set. The
polarizing voltage can be programmed to be either the zero-sequence voltage calculated from the phase
voltages ("Calculated V0") or supplied externally as an auxiliary voltage ("Measured VX")
Default: 0.020 x VT
The zero-sequence (V0) or auxiliary voltage (Vx), accordingly, must be greater than the Polarizing supervision
voltage configured in this setting, to be validated for use as a polarizing signal. If the polarizing signal is invalid,
neither forward nor reverse indication is given.
FORWARD ECA
Range: –180° to 180° in steps of 1°
Default: 75°
This setting defines the element characteristic angle (ECA) for the forward direction in "Voltage" polarizing mode.
"Current" polarizing mode uses a fixed ECA of 0°. The ECA in the reverse direction is the angle set for the
forward direction shifted by 180°.
364 1601-0320
Chapter 8 - Protection
FORWARD PICKUP
Range: 0.050 to 30.000 x CT in steps of 0.001 x CT
Default: 0.050 x CT
This setting defines the Pickup level for the overcurrent unit of the element in the forward direction.
REVERSE PICKUP
Range (3.xx): 0.050 to 30.000 x CT in steps of 0.001 x CT
Range (4.10): 0.010 to 30.000 x CT in steps of 0.001 x CT
Default: 0.050 x CT
This setting defines the Pickup level for the overcurrent unit of the element in the reverse direction.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Self-reset
1601-0320 365
Chapter 8 - Protection
operation is reached. When Definite Time is selected, the time for Sensitive Ground TOC operation is defined only
by the TDM setting.
Path: Setpoints > Protection > Group 1(6) > Current > Sensitive Ground TOC 1(X)
FUNCTION
Range: Disabled, Trip, Latched Trip, Alarm, Latched Alarm, Configurable
Default: Disabled
INPUT
Range: Phasor, RMS
Default: Phasor
This selection defines the method of processing of the current signal. It can be Root Mean Square (RMS) or
Fundamental Phasor Magnitude.
PICKUP
Range: 0.002 to 3.000 x CT in steps of 0.001 x CT
Default: 1.000 x CT
The 50:0.025 Ground input (K1-Ig) range is as follows:
Range: 0.50 to 15.00 A in steps of 0.01 A
Default: 10.00 A
This setting sets the sensitive ground overcurrent pickup level specified as a multiplier of the nominal CT current.
For example, a PKP setting of 0.9 x CT with 300:5 CT translates into 270A primary current.
In the case of 50:0.025 Ground input (K1-Ig as current input), the pickup level is specified as Ampere in primary.
For example, with a PKP setting of 10.00 A, when ground current (primary) is 10.00A, the K1-Ig will measure
10.000 A, and this function should pick up.
CURVE
Range: Definite Time, IEC Curve A, IEC Curve B, IEC Curve C, IEC Short Inverse, Long Time Inverse,
Rectifier,SI(1.3s), BPN EDF, IEEE Mod Inverse, IEEE Very Inverse, IEEE Extr. Inverse, US Inverse, US ST
Inverse, ANSI Extr. Inverse, ANSI Very Inverse, ANSI Norm Inverse, ANSI Mod Inverse, IAC Extr. Inverse, IAC
Very Inverse, IAC Inverse, IAC Short Inverse, I2t, I4t, Rapid Inverse, IDG, EPATR B, FlexCurve A, FlexCurve B,
FlexCurve C, FlexCurve D.
Default: IEEE Mod Inverse
This setting sets the shape of the selected over-current inverse curve. If none of the standard curve shapes is
appropriate, a FlexCurve can be created. Refer to the User curve and the FlexCurve setup for more details on
their configurations and usage.
TDM
Range: 0.01 to 600.00 in steps of 0.01
Default: 1.00
This setting provides the selection for the Time Dial Multiplier by which the times from the inverse curve are
modified. For example if an ANSI Extremely Inverse curve is selected with TDM = 2, and the fault current is 5
366 1601-0320
Chapter 8 - Protection
times bigger than the PKP level, the operation of the element will occur but not before 2.59s of time has elapsed
from pickup.
TMS
Range: 0.025 to 1.200 in steps of 0.005
Default: 1.00
This is the Time Multiplier Setting to adjust the operate time of IEC Short Inverse, Long Time Inverse, Rectifier,
Standard Inverse SI(1.3s), BPN EDF and EPATR B curves.
K (RI)
Range: 0.10 to 10.00 in steps of 0.05
Default: 1.00
This setting defines the Time multiplier constant to adjust the operate time of the Rapid Inverse (RI) curve.
This k(RI) setting can be made visible from setting management, only when the Curve setting is selected as
Rapid Inverse.
IDG Is
Range: 1.0 to 4.0 in steps of 0.1
Default: 1.5
This setting is set as a multiple of the Ground Fault overcurrent setting IDG Is for the IDG curve.
It determines the actual current threshold at which the element starts.
IDG TIME
Range: 1.00 to 2.00 s in steps of 0.01 s
Default: 1.20
This setting sets the minimum operate time at high levels of fault current for IDG curves.
IDG Is and IDG Time settings can be made visible from setting management, only when the Curve setting is
selected as IDG.
TIME DELAY
Range: 0.000 s to 200.000 s in steps of 0.001 s
Default: 1.000
This setting defines the time delay for operation. This Time Delay setting can be made visible from setting
management, only when the Curve setting is selected as DT.
DT ADDER
Range: 0.00 to 100.00 s in steps of 0.01 s
Default: 0.00
This setting adds an additional fixed time delay to the IDMT Operate characteristic.The DT Adder setting will be
visible for when any IDMT curves are selected under the Curve setting.
1601-0320 367
Chapter 8 - Protection
RESET
Range: DT, Inverse
Default: DT
Selection of a Definite Time (DT) or Inverse reset time is provided using this setting.
If Definite Time (DT) reset is selected, the Phase TOC element will reset after a time delay provided by the
Reset Time setting. If Inverse reset is selected, the time to reset is calculated based on the reset equation for
the selected inverse curve.
Note: When using IEC Short Inverse, Long Time Inverse, BPN EDF, Rectifier, Rapid Inverse curves for the
Operate characteristic, Definite Time is used by default as Reset characteristic.
RESET TIME
Range: 0.000 to 100.000 in steps of 0.001
Default: 0.000
This setting provides selection for dropout time delay used to delay the dropout of the detection of the
overcurrent condition.
This can be made visible from setting management when the Reset setting is selected as DT or when using
Long Time Inverse, IEC Short Inverse, BPN EDF, Rectifier, IDG, EPATR B and Rapid Inverse curves.
DIRECTION
Range: Disabled, Forward, Reverse
Default: Disabled
This setting defines the operation direction of the Sensitive Ground TOC element. Entering the direction for the
Sensitive Ground TOC element does not automatically apply the selection. The direction detection is performed
by the element Sensitive Ground Directional OC, which must be enabled and configured according to the
directionality criteria of the feeder currents.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
The Sensitive Ground TOC is blocked, when the selected operand is asserted.
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Enabled, Disabled
Default: Enabled
This also sets the events of Sensitive Ground TOC function.
TARGETS
Range: Self-reset, Latched, Disabled
368 1601-0320
1601-0320
Default: Self-reset
FLEXLOGIC OPERAND
Any Trip
LED: TRIP
8S: To operate Output
AND
Relay 1(TRIP)
OR
S
AND
SETPOINT LATCH
FUNCTION: R
LED: ALARM
Disabled
AND
FLEXLOGIC OPERAND
Trip
SETPOINTS OR Any Alarm
Latched Trip
PICKUP: S
Alarm
OR
AND
Latched Alarm LATCH SETPOINT
CURVE:
Configurable Command R Output Relay X
Time Dail/TMS/Time Delay RESET Do Not Operate, Operate
FLEXLOGIC OPERAND
Direction (from Sens Ground Directional Reset Char
SGnd TOC 1 OP
OR
OC element)
RESET:
Bridge P14D only
SETPOINTS DIRECTION:
AND
Off = 0
SETPOINTS
Adjust PKP
INPUT:
From Sensitive Ground CT
LED: PICKUP
Sens Ground current (Isg)
Phasor, RMS FLEXLOGIC OPERANDS
Ig (From 50:0.025 CBCT) SGnd TOC 1 PKP
Input for 859
From Autoreclose
(per shot settings)
369
Chapter 8 - Protection
Chapter 8 - Protection
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
PICKUP
Range: 0.002 to 3.000 x CT in steps of 0.001 x CT
Default: 1.000 x CT
This setting sets the instantaneous Sensitive Ground overcurrent pickup level specified as a multiplier of the
nominal CT current for sensitive CT input. For example, a PKP setting of 0.9 x CT with 300:5 CT translates into
270A primary current.
DIRECTION
Range: Disabled, Forward, Reverse
Default: Disabled
This setting defines the operation direction of the Sensitive Ground time overcurrent element. Entering the
direction for the Sensitive Ground IOC element, does not automatically apply the selection. The direction
detection is performed by the element Sensitive Ground Directional OC, which must be enabled and configured
according to the directionality criteria of the feeder currents.
PICKUP DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.000 s
This setting provides the selection for the pickup time delay used to delay the operation of the protection.
DROPOUT DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.000 s
This setting provides the selection for the dropout time delay used to delay the dropout of the detection of the
overcurrent condition.
BLOCK
Range: Off, Any FlexLogic operand
370 1601-0320
Chapter 8 - Protection
Default: Off
The Sensitive Ground IOC is blocked, when the selected operand is asserted.
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Self-reset
1601-0320 371
372
8.2.2.13
Chapter 8 - Protection
FLEXLOGIC OPERAND
Any Trip
LED: TRIP
8S: To operate Output
AND
Relay 1(TRIP)
OR
AND S
SETPOINT LATCH
FUNCTION: R
LED: ALARM
Disabled
AND
FLEXLOGIC OPERAND
Trip
OR
Any Alarm
Latched Trip
Alarm S
OR
AND
PICKUP: SETPOINTS
AND
Off = 0
Isg > PICKUP tPKP
tRST
From Cold Load Pickup
are asserted if the magnitude of the operating current is above a Pickup level (overcurrent unit) and the fault
indications shown by the operands S.Gnd Dir OC FWD and S.Gnd Dir OC REV respectively. The output operands
The Sensitive Ground Directional Overcurrent protection element provides both forward and reverse fault direction
1601-0320
Chapter 8 - Protection
The overcurrent unit responds to the magnitude of a fundamental frequency phasor of the sensitive ground current.
There are separate Pickup settings for the forward-looking and reverse-looking functions.
The directional unit uses the sensitive ground current (Ig) for fault direction discrimination and may be programmed
to use either zero-sequence voltage (Calculated V0 or Measured VN), ground current (Ig), or both for
polarizing. The following tables define the Sensitive Ground Directional Overcurrent element.
Directional Unit
Overcurrent unit
Polarizing mode Direction Compared phasors
Voltage Forward -V0 Isg GROUND CURRENT (Isg)
Voltage Reverse -V0 -Isg GROUND CURRENT (Isg)
Current Forward Ipol Isg GROUND CURRENT (Isg)
Current Reverse Ipol -Isg GROUND CURRENT (Isg)
Dual Forward -V0 Isg GROUND CURRENT (Isg)
Dual Forward Ipol Isg GROUND CURRENT (Isg)
Dual Reverse -V0 -Isg GROUND CURRENT (Isg)
Dual Reverse Ipol -Isg GROUND CURRENT (Isg)
Where:
V_0 = 1/3 * (Vag + Vbg + Vcg) = zero sequence voltage
When POLARIZING VOLTAGE is set to “Measured VX,” one-third of this voltage is used in place of V_0. The
following figure explains the usage of the voltage polarized directional unit of the element by showing the voltage-
polarized phase angle comparator characteristics for a phase A to ground fault, with:
● ECA = 90° (element characteristic angle = centerline of operating characteristic)
● FWD LA = 80° (forward limit angle = the ± angular limit with the ECA for operation)
● REV LA = 80° (reverse limit angle = the ± angular limit with the ECA for operation)
The element incorporates a current reversal logic: if the reverse direction is indicated for at least 1.25 of a power
system cycle, the prospective forward indication will be delayed by 1.5 of a power system cycle. The element is
designed to emulate an electromechanical directional device. Larger operating and polarizing signals will result in
faster directional discrimination bringing more security to element operation.
The forward-looking function is designed to be more secure as compared to the reverse-looking function, and
should therefore be used for the tripping direction. The reverse-looking function is designed to be faster as
compared to the forward-looking function and should be used for the blocking direction. This allows better protection
coordination.
The above bias should be taken into account when using the Sensitive Ground Directional Overcurrent element to
directionalize other protection elements.
1601-0320 373
Chapter 8 - Protection
-V !
REV L F L
V G
(
L L
E
E
-E
- L
VG L
VG
REV L F L
V !
8 8
For 850D dual feeder applications, when the signal input is from CT Bank 1 – J1, VT Bank 1 -J2 is used as the
polarizing voltage source. Similarly, when the signal input is from CT Bank 2 – K1, VT Bank 2 – K2 is used as the
polarizing voltage source.
Path: Setpoints > Protection > Group 1(6) > Current > Sens Ground Directional OC 1(X)
FUNCTION
Range: Disabled, Enabled
Default: Disabled
POLARIZING MODE
Range: Voltage, Current, Dual
Default: Voltage
374 1601-0320
Chapter 8 - Protection
This setting selects the polarizing mode for the directional unit.
● If Voltage polarizing mode is selected, the element uses the zero-sequence voltage angle for polarization.
Select either the zero-sequence voltage V_0, calculated from the phase voltages, or the zero-sequence
voltage supplied externally as the auxiliary voltage V_X. The calculated V_0 can be used as polarizing
voltage only if the voltage transformers are connected in Wye. The auxiliary voltage can be used as the
polarizing voltage if the auxiliary voltage is connected to a zero-sequence voltage source (such as the open
delta connected secondary of VTs). The zero-sequence (V_0) or auxiliary voltage (Vx), accordingly, must be
greater than the voltage set under "Polarizing Volt Supv" to be validated for use as a polarizing signal. If the
polarizing signal is invalid, neither forward nor reverse indication is given.
● If Current polarizing mode is selected, the element uses the angle of the ground current measured on the
ground current input. The ground current must be greater than 0.05 x CT to be validated as a polarizing
signal. If the polarizing signal is not valid, neither forward nor reverse indication is given. For a choice of
current polarizing, it is recommended that the polarizing signal be analyzed to ensure that a known direction
is maintained irrespective of the fault location.
● If Dual polarizing mode is selected, the element performs both directional comparisons as described above. A
given direction is confirmed if either voltage or current comparators indicate so. If a conflicting (simultaneous
forward and reverse) indication occurs, the forward direction overrides the reverse direction.
POLARIZING VOLTAGE
Range: Calculated V0, Measured VN(VX)
Default: Calculated V0
Selects the polarizing voltage used by the directional unit when "Voltage" or "Dual" polarizing mode is set. The
polarizing voltage can be programmed to be either the zero-sequence voltage calculated from the phase
voltages ("Calculated V_0") or supplied externally as an auxiliary voltage ("Measured VN(VX)").
FORWARD ECA
Range: –90° to 90° in steps of 1°
Default: 75°
This setting defines the element characteristic angle (ECA) for the forward direction in "Voltage" polarizing mode.
"Current" polarizing mode uses a fixed ECA of 0°. The ECA in the reverse direction is the angle set for the
forward direction shifted by 180°.
1601-0320 375
Chapter 8 - Protection
FORWARD PICKUP
Range: 0.005 to 3.000 x CT in steps of 0.001 x CT
Default: 0.050 x CT
This setting defines the Pickup level for the overcurrent unit of the element in the forward direction.
REVERSE PICKUP
Range: 0.005 to 3.000 x CT in steps of 0.001 x CT
Default: 0.050 x CT
This setting defines the Pickup level for the overcurrent unit of the element in the reverse direction.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Self-reset
376 1601-0320
Chapter 8 - Protection
R
D
W
Q
F
c
d
@
b
J
h
X
[
f
f
>
a
W
e
X
@
d ?
e
>
]
e
T _
b k
<
V V
D
D D
D D
F
F
F
F F
-
5
+
;
V
&
7
: +
8
&
$
S
#
5
3
2
'
S
S
S
&
$ 0
L
L
/
#
S S S
"
.
S
S
S
S
S
I S
q w
u
s
{
r
|
p
{
z
B
{
n y
S
v
{
G
V
A
P
S S
M
S
M
O
O
M M
L V
S S F S B S S S S
V
S
1601-0320 377
Chapter 8 - Protection
The resultant primary current can be negligible for ground winding faults within 35% of the distance from the neutral
point since the fault voltage is not the system voltage, but rather the result of the transformation ratio between the
primary windings and the percentage of shorted turns.
Application of Restricted Ground Fault protection extends the fault coverage towards the neutral point for low-
impedance grounded winding.
378 1601-0320
Chapter 8 - Protection
RGF protection in the 8-series range of relays uses a low impedance current differential scheme. The relay
calculates the magnitude of the ground differential current as an absolute value from the vector summation of the
computed residual current, and the measured ground current, and applies a restraining current defined as the
maximum measured line current (Imax) to produce a percent slope value. The slope setting allows determination of
the sensitivity of the element based on the class and quality of the CTs used. The figure below shows typical wiring
between the winding and ground CTs and the CT terminals, to assure correct performance of the protection.
Figure 134: Three CT wiring for the Restricted Ground Fault protection
RGF protection includes ground current supervision mechanism to provide more security during external non-
ground faults associated with CT saturation. This can cause spurious neutral currents, which may jeopardize the
security of the RGF 1 protection. Therefore, when the GROUND CURRENT SUPERVISION setting is enabled, the
algorithm checks whether the ground current measured by the relay satisfies the selected GROUND CURRENT
SUPERV LEVEL, before making an operation decision. The ground current supervision is not active if the
GROUND CURRENT SUPERVISION is selected as Disabled. The RGF 1 protection works without the
supervision as well.
The settings of this function are applied to the ground and all three phase currents to produce pickup and trip flags.
The RGF 1 pickup flag is asserted, when the restrained ground differential current is above the PKP value. The
RGF 1 operate flag is asserted if the element stays picked up for the time defined in RGF 1 PKP DELAY. The
element drops from Pickup without operation, if the calculated restrained ground differential current drops below
97-98% of the Pickup value, before the time for operation is reached.The Restricted Ground Fault function can be
inhibited by a blocking input.
Path: Setpoints > Protection > Group 1(6) > Current > RGF 1 (X)
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
1601-0320 379
Chapter 8 - Protection
SIGNAL INPUT
Range: dependent upon the order code
Default: CT Bank 1 -J1
PICKUP
Range: 0.050 to 30.000 x CT in steps of 0.001 x CT
Default: 0.300 x CT
This setting defines the minimum Pickup level of the ground differential current required for operation. The
Pickup value is expressed in times Phase CT (primary) rating.
SLOPE
Range: 0 to 100% in steps of 1%
Default: 50%
This setting defines the slope as the ratio between the ground differential current and the maximum line current
(ground restraining current) as a percentage. The RGF 1 element operates if the actual ground differential/
restraint ratio is greater than the slope and the ground differential current is greater than the RGF 1 Pickup
setting.
PICKUP DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.100 s
The RGF 1 Pickup Time Delay setting defines the time required for the RGF 1 element to operate after it has
picked up. This time delay overrides the spurious ground differential current condition caused by CT saturation
due to external non-ground faults, or during transformer energization. Since RGF 1 protection is intended to
detect small ground fault currents, delayed clearance of such a fault is not a high concern. On the other hand
delayed RGF 1 operation due to a spurious ground differential current caused by an out-of-zone fault can be
used as a backup for downstream protections should they fail to clear the fault.
380 1601-0320
Chapter 8 - Protection
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Self-reset
Example: Transformer : 5MVA, 13.8kV/4.16kV, D/Yg1 type
● Rg = 10 ohms
● Phase CTs: 800:5
● Ground CT: 300:5
● Ifgnd (max) = 4.16kV/(10 ohms *√3) = 240A - maximum ground fault current
To detect a ground fault on the Wye winding at 15% distance from the neutral point, the relay shall detect ground
differential current of:
● Igd = (15x240)/100 = 36 A/800 = 0.045 x CT – PKP setting for the RGF protection
The transformer loading is almost unaffected for ground faults close to the winding neutral, so that the winding rated
load can be used as a reference in defining the RGF 1 slope setting. The rated load for 4.16kV Wye winding is:
● Irated = 5MVA/(4.16kV*√3) = 693 A
Slope setting, % = (36 A/693A)*100 = 5.1%. Select 5% if the transformer is expected to run most of the time at full
load. If most of the time the transformer runs at lower than the nominal loads, the slope setting can be set to higher
value:
● @ 70% load the slope setting would be: (36 / 485 A)*100 = 7%
● @ 50% load the slope setting would be: (36 / 346 A)*100 = 10%
● @ 30% load the slope setting would be: (36 / 208 A)*100 = 17%
The ground current supervision feature and/or the RGF 1 Pickup time delay can be used if CT saturation due to
heavy external fault, is a concern.
1601-0320 381
382
8.2.2.15
Chapter 8 - Protection
FLEXLOGIC OPERAND
Any Trip
LED: TRIP 8S: To operate Output Relay
AND
1(TRIP)
Configurable in 845
OR
AND
SETPOINT LATCH
FUNCTION: R
LED: ALARM
Disabled AND
FLEXLOGIC OPERAND
Trip
OR
Any Alarm
Latched Trip
Alarm S
OR
AND
|I2|=1/3*|Ia+Ib*(1∠240º)+Ic*(1∠120 º)|
FLEXLOGIC OPERAND
RGF 1 RGF 1 OP
OR
AND
BLOCK :
Off = 0
METERING
Currents
SETPOINTS
I0 RGF 1
SETPOINTS Ig PICKUP:
Igd RGF 1
SIGNAL INPUT:
SLOPE:
IA RUN SETPOINTS
IC 0 FlexLogic Operands
Igd >= I pickup RGF 1 PKP
Ig
the negative sequence current magnitude |I2| using the following formula:
Calculate 3Io
USED ONLY IN 845
Igd = |3Io + Ig|
SETPOINTS
RGF 1
GND CURR SUPERV:
OR
Disabled = 0
Enabled = 1 FlexLogic Operands
RGF 1 GND CURR SUPERV
LEVEL: RGF 1 Superv ON
AND
Ig > I Level
system. The input for computing negative sequence current is the fundamental phasor value. The relay computes
The Negative Sequence Instantaneous Overcurrent element may be used to determine and clear unbalance in the
1601-0320
Chapter 8 - Protection
The element responds to the negative-sequence current and applies a positive sequence restraint for better
performance: a small portion (12.5%) of the positive sequence current magnitude is subtracted from the negative
sequence current magnitude when forming the operating quantity:
Iop = |I2| - K * |I_1|
where K = 1/8 and |I_1| = 1/3*|Ia+Ib*(1∠120º)+Ic*(1∠240 º)|
The positive sequence restraint allows for more sensitive settings by counterbalancing spurious negative-sequence
currents resulting from:
● system unbalances under heavy load conditions
● current transformer (CT) transformation errors during three-phase faults
● fault inception and switch-off transients during three-phase faults.
The positive sequence restraint must be considered when testing for Pickup accuracy and response time (multiple
of Pickup). The operating quantity depends on the way the test currents are injected into the relay (single-phase
injection: Iop = 0.2917 * I_injected; three-phase injection, opposite rotation: Iop = I_injected).
The settings of this function are applied to the calculated negative sequence current to produce Pickup and Trip
flags. The Negative Sequence IOC Pickup flag is asserted, when the negative sequence current is above the pickup
value. The Negative Sequence IOC Operate flag is asserted if the element stays picked up for the time defined by
the Negative Sequence IOC PICKUP DELAY setting. If the Pickup time delay is set to 0.000 seconds, the Pickup
and Operate flags are asserted at the same time. The element drops from Pickup without operation if the negative
sequence current drops below 97 to 98% of the Pickup value.
Path: Setpoints > Protection > Group 1(6) > Current > Negative Sequence IOC 1(X)
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
SIGNAL INPUT
Range: dependent upon the order code
Default: CT Bank 1-J1
This setting provides the selection for the current input bank. The default bank names can be changed in:
Setpoints > System > Current Sensing > [Name] > CT Bank Name.
PICKUP
Range: 0.020 to 30.000 x CT in steps of 0.001 x CT
Default: 1.000 x CT
DIRECTION
Range: Non-Directional, NegSeq Dir [1-4] FWD, NegSeq Dir [1-4]
Default: Non-Directional
PICKUP DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
1601-0320 383
Chapter 8 - Protection
Default: 0.000 s
DROPOUT DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.000 s
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Self-reset
384 1601-0320
Chapter 8 - Protection
FLEXLOGIC OPERAND
Do Not Operate, Operate
FLEXLOGIC OPERAND
FLEXLOGIC OPERANDS
FLEXLOGIC OPERAND
894042C1
Neg Seq IOC 1 OP
1(TRIP)
SETPOINT
Output Relay X
LED: ALARM
LED: TRIP
OR
OR OR
LATCH
LATCH
R
S
R
S
AND AND AND AND
Command
RESET
LED: PICKUP
tDPO
SETPOINTS
DROPOUT DELAY:
PICKUP DELAY:
DIRECTION:
PICKUP:
RUN
AND
Phasor
OR
OR
Negative Sequence IOC source
From Manual Close Blocking
Direction (from Neg Seq
Directional OC element)
From Autoreclose
(per shot settings)
SETPOINTS
SETPOINT
BLOCK:
Alarm
Off = 0
Trip
1601-0320 385
Chapter 8 - Protection
of the negative sequence phase current. A positive sequence restraint is applied for better performance: a small
user-programmable portion of the positive sequence current magnitude is subtracted from the negative sequence
current magnitude when forming the element operating quantity:
Iop = |I_2| - K * |I_1|
The positive sequence restraint allows for more sensitive settings by counterbalancing spurious negative sequence
currents resulting from:
● system unbalances under heavy load conditions
● current transformer (CT) transformation errors
● fault inception and switch-off transients.
The operating quantity depends on the way the test currents are injected into the relay. For single phase injection:
Iop = 1/3 * (1 – K) × Iinjected for I_2 mode
The directional unit uses the negative sequence current (I_2) and negative-sequence voltage (V_2).
The following tables define the Negative Sequence Directional Overcurrent element.
The negative sequence voltage must be greater than 0.02 x VT to be validated for use as a polarizing signal. If the
polarizing signal is not validated, neither forward nor reverse indication is given. The figure below explains the
usage of the voltage polarized directional unit of the element by showing the phase angle comparator
characteristics for a phase A to ground fault, with settings of:
● ECA = 75° (element characteristic angle = centerline of operating characteristic)
● FWD LA = 80° (forward limit angle = ± the angular limit with the ECA for operation)
● REV LA = 80° (reverse limit angle = ± the angular limit with the ECA for operation)
The element incorporates a current reversal logic: if the reverse direction is indicated for at least 1.25 of a power
system cycle, the prospective forward indication is delayed by 1.5 of a power system cycle. The element is
designed to emulate an electromechanical directional device. Larger operating and polarizing signals result in faster
directional discrimination bringing more security to the element operation.
386 1601-0320
Chapter 8 - Protection
-V
REV F
LA LA VA
REV
R
LA
EA
LA EA
- LA
F
R
-EA
LA
V V
REV F
LA LA
V 8 8
The forward-looking function is designed to be more secure compared to the reverse-looking function, and should
therefore be used for the tripping direction. The reverse-looking function is designed to be faster compared to the
forward-looking function and should be used for the blocking direction. This allows better protection coordination.
The above bias should be taken into account when using the Negative Sequence Directional Overcurrent element
to directionalize other protection elements.
For dual feeder applications, when the signal input is from CT Bank 1 – J1, VT Bank 1 -J2 is used as the polarizing
voltage source. Similarly, when the signal input is from CT Bank 2 – K1, VT Bank 2 – K2 is used as the polarizing
voltage source.
Path: Setpoints > Protection > Group 1(6) > Current > Negative Sequence Dir OC 1(X)
FUNCTION
Range: Disabled, Enabled
Default: Disabled
1601-0320 387
Chapter 8 - Protection
SIGNAL INPUT
Range: dependent upon the order code
Default: CT Bank 1 -J1
This setting provides a selection for the CT Bank input.
POS-SEQ RESTRAINT
Range: 0.000 to 0.500 in steps of 0.001
Default: 0.063
The setting controls the positive-sequence restraint. Set to 0.125. Set to zero to remove the restraint. Set higher
if large system unbalances or poor CT performance are expected.
FORWARD ECA
Range: 0 to -90° in steps of 1°
Default: -75°
The setting selects the element characteristic angle (ECA) for the forward direction. The element characteristic
angle in the reverse direction is the angle set for the forward direction shifted by 180°.
FORWARD PICKUP
Range: 0.020 to 30.000 x CT in steps of 0.001 x CT
Default: 0.050 x CT
The setting defines the Pickup level for the overcurrent unit in the forward direction. When selecting this setting it
must be kept in mind that the design uses a positive-sequence restraint technique.
REVERSE PICKUP
Range: 0.020 to 30.000 x CT in steps of 0.001 x CT
Default: 0.050 x CT
The setting defines the Pickup level for the overcurrent unit in the reverse direction. When selecting the setting it
must be kept in mind that the design uses a positive-sequence restraint technique.
BLOCK
Range: Off, Any FlexLogic operand
388 1601-0320
Chapter 8 - Protection
Default: Off
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Self-reset
h
9
<
f
g
>
8 e
C
i
m
7
,
@
g c
j
j
5
b
i
m
=
a
6
j
j
<
s
r
6
_
j
<
%
i
r ^
3
'
j
4
]
5
;
%
i 3
\
'
%
g q
3
4
:
2
h
%
g q
:
2
"
"
W U
Y
! !
V
T
#
F
"
% )
N N
%
M M
;
#
;
I I
)
)
- -
)
D D
O
P
%
E E
I I
#
#
L L
"
(
=
R
% %
K K
Q
@
'
Q
*
&
J J
% %
% (
%
I I
" "
$ %
;
/ /
'
#
D D
% %
E E
I I
" "
$ $
H H
% %
G G G
* *
F F F
-
% %
?
?
"
<
&
t
:
-
B
)
3
y
)
8
x
P
/
)
/
u }
E
6
D
'
t
=
8
C E
1601-0320 389
Chapter 8 - Protection
Note:
SOTF 1 (2 or 3) are associated with Breaker 1. The SOTF logic uses breaker status from BKR1. SOTF 4 (5 or 6) are
associated with Breaker 2. The SOTF logic uses breaker status from BKR2. The CT Input and VT Input settings should be
configured to match their respective breakers.
Path: Setpoints > Protection > Group 1(6) > Current > SOTF 1(X)
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
VT INPUT
Range: Ph VT Bnk1-J2
Default: Ph VT Bnk1-J2
CT INPUT
Range: CT Bank 1-J1
Default: CT Bank 1 -J1
390 1601-0320
Chapter 8 - Protection
This setting defines the dead line pickup delay. Once in dead line condition for current AND voltage, the dead
line signal will be set after this delay if conditions are still true. This value should be longer than the longest
autoreclose shot time.
Note:
VTs should be connected to the line side and not the bus side for detection by voltage and currents.
PICKUP DELAY
Range: 0.000 to 6000.000 s in steps of 0.001
Default: 0.000 s
This setting defines a potential delay before trip when SOTF is detected.
Note:
The current pickup and the pickup delay settings must be defined according to the potential starting inrush currents and the
inrush time upon breaker closure.
BLOCK
Range: Off, Any FlexLogic operand
1601-0320 391
Chapter 8 - Protection
Default: Off
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-Reset, Latched
Default: Latched
392 1601-0320
8.2.2.18
1601-0320
SETPOINT
Function:
Disabled = 0
Trip
Latched Trip
Alarm
OR
Latched Alarm
FLEXLOGIC OPERAND
Configurable
Any Trip
LED:
TRIP
SETPOINT
Relay
BROKEN CONDUCTOR
BLOCK:
OR
Off = 0
S
AND
LATCH
FlexLogic Operands R LED:
BKR Local Close SETPOINT ALARM
AND
OR
AND
BKR Remote Close Dropout Delay: FLEXLOGIC OPERAND
SETPOINTS
OR
0 S
OR
CT input
t dpo LATCH
Ia < Dead Line Pickup Delay
Phase A Current (IA) Command R
Ib <
RESET
OR
0
Phase C Current (IC)
SETPOINT
SETPOINTS SETPOINTS SETPOINT Output Relay X
VT input Dead Line Max Voltage Do Not Operate, Operate
Pickup Delay:
SOTF detection delay FlexLogic Operands
Phase A Voltage (VA) Va <
OR
SOTF OP
Phase B Voltage (VB) Vb < pkp t
0
Phase C Voltage (VC) Vc <
FlexLogic Operands
FlexLogic Operands SOTF PKP
BKR1 Open
SETPOINTS
OR
OR
Ib >
Ic >
AND
SETPOINTS SETPOINT
SOTF Max Voltage External SOTF Trigger
Operand set = 1
Va < AND
Vb <
The Broken Conductor detection function detects a line broken conductor condition or a single-pole breaker
malfunction condition through checking the phase current input phasors and the I_2 / I_1 ratio. In normal and
balanced load situations this ratio is zero, while in severe load fault conditions an unbalance is produced and this
ratio increases. The intention of this function is to detect a single-phase broken conductor only. As such two-phase
393
Chapter 8 - Protection
Chapter 8 - Protection
To distinguish between single-phase disappearance and system disturbance in all three phases (such as load
change, switching, etc.), the broken conductor element monitors the change in all three phase currents at the
present instance and at four cycles previous. It also monitors changes in the I_2 / I_1 ratio, I_1 minimum, and I_1
maximum.
The broken conductor function is not to be used to respond to fault transients and single-pole tripping/reclosing
conditions. The time delay is programmed to a sufficient length to ensure coordination with the breaker dead time of
the recloser function.
The broken conductor Pickup flag is asserted, when the I_2 / I_1 ratio of the current bank is above the PKP value,
the positive current is in a range of nominal, and phase current changes. The broken conductor Trip flag is asserted
if the element stays picked up for the time defined by the Pickup time delay. The element instantaneously drops
from Pickup without operation, if the I_2 / I_1 ratio decreases to 97% to 98% of the Pickup value, before the time for
operation is reached.
Path: Setpoints > Protection > Group 1(6) > Current > Broken Conductor 1(X)
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
SIGNAL INPUT
Range: dependent upon the order code
Default: CT Bank 1 -J1
This setting provides the selection for the current bank input.
I_2/I_1 RATIO
Range: 10.0% to 100.0% in steps of 0.1%
Default: 20.0%
The setting specifies the ratio of negative-sequence current to positive-sequence current. When one phase
conductor is broken, the I_2 / I_1 ratio with balanced remaining two phases is 50%. So normally the setting
should be set below 50% (for example, to 30%).
I_1 MIN
Range: 0.05 to 1.00 x CT in steps of 0.01 x CT
Default: 0.10 x CT
The setting specifies the minimum positive-sequence current supervision level. Ensure the setting is
programmed to a level sufficient to prevent I_2 / I_1 from erratic pickup due to a low I_1 signal. However, the
setting is not to be set too high since the broken conductor condition cannot be detected under light load
conditions when I_1 is less than the value specified by this setting.
I_1 MAX
Range: 0.05 to 5.00 x CT in steps of 0.01 x CT
Default: 1.50 x CT
394 1601-0320
Chapter 8 - Protection
The setting specifies the maximum I_1 level allowed for the broken conductor function to operate. When I_1
exceeds this setting, it is considered a fault. This broken conductor function should not respond to any fault
conditions so normally the setting is programmed to less than the maximum load current.
PICKUP DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 20.000 s
CURRENT SUPERVISION
Range: Disabled, Enabled
Default: Disabled
This setting enables or disables the current supervision functionality in Broken Conductor.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Self-reset
1601-0320 395
Chapter 8 - Protection
LED: TRIP
AND
To operate Output Relay
1(TRIP)
OR
S
AND
LATCH
SETPOINTS R
LED: ALARM
AND
BROKEN CONDUCTOR
FUNCTION:
OR
Disabled
Trip
AND
S
Latched Trip LATCH SETPOINT
OR
Alarm SETPOINTS
Command R Output Relay X
Latched Alarm BROKEN CONDUCTOR Do Not Operate, Operate
RESET
I_2/I_1 RATIO:
Configurable FLEXLOGIC OPERAND
BROKEN CONDUCTOR I_1
OR
MIN: Broken Cond OP
BLOCK: RUN
Off=0 |I_2|/|I_1| > RATIO
|I_1| > I_1 MIN
|I_1| < I_1 MAX
SETPOINTS
BROKEN CONDUCTOR
PICKUP DELAY:
tPKP
AND
Current Inputs SETPOINTS 0
SETPOINTS BROKEN CONDUCTOR I_1 LED: PICKUP
Negative Current (I2)
MIN:
Positive Current (I1) SIGNAL INPUT: RUN
Phase A Current (IA) |IA| < I_1 MIN
Broken Cond PKP
AND
OR
AND
|IB| - |IB| > 0.05pu 0
OR
|IC| - |IC| > 0.05pu
AND
I is 4 cycles old
SETPOINTS
Current Supervision
Disabled
Enabled 894043C1
Note:
Breaker has to be configured as Breaker 1 (programmed under Setpoints > System > Breaker 1) to monitor the breaker
close status.
Path:Setpoints > Protection > Group 1 > Current > Undercurrent 1(X)
TRIP FUNCTION
Range: Disabled, Trip, Latched Trip, Configurable
Default: Disabled
This setting enables the Undercurrent Trip functionality.
SIGNAL INPUT
Range: dependent upon the order code
Default: CT Bank 1-J1
396 1601-0320
Chapter 8 - Protection
This setting provides the CT Bank input for the Undercurrent element.
TRIP PICKUP
Range: 0.05 to 0.95 x CT in steps of 0.01 x CT
Default: 0.60 x CT
This setting specifies a pickup threshold for the trip function.
ALARM FUNCTION
Range: Disabled, Alarm, Latched Alarm
Default: Disabled
This setting enables the Undercurrent Alarm functionality.
ALARM PICKUP
Range: 0.05 to 0.95 x CT in steps of 0.01 x CT
Default: 0.65 x CT
This setting specifies a pickup threshold for the alarm function.
1601-0320 397
Chapter 8 - Protection
Default: 1.00 s
This setting specifies a time delay for the alarm function.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
The Undercurrent can be blocked by any asserted FlexLogic operand.
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Latched
398 1601-0320
Chapter 8 - Protection
FLEXLOGIC OPERAND
Any Trip
LED: TRIP
AND
8S: To operate Output
Relay 1(TRIP)
OR
SETPOINT S
AND
Phase Currents Trip Pickup SETPOINTS
SETPOINTS
Phase A Current (Ia) RUN Trip Pickup Delay LATCH
Ia < Trip Pickup
SIGNAL INPUT: Trip Dropout Delay FLEXLOGIC OPERANDS
Phase B Current (Ib) RESET R
OR
Ib < Trip Pickup tPKP Undercur Trip OP
Phase C Current (Ic) tRST Command
CT Bank 1 - J1 Ic < Trip Pickup
OR
SETPOINT
SETPOINT Trip Output Relay X
850 Only Alarm Pickup SETPOINTS Do Not Operate, Operate
RUN Alarm Pickup Delay
Ia < Alarm Pickup
Alarm Dropout Delay
OR
Ib < Alarm Pickup tPKP FLEXLOGIC OPERANDS
tRST
Ic < Alarm Pickup Undercur Trip PKP
TRIP FUNCTION:
AND
Disabled=0
Trip
OR
OR
Latched Trip
AND
AND
Configurable S
LATCH
RESET R
Command
FLEXLOGIC OPERANDS
Undercur Alarm OP
SETPOINT
Undercur Alarm PKP
Block
Off=0 SETPOINT SETPOINT
Start Block Delay
Alarm Output Relay X
tBLK 0
FLEXLOGIC OPERAND Do Not Operate, Operate
AND
BKR 1 Closed
SETPOINT
Alarm Function
Disabled
Alarm
OR
Latched Alarm
1601-0320 399
Chapter 8 - Protection
I phase Λt
2 2
I
− − θ ( t − 1) × e 1
τ
θ = phase
k .I
pickup k .I pickup
Where:
● θ (t) = Cable thermal capacity (%) at time t
● θ (t-1) = Cable thermal capacity (%) at time t-1
● Iphase/Ipickup = Ratio between the actual load current and the pickup setting.
● k = overload factor, a setpoint k-Factor, settable between 1 and 1.5
● Δt/τ = Time step Δt divided by the heating or cooling time constant τ.
● τ = Heating and cooling time constant, usually provided by the manufacturer.
The heating time constant is used when the squared (lPhase/(k x IPickup)) ratio is greater than the thermal capacity
θ(t-1) estimated in the previous time step. Otherwise the formula uses the cooling time constant.
When the load current exceeds the (k x PKP setting), and the element picks up. At the same time the thermal
capacity will start to increase at a rate depending on the current amplitude, the prior loading condition of the cable
and heating time constant. When the thermal capacity exceeds the alarm level, the element will generate an alarm
signal that may turn on a programmable LED. The thermal model alarm can be used as a warning for the start of
dangerous overloading conditions and can prevent unnecessary tripping. When the thermal capacity exceeds the
Trip level (i.e., higher than 100% thermal capacity), the element will generate a Trip signal. The Trip flag will drop
out when the Thermal capacity falls below 97%.
I phase I
2 2 Λt 2 Λt
I
− − θ 0 _ copper × 0.4e −
τ1 τ2
θ = phase phase
− θ 0 _ oil × 0.6e
k .I
pickup k .I pickup
k .I pickup
where:
● τ1 = heating and cooling time constant of the transformer windings
● τ2 = heating and cooling time constant of the insulating oil
Path: Setpoints > Protection > Group 1(6) > Current > Thermal Overload 1(X)
400 1601-0320
Chapter 8 - Protection
FUNCTION
Range: Disabled, Trip, Alarm, Latched Trip, Latched Alarm, Configurable
Default: Disabled
Any setting apart from Disabled enables the setting.
CHARACTERISTIC
Range: Single, Dual
Default: Single
This setting determines the operate characteristic for the thermal overload element.
SIGNAL INPUT
Range: dependent upon the order code
Default: CT Bank 1 –J1
This setting provides selection for the current bank input.
PICKUP
Range: 0.050 to 30.000 x CT in steps of 0.001 x CT
Default: 1.000 x CT
This setting sets the pick-up threshold of the thermal characteristic.
Ipickup = Ibase:
This would normally be the maximum full load current.
Ibase
Permissible current of the equipment to be thermally protected (in many cases this is the maximum continuous
current for the equipment within its thermal limits).
ALARM
Range: 50.0 to 110.0% in steps of 0.1%
Default: 80.0%
The setting sets the Alarm level for the accumulated thermal capacity above which the element generates an
alarm. The Alarm signal can be displayed by the user-programmable LED.
1601-0320 401
Chapter 8 - Protection
K FACTOR
Range: 1.00 to 1.50 in steps of 0.01
Default: 1.00
This setting sets the Overload factor
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
The element is blocked when the operand is asserted.
OUTPUT RELAYS 3 to 7
Range: Operate, Do Not Operate
Default: Do Not Operate
Any, or all, of output relays 3 to 7 can be selected to operate. The operation of the general relays is programmed
by the user. Each relay can be selected to become either energized or de-energized when operated, and to
operate as latched, self-resetting or pulsed
EVENTS
Range: Enabled, Disabled
Default: Enabled
The selection of the Enabled setting enables the events of the function.
TARGETS
Range: Self-Reset, Latched, Disabled
Default: Self-Reset
402 1601-0320
Chapter 8 - Protection
The setting is used to define the operation of an element target message. When disabled, no target message is
issued upon operation of the element. When set to Self-Reset, the target message and LED indication follow
the operate state of the element, and self-resets once the operate element condition clears. When set to
Latched, the target message will remain visible after the element output returns to logic 0 until a RESET
command is received by the relay.
LED: TRIP
AND
Operate Output Relay
1 (TRIP)
OR
AND
S
LATCH
Set-Dominant
R
LED: ALARM
AND
SETPOINT
FUNCTION:
OR
Disabled=0
AND
S
Trip
Latched Trip LATCH
OR
Alarm
Set-Dominant
Latched Alarm Command
R
Configurable SETPOINTS RESET
PICKUP
SETPOINTS
CHARACTERISTIC SETPOINTS
BLOCK:
AND
OR
Thermal OP
COOL TIME CONST 2
850 Only
SETPOINTS
OR
Thermal 1 Alarm
ALARM:
K-FACTOR:
OR
Thermal 1 PKP
RUN
IA > k x PICKUP Thermal 1 PKP A
Figure 143:
The relay will continuously calculate the thermal capacity as a percentage of the total thermal capacity. The thermal
capacity is calculated as follows:
Where:
● θ (t) = Cable thermal capacity (%) at time t
● θ (t-1) = Cable thermal capacity (%) at time t-1
1601-0320 403
Chapter 8 - Protection
Note:
At 0% of Pickup, the operating time equals the Undervoltage PICKUP TIME DELAY setpoint.
404 1601-0320
Chapter 8 - Protection
If FlexCurves are selected, the operating time determined based on following equation:
T = FlexCurve (Vpkp / V)
Note:
FlexCurve reverses the ratio of voltages. The ratio of set pickup value to the measured voltage.
Example: For a Pickup set to 0.9 x VT, when the measured voltage is 0.82 x VT, the ratio would be 0.9/0.8 = 1.1,
therefore in the FlexCurve, the corresponding Trip time setting entry is at 1.1 x PKP (not at 0.82 x PKP). On the
other hand, when the measured voltage is 1 x VT, the ratio is 0.9/1 = 0.9, therefore, in the FlexCurve, the
corresponding Reset time entry is at 0.9 x PKP.
Note:
VT is the secondary voltage programmed under Setpoints > System > Voltage Sensing > Phase VT Secondary.
Path:Setpoints > Protection > Group 1(6) > Voltage > Phase Reversal
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
This setting enables the Phase Reversal functionality.
1601-0320 405
Chapter 8 - Protection
PICKUP DELAY
Range: 0.00 to 180.00 s in steps of 0.01 s
Default: 1.00 s
This setting specifies the pickup delay of the element.
DROPOUT DELAY
Range: 0.00 to 180.00 s in steps of 0.01 s
Default: 1.00 s
This setting defines the reset delay of the element.
BLOCK
Range: Any FlexLogic Operand
Default: Off
The Phase Reversal can be blocked by any asserted FlexLogic operand.
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-Reset, Latched, Disabled
Default: Self-Reset
406 1601-0320
Chapter 8 - Protection
SETPOINT
FUNCTION: FLEXLOGIC OPERAND
Disabled=0 Any Trip
Trip LED: TRIP
AND
869: To operate Output
Latched Trip SETPOINT
Relay 1(TRIP)
OR
Alarm PHASE ROTATION:
OR
AND
Latched Alarm Rev Ph Rotation-VT Bnk: 859: To operate the
Configurable RUN S selected Breaker/
AND
Contactor Trip Relay
LATCH
AND
From Setpoints > System > FLEXLOGIC OPERAND
OR
SETPOINT Power System SETPOINTS Any Alarm
PICKUP DELAY:
BLOCK:
AND
DROPOUT DELAY: S
Off=0 tPKP
OR
tRST LATCH
SETPOINT SETPOINT
PHASE ROTATION: Command R Output Relay X
ACTUAL VALUES
Rev Ph Rotation-CT Bnk: RESET Do Not Operate, Operate
Vab > 50% x VT
AND
OR
Phase Reversal OP
ACTUAL VALUES Phase Reversal
AND
IA > 5% x FLA
AND
VA VAB
VB VBC
VC VCA
IA
IB
IC
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
1601-0320 407
Chapter 8 - Protection
Default: Disabled
SIGNAL INPUT
Range: dependent upon the order code
Default: Ph VT Bnk1-J2 or LEA Bnk1-J2 (order code dependent)
This setting provides the selection for the voltage signal input.
MODE
Range: Phase to Ground, Phase to Phase
Default: Phase to Ground
Note: F/W rev 4 default is Phase to Phase
This setting provides the selection of phase to ground and phase to phase voltages for a Wye VT connection
(phase to phase for delta connected VT connection).
Note:
Only Phase-to-Phase mode should be used when Delta/Single’ VT Connection Type and Pseudo Reference Phase-to-Phase
is programmed for the Phase VT Connection setting under System/Voltage Sensing.
PICKUP
Range: 0.00 to 1.50 x VT in steps of 0.01 x VT
Default: 1.00 x VT
This setting sets the Phase Undervoltage Pickup level specified per times VT.
For example, a Pickup setting of 0.80 x VT with a 13800:115 VT translates into 11.04kV (or 92V secondary). If
the mode selection is phase to phase and the Setpoints/System Setup/Voltage Sensing/Phase VT Connection
selection is Wye, the previous example translates to the phase to phase voltage value of 11.04kV x 1.732 =
19.12kV.
MINIMUM VOLTAGE
Range: 0.00 to 1.50 x VT in steps of 0.01 x VT
Default: 0.20 x VT
This setting sets the minimum operating voltage for the undervoltage Pickup level specified per times VT.
For example, a PKP setting of 0.20 x VT with 13800:115 VT translates into 2.76kV (or 23V secondary).
If the Mode setting selection is Phase to Phase and the Setpoints/System Setup/Voltage Sensing/Phase VT
Connection selection is Wye, the previous example translates to a
Phase to Phase voltage value of 2.76kV x 1.732 = 4.78kV.
408 1601-0320
Chapter 8 - Protection
UNDERVOLTAGE CURVES
Range: Definite Time, Inverse Time, FlexCurves A/B/C/D
Default: Definite Time
This setting provides the selection of definite time delay or time delay inverse undervoltage curves, or
FlexCurves. In the case of FlexCurves, the voltage ratio used is reversed. Refer to the equation and note
regarding FlexCurves in the previous section .
PICKUP DELAY
Range: 0.020 to 6000.000 s in steps of 0.001 s
Default: 1.000 s
This setting provides definite time pickup delay. This setting can be made visible from setting management, only
when ‘Curve’ setting is selected as DT (Definite Time).
RESET TIME
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.000 s
This setting provides selection for dropout time delay used to delay the dropout of the detection of the
undervoltage condition.
RESET MODE
Range: Definite Time, Dependent Time
Default: Definite Time
This setting is based on IEC 60255-151 reset characteristics.
If Definite Time is selected, the percentage of elapsed time for the operate timer is memorized for the set reset
time. If the pickup condition returns before the reset timer has timed out, the operate time initializes from the
memorized value. Otherwise, the memorized value is reset to zero after the reset time times out.
If Dependent Time is selected, the operate timer start decrementing when the pickup condition resets. If the pickup
condition returns before the reset timer has timed out, the operate timer again start incrementing. Otherwise, the
relay returns to its reset state after the set reset time.
1601-0320 409
Chapter 8 - Protection
Figure 147: Reset Mode Dependent Time
Note:
This setting is hidden when Undervoltage Curve is configured to Definite Time. When Curve is programmed as Definite Time,
the Reset Mode is always Definite Time.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
410 1601-0320
8.2.3.4
1601-0320
FLEXLOGIC OPERAND
Any Trip
SETPOINT
LED: TRIP
FUNCTION: 8S: To operate Output Relay
AND
1(TRIP)
Disabled Configurable in 845 & 859
Trip OR
Latched Trip S
AND
LATCH
Alarm
OR
R
Latched Alarm
LED: ALARM
Configurable
AND
FLEXLOGIC OPERAND
OR
Any Alarm
SETPOINTS
S
BLOCK : AND
LATCH SETPOINT
Off = 0
AND
Command R Output Relay X
RESET Do Not Operate, Operate
859
SETPOINT FLEXLOGIC OPERAND
Phase UV1 OP
OR
OR
No
PICK-UP DELAY
FLEXLOGIC OPERAND
TMS
AND
Motor Stopped
UNDERVOLTAGE CURVES
AND
SIGNAL INPUT: MINIMUM VOLTAGE:
AND
ALL THREE }
VB(VBC) MINIMUM Phase UV1 OP A:
ANY ONE
SETPOINTS VC(VCA) MINIMUM RUN VC(VCA) < PICKUP ANY TWO { Phase UV1 OP B:
AND
PICK-UP:
OR
Phase-to-Ground Voltages
Wye connection MODE: ALL THREE } Phase UV1 OP C:
859
FLEXLOGIC OPERAND
Motor Starting
The relay provides two identical Auxiliary Undervoltage (UV) elements per protection group, or a total of 12
elements. Each Auxiliary Undervoltage element may be used to protect voltage sensitive loads and system
components against sustained undervoltage conditions. This element may be used for permissive functions,
411
Chapter 8 - Protection
Chapter 8 - Protection
The Auxiliary Undervoltage element may be set as an instantaneous element with no time delay or as a time
delayed element which can be programmed with definite time, inverse time or FlexCurves. The Auxiliary
Undervoltage element has a programmable minimum operating threshold to prevent undesired operation when
voltage is not available. The input voltage is the auxiliary voltage.
The settings of this function are applied to auxiliary voltage input to produce Pickup and Trip flags. The Auxiliary UV
Pickup flag is asserted when the auxiliary input voltage is below the PKP value. The Auxiliary UV Trip flag is
asserted if the element stays picked up for the time defined by Pickup time delay or for the time defined by the
selected inverse curve/FlexCurve. The element drops from Pickup without operation if the measured voltage rises
above 102 to 103% of the Pickup value before the time for operation is reached.
The minimum voltage setting selects the operating voltage below which the element is blocked (a setting of 0 will
allow a dead source to be considered a fault condition).
This element may be used to give a desired time-delay operating characteristic versus the applied voltage, or as a
definite time element. For the inverse time setpoint, the undervoltage delay setpoint defines a family of curves.
Path: Setpoints > Protection > Group 1(6) > Voltage Elements > Auxiliary UV 1(X)
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
SIGNAL INPUT
Range: dependent upon the order code
Default: Ax VT Bnk1-J2
This setting provides the selection for the voltage signal input.
PICKUP
Range: 0.00 to 1.50 x VT in steps of 0.01 x VT
Default: 1.00 x VT
This setting sets the Auxiliary Undervoltage Pickup level specified per times VT. For example, a Pickup setting of
0.80 x VT with a 13800:115 VT translates into 11.04kV (or 92V secondary).
MINIMUM VOLTAGE
Range: 0.00 to 1.50 x VT in steps of 0.01 x VT
Default: 0.20 x VT
This setting sets the minimum operating voltage for the undervoltage Pickup level specified per times VT.
UNDERVOLTAGE CURVES
Range: Definite Time, Inverse Time, FlexCurves A/B/C/D
Default: Definite Time
This setting provides the selection of definite time delay or time delay inverse undervoltage curves. In the case of
FlexCurves, the voltage ratio is reversed.
412 1601-0320
Chapter 8 - Protection
PICKUP DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 1.000 s
If Inverse Time is selected as an Undervoltage Curve setpoint, the Pickup Delay value is loaded to variable D in
the curve formula.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
LED: TRIP
AND
Operate Output Relay 1 (TRIP)
OR
S
AND
FLEXLOGIC OPERAND
LATCH Any Trip
SETPOINT R
FUNCTION: Set Dominant LED: ALARM
AND
OR
Trip Any Alarm
Latched Trip
AND
S
OR
BLOCK :
UNDERVOLTAGE CURVES:
Off = 0
AND
MINIMUM VOLTAGE:
SETPOINTS Aux UV 1(2) PKP:
Vx > MINIMUM
SIGNAL INPUT:
NAME( Ax VT Bnk1-J2
889
Auxiliary voltage (Vaux)
1601-0320 413
Chapter 8 - Protection
The settings of this function are applied to each of the three voltage inputs to produce Pickup and Trip flags per
voltage input. The OV Pickup flag is asserted when the voltage on any voltage input is above the PKP value. The
OV Trip flag is asserted if the element stays picked up for the time defined by the Pickup time delay and that
number of voltages required for operation is equal to the number defined by voltages required for the operation
setting. The element drops from pickup without operation, if the measured voltage drops below the configured
dropout level of the pickup value, before the time for operation is reached. The dropout level can be configured at
Setpoints > Device > Installation > OV/UV DPO Range.
Phase Overvoltage elements may be used to protect voltage sensitive loads and system components against
sustained overvoltage conditions. The Phase Overvoltage element may be set as an instantaneous element with no
time delay or may be set as a definite time element, Inverse Time, or with FlexCurve. The input voltages are the
three phase to phase voltages from delta connected VTs, or the three phase to ground voltages from wye
connected VTs.
This element may be used to give a desired time-delay operating characteristic versus the applied voltage or as a
definite time element. For the inverse time setpoint, the overvoltage pickup delay setpoint defines a family of curves
as shown below.
The operating time is given by:
414 1601-0320
Chapter 8 - Protection
where:
● T = trip time in seconds
● D = Overvoltage Pickup Delay setpoint
● V = actual phase-phase voltage
● Vpickup = Overvoltage Pickup setpoint
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
1601-0320 415
Chapter 8 - Protection
SIGNAL INPUT
Range: dependent upon the order code
Default: Ph VT Bnk1-J2 or LEA Bnk1-J2, dependent on order code
This setting provides the selection for the voltage signal input.
MODE
Range: Phase to Ground, Phase to Phase
Default: Phase to Ground
Note: F/W rev 4 default is Phase to Phase
This setting provides the selection of phase to ground and phase to phase voltages for a Wye VT connection
(phase to phase for delta connected VT connection).
Note:
Only Phase to Phase mode should be selected when Delta/Single VT Connection Type and Pseudo Reference Phase-to-
Phase is programmed for the Phase VT Connection setting under Setpoints > System > Voltage Sensing.
PICKUP
Range: 0.02 to 3.00 x VT in steps of 0.01 x VT
Default: 1.50 x VT
The setting sets the phase overvoltage pickup level to specified per times VT.
For example, a Pickup setting of 1.10 x VT with 13800:115 VT translates into 15.18kV. If the mode selection is
phase to phase and Setpoints > System Setup > Voltage Sensing > Phase VT Connection selection is Wye,
the previous example translates to the phase to phase voltage value of 15.18kV x 1.732 = 26.29kV.
CURVE
Range: Definite Time, Inverse Time, FlexCurve A, FlexCurve B, FlexCurve C, FlexCurve D
Default: Definite Time
This setting provides selection of curves for overvoltage as definite time, inverse time overvoltage curves or
FlexCuves.
PICKUP DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 1.000 s
This setting provides definite time pickup delay.
416 1601-0320
Chapter 8 - Protection
Note:
This Time Delay setting is visible from setting management, only when ‘Curve’ setting is selected as DT (Definite Time).
TMS
Range: 0.5 to 100.0 in steps of: 0.5
Default: 1.0
If the Inverse Time is selected as an Curve setpoint, the TMS value is loaded to variable “D” in the curve formula
Note: This TMS setting is visible from setting management, only when ‘Curve’ setting is selected as IDMT
or Inverse Time.
DROPOUT DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 1.000 s
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
1601-0320 417
Chapter 8 - Protection
FLEXLOGIC OPERAND
Any Trip
SETPOINT
LED: TRIP
8S: To operate Output Relay
AND
FUNCTION:
1(TRIP)
Disabled Configurable in 845 & 859
OR
Trip
S
AND
Latched Trip
LATCH
OR
Alarm
R
Latched Alarm
LED: ALARM
AND
Configurable
FLEXLOGIC OPERAND
OR
Any Alarm
AND
S
LATCH SETPOINT
SETPOINTS Command R Output Relay X
RESET Do Not Operate, Operate
SETPOINTS PICKUP: SETPOINTS FLEXLOGIC OPERAND
OR
AND
Off = 0 CURVE:
DROPOUT DELAY: SETPOINTS
RUN VA(VAB) > PICKUP
t PKP
889 only
t RST PHASES FOR OPERATION:
SETPOINTS RUN
t PKP
SIGNAL INPUT: VB(VBC) > PICKUP t RST ANY PHASE
RUN
OR
t PKP OPERATE: ANY TWO
NAME( Ph VT Bnk1-J2 THREE FlexLogic Operands
VC(VCA) > PICKUP t RST }
PHASE
Phase OV 1 OP A:
ANY PHASE
SETPOINTS ANY TWO { Phase OV 1 OP B:
OR
PICKUP:
THREE
Phase-to-Ground Voltages PHASE }
Wye connection MODE: Phase OV 1 OP C:
Phase A voltage (VA)
Phase B voltage (VB)
Phase C voltage (VC)
Phase-to-Phase Voltages
Delta connection
Ph-Ph AB voltage (VAB) LED: PICKUP
Ph-Ph BC voltage (VBC) MODE: Phase to Ground, Phase
to Phase (for wye connection)
Ph-Ph CA voltage (VCA) Phase to Phase (Delta
Calculated Phase-to-Phase connection) Phase OV 1 PKP:
Voltages Wye connection
Ph-Ph AB voltage (VAB) Phase OV 1 OP A:
Ph-Ph BC voltage (VBC)
Ph-Ph CA voltage (VCA) { Phase OV 1 OP B:
Phase OV 1 OP C:
418 1601-0320
Chapter 8 - Protection
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
SIGNAL INPUT
Range: Ax VT Bnk1-J2
Default: Ax VT Bnk1-J2
This setting provides the selection for the signal input.
PICKUP
Range: 0.00 to 3.00 x VT in steps of 0.01 x VT
Default: 1.50 x VT
This setting sets the auxiliary overvoltage pickup level specified per times VT.
For example, a Pickup setting of 1.10 x VT with 13800:115 VT translates into 15.08kV (or 126.5V secondary).
CURVE
Range: Definite Time, Inverse Time, FlexCurves A/B/C/D
1601-0320 419
Chapter 8 - Protection
PICKUP DELAY
Range: 0.000 - 6000.000s in steps of 0.001s
Default: 1.000s
DROPOUT DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 1.000 s
This setting provides definite time dropout delay of the operate signal if the Curve setting is selected as Definite
Time. An instantaneous reset is provided by dropout time delay setting of 0.000 s.If the selected Curve setting is
Inverse Time, the dropout delay value is used to linearly reset the element. If the Curve is selected as a
FlexCurve, the reset setpoints of the FlexCurve are used to reset the element.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
420 1601-0320
Chapter 8 - Protection
LED: TRIP
AND
Operate Output Relay 1 (TRIP)
OR
S
AND
FLEXLOGIC OPERAND
LATCH Any Trip
SETPOINT
R
FUNCTION: Set Dominant LED: ALARM
AND
Disabled FLEXLOGIC OPERAND
OR
Trip Any Alarm
Latched Trip
AND
S
OR
Alarm
LATCH SETPOINT
Latched Alarm
Command R Output Relay X
Configurable RESET Set Dominant Do Not Operate, Operate
FLEXLOGIC OPERAND
SETPOINTS SETPOINTS
OR
Aux OV OP
AND
BLOCK : PICKUP:
Off = 0 LED: PICKUP
Overvoltage Curves:
RUN
Vx > PICKUP
SETPOINTS
SIGNAL INPUT:
PICK-UP DELAY:
NAME( Ax VT Bnk1-J2
DROP-OUT DELAY:
t PKP
t RST
Auxiliary voltage
Note:
The same curves used for the time overcurrent elements are used for Neutral Displacement. When using the curve to
determine the operating time of the Neutral Displacement element, substitute the ratio of neutral voltage to Pickup level for the
current ratio shown on the horizontal axis of the curve plot.
The relay provides Neutral Overvoltage protection with independent time delay characteristics. Each stage provides
a choice of operate characteristics, where you can select between:
● An IDMT characteristic
● A range of user-defined curves
● DT (Definite Time)
The undervoltage delay setpoint defines a family of curves as shown below.
The Inverse Time characteristics is given by:
T = D / [(V/Vpkp) - 1]
1601-0320 421
Chapter 8 - Protection
where:
● T = Operating Time
● D = neutral over voltage Pickup Time Delay setpoint (for D = 0.00 operates instantaneously)
● V = Voltage as a fraction of the nominal VT Secondary Voltage
● Vpkp = neutral over voltage Pickup Level
If FlexCurves are selected, the same curves used for the time overcurrent elements are used for Neutral
Displacement. When using the curve to determine the operating time of the Neutral Displacement element,
substitute the ratio of neutral voltage to the pickup level for the current ratio shown on the horizontal axis of the
curve plot.
T = FlexCurve(V/Vpkp)
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
422 1601-0320
Chapter 8 - Protection
SIGNAL INPUT
Range: dependent upon the order code
Default: Ph VT Bnk1-J2 or LEA Bnk1-J2, Dependent on order code
This setting provides the selection for the voltage bank input.
PICKUP
Range: 0.02 to 3.00 x VT in steps of 0.01 x VT (FW up to 3.xx)
Range: 0.02 to 4.00 x VT in steps of 0.01 x VT (FW from 4.10 onwards)
Default: 0.30 x VT
CURVE
Range: Definite Time, FlexCurve A, FlexCurve B, FlexCurve C, FlexCurve D, Inverse time (from FW4.10)
Default: Definite Time
PICKUP DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 1.000 s
The NEUTRAL OV 1 PICKUP DELAY setting applies only if the NEUTRAL OV 1 CURVE setting is Definite
time.
If Inverse Time is selected as neutral OV Curve, the Pickup Delay value is loaded to variable D in the curve
formula.
DROPOUT DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 1.000 s
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
1601-0320 423
424
8.2.3.8
Chapter 8 - Protection
or a total of 6 elements.
FLEXLOGIC OPERAND
Any Trip
SETPOINT
LED: TRIP 8S: To operate Output Relay
FUNCTION:
AND
1(TRIP)
Disabled Configurable in 845 & 859
OR
Trip
Latched Trip S
AND
Alarm
LATCH
OR
Latched Alarm
R
LED: ALARM
Configurable
AND FLEXLOGIC OPERAND
OR
Any Alarm
S
AND
LATCH SETPOINT
SETPOINTS Command R Output Relay X
RESET Do Not Operate, Operate
PICK-UP DELAY:
FLEXLOGIC OPERAND
SETPOINTS SETPOINTS DROP-OUT DELAY: Neutral OV 1 OP
OR
BLOCK : PICKUP:
CURVE:
Off = 0 RUN
AND
t PKP
OR
Vbn > 0.85 x VT
Neutral OV 1 PKP:
Phase Voltages
SETPOINTS
Phase A Voltage (Va) SIGNAL INPUT:
Phase B Voltage (Vb) 3_V0
Phase C Voltage (Vc)
Ph VT Bank 1-J2
The relay provides one Negative Sequence Overvoltage (Negative Sequence OV 1) element per protection group,
1601-0320
Chapter 8 - Protection
The Negative Sequence Overvoltage element can be used to detect an asymmetrical system voltage condition, loss
of one or two phases of the source, or reversed phase sequence of voltages. The element responds to the negative
sequence voltage (V2), calculated from the phase voltages. The Negative Sequence Overvoltage element may be
set as an instantaneous element with no time delay, or may be set as a definite time element.
The settings of this function are applied to the calculated Negative Sequence Voltage to produce Pickup and Trip
flags. The Negative Sequence OV Pickup flag is asserted when the Negative Sequence Voltage is above the PKP
value. The Negative Sequence OV Trip flag is asserted if the element stays picked up for the time defined by Pickup
time delay. The element drops from Pickup without operation if the calculated Negative Sequence Voltage drops
below 97 to 98% of the Pickup value before the time for operation is reached.
Path: Setpoints > Protection > Group 1(6) > Voltage > Neg Seq OV 1(X)
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
SIGNAL INPUT
Range: dependent upon the order code
Default: Ph VT Bnk1-J2 or LEA Bnk1-J2, dependent on order code
PICKUP
Range: 0.00 to 3.00 x VT in steps of 0.01 x VT
Default: 1.00 x VT
This setting sets the Negative Sequence Overvoltage Pickup level specified per times VT. For example, a Pickup
setting of 0.80 x VT with 13800:115 VT translates into 11.04 kV (or 92 V secondary).
Note:
If the 3 phase VT is delta connected, the Negative Sequence Overvoltage pickup level is internally changed to 1/Ö3 of the
user setting, before being compared to the actual negative sequence voltage.
PICKUP DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 1.000 s
This setting provides definite time pick-up delay. Instantaneous operation is selected by pick-up time delay
setting of 0.000 s.
DROPOUT DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 1.000 s
This setting provides definite time drop-out delay. An instantaneous reset is provided by drop-out time delay
setting of 0.000 s
1601-0320 425
Chapter 8 - Protection
BLOCK
Range: Off, Any FlexLogic operand
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
426 1601-0320
8.2.3.9
1601-0320
FLEXLOGIC OPERAND
Any Trip
LED: TRIP
8S: To operate Output Relay
AND
1(TRIP)
LATCH
R
SETPOINT
LED: ALARM
AND
Any Alarm
Disabled
Trip S
AND
OR
Command
Latched Alarm RESET Do Not Operate, Operate
Configurable FLEXLOGIC OPERAND
SETPOINTS Neg Seq OV 1 OP:
OR
AND
t PKP
Off = 0 V_2 > PICKUP
t RST
voltage on the relay terminals, the V/Hz value is automatically set to “0”. The V/Hz value is established as per
menu are used for V/Hz operation, then V/Hz is based on the selected Setpoint > System > Voltage Sensing >
The volts-per-hertz (V/Hz) value is calculated using the maximum of the three-phase voltage inputs. If there is no
voltage and nominal frequency power system settings as follows: if the phase voltage inputs defined in the source
427
Chapter 8 - Protection
Chapter 8 - Protection
Ph VT Bnk1-J2 > Voltage 1 > Phase VT Secondary setting, and the Setpoint > System > Power System >
Nominal Frequency setting.
For example, if Phase VT Secondary and Nominal Frequency are set as 120 V and 60 Hz, respectively, these set
values define the base unit as 1 x (V/Hz).
The volts-per-hertz ratio after division of these nominal settings is 120/60 = 2.
Assume the PICKUP setpoint from the V/Hz element is set to 1.05 x (V/Hz). This will mean that in order for the
element to pick up, the actual volts-per-hertz ratio after division should be 2 *1.05 = 2.1.
The ratio of 2.1 can be achieved if for example the measured voltage is 126V and frequency is 60 Hz, or the voltage
is constant at 120 V and the frequency is 57.14 Hz, or any other combination of these two values, which after V/Hz
division equals 2.1.
To check back the PICKUP setting, we use the base (V/Hz) unit = 120/60 = 2, such that the PICKUP setting value is
2.1/2 = 1.05 x (V/Hz).
The element has a linear reset characteristic. The reset time can be programmed to match the cooling
characteristics of the protected equipment. The element will fully reset from the trip threshold in Reset Time
seconds. The V/Hz element can be used as an instantaneous element with no intentional time delay or as a Definite
or Inverse timed element. The characteristics of the inverse curves are shown as follows.
Path: Setpoints > Protection > Group 1(6) > Voltage > Volts per Hertz 1(2)
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
SIGNAL INPUT
Range: dependent on the order code
Default: Ph VT Bnk1-J2
This setting specifies the input voltage used to calculate the per-unit volts-per-Hertz (V/Hz). If three phase
voltages are used then set the AC Inputs to “Ph VT Bnk1-J2”. To use the V/Hz element with auxiliary voltage, set
AC Inputs to “Aux VT Bnk1-J2”.
VOLTAGE MODE
Range: Phase-ground, Phase-phase
Default: Phase-ground
If the Phase VT Connection is selected as “Wye”, then the VOLTAGE MODE setting further defines the
operating quantity and per-unit value for this element. If the VOLTAGE MODE is set as “Phase-phase”, then the
operating quantity for this element will be phase-to-phase nominal voltage. Likewise, if the VOLTAGE MODE is
set to “Phase-ground”, then the operating quantity for this element will be the phase-to-ground nominal voltage.
If the Phase VT Connection (set under Setpoint > System > Voltage Sensing) is selected as “Delta”, then the
phase-to-phase nominal voltage is used to define the per-unit value, regardless of the Voltage Mode selection.
PICKUP
Range: 0.80 to 4.00 V/Hz in steps of 0.01
428 1601-0320
Chapter 8 - Protection
CURVE
Range: Definite Time, Inverse A, Inverse B, Inverse C, FlexCurve A, FlexCurve B, FlexCurve C, FlexCurve D
Default: Definite Time
Definite Time: For the definite time curve, T(s) = TD multiplier. For example, setting the TD multiplier to 20
results in a time delay of 20 seconds to operate when above the Volts/Hz pickup setting. Instantaneous
operation can be obtained the same way by setting the TD multiplier to “0”.
Inverse Curve A: The curve for the Volts/Hertz Inverse Curve A shape is derived from the formula:
2 `
1
where:
● T = Operating Time
● TDM= Time Delay Multiplier (delay in seconds)
● V = fundamental RMS value of voltage (pu)
● F = frequency of voltage signal (pu)
1601-0320 429
Chapter 8 - Protection
Inverse Curve B:The curve for the Volts/Hertz Inverse Curve B shape is derived from the formula:
TDM V
T when Pickup
V F
Pickup 1
where:
where:
● T = Operating Time
● TDM = Time Delay Multiplier (delay in seconds)
● V = fundamental RMS value of voltage (pu)
● F = frequency of voltage signal (pu)
430 1601-0320
Chapter 8 - Protection
Inverse Curve C:The curve for the Volts/Hertz Inverse Curve C shape is derived from the formula:
TDM V
T when Pickup
1/2 F
V
Pickup 1
where:
● T = Operating Time
● TDM = Time Delay Multiplier (delay in seconds)
1601-0320 431
Chapter 8 - Protection
TD MULTIPLIER
Range: 0.05 to 600.00 in steps of 0.01
Default: 1.00
This setting provides a selection for the Time Dial Multiplier which modifies the operating times for the selected
inverse curve.
T RESET
Range: 0.00 to 6000.00 in steps of 0.01
Default: 1.00
Enter the time that the Volts per Hertz value must remain below the pickup level before the element resets.
432 1601-0320
Chapter 8 - Protection
BLOCK
Range: Off, Any FlexLogic Operand
Default: Off
The Volts per Hertz can be blocked by any asserted FlexLogic operand.
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
1601-0320 433
434
8.2.4
8.2.4.1
Chapter 8 - Protection
SETPOINT
OUT-OF-STEP (78)
FUNCTION:
Disabled=0
FLEXLOGIC OPERAND
Trip SETPOINTS Any Trip
Latched Trip
Voltage Mode: LED: TRIP 869: To operate
OR
Alarm
Output Relay 1(TRIP)
AND
IMPEDANCE ELEMENTS
Configurable
OR
Curve:
TD Multiplier: S
AND
LATC
Reset Time:
H
SETPOINT RUN R
AND
Block: LED:
ALARM
AND
Any Alarm
SETPOINT
SIGNAL INPUT: S
AND
t LATC
Ph VT H SETPOINT
Phase Voltage Inputs from Ph VT
Bnk1-J2 Bnk1-J2 Command R Output Relay X
Actual Values RESET Do Not Operate, Operate
WYE Delta FLEXLOGIC OPERAND
Van Vab Aux VT
Volts/Hz 1 OP
OR
Bnk1-J2
Vbn Vbc MAX V/Hz
V, F
Vcn Vca
J2-3VT Frequency
The element measures the positive-sequence apparent impedance, and traces its locus with respect to a single
The Out-of-step element provides an out-of-step (loss-of-synchronism or pole slip) tripping function for machines.
1601-0320
Chapter 8 - Protection
blinder operating characteristic with an offset mho supervisory. The purpose of the supervisory mho is to permit
tripping for swings that pass through the machine and a limited portion of the system, but to prevent operation on
stable swings that pass through both blinders and outside the mho characteristic.
The out-of-step tripping feature operates as follows: The trip sequence identifies unstable power swings by
determining whether the impedance locus enters one blinder, spends a finite time between the left and right blinder
characteristics, and then exits the opposite blinder. The out-of-step trip process is supervised by a mho
characteristic. If the locus enters the left blinder, right blinder and mho characteristic (indicated by the AND
operation of OOS LFT BLD PKP and OOS RGT BLD PKP FlexLogic operands) for an interval longer than PICKUP
DELAY, the timing out signal (OOS TIMER PKP FlexLogic operand) is established. After the PICKUP DELAY timer
times out, latch 1 is set as long as the impedance stays within the mho characteristic. If afterwards, at any time
(given the impedance stays between the two blinders characteristic), the locus exits from the opposite blinder, latch
2 is set as long as the impedance stays inside the mho caracteristic. The element is now ready to trip. If the “Blinder
Exit” trip mode is selected, the OOS OP operand is set immediately and sealed-in for the interval set by the SEAL-
IN DELAY. If the “MHO Exit” trip mode is selected, the element waits until the impedance locus leaves the mho
characteristic, and then the OOS OP operand is set and sealed-in.
The element is set to use the single blinder characteristic with a supervisory mho as illustrated below.
The FlexLogic output operands for the out-of-step element are described as follows:
● The OOS Lft Bld PKP, OOS Rgt Bld PKP, and OOS Timer PKP FlexLogic operands are auxiliary operands
that can be used to facilitate testing and special applications.
● The OOS OP FlexLogic operand can be used to trip the circuit breaker to isolate the loss-of-synchronism .
1601-0320 435
Chapter 8 - Protection
Follow these steps for a typical setting procedure of the out-of-step element:
1. Carry out detailed transient stability studies for the overall system.
2. Determine the values of generator transient reactance (X'd), step-up transformer reactance (XT), and system
impedance under maximum generation (ZmaxS). The total impedance is given by:
3. Determine the values of the machine transient reactance (X'd), and system impedance (ZS). The total
impedance is given by Ztotal = ZS + j * X’d
4. Set MHO FORWARD REACH to 1.5 times the transformer impedance in the system direction. Set MHO
REVERSE REACH to twice the generator transient reactance in the generator direction.
5. Set BLINDERS RCA to the angle of Ztotal, θ.
6. Using the results of transient stability analysis, find the critical angle δc between the machine and the system,
beyond which the system begins to become unstable. If a stability study is not available, this angle is typically
set at 120°. Then, 10 degrees are normally added in order to increase relay operation security, δ = δc +10.
7. Determine the blinder distance, d, from the following equation:
436 1601-0320
Chapter 8 - Protection
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
SIGNAL INPUT
Range: Positive Impedance 1, Positive Impedance 2
Default: Positive Impedance 1
This setting provides the selection for the positive sequence impedance which is calculated by terminal side or
neutral side CT. Positive sequence impedance 1 is calculated using 3-phase J1 currents and 3-phase J2
voltages. Positive sequence impedance 2 is calculated using 3-phase K1 currents and 3-phase J2 voltages.
1601-0320 437
Chapter 8 - Protection
This setting specifies the forward reach of the mho characteristic. The reach impedance is entered in secondary
ohms. The reach impedance angle is fixed to 90 degrees.
RIGHT BLINDER
Range: 0.10 to 500.00 ohms in steps of 0.01 ohms
Default: 2.00 ohms
This setting defines the right blinder position of the blinder characteristic along with the resistive axis of the
impedance plane, expressed ins secondary ohms. The angular position of the blinder is adjustable with the use
of the BLINDERS RCA setting.
LEFT BLINDER
Range: 0.10 to 500.00 ohms in steps of 0.01 ohms
Default: 2.00 ohms
This setting defines the left blinder position of the blinder characteristic along with the resistive axis of the
impedance plane, expressed ins secondary ohms. The angular position of the blinder is adjustable with the use
of the BLINDERS RCA setting.
BLINDERS RCA
Range: 40 to 90° in steps of 1°
Default: 90°
This setting defines the angular position of the left and right blinders.
PICKUP DELAY
Range: 0.000 to 1.000 s in steps of 0.001 s
Default: 0.100 s
This setting should be set to detect the fastest expected unstable power swing and produce out-of-step tripping
in a secure manner. This timer defines the interval that the impedance locus must spend between the left and
right blinders to establish the out-of-step tripping signal. This time delay must be set shorter than the time
required for the impedance locus to travel between the left and right blinders during the fastest expected out-of-
step. Setting the delay too long can reduce dependability.
TRIP MODE
Range: Blinder Exit, MHO Exit
Default: MHO Exit
Selecting Blinder Exit results in an instantaneous trip after the last step in the out-of-step tripping sequence
is completed (the impedance locus leaves the opposite blinder). The Blinder Exit trip mode stresses the circuit
438 1601-0320
Chapter 8 - Protection
breakers as the currents at that moment are high (the electromotive forces of the two equivalent systems are
close to 180° apart).
Selecting MHO Exit results in a trip at the moment when the impedance locus leaves the mho characteristic.
The MHO Exit trip mode relaxes the operating conditions for the breakers as the currents at that moment are
low, preventing the breakers from a maximum recovery voltage during interruption. The selection should be
made considering the capability of the breakers in the system.
VTFF SUPERVISION
Range: Disabled, VT Fuse Failure 1, VT Fuse Failure 2
Default: Disabled
A VT fuse failure could cause a maloperation of a distance element unless the element is supervised by the
VTFF element.
VTFF Supervision is only available if VT Fuse Failure 1(2) function is enabled, otherwise this setpoint is hidden.
SEAL-IN DELAY
Range: 0.000 to 1.000 s in steps of 0.001 s
Default: 0.100 s
The out-of-step trip FlexLogic operand (OOS OP) is sealed-in for the specified period of time. The sealing-in is
crucial to the MHO Exit trip mode, as the original trip signal is a very short pulse occurring when the impedance
locus leaves the mho characteristic after the out-of-step sequence is completed.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Latched
1601-0320 439
440
8.2.4.1.1
Chapter 8 - Protection
FLEXLOGIC OPERAND
FUNCTION:
OR
Any Trip
Disabled
S
Trip
AND
LATCH
Latched Trip
R
Alarm
OR
LED: ALARM
Latched Alarm
AND
S Q3 FLEXLOGIC OPERAND
XOR
Configurable
OR
Any Alarm
SETPOINT LATCH3
SETPOINT S
AND
POS SEQ CURR SUPV:
AND
Reset-
BLOCK: RUN LATCH SETPOINT
Dominant
Off=0 R Command R Output Relay X
| I_1 | > PICKUP
RESET Do Not Operate, Operate
S Q4
AND
AND
SETPOINT Reset-
0.5 cyc Dominant
VTFF SUPERVISION: R
AND
0
VT Fuse Failure 1 SETPOINTS
AND
FlexLogic Operands FlexLogic Operands
RIGHT BLINDER: SETPOINT
OR
VT Fuse Fail 1 OP OOS Rgt Bld PKP
LEFT BLINDER: TRIP MODE:
VT Fuse Fail 2 OP
BLINDERS RCA: Blinder Exit
AND
RUN SETPOINT OOS Lft Bld PKP
Mho Exit
PICKUP DELAY:
tPKP
AND
Mho SETPOINT OOS Timer PKP
0
AND
SETTING S Q1
AND
0.5 cyc
AND
S Q2
OR
V1 Impedance 1 or 2 depending
which can also provide protection for the generator step-up transformer.
Left Blinder Reset- tRST
I1 on Signal Input selection
Dominant LATCH2
AND
RUN 0.5 cyc R
0
AND
Set-Dominant
AND
R
Right Blinder
894138C1
using the offset mho characteristics. This protection is intended as backup to trip generator for the uncleared
system fault. The elements make use of the generator terminal voltage and terminal or neutral current signals,
The distance protection function (ANSI device 21) implements two zones of phase-to-phase distance protection
1601-0320
Chapter 8 - Protection
The first zone is typically used to provide a backup protection for a step-up transformer and generator system bus
protection. The reach is set to cover the step-up transformer impedance with some margin, say 25%. The time
delay should be coordinated with step up transformer and bus backup protection.
Alternatively, first zone reach can set to 50% of transformer impedance with small or no operating time delay to
provide high-speed protection for phase faults, in addition to the generator differential protection. Care must be
taken for possible wrong operation on an out-of-step power swing condition.
The second zone reach is typically set to cover the longest transmission line or feeder outgoing from the generating
station. Care must be taken for possible under-reaching effects due to the fault contribution from other lines or
generators. The element is intended for backup protection and therefore time delay should always be included. This
element is typically set to coordinate with the longest operating time of the system distance relays protecting lines
outgoing from the station.
Relay provides simple phase distance function that uses offset mho characteristic with overcurrent supervision
feature. The offset mho function has the reverse reach controlled independently from the forward reach.
Each phase distance zone is configured individually through its own setting menu.
The element provides a separate measurement in three loops for AB, BC, and CA faults.
There is a setting for provision of the generator step-up transformer connection. In systems with a delta-wye or wye-
delta transformer, the appropriate transformations of voltage and current signals are implemented internally to allow
proper detection of transformer high-side phase-to-phase faults. If this setting is chosen as None, then it is assumed
that the transformer is wye-wye connected or that there is no step-up transformer. The reach setting is the positive
sequence impedance to be covered, per phase, expressed in secondary ohms.
The element uses the following operating quantities.
AB Ö3 x Ia (Vab – Vca) / Ö3
Equations from the Current and Voltage columns are used to derive inputs to the three (AB, BC, and CA) phase
distance elements. For example, CTs are located at the delta side of the delta-wye 11 transformer, and a given zone
is set to look through the transformer into the system connected to the wye winding, the transformer setup for that
zone shall be set to Dy11 and the relay would use -Ö3 x Ib instead of a traditional Ia – Ib for the AB phase distance
element.
The phase distance Offset MHO characteristics is described below.
1601-0320 441
Chapter 8 - Protection
a) Definitions
The following definitions pertain to all of the distance functions:
● Iloop: loop current phasors.
● Vloop: loop voltage phasors.
● ( )_1: positive-sequence phasor of ( ) derived from the loop quantities.
● Z: reach impedance (REACH ∠ RCA).
● ZREV: reverse reach impedance (REV REACH ∠ (REV REACH RCA + 180°)).
Figure 162:
" ! "
Figure 163: Offset Mho and Lens Characteristics
c) Overcurrent supervision
The overcurrent supervision responds to the following currents:
Iloop / Ö3
The following table summarizes the characteristics of the distance elements.
442 1601-0320
Chapter 8 - Protection
SIGNAL INPUT
Range: CT Bank 1 -J1, CT Bank 2 -K1
Default: CT Bank 1 -J1
This setting provide selection of terminal or neutral side CTs inputs. When Signal Input is configured to CT Bank
1 -J1, the relay calculates loop currents from 3-phase J1-slot currents. When configured to CT Bank 2 -K1, the
relay calculates loop currents from 3-phase K1-slot currents. 889 Distance always require generator terminal
voltage connected to VT Bank 1 – J2 slot.
XFMR SETUP
Range: None, Dy1, Dy11
Default: None
The phase distance elements can be applied to look through a three-phase delta-wye power transformer. This
element requires phase VTs located at the generator terminals side and CTs located at the generator terminals
side or neutral side. If the transformer is wye-wye connected or there is no step-up transformer, this setting shall
be set to "None". As for a delta-wye transformer, the generator side is connected to the delta winding and the
line side to the wye winding.
Figure 164: Phase Distance Transformer Setup
Note:
In applications involving power transformers, the details to calculate distance reach setting are explained after the logic
diagram
FUNCTION
Range: Disabled, Trip, Latched Trip, Alarm, Latched Alarm, Configurable
Default: Disabled
The zone spans between the forward reach impedance defined by the REACH and RCA settings, and the
reverse or offset reach impedance defined by REV REACH and REV REACH RCA as illustrated below.
Note:
The CT polarity need to be considered when setting the protection zone direction. The forward direction is defined as to
protect the system if the current wiring is per the typical wiring diagram.
1601-0320 443
Chapter 8 - Protection
REACH
Range: 0.02 to 500.00 ohms in steps of 0.01 ohms
Default: 2.00 ohms
This setting defines the forward reach of the zone. The offset reach is set independently defined as Rev Reach.
The reach impedance is entered in secondary ohms. The reach impedance angle is entered as the RCA setting.
RCA
Range: 30 to 90º in steps of 1º
Default: 85º
This setting specifies the characteristic angle (similar to the ‘maximum torque angle’ in previous technologies).
This setting defines the angle of the forward reach impedance. The setting is an angle of reach impedance as
shown in the distance characteristic figures shown earlier.
REV REACH
Range: 0.02 to 500.00 ohms in steps of 0.01 ohms
Default: 2.00 ohms
This setting defines the offset or reverse reach of the offset mho characteristics. The value must be entered in
secondary ohms.
444 1601-0320
Chapter 8 - Protection
COMP LIMIT
Range: 30 to 90º in steps of 1º
Default: 90º
This setting shapes the operating characteristic. In particular, it produces the lens-type characteristic of the mho
function. In conjunction with the mho shape, the setting improves loadability of the protected line.
OC SUPERVISION
Range: 0.05 to 30.00 x CT in steps of 0.01 x CT
Default: 0.20 x CT
The phase distance elements are supervised by the magnitude of the line-to-line current (fault loop current used
for the distance calculations). For convenience, √3 is accommodated by the pickup (that is, before being used,
the entered value of the threshold setting is multiplied by √3).
If the minimum fault current level is sufficient, the overcurrent supervision pickup should be set above maximum
full load current preventing maloperation under VT fuse fail conditions. This requirement may be difficult to meet
for remote faults at the end of zones 2. If this is the case, the overcurrent supervision pickup would be set below
the full load current, but this may result in maloperation during fuse fail conditions.
DELAY
Range: 0.000 to 600.000 s in steps of 0.001 s
Default: 0.500 s
This setting allows the user to delay operation of the distance elements and implement stepped distance
protection. The distance element timers for zones 2 apply a short dropout delay to cope with faults located close
to the zone boundary when small oscillations in the voltages or currents could inadvertently reset the timer. Zone
1 does not need any drop out delay since it is sealed-in by the presence of current.
VTFF SUPERVISION
Range: Disabled, VT Fuse Failure 1, VT Fuse Failure 2
Default: Disabled
1601-0320 445
Chapter 8 - Protection
A VT fuse failure could cause a maloperation of a distance element unless the element is supervised by the
VTFF element.
VTFF Supervision is only available if VT Fuse Failure 1(2) function is enabled, otherwise this setpoint is hidden.
OUTPUT RELAY X
Range: Do Not Operate, Operate
Default: Do Not Operate
BLOCK
Range: Off, Any operand from the list of FlexLogic operands
Default: Off
This setting enables the user to select a FlexLogic operand to block a given distance element. VT fuse fail
detection is one of the applications for this setting.
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Self-reset
446 1601-0320
Chapter 8 - Protection
LED: TRIP
SETPOINT
AND
FUNCTION: FLEXLOGIC OPERAND
OR
Disabled Any Trip
Trip
S
AND
Latched Trip
LATCH
OR
Alarm
R
Latched Alarm LED: ALARM
AND
Configurable
FLEXLOGIC OPERAND
OR
IA Any Alarm
Event
SETPOINT
Switch-off Transient
AND
Ph Dist Z1 SW BLK AB S
BLOCK: Delta Wye Blocking
Off=0 LATCH SETPOINT
VAB VA
Command R Output Relay X
RESET Do Not Operate, Operate
SETPOINT
FLEXLOGIC OPERAND
LOAD ENCRO BLOCK:
AND
OR
OR
Ph Dist Z1 PKP AB
Ph Dist Z1 OP
Load Encroachment 1
Load Encroachment 2 Phase AB Switch-off Transient Blocking
AND
FlexLogic Operands
OR
XFMR SETUP:
FlexLogic Operands Ph Dist Z1 Supv BC
REACH/REV REACH:
OR
OR
AND
AND
DELAY:
SIGNAL INPUT A-B Element
Vloop_AB tPKP Ph Dist Z1 OP AB
0
IA
Loop Current Iloop_BC |Iloop_BC| > 3 PKP
IB tPKP
AND
and Loop 0 Ph Dist Z1 OP BC
IC Voltage B-C Element
Vloop_BC tPKP
I_1 0 Ph Dist Z1 OP CA
Iloop_CA |Iloop_CA| > 3 PKP
AND
C-A Element
Vloop_CA
J2 Voltage Inputs
Delta Wye LED: PICKUP
VAB VA-VB
VBC VB-VC
VCA VC-VA
OR
I_1 > 0.025 x CT Ph Dist Z1 PKP
V_1
1 cyc
OR
Ph Dist Z1 PKP CA
Figure 166: Phase Distance Zone 1 Protection Logic Diagram (Zone 2 Logic is similar to Zone 1)
Phase distance elements could be set to respond to faults beyond any three-phase power transformer. The relay
guarantees accurate reach and targeting for any phase fault.
The following setting rules apply to this feature:
● A given distance zone is terminated by location of the VTs, not the CTs.
● Consequently, the positive-sequence impedance of a transformer must be included in the reach setting only if
the transformer is located between the potential source and the intended reach point.
● The reach setting is entered in secondary ohms and as such must take into account location and ratios of
VTs and CTs as well as voltage ratio of the involved power transformer.
The following equations explain the setting rules. Consider one application as shown in the figure below:
1601-0320 447
Chapter 8 - Protection
where:
● ZX = intended reach impedance for Zone 1 (primary ohms)
● ZT = positive-sequence impedance of the transformer
VX, VH = transformer rated voltages
● nCT = transformation ratio of the CTs
● nVT = transformation ratio of the VTs
● Z1 = Zone 1 reach setting (secondary ohms)
As the transformer is located between the potential source and the reach point for Zone 1, the reach impedance
must include the positive-sequence impedance of the transformer. In addition, the primary impedance must be re-
calculated for the voltage level of the VTs and CTs, and eventually, re-calculated to secondary quantities:
The element operates if the positive-sequence voltage is above a set level, and asserts its output signal so that it
can be used to block selected protection elements such as Phase Overcurrent.
448 1601-0320
Chapter 8 - Protection
The settings of this function are applied to the positive sequence voltage and positive sequence impedance. The
Load Encroachment Pickup flag is asserted when the impedance is inside the Load Encroachment operating area
(see the above figure) and the positive sequence voltage is above the minimum operating value. The Load
Encroachment Trip flag is asserted if the element stays picked up for the time defined by the Pickup time delay.
Load Encroachment can be inhibited by a blocking input.
Path: Setpoints > Protection > Group 1(6) > Current > Load Encroachment
FUNCTION
Range: Disabled, Enabled
Default: Disabled
CT INPUT
Range: CT Bank 1 –J1, CT Bank 2 –K1
Default: CT Bank 1 -J1
This setting provides the selection for the current bank input.
MODE
Default: 3Ph(based on Z1)
Range: 3Ph(based on Z1), 1Ph(based on Z)
This setting sets the Load Encroachment to three-phase or single-phase blocking.
If Load Encroachment Mode is 3ph (based on Z1):
Positive
○ sequence voltage (V1) and positive sequence current (I1) are considered for Z1 calculation.
Only
○ 3 phase calculations are performed, individual phase calculations are not necessary.
Output
○ operands: Load Encro FWD, Load Encro REV, Load Encro PKP, Load Encro OP
DIRECTION
Range: Reverse, Forward, Both
Default: Both
This setting sets the Load Encroachment direction measurement.
When Direction setting is set as FORWARD:
PICKUP = {|V1| > FORWARDREACH . |I1|} AND {|angle(V1) - angle(I1)|< FORWARDANGLE}
When Direction setting is set as REVERSE:
PICKUP = {|V1| > REVERSEREACH . |I1|} AND {|angle(V1) - angle(I1)|> 180° - REVERSEANGLE}
1601-0320 449
Chapter 8 - Protection
MINIMUM VOLTAGE
Range: 0.00 to 1.50 x VT in steps of 0.01 x VT
Default: 0.20 x VT
The setting sets the minimum operating positive-sequence voltage/phase voltage required for operation of the
Load Encroachment element. If this voltage is below the set minimum threshold, the element does not operate.
Note:
If 3-phase VT is delta connected, the true supervision level is internally changed to 1/Ö3 of the user setting since the base of
VT here is the phase-phase voltage.
MAXIMUM I2
Range: 0.00 to 1.50 x CT in steps of 0.01 x VT
Default: 0.20 x CT
This setting sets the Negative Phase Sequence current threshold for the Load Encroachment function.
FORWARD REACH
Range: 0.02 to 250.00 Ω in steps of 0.01 Ω
Default: 5.00 Ω
The setting specifies the resistive reach of the element as shown in the Load Encroachment characteristic
diagram. The setting is entered in secondary ohms and is calculated as the positive-sequence resistance seen
by the relay under maximum load conditions and unity power factor.
FORWARD ANGLE
Range: 5 to 85° in steps of 1°
Default: 30°
This setting specifies the size of the blocking region as shown on the Load Encroachment characteristic
diagram, and applies this to the positive-sequence impedance.
REVERSE REACH
Range: 0.02 to 250.00 Ω in steps of 0.01 Ω
Default: 5.00 Ω
This setting specifies the resistive reach of the element as shown in the Load Encroachment characteristic
diagram. This setting should be entered in secondary ohms and be calculated as the positive-sequence
resistance seen by the relay under maximum load conditions and unity power factor.
REVERSE ANGLE
Range: 5 to 85° in steps of 1°
Default: 30°
This setting specifies the size of the blocking region as shown on the Load Encroachment characteristic diagram
and applies this to the positive-sequence impedance.
450 1601-0320
Chapter 8 - Protection
PICKUP DELAY
Range: 0.000 to 6000.00 s in steps of 0.001 s
Default: 0.000 s
Note:
It has to be taken into account that the Pickup time delay programmed in the overcurrent elements (or the other elements)
that are blocked with Load Encroachment must be higher than the time programmed in the Load Encroachment function, in
order to avoid false tripping.
DROPOUT DELAY
Range: 0.000 to 6000.00 s in steps of 0.001 s
Default: 0.000 s
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Disabled
Note:
As the Load Encroachment function operates during normal conditions it is recommended that targets be disabled.
1601-0320 451
452
8.2.5
8.2.5.1
Chapter 8 - Protection
SETPOINTS
SETPOINT
LOAD ENCROACHMENT
FUNCTION:
LOAD ENCROACHMENT MODE:
POWER ELEMENTS
Disabled
OR
FlexLogic Operands
SETPOINTS
Both SETPOINTS
OR
Reverse OUTPUT RELAYS 3 to 7
BLOCK:
AND
Off = 0 Do Not Operate, Operate
OR
SETPOINTS
SETPOINT
AND
LOAD ENCROACHMENT
- Ph VT Bank 1 J1 Load Encro A FWD
DROPOUT DELAY: FlexLogic Operands
|V_1| > MINIMUM V
tDPO
OR
Load Encro OP B
OR
RUN
SETPOINT LOAD ENCROACHMENT
DROPOUT DELAY: Load Encro A REV
MINIMUM VOLTAGE:
tPKP Load Encro B REV
AND
tDPO
|V| > MINIMUM V
Load Encro C REV
AND
SETPOINT
MAXIMUM I2
The relay provides two identical Directional Power elements per protection group; a total of 12 elements.
1601-0320
Chapter 8 - Protection
The Directional Power element responds to three-phase directional power and is designed for reverse power
(32REV) and low forward power (32FWD) applications for synchronous machines or interconnections involving co-
generation. The relay measures the three-phase power from either a full set of wye-connected VTs or a full-set of
delta-connected VTs. In the latter case, the two-wattmeter method is used.
The element has an adjustable characteristic angle and minimum operating power as shown in the Directional
Power characteristic diagram. The element responds to the following condition:
Pcosq + Qsinq > MIN
Where:
● P and Q are active and reactive powers as measured per the metering convention
● Ɵ is a sum of the element characteristic (DIR POWER 1 RCA) and calibration (DIR POWER 1
CALIBRATION) angles
● SMIN is the minimum operating power.
The element has two independent (as to the PICKUP and DELAY settings) stages for Alarm and Trip, and they can
be set separately to provide mixed power protection.
By making the characteristic angle adjustable and providing for both negative and positive values of the minimum
operating power, a variety of operating characteristics can be achieved as presented in the figure below. For
example, section (a) in the figure below shows settings for reverse power, while section (b) shows settings for low
forward power applications.
1601-0320 453
Chapter 8 - Protection
Path: Setpoints > Protection > Group 1(6) > Power > Directional Power 1(X)
454 1601-0320
Chapter 8 - Protection
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
SIGNAL INPUT
Range: Power 1, Power 2
Default: Power 1
This setting provides the selection for the power input. Depending on the order code selection, the
corresponding CT/VT inputs to calculate power are selected under Setpoints > System > Power Sensing.
RCA
Range: 0 to 359° in steps of 1°
Default: 180°
This setting specifies the Relay Characteristic Angle (RCA) for the Directional Power function. Application of this
setting provides the following benefits:
It allows
○ the element to respond to active or reactive power in any direction (active overpower/underpower,
etc.).
Together
○ with a precise calibration angle, it allows compensation for any CT and VT angular errors to permit
more sensitive settings.
It allows
○ for required direction in situations when the voltage signal is taken from behind a delta-wye
connected power transformer and phase angle compensation is required.
For example, the active overpower characteristic is achieved by setting DIR POWER 1 RCA to “0°,” reactive
overpower by setting DIR POWER 1 RCA to “90°,” active underpower by setting DIR POWER 1 RCA to “180°,”
and reactive underpower by setting DIR POWER 1 RCA to “270°”.
CALIBRATION
Range: 0 to 0.95° in steps of 0.05°
Default: 0°
This setting allows the Relay Characteristic Angle to change in steps of 0.05°. This may be useful when a small
difference in VT and CT angular errors is to be compensated to permit more sensitive settings.
The setting enables calibration of the Directional Power function in terms of the angular error of applied VTs and
CTs. The element responds to the sum of the DIR POWER 1 RCA and DIR POWER 1 CALIBRATION settings.
STAGE 1 SMIN
Range: -3.000 to 3.000 x Rated Power in steps of 0.001 x Rated Power
Default: 0.100 x Rated Power
The setting specifies the minimum power as defined along the relay characteristic angle (RCA) for the stage 1 of
the element. The positive values imply a shift towards the operate region along the RCA line; the negative
values imply a shift towards the restrain region along the RCA line. Refer to the Directional power sample
1601-0320 455
Chapter 8 - Protection
applications figure for details. Together with the RCA, this setting enables a wide range of operating
characteristics.
The setting applies to three-phase power and the rated power is as follows:
Rated Power = 3 x VTSecondary (phase-neutral) x VTRatio x CTPrimary(Wye-connected VT), or Rated Power =
(3)1/2x VTSecondary (phase-phase) x VTRatio x CTPrimary (Delta-connected VT)
For example:
A setting of 2% for a 200 MW machine is 0.02 × 200 MW = 4 MW.
If 7.967 kV is a primary VT phase-neutral voltage and 10 kA is a primary CT current, the source rated power is
239 MVA, and, SMIN must be set at 4 MW/239 MVA =0.0167 x Rated ≈ 0.017 x Rated.
If the reverse power application is considered, RCA = 180° and SMIN = 0.017 x Rated.
The element drops out if the magnitude of the positive-sequence current becomes virtually zero, that is, it drops
below the cutoff level.
STAGE 1 DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.500 s
The setting specifies a time delay for stage 1. For reverse power or low forward power applications for a
synchronous machine, stage 1 is typically applied for alarming and stage 2 for tripping.
STAGE 2 SMIN
Range: -3.000 to 3.000 x Rated Power in steps of 0.001 x Rated Power
Default: 0.100 x Rated Power
The setting specifies the minimum power as defined along the relay characteristic angle (RCA) for stage 2 of the
element. The setting needs to be coordinated with the setting of stage 1.
STAGE 2 DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 20.000 s
The setting specifies a time delay for stage 2. For reverse power or low forward power applications for a
synchronous machine, stage 1 is typically applied for alarming and stage 2 for tripping.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Enabled, Disabled
456 1601-0320
1601-0320
TARGETS
Default: Enabled
Default: Self-reset
AND
( '& %$ V UTSLR MQPO N MKXLKJ
OR
Any Trip
+%*+@Z
Disabled
Trip S
AND
LATCH
Range: Self-reset, Latched, Disabled
Latched Trip
Alarm R
OR
LED: ALARM
Latched Alarm
AND
Configurable
V UTSLR MQPO N MKXLKJ
OR
Any Alarm
AND
LATCH Y UO MRYLW
Command R Output Relay X
RESET
Do Not Operate, Operate
!
SETPOINTS "
# V UTSLR MQPO N MKXLKJ
OR
FlexLogic Operands
'+%+ A Z 9C 2 8:9876
][7\[C
010 SETPOINTS
3
( '& %$
SETPOINTS
)
( '& %$
g2f eeCd`_ dcbaa`_ ^ +%*) %) ( '& %$ D
*I1 is positive-sequence current of the Current Cutoff is programmed FlexLogic Operands
/)'$ ( '.)*- E
current source selected to determine Power
( '& %$
configured under setting Signal Input. under Path: Setpoints\Device\ +%A- ( '.)*- 010
Installation ( '& %$ 9C 2=<; 2 8:9876
SETPOINTS +%A- B '.)*- 54332
IHG% GF- +@ 9?9 2=<; 2 8:9876
'& )+%*' %$
-%*-% '*) ), 9?9 >=<; 2 8:9876
Three-phase Power SETPOINTS
( '& %$
D
/)'$ B '.)*- E 9?9 2 8:9876
010
9C >=<; 2 8:9876
54332
kmilkjih
457
Chapter 8 - Protection
Chapter 8 - Protection
TRIP FUNCTION
Range: Disabled, Trip, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
This setting enables the Reactive Power Trip functionality.
TRIP RELAY X
Range: Operate, Do Not Operate
458 1601-0320
Chapter 8 - Protection
ALARM FUNCTION
Range: Disabled, Alarm, Latched Alarm
Default: Disabled
This setting enables the Reactive Power alarm functionality.
ALARM RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
BLOCK
Range: Off, Any FlexLogic operand
1601-0320 459
Chapter 8 - Protection
Default: Off
EVENTS
Range: Disabled, Enabled
Default: Disabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
460 1601-0320
Chapter 8 - Protection
461
@8BkP(
,+(( *)(
9: ,+((
; ; R@46( @4? Q7/ $#87654321
; ; R@46( @4? 3<; '
%& !/0)/.- ,+((
yKx Lw NvNu
=G4G2R<1=7i
gnq ngp
+ '
%& onml
; R@46( @4? Q7/ *)( ' 9: hfgffed
yKx LwNvNu %&
i '
9: %& $#7G</
!7Aj) @<=<, kBGji
; R@46( @4? 3<; ' ADCB2; H J@7E<; 7>2=B47+J
yKx LwNvNu %& $ tct=
I
9:
$ _ @4?C G7FE $ cba= '
!s(`1 R@46( @4? 7>2=4Q7/ /.+ ' %&
!`/0/ ,+-
=G4G2R<1=7i !ADCB2; R@46( @4? 7>2=4Q7/ %&
+ )`i`+
8G4RR< $#"
7=4@7A z7=4@7A =</ <1 *)( ADCB2; H J@7E<; 7>2=B47+J
!3j467+ =DA=D R@46( 9: I
!
$ tct= $ H @4?C G7FE
i ' '
9: %& !s(`1 R@46( @4? 7>2=23<; /.+ %&
,+(( !1` !ADCB2; R@46( @4? 7>2=23<; 7654@DQrG<
' ' A2@) 87FB=4
%& %& 9:
A2@)
$#87654321
!/0)/.- ;0+)
; ; A2@) @4? Q7/
; ; A2@) @4? 3<;
yKx LwNvNu
; A2@) @4? Q7/ ADCB2; H J@7E<; 7>2= B47+J
| ~N}|{u 9: I
$ tct= $ _ @4?C G7FE
!s(`1 ;0+) @4? 7>2=4Q7/ /.+
=G4G2R<1=7i
!ADCB2; A2@) @4? 7>2=4Q7/
+
^VT]\[ZYXWVTUTS R<@-
*)( ADCB2; H J@7E<; 7>2= B47+J
1601-0320
Chapter 8 - Protection
High-Speed Frequency
Range: Disabled, Enabled
Default: Disabled
This setting enables measurement of Hi-Speed Freq. When enabled, all the frequency-based elements (UF, OF,
ROCOF) provide user-configurable selection between Normal and Hi-Speed Freq. The selection between
Normal and Hi-Speed Freq is specified by the setpoint Frequency Input. When disabled, all the frequency-
based elements (UF, OF, ROCOF) use Normal Frequency.
462 1601-0320
Chapter 8 - Protection
which can lead to a complete collapse. The relay provides four identical Underfrequency (UNDERFREQ) elements
per protection group, or a total of 24 elements, which can automatically disconnect sufficient load to restore an
acceptable balance between load and generation. The Underfrequency element can be set as an instantaneous
element with no time delay or as a definite time delayed element. The Underfrequency element has the
programmable minimum operating thresholds to prevent undesired operation during periods of light load or
unavailable voltage. The input voltages are the three phase-to-phase voltages from delta connected VTs (PTs),
three phase-to-ground voltages from wye connected VTs (PTs), or single phase auxiliary voltage. The input currents
are the three phase currents.
The Underfrequency Pickup flag is asserted when the measured frequency of the specified source is below the PKP
value and the voltage and current are above the MINIMUM levels. The Underfrequency Trip flag is asserted if the
element stays picked up for the time defined by the Pickup time delay. The element drops from Pickup without
operation if the measured frequency rises above 0.03Hz of the Pickup value and stays dropped-out for the defined
time delay before the time for operation is reached.
The minimum operating voltage setting selects the minimum voltage below which the element is blocked.
The minimum operating current setting selects the minimum current below which the element is blocked. Operation
during periods of light load are prevented.
Path: Setpoints > Protection > Group 1(6) > Frequency > Underfrequency 1(X)
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
FREQUENCY INPUT
Range: Normal, High-Speed
Default: Normal
You can select Normal or High-speed frequency as an input. Compared to the regular metered voltage
frequency value, the high-speed frequency has the faster response but lesser accuracy. This setpoint is only
available when Hi-Speed Freq is enabled under the path: Setpoints\Protection\Frequency\Common Setup.
PICKUP
Range (normal frequency): 15.00 to 65.00 Hz in steps of 0.01 Hz
Range (high-speed frequency): 40.00 to 65.00 Hz in steps of 0.01 Hz
Default: 59 Hz
1601-0320 463
Chapter 8 - Protection
PICKUP DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 2.000 s
DROPOUT DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 2.000 s
Default: Ph VT Bnk1-J2
VT INPUT
Range: dependent upon the order code
Default: Ph VT Bnk1-J2 or LEA Bnk1-J2, Dependent on order code
MINIMUM VOLTAGE
Range: 0.000 to 1.250 x VT in steps of 0.001 x VT
Default: 0.700 x VT
The setting sets the minimum voltage for Underfrequency element operation specified per times VT. The setpoint
prevents incorrect operation before energization of the source to the relay location, and during voltage dips.
Note:
If the 3-phase VT uses a delta connection and SIGNAL INPUT is set to Ph VT Bnk1-J2, the positive sequence voltage is used
as the supervision voltage. In such condition, the true supervision level is internally changed to 1/Ö3 of the user setting since
the base of VT here is the phase-phase voltage.
Note:
If the 3-phase VT uses a delta connection, the positive sequence voltage is used as the supervision voltage. In such
condition, the true supervision level is internally changed to 1/Ö3 of the user setting since the base of VT here is the phase-
phase voltage.
Note:
When the source input for tracking frequency differs from that used for Under Frequency function, due to frequency variations,
you may encounter notable voltage measurement errors as the frequency of input signal moves away from the tracking
frequency source input. For instance, when the setting `Frequency Input' is configured to auxiliary voltage (from the 4th VT),
while the tracking frequency comes from the main source's three-phase voltages, any difference between the frequency of the
auxiliary voltage (Vx) and the three-phase voltages (3VT) leads to a magnitude measurement error in Vx, caused by the
deviation of Vx frequency from the main frequency
MINIMUM CURRENT
Range: 0.000 to 30.000 x CT in steps of 0.001 x CT
464 1601-0320
Chapter 8 - Protection
Default: 0.200 x CT
The setting sets the minimum value of current required on any phase to allow the Underfrequency element to
operate. The setpoint is used to prevent underfrequency tripping during periods of light load, when this action
would have an insignificant effect on the system. A setting of zero is suspend current supervision.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
jh
/
0 klmnopm kqplqp hmros t ujhv
1
g ghi
/
!"#$%&'#! 0
1
2345436
5) +
G
/ H
2789:;< 0
1 f
=7>
(?|
?:=@ G
H
f;AJ
(ABC;< ?:=@ D@@<
2D@7A
43f3 4
D,7EF=9:;
!"#$%&'#!
()* +
/
0
),,-. 1 WXYZ[\]^_ %`Yabcde
<;=,=;K )
!"#$%&'#! !"#$%&'#!
2345436 2345436
!"#$%&'#! LLL 443 + * 23(?R +
!"#$%&'#!
4 2345436
2345436
D87A7I; J !"#$%&'#!
MLLL *+ 24)) 23(?R +
/
8;KF;B; 0 ) 43(?Rf wxyz
1 4 ASTS
2D DA )>;=A; { )>;=A;
. P , Q* AUSV
!"#$%&'#!
2345436 !"#$%&'#!
N + 2345436
C N } LLL N)(?O3 +
4
<;=,=;K *
D87A7I; J
8;KF;B; N MLLL
~
D@>D87A;
54363R ,
1601-0320 465
Chapter 8 - Protection
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
SIGNAL INPUT
Range: dependent upon the order code
Default: Ph VT Bnk1-J2 or LEA Bnk1-J2, Dependent on order code
This setting provides selection of the frequency input.
FREQUENCY INPUT
Range: Normal, High-Speed
Default: Normal
You can select Normal or High-speed frequency as an input. Compared to the regular metered voltage
frequency value, the high-speed frequency has the faster response but lesser accuracy. This setpoint is only
available when Hi-Speed Freq is enabled under the path: Setpoints\Protection\Frequency\Common Setup.
466 1601-0320
Chapter 8 - Protection
PICKUP
Range (normal frequency): 15.00 to 65.00 Hz in steps of 0.01 Hz
Range (high-speed frequency): 40.00 to 65.00 Hz in steps of 0.01 Hz
Default: 59 Hz
PICKUP DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 2.000 s
DROPOUT DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 2.000 s
MINIMUM VOLTAGE
Range: 0.000 to 1.250 x VT in steps of 0.001 x VT
Default: 0.700 x VT
The setting sets the minimum voltage for Overfrequency element operation specified per times VT.
Note:
If the 3-phase VT uses a delta connection and SIGNAL INPUT is set to Ph VT Bnk1-J2, the positive sequence voltage is used
as the supervision voltage. In such condition, the true supervision level is internally changed to 1/Ö3 of the user setting since
the base of VT here is the phase-phase voltage.
Note:
If the 3-phase VT uses a delta connection, the positive sequence voltage is used as the supervision voltage. In such
condition, the true supervision level is internally changed to 1/Ö3 of the user setting since the base of VT here is the phase-
phase voltage.
Note:
When the source input for tracking frequency differs from that used for Under Frequency function, due to frequency variations,
you may encounter notable voltage measurement errors as the frequency of input signal moves away from the tracking
frequency source input. For instance, when the setting `Frequency Input' is configured to auxiliary voltage (from the 4th VT),
while the tracking frequency comes from the main source's three-phase voltages, any difference between the frequency of the
auxiliary voltage (Vx) and the three-phase voltages (3VT) leads to a magnitude measurement error in Vx, caused by the
deviation of Vx frequency from the main frequency.
1601-0320 467
Chapter 8 - Protection
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
468 1601-0320
Chapter 8 - Protection
FLEXLOGIC OPERAND
Any Trip
LED: TRIP 8S: To operate Output Relay
AND
SETPOINT
1(TRIP)
FUNCTION: Configurable in 845 & 859
OR
Disabled
S
AND
Trip
LATCH
Latched Trip
R
OR
Alarm
LED: ALARM
AND
Latched Alarm
FLEXLOGIC OPERAND
Configurable
OR
Any Alarm
SETPOINT
AND
FLEXLOGIC OPERAND START BLOCK DELAY: S
Motor Stopped tBLK 0 LATCH SETPOINT
Applicable to 869 & 859 Command R Output Relay X
RESET Do Not Operate, Operate
SETPOINTS
FLEXLOGIC OPERAND
BLOCK:
OR
Overfreq1 OP
AND
Off=0
Voltage Inputs
None
SETPOINTS SETPOINTS
SETPOINTS
OVERFREQ1
SIGNAL INPUT*: OVERFREQ1 PICKUP DELAY:
MINIMUM OPERATING SETPOINTS
WYE DELTA VOLTAGE: OVERFREQ1
OVERFREQ1
VA VAB RUN DROPOUT DELAY:
PICKUP:
tPKP
AND
VB VBC Positive-sequence RUN
AND
V MINIMUM
VC VCA tDPO
OR
f PICKUP
Composite
Vx* FREQUENCY f LED: PICKUP
FREQUENCY f high-speed FAST RESET
*Not applicable to 859 FREQUENCY f reset DELAY
SETPOINTS 60 ms FlexLogic Operands
SETPOINTS 0
OVERFREQ1
AND
Overfreq1 PKP
Freq Set #Semicycles AND PICKUP:
RUN
Freq Reset #Semicycles
f high-speed PICKUP
From: Setpoints\Protection\
Frequency\Common Setup
f reset < PICKUP
SETPOINTS
Frequency Input
Normal
High-speed
FLEXLOGIC OPERAND
Any Trip
LED: TRIP 8S: To operate Output Relay
AND
SETPOINT
1(TRIP)
FUNCTION: Configurable in 845 & 859
OR
Disabled
S
AND
Trip
LATCH
Latched Trip
R
OR
Alarm
LED: ALARM
AND
Latched Alarm
FLEXLOGIC OPERAND
Configurable
OR
Any Alarm
SETPOINT
AND
FLEXLOGIC OPERAND START BLOCK DELAY: S
Motor Stopped tBLK 0 LATCH SETPOINT
Applicable to 869 & 859 Command R Output Relay X
RESET Do Not Operate, Operate
SETPOINTS
FLEXLOGIC OPERAND
BLOCK:
OR
Overfreq1 OP
AND
Off=0
Voltage Inputs
None
SETPOINTS SETPOINTS
SETPOINTS
OVERFREQ1
SIGNAL INPUT*: OVERFREQ1 PICKUP DELAY:
MINIMUM OPERATING SETPOINTS
WYE DELTA VOLTAGE: OVERFREQ1
OVERFREQ1
VA VAB RUN DROPOUT DELAY:
PICKUP:
tPKP
AND
V MINIMUM
VC VCA tDPO
OR
f PICKUP
Composite
Vx* FREQUENCY f LED: PICKUP
FREQUENCY f high-speed FAST RESET
*Not applicable to 859 FREQUENCY f reset DELAY
SETPOINTS 60 ms FlexLogic Operands
SETPOINTS 0
OVERFREQ1
AND
Overfreq1 PKP
Freq Set #Semicycles PICKUP:
AND
RUN
Freq Reset #Semicycles
f high-speed PICKUP
From: Setpoints\Protection\
Frequency\Common Setup
f reset < PICKUP
SETPOINTS
Frequency Input
Normal
High-speed
1601-0320 469
Chapter 8 - Protection
The Frequency Rate of Change Pickup flag is asserted when the calculated frequency rate of change of the
specified source is above the PKP value, the voltage and current are above the MINIMUM levels, and the frequency
is within a certain range. The Frequency Rate of Change Trip flag is asserted if the element stays picked up for the
time defined by the Pickup time delay. The element instantaneously drops from Pickup without operation, if the
frequency rate of change drops below 96% of the Pickup value, before the time for operation is reached.
The minimum voltage and current thresholds select the minimum voltage and current below which the element is
blocked.
The minimum and maximum frequencies set the operating frequency range out of which the element is blocked.
Path: Setpoints > Protection > Group 1(6) > Frequency > Frequency Rate of Change 1(X)
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
The selection of Trip, Latched Trip, Alarm, Latched Alarm, or Configurable setting enables the element.
FREQUENCY INPUT
Range: Normal, High-Speed
Default: Normal
You can select Normal or High-speed frequency as an input. Compared to the regular metered voltage
frequency value, the high-speed frequency has the faster response but lesser accuracy. This setpoint is only
available when Hi-Speed Freq is enabled under the path: Setpoints\Protection\Frequency\Common Setup.
TREND
Range: Decreasing, Increasing, Bi-directional
Default: Decreasing
The setting allows configuring of the element to respond to increasing or decreasing frequency, or to a frequency
change in either direction.
PICKUP
Range: 0.10 to 15.00 Hz/sec in steps of 0.01 Hz/sec
Default: 0.50 Hz/sec
The setting specifies an intended Pickup threshold.
For applications monitoring a decreasing trend, set TREND to Decreasing and specify the Pickup threshold
accordingly. The operating condition is: -df/dt > PKP.
For applications monitoring an increasing trend, set TREND to Increasing and specify the pickup threshold
accordingly. The operating condition is: df/dt > PKP.
For applications monitoring rate of change of frequency in any direction, set TREND to “Bi-Directional” and
specify the Pickup threshold accordingly. The operating condition can be either of the above two conditions.
PICKUP DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
470 1601-0320
Chapter 8 - Protection
Default: 2.000 s
This setting provides a definite Pickup time delay. Instantaneous operation is selected by a Pickup time delay
setting of 0.000 s.
MINIMUM FREQUENCY
Range: 20.00 to 80.00 Hz in steps of 0.01 Hz (3.x.x, normal speed with 4.xx)
Range: 40.00 to 70.00 Hz in steps of 0.01 Hz (4.xx high speed)
Default: 45.00 Hz
The setting defines the minimum frequency level required for operation of the element.
The setting may be used to effectively block the feature based on frequency. For example, if the intent is to
monitor an increasing trend but only if the frequency is already above certain level, this setting is set to the
required frequency level.
MAXIMUM FREQUENCY
Range: 20.00 to 80.00 Hz in steps of 0.01 Hz (3.x.x, normal speed with 4.xx)
Range: 40.00 to 70.00 Hz in steps of 0.01 Hz (4.xx high speed)
Default: 65.00 Hz
The setting defines the maximum frequency level required for operation of the element.
The setting may be used to effectively block the feature based on frequency. For example, if the intent is to
monitor a decreasing trend but only if the frequency is already below a certain level (such as for load shedding),
this setting is set to the required frequency level.
VT INPUT
Range: dependent upon the order code
Default: Ph VT Bnk1-J2 or LEA Bnk1-J2, Dependent on order code
This setting provides selection of the frequency input.
MINIMUM VOLTAGE
Range: 0.000 to 1.250 x VT in steps of 0.001 x VT
Default: 0.700 x VT
The setting defines the minimum voltage level required for operation of the element. The supervising function
responds to the positive-sequence voltage. Overvoltage supervision is used to prevent operation under specific
system conditions such as faults.
Note:
If the 3-phase VT uses a delta connection and FREQUENCY INPUT is set to Ph VT Bnk1-J2, the positive sequence voltage is
used as the supervision voltage. In such condition, the true supervision level is internally changed to 1/Ö3 of the user setting
since the base of VT here is the phase-phase voltage.
1601-0320 471
Chapter 8 - Protection
Note:
If the 3-phase VT uses a delta connection, the positive sequence voltage is used as the supervision voltage. In such
condition, the true supervision level is internally changed to 1/Ö3 of the user setting since the base of VT here is the phase-
phase voltage.
CT INPUT
Range: dependent upon the order code
Default: CT Bank1-J1 or CT Bank1-K1, dependent on order code
This setting provides the current bank selection for the minimum current setting.
MINIMUM CURRENT
Range: 0.000 to 30.000 x CT in steps of 0.001 x CT
Default: 0.200 x CT
This setting defines the minimum current level required for operation of the element. The supervising function
responds to the positive-sequence current. Typical application includes load shedding. Set the Pickup threshold
to zero if no overcurrent supervision is required. The setting of zero suspends the current supervision.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
The element will be blocked when the selected operand is asserted.
OUTPUT RELAYS
Range: Operate, Do Not Operate
Default: Do Not Operate
Each relay can be selected to become either energized or de-energized when operated, and to operate as latched,
self-resetting or pulsed.
EVENTS
Range: Enabled, Disabled
Default: Enabled
The selection of the Enabled setting enables the events of the function.
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
This setting is used to define the operation of an element target message. When disabled, no target message is
issued upon operation of the element. When set to Self-Reset, the target message and its LED indication
follow the operate state of the element, and self-reset once the operate element condition clears. When set to
Latched, the target message will remain visible after the element output returns to logic 0 until a RESET
command is received by the relay.
472 1601-0320
1601-0320
LED: TRIP
AND
FLEXLOGIC OPERAND
OR
Any Trip
SETPOINT
FUNCTION: S
AND
LATCH
Disabled
R
Trip
LED: ALARM
Latched Trip
AND
FLEXLOGIC OPERAND
Alarm
OR
OR
Any Alarm
Latched Alarm
Configurable S
AND
LATCH SETPOINT
Command R Output Relay X
SETPOINTS
RESET Do Not Operate, Operate
BLOCK:
Off=0 FLEXLOGIC OPERAND
SETPOINTS
AND
FreqRate1 OP
OR
OR
SETPOINTS FREQ RATE Increasing
OR
CT Bank 1 J1 Positive-sequence SETPOINTS
OR
I MINIMUM
Only 850 and 845 SETPOINTS
FREQ RATE
Voltage Inputs FREQ RATE PICKUP: PICKUP DELAY:
None FlexLogic Operands
RUN tPKP
AND
FreqRate1 Dwn OP
AND
SETPOINTS
-df/dt PICKUP 0
FREQ RATE SETPOINTS
VT INPUT: SETPOINTS
FREQ RATE SETPOINTS
869 Ph VT Bnk 1 J2 MINIMUM VOLTAGE: FREQ RATE
FREQ RATE PICKUP: PICKUP DELAY:
859 Ph VT RUN
RUN tPKP
AND
Composite SETPOINTS
FreqRate1 Up PKP
Vx FREQ RATE
MIN FREQUENCY:
FreqRate1 PKP
OR
473
Chapter 8 - Protection
Chapter 8 - Protection
474 1601-0320
CHAPTER 9
MONITORING
Chapter 9 - Monitoring
476 1601-0320
Chapter 9 - Monitoring
1601-0320 477
Chapter 9 - Monitoring
@893A98
Poo ,+s ,) #-)$ u')$ )'*
2343 5364789
]699^ _8>49<4=>; -+s( .-$/-$s
R"#$)H w
2343
QU2 5364789
U9V69834789 %)*)$"+ ,-'$ s
1//" '$ w
[>?? >\
2343 5>VV?
5364789
L L L L L J
478 1601-0320
Chapter 9 - Monitoring
FUNCTION
Range: Disabled, Alarm, Latched Alarm, Configurable
Default: Disabled
Note:
In order to apply the initial running hours, first clear the Running hours using Records > Clear Records > Clear Running
Hours. Upon execution of “Clear Running Hours” command, the value set in this INITIAL RUN HRS will be initialized in the
running hour counter.
OUTPUT RELAY
Range: Do Not Operate, Operate
Default: Do Not Operate
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
1601-0320 479
Chapter 9 - Monitoring
EVENT
Range: Enabled, Disabled
Default: Disabled
TARGET
Range: Self-reset, Latched, DIsabled
Default: Self-reset
480 1601-0320
Chapter 9 - Monitoring
:D m
L
A
e
HT
AL ep
R )x , EP
IO (3 e
T n P y e I
O
m
m E Re p GO s
R u X
p N H
E n
u D Ru
i
imL
IO m >s
PE Ls H
H n
n N Ru
Ru UR
%!
$
I s h
OP H g
E nu c "#
c "
R "
ii !
n
dr TV zH
aC x 01
5.
Jt 0 >.q
loS > e
1
V F
YB
:N v{ ?B
~ [K
IO T }| YK
P NU =0 RMA {w P 42
E F e AL v
`
_ k BZY 7 /*
RMA b RM
HT
^] fj QWK 6 -+
AL iDs AAL AL \ ^ B *'
@? &
;<
98
1601-0320 481
Chapter 9 - Monitoring
MINIMUM VOLTAGE
Range: 0.10 to 1.25 x VT in steps of 0.01 x VT
Default: 0.10 x VT
This setting specifies the minimum positive-sequence voltage level required to allow the frequency out-of-band
accumulators to operate. This threshold is used to prevent an incorrect accumulation when operating quantity is
too low.
RESET ACCUMULATORS
Range: Off, Any FlexLogic operand
Default: Off
Frequency OOB accumulators can be reset to zero using any FlexLogic operand.
Note:
Using Virtual Input with the Self-reset option is not recommended. Any FlexLogic operand selected as a reset input should
remain high for at least two power cycles.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
This setting selects a FlexLogic operand to block out-of-band frequency accumulation ina ll bands/accumulators.
This is typically required to avoid unnecessary accumulation when relay testing is being performed.
EVENT
Range: Enabled, Disabled
Default: Disabled
482 1601-0320
Chapter 9 - Monitoring
TARGET
Range: Self-reset, Latched, Disabled
Default: Self-reset
The following individual settings are available for each of the seven frequency out-of-band accumulators.
Path: Setpoints > Monitoring > Generator > Frequency OOB Accumulation > Accum 1(7)
FUNCTION
Range: Disabled, ALarm, Latched Alarm, Configurable
Default: Disabled
This setting enables and disables a specific frequency band accumulator.
UPPER FREQUENCY
Range: 5.00 to 70.00 Hz in steps of 0.01 Hz
Default: 60.00 Hz
This setting specifies the upper frequency value, in Hz, below which Accumulator 1(7) starts accumulating time
and asserts the PKP operand. This upper frequency value must be greater than the lower frequency value.
LOWER FREQUENCY
Range: 5.00 to 70.00 Hz in steps of 0.01 Hz
Default: 60.00 Hz
This setting specifies the lower frequency value, in Hz, above which Accumulator 1(7) starts accumulating time
and asserts the PKP operand. This lower frequency value must be less than the upper frequency value.
TIME LIMIT
Range: 1 to 100000 s in steps of 1 s
Default: 200 s
This setting specifies the accumulating time limit (in seconds) above which this function asserts the OP operand.
TIME PRESET
Range: 0 to 100000 s in steps of 1 s
Default: 0 s
This setting allows the user to initialize or preset the accumulator time (in seconds) in case this value is known
from previous operation of a turbine.
Note:
The TIME PRESET value must be higher than the current accumulator value in order to Preset.
OUTPUT RELAY
Range: Do Not Operate, Operate
Default: Do Not Operate
1601-0320 483
Chapter 9 - Monitoring
l
) <<) m :5q; WX"
n
8=7?A= j
k
qCrXsWp Z ` l
m
n P
:49 j :?7
:?7o :49 k o
45P5? 4
7=A@84:5
l 7\""XDp
m
n
) <<)
456 7789 :7$;
FF
) <<
!Qt!Q 4WXEu Q\ v
) <<) 3 q\ =\Q tXQw tXQ
PW\Q x 7Xp 2
1
%&'( )*+%,- ,.,/0(0. 9A= >:?
) <<)
>:? 9@ > B 9CDC"!" ) <<)
8##54 456;
!D E
?A95 :A9A?
:G54 456
3 ?A95 #45P5?;
2 48= !"!WXQCDY
1
FHIJKL M F ð FNOOKL 48=
QRSSNT B QHUTUV !" #
<a b a )
456 7789 Z [ Q!XW
!"!WXQ\ >XW!] ?A95 :A9A?
^_``
cdefghiec
45PP5? 77898:?4P 45PP5? 77898:?4PM 456 7789
!" #$#
484 1601-0320
Chapter 9 - Monitoring
Note:
The equations shown above (EQN1, 2, 3, 4) are not applicable when a setpoint Overload Curve is programmed as a
FlexCurve.
Once the load current exceeds the overload level (k x Ib), it enters an overload phase; that is, heat accumulation
becomes greater than heat dissipation. The thermal overload element reacts by incrementing the thermal capacity
used (TCU) at a rate dependent on the selected thermal curve and overload level. When the accumulated thermal
capacity reaches 100%, the Thermal OL OP operand is set. This operand remains asserted until it is reset.
The thermal overload protection element estimates thermal capacity used TCU using the following equations
calculated each power cycle. When current is greater than the pickup level, I > k x Ib, element starts increasing the
thermal capacity (EQN 5):
When current is less than the dropout level, |I < 0.97 x k x Ib|, the element starts decreasing the thermal capacity
(EQN 6):
1601-0320 485
Chapter 9 - Monitoring
where:
● TCUn = thermal capacity used at index n
● TCUn-1 = thermal capacity used at index n - 1
● Δt = power cycle duration
100
T =
10
ô rs = 3
ô o = 3
)n
i
(mt 1
0.1
0.01
0.1 1 10 100
I / Ipkp 8944 CDR
Figure 180: IEC 255-8 Sample Operate and Reset Curves
486 1601-0320
Chapter 9 - Monitoring
The thermal overload protection element removes the Thermal OP output operand when E < 5%. In case of
emergency, the thermal memory and Thermal OP output operand can be reset using the FlexLogic operand
programmed under the Thermal Reset setting.
All calculations are performed per phase. If the accumulated thermal capacity reaches a value of 100% in any
phase, the thermal overload protection element operates, and only resets when thermal capacity is less than 5% in
all three phases.
Path: Setpoints > Monitoring > Thermal Overload Protection
FUNCTION
Range: Disabled, Alarm, Latched Alarm, Configurable
Default: Disabled
This setting enables the Thermal Overload functionality.
SIGNAL INPUT
Range: dependent upon the order code
Default: CT Bank 1-J1
This setting provides the selection for the 3-Phase CT bank inputs. This setting allows applying this element
either on the terminal side or neutral side of the Generator.
k-FACTOR
Range: 1.00 to 1.50 in steps of 0.01
Default: 1.10
This setting defines the current level at which the power system element is considered to be overloaded. If the
current exceeds the k x Ib threshold, the thermal overload protection reacts by accumulating thermal capacity.
OVERLOAD CURVE
Range: IEC, FlexCurve A, FlexCurve B, FlexCurve C, FlexCurve D
Default: IEC
The thermal overload curve determines the thermal limit overload conditions that can damage the power system
element. The overload curve can take one of five formats: IEC, FlexCurve A, FlexCurve B, FlexCurve C, or
FlexCurve.
TD MULTIPLIER
Range: 0.00 to 600.00 in steps of 0.01 when the thermal model curve is a FlexCurve
1601-0320 487
Chapter 9 - Monitoring
Default: 1.00
This setting is only applicable when the Overload Curve setting is programmed as one of the FlexCurves (A, B,
C, or D). TD Multiplier is used to shift the overload curve on the time axis to create a family of the different
curves. The TD Multiplier value is used to select the curve that best matches the thermal characteristics of the
protected power system element.
This setting allows the selection of a multiple of the base curve shape (where the time dial multiplier = 1) with the
curve shape setting. For example, all times for a TDM = 10 are ten times the multiplier 1, or base curve values.
THERMAL RESET
Range: Off, Any FlexLogic operand
Default: Off
In case of emergency, the thermal memory and thermal OP output operand can be reset using the Thermal
Reset operand.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
The thermal overload protection can be blocked by any asserted FlexLogic™ operand.
RELAYS
Range: Do Not Operate, Operate
Default: Do Not Operate
Any assignable output relay can be selected to operate upon Thermal Protection operation.
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
488 1601-0320
Chapter 9 - Monitoring
Default: Self-reset
978 +8
:"(*56%;12
,6*!$ < IJ
*)LM%; ,6*!$ = K
&'0"34!*56%
!"# "$% &'()*')
-78
)
0012 -%6*N(
UVWXYZ22[ / :& 8&) #%!*)%O #%!*)%
P%!6&*; 9*L)&! IJ G: ,,-.
+, -./ +, Q R S +5 K R S +5 + IJ
< K
+ -./ + Q R S +5 =
+ -./ + Q R S +5 <
=
IJ
K /
, F
-
-G/G
&$$*';
-%(%) "$% &'()*')
."'T -%(%) "$%
-78
>? @? AB CDE
) FG-., H
UVWX\ ][ - >? @? AB CDE
FG-., HH
>? @? AB CDE
FG-., -G/G R S + +
0012 -%(%) UVWX^ 2
9.3.4 SPEED
The relay is capable of measuring the motor/generator speed. Any of the input contacts can be used to read the
pulses from the input source. The source of the pulses can be an inductive proximity probe or Hall Effect gear tooth
sensor. The speed algorithm calculates the number of pulses in the window length (WL) and converts it into an
RPM value. A minimum pulse width of 10% of a revolution is required to detect a pulse from the pulse source.
The following equation is used to calculate the speed based on the detection of the number of pulses N during
window length WL.
Where:
●
N – number of pulses during time defined by the Cal. Window Length (WL)
●
PPR – pulses per revolution defined by setpoint PULSES PER REV (PPR)f – system frequency
●
WL – calculated window length in cycles is defined as: WL = (60 x f) / (PPR x 50)
●
This element has two modes of speed: under speed and over speed which is defined by the setpoint
DIRECTION.
In the under speed mode, a trip and alarm is configured so that the machine must be at a certain speed within a set
period of time from starting. The trip and alarm features are configured so that the specified speed (TRIP PICKUP
or ALARM PICKUP) must be reached in the specified time (TRIP DELAY or ALARM DELAY) otherwise the
element operates. Initially, the time delay begins when the machine starts rotating and resets when the desired
speed is reached. Once the machine is running with the rated speed and then that speed drops below the set
threshold, the time delay restarts and the designated output contact will operate if the machine fails to reach the set
speed in the allotted time.
In the over speed mode, the tachometer trip and alarm features are configured so that if the specified speed (TRIP
PICKUP or ALARM PICKUP) is exceeded for the specified time (TRIP DELAY or ALARM DELAY), the element
operates. Initially, the time delay begins when the machine speed exceeds the pickup value resets when the speed
drops below the pickup.
1601-0320 489
Chapter 9 - Monitoring
TRIP FUNCTION
Range: Disabled, Trip, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
This setting enables the Speed protection Trip functionality.
INPUT
Range: Off, Any Digital Input
Default: Off
Any of the digital input contacts can be used to read the pulses from the input source. For example, an inductive
proximity probe or Hall Effect gear tooth sensor may be used to sense the key on the motor. The probe can be
powered by the +24 V from the input switch power supply. The NPN transistor output can be sent to one of the
digital inputs.
Note:
The voltage threshold must be set to 17 V for the inputs to be recognized using the internal +24 V.
The following figure illustrates wiring examples of PNP-type and NPN-type speed probes connected to the input
terminals.
For illustration purposes, the breaker status inputs are shown along with the speed probe input.
Example a and b: Internal +24V supply is used to power both the speed probe connected to CI # 4 and breaker
status signals (DRY type) connected to CI # 1 & 2 of the same Slot F.
Example c and d: Internal +24V supply is used to power the speed probe connected to CI # 4 while an external
dc power supply is used by the breaker status signals (WET type) connected to CI # 1 and 2. In this example,
since both speed probe and breaker status signals are connected to Slot F, the voltage threshold must be set to
17V.
Note:
When the NPN type speed probe is used, the on/off state of the sensor input is reversed. When the probe sensor state is On
(Closed), the relay sensor Input will indicate Off (Open) and when the probe sensor state is Off (Open), the relay sensor Input
will indicate On (Closed). Thus, when the motor is stopped, the speed sensor input will be ON.
490 1601-0320
Chapter 9 - Monitoring
Note:
The maximum load current that can be delivered by the internal +24 V supply is 80 mA. When the internal +24 V supply is
used to power the probe, the current limitations of the 24V supply must be considered.
RATED SPEED
Range: 100 to 7200 RPM in steps of 1
Default: 3600 RPM
RPM defines the rated speed of the motor.
Note:
This setting is located under Setpoints > System > Generator Setup
1601-0320 491
Chapter 9 - Monitoring
DIRECTION
Range: Underspeed, Overspeed
Default: Overspeed
This setting defines the mode for speed protection. When DIRECTION is set to Underspeed, the Trip and/or Alarm
function picks up when the measured motor speed is below the set pickup level. Likewise, when the Direction is set
to Overspeed, the Trip and/or Alarm function picks up when the measured speed is above the programmed pickup
level.
TRIP PICKUP
Range: 20 to 120% in steps of 1
Default: 75%
This setting specifies a pickup threshold for the trip function.
ALARM FUNCTION
Range: Disabled, Alarm, Latched Alarm
Default: Disabled
This setting enables the speed protection Alarm functionality
ALARM PICKUP
Range: 20 to 120% in steps of 1
Default: 80%
This setting specifies a pickup threshold for the Alarm function.
492 1601-0320
Chapter 9 - Monitoring
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
The Speed protection can be blocked by any asserted FlexLogic operand.
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-Reset, Latched
Default: Latched
1601-0320 493
494
Chapter 9 - Monitoring
FLEXLOGIC OPERAND
Any Trip
LED: TRIP
869: To operate Output
AND
Relay 1(TRIP)
OR
AND
SETPOINT
ALARM PICKUP: Do Not Operate, Operate
Contact Input X status SETPOINTS
RUN Speed< Alarm Pickup ALARM PICKUP DELAY:
SETPOINT tPKP FLEXLOGIC OPERANDS
0
RUN Speed> Alarm Pickup Speed Trip PKP
TRIP FUNCTION:
Disabled=0 LED: Alarm
Trip
Latched Trip
OR
AND
Configurable
OR
FlexLogic Operand
Motor Stopped S
AND
OR
AND
Motor Tripped LATCH
SETPOINT R
AND
RESET
BLOCK: Command
Off = 0
AND
FLEXLOGIC OPERANDS
SETPOINT Speed Alarm OP
DIRECTION:
Under Speed Speed Alarm PKP
AND
Over Speed
SETPOINT
AND
SETPOINT Alarm Output Relay X
AND
Disabled
Alarm
OR
Latched Alarm ACTUAL VALUES
Speed
894176C1
1601-0320
Chapter 9 - Monitoring
FA_1 FA_2
NO NO
FA_1 FA_2
COM COM
V V
FA_1
OPT/V
FA_2
OPT/V
Trip Close
Coil Coil
Figure 184: Coil Circuits without Monitoring
FA_1 FA_2
NO
NO
FA_1 FA_2
COM COM
V V
FA_1
OPT/V
FA_2
OPT/V
Trip Close
Coil Coil
To monitor the trip coil circuit integrity, use the relay terminals FA_1 NO and FA_1 COM to connect the Trip coil, and
provide a jumper between terminals FA_1 NO and FA_1 OPT/V voltage monitor).
Some applications require monitoring of the Trip coil or/and Close coil continuously, regardless of the breaker
position (open or closed). This can be achieved by connecting a suitable resistor across the auxiliary contacts. With
1601-0320 495
Chapter 9 - Monitoring
such connections, the trickle current is maintained by the resistor. For these applications the setting for the Bypass
Breaker Status should be enabled.
D +
O 1 (T ) !"#!" $%&'* , .0$234
F_1 HIK,
O Er a L QR<S>;8G
Jr HIK, UWX@S>
F_1
NO M
V
F_1 HIK,
O T/V 30P
678 YZ@8[[
$ >S[?[<:>
9:;<89<
5a Ba
r r =>?@
c ac A:?G
D -
]^ `
defgef hijkl m n^odpqs ¡¢£¤ ¥ ¦§¨©ª
m ¹º»¥
^d zy{ ¼ Á±ÃÄ°²Å
m ¹º»¥ ÆÇÈÉÃÄ
d ½
\
m ¹º»¥
d\ ¾¿À
«¬ ÊËɲÌÌ
®¯°±²®± ÄÃÌÍ̱¯Ä
tuv {
h zx
wxyz{wz ³´µ¶·
³µ¸´
|}~
|~}
«¬ ÊËɲÌÌ
®¯°±²®± ÄÃÌÍ̱¯Ä
]^ b
Figure 186: Trip and Close Coil Circuit with Continuous Monitoring
496 1601-0320
Chapter 9 - Monitoring
Warning:
The Trip and Close Contacts must be considered unsafe to touch when the relay is
energized.
FUNCTION:
Range: Disabled, Latched Alarm, Alarm, Configurable
Default: Disabled
PICKUP DELAY:
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 10.000 s
DROPOUT DELAY:
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.000 s
This setting provides selection for reset time delay used to delay the dropout of the detection of the overcurrent
condition.
Note:
It is recommended to select the same Trip Relay set under the "Breaker: Trip Relay Select" option.
BLOCK:
Range: Off, Any FlexLogic operand
Default: Off
1601-0320 497
Chapter 9 - Monitoring
OUTPUT RELAY X
Range: Do Not Operate, Operate
Default: Do Not Operate
EVENTS:
Range: Disabled, Enabled
Default: Enabled
TARGETS:
Default: Self-reset
Range: Disabled, Self-reset, Latched
498 1601-0320
1601-0320
FUNCTION:
CLOSE CIRCUIT MONITORING
LED: ALARM
AND
SETPOINT
OR
TCM
FUNCTION: S
AND
Disabled
LATCH # 1
Alarm Command Set-Dominant
Latched Alarm
OR
RESET R
Configurable
TCM
DROP-OUT DELAY:
t PKP
AND
t RST
OUTPUT RLY #1 MONITORING
VOLTAGE < THRESHOLD
SETPOINT
TCM
BYPASS BKR STATE: FlexLogic Operand
Disabled = 0
Trip Coil 1 BKR1 PKP
BKR1 Closed
AND
OUTPUT RLY #1 TRIP
OPERATE
894080C2
499
Chapter 9 - Monitoring
Chapter 9 - Monitoring
Default: Disabled
PICKUP DELAY:
Default: 10.000 s
Range: 0.000 to 6000.000 s in steps of 0.001 s
DROPOUT DELAY:
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.000 s
Note:
We recommend selecting the same Trip Relay set under the Breaker: Close Relay Select option.
OUTPUT RELAY X
Range: Do Not Operate, Operate
Default: Do Not Operate
BLOCK:
Default: Off
Range: Off, Any FlexLogic operand
EVENTS:
Range: Disabled, Enabled
Default: Enabled
TARGETS:
Range: Disabled, Self-reset, Latched
Default: Self-reset
500 1601-0320
Chapter 9 - Monitoring
894079C2
LED: ALARM
FlexLogic Operand
FlexLogic Operand
Do Not Operate, Operate
OUTPUT RELAYS 3 to 7
Set-Dominant
LATCH # 1
R
S
AND AND OR
Command
RESET
t RST
SETPOINT
DROP-OUT DELAY:
PICK-UP DELAY:
t PKP
CCM
CCM
AND
OR
OUTPUT RLY #2 MONITORING
VOLTAGE < THRESHOLD
OR AND
Breaker 1 Monitor\Close Circuit
Setpoints\Monitoring\Breaker\
FlexLogic Operand
Monitoring\
CLOSE OPERATE
OUTPUT RLY #2
SETPOINT
SETPOINT
SETPOINT
BKR1 Opened
Configurable
Disabled = 0
FUNCTION:
BLOCK :
Disabled
Off = 0
Alarm
CCM
CCM
CCM
1601-0320 501
Chapter 9 - Monitoring
The same output operands that are selected to operate the Trip output relay that is used to trip the breaker
indicating a tripping sequence has begun, are used to initiate this feature. A time delay is introduced between
initiation and starting of integration to prevent integration of current flow through the breaker before the contacts
have parted. This interval includes the operating time of the output relay, any other auxiliary relays and the breaker
mechanism. For maximum measurement accuracy, the interval between the change-of-state of the operand (from 0
to 1) and contact separation should be measured for the specific installation. Integration of the measured current
continues for 100 ms, which is expected to include the total arcing period.
Path: Setpoints > Monitoring > Breaker > BKR 1 Monitor > BKR 1 Arcing Current
FUNCTION
Range: Disabled, Alarm, Latched Alarm, Configurable
Default: Disabled
INITIATION
Range: Off, Any FlexLogic operand
Default: Off
The setpoint selects the FlexLogic operand, digital input, virtual input or remote input that initiates the Breaker
Arcing Current scheme, typically the Trip signals from internal protection functions.
DELAY
Range: 0.000 to 6000.00 s in steps of 0.001 s
Default: 0.030 s
The setpoint provides a delay interval between the time the tripping sequence is initiated and the time the
breaker contacts are expected to part, starting the integration of the measured current.
ALARM LEVEL
Range: 0 to 50000 kA2-c in steps of 1 kA2-c
Default: 1000 kA2-c
The setpoint specifies the threshold value (kA2-cycle) above which the output operand is set.
502 1601-0320
Chapter 9 - Monitoring
OUTPUT RELAYS X
Range: Do Not Operate, Operate
Default: Do Not Operate
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Self-reset
1601-0320 503
504
9.4.3
Chapter 9 - Monitoring
SETPOINTS
OR
BKR 1 ARCING S
FUNCTION:
AND
Disabled LATCH # 1
Command Set-Dominant
Alarm
RESET R
Latched Alarm SETPOINTS
OR
AND
Configurable BKR 1 ARCING
DELAY:
OR
BKR 1 ARCING 0 0 OUTPUT RELAYS 3 to 7
BLOCK:
Do Not Operate, Operate
OR
Off = 0
AND
RECORDS FlexLogic Operands
SETPOINTS BKR 1 ARCING BKR 1 Arc OP
BKR 1 ARCING CURRENTS
INITIATION: Add to accumulator
Off = 0
Total I² cycle
SETPOINTS
RUN
CT Bank current IA BKR 1 ARCING
IA²t Integrate IA² cycle
ALARM LEVEL:
CT Bank current IB RUN
CT Bank current IC IB²t Integrate IB² cycle Select highest value kA² cyc > Alarm Level
RUN
COMMAND
IC²t Integrate IC² cycle
CLEAR BKR 1 ARCING
CURRENT:
YES = 1
NO = 0 Set all to 0
892743C1.vsdx
The relay provides breaker health information by monitoring and analyzing the operation count, arcing energy of
breaking current, arcing time, tripping time, closing time and spring charging time if applicable. The breaker health
1601-0320
status depends on many factors, such as permissible operation number, magnitude of breaking current, mechanical
Chapter 9 - Monitoring
The operation count is able to give direct information by comparing it with the permissible operation number. The
longer tripping time and closing time can provide an approximate estimation of trip/close coils and mechanical wear.
The increasing spring charging time may imply developing problems in motor and spring mechanisms. Meanwhile,
the increase in arcing energy of the breaking current may reflect the possibility of contact wear. Longer arcing time
may suggest the loss of dielectric strength in the arc chamber. If the arcing energy or any of the time intervals is
above the related Pickup levels for the use-defined times, the Alarm Led is lit.
The scheme is equipped with three incomplete sequence timers for Trip/Close time, arc time and spring charge time
respectively. So it automatically resets the related time interval after the programmed delay.
A breaker operation function is also included, where breaker operation failure is caused by either of the following
conditions:
● The breaker does not respond to a Trip command within the programmed breaker operation delay time.
● The breaker does not respond to a Close command within the programmed time.
Path: Setpoints > Monitoring > Breaker 1 > Breaker Health
FUNCTION
Range: Disabled, Alarm, Latched Alarm, Configurable
Default: Disabled
MODE
Range: Detection, Monitoring
Default: Detection
The Breaker Health has two running modes: detection and monitoring. Since the monitored time intervals differ
for different breaker types and manufacturers, the detection mode can be used to help set the Pickup settings
based on the historical true values. The operation count, arcing energy of the breaking current, arcing time,
tripping time, closing time and spring charging time are measured and displayed in Records > Breaker Health,
but the element does not pick up when in detection mode. Monitoring mode is the normal mod e, wherein
measurements are analyzed and the element may pick up accordingly.
TRIP TRIGGER
Range: Off, Any FlexLogic operand
Default: Off
This setting assigns the trip initiation signal.
CLOSE TRIGGER
Range: Off, Any FlexLogic operand
Default: Off
This setting assigns the close initiation signal.
1601-0320 505
Chapter 9 - Monitoring
506 1601-0320
Chapter 9 - Monitoring
Note:
The arc energy is calculated by the breaker arcing current element. If the breaker arcing current element is disabled, the arc
energy is not calculated and this setting should not be used. The arc energy used here is the individual value for each trip and
not the accumulated value recorded in the Breaker Arcing Current element.
ALARM COUNTER
Range: 1 to 100 in steps of 1
Default: 5
The setting sets the alarm counter level. One counter is used to accumulate the Pickup data from all monitoring
quantities. If the counter value is above the alarm counter level, the LED is lit and one operand is asserted.
OUTPUT RELAY X
Range: Do Not Operate, Operate
Default: Do Not Operate
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
1601-0320 507
Chapter 9 - Monitoring
LED: ALARM
AND
OR
AND
S
LATCH
Set-Dominant
Command
R
RESET
SETPOINTS
BKR HEALTH
FUNCTION: FlexLogic Operands
Disabled SETPOINTS BKR1 Hlth PKP
Alarm
OR BKR HEALTH
IN ALARM COUNTER:
Latched Alarm
OR
RUN SETPOINTS
Configurable
Counter Real Counter Alarm OUTPUT RELAYS (3-7):
Off=0
AND
SETPOINTS
BKR HEALTH
MODE:
OR
Detection
Monitoring
SETPOINTS SETPOINTS
BKR HEALTH BKR HEALTH
AND
OR
ARC TIME PICKUP:
START RUN
Current Inputs START t_arc_A BKR1 Arc PKP A
STOP (t_arc_A-t_trip-1 cyc) PKP
Phase A Current (ia) ia < 0.02 xCT for one cyc
RUN
START BKR1 Arc PKP B
START t_arc_B (t_arc_B-t_trip-1 cyc) PKP
STOP
Phase B Current (ib) ib < 0.02 xCT for one cyc RUN
BKR1 Arc PKP C
START (t_arc_C-t_trip-1 cyc) PKP
START t_arc_C
STOP
Phase C Current (ic) ic < 0.02 xCT for one cyc
SETPOINTS
AND
BKR HEALTH
OR
RUN
t_IAT
AND
t_IAT
OR
OR
BKR1 Arc Fail
AND
t_IAT
AND
Command
AND
OR
RESET
AND
SETPOINTS
BKR HEALTH
OR
RUN
OR
SETPOINTS
AND
BKR HEALTH
AND
CLOSE TRIGER:
Off=0 SETPOINTS
BKR HEALTH
CLOSE TIME PICKUP:
RUN
FlexLogic Operands START BKR1 Hlth Cls PKP
t_close t_close PKP
BKR1 Closed STOP
SETPOINTS
SETPOINTS
BKR HEALTH
BKR HEALTH CHARGE TIME PICKUP:
SPRING CHARGE STATUS: RUN
BKR1 Hlth Chg PKP
Off=0 t_charge t_charge PKP
SETPOINTS
BKR HEALTH
INCOMPLETE CHARGE TIME:
RUN
t_ICT
BKR1 Charge Fail
SETPOINTS
OR
BKR HEALTH
ARC ENERGY PICKUP:
Arc Energy Inputs RUN
BKR1 Engy PKP A
IA2t cycle IA2t PKP
RUN
BKR1 Engy PKP B
IB2t cycle IB2t PKP
RUN
BKR1 Engy PKP C
IC2t cycle IC2t PKP
508 1601-0320
Chapter 9 - Monitoring
9.5 FUNCTIONS
9.5.1 DEMAND
Current Demand is measured on each phase, and on three phases for real, reactive, and apparent power. Setpoints
allow emulation of some common electrical utility demand measuring techniques for statistical or control purposes.
Note:
The relay is not approved as, or intended to be, a revenue metering instrument. If used in a peak load control system, the
user must consider the accuracy rating and method of measurement employed, and the source VTs and CTs, in comparison
with the electrical utility revenue metering system.
The relay can be set to calculate Demand by any of three methods; Thermal Exponential, Block Interval, Rolling
Demand.
Thermal Exponential
This selection emulates the action of an analog peak recording Thermal Demand meter. The relay measures the
quantity (RMS current, real power, reactive power, or apparent power) on each phase every second, and assumes
the circuit quantity remains at this value until updated by the next measurement. It calculates the Thermal Demand
equivalent based on:
Block Interval
This selection calculates a linear average of the quantity (RMS current, real power, reactive power, or apparent
power) over the programmed Demand time interval, starting daily at 00:00:00 (i.e. 12 am). The 1440 minutes per
day is divided into the number of blocks as set by the programmed time interval. Each new value of Demand
becomes available at the end of each time interval.
1601-0320 509
Chapter 9 - Monitoring
Rolling Demand
This selection calculates a linear average of the quantity (RMS current, real power, reactive power, or apparent
power) over the programmed Demand time interval, in the same way as Block Interval. The value is updated every
minute and indicates the Demand over the time interval just proceeding the time of update.
FUNCTION
Range: Disabled, Alarm, Latched Alarm, Configurable
Default: Configurable
SIGNAL INPUT
Range: dependent upon the order code
Default: CT Bank 1-J1
This setting provides the selection for the current input bank. The bank names can be changed in: Setpoints >
System > Current Sensing > [Name] > CT Bank Name.
MEASUREMENT TYPE
Range: Blk Interval, Exponential, Rolling Dmd
Default: Blk Interval
This setting sets the measurement method. Three methods can be applied.
TIME INTERVAL
Range: 5 min, 10 min, 15 min, 20 min, 30 min
Range (859, 869 FW 4.10 onwards): Range: 5 to 90 min in steps of 1 min
Default: 20 min
Default (859, 869 FW 4.10 onwards): 15 min
This setpoint sets the time period over which the current demand calculation is to be performed. The setpoint is
visible only if MEASUREMENT TYPE is Block Interval or Rolling Demand.
510 1601-0320
Chapter 9 - Monitoring
PICKUP
Range: 10 to 10000 A in steps of 1 A
Range (859, 869 FW 4.10 onwards): 0 to 65000 A
Default: 5000 A
This setpoint sets the Current Demand Pickup level.
OUTPUT RELAY X
Range: Do Not Operate, Operate
Default: Do Not Operate
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
EVENTS
Range: Enabled, Disabled
Default: Disabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Disabled
AND
LED: ALARM
SETPOINTS
OR
AND
S
FUNCTION:
Disabled LATCH
Alarm Set-Dominant
OR
Command R
Latched Alarm
RESET
Configurable
SETPOINTS
AND
BLOCK:
LED: PICKUP
Off=0
SETPOINTS
OUTPUT RELAYS
Do Not Operate, Operate
OR
SETPOINTS
FlexLogic Operands
MEASUREMENT TYPE:
Current Dmd1 PKP
1601-0320 511
Chapter 9 - Monitoring
FUNCTION
Range: Disabled, Alarm, Latched Alarm, Configurable
Default: Configurable
SIGNAL INPUT
Range: Power x, (Dependent on order code)
Default: Power 1
MEASUREMENT TYPE
Range: Blk Interval, Exponential, Rolling Demand
Default: Blk Interval
This setting sets the measurement method. Three methods can be applied.
TIME INTERVAL
Range: 5 min, 10 min, 15 min, 20 min, 30 min
Default: 20 min
This setpoint sets the time period over which the Real Power Demand calculation is to be performed. The
setpoint is visible only if MEASUREMENT TYPE is Block Interval or Rolling Demand.
PICKUP
Range: 0.1 to 300000.0 kW in steps of 0.1 kW
Default: 5000.0 kW
This setting sets the Real Power Demand Pickup level. The absolute value of real power demand is used for the
Pickup comparison.
RESET DEMAND
Range: Off, Any FlexLogic operand
Default: Off
512 1601-0320
Chapter 9 - Monitoring
Any FlexLogic operand can be used to reset the minimum and maximum real power demand from the current
value to zero. These values are reset to zero at the rising edge of the set operand. After reset to zero, calculation
of minimum and maximum real power demand values continues until the next rising edge of the reset operand.
The Reset Demand operand doesn’t reset the current value of the demand used by the Real Power Demand
function.
OUTPUT RELAYS X
Range: Do Not Operate, Operate
Default: Do Not Operate
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
EVENTS
Range: Enabled, Disabled
Default: Disabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Disabled
1601-0320 513
Chapter 9 - Monitoring
LED: ALARM
AND
SETPOINTS
OR
REAL PWR DEMAND
AND
S
FUNCTION:
Disabled LATCH
Alarm Set-Dominant
OR
Command
Latched Alarm R
RESET
Configurable
SETPOINTS AND
BLOCK:
LED: PICKUP
Off=0
SETPOINTS
OUTPUT RELAYS
OR
Do Not Operate, Operate
SETPOINTS
REAL PWR DEMAND FlexLogic Operands
MEASUREMENT TYPE: RealPwr Dmd PKP
REAL PWR DEMAND
THERMAL 90% RESPONSE
TIME: SETPOINTS
SETPOINTS
REAL PWR DEMAND REAL PWR DEMAND
SIGNAL INPUT:
Real Power Inputs TIME INTERVAL: REAL POWER PICKUP:
RUN
Three-Phase Calculate:
Power 1 Real Demand |P Demand| PICKUP
Real Power (P)
Min Real Demand
Max Real Demand
Not available in 869 Reset Min & Max Real Demand
to 0
ACTUAL VALUES
SETPOINTS Pwr 1 Real Dmd
Pwr 1 Min Real Dmd
RESET DEMAND:
Pwr 1 Max Real Dmd
Off=0
FUNCTION
Range: Disabled, Alarm, Latched Alarm, Configurable
Default: Configurable
SIGNAL INPUT
Range: Power x (Dependent on order code)
Default: Power 1
SIGNAL INPUT
Range: Power 1, Power 2
Default: Power 1
MEASUREMENT TYPE
Range: Blk Interval, Exponential, Rolling Demand
514 1601-0320
Chapter 9 - Monitoring
TIME INTERVAL
Range: 5 min, 10 min, 15 min, 20 min, 30 min
Default: 20 min
The setpoint sets the time period over which the Reactive Power Demand calculation is to be performed. The
setpoint is visible only if MEASUREMENT TYPE is Block Interval or Rolling Demand.
PICKUP
Range: 0.1 to 300000.0 kvar in steps of 0.1 kvar.
Default: 5000.0 kvar
Any FlexLogic operand can be used to reset the accumulated reactive power demand from its current value to
zero. The accumulated value resets at the rising edge of the set operand. After reset to zero, the reactive power
demand element continues calculating the demand until the next rising edge of the reset operand.
RESET DEMAND
Range: Off, Any FlexLogic operand
Default: Off
Any FlexLogic operand can be used to reset the minimum and maximum reactive power demand from its current
value to zero. The minimum and maximum values reset at the rising edge of the set operand. After reset to zero,
calculation of minimum and maximum reactive power demand values continues until the next rising edge of the
reset operand.
The Reset Demand operand doesn't reset the current value of the demand used by the Reactive Power Demand
function.
OUTPUT RELAY X
Range: Do Not Operate, Operate
Default: Do Not Operate
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
1601-0320 515
Chapter 9 - Monitoring
EVENTS
Range: Enabled, Disabled
Default: Disabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Disabled
LED: ALARM
AND
SETPOINTS
OR
REACTIVE PWR DMD
AND
S
FUNCTION:
Disabled LATCH
Alarm Set-Dominant
OR
Command
Latched Alarm R
RESET
Configurable
SETPOINTS
AND
BLOCK:
LED: PICKUP
Off=0
SETPOINTS
OUTPUT RELAYS
OR
Do Not Operate, Operate
SETPOINTS
REACTIVE PWR DMD FlexLogic Operands
MEASUREMENT TYPE: ReactvPwr Dmd PKP
REACTIVE PWR DMD
THERMAL 90% RESPONSE SETPOINTS
TIME:
SETPOINTS REACTIVE PWR DMD
SIGNAL INPUT: REACTIVE PWR DMD REACTIVE POWER PICKUP:
Reactive Power Inputs TIME INTERVAL:
Calculate: RUN
Three-Phase
Power 1 Reactive Demand |Q Demand| PICKUP
Reactive Power (Q)
Min Reactive Demand
Max Reactive Demand
Not available in 869 Reset Min & Max Reactive ACTUAL VALUES
Demand to 0
Pwr 1 Reactive Dmd
Pwr 1 Min Reactive Dmd
SETPOINTS
Pwr 1 Max Reactive Dmd
RESET DEMAND:
Off=0
FUNCTION
Range: Disabled, Alarm, Latched Alarm, Configurable
Default: Configurable
SIGNAL INPUT
Range: Power x (Dependent on order code)
516 1601-0320
Chapter 9 - Monitoring
Default: Power 1
MEASUREMENT TYPE
Range: Blk Interval, Exponential, Rolling Demand
Default: Blk Interval
The setting sets the measurement method. Three methods can be applied.
TIME INTERVAL
Range: 5 min, 10 min, 15 min, 20 min, 30 min
Default: 20 min
The setpoint sets the time period over which the Apparent Power Demand calculation is to be performed. The
setpoint is visible only if MEASUREMENT TYPE is Block Interval or Rolling Demand.
PICKUP
Range: 0.1 to 300000.0 kVA in steps of 0.1 kVA
Default: 5000.0 kVA
The setting sets the Apparent Power Demand Pickup level.
RESET DEMAND
Range: Off, Any FlexLogic operand
Default: Off
Any FlexLogic operand can be used to reset the minimum and maximum apparent power demand from its
current value to zero. The minimum and maximum values reset at the rising edge of the set operand. After reset
to zero, calculation of minimum and maximum apparent power demand values continues until the next rising
edge of the reset operand.
The Reset Demand operand doesn't reset the current value of the demand used by the Apparent Power
Demand function.
OUTPUT RELAY X
Range: Do Not Operate, Operate
Default: Do Not Operate
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
1601-0320 517
Chapter 9 - Monitoring
EVENTS
Range: Enabled, Disabled
Default: Disabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Disabled
LED: ALARM
AND
SETPOINTS
OR
APPARENT PWR DMD
AND
S
FUNCTION:
Disabled LATCH
Alarm Set-Dominant
OR
Command
Latched Alarm R
RESET
Configurable
SETPOINTS
AND
BLOCK:
LED: PICKUP
Off=0
SETPOINTS
OUTPUT RELAYS
OR
Do Not Operate, Operate
SETPOINTS
APPARENT PWR DMD FlexLogic Operands
MEASUREMENT TYPE: ApprntPwr Dmd PKP
APPARENT PWR DMD
THERMAL 90% RESPONSE SETPOINTS
TIME:
SETPOINTS APPARENT PWR DMD
SIGNAL INPUT: APPARENT PWR DMD APPARENT POWER PICKUP:
Apparent Power Inputs TIME INTERVAL:
Calculate: RUN
Three-Phase Power 1 Apparent Demand S Demand PICKUP
Apparent Power (S)
Min Apparent Demand
Max Apparent Demand ACTUAL VALUES
Not available in 869 Reset Min & Max Apparent Pwr 1 Apparent Dmd
Demand to 0 Pwr 1 Min Apparent Dmd
Pwr 1 Max Apparent Dmd
SETPOINTS
RESET DEMAND:
Off=0
518 1601-0320
Chapter 9 - Monitoring
removed when the positive Watt hours stored at last pulse was 24.000 MWh, when control power is re-applied a
pulse occurs at 34.000 MWh if the energy increment is set at 10.000 MWh.
1. The Auxiliary Output relay(s) used for this element must be set to Self-Resetting. The pulses consist of a
one second on-time and a one second off-time. This feature is programmed such that no more than one
pulse per two seconds is required.
2. The relay is not a revenue class meter and cannot be used for billing purposes.
3. Energy quantities are displayed in MWh and MVarh, with resolutions of 1 kWh and 1 kVarh respectively.
Path: Setpoints > Monitoring > Functions > Pulsed Outputs
FUNCTION
Range: Disabled, Enabled
Default: Disabled
SIGNAL INPUT
Range: Power x (Dependent on order code)
Default: Power 1
This setting provides the power element selection for the CT and VT bank identification.
1601-0320 519
Chapter 9 - Monitoring
The setpoint specifies the positive VARhours threshold pulse increment after which the output pulse and output
operand are set.
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-Reset
520 1601-0320
Chapter 9 - Monitoring
$ $ $ $
) ) ) )
# # # #
4 4 4 4
+ + + +
3 3 3 3
! ! ! !
2 2 2 2
[ [ [ [
1 1 1 1
\ \ \ \
0 0 0 0
'
'
/ / / /
) ) ) )
'
. . . ' .
,
,
+ + + +
,
%
,
% w
- - - -
'
[ [ [ [
'
*
t
) ) ) )
% % ( % % ^
o
( ^
] ]
' '
& &
5 % 5 5 % 5 m
c c
b b
c c
b b
1 1
. .
? ?
% %
? ?
> >
/ /
= =
> >
= =
< <
* *
/ /
< <
9 9
- -
9 9
* *
E E
/ /
G G
8 8
( ( ^ ^
P P
7 7
Z Z Z Z
7 7
- - - -
1 1
. .
- - - -
1 1 1 % 1 %
` `
? ?
@ @
> >
= =
? ?
>
>
< <
> >
>
>
D
D
= = 9 9
C
C
D
D
C
C
1 B
< < B
E E
B
B
?
? .
.
9 9
G G
1
?
?
1
P P
A
A
8 8
.
A
%
A
9
9
7 7
7 7
9
9
E
E
1
; ;
; ;
8 G
G
8
X
_ _
: :
P
P
7 -
7
9 9
X
9 9
Y Y Y Y
7
7 /
/
A
E E
( ^
( ^ A
I
8 8
G G
- - - -
7 7
1 1
Z Z
P P
7 7
- - - -
% %
g
&
6
1 %
K K
W W W W
J J
T T T T
U U U U
E E
9
9 9
Q Q Q Q
9 9
F F
E
V V V E V E
K K
I I
U U U U
G
8 8 G G
J J
Q Q Q Q
F F
8 P
P P
7 7
E E
8 P
T T T T
7 7
S S S S
F F
F F F F
F F
R R R R
P P
P P
I I
N N
N N
Q Q Q Q
P P
N N
F F
O O
O O
O O
G G
H N H a N a
M M
J J
G G G G
'
F F F F F F
L L
5
E A E I E A E I
1601-0320 521
Chapter 9 - Monitoring
FUNCTION
Range: Disabled, Enabled
Default: Disabled
NAME
Range: Any 13 alphanumeric characters
Default: Counter 1
UNITS
Range: Any 5 alphanumeric characters
Default: Units
Assigns a label to identify the unit of measure with respect to the digital transitions to be counted. The units label
will appear in the metering corresponding Actual Values Status under Records > Digital Counters.
PRE-SET
Range: -2147483648, 0, +2147483647
Default: 0
The setpoint sets the count to a required pre-set value before counting operations begin, as in the case where a
substitute relay is installed in place of an in-service relay, or while the Counter is running.
COMPARE
Range: -2147483648, 0, +2147483647
Default: 0
The setpoint sets the value to which the accumulated count value is compared. Three FlexLogic output
operands are provided to indicate if the present value is ‘more than (HI)’, ‘equal to (EQL)’, or ‘less than (LO)’ the
set value.
UP
Range: Off, Any FlexLogic operand
Default: Off
The setpoint selects the FlexLogic operand for incrementing the Counter. If an enabled UP input is received
when the accumulated value is at the limit of +2147483647, the counter rolls over to -2147483648 and shows
the alarm ‘Digital Counter 1 at Limit’.
522 1601-0320
Chapter 9 - Monitoring
DOWN
Range: Off, Any FlexLogic operand
Default: Off
The setpoint selects the FlexLogic operand for decrementing the Counter. If an enabled DOWN input is received
when the accumulated value is at the limit of +2147483647, the counter rolls over to -2147483648 and shows
the alarm ‘Digital Counter 1 at Limit’.
SET TO PRE-SET
Range: Off, Any FlexLogic operand
Default: Off
The setpoint selects the FlexLogic operand used to set the counter to the pre-set value. The counter is set at
pre-set value in the following situations:
When
○ the Counter is enabled and Digital Counter 1 Set to Pre-Set operand has value 1 (when the Counter is
enabled and Digital Counter 1 Set to Pre-Set operand has value 0, the Counter will be set to 0).
When
○ the Counter is running and Digital Counter 1 Set to Pre-Set operand changes the state from 0 to 1
(Digital Counter 1 Set to Pre-Set changing from 1 to 0 while the Counter is running has no effect on the
count).
When
○ a reset or reset/freeze command is sent to the Counter and Digital Counter 1 Set to Pre-Set operand
has the value 1 (when a reset or reset/freeze command is sent to the Counter and Digital Counter 1 Set to
Pre-Set operand has the value 0, the Counter will be set to 0).
RESET
Range: Off, Any FlexLogic operand
Default: Off
The setpoint selects the FlexLogic operand for setting the count, either 0 or the pre-set value depending on the
state of the Counter 1 Set to Pre-set operand.
FREEZE/RESET
Range: Off, Any FlexLogic operand
Default: Off
The setpoint selects the FlexLogic operand for freezing (capturing) the accumulating count value into a separate
register with the associated date and time of the operation while resetting the count to either 0 or the pre-set
value depending on the state of the Counter 1 Set to Pre-set operand.
FREEZE/COUNT
Range: Off, Any FlexLogic operand
Default: Off
The setpoint selects the FlexLogic operand for freezing (capturing) the accumulating count value into a separate
register with the associated date and time of the operation while continuing counting. The present accumulated
value and frozen (captured) value with the associated date/time stamp are available as STATUS values. If
control power is interrupted, during the power-down operation, the accumulated and frozen (captured) values
are saved into non-volatile memory.
1601-0320 523
Chapter 9 - Monitoring
HI OUTPUT RELAY X
Range: Do Not Operate, Operate
Default: Do Not Operate
LO OUTPUT RELAY X
Range: Do Not Operate, Operate
Default: Do Not Operate
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
EVENTS
Range: Disabled, Enabled
Default: Enabled
Note:
The counter accumulated value can be reset to zero either by asserting an operand programmed under Reset from the
counter menu, executing the clear Digital Counters command under the Records/Clear menu, or by setting the function of the
counter to “Disabled”.
524 1601-0320
Chapter 9 - Monitoring
0 0 0 [
J
IH 2 )*( J
IH 2 )*( J
IH 2 )*( )*( ZY
X
G 1 ' G 1 ' G 1 ' ' V
& & & & W
,F 30 ,F 30 ,F 30 > - V
2 %$ E 2 %$ + > 2 %$ %$ U
T
1
#"
+
1
#"
!
1
#"
!
#" S
R
E 0 ! 0 0 ! Q
/ / /
4 4 4
/ / /
? ?
,4 ,4 ,4 P -
- - - O ,
K
N
D 9 C M -
,
L
,4 K ,
- ,
-
6
56 , E .,
-, . , :
4 , 6 ,
, 56
- ,
, - 4 6
, 6 6
;<= ;<=
;<= AB AB
65 6
4
8 : @? @?
:9 : : :9 :9 :9
9 > 9 9 6
4
7 6
1601-0320 525
Chapter 9 - Monitoring
The Harmonic detection 1(6) element monitors the selected 2nd to 5th harmonic or Total Harmonics Distortion
(THD), which is present in the phase currents. The relay provides six identical Harmonic Detection elements.
In a distribution network, harmonic detection can be used to monitor spurious harmonics from inverter based
distributed energy resources, and take control actions such as islanding DERs or turning on harmonic filters. During
transformer energization or motor starts, the inrush current present in phase currents can impact some sensitive
elements, such as negative sequence overcurrent. Therefore, the ratio of the second harmonic to the fundamental
magnitude per phase is monitored, while exceeding the settable pickup level, an operand is asserted, which can be
used to block such sensitive elements.
During startup or shutdown of generator connected transformers, or following a load rejection, the transformer can
experience an excessive ratio of volts to hertz, that is, become overexcited. Similarly, the ratio of the fifth harmonic
to the fundamental magnitude can be monitored to detect the overexcitation condition.
Note:
The harmonics monitored in this element is calculated from the phase currents, unlike the second or fifth harmonic differential
current used in the transformer differential element.
Note:
The harmonics are updated every protection pass. The THD is updated every three cycles, which is not recommended as a
blocking signal.
Path: Setpoints > Monitoring > Harmonic Detection > Harmonic Detection 1(X)
FUNCTION
Range: Disabled, Alarm, Latched Alarm, Configurable
Default: Disabled
SIGNAL INPUT
Range: dependent upon the order code
Default: CT Bank 1–J1
HARMONIC
Range: 2nd, 3rd, 4th, 5th, THD
Default: 2nd
This setting selects the specified harmonic or THD to be monitored. The harmonic or THD is expressed in
percent relative to the fundamental magnitude.
PICKUP
Range: 0.1 to 100.0% in steps of 0.1%
Default: 20.0%
526 1601-0320
Chapter 9 - Monitoring
PICKUP DELAY
Range: 0.000 to 60000.000 s in steps of 0.001 s
Default: 0.000 s
OUTPUT RELAY X
Range: Do Not Operate, Operate
Default: Do Not Operate
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Self-reset
1601-0320 527
Chapter 9 - Monitoring
D DEF
SETPOINT
, no pDqr Dstuvw
-
G
! HIJK8
"#$ ,
%&' ! "#$ - ($$)! G=>L
<M;NO9O>
()*+# 23C3 P
SETPOINT
SETPOINT
SETPOINT SETPOINT
SETPOINT . 23 "4C SQTR
000 .32 ./"C3C 2 ,
SETPOINT 223 . . .32" - ( (% U #% V U #%
. 2 2 "4 3 "% % ()
.' " +## )% Q"R " 1 000 /0" 1 . . U' U&X ! +UY SETPOINT
528 1601-0320
Chapter 9 - Monitoring
1601-0320 529
Chapter 9 - Monitoring
For a forward directional fault, the zero-sequence active power is the power loss of Petersen’s coil, which is
negative. For a reverse fault, the zero-sequence active power is the power loss of the transmission line, which is
positive. This method, however, is subject to the following disadvantages:
● The zero-sequence active power will be very small in magnitude for a reverse directional fault. Its value
depends on the power loss of transmission line.
● The zero-sequence active power may be too small in magnitude to be detected for a forward directional fault.
Its value depends on the power loss of Petersen coil.
● High resolution CTs are required
Due to the low magnitude of measured values, reliability is compromised. This product does not use the above
techniques for directionalisation. This product uses an innovative patented technique called Transient Reactive
Power method to determine the fault direction of an earth fault in a compensated network.
Transient Ground Fault Detection (TGFD) in this device comprises three modules:
● Transient Ground Fault Detection module (TGF)
● Fault Type Detector (FTD)
● Direction Detector (DD)
Note:
Note: TGF is implemented for 50Hz only.
530 1601-0320
Chapter 9 - Monitoring
DIRECTION DETECTOR
The Direction Detector (DD) uses a patented technique based on Transient Reactive Power (TRP) to establish the
direction of the fault. Unlike traditional methods, this TRP method does not require high resolution CTs or special
analogue filtering hardware and is therefore cheaper to implement.
It can be shown that the residual voltage and residual current components can be reliably used as discriminative
criteria between a faulty and healthy feeder at 220Hz.
The admittance response of a healthy distributed feeder is shown below using a Pi model:
In the above figure, the phase response of the admittance is consistent at 90o up to frequency f1 (approximately
3000Hz). For a compensated faulty feeder, the admittance response is shown below using a Pi model.
We can observe that the phase angle (and thus, the reactive power flow) changes from 90° to -90° at frequencies
higher than f2. Based on the above, we have clear direction discrimination between a healthy and faulted feeder at
any frequency between f2 and f1 approximately.
Note:
The resonant frequency in the above system is 70Hz. For a perfectly compensated system, this will be 50Hz.
IED’s use an anti-aliasing band pass filter with cut-off frequency of 150Hz. Furthermore, at 220Hz the post-filter
magnitude is approximately 0.5pu, and at 330Hz, it is less than 0.2pu. To avoid any integer harmonics, and to avoid
severely attenuated quantities due to the filter, we have chosen 220Hz as the most suitable frequency for direction
determination.
1601-0320 531
Chapter 9 - Monitoring
In the forward direction, the residual voltage leads the residual current by 90°, and in the reverse direction the
residual voltage lags the residual current by 90°. These criteria can be used to directionalise the fault.
The residual voltage (Vres) after passing through the bandpass filter tuned to 220 Hz, has 90° added to its phase.
The residual current (Ires) is also passed through a 220 Hz bandpass filter, but no phase shift is applied.
After residual voltage and current signals pass through the band pass filter, VN becomes VN’ due to 90º shift:
Figure 202: VN phase shift
Dynamic thresholds
The Transient P and transient Q are calculated during fault conditions to help determine the the fault direction.
The transient active power measurement is computed at nominal frequency. ( P. trans)
The transient reactive power measurement is computed at 220 Hz. (Q trans)
The maximum Values of the Transient P and Q are stored during the fault’s detection and are used for the
calculation of the dynamic thresholds.
After that, at every protection pass the dynamic thresholds are updated as:
● Q negative threshold = -Dir>Qf Pickup + 0.1 * QtransMax
● P negative threshold = -Dir>Qf Pickup + 0.1 * PtransMax
● P positive threshold = Dir>Qr Pickup + 0.1 * PtransMax
The P/Q threshold discriminates between the use of P transient and Q transient in the TGF algorithm. When the
active power is higher than this threshold while the Q transient value are kept below it, the algorithm uses the P
transient as the operate input, otherwise the Q transient value is used instead.
The next figure illustrates the Reactive and active power selection:
532 1601-0320
Chapter 9 - Monitoring
● FTD>VN 8.000 V
● Dir>Qf Pickup 50.0 KW
● Dir>Qr Pickup 21.0 KW
It is important to note that all settings for the TGFD function, including those at 220Hz, can be set based on 50Hz
nominal secondary values. This is because the gain of the 220Hz transient filter is 1.
The inputs to this module are:
● The residual voltage
● The residual current
● FTD>VN (defines the threshold for the TEFD detection ).
● P/Q Threshold (defines the threshold for the selection between P or Q in fault’s detection)
The TEFD outputs two signals to indicate a forward and a reverse fault.
The Direction Detector should be disabled in the case of solid grounded system and ground directional overcurrent
element is enabled. In such case, the directionality will be determined by the ground directional element. Therefore,
TGFD only should be enabled the FTD (Fault Type detector) to detect an intermittent fault or a transient fault.
The following Operands are also available:
Inhibit: used to inhibit the TEF function and reset all associated DDBs
Reset TEF: can be configured as a user-defined manual reset alarms.
1601-0320 533
Chapter 9 - Monitoring
FUNCTION
Range: Disabled, Alarm, Latched Alarm, Trip, Configurable
Default: Disabled
The selection of Trip, Alarm, Latched Alarm or Configurable setting enables the TEFD function.
When Alarm is selected and the TGFD operates, the LED ALARM will flash, and will self-reset, when the
operating conditions are cleared.
When Latched Alarm is selected and the TGFD operates, the LED ALARM will flash during the TGFD operating
condition, and will be alight steadily, after the conditions are cleared. The LED ALARM can be cleared by issuing
a reset command. The Output Relay #1 Trip will not operate if Latched Alarm or Alarm setting is selected.
The Output relay #1 Trip can be configured to operate using the TEFD output operands and the FlexLogic.
The output relay #1 Trip will operate only when Trip function is selected, and the TEFD operates. The LED
ALARM will not turn on, if the TEFD operates when set to function Trip.
When Configurable is selected, neither the trip output, nor the ALARM LED will turn on automatically. They
need be configured using their own menus, and FlexLogic operands.
VT INPUT
Range: Ph VT Bnk1-J2, Ph VT Bnk2-K1
Default: Ph VT Bnk1-J2
This setting provides selection of the voltage signal input.
CT INPUT
Range: CT Bank1-J1, CT Bank2-K1
Default: CT Bank 1-J1
This setting provides selection of the current signal input.
VN THRESHOLD
Range: 0.02 to 0.40 in steps of 0.01 x VT
Default: 0.05 x VT
This setting sets the voltage pickup level specified per times VT.
DIRECTIONAL STATUS
Range: Disabled, Direction Detector, Ground OC Dir
Default: Direction Detector
This setting determines the direction of measurement for the TEF element.
DIRECTIONAL MODE
Range: Standard, Advanced
534 1601-0320
Chapter 9 - Monitoring
Default: Standard
This setting determines which setting will be used for direction element
PQ THRESHOLD
Range: 5.0 to 2000.0 in steps of 0.1 KW
Default: 30.0 KW
This setting defines the PQ shift threshold in secondary primary values. Although the unit for this setting has
been expressed as KW; it summarizes the use of KW for active power P and KVar for reactive power Q.
When the reactive power is very small, but the Active power is larger than threshold, the Active Power is used to
detect the fault direction
DIR>QF PICKUP
Range: 10.0 to 2000.0 in steps of 0.1 KW
Default: 50.0 KW
This setting sets the pick-up threshold of the P and Q transition in primary values to detect a forward direction
fault.
DIR>QR PICKUP
Range: 5.0 to 2000.0 in steps of 0.1 KW
Default: 21.0 KW
This setting sets the pick-up threshold of the P and Q transitions in primary valuers to detect a reverse direction
fault.
Note:
[X]: Total No of Ground IOC elements and No of Ground TOC Elements, respectively
FTD> STATUS
Range: Disabled, Enabled
Default: Disabled
This setting enables the fault type detection in TEF element.
FTD> VN [ANSI]
Range: 0.02 to 0.40 in steps of 0.01 x VT
1601-0320 535
Chapter 9 - Monitoring
Default: 0.04 x VT
This setting sets the pick-up threshold for the resides voltage of the fault type detection element.
RESET TIME
Range: 30 s to 12000 s in steps of 30 s
Default: 60 s
This setting sets the reset timer.
RESET TGF[X]
Range: Off, Any FlexLogic Operand
Default: Off
This setting resets the Transient Ground Fault Detection element.
BLOCK
Range: Off, Any FlexLogic Operand
Default: Off
The TGFD element will be blocked, when the selected operand is asserted.
OUTPUT RELAYS
Range: Do Not Operate, Operate
Default: Do Not Operate
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-Reset, Latched
Default: Latched
536 1601-0320
Chapter 9 - Monitoring
45 45" +06
789;B7><C;7
FLEXLOGIC OPERANDS
789 @7>A:D
FLEXLOGIC OPERANDS
Figure 205:
1601-0320 537
Chapter 9 - Monitoring
INTERNAL VALUES
INTERNAL VALUES
#/!$)
45 /&0( 12,3
!" #!$$ %&'()*
++, -.
INTERNAL VALUES
7 I F*!$
INTERNAL VALUES
7 # F*!$
Figure 206: Scheme of the calculation of P Trans, Q Trans and U RMS inc
538 1601-0320
Chapter 9 - Monitoring
SETTING
,-./ 01234
d! & ' FLEXLOGIC OPERANDS
% 5 6$ #
() *+
!"# $
SETTING
abc
dOO C
<> <A.@3 01234
SETTING !7% i j elhlnmop
SETTING
BC
<=> 0?43@?-./
<> DE- 01234
!"# !7%
F ' INTERNAL STATUS
8' 8 $ '9:
% ': #
% GC
8: 8 ; '9:
SETTING
> DE- 01234
D14 H >I <1JKAE : W
D14 H >4 <1JKAE F ' INTERNAL STATUS
C
!7% 6CC % ' Z
XCC
' ; LMN $:O 'P Q R CS6 T ' "UV
Figure 207: TGFD Start, PQ Detector, Small PQ Selector and dynamic Q trans & P trans
1601-0320 539
Chapter 9 - Monitoring
INTERNAL STATUS
JRS NTQMOITPU NMIMOIPQ
VPWGHM
INTERNAL STATUS
FLEXLOGIC OPERANDS
INTERNAL STATUS Reset Dominant
FLEXLOGIC OPERANDS
' SETTING
A
!) 893 :8+;2<
,= >
?5@
Reset Dominant
Figure 208: TRP Direction detector Module and FA Fault Type Detector scheme
540 1601-0320
Chapter 9 - Monitoring
-
+, ./0 1.123
SETTING
Reset Dominant
- *
+,
Reset Dominant
+LM
-
+, ./0 4256
FLEXLOGIC OPERANDS Reset Dominant
*
- NH?ODA? NPAHPA
+, 2?CDQ R F4256J
Reset Dominant
SETTING
!"#$%& '"%"() FLEXLOGIC OPERANDS
* *K
*
*+
*
FLEXLOGIC OPERANDS
SETTING *
7 ) " 2?@?A BCDE
8 9
FAG HDE? IJ
FLEXLOGIC OPERANDS
-
SETTING
7 ) " :;
< = >
Figure 209: Alarm & Trip outputs signals and Reset scheme
1601-0320 541
Chapter 9 - Monitoring
RTD
1
8
Note:
To enhance the accuracy of the RTD, ensure all 3 cables are of the same length and gauge. In addition, the Compensation
and Return wires must be connected on the RTD side and not on the relay side.
RTD Inputs
The relay has two methods of supporting RTD inputs.
● I/O cards installed in the relay can supply up to 13 RTDs.
● An optional CANBUS-based Remote Input/Output module (RMIO unit) can also be installed, which can
monitor up to 12 additional RTDs (referred to as RRTDs). The RMIO unit supports 6, 9, or 12 RRTDs.
Hardware and software is provided to receive signals from external Resistance Temperature Detectors (RTDs) and
convert these signals into a digital format for use as required. These channels are intended to be connected to any
of the RTD types in common use.
Depending on the order code (Advanced Monitoring option selected), the relay is supplied with one combo card
consisting of one RTD input, one Ohms input, four DCmA inputs and seven DCmA outputs. Additionally, the relay
can be furnished with up to two optional RTD cards, each of them having 6 RTD input channels. Only slots B and C
can accept the optional RTD cards.
Note:
If only one RTD card is ordered at the time the relay is ordered, this RTD card is always shown in slot B. The order code
selection does not allow for an RTD card in slot C, if no RTD card is ordered in slot B.
542 1601-0320
Chapter 9 - Monitoring
Note:
An I/O card L ordered in Slot G will contain an additional RTD input on the card. It will be the highest RTD number shown (i.e.
if 1 additional RTD card is used, then the low voltage I/O (LVIO )RTD will be RTD #7).
An alphanumeric name is assigned to each channel; this name is included in the channel actual values. It is also
used to reference the channel as the input parameter to features designed to measure this type of parameter.
Selecting the type of RTD connected to the channel configures the channel. The conversion chart is shown in the
following table.
1601-0320 543
Chapter 9 - Monitoring
Note:
RTD type copper (Cu) is only available when order code option ‘S’ is chosen for Slot B or C.
RTD Protection
The relay can monitor up to 12 RTDs and 12 RRTDs, each of which can be configured to have a trip temperature
and an alarm temperature. The RTD Temperature protection menu will be seen on the relay upon availability of RTD
input/inputs. The RRTD Temperature protection setpoints can be seen only if the relay has the RMIO module
installed and validated. The minimum RTD Temperature requirement is to set the setpoint TYPE. The default value
for TYPE, for each RTD is 100 Ω Platinum. The protection RTD Trip, and RTD Alarm from the menu are
optional. They respond to directly measured RTD temperature. The Alarm temperature is set slightly above the
normal measured temperature for the transformer top-oil, bottom-oil, or LTC oil. The Trip temperature is normally
set at the maximum permissible oil temperatures defined as dangerous for the transformer and the transformer
insulation.
This element also monitors the RTD broken connection and blocks the RTD trip and alarm functions if the RTD
connection is detected as Open or Shorted and generates RTD Open and RTD Shorted FlexLogic operands. An
RTD is detected as Open when the RTD connection is either open or the temperature is greater than 250°C. An
RTD is detected as Shorted when the RTD connection is either shorted or the temperature is equal to less than
-40°C.
Note:
The RTD input is active regardless of whether or not, the RTD Trip, or/and RTD Alarm functions are enabled.
TRIP FUNCTION
Range: Disabled, Trip, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
If a trip is not required from the RTD, select Configurable. This enables the RTD without producing a trip.
NAME
Range: Up to 13 alphanumeric characters
Default: RTD 1
TYPE
Range: 100 Ω Platinum, 100 Ω Nickel, 120 Ω Nickel
Default: 100 Ω Platinum
544 1601-0320
Chapter 9 - Monitoring
APPLICATION
Range: None, Stator, Bearing, Ambient, Other
Default: None
The setting allows each individual RTD to be assigned to a group application. This is useful for some
applications, which require group measurement. Selecting None means that the RTD operates individually and
is not part of any RTD group. Common groups are provided for needs at rotating machines applications such as
Ambient or Bearing.
VOTING
Range: Off, RTD 1, RTD 2….RTD 12
Default: Off
This setting selects the RTD that must also exceed this RTD’s Trip Temperature for a trip to occur. Selecting the
same RTD to which the element is related to, has the same effect as selecting “Off”.
TRIP TEMPERATURE
Range: 1°C to 250°C in steps of 1°C (33°F to 482°F in steps of 2°F)
Default: 155°C (311°F)
ALARM FUNCTION
Range: Disabled, Alarm, Latched Alarm
Default: Disabled
ALARM TEMPERATURE
Range: 1°C to 250°C in steps of 1°C (33°F to 482°F in steps of 2°F)
Default: 130°C (266°F)
1601-0320 545
Chapter 9 - Monitoring
Default: 2 s
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Latched
hijklmnj 0!
6 & "7 -="> 3?6 '!! 37#
\g^T 345 # !$ ! ! N0
hijklmnj "! "7
!P Q 0! ! 898 * C¤¥)> $D &#
dX]T STUVUWXYZT[ ! :;< +
,
S\e f \T]^T_XW`_T
abYcT_WVbY FG HGIJ KLM
3" B CD'6
/0 0! 3" B CD6E6
/0 6 & "7
345
/0 "! "7
R Q/0 0!
!898 !:;<
'!! 37 N
" 5! '!O '!
-="> /0
! *
+,
"#$ -=" >
1 6 & 1
2 o 2
* p *
+ 1 q +
, 2 o ,
p A
q 1
2 -/@
3=A= 3
% & 00$
Srd
'() S x stuva
FG HGIJ KLM
3" B /0 '6
3" B /0 6E6
*
+ Srd
,
S £[wuva
/0 '!! 37 N
" 5! '!O'!
/0 !
"#$ FG HGIJ KLM
/0 1 h 3" B '
2
-! .$ /0 k k 3" B A.!$
\T]^T_XW`_T eVU^yXgz
{aTyUV`U| }X~_TY~TVW LJ ¡LG ¢LG¡
3" B 0!
546 1601-0320
Chapter 9 - Monitoring
FUNCTION
Range: Disabled, Alarm, Latched Alarm
Default: Disabled
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Latched
B!C
D
E
F
$
!"# %
$ D
E
% F
I
'GH
1601-0320 547
Chapter 9 - Monitoring
Note:
The MODBUS ACTIVITY TIMEOUT specifies the minimum time without Modbus communication. This timeout is used to
declare the Modbus ‘Loss of Communication’ state. The MODBUS ACTIVITY TIMEOUT must be set to a value other than 0
for the Loss of Communication”monitoring to work properly.
Note:
MODBUS ACTIVITY TIMEOUT is set under: Setpoints > Device > Communications > Modbus Protocol
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
INTERFACE
Range: Serial, Serial + Ethernet, Ethernet, All
Default: Serial
Only the protocols associated with the selected interface are shown in this screen as options. For example, if
“Ethernet” is selected, select the Ethernet protocols to monitor. The Ethernet protocols selection is defined as
EthernetProtocolBitmask bitmasks.
MODBUS
Range: Off, On
Default: Off
PICKUP DELAY
Range: 0 to 600 s in steps of 1
Default: 2 s
OUTPUT RELAY X
Range: Do Not Operate, Operate
Default: Do Not Operate
548 1601-0320
Chapter 9 - Monitoring
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Latched
>?@A :5;<
+
, ./01230 .43/43 5062789:5;<=
-
E F%
+
G( #HI*J ,
-
FK(L >?@ R>R5S A
B
MI#K C
#"'N*J MI#K
+ C D
&(m$K#HI* ,
- Z
\]^_`
T03
@VWX2X3
UVWW2XY
5?T?:
+
,
-
FO F PMQ!
!"#"$
O% O GPMQ
%&#'"()* cd edf ghijkfil ghijkfi
O
>?@A <;Uab<
nopqorstu rvpwxyz{
OO
1601-0320 549
Chapter 9 - Monitoring
550 1601-0320
CHAPTER 10
CONTROL
Chapter 10 - Control
552 1601-0320
Chapter 10 - Control
1601-0320 553
Chapter 10 - Control
h G
!"#$% &'#()#' *"+,'#-(.,/
S D G
KNQRNUWXYZ K[RWd\]U
y e ijk lk mn
I B789:87 >?@A7?<
O `paAc_ >?@A7?<
qrstuvw xz{ut |}zts}w
Po o
T
Mo o
B789:87 ;9a<=78
Co o
^7c ;<9H_
Fo
`b@c_7?c_8c:
g
VE ;=H8 ;9a<=78 J
VE ;=H8 ;9a<=78 f
554 1601-0320
Chapter 10 - Control
Note:
SET GROUP 2 defaults to PB 8 ON (ALT SETTING) for some order codes.
1601-0320 555
Chapter 10 - Control
EVENTS
Range: Disabled, Enabled
Default: Enabled
556 1601-0320
Chapter 10 - Control
! ! ! ! ! !
p
o
$ $ $ $ $ $ mn
l
"# "# "# "# "# "# k
j
1 2 3 4 5 6 j
i
h
g
F . F . F . F . F . F . e
T
EH
=
>T
@
I I
H >
=E K
T =
B ?
@ J
T
=
?
>
%&D %&D %&D %&D %&D =
T
%&D
%&D '(
%&D '(
%&D %&D %&D %&D %&D %&D
%&D '(
%&D '(
%&D '(
'(
'(
...
a b
` 7 7 c
_7 7^ ^ ^ 7^ d7
^ ^
61
1 2 3
< < < <
C C
C
C
1 $ $ $ $ $ 8; S
G 8; XY 0: " " " "
#" #" #" #" #" 0: 2 3 4 5 6 X 2 3 4 5 6 9: 2 3 4 5 6 C OO C OO C OO C OO
2 3 4 5 6 98 NV NV NV NV NV ,W0 NV NV NV NV NV , Y9 NV NV NV NV NV # # # ... #
07/ UP UP UP UP UP :
W: UP UP UP UP UP \-, :0 PU PU PU PU PU
[ ] M M M M M
S S
-, MR MR MR MR MR 09 MR MR MR MR MR [0 R R R R R
+ QP QP QP QP QP + QP QP QP QP QP
7 PQN PQN PQN PQN PQN
O O O O O f)* NM NM NM NM NM )*f NM NM NM NM NM Z ML ML ML ML ML
A
L L
L L
L
L L
L L
L
1601-0320 557
Chapter 10 - Control
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Default: Disabled
PICKUP DELAY
Range: 0.10 to 600.00 s in steps of 0.01 s
Default: 1.00 s
OUTPUT RELAY
Range: Do Not Operate, Operate
Default: Do Not Operate
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
EVENT:
Range: Enabled, Disabled
558 1601-0320
Chapter 10 - Control
Default: Enabled
TARGET:
Range: Self-reset, Latched, Disabled
Default: Self-reset
1601-0320 559
Chapter 10 - Control
32
1
0
/
.
-
,)'
*
+
*& 67
+
%
*' *
)( F
)
' lF i 9 cb cb
& NM E 9O T
12
% KLJ D
h
! `a_ T
`a_ T=
H I j W^ W^
0 '*B fg4 9 : :
e8d ! \][ S \][
S
<
9O YZX YZX
<
T WV WV
G 0 O U U
F
) B
E
"#$ "#$ "#$ E
D
C
k
f4
8e
T @A
=
?@
T
"#$
67
"#$ "#$
"#$
67
R
{
9: z m]
R 9R 9R
T y m`a
9R ~ x Z P! P!
84
!P o
c 9 9 u
5 }
o mn` h h Q Q
9 } w m r r sO ;Q
4 Q P Yv q q
RQ Y P VbW P
8
R P
t
R
5 ;: >P = gg qP e
| \U p p Q Q
! 9 > u U P 99 99
4 8
O
8< >
4 4 | 4R 4R 4 g 4 g
560 1601-0320
Chapter 10 - Control
Note:
A reverse power element may not be suitable when set to a very low setting, particularly under conditions of large reactive
loading on the generator. Under such conditions, we recommend low forward power.
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Default: Disabled
ARMING INPUT
Range: Off, Any FlexLogic operand
Default: Off
This setting selects a specific arming input from FlexLogic operands. Normally, sequential shutdown is armed/
initiated from digital input (from an external device).
Note:
NOTE: The Arming Input should remain ON/latched until the sequential shutdown operation is executed.
POWER DIRECTION
Range: Forward, Reverse
Default: Forward
This setting provides options for the direction of power flow.
PICKUP MW LEVEL
Range: 0.02 to 0.99 x Rated in steps of 0.01
Default: 0.05 x Rated
When the measured 3-phase total power falls below the setting of the forward pickup power level, or exceeds
the reverse power pickup level for the period of time specified, an OP operant is issued.
PICKUP DELAY
Range: 0.20 to 180.00 s in steps of 0.01 s
Default: 10.00 s
1601-0320 561
Chapter 10 - Control
OUTPUT DELAY
Range: Do Not Operate, Operate
Default: Do Not Operate
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
EVENT:
Range: Enabled, Disabled
Default: Disabled
TARGET:
Range: Self-reset, Latched, Disabled
Default: Self-reset
562 1601-0320
Chapter 10 - Control
)%
$
!T
(
1
#"
@
! !?
9
?>
O <
9;
O
z43 L
*+ y r
S
I xv& {L
us us
I~ om ^ om
YX r P
%$ W C H R alk ] la
T!> K VU Q G nd k P
< P L/ S ji h\[ 5L
< ijg v-
;9 fgc qe
JI T D/ ba [ fc
ba
w
; `_ v
AN AN AN H C
; _`
HG !
E
}
S x:&
D
S P
78
P
t7
4 P 4 P
: :
5
S p /,L P p 5/L P
L r 6|
LZ r, |
D
R /3 rD 5 rD
3
r 2 2
S R P
/
r2/ P
rM r /
P
rM
R F pR
P P | |
AN
*+
JI)
S
S S O S
P G~
: r'
0
= & S 9 P 4
rM
S S 0 1 " &
r' -, .Z5 I I# S r3
F r & L / B .= R& 2
O ?(
D v P/
1601-0320 563
Chapter 10 - Control
Note:
Note that one pair of PBs is used for breaker control, and another pair of PBs is used for switch control.
If contact inputs or other FlexLogic operands are used while the Select Before Operate (SBO) mechanism is
enabled, the breaker or the switch shall first be selected using the relay PBs, and then opened or closed using the
designated relay panel or cubicle PBs. (The SELECT BEFORE OPERATE setpoint is only available for relays
supporting a single breaker.) If the SBO mechanism is disabled while the relay supports configurable single line
diagrams (SLDs), only the breaker PBs either on the relay front panel or mounted nearby will work. The menu
setpoints for local switch Open and Close are hidden and deactivated.
If the relay does not support configurable SLD, the setpoints for local switch Open and Close are omitted from the
menu.
While in Local Mode, the letters LM are displayed on the relay display banner. In addition, an LED can be
programmed to turn ON when the relay is set to Local Mode. By default the relay comes with one LED programmed
to show Local Mode.
In Local Mode, control for the breakers and disconnect switches can be accessed from the relay front panel (PBs
programmed for Open and Close) or by contact inputs for Open and Close from PBs installed near the relay. Hard
coded SLD PBs are designated for Tag, Block and Bypass Block for each component upon selection. In this mode,
the LOCAL OPEN and LOCAL CLOSE setpoints for Breaker Control or Switch Control (see the respective logic)
are active.
Remote Mode
When Remote Mode is enabled, the switches are controlled (open/close) from any assigned FlexLogic operand,
contact input, virtual input, virtual output, remote input, or via communication. The Control Mode menu is designed
to switch the control for both breakers and switches to either Remote Mode (LOCAL MODE setpoint set to Off, or
the selected Local Mode input de-asserted), or Local Mode (LOCAL MODE setpoint asserted).
Navigation
The 8 Series front panel provides navigation pushbuttons (PBs) which highlight the component (breaker or
disconnect switch) from the single line diagram. The navigation PBs (Up/Down or Up/Down/Left/Right depending on
relay front panel model), are used to browse through the Single Line Drawing (SLD) components. These PBs are
used for SLD navigation only. The navigation starts with highlighting the first breaker, and then goes through all
other components in sequence, until the last one (breaker or switch). Only the breakers and switches included in
the SLD from the display will be browsed (navigated).
564 1601-0320
Chapter 10 - Control
Note:
The selected component from SLD will be deselected if either the time programmed in setpoint Bkr/Sw Select Timeout
expires, or the ESCAPE pushbutton is pressed. The HOME button will not de-select the selected object. To navigate to home
page, the component must be first de-selected on the SLD page.
The programmed PBs for breaker or switch Open and Close can be used only in local mode when an active object
is selected in the SLD. The selected device can be opened or closed provided it is not blocked or tagged. If no
operation is detected, the selection is removed, and the selected PB must be pressed again to enable the selection.
The local mode breaker selection and operation is only active if the user has proper level security access.
1601-0320 565
Chapter 10 - Control
G HI&JGIK
}~}
Y TUXW
&' ( '
@
?
}}
G HIoqIMK )*+,-./+
012345 467689 :;<6=>9
!"#$%
[\]^\_`ab _c]defg)
LM N h
LM O h
LM P h
LM O
LM P
opqIr q( ' s ' h F(' '
tu v (' s (w sxyh h yhh
i N
( z o y'h u' h 'F(' '{{h
sw ( '|y hyx txz
i O
A D
B i P E
C
i j
otx Gy'(uy' i k
i l
i m
i n
[\]^\_`ab _c]defg)
F(
i N h
i O h
i P h
i j h
i k h
i l h
i m h
i n h
<= >=?@ABC
./012134 IJKLJMNOP MQKRSTU
789:;
/54 06/2 #D E"
G
H
IJKLJMNOP MQKRSTU
E V$'W
566 1601-0320
Chapter 10 - Control
LMNOMPQRS PTNUVWX
[
LMNOMPQRS PTNUVWX
EF%)) !G HII
!" #$!%& '%(
) # *!+&"%"
:; <;=:>??
;@ABCD
,-./0/12 LMNOMPQRS PTNUVWX
J
K
LMNOMPQRS PTNUVWX
1601-0320 567
Chapter 10 - Control
U2V846;V
MWXXY X
@ AB Z [
012314567 4829:;< 012314567 4829:;<
>P QRS =B MN ?OO
=T QRS =B
012314567 4829:;<
'( )*+,- MN ?
$%& !
"! #
./
012314567 4829:;<
=>? @ AB CDEFDDGHIJKL
Note:
The pushbuttons, Tag, Block and Bypass Block are used for both breakers and switches when selected in the SLD. Only one
component at the time can be selected in the SLD.
Note:
Tagging, blocking, or bypassing block can be performed in Local Mode, and only when the component (breaker or switch) is
selected in the SLD. The applied action of tagging, blocking or bypassing block is retained for this component after it’s been
deselected. To change the status of the applied action, the component need be reselected.
Note:
The Local Mode control allows programming of separate pair of PBs for Open and Close commands to breakers and for Open
and Close commands to switches. If desired, one pair of pushbuttons can be programmed for Open and Close commands to
both breakers and switches.
568 1601-0320
Chapter 10 - Control
SETPOINT LM
AND
Select Before Operate
Disabled = 0, Enabled = 1
from Bkr/Sw selection logic FLEXLOGIC OPERAND
SBO Enabled
FLEXLOGIC OPERAND
BKR1 Selected
AND
AND
SETPOINT
Breaker Local Open
Off=0, Pushbutton # ON =1
869
PB Local Stop
PB BKR Local Open FLEXLOGIC OPERAND
AND
FLEXLOGIC OPERAND
BKR1 Rem Blk Open
AND
FLEXLOGIC OPERAND
OPEN command
To Selected BKR1 Trip
BKR1 Rem Blk Open By Setpoints/System/Breakers/
BKR1:
Output
Relay ( Ready = 1)
from Breaker status detection logic
OR
FLEXLOGIC OPERAND BKR 1: Trip Relay Select
AND
BKR1 Opened
FLEXLOGIC OPERAND
Bypass Block ON
FLEXLOGIC OPERAND
AND
AND
FLEXLOGIC OPERAND
BKR1 Local Close
FLEXLOGIC OPERAND
AND
FLEXLOGIC OPERAND
BKR1 Rem Blk Cls By
FLEXLOGIC OPERAND
AND
BKR1 Closed
FLEXLOGIC OPERAND
AND
FLEXLOGIC OPERAND
AND
The programmed value Bypass, Sync 1 Cls Perm, or Sync 2 Cls Perm for the setpoint Close
Sync Spvn BKR1 from BKR1 Control menu applies
894200C1
1601-0320 569
Chapter 10 - Control
J
o"
4 o"
o"
$ Ç#"o
J
I !"#
4 (II#
H"n $% !"#
¨
© !"# 'no
ª
º»¼½
H"n $% !"# $&
e\bgf
¬_\ h²°[e³ d[b[]d f`[`e[°\g a\¯°e ¨ [\ \][^][
© _`abc
ª
JKLMNOPLQRJSQLKTR d`a`e[`f [\
I !"#"o JKLMNOPLQRNPLkNlR JUOLVWKQRJXYZ
=>?@A B =>@CA D EF \^`g hij
JUOLVW NPLkNlR
¬_\ ®b¯¯°g¯ a\¯°e JXYZ ;< G !"# H"& ""I
)* + ,-./ ).0123/
5« 5 676
4 89:
¬_\ ·\eba ´a\eµ a\¯°e
$%
¨
©
ª $% !"# $&
J
I '("
4 (II# '("
¨
¾ ¿ÀÁÂÃ Äux|t ÅtuysÆ ©
ª
'(" 'no
¬_\ h²°[e³ ¹\g[_\a a\¯°e
¨
©
'("o ª
¨
©
ª $% '("
¨
©
ª $% '( $&
570 1601-0320
Chapter 10 - Control
Note:
For relays supporting single breaker control, the SW Local Open and SW Local Close setpoints appear in the menu only if the
relay is ordered with Advanced SLD; and the SELECT BEFORE OPERATE setpoint is enabled. In all other cases, these
setpoints are hidden and inactive.
Note:
When SBO is disabled, all local and remote flags such as blocking, bypassing, and tagging are reset.
Setting the SBO to Enabled enables the navigation and the selection of a component from the SLD, so that the
pushbuttons Open or Close from the front panel (or those mounted in close proximity to the relay) can be used in
Local Mode only after the component is selected. All flags such as blocking, bypassing and tagging can be
initiated during this mode. Blocking and bypassing can also be initiated remotely, when in Remote Mode.
LOCAL MODE
Range: Off, On, Any FlexLogic operand
Default: Pushbutton 5 Off
The LOCAL MODE setting places the relay in Local Mode. The relay is in Remote mode, if not forced into Local
mode by this setpoint (i.e. LOCAL MODE is disabled, or the selected input de-asserted). When in Local Mode,
both Breakers and Disconnect switches can be controlled using the faceplate pushbuttons and SLD
pushbuttons.
1601-0320 571
Chapter 10 - Control
MANUAL CONTROL
Range: Off, Any FlexLogic operand
Default: Off
Manual Control mode allows flexibility to use the open and close operation of the switch via front panel
pushbutton even during the Remote mode of operation.
Note:
hen you close a selected breaker locally using a relay pushbutton, Synchrocheck supervision is used, as defined by the
setting value configured for the setpoint Close Sync Spvn BKR[X] from the BKR[X] Control menu. For example, if you
select the value Sync 1 Cls Perm in the Close Sync Spvn BKR1 setpoint, initiation of the BKR Local Close command will
not close BKR1 unless the Synchrocheck 1 permits closing by producing a Sync 1 Cls Perm signal
SW LOCAL OPEN
Range: Off, Any FlexLogic operand
Default: Pushbutton 1 ON
This setpoint is active, when Local Mode is activated. The switch open command can be initiated by the
configured pushbutton. The setpoint appears in the Local Control Mode menu only when advanced SLD is
selected when ordering the relay.
SW LOCAL CLOSE
Range: Off, Any FlexLogic operand
Default: Dependent on order code
572 1601-0320
Chapter 10 - Control
This setpoint is active, when Local Mode is activated. The switch close command can be initiated by the
programmed faceplate pushbutton. The setpoint appears in the Local Control Mode menu only when advanced
SLD is selected when ordering the relay.
TAGGING
Range: Enabled, Disabled
Default: Enabled
When enabled, tagging control is enabled and the TAG key is displayed on the front panel interface. When a
breaker or a switch is tagged both the local and remote control of the device is inhibited.
Note:
Tagging is applied only from the TAG key and is mostly used for maintenance purposes, and in general when either the open
or close control must be inhibited. The tagging cannot be bypassed and can only be disabled (untagged) by pressing the TAG
key again.
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
1601-0320 573
Chapter 10 - Control
Note:
The breaker flags Remote Block Open, Remote Block Close, Bypass Rem Blk Open and Bypass Rem Blk Close are
inhibited, when the setpoint SELECT BEFORE OPERATE residing under Local Control Mode menu is disabled. The breaker
remote open and close commands are operational.
Note:
The relay provides control of up to three breakers, depending on the order code. An additional remote breaker status is
available for HMI status only.
REMOTE OPEN
Range: Off, Any FlexLogic operand
Default: Off
The setting specifies the input which, when asserted, initiates a Trip command to output relay selected to open
the recloser. When the selected input is asserted, the Trip contact is energized and stays energized until the
input drops off, the breaker opens, and the selected Trip seal-in time expires. This setpoint provides the flexibility
to operate the Trip output relay by selecting an operand from the list of FlexLogic operands, contact inputs,
virtual inputs, or remote inputs. For example the operand Trip Bus 1 Op can be selected to activate this output
according to the Trip conditions configured under the Trip Bus 1 menu.
REMOTE CLOSE
Range: Off, Any FlexLogic operand
Default: Off
The setting specifies the input which, when asserted, initiates a Close command to the output relay selected to
close the breaker. This setpoint provides flexibility to operate the output relay by selecting an operand from the
list of FlexLogic operands.
574 1601-0320
Chapter 10 - Control
Note:
If the supervision is not bypassed and Close is applied for an application where the breaker is located on radial feeders, or the
line is powered by one source only, the DEAD SOURCE PERM setpoint from the Synchrocheck menu shall not be disabled.
1601-0320 575
Chapter 10 - Control
012
!"
012
012
&' ()*+, -."' 012
# $% 34
&56) &-7 -89:6;97
/ ()*+, 012
-."' # $% &56) /9-9 -89:6;97
34
012
012
012 34
&56) 6 -89:6;97
*<==)>-)?"
Figure 224: IEC 61850 Control Authority Settings Logic Diagram
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
576 1601-0320
Chapter 10 - Control
&
&
¤®¯¦°±®ª'I
K & sI
Bjklm nAopqklpq>pr EF
1601-0320 577
Chapter 10 - Control
Note:
The switch Remote Block Open, Remote Block Close, Bypass Remote Block Open and Bypass Remote Block Close
flags are inhibited, when the setpoint Select Before Operate residing under Local Control Mode menu is disabled. The
remote open and close commands are still operational.
Path: Setpoints > Control > Switch Control > SW 1(X) Control
REMOTE OPEN
Range: Off, Any FlexLogic operand
Default: Off
This setting specifies an input which when asserted initiates the open command to the switch. This setpoint is
active only when the operand assigned for Local Mode is de-asserted, or Local Mode is set to “Off”.
REMOTE CLOSE
Range: Off, Any FlexLogic operand
Default: Off
This setting specifies an input which when asserted initiates the close command to the switch. This setpoint is
active only when the operand assigned for Local Mode is de-asserted, or Local Mode is set to “Off”.
OPEN SEAL-IN
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.000 s
This setting specifies the seal-in time of the open commands due to an operator initiated manual or remote open
command to the disconnect switch.
CLOSE SEAL-IN
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.000 s
578 1601-0320
Chapter 10 - Control
This setting specifies the seal-in time of the open commands due to an operator initiated manual or remote close
command to the disconnect switch.
Note:
To maintain the close/open command for a certain time, do so by either using the seal-in timers Open Seal-In and Close Seal-
In, or the setpoint "Seal-in" from the output relays, or FlexLogic.
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
1601-0320 579
Chapter 10 - Control
*+,+-. /01
736 89 !:
w
x
*+,+-. /01
L6y !:
*+,+-. /01
2! )69
*+,+-. /01
*+,+-. /01
!() 9
*+,+-. /01
!()9
qrq
Ss
S
% abcdefbghigbajh t
&
!() ' keblmaghnop
VWXYZ [ VWY\Z ] ^_ r u v
!"" # $ ;<==>?@
` !() 65 3
AB C DEFG AFHIJKG DP
L MNM
$ HGO
%
234 !() &
'
!"" # $
%
&
'
%
25(6 24 !() &
'
!"" # $
*+,+-. /01
*+,+-. /01
*+,+-. /01
qrq
TR
Ss
% S
& abcdefbghigbajh
t
' keblmaghnop
VWXYZ [ VWY\Z ] ^_ t uv
!"" # $ ;<==>?@
` 65 3
AB C QIDAF AFHIJKG DP
L MNM
%
234 & $ HGO
'
!"" # $
%
&
'
%
25(6 24 &
'
!"" # $
*+,+-. /01
*+,+-. /01
¡¢£¤
580 1601-0320
Chapter 10 - Control
1601-0320 581
Chapter 10 - Control
Note:
Output Relays configured for Recloser operation are under the Trip Close Logic. Setpoints under Trip Bus are not applicable
to the output relays set under Trip Close Logic.
The relay provides six identical Trip Bus elements. The Trip Bus element allows aggregating outputs of protection,
control elements, inputs without using FlexLogic and assigning them in a simple and effective manner. Each Trip
Bus can be assigned to trip, alarm or the other logic actions. Simple trip conditioning such as latch, delay, and seal-
in delay are available.
Path: Setpoints > Control > Trip Bus 1(X)
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
INPUT 1 to 16
Range: Off, Any FlexLogic operand
Default: Off
These settings select a FlexLogic operand to be assigned as an input to the Trip Bus.
LATCHING
Range: Enabled, Disabled
Default: Disabled
The setting enables or disables latching of the Trip Bus output. This is typically used when lockout is required or
user acknowledgement of the relay response is required.
RESET
Range: Off, Any FlexLogic operand
Default: Off
The trip bus output is reset when the operand assigned to this setting is asserted.
PICKUP DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.000 s
DROPOUT DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.000 s
582 1601-0320
Chapter 10 - Control
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Self-reset
Note:
The Any Trip operand must not be programmed as an input for the Trip Bus function.
1601-0320 583
584
Chapter 10 - Control
FLEXLOGIC OPERAND
Any Trip
SETPOINT
LED: TRIP 8S: To operate Output Relay
FUNCTION:
AND
1(TRIP)
Disabled Configurable in 845 & 859
OR
Trip
OR
R
Latched Alarm
LED: ALARM
Configurable
AND
FLEXLOGIC OPERAND
OR
Any Alarm
SETPOINTS
S
AND
TRIP BUS 1
BLOCK : LATCH SETPOINT
Off = 0 R Output Relay X
AND
Command
SETPOINTS RESET Do Not Operate, Operate
SETPOINTS TRIP BUS 1
FLEXLOGIC OPERAND
TRIP BUS 1 PICKUP DELAY:
NON VOLATILE Trip Bus 1 OP
OR
OR
...
FlexLogic Operands
... Trip Bus 1 PKP
SETPOINTS
TRIP BUS 1
INPUT 16:
Off = 0
SETPOINTS
TRIP BUS 1
LATCHING:
Disabled = 0
SETPOINTS
OR
TRIP BUS 1
RESET:
Disabled = 0
1601-0320
Chapter 10 - Control
1601-0320 585
Chapter 10 - Control
currents at small multiples of the Pickup value. The overcurrent detectors are required to operate after the Breaker
Failure delay interval to eliminate the need for very fast resetting overcurrent detectors.
Outputs
The outputs from the schemes are:
● Re-trip of the protected breaker
● FlexLogic operand that reports on the operation of the portion of the scheme where high-set or low-set
current supervision is used
● FlexLogic operand that reports on the operation of the portion of the scheme where 52b status supervision is
used only
● FlexLogic operand that initiates tripping required to clear the faulted zone. The Breaker Failure output can be
sealed-in for an adjustable period
● Target message indicating a failed breaker has been declared.
FUNCTION
Range: Disabled, Retrip, Alarm, Latched Alarm, Configurable
Range (from FW 4.10): Disabled, Retrip, Latched Retrip, Alarm, Latched Alarm, Configurable
Default: Disabled
When a Retrip function is selected and Breaker Failure is initiated (with re-trip current supervision), the output
relay Trip operates but the alarm LED does not turn on.
SIGNAL INPUT
Range: dependent upon the order code
Default: CT Bank 1-J1
USE SEAL-IN
Range: Yes, No
Default: Yes
If set to Yes, the element will only be initiated if current flowing through the breaker is above the supervision
pickup level.
586 1601-0320
Chapter 10 - Control
Default: 1.000 x CT
This setpoint specifies the neutral current Retrip level, which when exceeded after Breaker Failure initiation, will
Retrip its own breaker. The setting detects the lowest expected fault current on the protected circuit. Neutral
Retrip current supervision is used to provide increased sensitivity.
SUPERVISION
Range: Current, 52b & Current, 52b
Default: Current
The setpoint specifies the type of supervision of the Breaker Failure element. There are three options: current
only, breaker status only, or both.
BREAKER CLOSED
Range: Off, Any FlexLogic operand
Default: Off
The setpoint selects the FlexLogic operand (auxiliary switch contact) to indicate that the circuit breaker is closed.
T1 PICKUP DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.120 s
The setting provides a delay for Timer 1 logic which is supervised with current supervision only. The timer is set
to the expected opening time of the circuit breaker, plus a safety margin intended to overcome the relay
measurement and timing errors as well as relay processing time and current supervision reset time. In a
microprocessor relay this time is not significant. The current magnitude ramps-down to zero in ¾ of a power
cycle after the current is interrupted.
Note:
In bulk oil circuit breakers, the interrupting time for currents less than 25% of the interrupting rating can be significantly longer
than the normal interrupting time.
T2 PICKUP DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.120 s
The setting provides a delay for Timer 2 logic which is supervised with current supervision and breaker status
(52b indication). The timer is set to the expected opening time of the circuit breaker, plus a safety margin
intended to overcome the relay measurement and timing errors, relay processing time, current supervision reset
time, and the time required for the breaker auxiliary contact to open.
1601-0320 587
Chapter 10 - Control
T3 PICKUP DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.120 s
The setting provides a delay for Timer 3 logic which is supervised with breaker status only (52b indication). The
timer is set to the expected opening time of the circuit breaker, plus a safety margin intended to overcome the
relay timing errors, and the time required for the breaker auxiliary contact to open.
LOWSET DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.000 s
The setting provides the lowest current supervision Pickup. The setting is used in applications where a change in
supervision current level is required (for example: breakers with opening resistors).
The lowest delay (interval between high-set and low-set) is the expected breaker opening time.
DROPOUT DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
588 1601-0320
Chapter 10 - Control
Default: 0.100 s
The setting is used to set the period of time for which the Breaker Fail output is sealed-in. This timer must be
coordinated with the automatic reclosing scheme of the failed breaker, to which the Breaker Failure element
sends a cancel reclosure signal. Reclosure of a remote breaker can also be prevented by holding a transfer Trip
signal on for longer than the reclaim time.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
10.10.2 INITIATE
Path: Setpoints > Control > Breaker Failure 1(X) > BF1(X) Initiate
EXTERNAL INITIATE
Range: Off, Any FlexLogic operand
Default: Off
The setpoint selects the FlexLogic operand that initiates the Breaker Failure scheme; typically the trip signals
from external devices.
Note:
The trip signals from internal protection functions may be used with the help of FlexLogic, but for easier setting the Breaker
Failure function is provided with a BF1 INITIATE submenu.
INITIATE IN1(15)
Range: Off, Any FlexLogic operand
Default: Ph TOC 1 OP
The setpoint selects the FlexLogic operand that initiates the Breaker Failure scheme; typically the trip signals
from internal protection functions.
1601-0320 589
Chapter 10 - Control
Note:
The default setting includes the following protection functions:
● Ph TOC 1 OP
● Ph TOC 2 OP
● Ph IOC 1 OP
● Ph IOC 2 OP
● Ntrl TOC 1 OP
● Ntrl TOC 2 OP
● Ntrl IOC 1 OP
● Ntrl IOC 2 OP
● GND TOC 1 OP
● GND IOC 1 OP
590 1601-0320
1601-0320
LED:
AND
ALARM
OR
S
SETPOINTS SETPOINTS
LATCH # 1
AND
BF 1 OUTPUT RELAYS
Command Set-
FUNCTION: Dominant Do Not Operate, Operate
Disabled RESET R
FlexLogic Operands
Alarm
OR
BF1 OP
Latched Alarm
Re-trip
OR
Latched Re-trip
Configurable
SETPOINTS
BF1
AND
BLOCK :
SETPOINTS
AND
SETPOINTS
SETPOINTS BF1 PH RETRIP BF1 FlexLogic Operand
OR
SUPERV PICKUP: RETRIP PKP DELAY:
OR
AND
BF1 INITIATE: BF1 Retrip
tPKP
OR
EXTERNAL INITIATE 0 S
PICKUP:
LATCH # 1
AND
OR
RUN
AND
SETPOINTS
BF1 Setpoints/System/Breakers/
BF1 IC > PICKUP
PHASE HIGHSET PICKUP: BKR1: 845 & 889 &
USE SEAL-IN: RUN 859 only
IN > PICKUP BF1
YES = 1 BKR 1: Trip Relay Select
NTRL HIGHSET PICKUP:
NO = 0 RUN
IA > PICKUP
RUN
IB > PICKUP
OR
RUN
SETPOINTS
SETPOINTS IC > PICKUP
IA SIGNAL INPUT:
RUN
IB BF1 FlexLogic Operands
T1 PICKUP DELAY: IN > PICKUP
IC CT Bank 1 - J1 BF1 Highset OP
t1PKP SETPOINTS BF1
IN
AND
0 PHASE LOWSET PICKUP: BF1 Lowset OP
BF1
USED ONLY IN 845 & 889 LOWSET DELAY: BF1
SETPOINTS NTRL LOWSET PICKUP:
tLOW
SETPOINTS RUN
OR
BF1 0
BF1 SETPOINTS
T2 PICKUP DELAY: IA > PICKUP
SUPERVISION: BF1
t2PKP RUN
DROPOUT DELAY:
AND
Current 0
IB > PICKUP
52b& Current 0
OR
OR
RUN TDPO
52b
IC > PICKUP
RUN
SETPOINTS
IN > PICKUP
BF1
SETPOINT T3 PICKUP DELAY: FlexLogic Operands
BF1 t3PKP
BF1 52b Superv OP
AND
BREAKER CLOSED: 0
Off = 0
894067C1.vsdx
591
Chapter 10 - Control
Chapter 10 - Control
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Note: Relays with firmware version 4 and later have a Latched Trip option
Default: Disabled
The selection of Trip, Alarm, Latched Alarm or Configurable setting enables the HS Phase/Ground IOC function.
SIGNAL INPUT
Range: dependent upon the order code
Default: CT Bank 1 - J1
This setting provides the selections for the current input bank. The default bank names can be changed in:
Setpoints > System > Current Sensing > [Name] > CT Bank Name.
HS PHASE PKP
Range: 0.050 to 30.000 x CT in steps of 0.001 x CT
Default: 2.000 x CT
HS GROUND PKP
Range: 0.050 to 30.000 x CT in steps of 0.001 x CT
Default: 1.000 x CT
Note:
The value of HS Gnd PICKUP can be set to a very high value, when only the HS Phs element needs to be applied for Arc
Flash detection.
592 1601-0320
Chapter 10 - Control
Note:
The HS Ground PKP setting is not available if the order code is selected to have just one sensitive ground current input on the
J1-Bank (4-0B in the order code).
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
EVENTS
Range: Disabled, Enabled
Default: Enabled
This setting enables or disables the events of the Arc Flash function.
TARGETS
Range: Self-reset, Latched, Disabled
Default: Latched
1601-0320 593
Chapter 10 - Control
LED: TRIP
AND
Operate Output Relay 1 (TRIP)
OR
CONFIGURABLE IN 845
AND
FLEXLOGIC OPERAND
LATCH Any Trip
R
Set Dominant LED: ALARM
AND
FLEXLOGIC OPERAND
OR
Any Alarm
AND
SETPOINT S
FUNCTION: LATCH SETPOINT
Disabled Command R Output Relay X
Trip RESET Set Dominant Do Not Operate, Operate
OR
Arc Flash 1 OP
OR
Alarm
Latched Alarm
Configurable FlexLogic Operands
AF 1 HS Ph IOC PKP A
OR
SETPOINTS Ichs > PICKUP
BLOCK
Off = 0
SETPOINTS
FlexLogic Operands
HS Ground PKP
Arc Flash 1 S1 OP
SETPOINTS HS Phase Currents RUN
Arc Flash 1 S2 OP
SIGNAL INPUT: HS Phase A current (Iahs) Ighs > PICKUP
HS Phase B current (Ibhs) Arc Flash 1 S3 OP
AND
Level * Auto Calibration Level for
USED ONLY IN 845 & 889
Sensor 1 20 ms
RUN
Light Sensor 2 Input > Factory PKP 0 ms
AND
Level * Auto Calibration Level for
20 ms
OR
Sensor 2
Light Sensor Input
RUN
Light Sensor 1 Light Sensor 3 Input > Factory PKP 0 ms
AND
FlexLogic Operands
Level * Auto Calibration Level for 20 ms
Light Sensor 2
Sensor 3 AF 1 Light 1 PKP
Light Sensor 3
RUN 0 ms AF 1 Light 2 PKP
AND
Light Sensor 4
Light Sensor 4 Input > Factory PKP 20 ms
Level * Auto Calibration Level for AF 1 Light 3 PKP
Sensor 4
AF 1 Light 4 PKP
SETPOINTS
AND
FlexLogic Operands
OR
Programmable LED:
TROUBLE
594 1601-0320
Chapter 10 - Control
where:
● ΔΦ = phase angle difference in degrees
● ΔF = frequency difference in Hz.
Example: For the values ofΔΦ = 30° and ΔF = 0.1 Hz, the time during which the angle between the two voltages is
less than the set value is:
As a result the breaker closing time must be less than this computed time, to successfully close and connect both
energized sides.
If one or both sides of the synchronizing breaker are de-energized, the Synchrocheck programming can allow for
closing of the circuit breaker using undervoltage control to by-pass the Synchrocheck measurements (dead source
function).
The measured bus and line input voltage magnitudes, angles and frequencies, and calculated differential values of
angle magnitude and frequency are available as actual values under Metering > Synchrocheck 1.
The selection of Aux VT Connection under Setpoints > System > Voltage Sensing determines the voltage
used for Synchrocheck as derived from the three-phase voltages available on the relay. For example, if the Aux VT
Connection is selected as Vab, and the three-phase VTs are connected in Wye configuration, the relay computes
delta voltage Vab as well, and uses it for Synchrocheck.
Note:
The Synchrocheck cannot be performed if the three-phase VTs are Delta connected, and the Wye single voltage input is
selected under Aux VT connection. Wye voltages cannot be calculated from Delta connected VTs.
1601-0320 595
Chapter 10 - Control
Note:
If both Line and Bus sides are three-phase VTs, the VT types must match, i.e. either both Line and Bus Volt inputs are Delta
or both are Wye. If both sides are single-phase Aux VT inputs, then both Aux VT connection types must match, i.e. if the Line
side Aux VT type is Vab, then the Bus side Aux VT type must be Vab. Aux VT connection Vn is not a valid type for
synchrocheck.
Caution:
If the VT types on the Line and Bus side do not match, as specified above, the Synchrocheck does
not run even when the Function is set to Enabled.
Note:
Once the Synchrocheck function is programmed, it will perform a voltage input selection check, to determine that the voltage
magnitudes are not different by more than 5%. This check depends only on the settings entered for phase and auxiliary VTs
under Setpoints > System > Voltage Sensing. If the difference between the selected voltage inputs by calculation is bigger
than 5%, the Synchrocheck will not work. For example, the phase VT can be set to Wye connection with secondary voltage of
66.4V. The Aux. VT can be connected between phase A to B with the secondary voltage set to 115V. Then, one of the
Synchrocheck inputs can be set as the Wye connected phase voltage bank, and the other input can be the Aux. VT with
voltage Vab. Since the difference between the computed Vab input and the Aux. VT setting is 0%, the Synchrocheck will work.
However, if this difference is bigger than 5%, the Synchrocheck will not work.
FUNCTION
Range: Disabled, Enabled
Default: Disabled
596 1601-0320
Chapter 10 - Control
The setting selects the maximum frequency difference in ‘Hz’ between the two sources. A frequency difference
between the two input voltage systems below this value is within the permissible limit for synchronism.
1601-0320 597
Chapter 10 - Control
Note:
For an application where the breaker is located on radial feeders, or line is powered by one source only, the DEAD SOURCE
PERM setpoint shall not be disabled.
SYNCCHECK BYPASS
Range: Off, Any FlexLogic operand
Default: Off
The Synchrocheck is bypassed when the selected operand is asserted. Typically BKR(X) Disconnected is used
to bypass Synchrocheck.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
598 1601-0320
Chapter 10 - Control
The Synchrocheck is blocked when the selected operand is asserted. Typically 52a (the circuit breaker closed)
contact is used to block Synchrocheck (Synchrocheck is needed only when the circuit breaker is open).
Synchrocheck can be also blocked when the relay is tripping.
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
1601-0320 599
Chapter 10 - Control
WX
+* 0 / X/0 ]/
3 X0 3/ .
()' S 2 3/ ]0
& O ; 0/
]Z
.3
3
Y9 4
]0 -3
]Z
%$ X7 L 7X , 5 7 03 3 .
3
#" L ._, ]/ E
6 2 ] W Z ./
O X X / 0 a
! 7 7 D 1D P
3 D S
0 . /3 P33
1. 1. 1. 1. 1. 1.
5
/ 3
. : ] : /0 Z
- - - - - - - /
, , , , , 3 , , D Z 9 U
8
JNK
JNK JNK
:E :E
}v } I II II
v HI H H
G
{ E G G
S
E
6 zv 6 v CT B
FE uv FFE uv B
F AV I ¥ 0
tty D ? ¢¥ 0X
D x E7 @ @ @ X
7 wv ~ wv ?
M
?
M
?
M ¬« 3
S >= P]
[ tu 9 tu => => ¥
; sr ; sr V< <k `< ǻ
9
U q
9
U q ¨ 3
£
¥© H H @ @
¨¥ :; ? :; ?
M M M M :U
:
V : V 9 V
9
U V 6
§¦ U C U U E
H , C , H 5 ,
¤¥
£
,7
,7 B
7
7 B
E E , ,
L
V V G [ G L x
¢ [ HB [ HB [ ? ? 6 7 L D
¡ E , E D D D 6 u
, s
|h o|h
S
L > S 7 >
S L >G= S 7 >G=
S , ^ ^ ^
E
E
|h D D D , E v
pgi kg gp
[
E V [
E V 9E 9E 9E ]X
L 7 7 7 z
y
d pi i 7 7 D V D V D D 7 7 D D x
j m
ghp hg hg
f pf pf
|d j|
e nm|
e j e
d c m
c c
JNK
W W ,
,
P3/ ]X / P3/ ]X 95
]0 X ]0
LY
W
X
/2 , .0 W
X
/2 , X
/
O
0/ 0 0/ 0 .0
] W0 ./
b\[ Pb\ ] W0 l\[ Pl\ ®
E
: / [ -. \b ] /
./ -. S
S S : 0 [ Z 0 [ Z l\ ®
O 7
X
.X/ 0 X0 Z ` LZ .X/ 0 X0 Z ` R
R
QP ] ]
[ ] Y QP
P
F ]X
7 P
]Z ]] ]- _ W a
_ X7 ]] ]- Z W a
_ ,
D E L L 9 , 5 U F3 5 9 , 9 U F3 5
600 1601-0320
Chapter 10 - Control
FUNCTION
Range: Disabled, Alarm, Latched Alarm, Configurable
Default: Disabled
VT INPUT
Range: Dependent upon the order code
Default: Ph VT Bnk1-J2
CT INPUT
Range: Dependent upon the order code
Default: CT Bnk1-J1
TIME DELAY
Range: 0 to 60000 s in steps of 0.1 s
Default: 0.1 s
1601-0320 601
Chapter 10 - Control
This setting can be used to avoid fuse failure detection in the case of sudden loss of voltage when the current is
zero (breaker remains in open condition) and the transient negative sequence voltage appears. This setting
should be used where the VT is on the Bus side, in which case the relay may detect voltage loss when the
breaker is open.
Operate Delay:
Range: 1 to 10 sec in steps of 1 sec
Default: 5 Sec
This setting determines the operate time-delay upon detection of a VTS condition.
OUTPUT RELAY X
Range: Operate, Do Not Operate
Default: Do Not Operate
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
602 1601-0320
Chapter 10 - Control
Figure 231:
LED: ALARM / LATCHED
AND
ALARM
OR
SETPOINT
AND
SLATCH #
FUNCTION: 1
Disabled
Set-
Alarm Dominant
OR
Latched Alarm
RESET R
AND
Configurable
Command
OR
SLATCH #
2 FAU
AND
LT
Reset-
Dominant
SETPOINT SETPOINTS
AND
COMPARATORS OUTPUT RELAYS 3 to 7
VT INPUT SETPOINT
RUN
Do Not Operate, Operate
OR
Ph VT Bnk1 J2 V_2 Time Delay FUSE
OR
V_2 > 0.10 p.u. SLATCH #
TD FAILU
OR
Only for 850 and 889 RUN RE 3
AND
V_1 0 FlexLogic Operands
V_1 < 0.05 p.u.
AND
Reset- VT Fuse Fail 1 OP
RUN Dominant
I_1 > 0.075 p.u.
R
RUN TIMER
V_1 < 0.80 p.u.
2 cyc
AND
RUN 20 cyc SETPOINT
I_1 < 0.05 p.u.
Operate Delay FlexLogic Operands
RUN TD
0 VT Fuse Fail 1 Slow OP
I_1 |I _1| |I_1'| > 0.04 p.u.
AND
SETPOINT
RUN
CT INPUT I_2 |I _2| |I_2'| > 0.04 p.u.
OR
CT Bnk1 J1 RUN
I_0 |I _0| |I_0'| > 0.04 p.u.
AND
Not available for 869 & 859 Where I is 2 cycles old VT Fuse 1 V Loss
AND
ALARM
AND
SETPOINT
NTRL WIRE OPEN DETECTION
AND
OR
Enabled
AND
SLATCH #
OR
SETPOINT Set-
SETPOINT
Ntrl Wire Open PKP Level Dominant
AND
VT INPUT Timer
RUN
5 cyc RESET R
Ph VT Bnk1 J2 3V_0 (3rd Harm) 3V_0 (3rd Harm) > setting 0 Command
OR
TIMER
FlexLogic Operands
0
20 cyc
OR
VT Fuse 1 Ntrl Open
892734C1
1601-0320 603
Chapter 10 - Control
SETTING PARAMETER
Function Enabled
Name Bkr Trip Cct Out
Input Cont Op 1
Pickup Delay 0.200 s
Dropout Delay 0.100 s
Relays Relay : Disabled
Block CI 1 Off
Target Self-Reset
Events Enabled
604 1601-0320
Chapter 10 - Control
FUNCTION
Range: Disabled, Trip, Latched Trip, Alarm, Latched Alarm or Configurable
Default: Disabled
NAME
Range : 13 alphanumeric characters
Default: Digital Elem1
Assign a user-defined name to the Digital Element. This Name is used In Flexlogic operands, Target messages,
a blocking input from any selected flexlogic operands, and a timer for pickup and reset delays for the output
operands.
INPUT
Range : Off, Any FlexLogic operand
Default: Off
Selects a FlexLogic operand to be monitored by the digital element.
PICKUP DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.000
Sets the required time delay from element pickup to element operation. If a pickup
delay is not required, set to "0.000," To avoid nuisance alarms, set the delay greater than the operating time of
the breaker.
DROPOUT DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.000
Sets the dropout time delay to reset. If a reset delay is not required, set to “0.000.”
OUTPUT RELAY X
Range: Do Not Operate, Operate
Default: Do Not Operate
BLOCK
Range: FlexLogic operand
Default: Off
EVENTS
Range: Disabled, Enabled
Default: Enabled
1601-0320 605
Chapter 10 - Control
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
SETPOINT
FUNCTION:
FLEXLOGIC OPERAND
Disabled=0 Any Trip
Trip
LED: TRIP
AND
Latched Trip
To Trip Output Relay
OR
Alarm
OR
Latched Alarm
Configurable
S
AND
LATCH
SETPOINT
SETPOINT SETPOINT R
PICKUP DELAY
LED: ALARM
AND
AND
BLOCK NAME
DROPOUT DELAY
Off=0 RUN FLEXLOGIC OPERAND
tPKP
OR
tRST Any Alarm
INPUT = 1
AND
SETPOINT S
INPUT LATCH SETPOINT
Any FlexLogic Operand
Command R Output Relay X
RESET Do Not Operate, Operate
FLEXLOGIC OPERAND
OR
DIG ELEM 1 OP
606 1601-0320
CHAPTER 11
FLEXLOGIC
Chapter 11 - Flexlogic
608 1601-0320
Chapter 11 - Flexlogic
1601-0320 609
Chapter 11 - Flexlogic
11.2 FLEXLOGIC
To provide maximum flexibility, the arrangement of internal digital logic combines fixed and user-programmed
parameters. Logic upon which individual features are designed is fixed, and all other logic, from digital input signals
through elements or combinations of elements to digital outputs, is variable. The user has complete control of all
variable logic through FlexLogic. In general, the system receives analog and digital inputs, which then uses
FlexLogic to produce analog and digital outputs.
The major sub-systems of a generic 8 Series relay involved in this process are shown as follows.
Note:
For information on the Logic Designer and Logic Monitor menu items, refer to the Help menu.
!
"#$%
&% $%
'() )#
>?@<A=
*)# )(#+
1234526 789:;<=
MN
,)# ()- JKL
.-/0)+
O
P #+
610 1601-0320
Chapter 11 - Flexlogic
The states of all digital signals are represented by flags (FlexLogic operands). A digital 1 is represented by a Set
flag. Any external contact change-of-state can be used to block an element from operating, as an input to a control
feature in a FlexLogic equation, or to operate an output relay. The state of the contact input can be displayed locally
or viewed remotely via the communications facilities provided. In a simple scheme where a contact input is used to
block an element is desired, this selection is made within the menu of the element. This applies to other features
that set flags: elements, virtual inputs, remote inputs, schemes, and human operators.
When more complex logic than the one presented above is required, the FlexLogic tool should be used. For
example, if it is desired to block the operation of a Phase Time Overcurrent element by the closed state of a contact
input, and the operated state of a Phase Undervoltage element, the two input states need be programmed in a
FlexLogic equation. This equation ANDs the two inputs to produce a virtual output which then must be programmed
within the menu of the Phase Time Overcurrent as a blocking input. Virtual outputs can be created only by
FlexLogic equations.
Traditionally, protective relay logic has been relatively limited. Any unusual applications involving interlocks,
blocking, or supervisory functions had to be hard-wired using contact inputs and outputs. FlexLogic minimizes the
requirement for auxiliary components and wiring while making more complex schemes possible.
The logic that determines the interaction of inputs, elements, schemes and outputs is field programmable through
the use of logic equations that are sequentially processed. The use of virtual inputs and outputs in addition to
hardware is available internally and on the communication ports for other relays to use (distributed FlexLogic).
FlexLogic allows customization of the relay through a series of equations that consist of operators and operands.
The operands are the states of inputs, elements, schemes and outputs. The operators are logic gates, timers and
latches (with set and reset inputs). A system of sequential operations allows any combination of specified operands
to be assigned, as inputs to specified operators, to create an output. The final output of an equation is a numbered
register called a ‘Virtual Output’. Virtual Outputs can be used as an input operand in any equation, including the
equation that generates the output, as a seal-in or other type of feedback.
A FlexLogic equation consists of parameters that are either operands or operators. Operands have a logic state of 1
or 0. Operators provide a defined function, such as an AND gate or a Timer. Each equation defines the
combinations of parameters to be used to set a Virtual Output flag. Evaluation of an equation results in either a 1
(=ON, i.e. flag set) or 0 (=OFF, i.e. flag not set). Each equation is evaluated at least 4 times during every power
system cycle.
Some types of operands are present in the relay in multiple instances; e.g. contact and remote inputs. These types
of operands are grouped together (for presentation purposes only) on the faceplate display. The characteristics of
the different types of operands are listed in the table below.
FlexLogic Operands
A complete list of FlexLogic operands are available on the GE website.
The following operands can be re-named if required
● Breakers in the breaker control feature
● ID (identification) of contact inputs
● ID of virtual inputs
● ID of virtual outputs.
● If the default name or ID of any of these operands are changed, the assigned name appears in the relay list
of operands.
1601-0320 611
Chapter 11 - Flexlogic
FlexLogic Operators
TYPE SYNTAX DESCRIPTION NOTES
Editor INSERT Insert a parameter in an
equation list.
DELETE Delete a parameter from an
equation list.
End END The first END encountered
signifies the last entry in the list
of processed FlexLogic™
parameters.
One-shot POSITIVE ONE SHOT One shot that responds to a A ‘one shot’ refers to a single
positive going edge. input gate that generates a pulse
NEGATIVE ONE SHOT One shot that responds to a response to an edge on the
negative going edge. input. The output from a ‘one
shot’ is True (positive) for only
DUAL ONE SHOT One shot that responds to both one pass through the FlexLogic
the positive and negative going equation. There is a maximum of
edges. 64 ‘one shots’.
Logic gate NOT Logical NOT Operates on the previous
parameter.
OR(2)↓ OR(16) 2 input OR gate↓ 16 input OR Operates on the 2 previous
gate parameters.↓Operates on the 16
previous parameters.
AND(2)↓ AND(16) 2 input AND gate↓ 16 input Operates on the 2 previous
AND gate parameters. ↓Operates on the
16 previous parameters.
NOR(2)↓ NOR(16) 2 input NOR gate↓ 16 input Operates on the 2 previous
NOR gate parameters. ↓Operates on the
16 previous parameters.
NAND(2)↓ NAND(16) 2 input NAND gate↓ 16 input Operates on the 2 previous
NAND gate parameters. ↓Operates on the
16 previous parameters.
XOR(2) 2 input Exclusive OR gate Operates on the 2 previous
parameters.
LATCH (S,R) Latch (set, reset): reset- The parameter preceding
dominant LATCH(S,R) is the reset input.
The parameter preceding the
reset input is the set input.
Timer TIMER 1↓ TIMER 32 Timer set with FlexLogic™ timer The timer is started by the
1 settings.↓ Timer set with preceding parameter. The output
FlexLogic™ timer 32 settings. of the timer is TIMER #.
Assign virtual output = Virt Op 1↓ = Virt Op 32 Assigns previous FlexLogic™ The virtual output is set by the
operand to virtual output 1.↓ preceding parameter
Assigns previous FlexLogic™
operand to virtual output 96.
The characteristics of the logic gates are tabulated below, and the operators available in FlexLogic are listed in the
FlexLogic operators table.
612 1601-0320
Chapter 11 - Flexlogic
FLEXLOGIC RULES
When forming a FlexLogic equation, the sequence in the linear array of parameters must follow these general rules:
● Operands must precede the operator which uses the operands as inputs.
● Operators have only one output. The output of an operator must be used to create a Virtual Output if it is to
be used as an input to two or more operators.
● Assigning the output of an operator to a Virtual Output terminates the equation.
● A timer operator (for example, TIMER 1) or Virtual Output assignment may only be used once. If this rule is
broken, a syntax error will be declared.
FLEXLOGIC EVALUATION
● Each equation is evaluated in the order in which the parameters have been entered.
● FlexLogic provides latches which by definition have a memory action, remaining in the set state after the set
input has been asserted. However, they are volatile; that is, they reset on the re-application of control power.
● When making changes to settings, all FlexLogic equations are re-compiled whenever any new setting value
is entered, so all latches are automatically reset. If it is necessary to re-initialize FlexLogic during testing, for
example, it is suggested to power the unit down then back up.
11.2.1 TIMERS
Path: Setpoints > FlexLogic > Timers
There are 32 identical FlexLogic timers available. These timers can be used as operators for FlexLogic equations.
TIMER 1 TYPE
Range: Milliseconds, Seconds, Minutes
Default: Milliseconds
The setpoint is used to select the time measuring unit.
TIMER 1 MODE
Range: Pickup, Dropoff, Dwell, Pulse, Pickup/Dropoff,
Default: Pickup
1601-0320 613
Chapter 11 - Flexlogic
Default: 0 s
The setpoint sets the time delay to Pickup. If a Pickup delay is not required, set this function to “0”.
This setting is used to set the time delay for Pickup, Dwell, Pulse and Pickup/Dropoff.
NV LATCH 1 FUNCTION
Range: Disabled, Enabled
Default: Disabled
The setpoint enables or disables the Non-volatile Latch function.
NV LATCH 1 TYPE
Range: Reset-Dominant, Set-Dominant
Default: Reset-Dominant
The setting characterizes NV LATCH 1 to be set- or reset-dominant.
NV LATCH 1 SET
Range: Any FlexLogic operand
Default: Off
If asserted, this specified FlexLogic operand sets NV LATCH 1.
614 1601-0320
Chapter 11 - Flexlogic
LATCH 1 RESET
Range: Any FlexLogic operand
Default: Off
If asserted, this specified FlexLogic operand resets NV LATCH 1.
1601-0320 615
Chapter 11 - Flexlogic
Logic Design Last Saved, Logic Design Last Compiled, and FlexLogic Editor Last Saved: Each of these three
read-only variables holds the time stamp that represents the time that the operation (of the respective variable) was
performed.
● When no Logic (New file creation) is present these timestamps are set to default text representations.
● Time stamps are displayed in the format ‘Mon DD YYYY HH:MM:SS’ [Jun 22 1981 14:20:00]
● Each time a ‘Save’ operation is performed in the ‘FlexLogic Equation Editor’ screen, the ‘FlexLogic Editor
Last Saved’ entry gets updated.
● Based on the values present at each launch of the ‘FlexLogic Equation Editor’ screen, internal validation
prompts the relevant messages. These prompts must be followed to ensure that the ‘FlexLogic’ configuration
is synchronized with the ‘Logic Designer’. These three variables are shown in color in the FlexLogic Equation
Editor based on timestamps. Color is used to indicate the change (non-synchronization if any) of FlexLogic
between the FlexLogic Editor and Logic Designer Screens.
File Conversion and Handling of Time Stamps: When File Conversion is applied the three time stamps are
processed (either carry forwarded, defaulted, updated with latest PC time) based on the Source and Destination
File versions and Order code supported.
The following cases depict the nature of the three time stamps after a file conversion.
Source Version Target Version Is FlexLogic Change Time Stamps [LDLs, LDLc, FELs]**
Detected?
>= 160 >= 160 YES [ 0^ , 0 , PCTime**]
>= 160 >=160 NO *Existing time stamps are copied to the
converted file
< 160 >= 160 YES [ 0 , 0 , PCTime]
< 160 (& > 120***) >= 160 NO [PCTime, PCTime, PCTime,]
** LDLs – Logic Designer Last Saved, LDLc– Logic Designer Last Compiled and FELs – FlexLogic
Editor Last Saved
** PCTime The time that the file conversion took place
^0 Indicates the time stamps are being defaulted
*** There is no support for Logic Designer [Graphical Editor] below version 130
* For each specific case, the source files for Logic Designer (Graphical) content will also get
copied “as is” to the destination folder. This enables the user to retain old content “as is”.
In a typical scenario where both the FlexLogic Designer and FlexLogic Editor are used for configuring FlexLogic, the
updated time stamps appear as shown in the following figure.
616 1601-0320
Chapter 11 - Flexlogic
Logic Designer: This entry can be used to initiate the launch of the Logic Designer screen. Once chosen, the
existing FlexLogic Equation Editor screen is set to Read-only and then the Logic Designer screen launch is initiated.
If the user wants to re-visit the FlexLogic Editor Screen, any existing read-only screen has to be closed first. Then,
the screen has to be re-opened. The FlexLogic Editor screen is now editable, again.
In order to maintain synchronization of FlexLogic, the following update rules are defined.
For example, when a user tries to open the ‘FlexLogic Equation Editor’ of a particular device or file.
● If the Logic Designer screen is open and in Edit mode, a message prompts to save any changes. The
FlexLogic Equation Editor is not launched.
● If the Logic Designer is open and in saved mode (no edits to save or compile), the Logic Designer screen is
closed and then the FlexLogic Equation Editor launch is initiated.
1601-0320 617
Chapter 11 - Flexlogic
11.2.5 FLEXELEMENTS
There are 8 identical FlexElements. A FlexElement is a universal comparator, that can be used to monitor any
analog actual value measured or calculated by the relay, or a net difference of any two analog actual values of the
same type. Depending on how the FlexElement is programmed, the effective operating signal could be either a
signed signal or an absolute value.
You can configure the element to respond either to a signal level or to a rate-of-change (delta) over a pre-defined
period of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a
threshold chosen.
618 1601-0320
Chapter 11 - Flexlogic
" #"$%&
#'
!
"%$ ( #'
'@D E
'%
") "
FG)
$ ' *N&%&&
HH E
%$ *$ ( #
+,-
") " 'G$N
%$ *$ ( #
" !+.-
% '%" 'G$N
$/,0 10 234356 5789:
= IJKJ
" ; +<- ! "
> ILJM
$/,0 10
! ")"
96B93 C93B
! ? &@A
FUNCTION
Range: Disabled, Enabled
1601-0320 619
Chapter 11 - Flexlogic
Default: Disabled
NAME
Range: Up to 13 alphanumeric characters
Default: FlexEl 1
INPUT 1 (+)
Range: Off, any FlexAnalog signal
Default: Off
This setting specifies the first input (non-inverted) to the FlexElement. Zero is assumed as the input if this setting
is set to Off. For proper operation of the element at least one input must be selected. Otherwise, the element
will not assert its output operands.
INPUT 2 (-)
Range: Off, any FlexAnalog signal
Default: Off
This setting specifies the second input (inverted) to the FlexElement. Zero is assumed as the input if this setting
is set to Off. For proper operation of the element at least one input must be selected. Otherwise, the element
will not assert its output operands.
This input should be used to invert the signal if needed for convenience, or to make the element respond to a
differential signal such as for a top-bottom oil temperature differential alarm.
A warning message is displayed and the element does not operate if the two input signals are of different types,
for example if one tries to use active power and phase angle to build the effective operating signal.
PICKUP
Range: -30.000 to 30.000 pu in steps of 0.001 pu
Default: 1.000
This setting specifies the operating threshold for the effective operating signal of the element.
If the Over direction is set, the element picks up when the operating signal exceeds the Pickup value.
If the Under direction is set, the element picks up when the operating signal falls below the Pickup value.
The HYSTERISIS setting controls the element drop out.
Notice that both the operating signal and the pickup threshold can be negative when facilitating applications
such as reverse power alarms.
The FlexElement can be programmed to work with all analog values measured or computed by the relay. The
PICKUP setting is entered in pu values using the following definitions of the base units:
620 1601-0320
Chapter 11 - Flexlogic
HYSTERESIS
Range: 0.1 to 50.0% in steps of 0.1%
Default: 3.0%
This setting defines the pickup – drop out relation of the element by specifying the width of the hysteresis loop as
a percentage of the pickup value as shown above in the Direction, Pickup, and Hysteresis setpoints figure.
1601-0320 621
Chapter 11 - Flexlogic
622 1601-0320
Chapter 11 - Flexlogic
If we want to detect 2% voltage difference (2% @13.8kV = 276V) between the computed phase to phase Vab
voltage, and the measured Vaux voltage from a VT connected between phases A and B, the pickup per-unit setting
for the FlexElement can be set as follows:
Pickup = 276V/13800V = 0.02 pu
If the voltage difference between the selected inputs becomes bigger than 276 Volts, the FlexElement will pickup,
and operate, which can be used to energize contact, or initiate alarm, or trip.
1601-0320 623
Chapter 11 - Flexlogic
Note:
The minimum pickup should not be less than 0.01 pu, as the measurement resolution for the Power Factor is 0.01.
Note:
The harmonics and THD values are measured as percentage of the fundamental signal, and have resolution of 0.01%.
However for the minimum pickup setting of 0.001 pu, this would mean percentage step of 0.1%.
624 1601-0320
Chapter 11 - Flexlogic
programming of the pickup setpoint is straight forward for the desired FlexElement operation. For the example given
here, a value of 1.200 pu has been selected.
● Input 1(+): Volts Per Hertz 1Input 2(-): OffOperating Mode: AbsoluteInput Comparison Mode: LevelDirection:
OverPickup: 1.200 puHysteresis: 8.3%
Now, if the FlexElement is needed to drop down when the V/Hz ratio becomes equal to 1.1, the hysteresis can be
calculated as:1.2pu-1.1pu = 0.1 puHysteresis = (0.1*100)/1.2 = 8.3%
The base unit for the breaker arcing current is programmed in the relay as: BASE = 2000 kA2*cycle
● Input 1(+): Total Arcing Current
● Input 2(-): Off
● Operating Mode: Absolute
● Input Comparison Mode: Level
● Direction: Over
● Pickup: 2.500 pu
● Hysteresis: 0.0%
To configure the pickup setpoint for a total arcing current of 5000kA2/cycle, the per-unit pickup value can be
calculated as follows:
1601-0320 625
Chapter 11 - Flexlogic
626 1601-0320
CHAPTER 12
TESTING
Chapter 12 - Testing
628 1601-0320
Chapter 12 - Testing
1601-0320 629
Chapter 12 - Testing
!""
#""!$ 23
256578
%"!"&
9: ;<=:
'&()"$
>78? @83:
7:
4$
A3 BC:
630 1601-0320
Chapter 12 - Testing
12.3 SIMULATION
Path:Setpoints > Testing > Simulation
● Setup
● Pre-Fault
● Fault
● Post-Fault
The Simulation feature is provided for testing the functionality of the relay in response to programmed conditions,
without the need of external AC voltage and current inputs. First time users will find this to be a valuable training
tool. System parameters such as currents, voltages and phase angles are entered as setpoints. When placed in
simulation mode, the relay suspends reading actual AC inputs, generates samples to represent the programmed
phasors, and loads these samples into the memory to be processed by the relay. Normal (pre-fault), fault and post-
fault conditions can be simulated to exercise a variety of relay features. There are three sets of input parameters
used during simulation, each provides a particular state of the system as follows.
Note:
Simulation mode current input should be set at more than three times the CT rating. All Simulation setpoints revert to default
values at power-up.
Note:
Testing of Arc Flash functionality is not possible with the Simulation feature.
SIMULATION STATE
Range: Disabled, Prefault State, Fault State, Postfault State
Default: Disabled
Disable this setpoint if actual system inputs are to be monitored. If set to any other value, the relay is in test
mode and actual system parameters are not monitored, including Current, Voltage, and Contact Inputs. The
system parameters simulated by the relay will be those in the section below that correspond to the set value of
this setpoint. For example, if set to Fault, the system parameters will be set to those defined by the FAULT
setpoint values.
1601-0320 631
Chapter 12 - Testing
FORCE RELAYS
Range: Disabled, Enabled
Default: Disabled
When in test mode, and FORCE RELAYS is enabled, relay states can be forced from the Setpoints > Testing >
Output Relays menu, which overrides the normal operation of the output contacts. When in test mode, and
FORCE RELAYS is disabled, the relay states maintain their normal operation. Forcing of output relay states is
not performed when the Simulation State is disabled.
FORCE LEDS
Range: Disabled, Enabled
Default: Disabled
When in test mode, and FORCE LEDS is enabled, LED states and colors can be forced from the Setpoints >
Testing > Test LEDs menu, this will override the normal operation of the LEDs. When in test mode, and FORCE
LEDS is disabled, the LED states and colors will maintain their normal operation. Forcing of LEDs is not
performed when the SIMULATION STATE is disabled.
632 1601-0320
Chapter 12 - Testing
1601-0320 633
Chapter 12 - Testing
634 1601-0320
Chapter 12 - Testing
Note:
Test LEDs setpoints here will revert to default values at power-up.
LED 1 (17)
Range: Off, Red, Green, Orange
Default: Off
LED 1 (24)
Range for 1(14): Off, Red, Green, Orange
Range for 15(24): Off, Orange
Default: Off
1601-0320 635
Chapter 12 - Testing
Note:
Contact Inputs setpoints here will revert to default values at power-up.
CI 1(X):
Range: Off, On
Default: Off
The item name displays the user configurable name for the contact input.
636 1601-0320
Chapter 12 - Testing
Note:
Output Relays setpoints here will revert to default values at power-up.
1601-0320 637
Chapter 12 - Testing
638 1601-0320
CHAPTER 13
STATUS
Chapter 13 - Status
640 1601-0320
Chapter 13 - Status
1601-0320 641
Chapter 13 - Status
13.2 SUMMARY
Configurable Single Line Diagram (SLD)
The status of each SLD screen is displayed under Status > Summary > Configurable SLDs > SLD1(X).
Once in the SLD screen, by default no breaker/switch is highlighted or selected. Pressing the Up/Dn (or Up/Dn/Left/
Right) navigation keys highlights BKR1 and navigates through BKR1, 2, 3, etc. and then through Switch1, 2, 3, etc.
If the Up/Dn/Left/Right keys are used, the selection moves to the closest available breaker/switch from the currently
highlighted object. To select the breaker/switch, press the enter key. Upon pressing the Enter key, the tab labels
change to the programmable tab pushbutton labels and a flash message for the breaker selected appears (Flash
Message: BKR1 Selected). Pressing Escape de-selects the breaker/switch and the tab pushbutton labels.
Annunciator
The graphical annunciator panel emulates a physical annunciator panel. Indicators on the graphical panel are
backlit and have a description of the alarm condition that lights each indicator. The annunciator panel status window
shows the alarms that are active.
To reset an active alarm, first highlight the active alarm using the navigation keys, then press the reset button to
reset the highlighted alarm. If no indicator is selected, all alarms on the page are reset by pushing the reset button.
642 1601-0320
Chapter 13 - Status
Ho e\HMI\Annunciaor\Pae1
Sttg S
G C k
tv Fl
Bk
C l Fl
tv
. . 2 . 3 . 4 >>
Tab pushbuttons
Navigation
There are two ways to navigate to the Tab Pushbutton control pages:
● Relay Home Screens
● Path: Status > Summary > Tab Pushbuttons (from relay) Home Screens
By default, the Tab Pushbuttons summary page is programmed as one of the Home Screens. Press the home
button repeatedly to cycle through the programmed Home Screens.
Note:
Tab pushbuttons can only be controlled physically through the front panel of the relay. Their operation is not available from the
setup software.
1601-0320 643
Chapter 13 - Status
Figure 241: Tab pushbutton summary (left) and detailed view (right)
Only the tab pushbuttons that are not set to Disabled are shown in color; labels for the tab pushbuttons are shown
for both active and disabled pushbuttons if labels have been configured. (Configure tab pushbuttons from Device >
Front Panel > Tab PBs > Tab PB1(X).)
When the actual button is pressed, the button on the screen is highlighted in blue and the PB [X] PRESS operand
becomes active. Although a disabled pushbutton can be pressed, no action is taken and its operands are not
activated. Pressing ESCAPE returns the screen to Tab Pushbutton summary page. The Short Text for each Tab
Pushbutton is used on the Summary Page.
Pressing >> shows the next set of tab pushbuttons. For example, when in the page with pushbuttons 1 to 4,
pressing >> will navigate to the screen with pushbuttons 5 to 8. Press >> to cycle through all five pushbutton
screens. To go from page 2 to page 1, press >> 4 times to cycle through and navigate to page 1 with pushbuttons 1
to 4. Alternatively, escape to the overall summary screen and navigate to any desired page of pushbuttons.
644 1601-0320
Chapter 13 - Status
GENERATOR STATUS
Range: Online, Offline, Tripped, Unknown
Default: Offline
The Generator Status can be one these options: Online (connected to the system through breaker), Offline
(either not running or not connected to the system), Tripped (any tripped and with the system breaker open), or
Unknown (the generator is not tripped, online or offline, or the breaker status is unknown). Terminal voltage and
breaker status is used to determine if generator is online. The status is also available as FlexLogic operands,
and only one status is possible at a time. Refer to the generator status logic diagram.
FLEXLOGIC OPERANDS
BKR1 CLOSED
AND FLEXLOGIC OPERANDS
Gen Status Online
J - Slot Voltages
|VAB| |V AB | > 0.5 x VT
OR
FLEXLOGIC OPERANDS
ANY TRIP
FLEXLOGIC OPERANDS
Gen Status Tripped
AND
FLEXLOGIC OPERANDS
BKR1 OPENED
AND
FLEXLOGIC OPERANDS
FLEXLOGIC OPERANDS Gen Status
OR
Note:
The Generator breaker has to be configured as Breaker 1. If it is not configured as Breaker 1 or its status is unknown, the
Generator Status shows as Unknown.
RUNNING HOURS
Range: 0 to 100,000 hrs in steps of 1
Default: 0 hrs
The Running Hours field shows accumulated generator running time in hours. Refer to the Running Hours
element description for more details.
1601-0320 645
Chapter 13 - Status
646 1601-0320
Chapter 13 - Status
STATE
Range: Not Configured, Opened, Closed, Disconnected, State Unknown
The Unknown state is displayed upon discrepancy of the 52a and 52b contacts for more than 30 milliseconds.
TRIP COIL
Range: Not Set, Fail, OK
The Trip Coil state is displayed when Form -A output relays are used, and Trip Coil monitoring is enabled.
CLOSE COIL
Range: Not Set, Fail, OK
The Close coil state is displayed when Form -A output relays are used, and Close Coil monitoring is enabled.
1601-0320 647
Chapter 13 - Status
13.5 INFORMATION
Path: Status > Information > Relay Info
The Information pages display fixed device information. the pages are divided into three sections: Main CPU,
Comms CPU, and Hardware Versions.
Main CPU
The Information related to the Main CPU is displayed here.
Path: Status > Information > Relay Info > Main CPU
● Order Code: The installed Order Code
● Product Serial #: The relay serial number
● Hardware Revision: The hardware revision of the relay
● Firmware Version: The firmware version of the Main CPU
● Firmware Date: The Main CPU firmware build date in the format mm/dd/yyyy
● Firmware Time: The Main CPU firmware build time
● Boot 1/2 Version: The boot 1/2 code version of the Main CPU
● Boot 1/2 Date: The Main CPU boot 1/2 code build date in the format mm/dd/yyyy
● Boot 1/2 Time: The Main CPU boot 1/2 code build time
● MAC Address 1: The MAC address for copper Ethernet port 1
● Remote CANBUS RMIO: The commissioned value of the CANBUS IO is displayed here. If the relay has
never been commissioned then the value is None, i.e. default = None and Range = 6 alphanumeric
characters.
● NUM of RMIO RTDs: The number of remote RTDs detected
Comms CPU
The Information related to the Comms CPU is displayed here.
Path: Status > Information > Relay Info > Comms CPU
● Comms CPU FW Version: The firmware version of the Comms CPU
● Comms CPU Firmware Date:The Comms CPU firmware build date in the format mm/dd/yyyy
● Comms CPU Firmware Time: The Comms CPU firmware build time
● Boot Version: The boot code version of the Comms CPU
● Boot Date: The Comms CPU boot code build date in the format mm/dd/yyyy
● Boot Time: The Comms CPU boot code build time
● MAC Address 1: The MAC address for Ethernet port 4
● MAC Address 2: The MAC address for Ethernet port 5
Hardware versions
Path: Status > Information > Relay Info > Hardware Versions
The Information related to the relay hardware is displayed here.
648 1601-0320
Chapter 13 - Status
Environment
The Information related to Environmental is displayed here.
Note:
The Temperature Display setpoint can be changed from Celsius to Fahrenheit under Setpoints > Device > Installation.
1601-0320 649
Chapter 13 - Status
● Temp (e.g. <=-20°C): The accumulated amount of time (hrs) that the temperature measured by the EAM
stayed in the range specified.
● Temp and Humidity (e.g. >40°C and <55%): The accumulated amount of time (hrs) that the temperature
and humidity measured by the EAM stayed in the ranges specified.
● Surge Count: The number of surge (>500 V/1.2/50 µS) events that have occurred since the EAM started
recording data.
The Information related to settings changes and settings file history is displayed here.
Settings Audit
Path: Status > Information > Settings Audit
● Last Setting Change: The date and time of the last setting change.
● File Modified:
● File Received:
● File Origin:
● File Name:
650 1601-0320
Chapter 13 - Status
13.6.1 GOOSE
The relay supports 16 GOOSE transmissions and 64 GOOSE receptions each with 64 items per transmission or
reception. Non-structured GOOSE is supported. Each item within the GOOSE message can be a digital or analog
value. Messages are launched within one scan of a digital point status change or an analog exceeding its
deadband.
The server supports a subset of the server features described in part 7.2 of the IEC61850 standard.
Goose Messaging
The details are shown in the table below:
Service Launch Support for Programmable # of Tx # of Rx Test Bit Number of items in Number of remote
Speed* time to live Support each transmission inputs per relay
or reception
Configurabl Within 2 ms Time to live programmable 16 64 Y 64 Data Items per 32
e GOOSE (1 CPU from 1000 to 60000 ms Data Set
scan)*
* Launch speed is measured by comparing the time stamp in SOE of digital remote output status change to the time
stamp of message seen on the network by a computer who’s clock is synchronized by an IRIG-B card to the same
IRIG-B source as the relay.
REMOTE INPUTS
Path:Status > Communications > Remote Inputs
The present state of the 32 remote inputs are shown here. The state displayed is the remote point unless the
remote device has been established to be Offline in which case the value shown is the programmed default state for
the remote input.
GGIO1 INDICATIONS
Path:Status > Communications > GGIO1 Indications
The present state of the 32 GGIO1 Indications are shown here. There are up to 32 GGIO indications that can be
used to map any FlexLogic operand into the IED 61850 information model. Default value is “Off”.
GOOSE STATUS
Path: Status > Communications > GOOSE Status
Range: OFF, ON
Default: OFF
This setting indicates GOOSE communications are being received. A GOOSE STATUS of “ON” indicates
successful receipt of the last GOOSE packet. A GOOSE STATUS of “OFF” indicates the communications link
has failed, with the speed this setting changes determined by the Update Time setting configured under GOOSE
Transmission.
1601-0320 651
Chapter 13 - Status
GOOSE HEADER
Path:Status > Communications > GOOSE HDR Status
Range: OFF, ON
Default: OFF
This setting validates the GOOSE packet structure. A GOOSE HEADER STATUS of “ON” indicates that the
structure of the last GOOSE packet was valid.
GOOSE ANALOG
Path:Status > Communications > GOOSE Analog AV
FLOAT 1 to 24
Range:
Default: 0.0
SINT32 1 to 8
Range:
Default: 0
652 1601-0320
Chapter 13 - Status
Range: YES, NO
Default: YES
MAIN VALIDATED DONE
Range: YES, NO
Default: YES
NOT RUNNING.ERROR CID
Range: NO, YES
Default: NO
RUNNING.DEFAULT CID
Range: NO, YES
Default: NO
RUNNING.SAVING CID TO FLASH
Range: NO, YES
Default: NO
CID HANDLING DONE
Range: YES, NO
Default: YES
NUMBER OF CONNECTED CLIENTS
Default: 0
CLIENT 1(8) IP ADDRESS
Range: 0, 0XFFFFFFFF
Default: 0
ACTIVITY STATUS
The communication state for each enabled communication type is shown by its value. The main CPU and Comms
software sets/resets the active bits for all enabled communication types. The communication state bits are not
latched.
Path:Status > Communications > Activity Status
SERIAL MODBUS
Range: NONE, ACTIVE
Default: NONE
ETHERNET MODBUS
Range: NONE, ACTIVE
Default: NONE
1601-0320 653
Chapter 13 - Status
Note:
The MODBUS ACTIVITY TIMEOUT specifies the minimum time without Modbus communication. This timeout is used to
declare the Modbus ‘Loss of Communication’ state. The MODBUS ACTIVITY TIMEOUT must be set to a value other than 0
for the Serial Modbus and Ethernet Modbus Activity Status to work properly.
Note:
MODBUS ACTIVITY TIMEOUT is set under:Setpoints > Device > Communications > Modbus Protocol
CONNECTIONS
Path:Status > Communications > Connections
MMS TCP - Maximum
Range: 0 to 99 in steps of 1
Default: 0
MMS TCP - Remaining
Range: 0 to 99 in steps of 1
Default: 0
Modbus TCP - Maximum
Range: 0 to 99 in steps of 1
Default: 0
Modbus TCP - Remaining
Range: 0 to 99 in steps of 1
Default: 0
DNP TCP - Maximum
Range: 0 to 99 in steps of 1
Default: 0
DNP TCP - Remaining
Range: 0 to 99 in steps of 1
Default: 0
IEC - 104 - Maximum
Range: 0 to 99 in steps of 1
Default: 0
IEC - 104 - Remaining
Range: 0 to 99 in steps of 1
Default: 0
OPC - UA - Maximum
Range: 0 to 99 in steps of 1
654 1601-0320
Chapter 13 - Status
Default: 0
OPC - UA - Remaining
Range: 0 to 99 in steps of 1
Default: 0
SFTP - Maximum
Range: 0 to 99 in steps of 1
Default: 0
SFTP - Remaining
Range: 0 to 99 in steps of 1
Default: 0
1601-0320 655
Chapter 13 - Status
SWITCH 1(X)
Range: Not Configured, Opened, Closed, Intermittent, Discrepancy
Default: Not Configured
Arc Flash
Path: Status > Arc Flash > Arc Flash 1
The status value shows the state of the given Flex operand related to Arc Flash protection.
Light 1(4) PKP
Range: ON, OFF
HS Phase IOC PKP A/B/C
Range: ON, OFF
HS Ground IOC PKP
Range: ON, OFF
Arc Flash OP
Range: ON, OFF
656 1601-0320
Chapter 13 - Status
Contact Inputs
Path: Status > Contact Inputs
The status of the Contact Inputs is shown here (see device menu via the menu path). The Off/On display indicates
the logic state of the Contact Input.
Output Relays
Path: Status > Output Relays
The status of all output relays is shown here, see above. In the Parameter column, the value indicates the label on
the output terminal. The Value column indicates the present ON or OFF state of the output relay.
Virtual Inputs
Path: Status > Virtual Inputs 1(X)
The state of all virtual inputs is shown here, see next figure. The value for each Virtual Input is shown on the control
panel graphically as a toggle switch in either the On (|) state or the Off (O) state.
Virtual Outputs
Path: Status > Virtual Outputs
1601-0320 657
Chapter 13 - Status
The state of all virtual outputs is shown here, see next figure. The value for each Virtual Output is shown on the
control panel graphically as a toggle switch in either the On (|) state or the Off (O) state.
Flex State
Path: Status > Flex States
There are 256 Flex state bits available. The status value indicates the state of the given Flex state bit.
Device Status
The general status of system components is displayed here.
Path: Status > Device Status
RUNNING, SAVING CID to FLASH
Range: YES, NO
Default: NO
CID HANDLING DONE
Range: YES, NO
Default: YES
SELF-TEST FAULT
658 1601-0320
Chapter 13 - Status
Range: YES, NO
Default: NO
MAINTENANCE
Range: YES, NO
Default: NO
IN SERVICE
Range: YES, NO
Default: YES
PICKUP STATE
Range: YES, NO
Default: YES
BREAKER X CONNECTED
Range: YES, NO
Default: YES
BREAKER X CLOSED
Range: YES, NO
Default: NO
BREAKER X TRIPPED
Range: YES, NO
Default: NO
ALARM
Range: YES, NO
Default: NO
TRIP
Range: YES, NO
Default: NO
ACTIVE GROUP
Range: SP Group 1-6 Active
Default: SP Group 1 Active
Clock Status
Path: Status > Clock
SYSTEM CLOCK
Range: MMM DD YY HH:MM:SS
RTC SYNC SOURCE
Range: None, Port 4 PTP Clock, Port 5 PTP Clock, IRIG-B, SNTP Server 1, SNTP Server 2
1601-0320 659
Chapter 13 - Status
The RTC SYNC SOURCE actual value is the time synchronizing source the relay is using at present.
PTP Status
The present values of the PTP protocol are displayed here.
Path:Status > PTP
Grandmaster ID is the grandmaster Identity code being received from the present PTP grandmaster, if any. When
the relay is not using any PTP grandmaster, this actual value is zero. The grandmaster Identity code is specified by
PTP to be globally unique, so one can always know which clock is grandmaster in a system with multiple
grandmaster-capable clocks.
RTC Accuracy is the estimated maximum time difference at present in the Real Time Clock (RTC), considering the
quality information imbedded in the received time signal, how long the relay has had to lock to the time source, and
in the case of time signal interruptions, the length of the interruption. The value 999,999,999 indicates that the
magnitude of the estimated difference is one second or more, or that the difference cannot be estimated.
Port 4 (5) PTP State is the present state of the port’s PTP clock. The PTP clock state is:
● DISABLED: If the port’s function setting is Disabled
● NO SIGNAL: If enabled but no signal from an active master has been found and selected
● CALIBRATING: If an active master has been selected but lock is not at present established
● SYNCH’D (NO PDELAY): If the port is synchronized, but the peer delay mechanism is non-operational
● SYNCHRONIZED: If the port is synchronized
HMI Display
The HMI Display menu option opens a virtual HMI Display window within the EnerVista D&I Setup software. The
virtual HMI display provides front panel access to the relay with clickable buttons and realtime display of the front
panel, including navigation and viewing relay settings, screens, and LEDs.
Path:Status > HMI Display
Note:
The HMI Display functionality is not available with the Advanced Cybersecurity option
660 1601-0320
CHAPTER 14
METERING
Chapter 14 - Metering
662 1601-0320
Chapter 14 - Metering
1601-0320 663
Chapter 14 - Metering
The relay measures all RMS (root mean square) currents and voltages, frequency, and all auxiliary analog inputs.
Other values like neutral current, phasor symmetrical components, power factor, power (real, reactive, apparent),
are derived. A majority of these quantities are recalculated every protection pass and perform protection and
monitoring functions. Displayed metered quantities are updated approximately three (3) times a second for
readability. All phasors and symmetrical components are referenced to the A-N voltage phasor for wye-connected
VTs; to the A-B voltage phasor for delta-connected VTs; or to the phase A current phasor when no voltage signals
are present.
664 1601-0320
Chapter 14 - Metering
Figure 249: An example of the Metering menu (not representative of all models)
All the measured values can be viewed on the front panel display or monitored by remote devices through the
communication system. An example of the HMI display showing actual currents is shown here.
1601-0320 665
Chapter 14 - Metering
The measured values can also be displayed in the PC (EnerVista D&I Setup software). An example follows.
666 1601-0320
Chapter 14 - Metering
The complete list of actual values available in the Metering menu is covered in the following sections.
1601-0320 667
Chapter 14 - Metering
668 1601-0320
Chapter 14 - Metering
1601-0320 669
Chapter 14 - Metering
670 1601-0320
Chapter 14 - Metering
Note:
The values for differential and restraint currents are displayed in per times CT. The CT primary, from the K2 CT Bank
assigned as Signal Input for Winding 1, is the reference CT (base CT) used for estimating the differential and restraint
currents. The winding reference is explained in the Transformer Setup section.
14.4.3 SPEED
Path: Metering > Generator > Speed
SPEED
Range: 0 to 8640 RPM in steps of 1
Default: 0
Note:
The following screen is only displayed if Setpoints \ Monitoring \Generator \ Freq OOB Accum \ Accum 1 \ Function is not
disabled.
1601-0320 671
Chapter 14 - Metering
Path: Setpoints > Metering > Generator > Frequency OOB Accumulation
Note:
Metering value 3rd Harm VN+V0 in Sec is only available if Setpoints>Protection>Group x >Generator > 3rd Harm
Voltage Difference trip or alarm functions are not disabled.
672 1601-0320
Chapter 14 - Metering
14.5 IMPEDANCE/ADMITTANCE
Z1 Resistance
Range: 0.00 to 6553.50 ohms in steps of 0.01
Z1 Reactance
Range: 0.00 to 6553.50 ohms in steps of 0.01
Z1 Magnitude
Range: 0.00 to 6553.50 ohms in steps of 0.01
Z1 Angle
Range: -359.9° to 359.9° in steps of 0.1
1601-0320 673
Chapter 14 - Metering
674 1601-0320
Chapter 14 - Metering
14.6 CURRENTS
Note:
The number of Currents supported is order code dependent.
The CT bank names shown are set in the CT Bank Name setpoints under Setpoints > System > Current Sensing
> CT Bank X.
Note:
Below is a complete list of quantities. The quantities visible to you will depend on the model and order code
Path: Metering > CT Bank 1-J1 (CT Bank 2-K1) (CT Bank 3-K2) (CT Bank 4-JK)
Ground (Ig)
Range: 0.000 to 12000.000 A
Neutral (In)
Range: 0.000 to 12000.000 A
1601-0320 675
Chapter 14 - Metering
Average (I AVG)
Range: 0.000 to 12000.000 A
Note:
Percent of load-to-trip is calculated from the phase with the highest current reading. This metered value is the ratio between
the highest phase current injected for the current bank, and the lowest pickup setting among all Phase Timed and
Instantaneous overcurrent elements. If all these elements are disabled, the value displayed is 0.
Note:
For example, if the lowest pickup is 0.5 xCT, and the highest injected phase current is 1 xCT, the displayed value for load-to-
trip is 200%.
676 1601-0320
Chapter 14 - Metering
1601-0320 677
Chapter 14 - Metering
14.8 VOLTAGES
Note:
The number of Voltages supported is order code dependent.
Note:
The VT bank names shown are set in the Phase VT Bank Name setpoints under Setpoints > System > Voltage Sensing >
VT.
Note:
Below is a complete list of quantities. The quantities visible to you will depend on the model and order code
Phase A (Van)
Range: 0.00 to 600000.00 V
Phase B (Vbn)
Range: 0.00 to 600000.00 V
Phase C (Vcn)
Range: 0.00 to 600000.00 V
Neutral (Vn)
Range: 0.00 to 600000.00 V
678 1601-0320
Chapter 14 - Metering
1601-0320 679
Chapter 14 - Metering
680 1601-0320
Chapter 14 - Metering
14.9 FREQUENCY
Note:
Below is a complete list of quantities. The quantities visible to you will depend on the model and order code
CT Frequency
Range: 20 to 100 Hz
3 VT Frequency
Range: 20 to 100 Hz
1601-0320 681
Chapter 14 - Metering
HIGH-SPEED ROCOF
Range: -120.00 to 120.00 Hz/sec in steps 0.01 Hz/sec
Default: 0.00 Hz/sec
682 1601-0320
Chapter 14 - Metering
14.10 HARMONICS
Note:
The number of Harmonics supported is dependent on the model and the order code.
All values relate to phase currents measured on the input cards (J1, etc.).
Path: Metering > Harmonics 1 - J1
1601-0320 683
Chapter 14 - Metering
14.11 SYNCHROCHECK
Path: Metering > Synchrocheck
684 1601-0320
Chapter 14 - Metering
14.12.1 POWER
The following figure illustrates the convention used for measuring power and energy in the 8 Series devices.
Note:
Power 1 is calculated using 3-phase J1 Currents & 3-phase J2 Voltages.
1601-0320 685
Chapter 14 - Metering
!""
2
456 9:
_* ` a*''( 05 ;< = >?@A ;< = >@I
"* ` a*''(
ab ` c OP
476 K; 9;
d%""! 08 07
;< = >@I ;< = >?@A
+,-./0.- 0.1
486 K:
3 [\]^ efhg
#!$%&'( )*'*'( WXYZ
!""
2
456 9:
_* ` a*''( BC D EFGH BC D EGJ
"* ` i'( 05 07
ab ` c 476 K; 9;
QR
d%""! ;< = >@I ;< = >?@A
08
+,-./0.- 0.1 486 LM
[\]^ WXYZ
)*'*'( efjg
#!$%&'( )*'*'(
3 [\]^
456 9:
;< = >?@A ;< = >@I
07 08
_* ` a*''(
"* ` i'( 476 K; 9;
ab ` c ST
05 ;< = >@I ;< = >?@A
d%""! 486
+,-./0.- 0.1 K:
2 WXYZ
!"" efkg
)*'*'(
[\]^
9:
456
08 ;< = >?@A ;< = >@I
_* ` a*''( UV
"* ` i'( 476 LB NB
ab ` c 05
07
d%""! BC D EGJ BC D EFGH
486
+,-./0.- 0.1 K:
2 WXYZ
eflg
!"" mnopqrsptuvw
Figure 254: Flow direction of signed values for watts and VARs
686 1601-0320
Chapter 14 - Metering
1601-0320 687
Chapter 14 - Metering
Directional Power 1
Range: -214748364.8 kW to 214748364.7 kW
Default: 0.0 kW
...
Directional Power X
Range: -214748364.8 kW to 214748364.7 kW
Default: 0.0 kW
688 1601-0320
Chapter 14 - Metering
14.13 ENERGY
Note:
Below is a complete list of quantities. The quantities visible to you will depend on the model and order code.
1601-0320 689
Chapter 14 - Metering
690 1601-0320
Chapter 14 - Metering
This value shows the current value of Pos WattHours energy accumulated during the previous day. This value is
logged at the end of the day, midnight, or 23:59 hrs.
Note:
All Energy Log values can be reset to zero using the command Energy Log Data under Records > Clear Records or by the
Flexlogic operand programmed by the setpoint ENERGY LOG DATA under Device > Clear Records. The Reset Energy Log
D/T in either case is recorded and displayed.
1601-0320 691
Chapter 14 - Metering
14.14 DEMAND
Note:
The number of Current Demand supported is Order Code dependent.
The relay measures Current Demand on each phase, and three phase Demand for real, reactive, and apparent
power. These parameters can be monitored to reduce supplier Demand penalties or for statistical metering
purposes. Demand calculations are based on the measurement type selected under Monitoring > Functions >
Demand. For each quantity, the relay displays the Demand over the most recent Demand time interval, the
maximum Demand since the last maximum Demand reset, and the time and date stamp of this maximum Demand
value. Maximum Demand quantities can be reset to zero at Records > Clear Records > Max Current Demand.
692 1601-0320
Chapter 14 - Metering
Note:
If average current drops below 0.02 x CT, calculation of the minimum real/reactive/apparent demand is blocked, and metering
remains at the level measured at the time of the block.
1601-0320 693
Chapter 14 - Metering
694 1601-0320
Chapter 14 - Metering
1601-0320 695
Chapter 14 - Metering
HS Ground Current
Range: 0.00 to 120000.00 A in steps of 0.01
696 1601-0320
Chapter 14 - Metering
RTDx
Range: -40 to 250°C (-40 to 482°F)
Temperatures < -40°C are displayed as Shorted and temperatures > 250°C are displayed as Open RTD.
Path: Metering > RRTDs
RRTDx
Range: -40 to 250°C
Temperatures < -40°C or temperatures >250°C are displayed as Trouble RRTD
Path: Metering > RTD Maximums
RTD x Max
Range: -40 to 250°C (-40 to 482°F)
Temperatures < -40°C are displayed as Shorted and temperatures > 250°C are displayed as Open RTD.
RRTD x Max
Range: -40 to 250°C (-40 to 482°F)
Temperatures < -40°C are displayed as Shorted and temperatures > 250°C are displayed as Open RRTD.
1601-0320 697
Chapter 14 - Metering
Analog Ip x
Range: -500000 to 500000 units in steps of 1
698 1601-0320
Chapter 14 - Metering
14.20 FLEXELEMENTS
Path: Metering > FlexElements
The operating signals for the FlexElements are displayed in pu values using the definitions of the base units in the
Definitions of the Base Unit for the FLEXELEMENT table. This table can be found in Setpoints > FlexLogic >
FlexElements.
1601-0320 699
Chapter 14 - Metering
700 1601-0320
CHAPTER 15
RECORDS
Chapter 15 - Records
702 1601-0320
Chapter 15 - Records
1601-0320 703
Chapter 15 - Records
15.2 EVENTS
The relay has an event recorder, which runs continuously. All event records are stored in non-volatile memory such
that information is permanently retained. The events are displayed from newest to oldest event. Each event has a
header message containing a summary of the event that occurred, and is assigned an event number equal to the
number of events that have occurred since the recorder was cleared. The event number is incremented for each
new event.
The Event Recorder captures contextual data associated with the last 1024 events listed in chronological order from
most recent to oldest. Events for a particular element are captured, if the setpoint EVENTS is selected as
“Enabled”. By default, the EVENTS setpoint from all elements is enabled.
Path: Records > Event Records
The events are cleared by pressing the pushbutton corresponding to the tab CLEAR, or when issuing clear event
records command from the general clear records menu.
704 1601-0320
Chapter 15 - Records
To open the Event Viewer for a connected device, follow these steps in the EnerVista D&I Setup software:
1. Establish communications with the relay.
2. Select the Setpoints > Records > Events menu item.
3. A small Events window opens displaying the following:
○ Date/Time of Last Clear
○ Events Since Last Clear
○ Date/Time of Last Retrieval
4. In addition, the Event Viewer launches for a detailed view of up to 1024 of the most recent events.
The Event Viewer window runs as a separate application, and can be moved outside of the main window and
resized as needed.
If EnerVista D&I Setup software is closed, the Event Viewer remains open but offline (no further events are received
from running devices, however event data is still available).
The Event List includes all events in descending chronological order. For multiple sources, a Source column
showing the device name or file name is shown between the Date/Time and the Event columns.
1601-0320 705
Chapter 15 - Records
To add an additional connected 8 Series relay to the open Event Viewer, follow these steps:
1. Establish communications with the relay.
2. Select the Setpoints > Records > Events menu item.
3. The Event Viewer adds up to 1024 of the most recent events to the open window, labeled with the new
device name in the Source column.
The Event column is only shown when Show Event Numbers is selected on the Data tab.
On the left side of the Event List a checkbox column with a toggle button at the top allows selection of specific
events. Only the selected events are saved or copied by the Save to File and Copy to Clipboard options in the
File tab.
Use the following keys to navigate quickly through the Event List:
● End scrolls to the bottom of the Event List
● Home scrolls to the top of the Event List
● Page Down scrolls one page down in the Event List
● Page Up scrolls one page up in the Event List
When the Event Viewer and the EnerVista D&I Setup software are both open, new events from connected devices
are added to the Event Viewer as they occur and oscillography and fault report records are gradually retrieved from
the device, in order of oldest to newest (assuming oscillography records and fault report records are saved in a
common location).
Oscillography record events (such as Trans. Rec Trigger shown above) have a symbol in the Data column that
includes a link to launch the oscillography record in the EnerVista D&I Setup software.
Fault report events (such as Fault Rpt Trig shown above) can be opened in the same manner by clicking the fault
report symbol in the Data column.
706 1601-0320
Chapter 15 - Records
FILE TAB
Use the File tab to open event files in the Event Viewer, save events to a file, or copy events to the clipboard.
● Open File: opens a window to browse to an events file (of type .eev, .txt. or .evt) and opens it in the existing
Event Viewer window, or in a new Event Viewer window.
○ Check In New Window to open the file in a new Event Viewer window.
● Save to File: saves the selected events to a file. Hidden (filtered) events are not saved.
○ Select the events to save using the checkboxes on the left of the events list.
○ Check Include Event Data to save full details of each event instead of just a summary.
● Copy to Clipboard: copies the selected events to the clipboard. Hidden (filtered) events are not copied.
○ Select the events to copy using the checkboxes on the left of the events list.
○ Check Include Event Data to copy full details of each event instead of just a summary.
HOME TAB
Use the Home tab to select the events shown in the detailed view, measure time between events, and view the
current Event Viewer statistics.
By default, the Event Viewer opens displaying the Home tab with the last three events selected. Details of these
three events are displayed in the lower pane of the Event Viewer window.
To select up to three events from the list displayed in the Event Viewer, follow these steps:
1. From the Home tab, choose which event to set by clicking button 1, 2, or 3 above the Event Selector label.
2. Click an event from the list of displayed events.
3. The event changes color to match the selected button (blue for 1, green for 2, or red for 3) and the event
details display in the lower pane, highlighted in the same color.
The absolute times between the three selected events are displayed above the Delta Times label.
The Statistics area in the Home tab includes the following information:
● Sources: the number of event sources (devices and files) currently available.
● Events: the number of events being managed by the Event Viewer.
● Filtered: the number of events shown after any active filters are applied. (Filters are applied in the Data tab).
DATA TAB
Use the Data tab to filter the events shown in the Event Viewer.
● Show Event Numbers: toggles on and off the event number column in the list of events. The event number
can be useful for reconciling events between the Eevnt Viewer and local HMI.
● Select Event Sources: provides a drop-down list of all available event sources (devices and files). Uncheck
a device or file to hide the associated events from the main list.
● By default events from all sources are shown.
● Cause of Event Filter: provides an alphabetized list of all event names, allowing different event types to be
shown or hidden.
● By default all events are shown.
1601-0320 707
Chapter 15 - Records
708 1601-0320
Chapter 15 - Records
NUMBER OF REPORTS
This value shows the number of reports since the last clear.
TYPE OF FAULT
Range: N/A, AG, BG, CG, AB, BC, CA, ABG, BCG, CAG, ABC
Default: N/A
This record displays the type of fault.
DISTANCE TO FAULT
Range: 0.00 to 99.99 km/Mile in steps of 0.01 km/Mile
Default: 0.00 km/Mile
This record displays the distance to fault, in kilometers or miles as selected by the UNITS OF LENGTH setpoint.
1601-0320 709
Chapter 15 - Records
"#$ % % &
"#$ +) &
"#! % % &
"#! +) &
+ % +?
+?
"#! %(% % % &
"#! %(% +) &
! +
./00123 425/36
+ , - ! @A@B
7089:3:;28< =;<38>1 425/36 )
'( )
& & C
) %+
& & + (
& &
& * & ! ) %+
GHI =;<38>1 425/36
JKLMNNOPQRST
&
&
&
&!
DE * ,
,F *
710 1601-0320
Chapter 15 - Records
1601-0320 711
Chapter 15 - Records
15.6 BREAKERS
ALARM COUNTER
Range: 0 to 100 in steps of 1
712 1601-0320
Chapter 15 - Records
1601-0320 713
Chapter 15 - Records
COUNTER X ACCUMULATED
Range: -2147483648 to 2147483647 in steps of 1
COUNTER X FROZEN
Range: -2147483648 to 2147483647 in steps of 1
DATE/TIME FROZEN
Range: Date/Time Format (MM/DD/YY HH:MM:SS)
Default: 01/01/70 00:00:00
COUNTER X us FROZEN
Range: 0 to 999999 µs in steps of 1
714 1601-0320
Chapter 15 - Records
DEVICE STATUS
Range: Offline, Online
Default: Offline
The DEVICE STATUS operand is asserted when the last communication attempt has failed. The operand is
deasserted following a successful communication attempt.
1601-0320 715
Chapter 15 - Records
Figure 256: Example of Digital States for the default BSG3 RMD profile
Path: Records > Remote Modbus Device > Device 1 > Analog Values
716 1601-0320
Chapter 15 - Records
RMD-FLEXANALOG 1-64
Range: -2147483648 to 2147483647 in steps of 1
Default: 0
Up to 64 FlexAnalog operands can be shown here.
The value displayed is based on the Enumeration field defined in the Remote Modbus Device Editor for each
specific digital point.
The displayed text is the FlexAnalog name defined in the Remote Modbus Device Editor ‘Label’ field for each
Analog Point in the current profile. See Device > Communications > Remote Modbus Device > Device 1.
The value displayed is based on the Data Type, Multiplier, Decimals, and Units fields defined in the Remote
Modbus Device Setpoint for each specific analog point.
Figure 257: Example for Analog Values of the default BSG3 RMD profile
1601-0320 717
Chapter 15 - Records
Note:
The Clear Records command is also available from Records > Clear Records, however there the allowable settings are only
ON and OFF. (FlexLogic operands cannot be used.)
718 1601-0320
CHAPTER 16
MAINTENANCE
Chapter 16 - Maintenance
720 1601-0320
Chapter 16 - Maintenance
1601-0320 721
Chapter 16 - Maintenance
722 1601-0320
Chapter 16 - Maintenance
1601-0320 723
Chapter 16 - Maintenance
724 1601-0320
CHAPTER 17
SPECIFICATIONS
Chapter 17 - Specifications
726 1601-0320
Chapter 17 - Specifications
17.1 DEVICE
1601-0320 727
Chapter 17 - Specifications
Note:
If the Operate time and/or Timer Accuracy (in ms) for 25 Hz is not specified, then it is 2 times longer than the time specified
for 50 Hz or 2.4 times longer if specified for 60 Hz only.
728 1601-0320
Chapter 17 - Specifications
1601-0320 729
Chapter 17 - Specifications
730 1601-0320
Chapter 17 - Specifications
1601-0320 731
Chapter 17 - Specifications
732 1601-0320
Chapter 17 - Specifications
1601-0320 733
Chapter 17 - Specifications
734 1601-0320
Chapter 17 - Specifications
1601-0320 735
Chapter 17 - Specifications
736 1601-0320
Chapter 17 - Specifications
Curve Timing Accuracy: Currents > 1.03 to 20 x pickup: ±%3 of operate time or ±½ cycle
(whichever is greater) from pickup to operate
Delay: 0.000 – 200.000 in steps 0.001
1601-0320 737
Chapter 17 - Specifications
738 1601-0320
Chapter 17 - Specifications
1601-0320 739
Chapter 17 - Specifications
Number of Elements:
6
740 1601-0320
Chapter 17 - Specifications
Note:
Typical times are average Operate Times including variables such as frequency change instance, test method, etc., and may
vary by ±0.5 cycles.
Note:
Typical times are average Operate Times including variables such as frequency change instance, test method, etc., and may
vary by ±0.5 cycles.
1601-0320 741
Chapter 17 - Specifications
742 1601-0320
Chapter 17 - Specifications
1601-0320 743
Chapter 17 - Specifications
17.3 CONTROL
17.3.3 SYNCHROCHECK
SYNCHROCHECK (25)
Maximum Frequency Difference: 0.01 to 5.00 Hz in steps of 0.01 Hz for frequency window of fnom
±5 Hz
Maximum Angle Difference: 1° to 100° in steps of 1°
Maximum Voltage Difference: 10 to 600000 V in steps of 1 V
Hysteresis for Maximum Frequency Difference: 0.01 to 0.10 Hz in steps of 0.01 Hz
Breaker Closing Time: 0.000 to 6000.000 s in steps of 0.001 s
Dead Source Function: None, LB & DL, DB & LL, DB & DL, DB OR DL, DB XOR DL
Dead/Live Levels for Bus and Line: 0.00 to 1.50 x VT in steps of 0.01 x VT
744 1601-0320
Chapter 17 - Specifications
1601-0320 745
Chapter 17 - Specifications
17.4 MONITORING
746 1601-0320
Chapter 17 - Specifications
17.4.7 DEMAND
DEMAND
Measured Values: Phase A/B/C present and maximum current, three-phase
present, maximum real/reactive/apparent power, minimum real/
reactive/apparent power
Measurement Type: Thermal Exponential, 90% response time (programmed): 5 to
90 min in steps of 1 min.
Block Interval / Rolling Demand, time interval (programmed): 5
to 90 min in steps of 1 min.
Current Pickup Level (845, 850, 889): 10 to 10000 in steps of 1 A
Dropout Level: 96-98% of Pickup level
Level Accuracy: ±2%
1601-0320 747
Chapter 17 - Specifications
17.5 RECORDING
748 1601-0320
Chapter 17 - Specifications
1601-0320 749
Chapter 17 - Specifications
17.6.1 FLEXLOGIC
FLEXLOGIC
Lines of code: 1024
Supported operations: NOT, XOR, OR (2 to 16 inputs), AND (2 to 16 inputs), NOR (2 to
16 inputs), NAND (2 to 16 inputs), latch (reset-dominant), edge
detectors, timers
Inputs: any logical variable, contact, or virtual input
Number of timers: 32
Pickup delay: 0 to 60000 (ms, sec., min.) in steps of 1
Dropout delay: 0 to 60000 (ms, sec., min.) in steps of 1
Timer accuracy: ±3% of delay setting or ±¼ cycle (whichever is greater) from
pickup to operate
17.6.2 FLEXELEMENTS
FLEXELEMENTS
Number of elements: 8
Operating signal: Any analog actual value, or two values in a differential mode
Operating signal mode: Signed, or Absolute value
Operating mode: Level, Delta
Comparison direction: Over, Under
Operate time: FlexElements are processed once per cycle (16 ms at 60 Hz, 20
ms at 50 Hz)
Pickup Level: -30.000 to 30.000 pu in steps of 0.001 pu
Hysteresis: 0.1 to 50.0% in steps of 0.1%
Delta dt: 40 msec to 45 days
Pickup and dropout delays: 0.000 to 6000.000 s in steps of 0.001 s
17.6.3 FLEXSTATES
FLEXSTATES
Number of States: 256 logical variables grouped under 16 Modbus addresses
Programmability: Any FlexLogic operand, any digital input, any virtual input, any
remote input
17.6.4 FLEXCURVES
FLEXCURVES
Number: 4 (A, B, C, D)
750 1601-0320
Chapter 17 - Specifications
FLEXCURVES
Reset points: 40 (0.00 to 0.98 x pickup)
Operate points: 80 (1.03 to 20.0 x pickup)
Time delay: 0 to 200,000,000 ms in steps of 1 ms
Saturation level: 20 times the pickup level
1601-0320 751
Chapter 17 - Specifications
17.7 METERING
Voltages
Parameters: Wye VTs: A-n, B-n, C-n, A-B, B-C, C-A, Average Phase, Neutral
and Residual. Delta VTs: A-B, B-C, C-A, Neutral and Residual
Accuracy: ±0.5% of reading from 15 to 208 V±2% for open Delta
connections
Sensitive Ground
Parameter: Isg
Accuracy (from 0.01 to 0.2 x CT): ±1.30% of rated
Accuracy (> 0.2 x CT): ±0.30% of reading or ±0.60% of rated (whichever is greater)
Power Factor
Parameters: 3-phase; per phase if VT is Wye
Range: 0.01 Lag to 1.00 to 0.01 Lead
752 1601-0320
Chapter 17 - Specifications
Power Factor
Accuracy: ±0.02 for 50 Hz and 60 Hz; ±0.05 for 25 Hz
17.7.2 PHASORS
PHASORS
Current
Parameters: Phase A, B, C, Neutral and Ground
Magnitude Accuracy: ±0.5% of reading or ±0.2% of rated (whichever is greater) from
0.1 to 2.0 x CT
±1.0% of reading > 2.0 x CT
Angle Accuracy: 2° (3° for 25 Hz)
CBCT Angle Accuracy: ±25° (For 50:0.025 CT between 0.5A to 15A)
Voltages
Parameters: Wye VTs: A-n, B-n, C-n, A-B, B-C, C-A, Average Phase, Neutral
and Residual
Delta VTs: A-B, B-C, C-A, Neutral and Residual
Magnitude Accuracy: ±0.5% of reading from 15 to 208 V
±1% for open Delta connections
±10% for 25 Hz with 150 V <V < 208V
Angle Accuracy: 0.5° (15 V <V < 208 V)
17.7.3 FREQUENCY
FREQUENCY
Range: 2.000 to 90.000 Hz
Accuracy at: V = 15 to 208 V: ±0.01 Hz (input frequency 15 to 70 Hz);
I = 0.1 to 0.4 x CT: ±0.020 Hz (input frequency 15 to 70 Hz);
I > 0.4 x CT: ±0.01 Hz (input frequency 15 to 70 Hz)
1601-0320 753
Chapter 17 - Specifications
754 1601-0320
Chapter 17 - Specifications
17.8 INPUTS
17.8.1 AC CURRENTS
AC CURRENTS
CT Rated Primary: 1 to 12000 A
CT Rated Secondary: 1 A or 5 A based on relay ordering
Nominal Frequency: 50 Hz and 60 Hz
Burden: < 0.2 VA at rated secondary
Conversion Range: Standard CT: 0.02 to 46 x CT rating RMS symmetrical.
Sensitive Ground CT module: 0.002 to 4.6 x CT rating RMS
symmetrical.
CBCT (50:0.025): 0 to 15 A
Short Term CT Withstand: 1 second at 100 x rated current
2 seconds at 40 x rated current
Continuous 3 x rated current
CBCT (50:0.025) Withstand: Continuous 150 mA
17.8.2 AC VOLTAGES
AC VOLTAGE
VT Range: 10 to 260 V
Nominal Frequency: 20 to 65 Hz
Burden: <0.25 VA at 120 V
Conversion Range: 1 to 275 V
Voltage Withstand: continuous at 260 V to neutral. 1 min/hr at 420 V to neutral
1601-0320 755
Chapter 17 - Specifications
Note:
For relays with Hardware Revision A, Clock Backup Retention is only 1 hour
756 1601-0320
Chapter 17 - Specifications
1601-0320 757
Chapter 17 - Specifications
17.9 OUTPUTS
758 1601-0320
Chapter 17 - Specifications
Note:
For order codes with a combined total of 2 or 3 type A and M I/O cards, the following ratings are applied to meet UL508
requirements: 1 second on / 10 seconds off, 9% duty cycle
1601-0320 759
Chapter 17 - Specifications
760 1601-0320
Chapter 17 - Specifications
1601-0320 761
Chapter 17 - Specifications
17.11 COMMUNICATIONS
17.11.1 ETHERNET
ETHERNET – BASE OFFERING (“SE” OPTION)
Modes: 10/100 Mbps
One Port: RJ45
Protocol: Modbus TCP, DNP
17.11.2 USB
USB
Standard specification: Compliant with USB 2.0
Protocols: Modbus TCP, TFTP
17.11.3 SERIAL
SERIAL
RS485 port: Isolated
Baud rates: Supports 9600, 19200, 38400, 57600, and 115200 kbps
Response time: 10 ms typical
Parity: None, Odd, Even
Protocol: Modbus RTU, DNP 3.0, IEC 60870-5-103
762 1601-0320
Chapter 17 - Specifications
SERIAL
Maximum distance: 1200 m (4000 feet)
Isolation: 2 kV
Cable: Belden 9841 or similar 24 AWG stranded, shielded twisted-pair
17.11.4 WIFI
WIFI
Standard specification: IEEE802.11bgn
Range: 30 ft (direct line of sight)
1601-0320 763
Chapter 17 - Specifications
17.12.1 APPROVALS
APPLICABLE COUNCIL DIRECTIVE ACCORDING TO
CE compliance Low voltage directive EN60255-27
EMC Directive EN60255-26
R&TTE Directive ETSI EN300 328, ETSI EN301 489-1,
ETSI EN301-489-17,
RoHS Directive RoHS Directive 2011/65/EU, 2015/863
North America cULus UL508, e57838 NKCR, NRGU
CSA C22.2.No 14, e57838 NKCR7,
NRGU7
ISO Manufactured under a registered quality ISO9001
program
764 1601-0320
Chapter 17 - Specifications
Note:
May contain components with FCC ID: XF6-RS9110N1122 and IC ID: 8407A-RS9110N1122
1601-0320 765
Chapter 17 - Specifications
17.13 ENVIRONMENTAL
AMBIENT TEMPERATURES
Storage/Shipping: -40°C to 85°C
Operating: -40°C to 60°C
Humidity Operating up to 95% (non condensing) @ 55°C (As per
IEC60068-2-30 Variant 2, 6 days)
Altitude: 2000m (standard base reference evaluated altitude)
5000m (maximum achievable altitude)
Pollution Degree: II
Overvoltage Category: II
Ingress Protection: IP54 Front (845,850, 869, 889)
IP 50 Front (859)
Insulation Class: 1
Noise: 0 dB
766 1601-0320
Chapter 17 - Specifications
1601-0320 767
Chapter 17 - Specifications
768 1601-0320
APPENDIX A
APPENDIX A
Appendix A - Appendix A
770 1601-0320
Appendix A - Appendix A
1 WARRANTY
For products shipped as of 1 October 2013, GE Digital Energy warrants most of its GE manufactured products for
10 years. For warranty details including any limitations and disclaimers, see the GE Digital Energy Terms and
Conditions on the GE website.
For products shipped before 1 October 2013, the standard 24-month warranty applies.
1601-0320 771
Appendix A - Appendix A
772 1601-0320
Imagination at work
GE Vernova
650 Markland Street
Markham, Ontario
Canada L6C 0M1
+44 (0) 1785 250 070
[email protected]
© 2023 General Electric. All rights reserved. Information contained in this document is indicative only. No representation or warranty is
given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and
commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third
parties, without express written authority, is strictly prohibited.
1601-0320