ED-2002-020 High Speed Mix Analog Input Output Module (4366)
ED-2002-020 High Speed Mix Analog Input Output Module (4366)
ED-2002-020 High Speed Mix Analog Input Output Module (4366)
Document No.:ED-2002-020
Version: 1.0
MESSUNG SYSTEMS
EL-2, J- Block MIDC Bhosari,
Pune – 411026.(INDIA)
High Speed Mix Analog Input Output Module(4366) Published July 2002
Document No.: ED-2002-020/V1.0 Page 1 of 28
EXGEN PLC I/O Modules Messung Systems
Revision
Published July 2002 High Speed Mix Analog Input Output Module(4366)
Page 2 of 28 Document No.: ED-2002-020/V1.0
Messung Systems NEXGEN PLC I/O Modules
INDEX
INDEX OF FIGURES
Figure 1 : Front View of High Speed Mix Analog Module..........................................................6
Figure 2 : Block diagram of High Speed Mix Analog Module ....................................................8
Figure 3 :Data Range of Analog Input Voltage Signal...............................................................9
Figure 4 :Data Range of Analog Input Current Signal.............................................................10
Figure 5 :Data Range of Analog Output Voltage Signal..........................................................11
Figure 6 :ADC Coversion Cycle ..............................................................................................13
Figure 7 : Digital Filter Action ..................................................................................................14
Figure 8 : Input Output Image Mapping of High Speed Mix Analog Module ...........................15
Figure 9 : Memory Mapping of High Speed Mix Analog Module ............................................16
Figure 10 :Connection diagram of High Speed Mix Analog Module .......................................19
High Speed Mix Analog Input Output Module(4366) Published July 2002
Document No.: ED-2002-020/V1.0 Page 3 of 28
EXGEN PLC I/O Modules Messung Systems
Note must be read and understood. Each of the symbols used is listed
below; with a brief description of its meaning.
Warning !
Warning !
Published July 2002 High Speed Mix Analog Input Output Module(4366)
Page 4 of 28 Document No.: ED-2002-020/V1.0
Messung Systems NEXGEN PLC I/O Modules
1. Module Overview
This is high speed mix analog module. It provides four differential analog
voltage input channels and two non-isolated analog output channels. Four
differential analog voltage/current inputs are converted into equivalent binary
numbers and for two channels, binary data from CPU module is converted to
equivalent analog voltage output. For analog input, this is sigma delta type
analog to digital conversion where as for analog output. R-2R type of digital
to analog conversion is used. ADC is with 16-bit resolution. DAC is with 12-
bit resolution. Conversion time for ADC is 1 ms per channel. Conversion time
for DAC is 200 µs
The analog range supported is.
Analog input
• 0 to +10 VDC
• 0 to 20 mA
Analog output
• 0 to +10 VDC
The resolution is 312.5 µV/ 625 µA for analog input. The resolution is 2.50
mV for analog output.
This is an intelligent module with on board processor and memory. The data
transfer between CPU module and high speed mix analog module takes
place by 'READ_W' and 'WRITE_W' functions in application program. The
module status is available in input image.
The figure 1 on next page shows front view of high speed mix analog
module.
High Speed Mix Analog Input Output Module(4366) Published July 2002
Document No.: ED-2002-020/V1.0 Page 5 of 28
EXGEN PLC I/O Modules Messung Systems
4366
Terminal Block MIXED ANALOG IO
Fixing Screw 4 IP –2 OP
NO 5 V SUPPLY
01 Module
02 CPU FAULT Status
03 ADC FAULT LEDs
04
05
06
07
08
09
10 CH0
11 CH1
Channel
Front Shield 12 Status
CH2
Plate 13 LEDs
CH3
14
V0 +
15
16
I0 +
17
18
V2 + IO Label
38 Pin COM 0
Removable 19
I2 +
Terminal Block 20
V1 +
21
COM 2
22
I1 +
23
V3 +
24
COM 1
25
I3 +
26
VOUT 1
27
COM 3
28
AG
29
VOUT 2
30
31
AG
32
33
34
FG
35
36
Terminal Block
37
Fixing Screw 38
The module provides LED indications on the front. Brief information about
channel can be written on the front door. Behind front door, 38-pin removable
terminal block is provided for interfacing. The wiring details are shown on
backside of front door.
The high speed mix analog module can be configured in any IO slot of the
PLC. The number of high speed mix analog module is limited by back panel
current capacity. In all, 13 words information per module is available.
Published July 2002 High Speed Mix Analog Input Output Module(4366)
Page 6 of 28 Document No.: ED-2002-020/V1.0
Messung Systems NEXGEN PLC I/O Modules
High Speed Mix Analog Input Output Module(4366) Published July 2002
Document No.: ED-2002-020/V1.0 Page 7 of 28
EXGEN PLC I/O Modules Messung Systems
2. Module Operation
This chapter helps in getting started with high speed mix analog module. It
describes the basic operation of the module. This chapter explains
operational details of:
• Block Diagram
• Input Range
• Output Range
• On-Board Processor Operations
• Module Information
Channel 0
Watch Analog to
0 to +10 VDC
Dog Digital
Channel 0 0 to 20 mA
+5V
Converter
Input 500 Ω
Circuit
On board O Instrumentation
Processor P Amplifier
T
I Channel 3
C
Channel 0 to +10 VDC
Memory for A
Configuration, L Multiplexer Channel 3 0 to 20 mA
Data, Status Input 500 Ω
Information I Circuit
S
O
L Output 0 Driver
A
T Channel 0
DAC0
I
R-2R
O 0 to +10 VDC
CPU
N Output Signal
Module
Module
Interface
Circuit Output 1 Driver
Channel 1
From DAC1
back R-2R
plane 0 to +10 VDC
Output Signal
+15 V
+ 5 VDC
-15 V Isolated
DC-to-DC Supply for
Converter +5 V
5 V GND Analog Circuit
GND
Published July 2002 High Speed Mix Analog Input Output Module(4366)
Page 8 of 28 Document No.: ED-2002-020/V1.0
Messung Systems NEXGEN PLC I/O Modules
The module provides four analog to digital channels for analog input. CPU
bus is optically isolated from ADC circuit. The enabled channel input signals
are multiplexed and then amplified by differential amplifier for ADC input.
Thus sigma-delta (Σ/ ∆) ADC converts only enabled analog channels to
digital value one by one. On-board processor manipulates the converted
count for each channel. It provides instantaneous as well as filtered channel
data information.
The module also provides two digital to analog channels. CPU bus is
optically isolated from DAC circuit. The data from CPU for two channels is
stored in dual port module memory registers. DAC (R–2R type) converts
binary data to an equivalent analog output voltage. The module provides
proportional 0 to + 10 VDC. In output driving stage, presets are provided for
adjustments of gain and offset for each channel. These are factory settings
and should not be tampered.
The module works on 5 VDC supply from back plane. 5 VDC supply is
directly given to digital circuit. Also, DC-to-DC converter generates isolated ±
15 VDC and + 5 VDC as required for analog section. If isolated supply doe
analog section is not available to module, it generates 'No 5 V Supply' signal
for main CPU.
0 VDC
+10 VDC
$0000
$ 7D00
High Speed Mix Analog Input Output Module(4366) Published July 2002
Document No.: ED-2002-020/V1.0 Page 9 of 28
EXGEN PLC I/O Modules Messung Systems
625 µA 20.48 mA
$1 $ 7FFF
0 VDC
20 mA
$0000
$ 7D00
The module provides 15-bit resolution. The figure above shows digital data
and associated input voltage values.
For 0 to +10 V range, the voltage span is 10 V and there can be 32,000 (15
bits) equal steps. Each step corresponds to –
10 V / 32000 = 312.5 µV
20 mA / 32000 = 625 µA
The table below shows typical data values in decimal as well as hexadecimal
format and their equivalent voltage values.
Input Voltage Input Current Data Data
Value Value (Decimal) (Hexadecimal)
0 0 0 0
312. 5 µV 625 µA 1 1
1V 2 mA 3200 C80
2V 4 mA 6400 1900
3V 6 mA 9600 2580
4V 8 mA 12800 3200
5V 10 mA 16000 3E80
6V 12 mA 19200 4B00
7V 14 mA 22400 5780
8V 16 mA 25600 6400
9V 18 mA 28800 7080
10 V 20 mA 32000 7D00
10.24 V 20.48 mA 32767 7FFF
Published July 2002 High Speed Mix Analog Input Output Module(4366)
Page 10 of 28 Document No.: ED-2002-020/V1.0
Messung Systems NEXGEN PLC I/O Modules
0 VDC
+10 VDC
$0000
$ 7D00
For voltage range of 0 to +10 V, the digital value ranges from 0 to +32,000
for user convenience.
For 0 to +10 V range, the voltage span is 10 V and there can be 4,000 (12
bits) equal steps. Each step corresponds to –
10 V / 4,000 = 2.5 mV
The table below shows typical data values in decimal as well as hexadecimal
format and their equivalent voltage values. Even though resolution is 2.5 mV
( 4000 steps in 0 to 10 VDC ), input range provided is 0 to +32,000 for user
convenience.
Output Data Data
Value (Decimal) (Hexadecimal)
0 0 0
2.5 mV 1 1
1V 3200 C80
2V 6400 1900
3V 9600 2580
4V 12800 3200
5V 16000 3E80
6V 19200 4B00
7V 22400 5780
8V 25600 6400
9V 28800 7080
10 V 32000 7D00
10.24 V 32767 7FFF
High Speed Mix Analog Input Output Module(4366) Published July 2002
Document No.: ED-2002-020/V1.0 Page 11 of 28
EXGEN PLC I/O Modules Messung Systems
The high speed mix analog module is intelligent module with on-board
processor. The functions of on-board processor are explained below.
After power ON, if isolated supply for analog section is absent then on-board
processor sets Ix.0 bit in input image. After power ON, this processor checks
the hardware called as self test. During self-test, Ix.7 bit is set in case of
watchdog fault and digital section hardware fault. Also ‘CPU Fault’ LED on
front panel is put ON indicating that module is not accessible. Also, during
module operation if digital section hardware is found faulty or watchdog error
is detected, Ix.7 bit is set.
If module CPU section is healthy, Ix.7 bit is cleared. The default values are
loaded for some parameters such as analog input filter values, etc. Module
starts ADC and DAC conversion as per data information available in module
memory. As per input channel selection, module starts sampling and digital
conversion cycle of enabled channels. For more details of IO image of
module, refer chapter 2.4.4. If ‘ADC hardware’ fault is detected, Ix.6 bit in
input image is set and analog input channel data is not updated.
For analog output channels, module reads channel binary data from module
memory and converts it to an equivalent analog output voltage. The module
provides proportional 0 to + 10 VDC. In case of ‘ADC Fault’, analog output is
updated as per binary data.
Published July 2002 High Speed Mix Analog Input Output Module(4366)
Page 12 of 28 Document No.: ED-2002-020/V1.0
Messung Systems NEXGEN PLC I/O Modules
The module samples an analog input channel and converts analog input to
its digital value one by one. After power on, conversion is started for enabled
analog input channels. The disabled are bypassed retaining earlier values.
After one channel conversion, module initiates next channel conversion.
During this conversion period, module processes converted data of previous
channel. The processed data for previous channel is made available during
this period. After converting all healthy channels, processed data of all the
channels is transferred to respective memory area on the module. This cycle
continues. Thus when the processor module performs READ_W operation, it
reads either old or new information i.e. data and status of channels.
Update all
channel
data
The module takes certain time to sample all enabled channels and convert
into digital value. The factors affecting module update time is number of
channels enabled. The module update time is minimum when only one
channel is enabled. Likewise the module update time is maximum when all
channels are enabled.
Band 1 is a band within which analog input count is treated as valid analog
input count. Module samples analog input channel in its scan and converts to
equivalent binary count. This ADC cycle is explained in chapter 2.3.2.
Module compares current count with previous count and if current count lies
within ± band 1, then current count is valid count and respective memory
locations are updated accordingly. If current count is crossing the band 1,
then previous count is considered as valid count and respective memory
locations are not updated. As explained in chapter 2.2, for analog input from
0 to 10 V, module provides equivalent 0 to 32,000 counts. If band 1 value is
50, then acceptable band is previous count ± band 1value.
High Speed Mix Analog Input Output Module(4366) Published July 2002
Document No.: ED-2002-020/V1.0 Page 13 of 28
EXGEN PLC I/O Modules Messung Systems
Band 2 parameter comes in picture when current analog input count crosses
band 1. Once current count has crossed the band 1, this changed count is
stored in temporary memory location. Previous count is treated as valid
count. Now current analog input count is compared with band 2. This is to
confirm whether the change in analog input count is a valid change or some
erroneous change due to noise, etc. If current count is within band 2 , then
current count replaces earlier count in temporary location. In this way if
number of successive samples of current count lies within band 2, then only
the change in analog input count is treated as valid and current count is
transferred to respective memory location. Parameter delay count decides for
how many samples the change in analog input count is to be confirmed. If at
any point, current count is again not within band 2, then changed value
replaces earlier count in temporary memory location and again change is
validated for number of samples as defined in parameter delay count. Thus,
once the change in analog input is detected, it is confirmed if number of
samples lies within a band defined as temporary memory location count ±
band 2 value.
Temporary Memory
location
Analog input
Band 1
Sampling Instance
Band 1
Once ADC cycle is over, module reads the binary data from respective
memory locations and transfers that data to DAC serially. DAC converts
binary data to equivalent voltage signal. This signal is then amplified by
amplifier. The amplifier stage has presets for adjusting offset and gain. The
output of amplifier is 0 to 10 VDC signal. The presets for offset and gain
adjustments are factory set and should not be tampered.
Published July 2002 High Speed Mix Analog Input Output Module(4366)
Page 14 of 28 Document No.: ED-2002-020/V1.0
Messung Systems NEXGEN PLC I/O Modules
This section explains the entire information required and available with high
speed analog module. The following points are discussed
Input output image mapping related to high speed mix analog module is
shown below.
Channel 1
Analog
Channel 2 Input
ADC Fault Ix.6
CPU Fault Ix.7 Module
Interface Channel 3
circuit
Logic Scan
Channel 0
IMM_IN Analog
EN ENO
Output
Channel 1
SLOT
Figure 8 : Input Output Image Mapping of High Speed Mix Analog Module
The module consumes 8 input bits (1 byte) of input image and 8 output bits
(1 byte) of output image in the CPU module. CPU reads the status of module
in input scan. For immediate updation of input image in application program,
IMM_IN functions can be used in application program whenever required.
For the details refer chapter 2.4.4.
High Speed Mix Analog Input Output Module(4366) Published July 2002
Document No.: ED-2002-020/V1.0 Page 15 of 28
EXGEN PLC I/O Modules Messung Systems
The memory mapping related to high speed analog module is shown in figure
below.
6 Words 6 Words
Analog input channels enable/disable MW50 WRITE_W Analog input channels enable/disable MMW00
Analog output channel 0 data MW52 EN ENO Analog output channel 0 data MMW02
Analog output channel 1 data MW54 Analog output channel 1 data MMW04
Analog input filter value 1 MW56 SLOT
Analog input filter value 1 MMW06
Analog input filter value 2 MW58 Analog input filter value 2 MMW08
DATA
Analog input filter value 3 MW60 Analog input filter value 3 MMW10
LEN
ADDR
9 Words 9 Words
Analog input channel 0 data (Filtered) MW100 Analog input channel 0 data (Filtered) MMW256
READ_W Analog input channel 1 data (Filtered) MMW258
Analog input channel 1 data (Filtered) MW102
EN ENO Analog input channel 2 data (Filtered) MMW260
Analog input channel 2 data (Filtered) MW104
Analog input channel 3 data (Filtered) MW106 SLOT Analog input channel 3 data (Filtered) MMW262
Analog input channel 0 data (Instant) MW108 Analog input channel 0 data (Instant) MMW264
Analog input channel 1 data (Instant) MW110 DATA Analog input channel 1 data (Instant) MMW266
Analog input channel 2 data (Instant) MW112 Analog input channel 2 data (Instant) MMW268
LEN Analog input channel 3 data (Instant) MMW270
Analog input channel 3 data (Instant) MW114
Module scan time MW116 Module scan time MMW272
ADDR
The analog input channel enable/ disable configuration and filter values from
PLC variable area e.g. memory or page is transferred to module memory
when WRITE_W function gets executed in application program i.e. in logic
scan. The module takes appropriate action on configuration information
change immediately. After power on, the module starts converting enabled
input channels. If filter values are modified or channel is enabled / disabled, it
takes effect only in the subsequent conversion cycle. The configuration, filter
values can be modified by using WRITE_W function. Similarly channel can
be enabled or disabled during normal operation for optimum results.
CPU writes binary data for two analog output channels to module memory
words. The module coverts this data to equivalent analog output voltage.
These values can be modified by using WRITE_W function.
The analog input channel readings and module scan time count can be read
from the module using READ_W function.
Published July 2002 High Speed Mix Analog Input Output Module(4366)
Page 16 of 28 Document No.: ED-2002-020/V1.0
Messung Systems NEXGEN PLC I/O Modules
As discussed in chapter 2.4.1, input image bits are used as module status
indications. User can check the module status through application program.
The module writes status in its input image area cyclically. The CPU reads
this input image area in input scan. If 'IMM_IN' function is executed in logic
scan for a particular slot, it stops current logic scan, executes input scan for
defined slot and resumes logic scan again. This is useful when ever
immediate updation of input image is needed. The functions of input image
bits are given below
Whenever accessing the module, user must check the module status bit Ix.0
and Ix.7. Whenever, isolated supply to analog section is absent or faulty, ‘No
5 V Supply’ bit Ixx.0 is set. In this case, ‘ADC Fault’ bit Ixx.6 also set.
High Speed Mix Analog Input Output Module(4366) Published July 2002
Document No.: ED-2002-020/V1.0 Page 17 of 28
EXGEN PLC I/O Modules Messung Systems
• Module Installation
• Connection Details
• Precautions to be taken
The installation procedure for high speed mix analog module is same as any
other discrete I/O module.
The figure on next page shows the connection diagram of high speed mix
analog module
Published July 2002 High Speed Mix Analog Input Output Module(4366)
Page 18 of 28 Document No.: ED-2002-020/V1.0
Messung Systems NEXGEN PLC I/O Modules
01
02
03
04
05
06
07
08
09
10
11
12
+
13
14
0 to 10 VDC Input V0 +
15
-- 16
I0 +
17
+ V2 +
18
0 to 20 mA Input 19
COM 0
-- I2 +
20
V1 +
21
To interface current input, it is COM 2
22
necessary to short Vn + and In I1 +
23
terminals of respective channel. V3 +
24
COM 1
25
I3 +
26
+ VOUT 1
27
0 to 10 VDC Output 28
COM 3
-- AG
29
+ 30
VOUT 2
0 to 10 VDC Output 31
-- 32
AG
33
34
FG
35
36
37
38
High Speed Mix Analog Input Output Module(4366) Published July 2002
Document No.: ED-2002-020/V1.0 Page 19 of 28
EXGEN PLC I/O Modules Messung Systems
Analog output is taken from VOUT n and AG. Analog output 1 can be taken
from terminal numbers 27 and 29. Analog output 2 can be taken from
terminal numbers 30 and 32.
• All power circuit wiring e.g. connected to power supply module, power
contactors, etc i.e. high voltage wiring should be kept separate and apart
from thermocouple signals.
• Digital input wiring and digital output wiring (especially, relay output and
AC output) should be separately bundled and kept as apart as possible
from analog signals.
• Analog signals should be carried through shielded cables.
Depending upon the type of modules used in PLC, separate ducts should be
provided for
• Power circuit wiring and power cables.
• Input cables
• Output cables
• All cables carrying low level signals for analog IO modules,
thermocouple/ RTD input modules and for communication.
The high speed mix analog module provides 4 analog input channels and 2
analog output channels, which can be independently operated. Configuring
the slot for high speed mix analog module is just like any other discrete IO
module only. The programming and documentation software DOXMINI+ is
used for configuration and programming. The module consumes 1 byte of
input image and 1 byte of output image. The input image is used for reading
status of module. For more details, refer chapter 2.4.4.
Input module in first slot 0 consumes IB0 to IB3 of input image. Output
module in slot 1 consumes QB4 to QB7 of output image. High speed mix
analog module consumes IB8 of input image and QB8 of output image.16
DC Output module in slot 3 consumes QB9 and QB10 of output image.
The high speed mix analog module can be configured in any slot of PLC. It
provides 4 differential input channels and 2 non-isolated output channels.
Analog input channels can be independently used for voltage or current
inputs. Following information is provided by CPU module to high speed mix
analog modules
• Channel enable/disable
• Analog input filter values
• Analog output binary data
High Speed Mix Analog Input Output Module(4366) Published July 2002
Document No.: ED-2002-020/V1.0 Page 21 of 28
EXGEN PLC I/O Modules Messung Systems
Bit wise information is stored in module memory word MMW #0 for four
analog input channels as shown below.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Analog Input 0 Enable 1
Disable 0
Analog Input 1 Enable 1
Disable 0
Analog Input 2 Enable 1
Disable 0
Analog Input 3 Enable 1
Disable 0
Analog input 0 enable/disable bit is bit 0 of MMW#0 and so on. If this bit is
set, analog input channel 0 is enabled and module samples and converts
input to equivalent binary value. Channel 0 data is updated accordingly. Also,
corresponding channel LED indication (green) on module is switched ON
indicating that channel is enabled. If this bit is reset, analog input channel 0 is
disabled and the channel is not sampled and channel data is not updated.
Corresponding channel LED indication on module is switched OFF.
During module power ON, default value $000F is loaded to MMW#0 enabling
all the four analog input channels. At the same time, all four channel LEDs
are switched ON. User can modify this word by WRITE_W function for
optimum module scan time.
Module memory word MMW #2 holds data for analog output channel 0
whereas MMW #4 holds data for analog output channel 1.
The data range is from 0 to 32,000 for 0 to 10 VDC output. For more details
of analog voltage output and equivalent binary data, refer chapter 2.2.
Published July 2002 High Speed Mix Analog Input Output Module(4366)
Page 22 of 28 Document No.: ED-2002-020/V1.0
Messung Systems NEXGEN PLC I/O Modules
Three filter values are to be programmed for stable analog input reading as
per varous site conditions. These three values are written to module memory
words MMW#6 to MMW#10.
During module power ON, following default values are loaded.User can
modify these words by WRITE_W function as per site conditions to get stable
analog input reading.
Module memory words MMW #256 to MMW #262 are module memory words
for four channel readings updated after applying software filter. Module
memory words MMW #264 to MMW #270 are module memory words for four
channel readings updated immediately.
Module scan count is available in module memory word MMW#272. The time
in nano seconds can be calculated as below.
High Speed Mix Analog Input Output Module(4366) Published July 2002
Document No.: ED-2002-020/V1.0 Page 23 of 28
EXGEN PLC I/O Modules Messung Systems
4.5 Programming
The data in PLC variables is transferred to the high speed mix analog
module when 'WRITE_W' function is executed. The data in the PLC variables
can be updated using functions like 'MOV_W', arithmetic or any other
functions. The data from high speed mix analog module memory can be
transferred to PLC variables when 'READ_W' function is executed.
The WRITE_W function below shows data transfer from the CPU module
memory to high speed mix analog module memory. The details of transfer
are -
'WRITE_W' function gets executed when condition for enable 'EN' is ON.
'ENO' output becomes ON, when EN is ON and function is executed
successfully. ENO is OFF if
The 'READ_W' function below shows data transfer from the high speed mix
analog module memory to CPU memory. The details of transfer are -
‘READ_W' function gets executed when condition for enable 'EN' is ON.
'ENO' output becomes ON, when EN is ON and function is executed
successfully. ENO is OFF if
Published July 2002 High Speed Mix Analog Input Output Module(4366)
Page 24 of 28 Document No.: ED-2002-020/V1.0
Messung Systems NEXGEN PLC I/O Modules
Example of basic application program is given below. For the same, refer
Nexgen PLC configuration shown in chapter 4.1. In the configuration,
following points are to be noted.
I 8.0 is a module status bit as 'No 5 V Supply' bit. I8.0 is set if 5 VDC supply
to module is not healthy.
I 8.6 is a 'ADC Fault' bit. It is set in case of ADC circuit hardware fault. If this
bit is set, analog input channel readings are not updated.
I 8.7 is a module CPU circuit status bit as 'CPU Fault' bit. This is set in case
of watchdog fault.
Check 'ADC Fault' bit I8.6 while reading analog input channel data. In case of
ADC fault, analog input channel data is not updated and so data is not valid.
During self test of module at the time of power ON, default values are loaded
in MMW#0 and MMW#6 to MMW#10. This enables all the four analog input
channels indicated by four channels status LEDs. Default filters values are
also loaded. If user wants to continue with this configuration, it is not
necessary to write the configuration again. If user wants change the
configuration, it can be done using WRITE_W function as explained further.
• Module Error bit becomes OFF i.e. System bit S4.2 is OFF
• No 5 V Supply bit becomes OFF i.e. Input bit I8.0 is OFF
• CPU Fault bit becomes OFF and Input bit I8.7 is OFF
High Speed Mix Analog Input Output Module(4366) Published July 2002
Document No.: ED-2002-020/V1.0 Page 25 of 28
EXGEN PLC I/O Modules Messung Systems
After transferring this information to high speed mix analog module memory,
module starts functioning as per requirement. Enable 'READ_W' function
with any condition M1.0 with interlocks of Module Error bit S4.2, 'CPU Fault'
bit I8.7 and ‘ADC Fault’ bit I8.6. When 'READ_W' function is executed, the
analog input channel readings stored in module memory MMW#256 to
MMW#270 and module scan count stored in MMW#272 are transferred to
CPU memory MW100 to MW#116 respectively.
Published July 2002 High Speed Mix Analog Input Output Module(4366)
Page 26 of 28 Document No.: ED-2002-020/V1.0
Messung Systems NEXGEN PLC I/O Modules
After execution, filtered analog input data from four channels is available in
PLC variables MW100 to MW106.
Instantanous analog analog input data from four channels is available in
MW108 to MW114. Module scan count is stored in MW116. This data can be
proceesed further in application program.
High Speed Mix Analog Input Output Module(4366) Published July 2002
Document No.: ED-2002-020/V1.0 Page 27 of 28
EXGEN PLC I/O Modules Messung Systems
MESSUNG SYSTEMS
EL – 2, J - Block, MIDC, Bhosari,
PUNE – 411 026. INDIA
Tel. – (+91) –020 – 712 0807, 712 2807
Fax. – (+91) –020 –712 0391
Document No.:ED-2002-006
Published July 2002 High Speed Mix Analog Input Output Module(4366)
Page 28 of 28 Document No.: ED-2002-020/V1.0