ASCE 7 10 Wind Load Example
ASCE 7 10 Wind Load Example
ASCE 7 10 Wind Load Example
Example
A fully worked example of ASCE 7-10 wind load
calculations
SkyCiv released a free wind load calculator that has several code
references including the ASCE 7-10 wind load procedure. In this section,
we are going to demonstrate how to calculate the wind loads, by using an
S3D warehouse model below:
64 ft × 104 ft in plan
Eave height of 30 ft
Dimensions
Apex height at elev. 36 ftRoof slope 3:16 (10.62°)
With opening
Although there are a number of software that have wind load calculation
already integrated into their design and analysis, only a few provide a
detailed computation of this specific type of load. Users would need to
conduct manual calculations of this procedure in order to verify if the
results are the same as those obtained from the software.
p=qGCp−qi(GCpi)p=qGCp−qi(GCpi) (1)
p=qGfCp−q(GCpi)p=qGfCp−q(GCpi) (2)
Where:
q=0.00256KzKztKdV2q=0.00256KzKztKdV2 (3)
qq = qhqh for leeward walls, side walls, and roofs,evaluated at roof mean
height, hh
qq = qzqz for windward walls, evaluated at height, zz
qiqi = qhqh for negative internal pressure, (−GCpi)(−GCpi) evaluation
and qzqz for positive internal pressure evaluation (+GCpi)(+GCpi) of
partially enclosed buildings but can be taken as qhqh for conservative
value.
KzKz = velocity pressure coefficient
KztKzt= topographic factor
KdKd= wind directionality factor
VV = basic wind speed in mph
We will dive deep into the details of each parameter below. Moreover, we
will be using the Directional Procedure (Chapter 30 of ASCE 7-10) in
solving the design wind pressures.
Risk Category
The first thing to do in determining the design wind pressures is to
classify the risk category of the structure which is based on the use or
occupancy of the structure. For this example, since this is a plant
structure, the structure is classified as Risk Category IV. See Table 1.5-1
of ASCE 7-10 for more information about risk categories classification.
When viewing the wind maps, take the highest category number of the
defined Risk or Occupancy category. In most cases, including this
example, they are the same. From Figure 26.5-1B, Cordova, Memphis,
Tennessee is somehow near where the red dot on Figure 3 below, and
from there, the basic wind speed, VV, is 120 mph. Take note that for other
locations, you would need to interpolate the basic wind speed value
between wind contours.
Figure 3. Basic wind speed map from ASCE 7-10.
Exposure Category
See Section 26.7 of ASCE 7-10 details the procedure in determining the
exposure category.
Exposure Example
Suburban residential area with mostly single-family dwellings – Low-rise structures, less than 30 ft high, in
the center of the photograph have sites designated as exposure b with surface roughness Category B terrain
around the site for a distance greater than 1500 ft in any wind direction.
An urban area with numerous closely spaced obstructions having the size of single-family dwellings or larger
Exposure – For all structures shown, terrain representative of surface roughness category b extends more than twenty
B times the height of the structure or 2600 ft, whichever is greater, in the upwind direction. Structures in the
foreground are located in exposure B – Structures in the center top of the photograph adjacent to the clearing
to the left, which is greater than approximately 656 ft in length, are located in exposure c when the wind
comes from the left over the clearing.
Flat open grassland with scattered obstructions having heights generally less than 30 ft.
Exposure
Open terrain with scattered obstructions having heights generally less than 30 ft for most wind directions, all
1-story structures with a mean roof height less than 30 ft in the photograph are less than 1500 ft or ten times
C
the height of the structure, whichever is greater, from an open field that prevents the use of exposure B.
A building at the shoreline (excluding shorelines in hurricane-prone regions) with wind flowing over open
Exposure water for a distance of at least 1 mile. Shorelines in exposure D include inland waterways, the great lakes,
D and coastal areas of California, Oregon, Washington, and Alaska.
Where:
Exposure α zgzg(ft)
B 7 1200
C 9.5 900
D 11.5 700
Usually, velocity pressure coefficients at the mean roof height, KhKh, and
at each floor level, KziKzi, are the values we would need in order to solve
for the design wind pressures. For this example, since the wind pressure
on the windward side is parabolic in nature, we can simplify this load by
assuming that uniform pressure is applied on walls between floor levels.
The plant structure has three (3) floors, so we will divide the windward
pressure into these levels. Moreover, since the roof is a gable-style roof,
the roof mean height can be taken as the average of roof eaves and apex
elevation, which is 33 ft.
Table 4. Calculated values of velocity pressure coefficient for each
elevation height.
10 0.85
20 0.90
30 0.98
1.00 KzhKz
33
h
Velocity Pressure
From Equation (3), we can solve for the velocity pressure, qq in PSF, at
each elevation being considered.
External Pressure Coefficients for the walls and roof are calculated
separately using the building parameters L, B, and h, which are defined in
Note 7 of Figure 27.4-1.
Windward
0.8
wall
Windward Leeward
h/L
10.62
10° 15° 10° 10.62° 15°
°
-0.9
0 to h
-0.18
-0.9
h/2 to h
-0.18
0.317
-0.5
h to 2h
-0.18
-0.3
>2h
-0.18
External pressure coefficient with two values as shown in Tables 7 and 8
shall be checked for both cases.
26.6
10 0.88 (0.88) 35.35 (35.35)
3
28.2
20 1.94 (1.94) 36.41 (36.41)
0
-30.55 3.92 -35.88 -1.41
(-30.55) (3.92) (-35.88) (-1.41)
30.7
30 3.65 (3.65) 38.12 (38.12)
1
31.3
33 4.07 (4.07) 38.54 (38.54)
3
Design Roof Pressure, psf (along L) Design Roof Pressure, psf (along B)
Surface
(+GCpi) (−GCpi) Location (+GCpi) (−GCpi)
(+GCpi) (−GCpi) (from windward edge) (+GCpi) (−GCpi)
Take note that a positive sign means that the pressure is acting towards
the surface while a negative sign is away from the surface. Bay length is
26 feet.
p=qh[(GCp)−(GCpi)]p=qh[(GCp)−(GCpi)] (6)
Where:
For this example, (GCp(GCp) will be found using Figure 30.4-1 for Zone 4
and 5 (the walls), and Figure 30.4-2B for Zone 1-3 (the roof). In our case,
the correct figure used depends on the roof slope, θ, which is 7°< θ ≤
27°. (GCp(GCp) can be determined for a multitude of roof types depicted in
Figure 30.4-1 through Figure 30.4-7 and Figure 27.4-3 in Chapter 30 and
Chapter 27 of ASCE 7-10, respectively.
We shall only calculate the design wind pressures for purlins and wall
studs. Zones for components and cladding pressures are shown in Figure
9.
Based on Figure 30.4-1, the (GCp(GCp) can be calculated for zones 4 and 5
based on the effective wind area. Take note that the definition of
effective wind area in Chapter C26 of ASCE 7-10 states that: “To better
approximate the actual load distribution in such cases, the width of the
effective wind area used to evaluate (GCp(GCp) need not be taken as less
than one-third the length of the area.” Hence, the effective wind area
should be the maximum of:
The positive and negative (GCp(GCp) for walls can be approximated using
the graph shown below, as part of Figure 30.4-1:
Figure 10. Approximated (GCp(GCp) values from Figure 30.4-1 of ASCE 7-
10.
10.97 -48.56
4 0.90 -1.0
45.43 -14.10
10.97 -54.83
5 0.90 -1.2
45.43 -20.36
From 30.4-2B, the effective wind pressures for Zones 1, 2, and 3 can be
determined. Since trusses are spaced at 26ft, hence, this will be the
length of purlins. The effective wind area should be the maximum of:
The positive and negative (GCp(GCp) for the roof can be approximated
using the graph shown below, as part of Figure 30.4-2B:
Figure 11. (GCp(GCp) values from Figure 30.4-2B of ASCE 7-10.
-7.83 -42.30
1 0.30 -0.80
26.63 -7.83
-7.83 -54.83
2 0.30 -1.2
26.63 -20.36
-7.83 -79.89
3 0.30 -2.0
26.63 -45.43
Otherwise, try our SkyCiv Free Wind Tool for wind speed and wind
pressure calculations on simple structures.
SKYCIV WIND LOAD CALCULATOR
Patrick Garcia
Structural Engineer, Product Development
BEng (Civil)
References:
Mehta, K. C., & Coulbourne, W. L. (2013, June). Wind Loads: Guide
to the Wind Load Provisions of ASCE 7-10. American Society of
Civil Engineers.
Minimum Design Loads for Buildings and Other Structures. (2013).
ASCE/SEI 7-10. American Society of Civil Engineers.