Boiler AUTOTREAT - 25 LTR
Boiler AUTOTREAT - 25 LTR
Boiler AUTOTREAT - 25 LTR
AUTOTREAT - 25 LTR
Product group: 655 Product number: 698720
Product information
Autotreat combines well-known phosphate treatment with new polymer technology. This ensures that
precipitates are kept soft and non-adherent for easy removal by blowdown.
Features
Liquid boiler water treatment chemical for simplified dosing and handling
Suitable for all boilers, up to 30 bar pressure
Contains volatile amines to neutralise acids occurring in condensate system
Dispersant action suspends sludge and sediment particles for efficient removal by blowdown
Keeps boiler tube surfaces clean, promoting the best heat transfer conditions
Simple testing to determine treatment level
Benefits
Multifunctional boiler water treatment
Prevents scaling and corrosion, increasing system life and reliability
Specification
Form Liquid
pH 13-14
Technical data
Documents
NALFLEET™ Autotreat is a boiler water conditioner designed for optimum protection of ships boiler systems when used in
conjunction with an oxygen scavenger. The product combines well known phosphate treatment with new polymer technology. This
ensures that precipitates are kept soft and nonadherent for easy removal by blowdown. The product should always be used in
conjunction with an oxygen scavenger, preferably NALFLEET™ Oxygen Scavenger Plus. Note that this product is formulated for use
in conjunction with good quality feed water.
Dosing method
The product should preferably be dosed continuously with an automatic dosing unit. Alternatively the product can be fed into the
feed line by means of a by-pass pot feeder.
Initial fill dosage is 2.4 litres of NALFLEET™ Autotreat/ton of boiler capacity to reach a P-Alkalinity level of approx. 200 ppm. For an
untreated system it is recommended to initially bring the treatment up to a suitable level of 200 ppm p-Alkalinity. The dosage chart
given below is for convenience to determine the amount of product required to elevate P-Alkalinity. Note that the table is based on
reaching 200 ppm.
These are recommended values based on experience, and are in no way intended to replace the boiler manufacturers specifications,
or company regulations. Typical control limits are: * P-Alkalinity: 150-300 ppm as CaCO3. * Chlorides: 200 ppm Cl max. * Condensate
pH 8.3-9.0. Excessive Chlorides are removed by blowdown.
A representative sample of boiler water should be drawn for analysis daily. The sample should always be taken from the same point
after blowdown, cooled and tested immediately. Follow the WSS Test Kit instructions and log the results in Waterproof. The results
should be sent to WSS as stated in the Waterproof instructions.
It is important that regular testing is carried out to ensure that treatment levels are correct.