sc5811 Eng
sc5811 Eng
sc5811 Eng
2 Heat/2 Cool
Auto Changeover
Hardwire
Programmable Electronic Thermostat
Up button
Down button
S1 S2 R C W Y1 W2 Y2 G
FP O/B
Right (fan)
button
RESET CONFIG
Left (system)
button
Icon Descriptions
Room
temperature
offset activated
Fan operation icon
Lock mode
Cooling operation icon activated
Specifications
Electrical rating: • 24 VAC (18-30 VAC)
• 1 amp maximum per terminal
• 3 amp maximum total load
Temperature control range: 45°F to 90°F (7°C to 32°C) Accuracy: ± 1°F (± 0.5°C)
System configurations: 2-stage heat, 2-stage cool, heat pump, gas, oil, electric
Timing: Anti-short Cycle: 4 minutes (bypass anti-short cycle delay by returning to OFF
mode for 5 seconds)
Backlight Operation: 10 seconds
Terminations: S1, S2, R, C, W/O/B, Y1, W2, Y2, G
Important Safety Information
WARNING!: Always turn off power at the main power supply before installing, cleaning, or
removing thermostat.
• This thermostat is for 24 VAC applications only; do not use on voltages over 30 VAC
• Do not short across terminals of gas valve or system control to test operation; this will damage your
thermostat and void your warranty
• All wiring must conform to local and national electrical and building codes
• Do not use air conditioning when the outdoor temperature is below 50 degrees; this can damage your
A/C system and cause personal injuries
• Use this thermostat only as described in this manual
Wiring Diagrams
Heat/Cool Systems
Optional
remote or
outdoor sensor
Transformer
120 24 VAC
VAC
Heat #1
Cool #1
Heat #2
Cool #2
Fan
Single Compressor Dual Compressor
heat pump with electric backup heat pump with electric backup
Optional Optional
remote or remote or
outdoor sensor outdoor sensor
Transformer Transformer
Compressor Compressor #1
Compressor #2
Fan Fan
Remote Sensor Installation (Optional)
1. Remove cover from remote sensor housing.
2. Select an appropriate location for mounting the remote sensor.
3. Mount remote sensor unit using hardware provided.
4. Install two strand shielded wire between remote sensor and thermostat. Shielded wire must be used. Do not
run remote sensor wire in conduit with other wires.
• Wire 1 should run between the S1 terminal on the thermostat and the S1 terminal on the remote sensor
• Wire 2 should run between the S2 terminal on the thermostat and the S2 terminal on the remote sensor
• Connect the shielding of the wire to the S2 terminal on the thermostat
5. Configure the thermostat to operate with the remote indoor sensor (see Configuration Mode setting 13,
Page 14) or use it for an outdoor sensor.
The SC5811 thermostat is configurable for all systems. The configuration directly affects the outputs.
Use the output chart to correctly configure and wire the thermostat to your system.
Configuration Mode
The configuration mode is used to set the SC5811 to match your heating/cooling system. The SC5811
functions with heat pump, air conditioning, gas, oil or electric heat systems.
To configure the SC5811, perform the following steps:
2. Remove the cover of the thermostat by gently pulling near one of the
PM
corners at the top of the thermostat. OFF
3. Press the CONFIG button for 1 second while the SC5811 is in OFF mode.
CONFIG
S1 S2 R C W Y1 W2 Y2 G W3
FP O/B
RESET CONFIG
Configuration Mode Settings
The setup screens for Configuration Mode are as follows:
1. Temperature Scale (F or C)
Choose Fahrenheit or Celsius.
Press the up or down button to select.
Press the right button to advance to the next screen.
10
4. Staged Off Outputs
Select whether the outputs for heating and cooling are staged off
independently or are satisfied simultaneously.
1 = outputs staged off independently
0 = outputs off simultaneously
Press the up or down button to set.
Press the right button to advance to the next screen.
11
6. System – Set for heat pump, non-heat pump, reversing valve operation and number of compressors
in your system.
12
7. Auxiliary Delay ON – (0-30 minutes) – Set the delay time in minutes for
auxiliary heat to be locked out after a call for second stage. This extra
savings feature is used to temporarily lock out auxiliary heat devices,
allowing just heat pump to try to satisfy heat call.
Press the up or down button to select.
Press the right button to advance to the next screen.
13
11. Room Temperature Offset (+9°F to -9°F) (+4.5°C to -4.5°C)
Adjust to calibrate displayed room temperature to match actual room
temperature.
Note: When not set to 0, will display.
Press the up or down button to select.
Press the right button to advance to the next screen.
14
14. Cooling Fan Delay Off Time (0, 30, 60, 90 seconds)
Select the fan purge time for cooling.
Press the up or down button to select.
Press the right button to advance to the next screen.
OFF
15
Mode of Operation
The SC5811 is a programmable, manual or auto changeover, 2-stage heat, 2-stage cool thermostat. It
functions with air conditioning, heat pumps, gas, oil or electric heat systems. An outdoor sensor can be
used to monitor the outdoor temperature.
The thermostat activates the heating appliance when the room temperature is below the set heat
temperature (by the differential temperature) and the red indicator light (configurable) on the
thermostat will light. The SC5811 will stop outputting and the red light will turn off when the call for
heat has been satisfied. With heat pumps, the thermostat will not let the compressor come on for 4
minutes after it turns off. This protects your compressor.
When the room temperature is greater than the set cool temperature (by the differential temperature),
the cooling device is activated and the green indicator light (configurable) on the thermostat will turn
on. The SC5811 will stop outputting and the green light will turn off when the call for cooling is satisfied.
The thermostat will not let the compressor come on for 4 minutes after it turns off. This protects your
compressor.
The SC5811 has five possible operating modes: OFF, Heat, Cool, Heat & Cool, and Program mode. In
off mode, the thermostat will not turn on heating or cooling devices. The manual fan can be turned on
in all operating modes using the fan button. In heat mode, the thermostat controls the heating system.
In the cool mode, the thermostat controls the cooling system. In heat & cool mode, the thermostat
controls both the heating and cooling systems. In program mode, the thermostat will automatically be
controlled by the set program. Program mode can function with heat mode, cool mode, or heat & cool
mode. The clock display alternates with the set temperature display for heat & cool mode.
The program schedule can be overridden by changing the set temperature (up or down button). This
puts the SC5811 thermostat into a 2-hour temporary hold. After 2 hours, it will automatically return to
the program schedule.
The programmable fan feature can be used to recirculate air while in Program mode. It is activated
during the program schedule set up.
The SC5811 also has a button lockout feature. This enables the thermostat to be set to the proper
mode and temperature and locked so it cannot be tampered with.
16
Button Functions
Up button
Down button
PROG
UP
Used to increase the time, set temperatures and to adjust configuration settings.
DOWN
Used to decrease the time, set temperatures and to adjust configuration settings.
SYS (left)
Used to change from OFF, HEAT, COOL and AUTO changeover modes
FAN (right)
Used to turn on and off the indoor fan.
UP and PROG
Held in simultaneously for 10 seconds to lock and unlock the thermostat.
17
Operating Modes
There are five possible operating modes for the SC5811. Off, Cool, Heat, and Cool & Heat modes are
accessed by pressing the SYS (left) button. Program mode is accessed by pressing the SYS (left) and
FAN (right) buttons simultaneously.
OFF Mode
• In this mode, the thermostat will not turn on the heating or cooling
devices
Note: The indoor fan can be turned on manually in every operating
mode by pressing the FAN (right) button. The word FAN
shows on the display and the fan icon appears when the
fan operates. OFF
Heat Mode
• In this mode, the thermostat controls the heating system. When the
heat outputs, the flame icon apprears on the display.
Note: For heat pumps, there is a four minute delay for your
compressor to restart after it has turned off. To bypass the
compressor time delay, go to OFF mode for 5 seconds.
18
Emergency Heat Mode (Heat pump systems only)
• In emergency heat mode, the heat pump system will be disabled and
auxiliary heat will become the primary source of heat.
Cool Mode
• In this mode, the thermostat controls the cooling system. When the
cooling outputs, the snowflake icon apprears on the display.
Note: There is a four minute delay for your compressor to restart
after it has turned off. To bypass the compressor time delay,
go to OFF mode for 5 seconds.
19
Program Mode
• In this mode, the program function is on (PROG displays), and the
thermostat will automatically be controlled by the set program schedule.
Program mode can function with heat mode, cool mode, or heat & cool
mode. The program schedule can be overridden by changing the set
temperature (up or down button). After 2 hours, the program schedule
will automatically be resumed. To manually return to the program PROG
schedule, press the PROG button twice.
PROG
PROG
20
Testing the Thermostat
Once the thermostat is configured, it should be thoroughly tested.
CAUTION!: Do not energize the air conditioning system when the outdoor temperature is
below 50 degrees. It can result in equipment damage or personal injury.
Heat Test
1. Press SYS (left) button until heat mode is displayed.
2. Adjust the set temperature so it is 5 degrees above the room temperature.
3. Heat should come on within a few seconds. Red LED may turn on.
4. Adjust the set temperature 2 degrees below the room temperature and the PM
heat should turn off. There may be a fan delay on your system.
Note: For heat pumps, there is a four-minute delay to protect your compressor after it turns off.
To bypass the compressor time delay, go to OFF mode for 5 seconds.
Cool Test
1. Press SYS (left) button until cool mode is displayed.
2. Adjust set temperature so it is 5 degrees below room temperature.
3. A/C should come on within a few seconds. Green LED may turn ON.
4. Adjust the set temperature 2 degrees above the room temperature and the PM
A/C should turn off. There may be a fan delay on your system.
Note: There is a four-minute time delay to protect the compressor after it turns off. To bypass the
compressor time delay, go to OFF mode for 5 seconds.
Fan Test
1. Press FAN (right) button. Fan displays. Indoor fan turns ON.
2. Press FAN (right) button. Indoor fan turns OFF.
PM OFF
21
Setting the Time and Day of the Week
The time and day of the week must be set for your program schedule to operate correctly.
1. Press the SYS (left) button until you are in the OFF mode.
2. Press and hold the PROG button (SYS (left) and FAN (right) buttons
pressed simultaneously) in for 6 seconds.
4. Press the FAN (right) button once to select minutes (minutes flashing).
Press the up or down button to adjust the minutes.
5. Press the FAN (right) button once to select day of the week (TODAY
flashing).
Press the up or down button to select current day of the week.
Note: At any time, press the SYS (left) button to return to the previous
screen or press the FAN (right) button to advance to the next screen.
Press the PROG button in for 2 seconds to lock values into memory and return TODAY MON
to the OFF mode or press the FAN (right) button once to enter programming.
22
Programming
Program Overview
The SC5811 programmable thermostat has four periods (MORN, DAY, EVE, NITE) that are customizable
for each day of the week. Each period will have a start time, heat temperature, cool temperature
and programmable fan option. The SC5811 monitors the day and time, while maintaining the specific
conditions you have chosen for each period in your program.
Setting the program schedule:
1. Press the SYS (left) button until you are in OFF mode.
2. Press and hold the PROG button (SYS and FAN buttons pressed simultaneously) for 6 seconds.
3. Press the FAN (right) button 3 times.
4. SUN thru SAT are blinking.
24
Lockout Feature
The SC5811 has a button lockout feature so the mode cannot be changed
and the temperature adjustment is limited. Select the appropriate lockout
from Configuration Mode Settings (Step 8, Page 13) of this guide.
To activate the LOCK feature:
1. Simultaneously press the SYS, FAN and UP buttons for 10 seconds.
2. will display and the lockout function will be enabled.
To deactivate the LOCK feature, repeat steps 1 and 2 above.
25
Factory Preprogramming
The SC5811 comes preprogrammed with the following schedule:
MONDAY MORN 6:00 AM DAY 8:00 AM EVE 6:00 PM NITE 10:00 PM
thru HEAT 70°F HEAT 62°F HEAT 70°F HEAT 62°F
SUNDAY COOL 78°F COOL 85°F COOL 78°F COOL 82°F
FAN Off FAN Off FAN Off FAN Off
27
SimpleSetTM Field Programming
Requires SimpleSetTM Transfer Cable (ACC-WIH21)
This feature is used for transferring configuration and program schedule from the master to the target
thermostat. All thermostats for a job can be mounted and powered up. Configure and program one
thermostat. This will be the master. The master will be used to copy the program to the rest of the
thermostats.
Preparing the master to Send:
1. The master must be powered with 24 VAC.
2. Verify the master thermostat is in OFF mode.
3. Press SYS (left) button until OFF mode displays.
4. Remove cover of the master thermostat by gently pulling near one of the corners
at the top of the thermostat. OFF
5. Press the up and down buttons and CONFIG switch simultaneously for 5 seconds.
6. The OUT screen displays indicating the master thermostat is ready to transfer data.
Note: Press the up and down buttons and CONFIG switch simultaneously for 5
seconds to exit from data transfer mode and to return the master to the
OFF mode.
7. Turn off power to the master and remove it from the wall.
8. Connect the master to the target using the 3 wire connector. Attach one end to
the Master’s FP pins and the other end to the Target’s FP pins.
Note: Target thermostat must be powered with 24 VAC for field FP pins
programming to occur RESET
FP
CONFIG
S1 S2 R C W Y1 W2 Y2 G W3
O/B
When the connection has been made correctly, the master thermostat will power up and the target will
count from 5 down to 1. It will then display the LOCK confirming the data has been saved in memory.
When all target thermostats have been completed, reinstall the master thermostat.
Press the up and down buttons and the CONFIG switch simultaneously for 5 seconds to exit from the
data transfer mode and to return the master thermostat to the OFF mode.
28
Troubleshooting
Symptom Remedy
No display Check for 24 VAC at thermostat; display is blank when 24 VAC is not present
Time and day of week must be reset after extended power loss
System fan does not come on properly Verify wiring is correct, check Gas/Electric Configuration (see Setting 6, Page 12)
All thermostat buttons are inoperative Verify 24 VAC is present; unit locks out when 24 VAC is not present
No response with first button press First button press activates backlight only
Program schedule activates at the wrong Check time (AM/PM) set on thermostat (see Setting the Time, Page 22)
time
Thermostat turns on and off too Adjust temperature differential (see Configuration Mode Settings 2 & 3, Page 10)
frequently
Thermostat does not follow program Verify it is operating in program mode (PROG displays); check time (AM/PM);
check if in 2 hour program override
Fan runs continuously Press FAN (right) button to turn fan off
Fan turns on occasionally Program Mode: Check programmable fan setting in program schedule
(see Page 24)
Status indicator light not on during call Turn status indicator function on (see Configuration Mode Setting 15, Page 15)
Room temperature is not correct Calibrate thermostat (see Configuration Mode Setting 11, Page 14)
If remote sensor is used, check S1 and S2 terminal connections
displays when any button is pressed Thermostat has the button lockout function activated (see Lockout Feature, Page
25 and Configuration Mode Setting 8, Page 13)
on display instead of room Check for a bad connection at S1 and S2 terminals, if used (see Configuration
temperature Mode Setting 13, Page 14)
Heat or Cool not coming on Verify wiring is correct, gently pull on each wire to verify there is a good
connection at terminal block
Problem not listed above Press Reset button once*
* Reset Button Function Time and day are reset, configuration and program settings are unchanged.
29
ONE-YEAR LIMITED WARRANTY
The Seller warrants its products against defects in material or workmanship for a period of one (1)
year from the date of manufacture. The liability of the Seller is limited, at its option, to repair, replace
or issue a non-case credit for the purchase prices of the goods which are provided to be defective. The
warranty and remedies set forth herein do not apply to any goods or parts thereof which have been
subjected to misuse including any use or application in violation of the Seller’s instructions, neglect,
tampering, improper storage, incorrect installation or servicing not performed by the Seller. In order to
permit the Seller to properly administer the warranty, the Buyer shall: 1) Notify the Seller promptly of
any claim, submitting date code information or any other pertinent data as requested by the Seller. 2)
Permit the Seller to inspect and test the product claimed to be defective. Items claimed to be defective
and are determined by Seller to be non-defective are subject to a $30.00 per hour inspection fee. This
warranty constitutes the Seller’s sole liability hereunder and is in lieu of any other warranty expressed,
implied or statutory. Unless otherwise stated in writing, Seller makes no warranty that the goods
depicted or described herein are fit for any particular purpose.