LOCALISED ASPIRATING SMOKE DETECTOR

Key Features
■ Ultra small low cost aspirating smoke detector for easy and discreet
installation.
■ High sensitivity provided by laser based forward light scatter for reliable
early warning.
■ Single sampling pipe up to 50m in length (still air).
■ Unique ClassiFire® Perceptive Artificial Intelligence system that
dynamically adjusts the detector’s operating parameters, allowing for day
to day changes in the protected environment and dust separation system
contamination.
■ Unwanted alarms from dust are avoided using patented Dual Technology
LDD 3D3 Laser Dust Discrimination and elimination system.
■ RS485 communications built in as standard for networking and remote
communications.

Description
Stratos-Micra 25 is designed to provide very high sensitivity smoke detection
in a small package.
ClassiFire Perceptive Artificial Intelligence ensures that the detector operates at
optimum sensitivity for the protected environment, without the need for complex
setup. This means the product will configure itself to provide high sensitivity in
a computer room or reduced sensitivity in a smoky area.
The detector is designed to fit into a Docking Station. All sampling pipes and
cables are connected to the Docking Station as a first fix operation leaving the
detector to be fitted during the final commissioning phase if required. This
ensures that detectors are less likely to be damaged during the installation.
Upgradable volt-free Fire and Fault relay outputs are available for remote
monitoring by local fire detection or BMS systems.

Applications & Acceptance


Stratos detectors have been successfully applied in tens of thousands of
applications worldwide, ranging from Clean Rooms to Casinos.

Options Available
Stratos-Micra 25 detectors are able to be ■ Addressable Protocol Interface Cards APIC™ available for most popular
mounted in either ‘standard’ or ‘piped industry signalling protocols.
exhaust’ type Docking Stations as required
by the installation. ■ Command Module available for central monitoring and display.
■ SenseNet compatible - up to 127 detectors per loop.
■ Remote Display units available.
■ Suitable for Stratos-MatrixScan, a patented software system which
provides virtual addressable location detection - e.g. 10 physical
detectors would provide up to 45 unique addressable locations.

Approvals
■ Approved/listed by most major international fire protection certification
agencies. (contact AirSense Technology for latest details)
38.0 40.0
25.5 S P E C I F I C AT I O N S S t r a t o s - M i c r a 2 5

Supply Voltage 21.6V - 26.4V DC


29.0
Current consumption 250mA @ 24V DC
Size 140W x 200H x 85D
30.0
Weight 1.7kg
2 M20 Operating temperature range -10 to +38°C (UL268)
26.0 -10 to + 60°C (CEA4022)
Glands
Operating humidity range 0 - 90% non-condensing
Measurement range (%Obs/m) 0.0015% to 25%
Dimensions of
Maximum display resolution 0.0015% obscuration per metre
piped exhaust
Detection principle Laser light scattering mass
docking station detection and particle evaluation
Particle sensitivity range 0.003µ to 10µ
Dust discrimination principle 3D3 Laser Dust Discrimination (LDD)
40.0
Recommended max. 25m moving air
sampling pipe length 50m still air
Sampling pipe diameter 3/4” nominal bore
(27mm O/D)
Recommended no. 10
200 sampling holes
109.5 Alarm levels 4 (Aux, Pre-alarm, Fire 1 and Fire 2)
Laser chamber service intervals Greater than 10 years
(dependent on environment)
Laser lifetime (MTTF) Greater than 1000 years
Programming Command Module or
PC via RS232/RS485
Network data bus RS485
Maximum total data bus length 1.2 km
IP rating IP50
45.0 45.0 24.0 Sampling pipe inlets 1
Exhaust air pipe outlets 1 on optional Piped Exhaust docking
station
139.3

Leave 80mm clearance at top and bottom of docking


station for access

ORDERING INFORMATION APPLICATIONS


Part No. Description
30750 Stratos-Micra 25 Detector Module
Data storage units Air duct protection
30752 Docking Station (standard exhaust) Prison cells Heritage property protection
30753 Docking Station (piped exhaust)
Plant rooms Critical equipment
30436 Relay Input PCB
30755 Replacement Filter Air conditioning units Anti-smoking enforcement
30240 Setup and servicing Software (free of charge)
Equipment racks Motor rooms
30419 Serial PC Lead
30821 PS25 Power Supply Computer rooms
Shortform data sheet Micra 25 Issue 4 Nov ‘07
Stratos, HSSD, Micra and ClassiFire are registered
Copyright© 2007 AirSense Technology Ltd.
trademarks of AirSense Technology Ltd.

AirSense Technology Limited


1 Caxton Place • Caxton Way • Stevenage • Herts • SG1 2UG • UK
Tel: +44(0)1438 751296 • Fax: +44(0)1438 729137
e-mail: [email protected] • www.airsensetechnology.com
AirSense Technology Limited (Hong Kong)
1801 Wing On Central Building • 26 Des Voeux Road Central • Central Hong Kong
Tel: (852) 2961 4206 • Fax: (852) 3007 4737
e-mail: [email protected]