Energy efficient , Compact and Low noise

thermo Q Air Cooled Packaged Chiller Screw Type All units are compact , completely factory Assemble
Compressor has been developed for the requirements , and weather proof. its can reach on site easy to
featuring high efficiency , low noise , less vibration , handling on transportation .
easy installation and reliability . The unit is pressure tested , evacuated and fully
charges with Refrigerant – 22 .

Main Component
o Durable Screw Compressor
High efficiency profile
ƒ Further developed geometry high stiffness .
ƒ Double walled , pressure compensated rotor
housing
ƒ Extremely stable even at high pressure levels .
Long life bearing with pressure unloading
ƒ Robust axial tandem bearing
ƒ Bearing chamber pressure isolated from
compression chamber by sealing element .
ƒ Three stage oil separator , fine filter 10 micro
mesh size
ƒ Three stage oil separator , fine filter 10 micro mesh size

Intelligent electronics protection


ƒ Thermal motor temperature monitoring by
winding PTCs
ƒ Phase sequence monitoring for rotating
direction
ƒ Oil temperature protection
Dual capacity control
ƒ 4 step slider control with Vi compensation .
0% 25 % 50 % 75 % 100 %
100 % 75 % 50 % 25 % 0%
ƒ Automatic start unloading
Unloading hydraulic scheme

o Condenser & Low Noise Axial Fan


The highly efficient and compact Cross finned coil type are
designed with corrugated surface aluminum fins and extended
surface in inner tube.
Outdoor fan with best quality fan made convenience with low noise
level , saving energy and high ambient resistance temperature
use until 60 O C .
Axial type with external rotor motor , IP 54 motor protector and
Class F insulation ( DIN EN 60 034-1 )
The fan motor totally encloses weather proof type .

o High efficiency Evaporator


Dry expansion Shell and tube type Evaporator, compact and height
efficiency heat transfer.
All evaporator equipped with Anti freeze to protect the cooling tube from
being damage due to chilled water freeze up and chilled water
temperature sensor to reduce precision chilled water temperature .
A drain plug is provided in the evaporator inlet pipe to extract chilled
water .
Manufacture standard TEMA , ASTM .
GENERAL DATA AIR COOLED SCREW SEMI HERMETIC WATER CHILLER
TECHNICAL SPECIFICATION DATA
CA SERIES 50 SR 60 SR 70 SR 80 SR 90 SR 110 SR 125 SR 140 SR 160 SR2 180 SR2 220SR2 250 SR2 280 SR2 330 SR3 375 SR3 420 SR3 500SR4 560 SR4
COOLING CAPACITY kW 100,1 127,4 144,7 170,0 198,0 238,0 277,0 324,0 340,0 396,0 476,0 554,0 648,0 714,0 831,0 972,0 1108,0 1296,0
TR 29 37 42 49 57 68 79 93 97 113 136 158 185 204 237 277 315 369
COMPRESSOR Type Double Screw-Hermetic, Compact
Motor Size HP 50 60 70 80 90 110 125 140 160 180 220 250 280 330 375 420 500 560
RPM 1/min 2900 2900 2900 2900
Qty 1 1 1 1 1 1 1 1 2 2 2 2 2 3 3 3 4 4
Power Input kW 37,3 46,1 51,9 61,8 69,9 81,7 96,2 109,4 123,6 139,8 163,4 192,4 218,8 245,1 288,6 328,2 384,8 437,6
Capacity Control % 25 – 50 – 75 -- 100
Oil Charge L 8 8 14 14 14 18 18 18 28 28 36 36 36 54 54 54 72 72
CONDENSER COIL
Material Copper Tubes – Aluminum Fins
Tubes Diameter Inch (mm) 3/8 (9,5) 3/8 (9,5) 3/8 (9,5) 3/8 (9,5)
Face Area m2 327 525 525 525 554 780 1090 1090 1090 1108 1560 2180 2180 2220 3000 3300 4360 4360
Fin Spacing mm 2,1 2,1 2,1 2,1
CONDENSER FANS Type Propeller, Direct Drive
Fans Speed RPM 1340 850 1340 850 850
Blade Diameter mm 630 900 630 900 900
No. of Fans 3 3 3 4 3 3 3 4 4 6 6 6 8 10 10 12 12 16
Total Power kW 5,7 5,7 5,7 7,6 9,9 9,9 9,9 13,2 7,6 19,8 19,8 19,8 26,4 33 33 39,6 39,6 52,8
Total Airflow M3/h 45000 43500 43500 52000 81000 81000 81000 100000 110000 162000 162000 162000 200000 266000 262000 300000 324000 400000
EVAPORATOR Type Shell and Tubes, Direct Expansion, Removable Tube-Bundle
No. of Refrigerant Circuit 1 1 1 1 1 1 1 1 2 2 2 2 2 3 3 3 4 4
Water Volume L 35 41 46 54 65 81 95 100 114 133 162 184 215 230 278 334 382 453
Chilled water Flow L/s 4,77 6,07 6,89 8,10 9,43 11,36 13,19 15,44 16,20 18,87 22,71 26,39 30,89 34,07 39,58 46,33 52,77 61,77
Pressure Drop kPa 19 27 18,8 22,8 26,1 30,6 34 46,6 47,7 52,1 31,7 38,1 41,2 45,3 54,8 65,6 67,6 71
Inlet / Outlet Temperature 0C 12 / 7
Water Connection
Inlet / Outlet DN 80 80 100 100 100 125 125 150 150 150 200 200 200 200 200 200 200 200
Drain FPT 1/2 “
Cooling Capacity Based on ambient 350C, 55% RH, Refrigerant R-22, te 20C, tc 500C

CA Series 50 SR 60 SR 70 SR 80 SR 90 SR 110 SR 125 SR 140 SR 160 SR2


Dimension Length mm 3400 3400 3400 3400 3600 4000 4600 4600 4600
Width mm 1800 1800 1800 1800 1200 1200 1200 1200 1200
Height mm 1100 1100 1100 1100 2400 2400 2400 2400 2400
Weight kg 830 900 1120 1160 1200 1700 1800 1900 2400

CA Series 180 SR2 220SR2 250 SR2 280 SR2 330 SR3 375 SR3 420 SR3 500SR4 560 SR4
Dimension Length mm 3600 4000 4600 4600 6100 6700 6900 9000 9000
Width mm 2400 2400 2400 2400 2400 2400 2400 2400 2400
Height mm 2800 3700 4100 4300 2400 2400 2400 2400 2400
Weight kg 2800 3700 4100 4300 5500 5900 6300 8000 8000

We improve our products continuously; therefore we reserve the right to change in specification without prior notice.
Optional features :
♦ Ozone friendly refrigerant use
♦ Micro processor control base
♦ Heat recovery from refrigerant hot gas to reduce hot water
♦ Brine chiller type with brine temperature from 2 O C to - 8 O C

Programable Electronic Controller


High technology
A high performance 16-bit microprocessor guarantees high program running
speed and efficient management of the interfaces and the expansion boards,
including control of faster transients.The parameters can be protected by
various password levels (manufacturer, user).
All of components in this system can be connected to pLAN local networks
without requiring additional cards , for the exchanger of data and information .
Consequently, distributed control networks can be created simply and reliability
for optimized management of the installation.

Programmability
The exclusive Easy Tools system development system allows rapid customization of the software, made even
simpler by the use of flash RAM technology.
Communication
The pCO series controllers can interface to the more widely used communication standards, either directly or via
gateways (Modbus®, BACnet™, Johnson METASYS®, DLL for Windows®, TCP/IP, SNMP, LonWorks®,
TREND).

Refrigerant Hot Gas Heat Recovery


The refrigeration cycle of an air conditioner or chiller provides an opportunity to recover heat for water heating.
Compressors concentrate heat by compressing gaseous refrigerant. The resultant superheated gas is normally
pumped to condenser for heat rejection. How ever , a hot gas to water heat exchanger my be placed into the
refrigerant line between the compressor and condenser coil to capture a portion of the rejected heat .

Heat Recovery
You can get free Hot water every time when your Air
Conditioning / Chilling Unit operation .

That saves you energy and money every


month !

PLUS - Your Air Conditioner / Chiller cooling more


efficiently every time your Heat recovery unit runs.

That save your energy and money too!

Heat recovery from refrigerant hot gas to water .


O
Max. temperature of water can be reach = 70 C

Manufacturing

PT. Metalindo Prima Engineering


Heat Transfer Equipment Engineering
Jl. KH.Zaenal Mustafa No. 17 – Jatinegara
Jakarta Timur - 13350 - INDONESIA
Phone : 62 21 856 1234 ( Hunting )
Fax : 62 21 8513109
E-mail : [email protected]