Eaton DC Power Solutions

PowerManagerII™ Control and


Monitoring Software
Features The Eaton® PowerManagerII Remote Control and
software provides effective
• Windows® Based remote management for Eaton Monitoring
Graphical User Interface DC power systems. The
PowerManagerII can control
• Real-Time Monitoring intuitive, Windows® - based
and monitor power equipment
graphical user interface enables
• Automatic Alarm Indication at multiple sites from one
you to quickly ‘zoom in’ and
• Alarm and Activity Logging central location. It provides real-
view concise summary
time graphical displays of
• On-Line Access to System information, or specific control
system operating conditions,
Control Functions functions, key operational data,
and monitors all system
• Reduces the Need for Site or alarm details.
functions including individual
Visits PowerManagerII is cost- rectifier modules.
• International Language effective. Remote management
Options can reduce operating and Event Logs and Data
• User Configurable maintenance costs. The latest Logs
Navigation Maps power system information is
available where and when you PowerManagerII lists data from
• Remote Battery Testing want it, greatly reducing the each site. This includes all
need for site visits. Alarms are alarms, with activation details.
highlighted and detailed, to help Historical data can be recorded
you analyze faults and produce for fault analysis and preparation
maintenance histories and of maintenance schedules. The
schedules. information can be filtered,
sorted or exported to other
PowerManagerII is applications.
comprehensive. You can
connect as many power Customization
systems as you like, and all
necessary data is clearly PowerManagerII is designed for
presented. PowerManagerII is easy customization. Maps and
flexible. You can set up area locations of the sites can be
map views of urban areas and added to the PowerManagerII
wider regions, to help you interface.
visually navigate to any site -
In addition to Eaton DC Power
the choices are yours. And it’s
Systems, air-conditioning
simple to add new maps and
equipment and intruder alarms
site locations.
and other plant connected to
the system Supervisory Module
I/O connections, can also be
monitored.
With the SiteManager option,
PowerManagerII can monitor a
wide range of inputs using
SiteSure modules.
Technical Specifications
Control
Functions Data Networks
PowerManagerII includes graphical displays of all system control The Eaton Customer Services Team offers a complete installation and
processes. All parameters are displayed together with real-time software customization service, and can provide advice on integration
displays of the system operating conditions: of PowerManagerII into existing data networks.
System Displays operating conditions and system status.
schematic Computer
Individual rectifier PowerManagerII monitors individual rectifier Minimum
performance. Requirements
System summary Graphical real-time display of system status. Operating Windows 98, Windows NT 4.0 or later
System control Display of output voltage control systems. System
functions Ram 16Mb Windows 98, 24Mb Windows NT
Temperature Set temperature compensation parameters for Connection Standard Serial port (Com port)
Compensation optimum battery charging. Disc drive CD-ROM
Manual Equalize Initiate battery equalize charge.
Periodic Equalize Set the duration and level of auto battery equalize Comms
charges. Protocols SNMP (Can emit traps)
Fast Charge Set-up fast battery recharge parameters for S3P three layer protocol
optimum system recovery after AC outage. Interfaces RS232, RS485, Ethernet, TCP/IP, modem
Low Voltage Set the operational parameters of the low voltage
Disconnect disconnect module.
User
Battery Current Set the maximum battery recharge current.
Configurable
Limit
Graphics
Battery Test Conduct on-line battery tests to determine battery
Format Windows bitmap format (.BMP), or Windows
condition.
Metafile (.WMF) file formats supported
Discharge Test Calibrates the Battery Capacity remaining
algorithm.
Accessories
Hardware Copy protect device, null modem cable.
Included

In the interests of continual product improvement all specifications are


subject to change without notice.

Eaton, CellSure, SiteSure, DCTools and


PowerManager are trade names,
trademarks, and/or service marks of
Eaton Corporation or its subsidiaries and
affiliates. All other trademarks are
property of their respective owners.

© 2009 Eaton Corporation


Email: [email protected] All Rights Reserved
Internet: www.eaton.com/telecompower PM2 E
Eaton DC Power Solutions

DCTools™ Configuration Software


Eaton® DCTools is the new DCTools is the ideal setup and
configuration software for field diagnostic tool for field
technicians installing and technicians. It provides a very
maintaining Eaton DC power easy way for them to configure
systems. It is supplied at no an Eaton DC product, and view
charge by download from the status and alarm conditions.
Internet and simplifies the
Among the advantages of using
setup and operation of all Eaton
DCTools are reduced
DC power systems.
installation times, lower fault
Frontline staff will find DCTools response times, less need to
is a major benefit during the visit sites and better access to
installation, troubleshooting and operating data for fault analysis
support of any Eaton DC power and operating conditions such
system, CellSure battery as load growth.
monitoring systems and
These make the processes of
SiteSure ancillary monitoring
power system installation and
and control systems.
operation more efficient with
For added flexibility DCTools the potential for real operating
can connect to an Eaton DC cost savings.
power system in three ways;
DCTools is available for
directly through an RS232 serial
download at
connection; through a dialup or
www.powerware.com/downloads
cellular modem, or through an
Ethernet LAN/WAN.

Features
• DC power system configuration software
• Windows® compatible
• Easy to use graphical display
• Operates with all Eaton DC power systems, CellSure™ and
SiteSure™
• Local (RS232 serial) or remote (dialup modem or Ethernet)
connection
• Downloadable from the Internet at no charge
Technical Specifications
Computer
Minimum
Requirements
Operating Windows 98, Windows NT 4.0 or later
System
RAM 16Mb Ram Windows 98, 24Mb Windows NT

Connection Standard serial port (Com port)


Internet Required for download only
connection

Interfaces
Communications RS232, Ethernet, or modem
interfaces
supported

Availability
Free download www.powerware.com/downloads

In the interests of continual product improvement all specifications are


subject to change without notice.

Eaton, CellSure, SiteSure, DCTools and


PowerManager are trade names,
trademarks, and/or service marks of
Eaton Corporation or its subsidiaries and
affiliates. All other trademarks are
property of their respective owners.

© 2009 Eaton Corporation


Email: [email protected] All Rights Reserved
Internet: www.eaton.com/telecompower DCTools D

You might also like